Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Samsung Mono Controller Kit Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 48

',1*%$7%XOOHW

DINGBAT-Star

Air to Water Heat Pump


Installation manual
Control Kit MIM-E03CN
• Thank you for purchasing this Samsung Product.
• Before operating this unit, please read this installation manual carefully and retain it for future
reference.
Contents
Safety precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Product specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Main components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Installing the unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Wiring works . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Wiring schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Self-test mode of wired remote controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
DHW tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Mixing Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Concrete curing function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Installation option setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Error codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Reference (KEYMARK Certification) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

Correct Disposal of This Product


(Waste Electrical & Electronic Equipment)
(Applicable in countries with separate collection systems)
This marking on the product, accessories or literature indicates that the product and its electronic accessories (e.g.
charger, headset, USB cable) should not be disposed of with other household waste at the end of their working life.
To prevent possible harm to the environment or human health from uncontrolled waste disposal, please separate
these items from other types of waste and recycle them responsibly to promote the sustainable reuse of material
resources.
Household users should contact either the retailer where they purchased this product, or their local government
office, for details of where and how they can take these items for environmentally safe recycling.
Business users should contact their supplier and check the terms and conditions of the purchase contract. This
product and its electronic accessories should not be mixed with other commercial wastes for disposal.

2
Safety precautions
Carefully follow the precautions listed as below because they are essential to guarantee the safety of SAMSUNG product.
• Always disconnect a power supply of Air-Water Heat Pump before servicing it or accessing
components inside the unit.
WARNING • Verify that installation and testing operations shall be performed by qualified personnel.

ENGLISH
• To prevent serious damage on the system and injuries to users, precautions and other
notices shall be observed.

Warning
fCarefully read the contents of this manual before installing the control kit and store the manual in a safe place in order to
be able to use it as reference after installation.
fFor maximum safety, installers should always carefully read the following warnings.
fStore the manual in a safe location and remember to hand it over to the new owner if the kit is sold or transferred.
fThe kit is compliant with the requirements of the Low Voltage Directive (72/23/EEC), the EMC Directive (89/336/EEC) and
the Directive on pressurized equipment (97/23/EEC).
fThe manufacturer shall not be responsible for damage originating from unauthorized changes or the improper
connection of electric and hydraulic lines. Failure to comply with these instructions or to comply with the requirements
set forth in the “Operating limits” table, included in the manual, shall immediately invalidate the warranty.
fDo not use the units if you see some damages on the units and recognize something bad such as loud noisy, smell of
burning.
fIn order to prevent electric shocks, fires or injuries, always stop the unit, disable the protection switch and contact
SAMSUNG’s technical support if the unit produces smoke, if the power cable is hot or damaged or if the unit is very noisy.
fAlways remember to inspect the unit, electric connections, and protections regularly. These operations shall be
performed by qualified personnel only.
fThe unit contains various electric parts, which should be kept out of the reach of children.
fDo not attempt to repair, move, alter or reinstall the unit by unauthorized personnel, these operations may cause product
damage, electric shocks and fires.
fDo not place containers with liquids or other objects on the unit.
fAll the materials used for the manufacture and packaging of the air to water heat pump are recyclable.
fThe packing materials must be disposed of in accordance with local regulations.
fWear protective gloves to unpack, move, install, and service the unit to avoid your hands being injured by the edge of the
parts.
fDo not touch the internal parts while running the units.
fInspect the product shipped and check if damaged during transport. If the product has some damages, DO NOT INSTALL
and immediately discuss about the damages with the carrier or retailer (if the installer or the authorized technician has
collected the material from the retailer.)
fOur units shall be installed in compliance with the spaces described in the installation manual, to ensure accessibility
from both sides and allow repairs or maintenance operations to be carried out. If the units installed without complying
with procedures described in manual, additional expenses can be asked because special harnesses, ladders, scaffolding
or any other elevation system for repair service will NOT be considered part of the warranty and will be charged to the
end customer.
fWhen service works required, make sure to disconnect the power supply at least 1 minute to prevent electric shocks.
- Always check the voltage at the terminals of main PCB before trying to touch.
fUse electric wires which manual designated. Connections between wires and terminals shall be assembled without any
tension. If the assembly works is not implemented well, it can lead to have product damages and fires.
fAfter wiring works, terminal block cover shall be fixed firmly. Without cover, it can cause to have product damage and fire.
fBe sure not to perform power cable modification, midway wiring, and multiple wire connection.
- It may cause electric shock or fire due to poor connection or insulation and current limit override.
- When midway wiring is required due to power line damage, refer to "How to connect your extended power cables" in
the installation manual.

3
Product specifications
Item Description

MIM-E03CN

Wired remote controller (MWR-WW10N)

Temp. Sensor for DHW Tank (15m, YEL) (1EA)


Temp. Sensor Temp. Sensor for Mixing Valve (15m, BLU) (1EA)
Temp. Sensor for Heater (15m, BLK) (1EA)

PV Control / Peak power control cable(Red, 2 m, 1 EA)

Flow Sensor (1EA, 1.5m)

Sensor holder (2EA, OD 7.8mm)

Sensor clip (2EA)

Cable tie (4EA)

Aluminum tape (2EA)

Rubber tape (2EA)

Insulartor (2EA)

Back-up heater conector (Red)


LEAD CONNECTOR Back-up heater conector (Brown)
Back-up heater conector (White)

Installation manual

User manual

ASSY TUBE CONNECTOR-RIGHT (OD28.0, 1EA)

4
Item Description

ASSY TUBE CONNECTOR-LEFT (OD28.0, 1EA)

Fastener (2EA)

ENGLISH
O-Ring (2EA)

❋ Temp. sensor = Temperature sensor

Main components
Model name MIM-E03CN
Parts Qty.
Main PBA 1
ELCB
- Rated current : 30A 1
- Leakage current : 30mA
Detail components Grounding screw 7
Rubber 3
Base plate 1
Top cover plate 1
Case screw 2
Weight (Net) 3.5 kg
Packing size (W x H x D) 329 mm x 439 mm x 168 mm

❋ Flow sensor set point


AE050RXYD**/AE080RXYD** : 7LPM
AE120RXYD**/AE160RXYD** : 12LPM

Mounting the unit


Procedure Remark
1. Remove 2 screw from the unit.

Screw

2. Open the top cover and install 4 screws on the wall.

3. Close the top cover and install 2 screw again into the unit.

5
Installing the unit
Installing the remote controller
Dimension
(Unit : mm)
120 19

120

6
Wired Remote Controller Installation
1. Insert the flat-head screwdriver into two square grooves at the bottom of the Wired Remote Controller and rotate it to lift
the front cover for removal from the rear cover.

ENGLISH
2. Arrange the power cable and the communication cable so that they fit in the housing along the edges of the rear cover.

8 cm 8 cm
Area A
<When the cable is not concealed> <When the cable is concealed>

• When connecting the power and communication cables to the bottom of the Wired Remote Controller, first cut
NOTE off the area A.

7
Installing the unit
3. Using two or more screws, firmly affix the rear cover of the remote controller to the wall, and then cut off the grooves of
the front covers for communication and power cables, making sure these cables have reasonable length.

10 mm or more
10 mm or more

10 mm or more
Screw hole

50 mm or more
Rear cover

❋ Before fixing the rear cover, secure ❋ You must fit the
at least 10 mm space of upper side, screws into the
left side, right side, and 50 mm screw holes.
space of bottom side.

4. Connect the communication cables (F3, F4) to the terminals of the back of the front cover, and then fix the wires so that
they do not get stuck during connection.

F1 F2 V1 V2 F3 F4

Wire (not supplied)

Wired Remote
Controller

Front cover
F3(COM2_B) F4(COM2_A)
PCB terminal

❋ Do not tighten the screws on the PCB terminal with


excessive force.

• When using an electric screwdriver, tighten the screws to the standard torque because the top of screws may be
CAUTION worn out if you use a strong torque.

5. Reassemble the Wired Remote Controller.

• Align the controller with the upper groove first, and then insert it by turning it downwards as shown
NOTE
in the figure.
After assembly, check and confirm that no wires are stuck in the gap between the back and front
covers.

8
6. Remove the front protective film.

ENGLISH
• When installing a Wired Remote Controller by using a cable longer than 10 m, you must install the
CAUTION
communication cable and the power cable separately. (Electrical interference can cause the Wired Remote
Controller to malfunction.)
• When installing your Wired Remote Controller on the wall, consider the size of the wire hole, and select a wire
with a proper thickness.
• Wire that is connectable to Wired Remote Controller PCB.
- If you install the Wired Remote Controller by reclaiming, install it according to U-terminal cable specification.
- If you install the Wired Remote Controller by using two pieces of PVC wire, remove the 30 cm of the sheath of
the cable and install it only with the two pieces of wires. (Recommended specification: AWG20)
• The following are the specs of the compression ring terminal connected to your Wired Remote Controller PCB.
E

W Stud ØD

F G
L

Range of Permitted Wires Rated Size Stud Size Basic Size (mm)
AWG mm2 mm2 mm t øD G E F W L
22 ~ 16 0.25 ~ 1.65 1.5 3 0.7 3.8 10.0 4.5 6.5 6.0 21.2
❋ Maximum distance for connecting communication and power cable: 100 m
• Screws on the PCB terminal must be tightened with less than 6N-cm tightening torque. If the tightening torque
is greater, it may damage the screw thread.

9
Wiring works
• Field-supplied electrical components such as power switch, circuit breakers, wires, terminal blocks, etc must be
CAUTION properly chosen with compliance with national legislation or regulation.
• Switch off the power supply before making any connections.
• All field wiring and components must be installed by a licensed electrician.
• Use a dedicated power supply.
• All power connections must be protected from dew condensation by thermal insulation.
• The system shall be earthed. Do not earth the unit to a utility pipe, surge absorber or telephone earth.
Incomplete earth may cause electrical problems.

Layout of PCB
SMPS circuit 6

2 7 11

8
EEPROM
DIP switch
4 5 3

Micom 9

1
10
2-WIRE COMM

Load control

12
Fuse

14 13 15
1

ON
16
1 2 3 4

No. Note No. Note


FR Control Flow Switch
① CNS003(Green) ② CNS041(Yellow)
Temp. Sensor for DHW Tank Temp. Sensor for Heater
③ CNS042(Yellow) ④ CNS047(Black)
Temp. Sensor for Mixing Valve PV(Photovoltaic) Control Signal / Peak power control Signal
⑤ CNS045(Blue) ⑥ CNS046(Black)

10
No. Note No. Note
Thermistor
CNS043(White) TB-C(Black)
⑦ 1-2: Heater Out ⑧ F3-F4:COMM2 (Wired Remote Controller)
5-6: Eva In
Water Pump Signal
TB-C(Black) CNS1(White)
⑨ ⑩

ENGLISH
F1-F2:COMM1 (IN-OUT COMM) 1: Signal
3: Gnd
Flow Sensor
3-Way Valve
CNS057(White)
CNP501(White)
1: DC5V
⑪ 2: Signal ⑫ 1: Neutral
3: Signal_NO
3: Gnd
5: Signal_NC
4: N.C
Immersion Heater
Main Power TB-A(Black)
⑬ TB-A1(Block) ⑭ L-N, INPUT, AC
L-N, Output, AC
TB-B(Black)
Terminal No. Function Input /output Max. Current Description Remark
Water INV. pump operation (maximum input power of
B1/B6 Water Pump AC 230V output 0.5 A Mandatory
pump 100W). (B6 : Lived)
B2/B3/B5 Mixing valve AC 230V output 22 mA Mixing Valve operation(B2: CW, B3: CCW) Option
B4/B5 Backup Boiler AC 230V output 10 mA Signal output for Backup Boiler(B5: Neutral) Option
Additional Water pump operation (maximum input
B7/B8 Water Pump AC 230V output 0.5 A Option
power of pump 100W)(B8 : Lived)
B9/B10/ 2 Way Valve operation for Zone#1 (UFH)
2Way valve #1 AC 230V output 22 mA Option
B11/B12 (B9 : NO, B10 : NC, B11: Neutral, B12: Lived)
⑮ B13/B14/B11/ 2 Way Valve operation for Zone#2 (FCU)
2Way valve #2 AC 230V output 22 mA Option
B12 (B13 : NO, B14 : NC, B11: Neutral, B12: Lived)
B15/B16/B17/ 3 Way Valve operation for DHW
3Way valve AC 230V output 22 mA Option
B18 (B17 : NO, B18 : NC, B15: Neutral, B16: Lived)
Power to external thermostat(s)
B19/B20 Thermostats AC 230V output 22 mA Option
(B20: Lived)
Thermostat for zone#1 (UFH) Cooling(B21)/
B21/B22 Thermostat 1 AC 230V input 22mA Option
Heating(B22) Signal
Thermostat for zone#2 (FCU) Cooling(B23)/Heating(B24)
B23/B24 Thermostat 2 AC 230V input 22mA Option
Signal
Signal input from Solar Pump / DHW Thermostat
B25/B26 Solar Pump AC 230V input 10 mA Option
(B26 :Lived)

⑯ Dip Switch(K1~K4)

11
Wiring works
Selection for the power and booster heater wire terminal
fConnect the cables to the terminal board using the solderless ring terminal.
fUse certified and verified cables.
fConnect using a driver which is able to apply the rated torque to the screws.
fIf the terminal is loose, fire may occur caused by arc.
If the terminal is connected too firmly, the terminal may be damaged.
fExternal force should not be applied to the terminal block and wires.
fThe cable ties to fasten the wire should be an incombustible material, V0 or above.
(The cable ties should be used to fasten the power wire and they are supplied with the unit.)

Tightening Torque (kgf • cm)


M3 0.5 ~ 0.75
M3.5 8 ~ 12
M4 12 ~ 18
M5 20 ~ 30

fMain PCB

M3.5 Screw

M3 Screw

M3.5 Screw
M4 Screw

fELCB

M5 Screw

12
Selecting solderless ring terminal
fSelect a solderless ring terminal of a connecting power cable based on a nominal dimensions for cable.
fCover a solderless ring terminal and a connector part of the power cable and then connect it.

Silver solder

ENGLISH
Nominal dimensions for cable (mm2) 1.5 2.5 4/6 10
Nominal dimensions for screw (mm) 4 4 4 8 8
Standard dimension (mm) 8 9.5 9.5 12 12
B
Allowance (mm) ±0.2 ±0.2 ±0.2 ±0.2
Standard dimension (mm) 3.4 4.2 5.6 7.1
D +0.3 +0.3 +0.3 +0.3
Allowance (mm)
-0.2 -0.2 -0.2 -0.2
Standard dimension (mm) 1.7 2.3 3.4 4.5
d1
Allowance (mm) ±0.2 ±0.2 ±0.2 ±0.2
E Min. 4.1 4.1 6 7.9
F Min. 6 7 5 9 9
L Max. 16 17.5 20 28.5 30
Standard dimension (mm) 4.3 5.3 4.3 8.4 8.4
d2 + 0.2 + 0.2 + 0.2 +0.4 +0.4
Allowance (mm)
0 0 0 0 0
t Min. 0.7 0.8 0.9 1.15

13
Wiring works
How to connect your extended power cables
1. Prepare the following tools.
Tools Crimping pliers Connection sleeve (mm) Insulation tape Contraction tube (mm)

Spec MH-14 20xØ6.5(HxOD) Width 19mm 70xØ8.0(LxOD)

Shape

2. As shown in the figure, peel off the shields from the rubber and wire of the Power cable (Unit: mm)
power cable.
- Peel off 20 mm of cable shields from the pre-installed tube. 20 20 20
60
• For information about the power cable specifications for indoor and 120
180
outdoor units, refer to the installation manual.
CAUTION
• After peeling off cable wires from the pre-installed tube, insert a 180
120
contraction tube. 60
20 20 20

Pre-installed tube for the power cable

3. Insert both sides of core wire of the power cable into the connection sleeve.
fMethod 1
Push the core wire into the sleeve from both sides.
Connection sleeve

fMethod 2
Twist the wire cores together and push it into the sleeve.

Connection sleeve

• If cable wires are connected without using connecting sleeves, their contact area becomes reduced, or corrosion develops on the
outer surfaces of the wires (copper wires) over a long time. This may cause an increase of resistance (reduction of passing current)
CAUTION
and consequently may result in a fire.

4. Using a crimping tool, compress the two points and flip it over and compress another two points in the same location.
- The compression dimension should be 8.0.

Compression
dimension

- After compressing it, pull both sides of the wire to make sure it is firmly pressed.
fMethod 1 fMethod 2
Compress it 4 times Compress it 4 times

5 mm 5 mm

14
5. Wrap it with the insulation tape twice or more and position your contraction tube in the middle of the insulation tape.
fMethod 1 fMethod 2
Insulation tape Insulation tape

ENGLISH
40 mm 35 mm

6. Apply heat to the contraction tube to contract it.


fMethod 1 fMethod 2
Contraction tube Contraction tube

7. After tube contraction work is completed, wrap it with the insulation tape to finish.
Three or more layers of insulation are required.
fMethod 1 fMethod 2
Insulation tape Insulation tape

• Make sure that the connection parts are not exposed to outside.
CAUTION • Be sure to use insulation tape and a contraction tube made of approved reinforced insulating materials that have
the same level of withstand voltage with the power cable. (Comply with the local regulations on extensions.)

• In case of extending the electric wire, please DO NOT use a round-shaped Pressing socket.
WARNING - Incomplete wire connections can cause electric shock or a fire.

15
Wiring works
Grounding work
fGrounding must be done by a qualified installer for your safety.

Grounding the power cable


fThe standard of grounding may vary according to the rated voltage and installation place of a heating pump.
fGround the power cable according to the following.

Installation place
High humidity Average humidity Low humidity
Power condition

Perform the grounding Perform the grounding work 3 if


Electrical potential of lower than 150V
work 3. Note 1) possible for your safety. Note 1)

Must perform the grounding work 3. Note 1)


Electrical potential of higher than 150V
(In case of installing circuit breaker)

❋ Note 1) Grounding work 3


• Grounding must be done by your installation specialist.
• Check if the grounding resistance is lower than 100 Ω.
When installing a circuit breaker that can cut the electric circuit in case of a short circuit, the allowable grounding
resistance can be 30~500 Ω.

❋ Examples to use cable striper

<Cable striper>

1. Adjust the blade position by coin(the controller is at the bottom side of the tool). Fix the
blade position according to the outer sheath thickness of the power cable.

2. Fix the power cable and tool by using the hook at the top side of the tool.

3. Cut out the outer sheath of the power cable by revolving the tool in the direction of the
arrow, two or three times.

4. At this situation, cut out the outer sheath of the power cable by moving the tool toward
the arrow direction expressed.

5. Slightly bend the wire and pull out the cut part of the outer sheath.

16
Power and communication with outdoor unit

ENGLISH
Communication
Wire

ELCB

N L

Power Wire

• Be careful when connecting L, N.


CAUTION

Connecting the power wire


1. Connect ‘Live’ and 'Neutral’ power line with ‘L, N’ of a ELCB.
2. Connect ‘L,N’ of a ELCB with ‘A1 and A2’ in TB-A.
3. Connect ‘Protective Earth’ line with ‘Earth screw’ In case.

Recommended wire specification

Power Cable Max. Length


Load Power Supply
mm2, wires m
Do NOT use Heater (Water Pump, Valve, 1.5 / 3 L < 10m
Wired RMC) 2.5 / 3 10m < L
1Ø, 220-240V, 50Hz
4.0 / 3 L < 10m
Use Booster Heater (Max. 3kW)
6.0 / 3 10m < L

fThe power cable is not supplied with Air to water heat pump.
fThis equipment with "IEC 61000-3-12".
fPower supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible
cord. (Code designation IEC:60245 IEC 57 / CENELEC: H05RN-F or IEC:60245 IEC 66 / CENELEC: H07RN-F)
fWhen installing the control kit in a computer room or net work room, server room or in the presence of risk of
disturbance to the communication cable, use the double shielded (tape aluminium / polyester braid + copper) cable of
FROHH2R type.

17
Wiring works
Connecting the communication wire
fConnect ‘outdoor unit’s F1&F2’ with ‘control kit’s F1&F2 in TB-C’ by 2 core cable.

Outdoor Unit
(at Control Plate)
Control Kit

Communication with a wired remote controller (1 unit)

Wired Remote Controller


(Master)

Communication with a wired remote controller (2 units)

Wired Remote Controller


(Slave)

Wired Remote Controller


(Master)

18
Connecting a wired remote controller
1. Connect 'F3, F4' of TB-C kit with 'F3, F4' of a wired remote controller.
f2 units (wired remote controllers) are able to be installed on TB-C.
fWhen 2 units are installed, either one shall has "Master" setting and another one shall have "Slave" settings on a wired
remote controller.

ENGLISH
Temp. Sensor for DHW, Backup heater and a Water Flow Sensor
External wiring to control a switch of relay by a installer

Temp. sensor for backup heater Relay

Temp. sensor for DHW


Flow Sensor

Connecting a temp. sensor wire into DHW


1. Put the sensor side of a temp. sensor wire into the designated location in a DHW.
2. Connect the other side of the line at CNS042.

Connecting a temp. sensor wire to outlet of backup heater


1. Put the sensor side of a temp. sensor wire into the designated location in a backup heater.
2. Connect the other side of the line at CNS047.

Connecting a flow sensor


1. Install a flow sensor in water line.
2. Connect a wire a flow sensor into 'CNS057' connector.

Connecting a PV(Photovoltaic) Signal / Peak power control Signal


1. Install as above diagram.
2. Connect the PV / Peak power control signal wire to the 'CNS046' connector.

• It operates according to the setting of FSV, and both functions can not be used at the same time.
NOTE (PV Control / Peak power control)

19
Wiring works
Backup heater

Relay or Magnetic Contactor Wire

Connecting a relay or a magnetic contactor for a backup heater (Not Directly connect a backup heater)
1. Connect a "relay or a magnetic contactor" with "CNP003,CNP001,CNP002".
fWhen a backup heater mode is "ON" at 1st step, a control signal of AC 230V goes through CNP003 and CNP001.
fWhen a backup heater mode is "ON" at 2nd step, a control signal of AC 230V goes through CNP003 and CNP002..
1st step 2nd step

N L1 N L2

This port can NOT supply enough power for driving a backup heater.
NOTE It’s just for providing a ON/OFF control signal.
Maximum current is 0.5A.

20
Specification table

Part Specification
Step1 : CNP003, CNP001
Tab-Terminal (output)
Step2 : CNP003, CNP002
Connection load Relay or Magnetic contactor for a control signal

ENGLISH
Output(CNP003,CNP001 or
AC 230V (MAX 0.5A)
(CNP003,CNP001)+(CNP003,CNP002)

Backup boiler

Connection of the back-up boiler


Description No. of wires Min. / Max. current Thickness Supply Scope
0.75mm2 H05RN-F or Field supply
Back-up Boiler 2+ground 10mA / 50mA
H07RN-F (220-240V~, Input)

1. Before the installation, control kit should be turned off.


2. Using the appropriate equipment to correct position of terminal
block as shown on the diagram.
B5 : Neutral (N) 3. Make sure EXT-CTRL signal of back up boiler must be 220-240V~.
B4 : Back-up boiler (L)
When it set back up
- Do not connect supply power of back up boiler directly.
When it order to back up
boiler on the control kit boiler operates (relay on) ❋ Heat pump does not work when the Back-up boiler operates.
(relay off )
L N L N

Boiler Boiler

21
Wiring works
Connection guide of additional pump
Case 1) INV. pump
Connect the PWM control external type pump to PWM terminal block and power cable to the external contact terminal.
The maximum number of additional pump installation is one inverter pumps (Input power 100W).
1. Power supply (For additional INV. Pump)

B6 : Live additional pump


B1 : Neutral additional pump

2. PWM control (For additional INV. Pump only), refer to page 29

Reference (GND)

PWM signal (SIG)

• If there is wrong wiring between PWM and reference, INV. Water Pump may not work or wrong operation.
CAUTION

PWM characteristic curve


Max.
Speed

PWM input signal(%)

The additional pump should be the same type of product as the above graph.
5~16kW : GRUNDFOS UPMM 25-95 (Heating Type)

22
Case 2) AC pump
The maximum number of additional pump installation is one AC pumps (Input power 100W).
1. Power supply (AC Pump)

ENGLISH
B8 : Live additional pump
B7 : Neutral additional pump

Neutral additional pump

PCB Live additional pump

Terminal block B7 B8

Pump

Power L M/C
N

• Terminal of this product is for additional water pump and the maximum allowable current is 0.5 A.
CAUTION

23
Wiring works
Connection of the 2-way valve
Description No. of wires Min. / Max. current Thickness Supply Scope
Motorized 2-way valve to shut off > 0.75 mm2, H05RN-F or Field supply
2+ground 10mA / 50mA
UFH loops during cooling. H07RH-F (220-240V~, Output)

2-way motorized valve


fWhen outlet water temperature reach to lower than 16 °C in
B9 : 2WAY1 (L1) B14 : 2WAY2 (L2) cooling mode, UFH loops will be closed.
B10 : 2WAY1 (L2) B13 : 2WAY2 (L1) f220-240V~
B11 : Neutral (N) B12 : Live (L) f2 wires(Normal Open or Normal Close)
* Connection of 2 wires 2-way valve
1. Before the installation, control kit should be turned off.
2. Using the appropriate equipment to correct position of terminal
Normal
closed type
Normal
Open type block as shown on the diagram.
3. Make sure what type is you use.
In case of normal closed type
- When it closes -When it opens - Normal OPEN or Normal CLOSED.

• There are 2 types of 2-way valve, normal open type and


N L1 normal closed type. Make sure to connect terminals
CAUTION
Mixing Tank Floor Mixing Floor to right positions of terminal block. As detailed on the
Heating Tank Heating
2Way Valve
wiring diagram and illustrations above.

In case of normal open type


-When it opens - When it closes

N L2

Mixing Tank Floor Mixing Floor


Heating Tank Heating

2Way Valve

24
Connection of the 3-way valve
Description No. of wires Min. / Max. current Thickness Supply Scope
Diverting type 3way > 0.75 mm2, H05RN-F or Field supply
4 10mA / 50mA
valve H07RN-F ( 220-240V~, Input)

Status L1 L2 3-way diverting valve for water tank

ENGLISH
A fDiverting typecooling mode, UFH loops will be closed.
OFF ON
B15: Neutral (N) B18: 3WAY (L2) (Initial) f220-240V~
B16: Live (L) B17: 3WAY (L1) B ON OFF 1. Before the installation, control kit should be turned off.
2. Using the appropriate equipment to correct position of
Field Setting Valve (#3071) “0” Field Setting Valve (#3071) “1” terminal block as shown on the diagram.
Floor heating as default DHW tank as default 3. Make sure what type of 3 way V/V you use.
A A
FLOOR HEATING FLOOR HEATING

Outdoor Unit Outdoor Unit

3WAY V/V 3WAY V/V

DHW TANK DHW TANK

B FLOOR HEATING
B
FLOOR HEATING

Outdoor Unit Outdoor Unit

3WAY V/V 3WAY V/V

DHW TANK DHW TANK

Connection of the thermostat


escription No. of wires Max. current Thickness Supply Scope
> 0.75 mm2, H05RN-F or Field supply
Room Thermostat 4 22mA
H07RH-F (220-240V~, Input)

1. Before the installation, control kit should be turned off.


2. Using the appropriate equipment to correct position of terminal
B19: Neutral (N) block as shown on the diagram.
B20 : Live (L) 3. Make sure what type is you use.
B21 : THERMOSTAT01_COOLING (C1) - Contact signal must be “ L “. When you install two thermostats,
B22 : THERMOSTAT01_HEATING (H1)
thermostat2 is prior to thermostat1.
B23 : THERMOSTAT02_COOLING (C2)
B24 : THERMOSTAT02_HEATING (H2) • Product will not operate when signal for cooling and
N L C1 H1 N L C2 H2 CAUTION heating mode is inputed at the same time.

THERMOSTAT01 THERMOSTAT02

25
Wiring works
Example

zone#1 only : cooling mode zone#2 only : cooling mode zone#1, zone#2 : cooling mode

N L N L N L

Room thermostat Room thermostat Room thermostat

zone#1 only : heating mode zone#2 only : heating mode zone#1, zone#2 : heating mode

N L N L N L

Room thermostat Room thermostat Room thermostat

• Before completing installation of Room thermostat, check the wiring method in a manual of Room thermostat
WARNING to output L line.

Target zone Zone 1


Thermostat on/off controller's output signal Only Heat

fConnect a thermostat on/off controller's power to B19, B20 and connect output of a thermostat on/off controller to B22.

26
Example of RX1 (Danfoss)
fIn manual of a RF receiver

RX1 and RX2

ENGLISH
Electronics

Terminal 1
RX2 only 1 /    
Zone 2 Zone 1 Zone 1
Com
on on off

fExample of wiring works


Control kit

Cool Heat Cool Heat


(zone#1) (zone#1) (zone#2) (zone#2)

     

1 /    
Com

RF receiver (RX1)

27
Wiring schematics
Wiring diagram

• It does not support external input(CNS083)/output(CNS081) signal function.


NOTE

28
Self-test mode of wired remote controller
Use of self-test mode

ENGLISH
Service mode
Service mode
Reset All Service Mode

Power Master Reset

ODU K3 Reset
0 Field Setting Value
Self-Test Mode

Indoor Unit Option


Please enter your PASSWORD

1. If you want to use the various additional functions for your Wired Remote Controller, press the and buttons at the
same time for more than 3 seconds.
fThe password entry screen appears.
2. Enter the password, “0202,” and then press the button.
fThe settings screen for installation/service mode appears.
3. Select Self-Test Mode in Service Mode.
4. Self-Test Mode consists of Self-Test Mode Display that shows operation value satus and menus that can turn each
component on or off.

Self-Test Mode Self-Test Mode Display


Self-Test Mode Display
Water Inlet Temp.: -00.0ঐ to 000.0ঐ
Water Pump < OFF >
Water Outlet Temp.: -00.0ঐ to 000.0ঐ
Booster Heater < OFF >
Backup Heater Outlet Temp: -00.0ঐ to 000.0ঐ
DHW Valve (3 Way valve) < OFF >
Mixing valve Outlet Temp.: -00.0ঐ to 000.0ঐ
Zone#1 Valve < OFF >
Tank Temp: -00.0ঐ to 000.0ঐ
Back Up Heater1 + Water Pump < OFF >
Indoor Ambient Temp.: -00.0ঐ to 000.0ঐ
Back Up Heater2 + Water Pump < OFF >
Back Up Boiler < OFF >
Zone#2 Valve < OFF > Self-Test Mode Display

Mixing Valve < OFF > Indoor Ambient Temp. (Zone2): -00.0ঐ to 000.0ঐ

Flow Temp. Sensor #1(Zone1): -00.0ঐ to 000.0ঐ

Flow Temp. Sensor #2(Zone2): -00.0ঐ to 000.0ঐ

Termostat #1(Zone #1): Coo/Heat

Termostat #2(Zone #2): Coo/Heat

Solar Panel On/Off: On/Off

29
DHW tank
Electrical connections
Procedure

• Switch off the power supply before making any connections.


WARNING • Use a thermal grease in thermistor pocket after installing electric connections.

Connections to be made in the electrical box of DHW tank


1. Connect the booster heater power supply and thermal protection cable.
2. Make sure to ensure strain relief of the cable.

Connections to be made in the electrical box of indoor units


3. Plug the thermistor cable connector in the connector CNS042 on the pcb.
4. Connect the booster heater power supply and thermal protection cable(field supply) to terminal TB-A1 and earth on the
terminal block.
5. Connector the loose ends of the TB-A1 on the terminal block and the connector CNS042 on the PCB.
6. Plug the thermistor cable connector in the socket X9A on the PCB.
7. Connect the booster heater power supply and thermal protection cable (field supply) to terminal 7, 8, 21, 22 and earth on
the terminal block.
8. Connect the booster heater power supply cable to the circuit breaker and earthing screw.
9. Fix the cables to the cable tie mountings with cable ties to ensure strain relief.

• It is of great importance that the heater is filled with water before the electricity is hooked up, or else- the
CAUTION warranty is not valid. If the heater is installed and not used, it must be flushed with water once a week.

Connection of the solar circulation pump / DHW Thermostat for DHW tank
Description No. of wires Max. current Thickness Supply Scope
Solar pump / 0.75mm2 H05RN-F or Field supply
2+ground 10 mA
DHW Thermostat H07RN-F (230 V~, Input)

1. Before the installation, control kit should be turned off.


2. Using the appropriate equipment to correct position of terminal
block as shown on the diagram.
B25: SOLAR PUMP / DHW Thermostat (N) 3. It is for control kit to inform that the Solar pump / DHW Thermostat
B26: SOLAR PUMP / DHW Thermostat (L)
is operating.
4. Solar pump / DHW Thermostat is controlled by installer’s handling.
SOLAR PUMP / And it send the signal to control kit depending on Solar pump /
DHW Thermostat DHW Thermostat conditions. In operating mode, signal shall be
Controller
Power around 230Vac B/W N&L. In non-operating mode, signal shall be
around 230Vac B/W N&L. When solar pump signal is On, Control kit
Solar pump operates when FSV 3061=1 is set, and DHW DHW mode will be turned off.
Thermostat operates when FSV 3061=2 is set.
• Maximun allwable current of each terminal is below 10 mA.
CAUTION • Ports number B25, B26 are for input port for detection
and they do not supply power to a Solar pump / DHW
Thermostat.

30
Booster heater

ENGLISH
Booster heater

Recommended wire specification

Power Cable Max. Length


Load Power Supply
mm2, wires m
4.0 / 3 L < 10m
Use Booster Heater (Max. 3kW) 1Ø, 220-240V, 50Hz
6.0 / 3 10m < L

❈ Code designation IEC: 60245 IEC 57/ CENELEC: H05RN-F

Connecting a booster heater (PTC heater – allowed limit : Max. 3kW)


1. Directly connect a ‘Booster heater’ with ‘A3 and A4 ’ in TB-A.
• Wire spec : 6.0 mm2 (regardless of distance)
NOTE • Code designation IEC : 60245 IEC 57 / CENELEC : H05RN-F

Specification table

Part Specification
Terminal Block (output) N, L of TB-A1
Connection load Direct connection a booster heater
Output (N, L) AC 230V (MAX 20A)

31
DHW tank
DHW tank Switch box layout

DHW Tank Temp. (15m) CNS042(YEL)

❋ Use a correct sensor pocket which is fit for the DHW tank sensor(OD Ø6).
If the gap between the supplied sensor and DHW tank sensor pocket is big, use thermal grease.

• When you set the hot water supply temperature to 55°C or less, do not use the booster heater.
NOTE - The heatpump and the booster heater operate until the initial set temperature is reached. After that, only the
booster heater may operate depending on the settings.

32
Troubleshooting
IMPORTANT: All maintenance or repair work must be executed by an approved installer.

Problem Possible cause Solution

Check if there is any power on the power supply terminal


No power supply to the water heater
on the thermostat.

ENGLISH
Hot water is not coming out.
The thermostat may be set too high and Reduce thermostat setting by 5 °C and press the reset
cause the fuse or safety cut-off to operate. button.

Check if there is any power on the power supply on the


Heating element or internal electrical wiring connector of the heating element between black and
Heating is not working
is out of order. yellow/green wires. If this is OK, press the reset button
on the fuse/safety cut-off.

Thermostat is set too low. Adjust the thermostat up using a standard screwdriver.

Check the resistance of the heating element on the


Heating element or the internal electrical
connector of the heater bundle, and the condition of the
Water is not warm enough wiring is partially out of order.
internal wiring.

UX mixing valve(fitted on top) is incorrectly Adjust the UX mixing valve correctly to the preferred
adjusted. temperature.

Water expands when heated. If there is no


If drip from the SV is severe, it might need to be replaced.
consumption of hot water over a period of
Safety valve(SV) is dripping. Some dripping is normal. Alternatively an expansion
time pressure builds up, causing the safety
vessel can be fitted.
valve to open.

The heating element may not be properly


Leak warning outlet is tightened. Check the heating element o-ring seal and all
dripping. connections.
There may be a leak.

Other problems, or if none


of the above solves the - Contact the installer/supplier regarding any other failure.
problem.

Incorrect handling of thermostat, safety valve or other valves may lead to tank rupture. When servicing the unit
WARNING follow instructions carefully:
• Always turn off main power supply when water supply is being shut off.
• Test the free operation of the safety valve regularly by opening the valve ensuring the water flows freely.
• Electrical connection and all servicing of the electrical components should only be carried out by an authorized
electrician.
• Fitting and all servicing of plumbing fixtures should only be carried out by an authorized installer.
• When replacing the thermostat, safety valve or any other valve or part supplied with this unit, use only approved
parts of the same specification.

• Before resetting the safety cut-off or altering the thermostat setting, always remember to isolate the electrical
CAUTION supply to the unit. This must be done prior to removing the electrical box lid.
• If the electric element or thermostat is defective, contact authorized electrician.
• After adjustments are completed, ensure the lid to the electrical box is refitted correctly and that the retaining
screw is properly fitted.

33
Mixing Valve
Installation of mixing valve
Radiator

TW4

Balancing Vessel
(Mixing tank)
Under Floor

When two different zones are used with different temperature, adjust the temperature of discharge water to high
temperature water and control the amount of bypass to provide low temperature water by applying the mixing valve and
temperature sensor of the mixing valve (TW4).
1. Select a mixing valve from the manufacturers as below (recommended) and install it at the enterance of the zone.
2. Install the supplied temperature sensor (TW4) on the rear part of the mixing valve. Install TW4 Sensor within 1m of
Mixing Valve.
3. Since running time varies depending on the manufacturer, set the FSV (default 90 sec.) by referring to the FSV value below.

Maker BELIMO SIEMENS HONEYWELL


3 Way Valve R3020-6P3-S2 VXP45.20-4 (kvs 4) V5011E1213
Model code
Actuator LR230A(-S) SSB31 ML6420A3015
Running time 90 sec. 150 sec. 60 sec.
FSV(#4046) setting 9 15 6

❋ The table above is for your reference. It can be changed without advanced notice.
4. Set the FSV value by referring to the table below depending on installation environment.

Function Details Code Unit Default Min. Max.


Use or not 4041 - 0(No) 0 2
Target temperature difference (Heating) (TW2-TW4) 4042 °C 10 5 15
Target temperature difference (Cooling) (TW4-TW2) 4043 °C 10 5 15
Mixing valve
Control factor 4044 - 2 1 5
Interval of valve control 4045 Min. 2 1 30
Running time (10 second unit) 4046 (x10) sec 9 6 24

❋ 4041 =1 : Controlled based on the temperature difference (4042, 4043)


❋ 4041 =2 : Controlled based on the temperature difference of the WL value

34
ex)
<#4041=1> <#4041=2>
Heating
Tw2 Tw2
Water Water
Temp. Temp.
TW3 TW3

#4042

ENGLISH
TW4 TW4

Ta Ta
Outdoor Ambient Temp. Outdoor Ambient Temp.

❋ The mixing valve is controlled based on the FCU WL value.


❋ As the #4044 value increases and the #4045 value decreases, the control speed increases. (Temperature hunting may
occur if the control speed increases depending on the load.)
❋ The additional pump and mixing valve should be purchased separately. TW4 sensor is included in the product accessories.
❋ TW2 : Water temp. sensor 2

• When the thermostat control is set as 'Use', the mixing valve can be used for Zone 1 and Zone 2. (When both FSV
CAUTION #2091 and #2092 are set as 1)

Connection of the mixing valve

Mixing Senser
(Default, 15 m) CNS045(BLU)

Radiator
N L N L
N L

2: Mixing Valve_CW
3: Mixing Valve_CCW
5: Neutral
TW4

Balancing Vessel
(Mixing tank) Under Floor

35
Mixing Valve
Description No. of wires Max. current Thickness Supply Scope
Mixing valve 4 22 mA > 0.75 mm2, H05RN-F or H07RH-F Field supply (230 V~, Input)

1. Before the installation, control kit should be turned off.


2. Using the appropriate equipment to correct position of terminal
block as shown on the diagram.
B5: Neutral (N)
B3: CCW (L2)
B2: CW (L1)

Example of sensor installation (TW3 / TW4)


Weld the sensor holder on the selected location of the pipe and then insulate it.

When the pipe is a copper pipe When the pipe is not a copper pipe

Pipe Pipe

Sensor Sensor
holder

Sensor
Aluminum tape Rubber tape

Sensor Sensor
Sensor clip

Cable-tie

Insulator Insulator

• When the holder sensor cannot be welded on the pipe, fix the senor with aluminum tape and insulate it.
NOTE

36
Concrete curing function
When pipes of floor heating are installed, operation for reinforcing concrete curing is applied. (Period of operation: 23 days)
Entering procedure
1. After turning off the DIP switch K3 (3rd switch of SW03) of control kit (Default ON), turn off and turn on the control kit. The
operation for concrete curing starts automatically. (If blackout occurs and communictation restarts later, operation will
continue.)

ENGLISH
2. Temperature of discharge water is controlled as time goes on like below.
[Temp.]
ՑՋ

ՐՐ

ՐՋ

ՏՐ

ՏՋ

ՎՐ

ՎՋ

ՍՐ

ՍՋ
Ռ Ս Վ Տ Ր Ց Ւ Փ Ք ՌՋ ՌՌ ՌՍ ՌՎ ՌՏ ՌՐ ՌՑ ՌՒ ՌՓ ՌՔ ՍՋ ՍՌ ՍՍ ՍՎ [Day]

Initial Total
Classification Step raise Heating Step down
Heating (Hour)
Time 96 72 24 24 24 24 24 144 24 24 24 24 24 552
Temperature 30 55 30 35 40 45 50 55 50 45 40 35 30 -

3. Remaining days are displayed on the wired remote controller during operation but key operation is unavailable.

Remaining days are Concrete Curing


displayed. Remaining days:

❋ If an error is displayed, concrete curing function does not work.

37
Concrete curing function
• Definition of Dip switch function
NOTE

Dip S/W S/W #1 S/W #2 S/W #3 S/W #4

• Turn off when


ON
• None • None • None an E101 error
(default)
occurs

• Emergency • Emergency hot • E101 error does


OFF • Concrete curing
heating water supply not turn off

• Please refer to
• Please refer to
reference item • Please refer to the user manual the previous
below
page

DIP
DIP switch
switch

• When outdoor unit only power supply change by local condition, it is an option to auto restart system.

Classification When the outdoor unit is power off When the outdoor unit is power on

ON • Hydro Unit E101 error disappears.


Hydro Unit • Hydro Unit E101 error occurs.
(default) • Hydro Unit operation turns off.
operation
according to the
• Hydro Unit E101 error disappears.
DIP S/W #4 setting OFF • Hydro Unit E101 error occurs.
• Hydro Unit keeps its previous operation.

- The outdoor unit on/off control is not available with the A2A indoor unit.
- Although the outdoor unit is turned on after the E101 error occurred, the A2A indoor unit operation keeps turned off.

38
Installation option setting
fSet the control kit installation option with remote controller option.

The procedure of option setting

ENGLISH
Entering mode for option setting Option setting mode

Mode change

High Temp Button High Fan Button

Low Temp Button Low Fan Button

Entering mode to set option


1. Remove batteries from the remote controller.
2. Insert batteries and enter the option setting mode while pressing High Temp button and Low Temp button.

3. Check if you have entered the option setting status.

39
Installation option setting
Changing a particular option
You can change each digit of set option.

Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6


The tens’ digit of an The unit digit of an
The option mode you
Explanation PAGE MODE option SEG you will option SEG you will The changed value
want to change
change change

Remote
Controller
Display

Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details
Indication and
Details Tens’ digit Unit digit The changed
0 D Option mode 1~6 0~9 0~9 0~F
of SEG of SEG value

• When changing a digit of an control kit address setting option, set the SEG3 as ‘A’.
NOTE • When changing a digit of control kit installation option, set the SEG3 as ‘2’.
Ex) When setting the ‘central controller’ into disuse status.
Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
The tens’ digit The unit digit
The option
of an option of an option The changed
Explanation PAGE MODE mode you want
SEG you will SEG you will value
to change
change change
Indication 0 D 2 0 5 0

❋ 02 Series installation option

Classification SEG1~24
Use central controller (Default) 020010 100000 200000 300000
Disuse central controller 020000 100000 200000 300000

❋ 01 Series Production Option (Factory default)

Mode 1 SEG1~24
MIM-E03CN 012300 100000 200000 300000

40
Troubleshooting
If the unit has some problem to work properly, some error codes will be displayed on the controller.
The following table described the explanation of error codes on the LCD display.

Thermistor

ENGLISH
fCheck its resistance. 10kohm@25 °C (Control kit), 200kohm@25 °C (DHW Tank, Solar)
fCheck its location as shown at the diagram.
fCheck its contact status with pipe.
fFinal solution is to change parts
Display Explanation
Short- or open-circuit error of the room temperature sensor of the Zone 2 indoor unit (detected only when the
room thermostat is used)
Short- or open-circuit error of the room temperature sensor of the Zone 1 indoor unit (detected only when the
room thermostat is used)
Wired remote controller thermistor SHORT or OPEN

Water Inlet thermistor SHORT or OPEN

PHE Outlet thermistor SHORT or OPEN

Water outlet (Back up Heater) temp sensor SHORT or OPEN (The Backup heater for using)

Water TANK thermistor SHORT or OPEN

Outdoor Eva Inlet Temp Sensor SHORT or OPEN

Mixing Valve thermistor SHORT or OPEN

Wired remote controller temp sensor


E653

EVA inlet Water Outlet


E906 Tr1 Tw2 E902

Ref' In

PHE

Ref' Out

Water inlet
Tw1
E901

Outdoor Unit Water tank temp sensor


E904

41
Troubleshooting
Communication
Display Explanation
Communication error between remote controller and the Control kit

Tracking error between remote controller and the Control kit

Memory(EEPROM) Read/Write Error(Wired remote Controller data error)

E601, E604

E654
MEMORY(EEPROM) Read/Write Error (Wired controller data error)

Micro SD card
Download connector

EEPROM

F3(COM2_B)/
F4(COM2_A)
Thermistor Terminal Block
Connector

42
Water pump & Flow Sensor
Display Explanation
Low flow rate error
• in case of low flow rate in 30 sec during water pump signals is ON(Starting)
• in case of low flow rate in 15 sec during water pump signals is ON(After starting)

ENGLISH
Normal flow rate error
• in case of normal flow rate in 10min during water pump signal is OFF

E911
fWater pump ON ( Low flow rate ) : NOT enough water flow

Water flow < 12LPM(Outdoor unit capacity > 9kW)


Water flow < 7LPM(Outdoor unit capacity ≤ 9kW)

E912
fWater pump OFF ( Normal flow rate )

Water flow > 12LPM(Outdoor unit capacity > 9kW)


Water flow > 7LPM(Outdoor unit capacity ≤ 9kW)

43
Error codes
If the unit has some problems and does not work normally, error code is shown on the OUTDOOR UNIT main PBA or LCD of
the wired remote controller.

Display Explanation Error Source


CONTROL KIT,
101 CONTROL KIT / OUTDOOR UNIT wire connection error
OUTDOOR UNIT
Short- or open-circuit error of the room temperature sensor of the Zone 2 indoor unit
120 (detected only when the room thermostat is used)
CONTROL KIT
Short- or open-circuit error of the room temperature sensor of the Zone 1 indoor unit
121 (detected only when the room thermostat is used)
CONTROL KIT

162 EEPROM Error CONTROL KIT

198 Error of Terminal Block's Thermal Fuse(Open) CONTROL KIT

CONTROL KIT,
201 CONTROL KIT/OUTDOOR UNIT communication error (Matching error)
OUTDOOR UNIT

CONTROL KIT,
202 CONTROL KIT/OUTDOOR UNIT communication error (3 min)
OUTDOOR UNIT

203 Communication error between INVERTER and MAIN MICOM (6 min) OUTDOOR UNIT

221 OUTDOOR UNIT temperature sensor error OUTDOOR UNIT

231 Condenser temperature sensor error OUTDOOR UNIT

251 Discharge temperature sensor error OUTDOOR UNIT

320 OLP sensor error OUTDOOR UNIT

403 Detection of OUTDOOR UNIT compressor freezing (During cooling operation) OUTDOOR UNIT

Protection of OUTDOOR UNIT when it is overload (during Safety Start, Normal operation
404 state)
OUTDOOR UNIT

407 Comp down due to high pressure OUTDOOR UNIT

416 Discharge of a compressor is overheated OUTDOOR UNIT

425 Power source line missing error (only for 3-phase model) OUTDOOR UNIT

440 Heating operation blocked (outdoor temperature over 35°C) OUTDOOR UNIT

441 Cooling operation blocked (outdoor temperature under 9°C) OUTDOOR UNIT

458 OUTDOOR UNIT fan1 error OUTDOOR UNIT

461 [Inverter] Compressor startup error OUTDOOR UNIT

462 [Inverter] Total current error/PFC over current error OUTDOOR UNIT

463 OLP is overheated OUTDOOR UNIT

464 [Inverter] IPM over current error OUTDOOR UNIT

465 Compressor V limit error OUTDOOR UNIT

466 DC LINK over/low voltage error OUTDOOR UNIT

467 [Inverter] Compressor rotation error OUTDOOR UNIT

468 [Inverter] Current sensor error OUTDOOR UNIT

469 [Inverter] DC LINK voltage sensor error OUTDOOR UNIT

44
Display Explanation Error Source
470 Outdoor unit EEPROM Read/Write Error OUTDOOR UNIT

471 Outdoor unit EEPROM Read/Write Error(OTP error) OUTDOOR UNIT

474 IPM(IGBT Module) or PFCM temperature sensor Error OUTDOOR UNIT

475 OUTDOOR UNIT fan2 error OUTDOOR UNIT

ENGLISH
484 PFC Overload Error OUTDOOR UNIT

485 Input current sensor error OUTDOOR UNIT

500 IPM is overheated OUTDOOR UNIT

554 Gas leak error OUTDOOR UNIT

Wired Remote
601 Communication error between the CONTROL KIT and wired remote controller
Controller

Wired Remote
602 Wired remote controller Master/Slave setting error
Controller

CONTROL KIT,
604 Communication tracking error between the CONTROL KIT and wired remote controller Wired Remote
Controller

Wired Remote
607 Communication error between the Master and Salve wired remote controllers
Controller

899 Short- or open-circuit error of the Zone 1 water-out temperature sensor CONTROL KIT

900 Short- or open-circuit error of the Zone 2 water-out temperature sensor CONTROL KIT

901 Water inlet (PHE) temperature sensor error(open/short) OUTDOOR UNIT

902 Water outlet (PHE) temperature sensor error(open/short) OUTDOOR UNIT

903 Water outlet (backup heater) temperature sensor error. CONTROL KIT

904 DHW tank temperature sensor error CONTROL KIT

906 Outdoor evaporator inlet temperature sensor (open/short) OUTDOOR UNIT

Low flow rate error


911 • in case of low flow rate in 30 sec during water pump signals is ON(Starting) CONTROL KIT
• in case of low flow rate in 15 sec during water pump signals is ON(After starting)

Normal flow rate error


912 CONTROL KIT
• in case of normal flow rate in 10min during water pump signal is OFF

916 Mixing valve temperature sensor (open/short) CONTROL KIT

Error that the set temperature for disinfection operation is not reached, or, after reaching, the
919 temperature fails to continue for the requested time
CONTROL KIT

45
Reference (KEYMARK Certification)
Accessory*
Model code Outdoor Model code Indoor Registration number
Mono Control Kit
AE050RXYDEG/EU AE200RNWMEG/EU
007-CU0101
AE050RXYDEG/EU (space heating only) MIM-E03CN
AE080RXYDEG/EU AE200RNWMEG/EU
007-CU0102
AE080RXYDEG/EU (space heating only) MIM-E03CN
AE080RXYDEG/EU AE260RNWMEG/EU
AE080RXYDGG/EU AE260RNWMGG/EU 007-CU0103
AE080RXYDGG/EU (space heating only) MIM-E03CN
AE120RXYDEG/EU AE200RNWMEG/EU
AE120RXYDEG/EU (space heating only) MIM-E03CN
007-CU0104
AE160RXYDEG/EU AE200RNWMEG/EU
AE160RXYDEG/EU (space heating only) MIM-E03CN
AE120RXYDEG/EU AE260RNWMEG/EU
AE120RXYDGG/EU AE260RNWMGG/EU
AE120RXYDGG/EU (space heating only) MIM-E03CN
007-CU0105
AE160RXYDEG/EU AE260RNWMEG/EU
AE160RXYDGG/EU AE260RNWMGG/EU
AE160RXYDGG/EU (space heating only) MIM-E03CN

46
ENGLISH

47
Memo
Samsung, PO Box 12987, Blackrock, Co. Dublin. Ireland
or Blackbushe Business Park, Yateley, GU46 6GG. UK

This appliance is
ѣ̷̷ʪʒӥϩ˵ŵࣗߤߣࢋ

You might also like