Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Pressure Reducing Valve W M115 ANBI

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Series W-M115 Thread BSPT(DN32-DN50)

Series W-M115 Flange(DN50-DN300)


Pressure Reducing Valve
11
Application:
Pressure Reducing Valve

The Watts W-M115 Pressure Reducing Valve is designed to adjust,


set and maintain downstream pressure of pipeline. It’s generally
used in city water supply, industrial and agricultural water
transmission pipeline, etc.

Features:
1. Stable performance, safe and reliable.
2. Simple operation, convenient adjusting.
3. Precise pressure reducing.
4. Long service life.
Operating Principles:
The Watts ACV Pressure Reducing Control Valve is designed to
automatically reduce a fluctuating higher upstream pressure to a constant lower downstream
pressure regardless of varying flow rates. It is controlled by a normally open, pressure
reducing pilot designed to: 1) Open (allowing fluid out of the main valve cover chamber) when
downstream pressure is below the adjustable setpoint, and 2) Close (allowing fluid to fill the
main valve cover chamber) when downstream pressure is above the adjustable setpoint. A
decrease in downstream pressure causes the valve to modulate toward an open position,
raising downstream pressure. An increase in downstream pressure causes the valve to
modulate toward a closed position, lowering downstream pressure
Technical Specification:
Nominal Diameter: DN32~DN300
Maximum Pressure: PN16/CL150/CL300
Working Temperature: 0℃~80℃
Fluid Medium: Water
Test Standard: ISO/DIS 5208:2007
Pressure Reducing Range: 10PSI~125PSI (0.07MPa~0.9MPa)
Optional 20Psi~175Psi(0.137Mpa~1.2Mpa)
30Psi~300Psi(0.206Mpa~2.06Mpa)
Standard pressure setting: 50Psi (0.35MPa)
Connection Type: Thread / Flanged
Connection Standard: CL 300 BSPT to ISO 7-1
PN16 to BS EN 1092-2
CL150 to ANSI B16.42
CL300 to ANSI B16.42

Watts product specifications in metric units are provided for reference only. For precise measurements
please contact Watts Technical Service. Watts reserves the right to change or modify product design,
construction, specifications, or materials without prior notice and without incurring any obligation to
make such changes and modifications on Watts products previously or subsequently sold.

Page 1 / 4
Component Material :
Body/Bonnet: Ductile iron with epoxy resin ,NSF certified coating.

Stem/Seat: Stainless steel


Diaphragm: NBR+Nylon

11
Seal ring: NBR

Installation Dimensions:
Pressure Reducing Valve

Connection Dimension: PN16 to BS EN 1092-2

Size Dimensions(mm) Flange Dimensions(mm)


Weight(Kg)
DN L H H1 B C n-φD E T
32 BSPT 184 305 271 235 / / / / 17.5
40 BSPT 184 305 271 235 / / / / 17.5
50 BSPT 238 315 268 250 / / / / 18.2
50 230 325 245 260 125 4-φ19 165 19 18.6
65 290 343 250 265 145 4-φ19 185 19 19.2
80 310 345 245 275 160 8-φ19 200 19 20.1
100 350 395 285 345 180 8-φ19 220 19 36.5
125 400 413 288 380 210 8-φ19 250 19 58.6
150 480 430 288 405 240 8-φ23 285 19 72
200 600 540 370 475 295 12-φ23 340 20 140
250 660 650 450 560 355 12-φ28 406 30.5 265
300 762 755 520 670 410 12-φ28 482 31.8 465
*Please contact the local salesmen if the size ≥DN300 are needed.
Flow Rates:
Size (DN) 32 40 50 65 80 100 150 200 250 300
Maximum Continuous (GPM) 95 130 210 300 485 800 1850 3100 5000 7000
Maximum Intermittent (GPM) 119 161 265 390 590 1000 2300 4000 6250 8725
Minimum Continuous (GPM) 1 1 1 20 30 50 115 200 300 400
*NOTE:The above chart is a suggested guide .Inlet pressure, outlet pressure, minimum, normal and maximum
flow rates should be considered for specific valve sizing. Contact Watts ACV details.
Watts product specifications in metric units are provided for reference only. For precise measurements
please contact Watts Technical Service. Watts reserves the right to change or modify product design,
construction, specifications, or materials without prior notice and without incurring any obligation to
make such changes and modifications on Watts products previously or subsequently sold.

Page 2 / 4
Cavitation Chart:
After selecting the valve size , locate inlet and outlet pressure on this chart. If the intersection point falls in the
shaded area ,cavitation can occur. Operation of valves continually in the cavitation zone should be avoided .
Consult Watts ACV for alternatives.

11
Pressure Reducing Valve

Typical Application:
1. Water plant and water source project.
2. Environmental protection.
3. Municipal facilities.
4. Electric power and utilities.
5. Construction industry.

Watts product specifications in metric units are provided for reference only. For precise measurements
please contact Watts Technical Service. Watts reserves the right to change or modify product design,
construction, specifications, or materials without prior notice and without incurring any obligation to
make such changes and modifications on Watts products previously or subsequently sold.

Page 3 / 4
Installation Instructions:
(1) The installer must be trained or experienced so as to operate the installation correctly.
(2) Water supply pipe network should be washed before pressure reducing valve installation,
eliminating sand, gravel and other debris in the pipe.
(3) The flow direction from inlet to outlet should be paid attention to in installation, and

11
maintenance space around the valve is convenient to assemble.
(4) For the size below DN150, the main valve can be installed horizontally or vertically, but
horizontal installation is better. The size above DN150 only can be installed horizontally.
Pressure Reducing Valve

(5) After debugging, the pilot valve and the needle type flow valve must be locked with locknut.
(6) Valve should be checked regularly, ensuring the debris in filter being cleaned.
(7) Dimension of Tubing: Size: 3/8” and 1/2”
(8) Pilot valve: 10 to 125Psi —LF26A
20 to 175Psi —LF263AP
30 to 300Psi—LFCP15
(9)The pressure gauge range: 0-350Psi.

Watts product specifications in metric units are provided for reference only. For precise measurements
please contact Watts Technical Service. Watts reserves the right to change or modify product design,
construction, specifications, or materials without prior notice and without incurring any obligation to
make such changes and modifications on Watts products previously or subsequently sold.

Page 4 / 4

You might also like