SG 38mura 02
SG 38mura 02
SG 38mura 02
Service Manual
TABLE of CONTENTS
PAGE
WARNING
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
MODEL / SERIAL NUMBER NOMENCLATURES . . . . . . . . . . . 2 ELECTRICAL SHOCK HAZARD
WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Failure to follow this warning could result in personal injury
WIRING DIAGRAMS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 or death.
REFRIGERANT CYCLE DIAGRAMS . . . . . . . . . . . . . . . . . . . . . 14
REFRIGERANT LINES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Before installing, modifying, or servicing system, main
SYSTEM EVACUATION AND CHARGING . . . . . . . . . . . . . . . . 17 electrical disconnect switch must be in the OFF position.
ELECTRONIC FUNCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 There may be more than 1 disconnect switch. Lock out and
OUTDOOR UNIT POINT CHECK FUNCTION . . . . . . . . . . . . . . 21 tag the switch with a suitable warning label.
INFORMATION INQUIRY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
GENERAL TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . 24
DIAGNOSIS AND SOLUTION . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
CHECK PROCEDURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
WARNING
DISASSEMBLY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . 53
EXPLOSION HAZARD
REMOVE THE ELECTRICAL PARTS . . . . . . . . . . . . . . . . . . . . . 66
Failure to follow this warning could result
APPENDICIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
in death, serious personal injury, and/or
property damage. Never use air or gases
containing oxygen for leak testing or
Installing, starting up, and servicing air-conditioning equipment can
operating refrigerant compressors.
be hazardous due to system pressures, electrical components, and
Pressurized mixtures of air or gases
equipment location (roofs, elevated structures, etc.). Only trained,
containing oxygen can lead to an explosion.
qualified installers and service mechanics should install, start-up, and
service this equipment.
Untrained personnel can perform basic maintenance functions such as
coil cleaning. All other operations should be performed by trained
service personnel.
CAUTION
When working on the equipment, observe precautions in the product EQUIPMENT DAMAGE HAZARD
literature and on tags, stickers, and labels attached to the equipment. Failure to follow this caution may result in equipment damage
Follow all safety codes. Wear safety glasses and work gloves. Keep a or improper operation.Do not bury more than 36 in. (914 mm)
quenching cloth and fire extinguisher nearby when brazing. Use care of refrigerant pipe in the ground. If any section of pipe is
in handling, rigging, and setting bulky equipment. buried, there must be a 6 in. (152 mm) vertical rise to the valve
Read this manual thoroughly and follow all warnings or cautions connections on the outdoor units.
included in the literature and attached to the unit. Consult local
If more than the recommended length is buried, refrigerant
building codes and National Electrical Code (NEC) for special
may migrate to the cooler buried section during extended
requirements. Recognize safety information. This is the safety-alert
periods of system shutdown. This causes refrigerant slugging
symbol . When you see this symbol on the unit and in instructions and could possibly damage the compressor at start-up.
or manuals, be alert to the potential for personal injury.
Understand these signal words: DANGER, WARNING, and
CAUTION. These words are used with the safety-alert symbol. INTRODUCTION
DANGER identifies the most serious hazards which will result in This service manual provides the necessary information to service,
severe personal injury or death. WARNING signifies hazards which repair, and maintain the 38MURA family of heat pumps. This manual
could result in personal injury or death. CAUTION is used to identify has an “APPENDICIES” with data required to perform
unsafe practices which may result in minor personal injury or product troubleshooting. Use the “TABLE of CONTENTS” to locate a desired
and property damage. NOTE is used to highlight suggestions which topic.
will result in enhanced installation, reliability, or operation.
OUTDOOR UNIT
38 MU R A Q 36 3
38 = OUTDOOR UNIT
VOLTAGE
3=208/230-1-60
MU = MODEL VARIATION
A = Standard
B = High Heat
49 22 V 10001
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
2
38MURA: Service Manual
WIRING
All wires must be sized per NEC (National Electrical Code) or CEC
(Canadian Electrical Code) and local codes. Use Electrical Data table
CAUTION
MCA (minimum circuit amps) and MOCP (maximum over current
protection) to correctly size the wires and the disconnect fuse or breakers EQUIPMENT DAMAGE HAZARD
respectively. Failure to follow this caution may result in equipment damage
All field wiring construction should be finished by a qualified electrician. or improper operation.
Air conditioning equipment must be grounded according to the local Wires should be sized based on NEC and local codes.
electrical codes.
Current leakage protection switch should be installed.
NOTE: DO NOT connect the power wire to the terminal of the signal CAUTION
wire. Connection of power to any other terminal other than
L1 or L2 will cause damage to the control board. EQUIPMENT DAMAGE HAZARD
Any control signal cable should be run separately from the power wiring.
Failure to follow this caution may result in equipment damage
Use of metallic conduit or shielded cable is recommended. Maintain a
or improper operation.
distance of 12 inches(300mm) from the power wiring.
Be sure to comply with local codes while running wire from
NOTE: DO NOT run the power wiring and control wiring in the the indoor unit to the outdoor unit.
same conduit.
Every wire must be connected firmly. Loose wiring may
Size the wiring in accordance to the NEC / CEC or Table 2. Select cause the terminal to overheat or result in unit malfunction. A
different colors for different wire according to relevant regulations. fire hazard may also exist. Ensure all wiring is tightly
Ensure that the wire color of the outdoor and the terminal number are the connected.
same as those of the indoor unit.
No wire should touch the refrigerant tubing, compressor or
Table 2 — For North America Wiring any moving parts.
Appliance Rated Current AWG Disconnecting means must be provided and shall be located
6 18 within sight and readily accessible from the air conditioner.
6-10 16
10-16 14
16-25 12
25-32 10
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
3
38MURA: Service Manual
WIRING DIAGRAMS
Standard Models
PRESSURE
SENSOR
Condens er TEMP. Sens or
Ambient
TEMP.
Sensor
T3 T4 TP
HEATER
HEATER
SUCTION
Y/G TEMP. SENSOR 3
BROWN
BLUE
BLACK
SWITCH
CN60 CN7
4-WAY DC FAN
BLACK
POWER SUPPLY
BLUE
RED
U V W
INDOOR AND
OUTDOOR MODE
CN1 INPUT 230V AC
S1 S2 B W D
CN3/4/7 OUTPUT 230V AC R C Y1 Y2 L
DC FAN
CN28 OUTPUT 0~12V DC
U V W CN9/12/38 OUTPUT 0~5V DC CN6
COMPRESSOR
TO INDOOR UNIT
CN1A INPUT 230V AC
S1 OFF ON OUTDOOR UNIT
CN7 OUTPUT 0~310V AC ONLY MODE
INDOOR UNIT OUTDOOR UNIT
1 THROTTLING THROTTLING CN60 OUTPUT 230V AC
INDOOR AND OUTDOOR UNIT S1 S2 B W D
2 CN21 OUTPUT 0~5V DC
OUTDOOR MODE ONLY MODE R C Y1 Y2 L
CN15 OUTPUT 230V AC
3 NONE PRESSURE CN17 OUTPUT 230V AC CN6
COMPENSATION
4 NONE NONE CN50 OUTPUT 0~310V AC TO 24V THERMOSTAT
A221421
Fig. 1 — Wiring Diagram Size 18K
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
4
38MURA: Service Manual
PRESSURE
SENSOR
HEATER
HEATER
Y/G SUCTION
TEMP. SENSOR BLACK
BROWN
BLUE
BLACK
HQ CN11 CN3 CN4 CN7 CN9
LMG CGQ L-OUT N-OUT S YL
REFRIGERANT WHITE
TEMP. SENSOR 24V BOARD
CN16 CN19 CN8 6 CN28
CN17 CRANKCASE PAN CN2 CN7 EEV M
T.M.P_Sensor N-IN L-IN EEV
HEATER HEATER S ELECTRIC S1 ON
1 23 4
EXPANSIVE VALVE
ON~OFF
HIGH
CN38
PRESSURE GY CN6
MAIN BOARD SWITCH
CN1 L1 L2 S1S2 B W D
BLACK CN29 R C Y1Y2 L
CN27
RED CN28
U V W
Y/G Y/G INDOOR AND
OUTDOOR MODE
CN1 INPUT 230V AC
S1 S2 B W D
CN3/4/7 OUTPUT 230V AC
DC FAN R C Y1 Y2 L
CN28 OUTPUT 0∼12V DC
U V W CN6
COMPRESSOR CN9/11/38 OUTPUT 0∼5V DC
TO INDOOR UNIT
CN2/7/8 INPUT 230V AC
S1 OFF ON OUTDOOR UNIT
CN414 OUTPUT 0∼310V AC ONLY MODE
INDOOR UNIT OUTDOOR UNIT
1 THROTTLING THROTTLING CN60 OUTPUT 230V AC
INDOOR AND OUTDOOR UNIT CN17 OUTPUT 0∼5V DC S1 S2 B W D
2 OUTDOOR MODE ONLY MODE R C Y1 Y2 L
CN16 OUTPUT 230V AC
3 NONE PRESSURE CN19 OUTPUT 230V AC CN6
COMPENSATION
4 NONE NONE CN27/28/29 OUTPUT 0∼310V AC TO 24V THERMOSTAT
A221422
Fig. 2 — Wiring Diagram - Size 24K
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
5
38MURA: Service Manual
7 7 73
+352
/352
%/$&.
: )0
5('
&203 9 %/8(
<* 8 <*
<(//2: 5('
<(//2: 5('
%/$&.
: &1 &1 &1 &1
5('
9
%/8(
7KHHOHFWULFKHDWLQJ 8
EHOWRIFRPSUHVVRU 5(' 5(' &1
+($7 %/$&. 0$,1%2$5'
&1
:+,7( 5('
+($7 &1
%/$&.
&1
7KHHOHFWULFKHDWLQJ Y/G
EHOWRIFKDVVLV &1 &1
%/8( &1 &1
69 :$<
%/8( &7
127( )RXUZD\YDOYH
LVXVHGLQWKHFRROLQJ
DQGKHDWLQJXQLWRQO\PRGHV </
35(6685( 5(' %/$&. <(//2:
6(1625
68&7,21 +4 %/$&. &1
7(036(1625 &1
/0*
5()5,*(5$17 :+,7( &1 <(//2:
%/8(
7(036(1625 9%2$5' &1 <*
5('
((9 0 &1 &1
&1
6 6 % : '
6 21 5 & < < /
-; / /
21 2))~
,1 ' 2 25 $ 1 '
1RWHV 2 8 7' 22 50 2' ( 287'22581,7
This symbol indicates 21/<
the element is optional, 66 % : ' 02'( 66 % : '
the actual shape shall 5 & << / &1 5 & << /
&1
be prevail. 72,1'22581,7 7297+(50267$7
A221423
Fig. 3 — Wiring Diagram Sizes 30K-36K
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
6
38MURA: Service Manual
S1 OFF ON
1 Indoor Unit Throttling Outdoor Unit Throttling
2 Indoor and Outdoor Mode Outdoor Unit Only Mode
3 None Pressure Compensation
4 None None
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
7
38MURA: Service Manual
L1 L2
CN3 PRESSURE
CN2 RED YL
CN4 SENSOR
CN3 CN1
RED 3
CT1 CN9 6 EEV
CN28
IPM&PFC BOARD RED M
YELLOW 24V BOARD
BLACK CN2 CN21 CN7 S
W
BLUE/(BLACK) S1 ON
RED P7 CN4 N-OUT 1 23 4
V 10
BLUE CN9 CN6 BROWN/(RED)/(WHITE) ON~OFF
U P8 CN3 L-OUT
WVU MAIN CONTROL BOARD CN6 S1S2 B W D
COMP CN11 R C Y1Y2 L
LOW PRESSURE S1 S2 B W D
L-PRO R C Y1 Y2 L
SWITCH
SV REVERSING VALVE CN6
TP COMP. DISCHARGE TO 24V THERMOSTAT
TEMP. SENSOR
T3 COIL TEMP. SENSOR s1 OFF ON
INDOOR UNIT OUTDOOR UNIT
T4 OUTDOOR AMBIENT 1 THROTTLING THROTTLING
TEMP. SENSOR Notes: INDOOR AND OUTDOOR UNIT
2 OUTDOOR MODE ONLY MODE
HQ SUCTION TEMP. SENSOR This symbol indicates
LMG REFRIGERANT the element is optional, 3 NONE PRESSURE
TEMP. SENSOR the actual shape shall prevail COMPENSATION
COMP. TOP OLP 4 NONE NONE
COMP TOP TEMP. SENSOR
MAIN CONTROL BOARD IPM&PFC BOARD
A221424
Fig. 4 — Wiring Diagram Sizes 48K-60K
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
8
38MURA: Service Manual
PRESSURE
SENSOR
HEATER
HEATER
Y/G SUCTION
TEMP. SENSOR BLACK
BROWN
BLUE
BLACK
HQ CN11 CN3 CN4 CN7 CN9
LMG CGQ L-OUT N-OUT S YL
REFRIGERANT WHITE
TEMP. SENSOR 24V BOARD
CN16 CN19 CN8 6 CN28
CN17 CRANKCASE PAN CN2 CN7 EEV M
T.M.P_Sensor N-IN L-IN EEV
HEATER HEATER S ELECTRIC S1 ON
1 23 4
EXPANSIVE VALVE
ON~OFF
HIGH
CN38
PRESSURE GY CN6
MAIN BOARD SWITCH
CN1 L1 L2 S1S2 B W D
BLACK CN29 R C Y1Y2 L
CN27
RED CN28
U V W
Y/G Y/G INDOOR AND
OUTDOOR MODE
CN1 INPUT 230V AC
S1 S2 B W D
CN3/4/7 OUTPUT 230V AC
DC FAN R C Y1 Y2 L
CN28 OUTPUT 0∼12V DC
U V W CN6
COMPRESSOR CN9/11/38 OUTPUT 0∼5V DC
TO INDOOR UNIT
CN2/7/8 INPUT 230V AC
S1 OFF ON OUTDOOR UNIT
CN414 OUTPUT 0∼310V AC ONLY MODE
INDOOR UNIT OUTDOOR UNIT
1 THROTTLING THROTTLING CN60 OUTPUT 230V AC
INDOOR AND OUTDOOR UNIT CN17 OUTPUT 0∼5V DC S1 S2 B W D
2 OUTDOOR MODE ONLY MODE R C Y1 Y2 L
CN16 OUTPUT 230V AC
3 NONE PRESSURE CN19 OUTPUT 230V AC CN6
COMPENSATION
4 NONE NONE CN27/28/29 OUTPUT 0∼310V AC TO 24V THERMOSTAT
A221425
Fig. 5 — Wiring Diagram Sizes 18K HH
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
9
38MURA: Service Manual
7 7 73
+352
/352
%/$&.
: )0
5('
&203 9 %/8(
<* 8 <*
<(//2: 5('
<(//2: 5('
%/$&.
: &1 &1 &1 &1
5('
9
%/8(
7KHHOHFWULFKHDWLQJ 8
EHOWRIFRPSUHVVRU 5(' 5(' &1
+($7 %/$&. 0$,1%2$5'
&1
:+,7( 5('
+($7 &1
%/$&.
&1
7KHHOHFWULFKHDWLQJ Y/G
EHOWRIFKDVVLV &1 &1
%/8( &1 &1
69 :$<
%/8( &7
127( )RXUZD\YDOYH
LVXVHGLQWKHFRROLQJ
KHDWLQJXQLWRQO\ </
35(6685( 5(' %/$&. <(//2:
6(1625
68&7,21 +4 %/$&. &1
7(036(1625 &1
/0*
5()5,*(5$17 :+,7( &1 <(//2:
%/8(
7(036(1625 9%2$5' &1 <*
5('
((9 0 &1 &1
&1
6 6 % : '
6 21 5 & < < /
-; / /
21 2))~
,1 ' 2 25 $ 1 '
1RWHV 2 8 7' 22 50 2' ( 287'22581,7
This symbol indicates 21/<
the element is optional, 66 % : ' 02'( 66 % : '
the actual shape shall 5 & << / &1 5 & << /
&1
prevail. 72,1'22581,7 7297+(50267$7
A221426
Fig. 6 — Wiring Diagram Sizes 24K - 30K HH
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
10
38MURA: Service Manual
S1 OFF ON
1 Indoor Unit Throttling Outdoor Unit Throttling
2 Indoor and Outdoor Mode Outdoor Unit Only Mode
3 None Pressure Compensation
4 None None
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
11
38MURA: Service Manual
L1 L2
CN3 PRESSURE
CN2 RED YL
CN4 SENSOR
CN3 CN1
RED 3
CT1 CN9 6 EEV
CN28
IPM&PFC BOARD RED M
YELLOW 24V BOARD
BLACK CN2 CN21 CN7 S
W
BLUE/(BLACK) S1 ON
RED P7 CN4 N-OUT 1 23 4
V 10
BLUE CN9 CN6 BROWN/(RED)/(WHITE) ON~OFF
U P8 CN3 L-OUT
WVU MAIN CONTROL BOARD CN6 S1S2 B W D
COMP CN11 R C Y1Y2 L
R C Y1 Y2 L
CN6
TO 24V THERMOSTAT
s1 OFF ON
Notes: INDOOR UNIT OUTDOOR UNIT
1 THROTTLING THROTTLING
This symbol indicates
the element is optional, 2 INDOOR AND OUTDOOR UNIT
OUTDOOR MODE ONLY MODE
the actual shape shall prevail PRESSURE
3 NONE
COMPENSATION
MAIN CONTROL BOARD 4 NONE NONE
24V BOARD
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
12
38MURA: Service Manual
L1 L2
CN3 PRESSURE
CN2 RED YL
CN4 SENSOR
CN3 CN1
RED 3
CT1 CN9 6 EEV
CN28
IPM&PFC BOARD RED M
YELLOW 24V BOARD
BLACK CN2 CN21 CN7 S
W
BLUE/(BLACK) S1 ON
RED P7 CN4 N-OUT 1 23 4
V 10
BLUE CN9 CN6 BROWN/(RED)/(WHITE) ON~OFF
U P8 CN3 L-OUT
WVU MAIN CONTROL BOARD CN6 S1S2 B W D
COMP CN11 R C Y1Y2 L
R C Y1 Y2 L
CN6
TO 24V THERMOSTAT
CODE PART NAME s1 OFF ON
Notes: COMP COMPRESSOR INDOOR UNIT OUTDOOR UNIT
AC CURRENT 1 THROTTLING THROTTLING
This symbol indicates CT1
DETECTOR 2 INDOOR AND OUTDOOR UNIT
the element is optional, ELECTRONIC OUTDOOR MODE ONLY MODE
EEV
the actual shape shall prevail EXPANSION VALVE PRESSURE
DCFAN1 3 NONE
OUTDOOR DC COMPENSATION
DCFAN2 FAN MOTOR 4 NONE NONE
HEAT_D CHASSIS HEATER
HEAT_Y CRANKCASE HEATER MAIN CONTROL BOARD
H-PRO HIGH PRESSURE
SWITCH
L-PRO LOW PRESSURE CN1~CN3 Input:230VAC High voltage
SWITCH
P5 P6 Connection to the earth
SV REVERSING VALVE
P8~P7 Output:230VAC High voltage to 24V BOARD
TP COMP. DISCHARGE
TEMP. SENSOR CN21 Output:Pin1(Connection of the high voltage)”S”
T3 COIL TEMP. SENSOR CN17~CN18 Output:230VAC High voltage----REVERSING VALVE
T4 OUTDOOR AMBIENT CN24~CN25 Output:230VAC High voltage----CRANKCASE HEATER
TEMP. SENSOR CN19~CN20 Output:230VAC High voltage----CHASSIS HEATER
HQ SUCTION TEMP. SENSOR
CN8 Input:Pin1(0-5VDC),Pin2(5VDC)
LMG REFRIGERANT
TEMP. SENSOR CN9 Input:Pin3 Pin4(5VDC),Pin2(0VDC),Pin1 Pin5(0-5VDC)
COMP. TOP OLP CN6 Communication:Pin1-Pin6 Pulse waveform(0-5VDC),Pin7,
COMP TOP TEMP. SENSOR Pin9(0VDC),Pin8(0-5VDC),Pin10(5VDC)--to IPM&PFC BOARD
CN2~CN4 Output:230VAC High voltage to IPM&PFC BOARD
CN10 Input:Pin2 Pin4(0VDC),Pin1 Pin3(0-5VDC)--H/L Pressure switch
CN14 Input:Pin1(5VDC),Pin2(0-5VDC)--COMP. TOP OLP TEMP.SENSOR
CN23 Output:Pin1-Pin4 Pulse waveform(0-12VDC),
Pin5 Pin6(12VDC) to EEV
IPM&PFC BOARD
24V BOARD
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
13
38MURA: Service Manual
A230068
Fig. 9 —Refrigerant Cycle Diagram (Size 18K)
Accumulator
A230069
Fig. 10 — Refrigerant Cycle Diagram (Sizes 24K and 30K)
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
14
38MURA: Service Manual
A230070
Fig. 11 —Refrigerant Cycle Diagram (Sizes 36K and 48K)
A230071
Fig. 12 —Refrigerant Cycle Diagram (Size 60K)
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
15
38MURA: Service Manual
REFRIGERANT LINES
General Refrigerant Line Sizing
1. The outdoor units are shipped with a full charge of R410A refrigerant. All charges, line sizing, and capacities are based on runs of 25ft. (7.6 m).
For runs over 25 ft. (7.6 m), consult the long-line applications section for the proper charge adjustments.
2. The minimum refrigerant line length between the indoor and outdoor units is 10 ft. (3 m).
3. Refrigerant lines should not be buried in the ground. If it is necessary to bury the lines, not more than 36 in (914 mm) should be buried. Provide a
minimum 6in (152 mm) vertical rise to the service valves to prevent refrigerant migration.
4. Suction line must be insulated. Use a minimum of 1/2in. (12.7 mm) thick insulation. Closed-cell insulation is recommended in all long-line
applications.
5. Special consideration should be given to isolating interconnecting tubing from the building structure. Isolate the tubing so vibration or noise is not
transmitted into the structure.
• ǂ The charge amount listed in Table 5 is for piping runs up to 25 ft. (7.6 m).
• For piping runs longer than 25 ft. (7.6 m), add the refrigerant up to the allowable length as specified in Table 5.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
16
38MURA: Service Manual
CAUTION The deep vacuum method requires a vacuum pump capable of pulling a
vacuum of 500 microns and a vacuum gage capable of accurately measuring
the vacuum depth. The deep vacuum method is the most effective way of
UNIT DAMAGE HAZARD assuring a system is free of air and liquid water (see Fig. 15).
Failure to follow this caution may result in equipment damage
or improper operation.
5000
Never use the system compressor as a vacuum pump. 4500
4000
3500 LEAK IN
Refrigerant tubes and indoor coil should be evacuated using the
MICRONS
SYSTEM
recommended deep vacuum method of 500 microns. Always break a 3000
vacuum with dry nitrogen. 2500
System Vacuum and Charge 2000
1500 VACUUM TIGHT
Using Vacuum Pump TOO WET
1000
1. Completely tighten all flare nuts and connect the manifold gage 500
TIGHT
DRY SYSTEM
charge hose to a charge port of the low side service valve (see Fig.
13). 0 1 2 3 4 5 6 7
2. Connect the charge hose to the vacuum pump. MINUTES
A230074
3. Fully open the low side of the manifold gage (see Fig.14).
Fig. 15 — Deep Vacuum Graph
4. Start the vacuum pump.
5. Evacuate using the triple evacuation method. Triple Evacuation Method
6. After evacuation is complete, fully close the low side of the Proceed as follows (see Fig. 16).
manifold gage and stop the vacuum pump operation.
7. The factory charge contained in the outdoor unit is good for up to 25 1. Pump the system down to 500 MICRONS of mercury and allow the
ft. (8 m) of line length. For refrigerant lines longer than 25 ft. (8 m), pump to continue operating for an additional 15 minutes.
add refrigerant as specified in Table 5 on page 16. 2. Close the service valves and shut off the vacuum pump.
8. Disconnect charge hose from charge connection of the low side 3. Connect a nitrogen cylinder and regulator to the system and open
service valve. until the system pressure is 2 psig.
9. Fully open service valves B and A. 4. Close the service valve and allow the system to stand for 10 minutes.
10. Securely tighten caps of service valves. During this time, dry nitrogen will be allowed to diffuse throughout
the system absorbing moisture.
5. Repeat this procedure as indicated in Fig. 16. The system is now free
Outdoor Unit Refrigerant Indoor Unit of any contaminants and water vapor.
A Low Side C
D EVACUATE
B High Side
BREAK VACUUM WITH DRY NITROGEN
Service Valve
WAIT
A230072
Fig. 13 — Service Valve EVACUATE
EVACUATE
500 microns CHECK FOR TIGHT, DRY SYSTEM
Low side valve High side valve (IF IT HOLDS DEEP VACUUM)
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
17
38MURA: Service Manual
Less than a 1 minute delay for the initial start-up and a 3 minute delay for
10.8°F (6.0°C)
all subsequent starts. a (H-L)*0.75+L
Compressor high temperature cutout 9°F (5.0°C)
b (H-L)*0.5+L
The unit stops working when the compressor high temperature cutout 7.2°F (4.0°C)
opens, and restarts after the compressor high temperature cutout closes. c (H-L)*0.25+L
4.5°F (2.5°C)
Compressor discharge temperature protection L
d
Compressor discharge temp. T5>239°F(115°C) for 5s, compressor stops. 1.8°F (1.0°C)
e
Fan speed is out of control A230076
When the indoor fan speed is too low (300RPM) or too high (1500RPM) Fig. 17 — AUTO FAN Mode
for a certain time, the unit stops and the LED displays the failure. COOLING Mode
Inverter module protection Compressor Running Rules:
The inverter module has a protection function for current, voltage and • When T1-Ts < -4°F (-2°C), the compressor stops.
temperature. If any of these protections engage, the corresponding code • When T1-Ts > -1°F (-0.5°C), the compressor activates.
displays on the indoor unit and the unit stops working. • When the AC runs in the mute mode, the compressor runs with low
Indoor fan delayed open function frequency.
• When the current is more than setting value, the current protection
When the unit starts up, the louver is active immediately and the indoor function activates, and the compressor stops.
fan opens 10s later. If the unit is running in the HEATING mode, the
indoor fan is also controlled by the anti-cold wind function. Outdoor Fan Running Rules:
Compressor preheating functions The outdoor unit runs at a different fan speed according to T4. For
different outdoor units, the fan speeds differ.
Preheat parameters: When the T4 (outdoor ambient temperature)
<37.4°F (3°C), preheat function is activated.
Zero crossing detection error protection T4
If the AC detects the time interval is not correct for a continuous 240s, the A ADD
D
DD
DC_FAN_HI_SPD_ADD
82.4°F (28°C)
unit stops and the LED displays the failure. The correct zero crossing
signal time interval should be between 6-13ms. 78.8°F (26°C)
This function is only active in the COOLING mode. The function helps 66.2°F (19°C)
prevent the compressor from being damaged by a refrigerant leak or a 62.6°F (17°C)
compressor overload. E SPD_A
ADD
D
DC_FAN_SSLOW_SPD_ADD
Open condition:
A230077
When the compressor is active, the evaporator T2 coil temperature value
has no or very little change.
Fig. 18 — Outdoor Fan Running Rules
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
18
38MURA: Service Manual
C H - (H- =H-G)
A230080
Fig. 21 —Compressor Temperature Protection
M + (M+=M+Z)
8.1°F (4.5°C) • Off: Compressor stops
D
5.4°F (3.0°C) M (M=M) • Decrease: Decrease the running frequency to the lower level
M E • Hold: Keep the current frequency
2.7°F(1.5°C)
• Resume: No limitation for frequency
M - (M- =M-Z)
F When the condenser temperature is higher than the setting value, the
compressor stops.
8.1°F (4.5°C)
L + (L+=L+D)
Evaporator Temperature Protection
G When the evaporator temperature is lower than the setting value the
L 5.4°F (3.0°C) L (L=L)
compressor stops.
H
54.4°F (13°C)
B
53.6°F (12°C) DC_FAN_MID_SPD_ADD
A
50°F (10°C) DC_FAN_HI_SPD_ADD
A230081
Fig. 22 — Outdoor Fan Running Rules
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
19
38MURA: Service Manual
-7.2°F(-4.0°C)
Setting Fan T1-Td+34.7°F (1.5 °C) Actual Fan (H+-L)*0.8+L
-9°F(-5.0°C)
Speed Speed
-10.8°F(-6.0°C) H+
-11.7°F(-6.5°C)
-2.7°F(-1.5°C) H - (H-=H-G)
H -5.4°F (-3.0°C)
H (=H)
-8.1°F(-4.5°C)
H + (H+ =H+G)
A230083
Fig. 24 — Auto Fan Action in HEATING Mode
-2.7°F(-1.5°C) M - (M-=M-Z)
M -5.4°F (-3.0°C)
M (M=M)
-8.1°F(-4.5°C)
M + (M+ =M+Z)
-2.7°F(-1.5°C) L - (L-=L-D)
L
-5.4°F (-3.0°C)
L (L=L)
-8.1°F(-4.5°C)
L + (L+ =L+D)
A230082
Fig. 23 — Indoor Fan Running Rules
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
20
38MURA: Service Manual
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
21
38MURA: Service Manual
INFORMATION INQUIRY
To enter the engineer mode, in power-on or standby mode, and in non-locked state using hand held remote,
1. Press the key combination On/Off + Fan for 7 seconds:
2. After entering the engineer mode, the remote control displays the following icons “Auto, Cool, Dry, Heat”, plus the battery icon; at the same
time, it also displays the numeric code of the current engineer mode (for the initial engineer mode, the numeric code displayed is 0), and all other
icons are inactive. In engineer mode, the value of the current numeric code can be adjusted circularly through the Up/Down key, with the setting
range of 0 to 30. Each time the current numeric code is adjusted, the special code of the engineer mode is transmitted with a delay of 0.6s. The
code can also be transmitted by pressing “OK”, and the special code of the engineer mode sent contains information of the currently displayed
numeric code (if the numeric code is 0, the code to enter the engineer mode is transmitted). In engineer mode, other keys or operations are invalid
except for the On/Off key, the Up/Down key, the OK key or executing the operation to exit the engineer mode.
Table 7 — Inquiry Information
Inquiry Information (Sheet 1 of 2)
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
22
38MURA: Service Manual
In the channel 1~30 settings of the engineer mode, press the On/Off key to return the previous engineer mode.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
23
38MURA: Service Manual
GENERAL TROUBLESHOOTING
Table 8 — Error Display
DISPLAY MALFUNCTION OR PROTECTION PAGE #
EC 51 Outdoor EEPROM malfunction 25
EL 01 Indoor / outdoor units communication error 26
EL 16 Communication malfunction between adapter board and outdoor main board 49
PC 00 IPM module protection 32
PC 02 Top temperature protection of compressor or High temperature protection of IPM module 34
PC 06 Temperature protection of compressor discharge 37
PC 08 Outdoor overcurrent protection 38
PC 0A High temperature protection of condenser 44
PC 0F PFC module protection 45
PC 10 Outdoor unit low AC voltage protection 33
PC 11 Outdoor unit main control board DC bus high voltage protection --
PC 12 Outdoor unit main control board DC bus high voltage protection /341 MCE error 33
PC 30 High pressure protection 39
PC 31 Low pressure protection 35
PC 40 Communication malfunction between IPM board and outdoor main board 40
PC 41 Outdoor compressor current sampling circuit failure 41
PC 43 Outdoor compressor lack phase protection 42
PC 44 Outdoor unit zero speed protection 38
PC 45 Outdoor unit IR chip drive failure 43
PC 46 Compressor speed has been out of control 38
PC 49 Compressor overcurrent failure 38
EC 52 Condenser coil temperature sensor T3 is in open circuit or has short circuited 29
EC 53 Outdoor room temperature sensor T4 is in open circuit or has short circuited 29
EC 54 Compressor discharge temperature sensor TP is in open circuit or has short circuited 29
EC 57 Refrigerant pipe temperature sensor error 29
EC 5C High pressure sensor is in open circuit or has short circuited 29
EC 71 Over current failure of outdoor DC fan motor 27
EC 72 Lack phase failure of outdoor DC fan motor 47
EC 73 Zero-speed failure of outdoor DC fan motor --
EC 07 Outdoor fan speed has been out of control 27
PC 0L Low ambient temperature protection 43
LC 06 High temperature protection of IPM module 34
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
24
38MURA: Service Manual
Troubleshooting
Is it still displaying
NO The unit is operating normally.
the error code?
YES
A230085
Remarks:
EEPROM: A read-only memory whose contents can be erased and reprogrammed using a pulsed voltage. The location of the EEPROM chip on the
indoor and outdoor PCB is shown in Figures 25 and 26.
A230086
Fig. 25 —EEPROM Chip
A230087
Fig. 26 —EEPROM Chip
NOTE: For certain models, the outdoor PCB can not be removed separately. In this case, the outdoor electric control box should be replaced
as a whole. This figures (pictures) are only for reference, actual appearance may vary. Troubleshooting and repair of the compressor
driven chip EEPROM parameter error and communication error between outdoor main chip and compressor driven chip are the
same as EC 51.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
25
38MURA: Service Manual
Troubleshooting
XYE Communication:
Yes
No
Yes
Yes
Check whether the signal wire is broken. Yes Replace the signal wire.
No
Yes
No
A230088
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
26
38MURA: Service Manual
YES
Does it turn easily? NO Find the cause of the problem and resolve.
YES
YES
YES
A230092
NOTE: For certain models, the outdoor PCB cannot be removed separately. In this case, the outdoor electric control box should be replaced
as a whole.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
27
38MURA: Service Manual
A230094
Fig. 27 — Outdoor DC Fan Motor
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
28
38MURA: Service Manual
YES
Measure the resistance value
of the sensor.
Is it within acceptable
NO Replace the sensor.
parameters?
YES
A230095
A230096
Fig. 28 —Test
NOTE: For certain models, outdoor PCB could not be removed separately. In this case, the outdoor electric control box should be replaced as
a whole. This picture and the value are only for reference, actual appearance and value may vary.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
29
38MURA: Service Manual
NO
Is T1 too close to
YES Install correctly
Check system for leaks. the evaporator?
NO NO
NO
A230097
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
30
38MURA: Service Manual
YES
Is the
water-level switch Insert the water-level
NO
inserted properly? switch properly
YES
YES
YES
A230098
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
31
38MURA: Service Manual
NO
YES
YES
YES
A230099
NOTE: For certain models, the outdoor PCB can not be removed separately. In this case, the outdoor electric control box should be replaced
as a whole.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
32
38MURA: Service Manual
YES
YES
YES
NO
A230100
NOTE: For certain models, the outdoor PCB cannot be removed separately. In this case, the outdoor electric control box should be replaced
as a whole.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
33
38MURA: Service Manual
No
Yes
Yes
Yes
Measure the resistance
Check if the refrigerant
between the OLP’s two ports. No Replace the OLP.
system is normal? Is it zero?
No
Yes Yes Replace the outdoor control PCB.
NO
A230101
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
34
38MURA: Service Manual
Are the low pressure protector and Reconnect the low pressure protector
the main control board No
and main control board
wired properly?
Yes
No
No
Is the valve core of the high Open the valve core of the high
No
pressure valve fully opened? pressure valve.
Yes
Refer to the solution to the malfunction
Is the indoor fan running of Fan Speed Out of Control. Find
No
properly in the COOLING mode? the cause and resolve the problem..
Yes
Is it in working order?
No
NOTE: For certain models, outdoor PCB cannot be removed separately. In this case, the outdoor electric control box should be replaced as a
whole.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
35
38MURA: Service Manual
NO
YES
YES
YES
NOTE: For certain models, the outdoor PCB cannot be removed separately. In this case, the outdoor electric control box should be replaced
as a whole.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
36
38MURA: Service Manual
Is the compressor
discharge temperature
higher than 239°F (115°C) (R410a)/ Yes Is refrigerant leaking? Yes Stop the leak and add refrigerant
226.4°F(108°C) (R32)?
No
No
Yes
Yes
YES
YES
Replace high pressure
valve assembly
A230104
NOTE: For certain models, the outdoor unit uses combination sensor, T3,T4 and TP are the same of sensor. The images within this document
and the values are for reference only. The actual appearance and values may vary.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
37
38MURA: Service Manual
Was
Was the
the protection
protectionactivated
activated
in
in standby?
standby?
No Yes
Yes
Yes
Is the voltage between L and N normal? No Are L and N wired Reconnect L and N
properly?
Yes
Is the input voltage of the No Is the bridge rectifier wired Reconnect the
bridge rectifier normal? properly? bridge rectifier
Yes
No
I Is the reactor or
inductance wiring properly No Reconnect the wiring
Is the outdoor unit Ensure that the outdoor unit
No wired?
ventilation functioning properly? ventilate is working properly
Yes Yes
Refer to the
"Fan Speed is Operating
Is the outdoor fan running properly? No A the reactor andd
Are Replace reactor
Outside of the Normal Range"
inductance functioning No
solution. or inductance
normally?
Yes
No
No
No
A230105
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
38
38MURA: Service Manual
Are the high pressure switch and Connect the high pressure switch
No
main control board wired correctly? and main control board
Yes
Yes
No
Yes
Is the outdoor fan running properly? No Refer to the “Fan Speed is Operating Outside
of Nornal Range” Solution.
Yes
No
No
A230106
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
39
38MURA: Service Manual
No
No
Yes
Reconnect and retry.
Is the error still displayed?
Yes
No
Replace IPM board.
Is the system running normally? Yes
No
No
A230107
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
40
38MURA: Service Manual
Is it still displaying
NO The unit is operating normally.
the error code?
YES
A230108
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
41
38MURA: Service Manual
Yes
Yes
Yes
Yes
Trouble is solved.
A230109
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
42
38MURA: Service Manual
Yes
A230110
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
43
38MURA: Service Manual
Is the
connection
Is the condenser temperature between temperature
No No Correct the connection
higher than 149°F (65°C)? sensor and PCB
in working
order?
Yes
Yes
Is the outdoor ambient temperature
higher than 122°F/129.2°F (50°C/54°C) Yes Stop the unit
(tropical models)? Is the resistance
condenser temperature
No Replace the temperature sensor
sensor resistance normal?
No
No
Yes
No
Yes
Replace the outdoor main board.
Has the problem been resolved?
No
No
A230111
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
44
38MURA: Service Manual
At first test the resistance between every two ports of U, V, W of IPM and P, N. If any result of them is 0 or close to 0, the IPM is
defective. Otherwise, follow the procedure in the flowchart.
Yes
No
No
Yes
A230112
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
45
38MURA: Service Manual
WŽǁĞƌŽī͕ƚŚĞŶƌĞƐƚĂƌƚƚŚĞƵŶŝƚϮ
Is the main board minutes later. Does the outdoor main
No
displaying an error? board display an error code a few
minutes later?
Yes
Yes
Refer to the prescribed
steps for resolving the issue
A230113
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
46
38MURA: Service Manual
Yes
Yes
Yes
Issue resolved.
A230114
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
47
38MURA: Service Manual
Is it still displaying
the error code?
Yes
No
Yes
No
No
A230115
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
48
38MURA: Service Manual
EL 16 (Communication malfunction between adapter board and outdoor main board Diagnosis and Solution)
Description: The adapter PCB cannot detect the main control board.
YES
YES
YES
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
49
38MURA: Service Manual
CHECK PROCEDURES
Temperature Sensor Check
WARNING
Be sure to turn off all power supplies or disconnect all wires
to avoid electric shock. Operate after compressor and coil
have returned to normal temperature in case of injury.
A230118
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
50
38MURA: Service Manual
Compressor Check
A230119
Fig. 30 — Compressor Check
A230120
Fig. 31 —Test
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
51
38MURA: Service Manual
WARNING
Electricity remains in capacitors even when the power supply
is off. Ensure the capacitors are fully discharged before
troubleshooting.
1. Turn off the outdoor unit and disconnect the power supply.
2. Discharge the electrolytic capacitors and ensure the entire energy-storage unit has been discharged.
3. Disassemble the outdoor PCB or disassemble the IPM board.
4. Measure the resistance value between P and U (V, W, N); U (V, W) and N.
A230121
Fig. 32 — Resistance Value
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
52
38MURA: Service Manual
DISASSEMBLY INSTRUCTIONS
Panel Plate Size 18K Standard Heat
Pr o ce d u r e Illu st r a t io n
Handle
Top Cover
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
53
38MURA: Service Manual
Pr o ce d u r e Illu st r a t io n
Front Panel
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
54
38MURA: Service Manual
Pr o ce d u r e Illu st r a t io n
Right Panel
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
55
38MURA: Service Manual
Outdoor Unit Sizes 18K High Heat and 24K Standard Heat
Pr o ce d u r e Illu st r a t io n
Handle
Top Cover
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
56
38MURA: Service Manual
Outdoor Unit Sizes 18K High Heat and 24K Standard Heat (CONT)
Pr o ce d u r e Illu st r a t io n
Front Panel
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
57
38MURA: Service Manual
Outdoor Unit Sizes 18K High Heat and 24K Standard Heat (CONT)
Pr o ce d u r e Illu st r a t io n
Right Panel
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
58
38MURA: Service Manual
Outdoor Unit Sizes 24K High Heat, 30K Standard and High Heat and 36K Standard Heat
Pr o ce d u r e Illu st r a t io n
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
59
38MURA: Service Manual
Outdoor Unit Sizes 24K High Heat, 30K Standard and High Heat and 36K Standard Heat (CONT)
Pr o ce d u r e Illu st r a t io n
Front Panel
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
60
38MURA: Service Manual
Outdoor Unit Sizes 24K High Heat, 30K Standard and High Heat and 36K Standard Heat (CONT)
Pr o ce d u r e Illu st r a t io n
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
61
38MURA: Service Manual
Outdoor Unit Sizes 24K High Heat, 30K Standard and High Heat and 36K Standard Heat (CONT)
Pr o ce d u r e Illu st r a t io n
Right Panel
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
62
38MURA: Service Manual
Outdoor Unit Sizes 36K High Heat, 48K Standard and High Heat and 60K Standard and High Heat
Pr o ce d u r e Illu st r a t io n
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
63
38MURA: Service Manual
Outdoor Unit Sizes 36K High Heat, 48K Standard and High Heat and 60K Standard and High Heat (CONT)
Pr o ce d u r e Illu st r a t io n
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
64
38MURA: Service Manual
Outdoor Unit Sizes 36K High Heat, 48K Standard and High Heat and 60K Standard and High Heat (CONT)
Pr o ce d u r e Illu st r a t io n
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
65
38MURA: Service Manual
WARNING
Anti-static gloves must be worn when you disassemble the
electronic box.
Model 18K Standard Heat
Pr o ce d u r e Illu st r a t io n
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
66
38MURA: Service Manual
Pr o ce d u r e Illu st r a t io n
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
67
38MURA: Service Manual
Models: 24K High Heat, 30K Standard and High Heat and 36K Standard Heat
Pr o ce d u r e Illu st r a t io n
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
68
38MURA: Service Manual
Models: 36K High Heat, 48K Standard and High Heat and 60K Standard and High Heat
Pr o ce d u r e Illu st r a t io n
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
69
38MURA: Service Manual
PCB Board 8
Pr o ce d u r e Illu st r a t io n
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
70
38MURA: Service Manual
Pr o ce d u r e Illu st r a t io n
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
71
38MURA: Service Manual
Pr o ce d u r e Illu st r a t io n
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
72
38MURA: Service Manual
Fan Assembly
Pr o ce d u r e Illu st r a t io n
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
73
38MURA: Service Manual
Pr o ce d u r e Illu st r a t io n
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
74
38MURA: Service Manual
Sound Blanket
Pr o ce d u r e Illu st r a t io n
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
75
38MURA: Service Manual
WARNING
Evacuate the system and confirm there is no refrigerant left in
the system before removing the four-way valve and the
compressor.
For R32 and R290, evacuate the system with the refrigerant
recovery equipment; flush the system with nitrogen, then
repeat the two steps before heating up the brazed parts. The
operations above should be implemented by professionals.
NOTE: Remove the panel plate, connection of four-way valve on PCB before disassembling sound blanket.
Pr o ce d u r e Illu st r a t io n
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
76
38MURA: Service Manual
Compressor
WARNING
Evacuate the system and confirm that there is no refrigerant left in the
system before removing the four-way valve and the compressor.
For R32 and R290, evacuate the system with the refrigerant recovery
equipment; flush the system with nitrogen; then repeat the two steps
before heating up the brazed parts. The operations above should be
implemented by professionals.
Pr o ce d u r e Illu st r a t io n
Terminal Cover
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
77
38MURA: Service Manual
Compressor (CONT)
Pr o ce d u r e Illu st r a t io n
Suction Pipe
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
78
38MURA: Service Manual
APPENDICIES
Appendix 1
Table 15 — Temperature Sensor Resistance Value Table for T1, T2, T3, T4 (°C--K)
°C °F K Ohm °C °F K Ohm °C °F K Ohm °C °F K Ohm
- 20 -4 115.266 20 68 12.6431 60 140 2.35774 100 212 0.62973
- 19 -2 108.146 21 70 12.0561 61 142 2.27249 101 214 0.61148
- 18 0 101.517 22 72 11.5 62 144 2.19073 102 216 0.59386
- 17 1 96.3423 23 73 10.9731 63 145 2.11241 103 217 0.57683
- 16 3 89.5865 24 75 10.4736 64 147 2.03732 104 219 0.56038
- 15 5 84.219 25 77 10 65 149 1.96532 105 221 0.54448
- 14 7 79.311 26 79 9.55074 66 151 1.89627 106 223 0.52912
- 13 9 74.536 27 81 9.12445 67 153 1.83003 107 225 0.51426
- 12 10 70.1698 28 82 8.71983 68 154 1.76647 108 226 0.49989
- 11 12 66.0898 29 84 8.33566 69 156 1.70547 109 228 0.486
- 10 14 62.2756 30 86 7.97078 70 158 1.64691 110 230 0.47256
-9 16 58.7079 31 88 7.62411 71 160 1.59068 111 232 0.45957
-8 18 56.3694 32 90 7.29464 72 162 1.53668 112 234 0.44699
-7 19 52.2438 33 91 6.98142 73 163 1.48481 113 235 0.43482
-6 21 49.3161 34 93 6.68355 74 165 1.43498 114 237 0.42304
-5 23 46.5725 35 95 6.40021 75 167 1.38703 115 239 0.41164
-4 25 44 36 97 6.13059 76 169 1.34105 116 241 0.4006
-3 27 41.5878 37 99 5.87359 77 171 1.29078 117 243 0.38991
-2 28 39.8239 38 100 5.62961 78 172 1.25423 118 244 0.37956
-1 30 37.1988 39 102 5.39689 79 174 1.2133 119 246 0.36954
0 32 35.2024 40 104 5.17519 80 176 1.17393 120 248 0.35982
1 34 33.3269 41 106 4.96392 81 178 1.13604 121 250 0.35042
2 36 31.5635 42 108 4.76253 82 180 1.09958 122 252 0.3413
3 37 29.9058 43 109 4.5705 83 181 1.06448 123 253 0.33246
4 39 28.3459 44 111 4.38736 84 183 1.03069 124 255 0.3239
5 41 26.8778 45 113 4.21263 85 185 0.99815 125 257 0.31559
6 43 25.4954 46 115 4.04589 86 187 0.96681 126 259 0.30754
7 45 24.1932 47 117 3.88673 87 189 0.93662 127 261 0.29974
8 46 22.5662 48 118 3.73476 88 190 0.90753 128 262 0.29216
9 48 21.8094 49 120 3.58962 89 192 0.8795 129 264 0.28482
10 50 20.7184 50 122 3.45097 90 194 0.85248 130 266 0.2777
11 52 19.6891 51 124 3.31847 91 196 0.82643 131 268 0.27078
12 54 18.7177 52 126 3.19183 92 198 0.80132 132 270 0.26408
13 55 17.8005 53 127 3.07075 93 199 0.77709 133 271 0.25757
14 57 16.9341 54 129 2.95896 94 201 0.75373 134 273 0.25125
15 59 16.1156 55 131 2.84421 95 203 0.73119 135 275 0.24512
16 61 15.3418 56 133 2.73823 96 205 0.70944 136 277 0.23916
17 63 14.6181 57 135 2.63682 97 207 0.68844 137 279 0.23338
18 64 13.918 58 136 2.53973 98 208 0.66818 138 280 0.22776
19 66 13.2631 59 138 2.44677 99 210 0.64862 139 282 0.22231
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
79
38MURA: Service Manual
Appendix 2
Table 16 — Temperature Sensor Resistance Value Table for T5 (° C- -K)
°C °F K Ohm °C °F K Ohm °C °F K Ohm °C °F K Ohm
-20 -4 542.7 20 68 68.66 60 140 13.59 100 212 3.702
-19 -2 511.9 21 70 65.62 61 142 13.11 101 214 3.595
-18 0 483 22 72 62.73 62 144 12.65 102 216 3.492
-17 1 455.9 23 73 59.98 63 145 12.21 103 217 3.392
-16 3 430.5 24 75 57.37 64 147 11.79 104 219 3.296
-15 5 406.7 25 77 54.89 65 149 11.38 105 221 3.203
-14 7 384.3 26 79 52.53 66 151 10.99 106 223 3.113
-13 9 363.3 27 81 50.28 67 153 10.61 107 225 3.025
-12 10 343.6 28 82 48.14 68 154 10.25 108 226 2.941
-11 12 325.1 29 84 46.11 69 156 9.902 109 228 2.86
-10 14 307.7 30 86 44.17 70 158 9.569 110 230 2.781
-9 16 291.3 31 88 42.33 71 160 9.248 111 232 2.704
-8 18 275.9 32 90 40.57 72 162 8.94 112 234 2.63
-7 19 261.4 33 91 38.89 73 163 8.643 113 235 2.559
-6 21 247.8 34 93 37.3 74 165 8.358 114 237 2.489
-5 23 234.9 35 95 35.78 75 167 8.084 115 239 2.422
-4 25 222.8 36 97 34.32 76 169 7.82 116 241 2.357
-3 27 211.4 37 99 32.94 77 171 7.566 117 243 2.294
-2 28 200.7 38 100 31.62 78 172 7.321 118 244 2.233
-1 30 190.5 39 102 30.36 79 174 7.086 119 246 2.174
0 32 180.9 40 104 29.15 80 176 6.859 120 248 2.117
1 34 171.9 41 106 28 81 178 6.641 121 250 2.061
2 36 163.3 42 108 26.9 82 180 6.43 122 252 2.007
3 37 155.2 43 109 25.86 83 181 6.228 123 253 1.955
4 39 147.6 44 111 24.85 84 183 6.033 124 255 1.905
5 41 140.4 45 113 23.89 85 185 5.844 125 257 1.856
6 43 133.5 46 115 22.89 86 187 5.663 126 259 1.808
7 45 127.1 47 117 22.1 87 189 5.488 127 261 1.762
8 46 121 48 118 21.26 88 190 5.32 128 262 1.717
9 48 115.2 49 120 20.46 89 192 5.157 129 264 1.674
10 50 109.8 50 122 19.69 90 194 5 130 266 1.632
11 52 104.6 51 124 18.96 91 196 4.849
12 54 99.69 52 126 18.26 92 198 4.703
13 55 95.05 53 127 17.58 93 199 4.562
14 57 90.66 54 129 16.94 94 201 4.426
15 59 86.49 55 131 16.32 95 203 4.294
16 61 82.54 56 133 15.73 96 205 4.167
17 63 78.79 57 135 15.16 97 207 4.045
18 64 75.24 58 136 14.62 98 208 3.927
19 66 71.86 59 138 14.09 99 210 3.812
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
80
38MURA: Service Manual
Appendix 3
Table 17 — Degree Temperature Unit Reference C-F
°C °F °C °F °C °F °C °F °C °F
-5 23 21 69.8 51 123.8 82 179.6 113 235.4
-4 24.8 22 71.6 52 125.6 83 181.4 114 237.2
-3 26.6 23 73.4 53 127.4 84 183.2 115 239
-2 28.4 24 75.2 54 129.2 85 185 116 240.8
-1 30.2 25 77 55 131 86 186.8 117 242.6
0 32 25.5 77.9 56 132.8 87 188.6 118 244.4
0.5 32.9 26 78.8 57 134.6 88 190.4 119 246.2
1 33.8 27 80.6 58 136.4 89 192.2 120 248
1.5 34.7 28 82.4 59 138.2 90 194 121 249.8
2 35.6 29 84.2 60 140 91 195.8 122 251.6
2.5 36.5 30 86 61 141.8 92 197.6 123 253.4
3 37.4 31 87.8 62 143.6 93 199.4 124 255.2
3.5 38.3 32 89.6 63 145.4 94 201.2 125 257
4 39.2 33 91.4 64 147.2 95 203 126 258.8
4.5 40.1 34 93.2 65 149 96 204.8 127 260.6
5 41 35 95 66 150.8 97 206.6 128 262.4
6 42.8 36 96.8 67 152.6 98 208.4 129 264.2
7 44.6 37 98.6 68 154.4 99 210.2 130 266
8 46.4 38 100.4 69 156.2 100 212 131 267.8
9 48.2 39 102.2 70 158 101 213.8 132 269.6
10 50 40 104 71 159.8 102 215.6 133 271.4
11 51.8 41 105.8 72 161.6 103 217.4 134 273.2
12 53.6 42 107.6 73 163.4 104 219.2 135 275
13 55.4 43 109.4 74 165.2 105 221 136 276.8
14 57.2 44 111.2 75 167 106 222.8 137 278.6
15 59 45 113 76 168.8 107 224.6 138 280.4
16 60.8 46 114.8 77 170.6 108 226.4 139 282.2
17 62.6 47 116.6 78 172.4 109 228.2 140 284
18 64.4 48 118.4 79 174.2 110 230 141 285.8
19 66.2 49 120.2 80 176 111 231.8 142 287.6
20 68 50 122 81 177.8 112 233.6 143 289.4
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
81
38MURA: Service Manual
© 2023 Carrier. All rights reserved. Edition Date: 04/23 Catalog No: SG-38MURA-02
Replaces: SG-38MURA-01
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
82