Files Schnaider 1
Files Schnaider 1
Files Schnaider 1
Active
Catalog 2023
Cubicles up to 4000 A
Version 14
se.com
Table of Contents
Index Index Of Commercial References
p. A-2 > p. A-2
DD383737.eps
DD383738.eps
p. E-1
DD119392.ai
Dd383794.eps
DD119391.ai
p. F-1
DD119393.ai
DD384603.eps
p. G-1
Main distribution
Functionnal > p. H-4
partitioning
Dd384532.eps
p. H-1
Spare parts Electrical characteristics
Additional > p. I-4 > p. I-11
information
p. I-1
Practical information Maintenance
> p. J-2 > p. J-18
After sales tools
p. J-1
II Version : 14 - 15/12/2023
160E0500
PrismaSeT P Active
Index
p. A-2 A
PrismaSeT G enclousers
> p. B-14 Overview
p. B-1 B
Thermal characteristics Specific application
of switchboards > p. C-9 > p. C-17 Standards and
certifications
p. C-1 C
Selection guide
p. D-1 D
TransferPacT Fusegear Fusegear/Switch-disconnector Others
> p. E-54 > p. E-58 > p. E-59 > p. E-61
Functional units
DD439632_TR.eps
DD385570.eps
Dd383777.eps
DD119396.ai
SI
50Hz
60Hz 230
400
240
415
SII
250
U
t
6 3
10
84
4 2 (
2
3
5
12 14
6 7 16
) 10
5 10
8
9 18
20
20
30
TA25D4S250
Ie: 250A
AC-33B
Icw:
GB/T14048.11
4TPE
Ue: AC380-440V
IEC/EN
No. 220403010002
50/60Hz
10kA/0.5s,15kA/
60947-6-1
0.1s
Autom
atic
p. E-1 E
440 1 60
f 5s 220 (N
A)
0 (s)
5 10
0s 380 3 20
G
t Off Ue(V) 2 30
t
N)1 60
Mode SII (A 0 (min)
SI
N Non
Prio.
Auto Return
Return
Others
> p. F-23
Cubicles
DD119392.ai
p. F-1 F
Secondary distribution Terminal blocks and lines
> p. G-20 > p. G-35 Linergy distribution
systems
DD119394.ai
DD119395.ai
p. G-1 G
Functional partitioning
p. H-1 H
Additional information
p. I-1 I
Version : 14 - 15/12/2023
160E0500
III
PrismaSeT P Active - Index www.se.com
32610
300mm²
Compact NSX 400 to 630, 48 to E-51
A9XAH157 Acti 9 comb busbar AUX1P 100A
57 modules
G-29 A
415VAC 50/60Hz
A9XAH257 Acti 9 comb busbar aux2P 100A G-29
32611 Base plate with mechanical and E-51 57 modules
electrical interlocking
A9XAH357 Acti 9 comb busbar aux3P 100A G-29
33••• 57 modules
A9XAH457 Comb busbar aux4P 100A G-29
33596 3P arc chute insulating screen E-15, E-17,
57mod.
E-19
A9XAH557 Comb busbar aux5P 100A G-29
33597 4P arc chute insulating screen E-15, E-17,
57mod.
E-19
A9XAH657 Comb busbar aux3P repart. 100A G-29
33628 Terminal shield 3P E-49
57mod.
33629 Kit 3P vertical connection E-49
A9XPCD04 Acti 9 set of 4 connectors G-29, G-30
adapters
A9XPCM04 Acti 9 set of 4 connectors G-29, G-30
33642 3P cable lug adapter kit E-10, E-13,
E-15, E-19, A9XPE110 Acti 9 set of 10 end caps 1P G-29
I-47, I-48
A9XPE210 Acti 9 set of 10 end caps 2P G-29
33644 Interlocking kit for 2 breakers I-47, I-48
with rot A9XPE310 Acti 9 set of 10 end caps 3P G-29
33643 4P cable lug adapter kit E-10, E-15, A9XPE410 Acti 9 set of 10 end caps 4P G-29
E-19, I-47,
A9XPH106 Acti 9 comb busbar 1P 100A 6 G-29
I-48
modules
33645 Connection 3P for NS1600/3200A I-47, I-48
A9XPH112 Acti 9 comb busbar 1P 100A 12 G-29
33644 Interlocking kit for 2 breakers E-10, E-13, modules
with rot E-15, E-19,
A9XPH124 Acti 9 comb busbar 1P 100A 24 G-29
E-39
modules
33645 Connection 3P for NS1600/3200A E-10, E-15,
A9XPH157 Acti 9 comb busbar 1P 100A 57 G-29
E-19, E-39
modules
33890 Connection 4P for NS1600/3200A E-49
A9XPH212 Acti 9 comb busbar 2P 100A 12 G-29
33975 ComPacT NS1600/NS2500, 3 E-14, E-39 modules
poles, fixed, 1600A/2500A
A9XPH224 Acti 9 comb busbar 2P 100A 24 G-29
33976 ComPacT NS1600/NS2500, 4 E-14, E-39 modules
poles, fixed, 1600A/2500A
A9XPH257 Acti 9 comb busbar 2P 100A 57 G-29
modules
47•••
A9XPH312 Acti 9 comb busbar 3P 100A 12 G-29
47335 Arc chute insulating screen for E-10, E-11, modules
3P fixed E-13
A9XPH324 Acti 9 comb busbar 3P 100A 24 G-29
47336 Arc chute insulating screen for E-10, E-11 modules
4P fixed
A9XPH357 Acti9 - comb busbar - 3L - 18 mm G-29
49860 Distribution connectors, FuPacT E-59
ISFT100, 3x16mm² A9XPH412 Acti9 comb busbar 4P 100a 12 G-29
modules
49861 ISFT 100 3P feeding busbar for 2 E-59
switche A9XPH424 Acti9 comb busbar 4P 100a 24 G-29
modules
49862 ISFT 100 3P feeding busbar for 3 E-59
switche A9XPH457 Acti9 comb busbar 4P 100a 57 G-29
modules
49863 ISFT 100 3P feeding busbar for 4 E-59
switche A9XPH512 Acti9 comb busbar 4P repart. G-29
100a 12 m
49865 ISFT 100 3P feeding clamp for E-59
feeding bu A9XPH518 Acti9 comb busbar 4P repart. G-29
100a 18 m
A••• A9XPH524 Acti9 comb busbar 4P repart. G-29
A9N21035 Comb busbar 1P-n 63a 56mod. G-32 100a 24 m
A9N21036 Comb busbar 3P-n repart. 63a G-32 A9XPH557 Acti9 comb busbar 4P repart. G-29
56mod. 100a 57 m
A9N21037 Comb busbar 1P-n Vigi 63a G-32 A9XPM212 Comb busbar 2P 100A 12mod. G-30
56mod.
A9XPM412 #N/A G-30
A9N21038 Comb busbar 3P-n Vigi repart. G-32
A9XPM512 Comb busbar 4P repart. 100A G-30
63a 56mod.
12mod.
A9N21039 Set of 20 end caps 1P-n G-32
A9XPT920 Set of 20 tooth caps G-29, G-30
A9N21040 Set of 20 end caps 3P-n G-32
A9N21041 Set of 10 phase connectors G-32
A9N21042 Set of 10 neutral connectors G-32
Version : 14 - 15/12/2023
160E1100
A-3
PrismaSeT P Active - Index www.se.com
GS1AP43 Terminal protection shrouds, E-60 LV429256 Crimp lugs for copper cable E-56
TeSys GS, for 3-pole switches LV429257 Crimp lugs for copper cable E-56
160-400 A
LV429258 Crimp lugs for copper cable E-56
GS1AP44 Terminal protection shrouds, E-60
TeSys GS, for 4-pole switches LV429284 Escutcheon collar for Vigi E-24, E-29
160-400 A chassis ns
LV429285 Escutcheon with collar for Vigi E-22, E-23,
LGY••• module E-24, E-27,
LGY4193 Busbar support, Linergy BS, G-9 E-28, E-29,
630A E-33, E-34
LV429306
NSX
1 Connections adapter 3P for E-21, E-23,
LV432501 Crimp lugs for copper cable E-57 A
plug in bas E-24, E-29, LV432502 Crimp lugs for copper cable E-57
E-30, E-32, LV432503 Crimp lugs for copper cable E-57
E-34
LV432504 Crimp lugs for aluminium cable E-57
LV429307 1 Connections adapter 4P for E-21, E-23,
plug in bas E-24, E-29, LV432505 4 Crimp lugs - for aluminium E-57
E-30, E-32, cable
E-34
LV432506 Crimp lugs for aluminium cable E-57
LV429316 IP40 escutcheon for Vigi module E-27, E-28,
LV432507 Crimp lugs for aluminium cable E-57
E-33, E-34
LV432516 3P plug-in base E-40
LV429358 Accessory for sourcechangeover E-50, E-51
switch do LV432534 Escutcheon collar for toggle E-24, E-29,
E-30
LV429359 Accessory for sourcechangeover E-50, E-51,
switch do E-52, E-53 LV432584 1 Connections adapter 3P for E-21, E-23,
plug in bas E-24, E-26,
LV429369 Mechanical interlocking for 2 rot E-50
E-28, E-29,
handle
E-30
LV429504 3 Crimp lugs for aluminium cable E-56
LV432585 1 Connections adapter 4P for E-21, E-23,
150 mm²
plug in bas E-24, E-26,
LV429505 Crimp lugs for aluminium cable E-56 E-28, E-29,
E-30
LV429506 Connection accessories, E-56
Compact NSX LV432591 1 3P short terminal shield E-20, E-21,
E-22, E-23,
LV429507 4 Al 185mm² crimp lugs ph E-56 E-24, E-25,
barriers inv/ E-26, E-27,
LV429515 1 3P short terminal shield E-20, E-21, E-28, E-29,
E-22, E-23, E-30, E-50,
E-24, E-29, E-51
E-30, E-31, LV432592 1 4P short terminal shield E-20, E-21,
E-32, E-33, E-22, E-23,
E-34, E-50, E-24, E-25,
E-51 E-26, E-27,
LV429516 1 4P short terminal shield E-20, E-21, E-28, E-29,
E-22, E-23, E-30, E-40,
E-24, E-29, E-50, E-51
E-30, E-31, LV432593 1 3P long terminal shield E-20, E-21,
E-32, E-33, E-22, E-23,
E-34, E-50, E-24, E-25,
E-51 E-26, E-27,
LV429517 1 3P long terminal shield E-20, E-21, E-28, E-29,
E-22, E-23, E-30, E-50,
E-24, E-29, E-51
E-30, E-31, LV432594 1 4P long terminal shield E-20, E-21,
E-32, E-33, E-22, E-23,
E-34, E-50, E-24, E-25,
E-51 E-26, E-27,
LV429518 1 4P long terminal shield E-20, E-21, E-28, E-29,
E-22, E-23, E-30, E-40,
E-24, E-29, E-50, E-51,
E-30, E-31, E-52, E-53
E-32, E-33, LV432595 1 3P long terminal shield for E-50, E-51
E-34, E-40, spreader
E-50, E-51,
E-52, E-53, LV432596 1 4P long terminal shield for E-50, E-51
E-56 spreader
LV432475 2 Short rear connections E-20, E-21, LV432619 Accessory for sourcechangeover E-50, E-51
E-22, E-23, switch do
E-25, E-26,
LV432620 Accessory for sourcechangeover E-50, E-51,
E-24, E-27,
switch do E-52, E-53
E-28, E-29,
E-30, E-40 LV432621 Rotary handle mechanical E-50
interlocking n
LV432476 2 Long rear connections E-20, E-21,
E-22, E-23, LV434021 Energy sensor PowerTag E-56
E-24, E-25, Monoconnect 250A
E-26, E-27,
E-28, E-29, LV480756 Terminal covers x2 E-59
E-30, E-40
LV480811 ISFT160 feeding busbar for 2 E-59
LV432479 Aluminium bare cable E-57 devices
connectors
LV480812 ISFT160 feeding busbar for 3 E-59
LV432480 Aluminium bare cable E-57 devices
connectors
Version : 14 - 15/12/2023
160E1100
A-5
PrismaSeT P Active - Index www.se.com
LV480854 Kit for direct mounting 185mm E-58 LVS03050 #N/A E-30
LV480855 Direct connection to 185mm E-58 LVS03051 M.Pl.NSX/CVS/INS 250 v. fixed E-30
busbars for 2 devices rot.handle
LV480869 Sidewise angle bracket for side E-58 LVS03152 M.Plate for 2 3P-meters E-65
frame
LVS03164 20 M4 clip-nuts mod.dev.rails F-24
LV480870 Lenght adaptor and ident. Label E-58
LVS03165 20 M5 clip-nuts mod.dev.rails F-24
holder
LVS03166 20 M6 clip-nuts mod.dev.rails F-24
LVS01••• LVS03180 20 slotted m.Pl. M4 clip-nuts F-24
LVS01005 10 black line L900 stickers F-22
LVS03181 20 slotted m.Pl. M5 clip-nuts F-24
LVS01006 10 black arrow out. Stickers F-22
LVS03182 20 slotted m.Pl. M6 clip-nuts F-24
LVS01007 10 black arrow inc. stickers F-22
LVS03185 4 hexagonal spacers M5 H9 F-24
LVS01008 10 black transfomer stickers F-22
LVS03186 4 hexagonal spacers M5 H23 F-24
LVS01094 1/4 T locking front plate (2 by 10) I-5
LVS03187 4 hexagonal spacers M5 H55 F-24
LVS01100 Side panel access.Syst.P I-6
LVS03194 20 hexa.Spacer M6 captive nuts F-24
LVS01101 IP55 back access.Syst.P I-5
LVS03195 4 hexagonal spacers M6 H9 F-24
LVS01102 IP55 side panel access Syst.P I-6
LVS03196 4 hexagonal spacers M6 H23 F-24
LVS01103 IP55 roof access. Syst.P I-6
LVS03197 4 hexagonal spacers M6 H55 F-24
LVS01104 Framework access.Syst.P I-4
LVS03198 4 hexagonal spacers M6 H25 F-24
LVS01105 IP30/55 door access.Syst.P I-7
LVS03199 4 hexagonal spacers M8 H40+10 F-24
LVS01106 Back panel access.Syst.P I-5
LVS03202 Modular front plate W600/W650 E-68
LVS01109 12 Linergy LGY busbar stops G-4, G-7 2m
LVS01110 W150 plain wicket door E-61, I-5 LVS03203 Modular front plate W600/W650 E-62, E-63,
3m E-68
LVS01112 Roof access. Syst.P I-6
LVS03204 Modular front plate W600/W650 E-63, E-64
LVS01120 Frame bot. Cross-member L650 I-7 4m
LVS01121 Frame bot. Cross-member I-7 LVS03205 Modular front plate W600/W650 E-36, E-37,
L150+650 5m E-62, E-64
LVS01123 Fr.Pl.Sup. Striker kit Syst.P I-6 LVS03206 Front Plate, Transfer Pact, 3P/4P, E-54
LVS01124 locking kit for IP31/IP55 door (Ipc I-7 63A, Vertical, W650, 6M
Arc) LVS03207 Front Plate, Transfer Pact, 3P/4P, E-55
LVS01126 Green Cover W400 P for Wireless I-8 160A, Vertical, W650, 8M
PaS LVS03210 Faceplate TransferPact E-56
LVS01127 Green Cover W650 P for Wireless I-8 PrismaSeT P
PaS LVS03211 Faceplate TransferPact E-57
LVS01128 Green Cover W800 P for Wireless I-8 PrismaSeT P
PaS LVS03213 Modular front plate W300 3m E-63
LVS01130 Linergy LGYE busbar screw plate G-13, I-5 LVS03214 Modular front plate W300 4m E-63, E-64
kit
LVS03220 Blanking strip L1000 E-36, E-37,
LVS01198 Ph/PrismaSeT Plus IP55 cub. I-6 E-63, E-64,
Assoc. E-68, F-22
LVS01199 combination kit - Prisma (before I-6 LVS03221 4 divisible blanking plates W90 E-36, E-37,
2005)-Prisma IP30 (before 2020) E-63, E-64,
LVS01201 2 IPXXB clip-on covers Linergy I-4 E-68, F-22
BW LVS03222 NSX blanking plate electronic trip E-31, E-32,
LVS01202 4 IPXXB covers Linergy FM 200 G-25, I-4 unit E-33, E-34,
F-22
LVS01210 Linergy BW accessories I-4
160-400A LVS03223 Front plate 3 modular rows W600/ E-63
W650 8m
LVS01215 Cables membrane 70 x 40 (*5) F-27
LVS03226
W400 5m
Front plate NSXm -3P vert.Rot. E-36 LVS03345
W650 9m
Transparent front plate W600/ F-23
A
W650 5m W650 12m
LVS03227 Front plate NSXm -4P vert.Rot. E-36 LVS03346 FRONT PLATE HORI GS 250A 7M E-60
W650 5m W650
LVS03235 Fr.Pl.changeover INS-INV250 rot E-52 LVS03347 FRONT PLATE HORI GS 400A 8M E-60
W600 5m W650
LVS03241 Fr.Pl.3-4 Vigi NSX/CVS250 v.fix. E-31, E-32 LVS03349 FRONT PLATE VERT GS E-60
tog. 7m 250-400A 6M W650
LVS03243 Fr.Pl.3-4 NSX/CVS250 v.fixed tog/ E-29, E-31, LVS03352 Transparent front plate W300 4m F-23
rot 5m E-32, E-33,
E-34 LVS03353 Transparent front plate W300 6m F-23
LVS03244 Fr.Pl.3-4Vigi NSX/CVS250 v.rot/tl/ E-29, E-33, LVS03354 Transparent front plate W300 9m F-23
plug 7m E-34 LVS03371 Fixed L650 front plate support E-57, F-5
LVS03245 Fr.Pl. changeover NSX250 v.rot. E-50 frame
W600 5m LVS03401 W650 modular device rail E-62, E-63,
LVS03247 Front plate changeover INS250 E-53 PrismaSeT P Active E-64, E-68,
W600 5m F-26
LVS03248 Front plate INS250 vertical W600/ E-40 LVS03404 W400 adjustable mod. Dev. Rail E-63
W650 5m PrismaSeT P Active
LVS03249 Blanking plate NSX/CVS250- E-31, E-32, LVS03402 W650 adjustable mod. Dev. Rail E-37, E-62,
EZC100 v. W147 E-33, E-34, PrismaSeT E-68, F-26,
F-22 G-38
LVS03253 Fr.Pl. NSX/CVS 250 v.fix.tog/rot E-30 LVS03404 W400 adjustable mod. Dev. Rail E-63, E-64,
W300 9m PrismaSeT P Active E-68
LVS03274 Front plate INS630 vertic. W600/ E-40 LVS03405 Mount.Pl NSXm toggle/rot-3P/4P E-38
W650 10m vert.W400
LVS03275 Fr.Pl.NSX/CVS630 v.tog/rot/plug E-25, E-26, LVS03406 Mount.Pl NSXmVigi toggle-3P/4P E-36
W600 9m E-27, E-28, vert.W650
E-29 LVS03409 Mount.Pl NSXm toggle/rot-3P/4P E-35
LVS03283 Fr.Plate NSX/CVS 630 v.fix.rot. E-30 horz.W650
W300 12m LVS03410 Mount.Pl NSXm toggle/rot-3P/4P E-36
LVS03293 Front plate Vigi NSX250 v.tog. E-30 vert.W650
W300 11m LVS03411 Mount.Pl NSX/CVS.Toggle -3P E-20
LVS03297 Fr.Pl.Vigi NSX/CVS630 v.tog/rot E-25, E-26, 250A hz W650
W600 9m E-27, E-28, LVS03412 Mount.Pl NSX/CVS.Toggle -4P E-20, E-40
E-29 250A hz W650
LVS03299 Front pl.Vigi NSX630 v.fix.tog. E-30 LVS03413 Mount.Pl NSX/CVS plugin -3P E-21, E-22,
W300 10m 250A hz W650 E-23
LVS03308 FRONT PL. GS32 3P/4P W600 HZ/ E-60 LVS03414 Mount.Pl NSX/CVS plugin -4P E-21, E-22,
VT 3M 250A hz W650 E-23
LVS03309 FRONT PL. GS63-160 3P/4P E-60 LVS03415 Mount.Pl NSX withd -3/4P 250A E-24
W600 HZ/VT 5M hz W650
LVS03320 Front plate ISFT 100 vertic W600/ E-59 LVS03416 Mounting plate for Linergy FC E-36
W650 6m NSXm
LVS03321 Front plate ISFT 160 vertic W600/ E-59 LVS03417 M.Pl.Hz.NS250 c/o mot. Or ua/ba E-42, E-43,
W650 6m E-44, E-45,
LVS03322 Front plate ISFT 250 vertical E-59 E-46, E-47,
W650 9m E-48, E-51
LVS03323 Front plate ISFT 400 vertical E-59 LVS03420 M.Pl.4Vigi/NSX/CVS/ 3INS 250 v. E-31, E-40
W650 9m Fix. Toggle
LVS03324 Front plate ISFT 630 vertical E-59 LVS03421 M.Pl.3-4V.Withd.NS250 devices E-29, E-32,
W650 8m E-34
LVS03325 Front plate ISFT100N vertical E-59 LVS03422 M.Plate 4 Vigi NSX/CVS 250 v. E-33, E-34
W600/650 8m Fixed rot/tel
LVS03330 Fr. plate NSXm/Vigi/SDX hz.Tog. E-35 LVS03423 M.Pl.3-4 V.Withd.NS250 polyp. E-32
W600 3m LVS03424 Mounting Plate, Transfer Pact, E-54
LVS03331 Fr. plate NSXm hz.Rot.W600 3m E-35 3P/4P, 63A, Vertical W650
LVS03342 Transparent front plate W600/ E-62, E-68, LVS03425 Mounting Plate, Transfer Pact, E-55
W650 4m F-23 3P/4P, 160A, Vertical W650
LVS03343 Transparent front plate W600/ E-65, F-23 LVS03428 Mount.Pl changeover NSX/INS E-50, E-52,
W650 6m 250 rot.Vert E-53
Version : 14 - 15/12/2023
160E1100
A-7
PrismaSeT P Active - Index www.se.com
LVS03452 Mount.Pl NSX/CVS.Toggle -4P E-20, E-40 LVS03569 W800 plain backplate 36m F-25
630A hz W650 LVS03570 Plain backplate 36m W650 F-25
LVS03453 Mount.Pl NSX/CVS plugin -3P E-21, E-22, LVS03571 Slotted mounting plate 4modules E-62, F-26
630A hz W650 E-23
LVS03572 Slotted mounting plate 6modules E-62, F-26
LVS03454 Mount.Pl NSX/CVS plugin -4P E-21, E-22,
630A hz W650 E-23 LVS03574 Slotted mounting plate 12m F-26
LVS03457 Mount.Pl changeover NSX/INS E-51 LVS03580 4 Angle brackets + screws F-24
630 mot.Horz
LVS03581 2 universal angle brackets F-24, F-26,
LVS03458 Mount.Pl changeover NSX/INS E-50, E-52, F-28, G-38
630 rot.Horz E-53
LVS03582 6 Universal inserts Syst.P F-24, F-28
LVS03460 Kit For Control Support E-22
LVS03583 6 universal angle brackets F-24, H-6
LVS03461 Mount.Pl 2 NSX/CVS/INS -3P/4P E-25, E-26,
LVS03584 2 Side.Cross-members W400 E-7, F-20,
630A vert. E-27, E-28,
D400 F-28, G-38
E-29, E-40
LVS03586 2 Side.Cross-members W200 E-7, F-20,
LVS03462 Mount.Pl NSX withd -3/4P 630A E-24
D600 F-28
hz W650
LVS03587 2 Longitudinal cross-mbers F-20, F-28
LVS03480 Mount.Pl NS fixed -3P/4P 1000A E-17
W650
hz.W650
LVS03590 Rear modular device rail W650 F-26
LVS03482 Mount.Pl NS fixed -3P/4P 1600A E-15, E-16
vert.W650 LVS03593 2 Slide rails+angle brackets F-25, F-26,
F-28
LVS03483 M.Pl NT/NS withd -3P/4P 1600A E-10, E-11,
vert.W650 E-15, E-16, LVS03595 System G adapter W500 E-65, F-25
E-46, E-47,
E-48 LVS03596 System G adapter W250 E-30, F-25
LVS03484 Mount.Pl NT fixed -3P/4P 1600A E-10, E-11, LVS03604 Fr.Pl Vigi NSX.Tog/CVS.Rot -3P E-20, E-21,
vert.W650 E-46, E-47, 250 hz 3m E-22, E-23
E-48
LVS03606 Fr.Pl Vigi NSX.Tog/CVS.Rot -4P E-20, E-21,
LVS03487 Mount.Pl NS fixed -3P/4P 1600A E-18, E-30 250 hz 4m E-22, E-23
vert.W400
LVS03616 Fr.Pl.Hz.NSX250 c/over mot. E-51
LVS03488 Mount.Pl NT/NS withd -3P 1600A E-12, E-18
LVS03617 Fr.Pl.Hz.INS250 E-40
vert.W400
LVS03618 Fr.Pl.Hz. Withd. NSX250 E-24
LVS03489 Mount.Pl NT fixed -3P 1600A vert. E-12
W400 LVS03620 Fr.Pl.3-4 V.INS250 devices E-40
LVS03491 Mount.Pl changeover NS1000 rot. E-49 LVS03643 Fr.Pl Vigi NSX.Tog/CVS.Rot -3P E-20, E-21,
Horz.W650 630 hz 3m E-22, E-23
LVS03500 Mount.Pl NW fixed/withd -3P/4P E-2, E-4, LVS03644 Fr.Pl Vigi NSX.Tog/CVS.Rot -4P E-20, E-21,
vert.W650 E-6, E-8, 630 hz 4m E-22, E-23
E-9, E-42,
E-43, E-44, LVS03656 Fr.Pl.Hz.NSX630 c/over mot. E-51
E-45 LVS03657 Fr.Pl.Hz. Withd. NSX630 E-24
LVS03501 M.Pl NS3200 INS-INV2500 fixed E-14, E-39 LVS03658 Fr.Pl.Hz.INS630 E-40
vertical
LVS03659 Fr.Pl.Hz.NSX-INS630 c/over rot E-50, E-52
LVS03508 Prisma P M.Plate 2 3PH Counters E-65
3PH 6M LVS03661 Fr.Pl.Hz.Ns-INS630 changeover E-53
LVS03545 M.Pl.100mm b/centres ISFL160 E-58 LVS03663 Fr.Pl. Vert. 2 NSX630 E-25, E-26,
E-27, E-28,
LVS03546 M.Pl.185mm b/centres ISFL630 E-58 E-29
LVS03553 M.Plate ISFT 100N E-59 LVS03666 Fr.Pl.Vertical 2 NSX630 Vigi E-25, E-26,
LVS03554 M.Pl.ISFT100 E-59 E-27, E-28,
E-29
LVS03555 M.Pl busbar ISFT 100N/160 E-59
LVS03671 Fr.Pl.Ua or ba E-42, E-43,
LVS03556 M.Pl.ISFT160 E-59 E-44, E-45,
E-46, E-47,
LVS03557 M.Pl.ISFT630 E-59
E-48, E-51
LVS03559 M. PL GS 3P/4P 32A H+V W650 E-60
LVS03687 Fr.Pl.Hz.Fix.NS1600 tog/rot.4P E-17
LVS03560 M.PL GS 3P/4P 63-100-160A E-60
LVS03690 Fr.Pl.V.Fixed NS1600 E-15
HORZ W650
LVS03701 Fr.Pl.V.Fixed mot.NS1600 sp E-16
LVS03561 Canalis support E-4, E-11,
E-16 LVS03691 Fr.Pl.Withd.NS1600-NT E-10, E-11,
E-15, E-16,
LVS03563 M. PL GS 63-160A VERT W650 E-60
E-46, E-47,
LVS03564 M. PL GS 250A HORI W650 E-60 E-48
LVS03698 Fr.Pl.V.Fixed NT 3P W400 E-12 LVS03806 Plain front plate W600/W650 6m E-8, E-11,
E-14, E-16,
LVS03699 Fr.Pl.Withd.NS1600-NT 3P W400 E-12, E-18 E-42, E-43,
E-44, E-45,
LVS03701 Fr.Pl.V.Fixed mot.NS1600 sp E-16
E-62, E-65,
LVS03709 Front plate dedicated NW E-8, E-9 F-23, G-38
LVS03710 Fr.Pl.Withdrawable NW E-2, E-4, LVS03808 Plain front plate W600/W650 12m E-6, F-23
E-6, E-8,
LVS03811 Plain front plate W300 1m E-30, E-38,
E-42, E-43,
E-64, F-23
E-44, E-45
LVS03812 Plain front plate W300 2m E-30, E-38,
LVS03711 Fr.Pl.Fixed NW E-2, E-4,
F-23
E-6, E-42,
E-43, E-44, LVS03813 Plain front plate W300 3m F-23
E-45
LVS03814 Plain front plate W300 4m E-30, E-68,
LVS03713 Fr.Pl.INS1600 3P E-39 F-23
LVS03714 Fr.Pl.INS1600 4P E-39 LVS03815 Plain front plate W300 5m F-23
LVS03715 Fr.Pl.INS2500 3P/4P E-39 LVS03816 Plain front plate W300 6m E-30, F-23
LVS03716 Fr.Pl.NS3200 E-14 LVS03817 Plain front plate W300 9m F-23
LVS03722 Hinged fr.Pl.13M W400 E-12, E-18, LVS03891 IP30 ventilated front plate W600/ F-30
F-23 W650 1m
LVS03723 Hinged fr.Pl.Hsi 13m W400 E-12, E-18 LVS03895 IP30 ventilated front plate W600/ F-30
W650 3m
LVS03735 Ip20 front ISFL 185mm bc W650 E-58
LVS03900 Support 72x72 met.dev/pb for E-12, E-18,
LVS03736 Fr.Pl.ISFL 160 E-58
03904/03928 E-67
LVS03740 Blanking plate ISFL 160 E-58
LVS03901 Support 96x96 met.dev/pb for E-12, E-18,
LVS03741 Blanking plate ISFL 630 E-58 03904/03928 E-67
LVS03801 Plain front plate W600/W650 1m E-10, E-25, LVS03902 Supp.cut-out 72x72 met.dev/pb E-12, E-18,
E-26, E-27, 03904/03928 E-67
E-28, E-29,
LVS03903 Supp.cut-out 96x96met.dev/pb E-12, E-18,
E-31, E-32,
03904/03928 E-67
E-33, E-34,
E-36, E-40, LVS03904 Fr.Pl.72²/96² cut-out met.dev/pb E-66, E-67
E-47, E-60, W600 3m
E-62, F-23
LVS03907 Support 72x72 met.dev/pb for E-67
LVS03802 Plain front plate W600/W650 2m E-8, E-6, 03910/03912
E-10, E-14,
E-15, E-25, LVS03908 Support 96x96 met.dev/pb for E-67
E-26, E-27, 03911/03913
E-28, E-29, LVS03910 Fr.pl.72x72 6 Cut-Out Met.dev/Pb E-66, E-67
E-31, E-32, W600 3m
E-33, E-34,
E-36, E-40, LVS03911 Fr.pl.96x96 3 Cut-Out Met.dev/Pb E-66, E-67,
E-46, E-48, W600 3m E-68
E-50, E-52,
E-53, E-56, LVS03913 Fr.Pl.96X96 1 cut-out met.dev/pb E-66, E-67,
E-57, E-59, W600 3m E-68
F-23 LVS03914 Fr.Pl. 12 push-button/lamps E-66, E-67
LVS03803 Plain front plate W600/W650 3m E-4, E-10, W600/W650 2m
E-11, E-15, LVS03923 Fr.Pl. 1 pre cut-out 96x96 W300 E-67, E-68
E-16, E-25, 3m
E-26, E-27,
E-28, E-29, LVS03928 Visor 30°for metering dev/pb E-66, E-67
E-31, E-33, 72x72/96x96
E-39, E-46,
LVS03930 Mounting plate Vigilohm E-68
E-47, E-48,
xm200-300c
E-50, E-62,
F-23, G-38 LVS03932 Fr.Pl. Vigilohm xm200-300c E-68
W600/W650 6m
LVS03804 Plain front plate W600/W650 4m E-2, E-4,
E-6, E-8, LVS03970 Door for capacitors W650 E-61
E-9, E-10,
E-14, E-15, LVS03979 Varpluscan horizontal mounting E-61
E-25, E-27, plate
E-39, E-42,
E-44, E-46,
E-48, E-62,
E-68, F-23
Version : 14 - 15/12/2023
160E1100
A-9
PrismaSeT P Active - Index www.se.com
LVS04114 Insulated busbar - 630 A 3P - D-3 LVS04256 10 Hz. adjustable trunking sup F-27
L=1000 mm (Powerclip)
LVS04257 4Hz.trunking sections L450+sup F-27
LVS04116 Insulated busbar - 160 A 3P - D-3
LVS04262 12 Vertical cable straps F-27
L=1400 mm (Powerclip)
LVS04263 2 V.cable straps L1000 covers F-27
LVS04117 Insulated busbar - 250 A 3P - D-3
L=1400 mm (Powerclip) LVS04267 Vertical trunking L2000 F-27
LVS04406 Linergy FC distribution block for E-32, E-33, LVS04459 Universal connection in duct E-20, E-21,
ComPacT NSX250 4P fixed/ E-34, G-16 630A 3P E-22, E-23,
plug-in + connection E-24
LVS04407 Linergy FC distribution block for E-31, E-32, LVS04460 Universal connection in duct E-20, E-21,
ComPacT NSX250 3P fixed W/O E-33, E-34, 630A 4P E-22, E-23,
connection G-16 E-24
LVS04408 Linergy FC distribution block for E-31, E-32, LVS04461 Connection NSX toggle-3P 630A E-21, E-24
ComPacT NSX250 4P fixed W/O E-33, E-34, plugin hz
connection E-40, G-16 LVS04462 Connection NSX toggle-4P 630A E-21, E-24
LVS04410 Linergy FC distribution block for E-36, G-18 plugin hz
ComPacT NSXm 160A 3P toggle/ LVS04473 Connection NS -3P 1000A fixed E-17, I-22,
fixed + connection horizontal I-37
LVS04411 Linergy FC distribution block for E-36, G-18 LVS04474 Connection NT -4P 1000A fixed E-17, I-22,
ComPacT NSXm 160A 4P toggle/ horizontal I-37
fixed + connection
LVS04475 Connection NT -3P 1250A fixed E-10, E-11,
LVS04412 Linergy FC distribution block for E-36, G-18 I-21, I-36
ComPacT NSXm 160A 3P toggle/
fixed LVS04476 Connection NT -4P 1250A fixed E-10, E-11,
I-21, I-36
LVS04413 Linergy FC distribution block for E-36, G-18
ComPacT NSXm 160A 4P toggle/ LVS04477 Connection NS/NT -3P 1250A E-10, E-11,
fixed withdrawable E-15, E-16,
I-20, I-35
LVS04416 Linergy FC distribution block for E-36, G-18
ComPacT NSXm 160A 3P toggle/ LVS04478 Connection NS/NT -4P 1250A E-10, E-11,
fixed with VIGI + connection withdrawable E-15, E-16,
I-20, I-35
LVS04417 Linergy FC distribution block for E-36, G-18
ComPacT NSXm 160A 4P toggle/ LVS04481 Connection INS-INV -3P 1600A E-39
fixed with VIGI + connection fixed
LVS04418 Linergy FC distribution block for E-36, G-18 LVS04482 Connection INS-INV -4P 1600A E-39
ComPacT NSXm 160A 3P toggle/ fixed
fixed with VIGI
LVS04483 Conn.Transf. NS -3P 1000A fixed E-17, I-49
LVS04419 Linergy FC distribution block for E-36, G-18 horz
ComPacT NSXm 160A 3P toggle/
LVS04484 Conn.Transf. NS -4P 1000A fixed E-17, I-49
fixed without connection
horz
LVS04420 Linergy FC distribution block for E-36, G-18
LVS04485 Connection NS -3P 1250A fixed E-15, E-16,
ComPacT NSXm 160A 4P toggle/
I-20, I-35
fixed without connection
LVS04486 Connection NS -4P 1250A fixed E-15, E-16,
LVS04423 Connection NSX toggle-3P 250A E-20
I-20, I-35
fixed horz
LVS04487 Connection NS -3P 1600A fixed E-15, E-16,
LVS04424 Connection NSX toggle-4P 250A E-20
I-20, I-35
fixed horz
LVS04488 Connection NS -4P 1600A fixed E-15, E-16,
LVS04425 Conn.Transf. NSX tog -3P 250A E-20
I-20, I-35
fixed horz
LVS04489 Connection NT -3P 1600A fixed E-10, E-11,
LVS04426 Conn.Transf. NSX tog -4P 250A E-20
I-21, I-36
fixed horz
LVS04490 Connection NT -4P 1600A fixed E-10, E-11,
LVS04427 Conn. NSX/INS -3P 250A fixed/ E-22, E-23,
I-21, I-36
withd horz E-24, E-40
LVS04491 Connection NS/NT -3P 1600A E-10, E-11,
LVS04428 Conn. NSX/INS -4P 250A fixed/ E-22, E-23,
withdrawable E-15, E-16,
withd horz E-24, E-40
I-20, I-35
LVS04429 Universal connection in duct E-20, E-21,
LVS04492 Connection NS/NT -4P 1600A E-10, E-11,
250A 3P E-22, E-23,
withdrawable E-15, E-16,
E-24
I-20, I-35
LVS04430 Universal connection in duct E-20, E-21,
LVS04493 Connection horizontal LGYE NW E-3, E-5
250A 4P E-22, E-23,
1600A 3P
E-24
LVS04494 Connection horizontal LGYE NW E-3, E-5
LVS04431 Connection NSX toggle-3P 250A E-21, E-24
1600A 4P
plugin hz
LVS04495 Connection horizontal LGYE NW E-3, E-5
LVS04432 Connection NSX toggle-4P 250A E-21, E-24
2500A 3P
plugin hz
Version : 14 - 15/12/2023
160E1100
A-11
PrismaSeT P Active - Index www.se.com
LVS04538 Plain hz flat bar Linergy BS 80x5 G-3 LVS04642 Mounting hardware/joint>80mm G-4, G-6,
L2000 Linergy LGY G-7, G-8
LVS04545 Plain hz flat bar Linergy BS 50x10 G-3 LVS04637 Connect.Plate 3200A 10mm hz/ E-7, G-6
L2000 v.Flat bar
LVS04546 Plain hz flat bar Linergy BS 60x10 G-3 LVS04642 Mounting hardware/joint>80mm G-6
L2000 Linergy LGY
LVS04548 Plain hz flat bar Linergy BS 80x10 G-3 LVS04638 Connect.Plate 4000A 10mm hz/ G-4, G-6
L2000 v.Flat bar
LVS04550 Plain hz flat bar Linergy G-3, G-6 LVS04638 #N/A G-4
BS100x10 L2000 LVS04640 Joint for 50/60mm bar/Linergy BS F-16, G-3
LVS04552 Plain hz flat bar Linergy G-3, G-6 hz bbar
BS120x10 L2000 LVS04641 Joint for 80/100mm bar/Linergy F-16, G-3
LVS04560 Linergy LGYE profile 630A L2000 G-2, G-5 BS hz bar
LVS04561 Linergy LGYE profile 800A L2000 G-2, G-5 LVS04642 Mounting hardware/joint>80mm E-7
Linergy LGY
LVS04562 Linergy LGYE profile 1000A G-2, G-5
L2000 LVS04643 Joint for 120mm bar/Linergy BS G-3
hz.Busbar
LVS04563 Linergy LGYE profile 1250A G-2, G-5
L2000 LVS04645 20 Screw/joint 2x10mm Linergy G-6
BS hz/v bb
LVS04564 Linergy LGYE profile 1600A G-2, G-5
L2000 LVS04651 Linergy LGY lateral busbar G-4
support
LVS04565 Linergy LGYE profile 2000A G-2
L2000 LVS04652 Linergy LGY rear busbar support G-7
LVS04566 Linergy LGYE profile 2500A G-2 LVS04653 Linergy BS rear vert.Support G-8
L2000 5/10mm bar
LVS04669
LGYE/BS
Wedge, Linergy BS, for busbar G-8 LVS04694 Conn.Sup 115mm b/centres
E-15, E-16
E-2, E-4,
A
support E-6, E-14,
E-39
LVS04656 Linergy TB pen kit / LGY profile G-37
LVS04703 Canalis interface 1600A 3P E-11, E-16
LVS04657 Linergy TB 3 flat bar supp.For G-37
vert.Pe LVS04704 Canalis interface 1600A 4P E-11, E-16
LVS04658 12 Stops/1600A bott.Support G-5 LVS04711 Canalis conn.Front NS-NT 3P E-11, E-16
Linergy LGYE
LVS04712 Canalis conn.Front NS-NT 4P E-11, E-16
LVS04659 12 Stops/4000A bott.Support G-5
Linergy LGYE LVS04713 Canalis conn.Rear NS-NT 3P E-11, E-16
LVS04661 Fixed support vert. Bb Linergy G-5, G-6 LVS04714 Canalis conn.Rear NS-NT 4P E-11, E-16
LGYE/BS LVS04715 Canalis conn.1600A NW 3P E-4
LVS04646 Mounting hardware Linergy G-5 LVS04716 Canalis conn.1600A NW 4P E-4
LGYEu3200A
LVS04725 Canalis conn.2500A NW 3P E-4
LVS04671 Additionnal mounting hardware G-5, G-6
LVS04726 Canalis conn.2500A NW 4P E-4
LVS04662 Free busbar support Linergy E-3, E-5,
LGYE/BS E-10, E-11, LVS04735 Canalis conn.3200A NW 3P E-4
E-13, E-14,
LVS04736 Canalis conn.3200A NW 4P E-4
E-15, E-16,
E-19, E-39, LVS04742 Insulated flex.bar 20x2 L1800 G-20, G-21
F-16, G-2,
G-3, G-5, LVS04743 Insulated flex.bar 20x3 L1800 G-20, G-21
G-6
LVS04746 Insulated flex.bar 24x5 L1800 G-20, G-21
LVS04646 Mounting hardware Linergy G-2, G-5
LVS04751 Insulated flex.bar 32x5 L1800 G-20, G-21
LGYEu3200A
LVS04752 Insulated flex.bar 32x6 L1800 G-20, G-21
LVS04671 Additionnal mounting hardware G-2, G-3,
G-5, G-6 LVS04753 Insulated flex.bar 32x8 L1800 G-20, G-21
LVS04663 Bottom lat.V.5/10 Bb support lin. G-5, G-6 LVS04759 20 M8 torque nuts G-13
LGYE/BS
LVS04766 20 M8 LGY bolts for cab.Lug/flex G-13, G-37
LVS04664 Fixed support hz. Bb Linergy F-16, G-2, bar L25
LGYE/BS G-3
LVS04767 20 M8 LGY bolts for copper bar G-13
LVS04646 Mounting hardware Linergy G-2 L39
LGYEu3200A
LVS04768 Set of 12 screwplates for Linergy G-13
LVS04665 Horiz.10Mm bb support D600 G-2 evolution 2500A
Linergy BS
LVS04769 Set of 8 screwplates for Linergy G-13
LVS04666 Bot.Lat.5/10 Bb support W300 lin. G-5, G-6 evolution 4000A
LGYE/BS
LVS04773 20 M8/diam.24 Flat washers flex. G-13
LVS04661 Fixed support vert. Bb Linergy G-5, G-6 Bar/LGY
LGYE/BS
LVS04774 20 M8/diam.28 Flat washers flex. G-13
LVS04667 2 Horizontal pe supports Linergy F-24, G-37 Bar/LGY
TB
LVS04775 20 M8/diam.20 Flat washers G-13
LVS04669 Wedge, Linergy BS, for busbar G-8 lugs<25²/LGY
support
LVS04782 20 Bolts 8.8 Class M8x20 /Linergy G-6, G-13
LVS04671 Additionnal mounting hardware F-16, G-2, BS
G-3
LVS04783 20 Bolts 8.8 Class M8x25 /Linergy G-13
LVS04672 2 Connect.Plate hz/v.Pe bar G-37 BS
Linergy TB
LVS04784 22 Bolts 8.8 Class M8x30 /Linergy G-13
LVS04678 Free 5/10 busbar support D600 E-2, E-4, BS
Linergy BS G-2
LVS04785 23 Bolts 8.8 Class M8x35 /Linergy G-13
LVS04683 Joint Linergy vert.LGY/LGYE E-3, E-5 BS
1600A 3P
LVS04786 24 Bolts 8.8 Class M8x40 /Linergy G-13
LVS04684 Joint Linergy vert.LGY/LGYE E-3, E-5 BS
1600A 4P
LVS04787 25 Bolts 8.8 Class M8x45 /Linergy G-13
LVS04685 Joint Linergy vertical LGYE E-3, E-5 BS
2500A NW
LVS04788 26 Bolts 8.8 Class M8x50 /Linergy G-13
LVS04687 Joint Linergy vertical LGYE E-3, E-5 BS
3200A NW
LVS04794 12 Phase marker/Linergy LGY/ G-13
LVS04690 Flange for flat bars E-7 LGYE profile
LVS04691 Flange for edgewise bars E-10, E-13, LVS04809 Linergy FC tooth-caps E-31, E-32,
E-15, E-19 E-33, E-34,
E-40, G-17
LVS04692 Flange for flat bars W400 E-13, E-19
LVS04810 Tooth-cap 1P Linergy FC D.BLK E-36, G-19
NSXm 160A
Version : 14 - 15/12/2023
160E1100
A-13
PrismaSeT P Active - Index www.se.com
LVS08408 PrismaSeT P Active framework F-5 LVS08593 IP30 door cut-out hsi W300 F-14
W800 D400 LVS08594 IP30 door cut-out hsi W400 F-14
LVS08433 IP30 plain roof W300 D400 F-15 LVS08603 PrismaSeT P Active framework F-2, F-5,
LVS08434 IP30 plain roof W400 D400 F-15 W300 D600 F-20
LVS08436 IP30 plain roof W650 D400 F-2, F-3, LVS08604 PrismaSeT P Active framework F-5, F-20
F-4, F-15 W400 D600
LVS08438 IP30 plain roof W800 D400 F-3, F-4, LVS08606 PrismaSeT P Active framework F-2, F-4,
F-15 W650 D600 F-5, F-20
LVS08456 IP55 plain roof W650 D400 F-4 LVS08607 PrismaSeT P Active framework F-2, F-4,
W650+150 D600 F-5, F-20
LVS08458 IP55 plain roof W800 D400 F-4
LVS08608 PrismaSeT P Active framework F-5
LVS08476 IP30 ventilated roof W650 D400 F-32 W800 D600
LVS08478 IP55 ventilated roof W800 D400 E-61, F-32 LVS08633 IP30 plain roof W300 D600 F-2, F-15
LVS08483 IP55 plain gl.pl.W300 D400 F-19 LVS08634 IP30 plain roof W400 D600 F-15
LVS08484 IP55 plain gl.pl.W400 D400 F-19 LVS08636 IP30 plain roof W650 D600 F-2, F-4,
F-15
LVS08486 IP55 plain gl.pl.W650 D400 F-2, F-3,
F-4, F-19 LVS08638 IP30 plain roof W800 D600 F-2, F-4,
F-15
LVS08487 IP55 plain gl.pl.W650+150 D400 F-3, F-4,
F-19 LVS08640 PrismaSeT P Active Green Cover F-2, F-15
W300
LVS08488 IP55 plain gl.pl.W800 D400 F-19
LVS08641 PrismaSeT P Active Green Cover F-15
LVS08493 IP30 2-part gl.pl.W300 D400 F-19 W400
LVS08494 IP30 2-part gl.pl.W400 D400 F-19 LVS08642 PrismaSeT P Active Green Cover F-4, F-15
LVS08496 IP30 2-part gl.pl.W650 D400 F-19 W650
LVS08497 IP30 2-part gl.pl.W650+150 D400 F-19 LVS08643 PrismaSeT P Active Green Cover F-2, F-3,
W800 F-15
LVS08498 IP30 2-part gl.pl.W800 D400 F-19
LVS08656 IP55 plain roof W650 D600 F-4
LVS08513 IP30 plain door W300 F-2, F-14
LVS08658 IP55 plain roof W800 D600 F-4
LVS08514 IP30 plain door W400 F-14
LVS08676 IP55 ventilated roof W650 D600 F-32
LVS08516 IP30 plain door W650 F-3, F-4,
F-14 LVS08678 IP55 ventilated roof W800 D600 E-61, F-32
LVS08518 IP30 plain door W800 F-3, F-4, LVS08683 IP55 plain gl.pl.W300 D600 F-2, F-19
F-14 LVS08684 IP55 plain gl.pl.W400 D600 F-19
LVS08523 IP55 plain door W300 F-17 LVS08686 IP55 plain gl.pl.W650 D600 F-2, F-4,
LVS08524 IP55 plain door W400 F-17 F-19
LVS08526 IP55 plain door W650 F-4, F-17 LVS08687 IP55 plain gl.pl.W650+150 D600 F-2, F-4,
F-19
LVS08528 IP55 plain door W800 F-4, F-17
LVS08688 IP55 plain gl.pl.W800 D600 F-19
LVS08534 IP30 transparent door W400 F-14
LVS08693 IP30 2-part gl.pl.W300 D600 F-19
LVS08536 IP30 transparent door W650 F-2, F-4,
F-14 LVS08694 IP30 2-part gl.pl.W400 D600 F-19
LVS08538 IP30 transparent door W800 F-2, F-4, LVS08696 IP30 2-part gl.pl.W650 D600 F-19
F-14 LVS08697 IP30 2-part gl.pl.W650+150D600 F-19
LVS08544 IP55 transparent door W400 F-17 LVS08698 IP30 2-part gl.pl.W800 D600 F-19
LVS08546 IP55 transparent door W650 F-4, F-17 LVS08700 4 Lifting rings F-21
LVS08548 IP55 transparent door W800 F-4, F-17 LVS08701 Stabiliser kit F-21
LVS08560 10M hinged front.Plate sup. Kit E-8, F-5, LVS08702 Levelling kit F-21
W650 F-22
LVS08703 False floor fixing kit F-21
LVS08562 12M hinged front plate sup. E-8, E-9,
Frame W650 F-5, F-22 LVS08704 Floor/wall fixing kit F-21
LVS08564 Hinged fr.Plate sup.Frame W400 F-5, F-22 LVS08706 Handl. Plinth lh. 2000->2550 F-20, J-13
LVS08566 Hinged fr.Plate sup.Frame W650 F-2, F-3, LVS08710 Reinforcement bracket F-20
F-4, F-5, PrismaSeT P Active seismic
F-22
LVS08711 IP31 sealing kit F-15
LVS08574 IP30 cover frame W400 F-14
LVS08712 LGYE Corner Kit for 90 Deg F-16
Installed Panel
Version : 14 - 15/12/2023
160E1100
A-15
PrismaSeT P Active - Index www.se.com
LVS08720 2 Side plates for plinth D400 F-19 LVS08767D PrismaSeT P Active Green Cover F-4, F-18,
+ Wireless Panel Server W800 + F-20
LVS08721 2 Side plates for plinth D600 F-19 lateral panels D600
LVS08722 Combination kit for lifting F-20, J-13 LVS08773 4 Cable tie supports W300 F-20, F-28
LVS08723 Plinth h100 W300 D400 F-19 LVS08774 4 Cable tie supports W400 E-13, F-20,
F-28
LVS08724 Plinth h100 W400 D400 F-19
LVS08776 4 Cable tie supports W650 F-28
LVS08726 Plinth h100 W650 D400 F-19
LVS08778 4 Cable tie supports W800 F-28
LVS08728 Plinth h100 W800 D400 F-19
LVS08783 Form c cable tie sup. L1600 F-28
LVS08733 IP30 rear panel W300 F-2, F-14
LVS08794 4 Cable tie supports D400 E-13, E-19,
LVS08734 IP30 rear panel W400 F-14
F-26, F-28
LVS08736 IP30 rear panel W650 F-2, F-14
LVS08796 4 Cable tie supports D600 E-13, E-19
LVS08738 IP30 rear panel W800 E-61, F-2,
LVS08796 4 Cable tie supports D600 F-28
F-14
LVS08900 Switchboard identification pl. F-22
LVS08743 Rear panel F-17
LVS08903 12 adhesive label holders 24x432 F-22
LVS08744 Rear panel, PrismaSeT P, for F-17
enclosure W 400mm, IP55 LVS08904 12 adhesive label holders 36x432 F-22
LVS08746 Rear panel F-17 LVS08905 12 adhesive label holders 24x180 F-22
W300
LVS08748 IP55 rear panel W800 F-17
LVS08906 12 adhesive label holders 36x180 F-22
LVS08750 Set of 2 side panels D400 I-8
W300
LVS08750D PrismaSeT P Active Green Cover F-15
LVS08910 Earthing braid 6mm² F-22, F-29
+ Wireless Panel Server W400
+lateral panels D400 LVS08911 Earthing wire 6mm² F-22, F-29
LVS08751D PrismaSeT P Active Green Cover F-2, F-3, LVS08913 12 clip-on labels 18x35 F-22
+ Wireless Panel Server W650 F-15
+lateral panels D400 LVS08914 12 engraving plates 18x35 / F-22
support 08913
LVS08752D PrismaSeT P Active Green Cover F-15
+ Wireless Panel Server W800 LVS08915 12 clip-on labels 18x72 F-22
+lateral panels D400 LVS08916 12 engraving plates 18x72 / F-22
LVS08753 PrismaSeT P Active rear access F-3, F-4, support 08915
side Panels D400 F-15 LVS08917 12 clip-on labels 25x85 F-22
LVS08755 PrismaSeT P Active Green Cover F-20, I-8 LVS08918 12 engraving plates 25x85 / F-22
+ Wireless Panel Server W400 support 08917
+lateral panels D400
LVS08921 20 Framework screws+wing nuts F-6
LVS08755D Set of 2 side panels D400 F-18
LVS08961 Touch-up paint brush F-22
LVS08756 PrismaSeT P Active rear access F-15, F-18
side panels for L shape D400 LVS08963 Adhesive drawing holder F-22
LVS08756D PrismaSeT P Active Green Cover F-18 LVS08964 Switchboard lighting Syst G F-35
+ Wireless Panel Server W650 +
lateral panels D400 LVS08965 Switchboard portable lamp F-35
LVS08760 Set of 2 side panels D600 I-8 NSYCAF92 Filter std G2 cut-out 92x92mm F-30
LVS08760D PrismaSeT P Active Green Cover F-15 NSYCAF125 Filter std G2 cut-out.125X125mm F-30
+ Wireless Panel Server W400 + NSYCAF125T Fine filter G3 cut-out 125x125mm F-30
lateral panels D600
NSYCAF223 Filter std G2 cut-out.223X223mm F-30
LVS08761D PrismaSeT P Active Green Cover F-2, F-15
+ Wireless Panel Server W650 + NSYCAF223T Fine filter G3 cut-out 223x223mm F-30
lateral panels D600
NSYCAF228R Filter for roof o.Grid 228x228mm E-61
LVS08762D PrismaSeT P Active Green Cover F-4, F-15
+ Wireless Panel Server W800 + NSYCAF291 Filter std G2 cut-out.291X291mm F-30
lateral panels D600 NSYCAF291T Filter std G2 cut-out. 291x291mm F-30
NSYCAG125LPF
92x92mm
Outlet grille plast cut out F-30 NSYTRAB630
type, 6mm
Marking strip, Linergy TR, clip in G-40
A
125x125mm type, 6mm
NSYCAG291LPF Outlet grille - plastic - cut out E-61 NSYTRAB640 Marking strip, Linergy TR, clip in G-40
291x291mm type, 6mm
NSYCAG223LPF Outlet grille plast cut out F-30 NSYTRAB690 Marking strip, Linergy TR, clip in G-40
223x223mm type, 6mm
NSYCAG291LPF Outlet grille - plastic - cut out E-61, F-30 NSYTRAB5100 Marking strip, Linergy TR, clip in G-40
291x291mm type, 5mm
NSYCAP125LE EMC cover cut-out 125x125 F-30 NSYTRAB6100 Marking strip, Linergy TR, clip in G-40
type, 6mm
NSYCAP223LE EMC cover cut-out 223x223 F-30
NSYTRAB51100 Marking strip, Linergy TR, clip in G-40
NSYCAP291LE EMC cover cut-out 291x291 F-30 type, 5mm
NSYCCASTE Climasys CC - temperature range F-34 NSYTRAB61100 Marking strip, Linergy TR, clip in G-40
-30 to 80°C type, 6mm
NSYCCOHY230VID Climasys CC - electronic F-34 NSYTRABF510 Marking strip, Linergy TR, clip in G-40
hygrostat - 200…240 V type, 5mm
NSYCCOHYT230VID Hygrotherm 230V F-34 NSYTRABF520 Marking strip, Linergy TR, clip in G-40
NSYCCOTH230VID Electronical thermostat 230V F-34 type, flat, 5mm
NSYCCOTHD Double thermostat(no nc) (ºc) F-34 NSYTRABF530 Marking strip, Linergy TR, clip in G-40
type, flat, 5mm
NSYCCOTHI Thermostat w/invers contact (ºc) F-34
NSYTRABF540 Marking strip, Linergy TR, clip in G-40
NSYCR10WU2 ClimaSys PTC heating resistance F-33 type, flat, 5mm
10W, 110-250V
NSYTRABF550 Marking strip, Linergy TR, clip in G-40
NSYCR20WU2 ClimaSys PTC heating resistance F-33 type, flat, 5mm
55W
NSYTRAC22 Cover plate, Linergy TR, 2 points, G-40
NSYCR55WU2 ClimaSys PTC heating resistance F-33 2.2mm
100W 110-250V
NSYTRAC22BL Cover plate, Linergy TR, 2 points, G-40
NSYCR100WU2 ClimaSys PTC heating resistance F-33 2.2mm
100W 110-250V
NSYTRAC23 Cover plate, Linergy TR, 3 points, G-40
NSYCR150WU2 ClimaSys PTC heating resistance F-33 2.2mm
150W
NSYTRAC24 Cover plate, Linergy TR, 4 points, G-40
NSYCR250W230VV ClimaSys heating resistance F-33 2.2mm
ventil.250W
NSYTRACE24 Cover plate, Linergy TR, 2 level, G-40
NSYCR400W230VV ClimaSys heating resistance F-33 2.2mm
ventil. 400W 230V aluminium
NSYTRACE26 Cover plate, Linergy TR, 3 level, G-40
NSYCRP1W230VTVC ClimaSys PTC heating resistance F-33 2.2mm
350-550W
NSYTRACP43 Cover plate, Linergy TR, 2.2mm G-40
NSYCVF38M230PF ClimaSys PTC heating resistance F-30
350-550W NSYTRACPE26 Cover plate, Linergy TR, 2.2mm G-40
width
NSYCVF85M230PF ClimaSys forced vent. IP54, F-30
85m3/h, 230V NSYTRACR22 Cover plate, Linergy TR, 2.2mm G-40
NSYCVF165M230PF ClimaSys forced vent. IP54, F-30 NSYTRACR22BL Cover plate, Linergy TR, 2.2mm G-40
85m3/h, 230V NSYTRACR23 Cover plate, Linergy TR, 2.2mm G-40
NSYCVF300M230PF ClimaSys forced vent. IP54, F-30 NSYTRACR23BL Cover plate, Linergy TR, 2.2mm G-40
300m3/h, 230V
NSYTRACR24 Cover plate, Linergy TR, 2.2mm G-40
NSYCVF560M230PF ClimaSys forced vent. IP54, F-30, F-31
560m3/h, 230V NSYTRACR24BL Cover plate, Linergy TR, 2.2mm G-40
NSYCVF575M230MB ClimaSys forced vent. roof, E-61, F-32 NSYTRACR42 Cover plate, Linergy TR, 2 points, G-40
575m3/h, 230V 2.2mm
NSYCVF850M230PF ClimaSys forced vent. IP54, E-61, F-30, NSYTRACR43 Cover plate, Linergy TR, 3 points G-40
850m3/h, 230V F-31
NSYTRACRE24 Cover plate, Linergy TR, 2 level, G-40
NSYTRAB560 Marking strip, Linergy TR, clip in G-40 2.2mm
type, 5mm
NSYTRACRE26 Cover plate, Linergy TR, 3 level, G-40
NSYTRAB570 Marking strip, Linergy TR, clip in G-40 2.2mm
type, 5mm
NSYTRAL22 Plug-in bridge, Linergy TR, 2 G-40
NSYTRAB580 Marking strip, Linergy TR, clip in G-40 points
type, 5mm
NSYTRAL23 Plug-in bridge, Linergy TR, 3 G-40
NSYTRAB590 Marking strip, Linergy TR, clip in G-40 points
type, 5mm
NSYTRAL24 Plug-in bridge, Linergy TR, 4 G-40
NSYTRAB610 Marking strip, Linergy TR, clip in G-40 points
type, 6mm
Version : 14 - 15/12/2023
160E1100
A-17
PrismaSeT P Active - Index www.se.com
NSYTRP23BL Terminal block, Linergy TR, G-40 NSYTRR24MPBL Terminal block, Linergy TR, G-40
2.5mm² 2.5mm²
NSYTRP24 Terminal block, Linergy TR, G-40 NSYTRR26T Terminal block, Linergy TR, G-40
2.5mm² 2.5mm²
NSYTRP24BL Terminal block, Linergy TR, G-40 NSYTRR26TBL Terminal block, Linergy TR, G-40
2.5mm² 2.5mm²
NSYTRP24D Terminal block, Linergy TR, G-40 NSYTRR42 Terminal block, Linergy TR, G-40
2.5mm² 4mm²
NSYTRP24DBL Terminal block, Linergy TR, G-40 NSYTRR42AR Screw terminal, feed through G-40
2.5mm² NSYTRR42BL Screw terminal, feed through G-40
NSYTRP26T Terminal block, Linergy TR, G-40 NSYTRR43 Terminal block, Linergy TR, G-40
2.5mm² 4mm²
NSYTRP26TBL Terminal block, Linergy TR, G-40 NSYTRR43BL Terminal block, Linergy TR, G-40
2.5mm² 4mm²
NSYTRP42 Terminal block, Linergy TR, G-40 NSYTRV22 Screw terminal, feed through G-40
4mm²
NSYTRV22AR Screw terminal, feed through G-40
NSYTRP42BL Terminal block, Linergy TR, G-40
4mm² NSYTRV22BL Screw terminal, feed through G-40
NSYTRP43 Terminal block, Linergy TR, G-40 NSYTRV22M Screw terminal, feed through G-40
4mm²
NSYTRV22MBL Screw terminal, feed through G-40
NSYTRP43BL Terminal block, Linergy TR, G-40
4mm² NSYTRV23 Screw terminal, feed through G-40
NSYTRR22 Terminal block, Linergy TR, G-40 NSYTRV23BL Screw terminal, feed through G-40
2.5mm² NSYTRV24 Screw terminal, feed through G-40
NSYTRR22AR Terminal block, Linergy TR, G-40 NSYTRV24BL Screw terminal, feed through G-40
2.5mm²
NSYTRV24D Screw terminal, feed through G-40
NSYTRR22BL Terminal block, Linergy TR, G-40
2.5mm² NSYTRV24DBL Screw terminal, feed through G-40
NSYTRR22M Terminal block, Linergy TR, G-40 NSYTRV26T Screw terminal, 3 levels G-40
2.5mm²
NSYTRV26TBL Screw terminal, 3 levels G-40
NSYTRV43 Screw terminal, feed through G-40 TPSCON52 50 to 120 mm² cable kit for TA25 E-56
4P,load
NSYTRV43BL Screw terminal, feed through G-40
TPSCON53 35 to 300 mm² cable kit for TA63 E-57
NSYTRV44 Screw terminal, feed through G-40 3P
R9XFH157 Resi9 - comb busbar - 1L - 18 mm G-34 TPSCON61 Aluminium cable lug, 240 mm², E-57
TA63, 3P
R9XFH212 Resi9 - comb busbar - 1L+N - 18 G-34
mm TPSCON62 Aluminium cable lug, 240 mm², E-57
TA63, 4P
R9XFH218 Resi9 - comb busbar - 1L+N - 18 G-34
mm TPSCON63 Aluminium cable lug, 300 mm², E-57
TA63, 3P
R9XFH257 Resi9 - comb busbar - 1L+N - 18 G-34
mm TPSCON64 Aluminium cable lug, 300 mm², E-57
TA63, 4P
R9XFH312 Resi9 - comb busbar - 3L - 18 mm G-34
TPSIS042 Long terminal shield, E-57
R9XFH318 Resi9 - comb busbar - 3L - 18 mm G-34 TransferPacT
R9XFH357 Resi9 - comb busbar - 3L - 18 mm G-34 TPSIS066 Insulating Shield, TransferPacT, E-56
250 Amp Frame
R9XFH412 Resi9 - comb busbar - 3L+N - 18 G-34
mm TPSIS067 Insulating E-57
screen,TransferPacT,frame 630A
R9XFH418 Resi9 - comb busbar - 3L+N - 18 G-34
mm TPSISO30 Long Terminal Shields E-54
R9XFH457 Resi9 - comb busbar - 3L+N - 18 G-34 TPSISO31 Long Terminal Shields E-55
mm
TPSISO65 Interface barrier E-57
R9XFH518 Resi9 - comb busbar - 3L+N G-34
balanced - 18 mm X•••
R9XFH518G Resi9 - comb busbar - 3L+N G-34 XB5PRJ45 Panel mounted RJ45 port, G-35
balanced - 18 mm Harmony XB5
R9XFH557 Resi9 - comb busbar - 3L+N G-34 XB5PUSB3 Panel mounted USB 3.0 port, G-35
balanced - 18 mm Harmony XB5
R9XT20 Caps G-34
Z•••
S••• ZBSP1 Protection cover, Harmony XB5 G-35
SMT10015 Antenna for wireless panel I-8 ZBSP2 Protection cover, Harmony XB5 G-35
server
ZBSP3 Protection cover, Harmony XB5 G-35
SMT10016 Power supply wiring harness for I-8
wireless panel server
SMT10019 Communication module I-8
T•••
TPSAUX32 Coupling auxiliary module E-54, E-55
TPSAUX33 Coupling auxiliary module E-54, E-55
TPSAUX43 Auxiliary contact, TransferPacT E-56, E-57
TPSAUX44 Auxiliary contact, TransferPacT E-56, E-57
TPSCON47 1.5 to 35 mm² cable kit for TA25 E-56
3P
TPSCON48 1.5 to 35 mm² cable kit for TA25 E-56
4P
Version : 14 - 15/12/2023
160E1100
A-19
Overview
PrismaSeT P Active - Overview www.se.com
Contents
PrismaSeT G, Pack 250 enclosures up to 630 A - IP30, IP40, IP41, IP43, IP55 B-14
Original Manufacturer and Assembly Manufacturer: Both involved in tested assemblies B-17
Linergy offers you smart power network solutions for your switchboard. B-26
Secure power distribution and monitoring solution for operating theatres B-28
Version : 14 - 15/12/2023
160E2000 TOC B-1
PrismaSeT P Active - Reliable, Easily connected
The new PrismaSeT P Active switchboard is the market forerunner with
built-in cloud connectivity, allowing instant access to smart alarm
system, energy usage analysis, trends, and preventative maintenance
plans. Built-in cloud connectivity allows users to be notified of the
round-the-clock electrical distribution as well as voltage loss if any. This
maximizes efficiency and power availability, while creating the basis for
future innovations. The PrismaSeT P Active switchboard also allows easy
wireless integration of sensors.
Offer values
Robustness and Design • New design with new structure color, increased
frame and door robustness
Win more business • Increase the service business opportunities while
offering an affordable connected panel
Digital journey
Sheet
metal
thickness
1.5 mm
3 Hinges
B-4 TOC
Version : 14 - 15/12/2023
160E2100
PrismaSeT P Active - Performance Monitoring & Maintenance www.se.com
2 3 4
ALERT
Gateway Long Range power loss - New alert
detected on Canalis serveur.
PrismaSeT Active
Note: The voltage presence indication of the Wireless Panel Server is only indicative and cannot replace all safety measures
required before any intervention into the Low Voltage Switchboard
Version : 14 - 15/12/2023
160E2100 TOC B-5
PrismaSeT P Active - Selection guide www.se.com
Communication Architecture
General Principle
Antenna
Schneider Electric
……..
Facility Expert
Remote Energy
Monitoring Consumption
+ Management
Alarm System by using
by using Facility Expert
Facility Expert Energy*
Operation*
Fire
Prevention
PowerLogic Acti9 3 Heat Tags max.
HeatTag Active (2022)
Power
Availability
ComPacT 1 PowerLogic
OF/SD wireless PowerTag 2DI (2022)
Energy
Management
PowerLogic PowerTag Energy 15 PowerTags max
(10 if in combination
with HeatTags).
B-6 TOC
Version : 14 - 15/12/2023
160E2100
PrismaSeT P Active - Selection guide www.se.com
Communication Architecture
Main Features
LoRaWAN (Long Range Wide Area Network) is a networking protocol designed to connect
wirelessly in order to assure end-to-end communication services.
Version : 14 - 15/12/2023
160E2100 TOC B-7
www.se.com
PrismaSeT P Active - Selection guide
Communication Architecture
Built-in Gateway Wireless Panel Server built-in Check page F 15 Built in PrismaSeT P
LoRa additional length for Antenna - 5 m SMT10011 Improve the reception infront of the panel
(if needed)
Communication LoRa Tester SMT10013 Test the signal before and after installation
Accessories
In case of no reception of LoRa public
LoRa /IP Plug & Play Bridge via SIM Card SMT10024
network on your site
B-8 TOC
Version : 14 - 15/12/2023
160E2100
PrismaSeT P Active - Performance Monitoring & Maintenance www.se.com
PrismaSeT P Active
Wireless Panel Server
Version : 14 - 15/12/2023
160E2100 TOC B-9
www.se.com
PrismaSeT P Active - Performance Monitoring & Maintenance
B-10 TOC
Version : 14 - 15/12/2023
160E2100
PrismaSeT P Active - PowerLogic™ HeatTag www.se.com
Presentation
HeatTag smart sensor:
b Sends three levels of alert depending on the severity of the situation it detects.
b Helps preventpotential fire damages by analyzing gas and micro-particles emitted
by cable sheaths when overheating.
b Measures temperature and humidity.
b Communicates with all Schneider Electric EcoStruxure panel servers or gateways.
B
b Is integrated in EcoStruxure solutions.
The HeatTag sensor must be installed only in non-forced air ventilated switchboards.
It must be mounted on a DIN rail.
SMT10020 During the first 30 minutes after commissioning, HeatTag can generate an alert for
test. It then takes another 8 hours for HeatTag to define its nominal environment and
to be fully operational. Each time the HeatTag sensor is powered on, these
HeatTag is a smart sensor for early detection of 30-minute and 8-hour sequences are repeated.
overheating wire connections or overheating cables.
HeatTag helps prevent electrical switchboards from Operation
being damaged, by analyzing gas and particles
Paired with Schneider Electric panel servers or gateways, HeatTag reports:
in the air and sending alerts before any smoke or
b Alerts
insulator browning.
b Air quality index
b Temperature and humidity measurement
b Self-diagnosis information
Air Quality
HeatTag provides an air quality index, ranging from 0 to 10, and displays the air
quality evolution trend in a table.
When the air quality index is equal or above 10, HeatTag sends an alert. It has
detected abnormal cable sheath heating in the switchboard.
Detection Alert
An alert is triggered when HeatTag detects abnormal cable sheath heating in the
switchboard, which can be caused by:
b One or more loose connections (too high contact resistance)
b A poorly sized cable compared to the rated current
b Overcurrent and poorly regulated protective equipment
Alerts are triggered with three severity levels:
b Low level: a cable is slowly overheating in the installation, you must plan a
maintenance visit of the installation.
b Medium level: a cable is overheating in the installation, you must go quickly to the
installation for maintenance.
b High level: a cable overheats very quickly, you must check the installation
immediately.
The orange application led flashes when HeatTag sends an alert to the panel servers
or gateways.
Temperature
HeatTag provides a temperature value with a 30 second default transmission period.
The transmission period can be increased by the system in case of high wireless
Standards data traffic.
The HeatTag smart sensor complies
with the following standards: Humidity
b IEC 61010-1:2017 UL/CSA/EU CENELEC The HeatTag provides a humidity rate with a 30 second default transmission period.
deviations The transmission period can be increased by the system in case of high wireless
b IEC/EN 61326-1b FCC Part 15B and 15C data traffic.
b ETSI/EN 300328
b ETSI/EN 301489-1
b IEEE 802.15.4
Self-Diagnosis
HeatTag carries out two types of diagnosis:
b A minor alert is sent when the fan rpm is 80% of its nominal rpm, which means fan
clogging.
b A major alert is sent when HeatTag is faulty. In this case it cannot report measures
Note: at all, nor reports incorrect measures.
Do not use HeatTag as a safety device. HeatTag does not
replace the fire protection devices of the building.
Version : 14 - 15/12/2023
160E2100 TOC B-11
PrismaSeT P Active - PowerLogic™ HeatTag www.se.com
Electrical Characteristics
Supply voltage 110-277 V AC, -15 % / +15 %
Frequency 50-60 Hz
Max. consumption 0.1 A
Operating temperature -15 °C / +70 °C (5 °F to 158 °F)
Storage temperature -20 °C / +85 °C (-4 °F to 185 °F)
Relative humidity in operation 15-90 %
Altitude of use 0-2000 m (0-6500 ft)
Degree of pollution (IEC 60664-1) 3
Overvoltage category OVC III
Sensor Characteristics
Temperature Measurement range -15 °C / +70 °C (5 °F to 158 °F)
measurement Measurement accuracy -1.1 °C / +1.1 °C
Default transmission 30 seconds (higher in case of high
period wireless data traffic)
Humidity Measurement range 15–90 %
measurement Measurement accuracy ±9 RH %
Default transmission 30 seconds (higher in case of high
period wireless data traffic)
Air quality Index (0 to 10), alert generation when
index u 10
Test alert after pairing During the first 30 minutes
Environment auto-learning phase 8 hours after the first 30 minutes
Installation
DB436632.ai
Communication Architecture
List of compatible communicators:
b EcoStruxure Panel Servers
b PowerTag Link
b PrismaSeT Wireless Panel Server
Wiring Q1
110–277 Va
HeatTag must be protected by 2 A breaker. 2A
DB436538.ai
LN
68.5 90 107
Mechanical Characteristics
Dimensions (w x h x d) 108 x 107 x 55 mm
Weight 270 g
108 55
Degree of protection (IEC 60529) IP30
B-12 TOC
Version : 14 - 15/12/2023
160E2100
PrismaSeT P Active - PowerLogic™ HeatTag www.se.com
DB437105.ai
HeatTag must be installed following the Instruction Sheet recommendations
(MFR5173801).
MFR5173801
B
DB437101.ai
x x
x
A B C
Ref. LVS03581 and LVS04226 Ref. LVS03404, or LVS04226 Ref. LVS03581 and LVS04226
and LVS03581
DB437102.ai
x1 x1 x2 x1
(1) (1) (1) (1) (1) (2)
A B A/B A/B A C
Version : 14 - 15/12/2023
160E2100 TOC B-13
PrismaSeT P Active - Overview www.se.com
PB115624_28.eps
• Small companies
• Buildings 630 A
• Offices
• Laboratories
• Healthcare centres
• Hotels
250 A
• Supermarkets
• Malls, etc.
• Schools PrismaSeT G
• Small shops Pack 250 PrismaSeT G Active
• Hotels, etc.
B-14 TOC
Version : 14 - 15/12/2023
160E2100
PrismaSeT P Active - Overview www.se.com
4000 A
• Hospitals
• Data centres
• Logistics centres
• Shopping centres PrismaSeT P Active
• Offices buildings
• Medium industrial solutions
Version : 14 - 15/12/2023
160E2100 TOC B-15
PrismaSeT P Active - IEC 61439 standard www.se.com
The switchboard,
central to the electrical installation
Both the point of arrival of energy and a device for distribution to the site applications, the LV
switchboard is the intelligence of the system, central to the electrical installation.
It plays an essential role in the availability of electric power, while meeting the needs of personal and property safety.
Its definition, design and installation are based on precise rules; there is no place for improvisation. The IEC 61439 standard
aims to better define "low-voltage switchgear and controlgear assemblies", ensuring that the specified performances are
reached. It specifies in particular:
• the responsibilities of each player, distinguishing those of the original equipment manufacturer; the organization
that performed the original design and associated verification of an assembly in accordance with the standard,
and of the assembly manufacturer - the organization taking responsibility for the finished assembly;
• the design and verification rules, constituting a benchmark for product certification.
All the component parts of the electrical switchboard are concerned by the IEC 61439 standard. Equipment produced
in accordance with the requirements of this switchboard standard ensures the safety and reliability of the installation.
B-16 TOC
Version : 14 - 15/12/2023
160E2100
PrismaSeT P Active - IEC 61439 standard www.se.com
Specifier
• Specifies the needs and
constraints for design,
installation, operation
tion*
and upgrading of the
cifica complete system.
• Checks that its
ct spe
Assembly Manufacturer.
Depending on the
application, the specifier
could be the end-user or
a design office.
Tes
em ted
Syst As
sem
bly Assembly bly
sem
As Manufacturer
(Panel builder)
The organisation (whether
or not the same as the
OM) responsible for the
Original completed assembly.
Version : 14 - 15/12/2023
160E2100 TOC B-17
PrismaSeT P Active - IEC 61439 standard www.se.com
Safety
Voltage stresses withstand capability
To withstand long term voltages, and transient and temporary overvoltages according to the insulation
coordination principles and requirements.
Current-carrying capability
To protect against burns and to withstand temperature rise:
• when any circuit is continuously loaded, alone, to the specified current
• when the assembly is loaded to the specified current according to the specified load pattern (between circuits
and/or as a function of the time).
Short-circuit withstand capability
To withstand the stresses resulting from the prospective short-circuit current and from the associated data (High
forces between conductors, temp. rise in a very short time, air ionization, overpressure).
Protection against electric shock
• Hazardous-live-parts not to be accessible (basic protection)
• Accessible conductive parts not to become hazardous-live (fault protection).
Protection against risk of fire or explosion
• Resistance to internal glowing elements
Note: protection of persons, and optional protection of the assembly, against arcing due to internal fault can be specified through a "special test"
according to IEC 61641.
Continuity of service
Maintenance and modification capability
Capability to preserve continuity of supply without impairing safety during assembly maintenance or modification
• Electrical condition of the assembly or various circuits
• Speed of exchange of the functional units
• Test facilities…
Electro-Magnetic compatibility
To properly function (immunity) and not to generate EM disturbances (emission) in specified environmental conditions:
• Industrial networks or locations (Environment A)
• Domestic, commercial, and light industrial locations (Environment B).
B-18 TOC
Version : 14 - 15/12/2023
160E2100
PrismaSeT P Active - IEC 61439 standard www.se.com
• n
ot only self-checking to check effective Internal electric circuits and connections 11.6
tightening to torque;
Terminals for external conductors 11.7
• but also identification of any loosening.
Mechanical operation 11.8
IEC 61439-1 paragraph 11.9
Dielectric properties 11.9
Dielectric properties
The main circuits, and the auxiliary and Wiring, operating performance and function 11.10
control circuits connected to the main
circuit, shall be subjected to the test voltage
in accordance.
Date of verification:
IEC 61439-1 paragraph 11.10 ............ / ............ /.............
Wiring, operating performance and
function
Verifications performed by:
Verification of wiring and marking conformity
with the drawings, parts list and diagram. ..........................................................................…………………………
Version : 14 - 15/12/2023
160E2100 TOC B-19
PrismaSeT P Active - Overview www.se.com
• Available power
• Safety of people
and property
• Controlled costs
and delivery times
• Upgradeability
B-20 TOC
Version : 14 - 15/12/2023
160E2100
PrismaSeT P Active - Overview www.se.com
Prefabricated
connections
Front plate
Connection transfer
assemblies
Version : 14 - 15/12/2023
160E2100 TOC B-21
PrismaSeT P Active - Overview www.se.com
PD390150_SE_R.eps
Configuration 6 - v2.png
B-22 TOC
Version : 14 - 15/12/2023
160E2100
PrismaSeT P Active - Overview www.se.com
PB115600_56.eps
B
Version : 14 - 15/12/2023
160E2100 TOC B-23
PrismaSeT P Active - Overview www.se.com
B-24 TOC
Version : 14 - 15/12/2023
160E2100
PrismaSeT P Active - Overview www.se.com
• Live upgrading.
Version : 14 - 15/12/2023
160E2100 TOC B-25
PrismaSeT P Active - Overview www.se.com
B-26 TOC
Version : 14 - 15/12/2023
160E2100
PrismaSeT P Active - Overview www.se.com
Linergy FC
Quick distribution blocks
• ComPacT NSXm (4 x 4P / 5 x 3P) solution
• ComPacT NSX (3 x 4P / 4 x 3P) solution
• Reliable connection
• Quick connection system dedicated to
ComPacT NSXm up to 160A / ComPacT NSX
up to 250 A
• Simplicity of use
• Quick connection system dedicated to
ComPacT NSXm up to 160A / ComPacT NSX
up to 250 A
Linergy TR
Terminal blocks and bars
• Simplicity of use
• Consistency and cross-functionality
guaranteed
page G-40
Version : 14 - 15/12/2023
160E2100 TOC B-27
PrismaSeT P Active - Overview www.se.com
B-28 TOC
Version : 14 - 15/12/2023
160E2100
Green Premium
TM
certifications
30 Version : 14 - 15/12/2023
160E3000
PrismaSeT P Active - Standards and certifications www.se.com
Contents
Enclosure characteristics
Properties of metal enclosures C-7
Specific application
PrismaSeT P Active Seismic
Specific application C-17
Seismic kit C-18
Installation conditions C-19
Version : 14 - 15/12/2023
160E3000 TOC C-1
PrismaSeT P Active - Standards and certifications www.se.com
Standards
Regional standardization systems
b either a European standard (EN), often identical to the IEC standard, which then
Worldwide becomes the applicable national standard in all the member countries
b or, in the event of differences, a harmonisation document (HD).
Other IEC member countries
Each country is autonomous and can accept the IEC standard as the national
Other IEC standard, with or without modifications.
member Even though they are IEC members, countries such as Japan and the United States
countries continue to develop their own standardisation systems.
Countries without a standardisation system
It is possible to refer to an IEC standard in the framework of a project.
Countries
CEI / IEC
Commission Electrotechnique Internationale
CENELEC
Comité Européen de Normalisation ELECtrotechnique
UTE
Union Technique de l’Électricité
VDE
Verband der Elektrotechnik, Elektronik und Informationstechnik
e.v. (German electrotechnical, electronics and computer
technology standardisation organisation)
BSI
British Standards Institution
C-2 TOC
Version : 14 - 15/12/2023
160E3100
PrismaSeT P Active - Standards and certifications www.se.com
Standards
Standards types
Management standards
Dd381775.eps
Dd381776.eps
Dd381778.eps
v The majority of Schneider Electric development centres and factories are certified
ISO 9001 and ISO 14001.
Installation standards
The set of IEC 60364-X standards defines the main principles and rules on:
b determining general characteristics of installations
b protection
b selection and installation of equipment
Switchgear and controlgear. Installation.
b verification and maintenance of installations.
Product standards
They apply to devices or assemblies and are aimed at ensuring correct operation
and safety of the concerned products.
b standards on low-voltage switchgear and controlgear:
v IEC 60947-1: general rules
v IEC 60947-2: circuit breakers
v IEC 60947-3: switches and disconnectors
v IEC 60947-4: contactors
v IEC 62208: empty enclosures.
b standards on low-voltage switchgear and controlgear assemblies:
v IEC 61439-1: general rules
v IEC 61439-2: power switchgear and controlgear assemblies
v IEC 61439-3: distribution boards
v IEC 61439-4: assemblies for construction sites
v IEC 61439-5: assemblies for power distribution
v IEC 61439-6: busbar trunking systems.
Regulations in a given country may make certain standards legally binding and may
also create additional safety requirements.
Version : 14 - 15/12/2023
160E3100 TOC C-3
PrismaSeT P Active - Standards and certifications www.se.com
Standards
Consequences:
b the PrismaSeT P Active range falls under the LV directive only
b LV switchboards are covered by the LV directive and may also fall under the EMC
directive, depending on the type of devices incorporated.
e
For the PrismaSeT P Active range, e marking is applied:
b on the packing of “mechanical” components
b on the product itself for “electrical” components.
For the LV assemblies created by the panelbuilder, e marking is applied:
b on the packing
b on the rating plate (if applicable)
b on one of the documents accompanying the switchboard when it is shipped.
C-4 TOC
Version : 14 - 15/12/2023
160E3100
PrismaSeT P Active - Standards and certifications www.se.com
Standards
IP code Standard IEC 60529 (IP code, February 2001) indicates the degrees of protection
provided by an enclosure for electrical devices against access to hazardous parts,
against penetration of solid foreign objects and against penetration of water.
These standards do not apply for the protection against the risks of explosion or
conditions such a humidity, corrosive vapour, fungus or vermin.
The IP code is made up of two characteristic numerals and can include an additional
letter when the actual protection for persons against access to the hazardous parts is
better than that indicated by the first numeral.
The first numeral characterises the protection provided against the ingress of solid
foreign objects and the protection of persons.
The second numeral characterises the protection provided against the ingress of
water with harmful effects.
C
1st numeral 2nd numeral
Protection of persons Protection against ingress of solid Protection against ingress of water
objects
1 Protected against Protection against
1 Protected against
Dd381959.eps
Dd381959.eps
Dd381966.eps
access with back of solid foreign objects vertically dripping
hand larger than 50 mm water (condensation)
Dd381963.eps
Dd381967.eps
access with a finger solid foreign objects dripping water up to
larger than 12.5 mm 15° from vertical
Dd381961.eps
Dd381968.eps
access with a tool solid foreign objects spraying water up to
larger than 2.5 mm 60° from vertical
Dd381962.eps
Dd381969.eps
Dd381964.eps
Dd381970.eps
Dd381965.eps
Dd381971.eps
effects of temporary
immersion in water
effects of continuous
immersion in water
Version : 14 - 15/12/2023
160E3100 TOC C-5
PrismaSeT P Active - Standards and certifications www.se.com
Standards
IP Code The additional letter is used only if the actual protection of persons is higher than that
indicated by the first characteristic numeral of the IP code.
If only the protection of persons is of interest, the two characteristic numerals are
replaced by the letter “X”, e.g. IPXXB.
Illustration of the above explanations:
Protection against solid foreign objects
larger than 2.5 mm
No protection
IP30D
Protected against access
with a 1 mm diameter wire
Remarks
b The degree of protection IP must always be read and understood numeral by
numeral and not as a whole.
For example, an IP31 wall-mount enclosure is suitable for an environment that
requires a minimum degree of protection IP21. However an IP30 wall-mount
enclosure is not suitable.
b the degrees of protection indicated in this catalog are valid for the enclosures as
presented. However, the indicated degree of protection is guaranteed only when
installation and device mounting are carried out in accordance with professional
standards that conserve the initial degree of protection.
IK code Standard IEC 62262 defines an IK code characterising the capacity of products to
resist mechanical impacts from all sides.
IK code Impact energy (joules)
01 0.14
02 0.2
03 0.35
04 0.5
05 0.7
06 1
07 2
08 5
09 10
10 20
C-6 TOC
Version : 14 - 15/12/2023
160E3100
PrismaSeT P Active - Standards and certifications www.se.com
Enclosure characteristics
Anti-corrosion withstand Schneider Electric enclosures comply with standard IEC 62208, EN 50298 for empty
enclosures. The sheet metal used for Schneider Electric enclosures receives an
anti-corrosion cataphoresis primer treatment and a coating of a thermosetting,
polyester-resinmodified epoxy powder for colour and appearance.
This two-coat system provides excellent finish and corrosion protection.
The characteristics of this coating are much better than those of traditional epoxy
powders:
b improved colour stability
b wider operating temperature range.
Version : 14 - 15/12/2023
160E3200 TOC C-7
PrismaSeT P Active - Standards and certifications www.se.com
Enclosure characteristics
Chemical properties of powder Tests carried out at ambient temperature on phosphated test pieces coated
with a 150 to 200 micron film.
coating
Test duration (months) 2 4 6 8 10 12
Acids Concentration
Acetic 20 %
Sulphuric 30 %
Nitric 30 %
Phosphoric 30 %
Hydrochloric 30 %
Lactic 10 %
Citric 10 %
Bases Soda 10 %
Ammonia 10 %
Water Distilled water
Seawater
Tap water
Diluted bleach
Solvents Petrol
High alcohols
Aliphatics
Aromatics
Ketones, esters
Tri-perchlorethylene
Film intact.
C-8 TOC
Version : 14 - 15/12/2023
160E3200
PrismaSeT P Active - Standards and certifications www.se.com
Dd381483.eps
Dd381482.eps
Dd381481.eps
IP > 31 IP y 31 IP y 54 IP y 31
Forced-air Forced
ventilation with convection and
air-air exchanger cooling
Dd381920.eps
Dd381921.eps
IP > 31 IP > 31
On special request.
For these extreme cases, many installers prefer to set up the switchboards with
other electrotechnical and electronic devices in air-conditioned electrical rooms.
Heating
The means employed to raise the internal temperature in a switchboard is a
resistor-based heater, used to:
b avoid condensation by limiting variations in temperature
b ensure that the switchboard does not freeze.
Version : 14 - 15/12/2023
160E3200 TOC C-9
PrismaSeT P Active - Standards and certifications www.se.com
This IEC guide for switchboards proposes a calculation method to determine three
levels of internal temperature, depending on the dissipated power of the devices and
distribution blocks installed in the switchboard.
Users can consult this document when it is necessary to determine precisely the
internal temperature in view of optimising the switchboard.
On request, Schneider Electric can carry out a thermal study to check that the
installed assembly and the thermal capacity of the enclosure are compatible.
Comparative method
DD381350.eps
A number of qualified and tested configurations serve as the basis for indicating the
thermal capacity of PrismaSeT P Active enclosures.
This is en empirical means to check whether the dissipated power of the desired
configuration is close to that of a tested configuration.
For details on the calculation of the dissipated power in the device zone,
see page C-12.
C-10 TOC
Version : 14 - 15/12/2023
160E3200
PrismaSeT P Active - Standards and certifications www.se.com
DD385996.eps
wide, 400 mm deep, IP30
LGY
Diversity factor: 0.7 and 0.8
Ambient temperature around the switchboard: 35 °C NT1600
Cubicle 1 : P(W) of device zone = 580 W & MTZ1
NSX250
C
Linergy FM
NSX400
Linergy LGY
wide, 1000 mm deep, two 300 mm wide ducts, IP30
Diversity factor: 0.7
Ambient temperature around the switchboard: 35 °C
NSX400
Cubicle 1 : P(W) of device zone = 880 W NW32H1
& MTZ2
Cubicle 2 : P(W) of device zone = 330 W
NSX630
Version : 14 - 15/12/2023
160E3200 TOC C-11
PrismaSeT P Active - Standards and certifications www.se.com
DD385995.eps
wide, 1000 mm deep, two 300 mm wide ducts, IP30
Diversity factor: 0.7
Ambient temperature around the switchboard: 35 °C
NT1600
Cubicle 1 : P(W) of device zone = 580 W & MTZ1
NSX250
Linergy FM 200 A
NSX400
Application of the diversity factor In the configuration below, the standardised diversity factor (K div.) for a total of 14
outgoing circuits is 0.6, i.e. 60 % of In for each outgoing circuit.
Schneider Electric prefers a more conservative approach and therefore divides the
installation into four main circuits:
b ComPacT NSX250
b 200 A Linergy FM: 8 outgoers V K div. = 0.7
b Linergy FC: 4 outgoers V K div. = 0.8
b ComPacT NSX400.
1 ComPacT NSX250 + 1 Linergy FM 200 A + 1 Linergy FC + 1 ComPacT NSX400 V
4 outgoers, i.e. a diversity factor of 0.8.
As a result, the current flowing in each circuit is at least 70 % and up to 80 % of In.
Calculation of the power dissipated by Dissipated power of the NT1600 & MTZ1 indicated by the manufacturer: 460 W. The
power dissipated by the connections is approximately 30 % of the device P(W):
devices in the incoming cubicle 0.3 x 460 = 138 W.
Power of circuit breaker + connections = 460 + 138 = 598 W at 1600 A.
For I² (the Watts are proportional to the square of the current) at 1410 A
(In of the incoming device):
54.6 x
2002 = 35 W
2502
Dissipated power of the Linergy FC and its four ComPacT NSX250 circuit breakers:
4 x 35 W (same calculation as above) = 140 W
C-12 TOC
Version : 14 - 15/12/2023
160E3200
PrismaSeT P Active - Standards and certifications www.se.com
DD382423.eps
C
Draw a line parallel to the others on the chart and read the corresponding difference
in temperature.
For the given example, the heat rise is 22 °C at mid-height in the enclosure.
The internal temperature = external temperature + heat rise
= 35 °C + 22 °C = 57 °C
57 °C < 60 °C stipulated by the standard, i.e. the result is acceptable for an IP3
cubicle.
This gives roughly: Internal temperature = 60 °C at mid-height in the enclosure for a
low IP value.
Internal temperature = 70 °C at mid-height in the enclosure for a high IP value.
Version : 14 - 15/12/2023
160E3200 TOC C-13
PrismaSeT P Active - Standards and certifications www.se.com
DD382424.eps
DD382425.eps
For the enclosures not mentioned on the previous
pages, use the equation:
P
DT =
SxK
where:
DT: internal temperature - external temperature
P: power dissipated by the devices, connections and
busbars (in Watts)
S: total free surface area of the enclosure (expressed
in m²)
K: thermal-conduction coefficient of the material
(W/m² °C) IP3X cubicle, 800 mm deep IP3X cubicle, 1000 mm deep
DD382426.eps
DD382427.eps
K = 5.5 W/m² °C for painted sheet metal.
DD382429.eps
DD382431.eps
C-14 TOC
Version : 14 - 15/12/2023
160E3200
PrismaSeT P Active - Standards and certifications www.se.com
D = 3.1 x ( P
DT )
- KS
The chart below can be used to determine the necessary throughput, based on the
dissipated power, the difference in temperature (internal - external) and the exposed
surface area of the enclosure.
Example
Consider an IP3X cubicle, 650 mm wide and 400 mm deep, containing components
(devices, connections, busbars, etc.) dissipating 1000 W.
The ambient temperature around the cubicle is 50 °C.
Given that the average temperature at mid-height should not exceed 60 °C, the
C
difference in temperature DT is equal to 60 - 50 = 10 °C.
The exposed surface of the cubicle (non adjacent to a wall or other cubicle) is
4.46 m².
(back = 1.3 m², front = 1.3 m², roof = 0.26 m², side panels = 1.6 m²).
What is the necessary throughput of the ventilation system?
The throughput can be calculated as:
D = 3.1 x (
1000
10
- 5.5 x 4.46 )
D = 234 m3/h.
In the range of PrismaSeT P Active accessories, select a system with a throughput
of 300 m3/h.
Ref: LVS08710
Calculation data
P: power dissipated by the devices, connections and busbars (in Watts)
Pr: power of the heating resistor (in Watts)
Tm: maximum internal temperature in the device zone (in °C)
Ti: average internal temperature (in °C)
Te: average external temperature (in °C)
DTm = Tm – Te
DT = Ti– Te
S: total free surface area of the enclosure (expressed in m2)
K: thermal-conduction coefficient of the material (W/m2 °C)
K = 5.5 W/m2 °C for painted sheet metal
D: ventilation throughput (in m3/h)
Version : 14 - 15/12/2023
160E3200 TOC C-15
PrismaSeT P Active - Standards and certifications www.se.com
Dd381788.eps
Chart to determine the heating resistor for all types of enclosures and cubicles
Dd381789.eps
Calculation data
P: power dissipated by the devices, connections and busbars (in Watts)
Pr: power of the heating resistor (in Watts)
Tm: maximum internal temperature in the device zone (in °C)
Ti: average internal temperature (in °C)
Te: average external temperature (in °C)
DTm = Tm – Te
DT = Ti– Te
S: total free surface area of the enclosure (expressed in m2)
K: thermal-conduction coefficient of the material (W/m2 °C)
K = 5.5 W/m2 °C for painted sheet metal
D: ventilation throughput (in m3/h).
C-16 TOC
Version : 14 - 15/12/2023
160E3200
PrismaSeT P Active - Standards and certifications www.se.com
Specific application
Seismic zone
Around the world can be found
different zones with a specific
seismic risk.
These zones have been classified
according to the Uniform Building
Code (UBC).
Classification
From weak to strong earthquakes, PrismaSeT P Active has been tested in the following ground accelerations to
guarantee the right performance on seismic risk.
IEC 60068 -3-3 Seismic characteristics
Ground acceleration
References General description Richter scale magnitude MSK Intensity UBC Zone
AG2 Intensity from weak to average < 5 .5 < VIII 0
1
AG3 Intensity from average to strong 5.5 to 7.0 VIII to IX 2 3
AG5 Intensity from strong to very strong > 7.0 > IX 4
10 10
DB421393.eps
DB421392.eps
PrismaSeT
PrismaSeT
2.5
2
1.6
1 1
Acceleration (in g)
Acceleration (in g)
0.7
0.5
0.1 0.1
0.01 0.01
2 Frequency (Hz) 20 2 Frequency (Hz) 20
Version : 14 - 15/12/2023
160E3200 TOC C-17
PrismaSeT P Active - Standards and certifications www.se.com
Specific application
Reinforcement
PrismaSeT P Active seismic cubicles are 2.5 g compliant.
Special parts have been created, specific reinforced side panels and bottom reinforcement
brackets.
Reinforced side panels Seismic reinforcement brackets
Ref: LVS08765D Ref: LVS08710
To respect seismic withstand, use side panels in Foot part to be added in each bottom angle to
IP55 version (even with an IP30 switchboard). reinforce the structure.
C-18 TOC
Version : 14 - 15/12/2023
160E3200
PrismaSeT P Active - Standards and certifications www.se.com
Specific application
PrismaSeT P Active cubicle frames
PrismaSeT P Active cubicle frames have to be assembled according to the mounting instructions (04696505)
and must respect the tightening torque and association screws position.
Functional units have to be assembled according to the mounting instructions supplied with each reference.
Fixingpointsto ground
650 300
Structure fixing points 400 400 650 300
400 400
u M10
Sizes to respect
Dimensional specifications have to be taken into account for the switchboard sizes and busbar ratings.
Switchboard sizes: Maximum busbar ratings:
> Minimum switchboard width (1) = 1200 mm 3P 4P
> Minimum cubicle depth = 400 mm Horizontal Linergy BS 2b 80 x 10 2b 80 x 10
> Height = 2000 mm Horizontal Linergy LGYE LGYE 4000 LGYE 4000
Nota: Seismic switchboards must not be installed with any plinth.
(1) Switchboard must be equipped with horizontal busbars
NT / NW
PFC
MTZ1/MTZ2
NT / NW
MTZ1/MTZ2 NSX PFC
Yes No
PFC
NT / NW > C able entry : > C onnection
MTZ1/MTZ2 top/bottom to busways
Fuses
> T ransparent door > P linth 100 mm
PFC or 2 x 100 mm
> IP 30/31
> IP55
NOTICE
HAZARD OF STRUCTURAL FAILURE
Seismic cubicles must have the same depth. Plinths are not allowed in seismic configurations
Failure to follow these instructions can result in equipment damage
Version : 14 - 15/12/2023
160E3200 TOC C-19
Selection guide
PrismaSeT P Active - Selection guide www.se.com
Contents
Selection guide
Select a cubicle configuration D-2
Version : 14 - 15/12/2023
160E4000 TOC D-1
PrismaSeT P Active - Selection guide www.se.com
DD384077.eps
IP30 switchboard
NSX250 NSX250 NSX250 INS
NS1000
Order 4P 33597
Dd380822.eps
connections
b connection 2 Linergy LGY BB conn. Linergy LGY
Device Toggle
accessories. NSX100/250, Vigi NSX100/250
DD380873.eps
3P 4P
Prefabricated connection 04423 04424
Device Toggle
3 Connection NSX100/160 Vigi NSX100/160 NSX250
Number of device per row 3/4 3/4 3/4
DD380874.eps
modules]
b connection
Linergy LGY
accessories. 2 Linergy LGY BB conn. Device Toggle
NSX100/160, Vigi NSX100/160 NSX250, Vigi NSX250
3P 4P 3P 4P
DD380876.eps
Number of devices 4 3 4 3
Linergy FC distribution blocks 04403 04404 04403 04404
(with connection)
Device Toggle
3 Connection NSX100/160, Vigi NSX100/160 NSX250, Vigi NSX250
3P 4P 3P 4P
DD380877.eps
D-2 TOC
Version : 14 - 15/12/2023
160E4100
PrismaSeT P Active - Selection guide www.se.com
Install the modular devices 1 Acti 9 Device All modular devices Modular devices y 40 A
See page E-63 Rail length (modules of 9 mm) 48 48
Order the No. of vertical modules 4 3
DD385316.eps
mounting Rail (48 modules of 9 mm) 03401 03401
Modular front plates 03204 [4] 03203 [3]
Dd385315.eps
plates and
Prisma P Functional units
Select the enclosures 1 Frameworks Device 300 400 650 800 800 (650 + 150)
Base frame
See page F-1 Cat. no 08403 08404 08406 08408 08407
08564 08566
SeT
Cat. no
Prisma
Plan the distribution system Linergy LGY busbars Intensity (A) Linergy LGY profils Number of busbars supports
for table Icw (kA rms/1s)
See page G-1 1 See page G-4 IP y 31 IP > 31 25 30 40 50 60 65 75 85
630 04502
DD380880.eps
04503
Dd385317.eps
Linergy distribution systems
800 04503
04504 3
1000 04504
2 Linergy BW busbars
2
2 10mm
2 6mm
2 10mm
2 6mm
10mm
Version : 14 - 15/12/2023
160E4100 TOC D-3
www.se.com
Functional units
2 TOC
Version : 14 - 15/12/2023
160E5000
PrismaSeT P Active - Functional units www.se.com
Contents
Circuit breakers
MasterPacT MTZ2
Cables connection E-2
Canalis connection E-4
Dedicated cubicle E-6
Partial front plate support frames E-8
MasterPacT MTZ1
Toggle and motor mechanism - Cables connection E-10
Dedicated cubicle 3P E-12
ComPacT NS1600b to 3200
Cables connection E-14
ComPacT NS630b to NS1600
Canalis connection E-16
Horizontal mounting E-17
Dedicated cubicle E-18
ComPacT, ComPacT Vigi (ELCB) and VigiComPacT NSX
NSX 100 to 630 - Horizontal mounting E-20
NSX 400/630 - Vertical mounting E-25
NSX 100 to 630 - Vertical mounting W = 400 mm E-30
NSX 100/160/250 - Vertical mounting E-31
ComPacT NSXm up to 160
Horizontal mounting, vertical mounting, modular devices E-35
Switch-disconnectors E
ComPacT INS-INV630b to 2500
Vertical fixed mounting E-39
ComPacT INS-INV250 to 630
Horizontal / Vertical fixed mounting E-40
Source-changeover
MasterPacT MTZ1 06/16 E-41
MasterPacT MTZ2 08/32 E-42
ComPacT NS630b to 1000 E-49
ComPacT NSX100/630 E-50
ComPacT INS-INV250 to 630 - Front direct rotary handle E-52
ComPacT INS-INV250 to 630 - Complete assembly device E-53
Changeover System
TransferPacT
TransferPacT Frame 100A E-54
TransferPacT Frame 160A E-55
TransferPacT Frame 250A E-56
TransferPacT Frame 630A E-57
Fusegear
Fupact ISFL E-58
Fusegear/Switch-disconnector
Fupact ISFT E-59
Fupact GS E-60
Others
Power factor correction equipment E-61
Industrial control devices E-62
Modular devices
Acti 9 y 63 A, 80/160 A switchboard incomer E-63
Metering (Single-phase and 3-phase kilowatt-hour meters) E-65
Human-switchboard interface (PowerLogic™ Meters) E-67
Version : 14 - 15/12/2023
160E5000 TOC E-1
PrismaSeT P Active - Functional units www.se.com
MasterPacT MTZ2 08 to 32
Cables connection
Fixed, withdrawable
Circuit breakers
Mounting Front connection
60 150 60 300
0 650 0 650
Dd383686.eps
Devices Fixed device Withdrawable device
MTZ2 08/16 MTZ2 20/32 MTZ2 08/16 MTZ2 20/32
Number of devices per row 1 1 1 1
No. of vertical modules (1) 18 19 19 20
Mounting plates LVS03500 LVS03500 LVS03500 LVS03500
Front plates upstream LVS03804 [4] LVS03805 [5] LVS03804 [4] LVS03805 [5]
[No. of vertical with cut-out LVS03711 [9] LVS03711 [9] LVS03710 [10] LVS03710 [10]
modules] downstream LVS03805 [5] LVS03805 [5] LVS03805 [5] LVS03805 [5]
40 40
0
60 150 0
60 300
0 650 0 650
Dd383686.eps
E-2 TOC
Version : 14 - 15/12/2023
160E5100
PrismaSeT P Active - Functional units www.se.com
MasterPacT MTZ2 08 to 32
Cables connection
Fixed, withdrawable
Circuit breakers
Distribution Downstream on Linergy LGY, LGYE or BS busbars
DD385815.eps
G
FE
D
C
B
A
Devices Fixed and withdrawable Fixed and withdrawable Fixed and withdrawable
MTZ2 08/16 MTZ2 20/25 MTZ2 32
3P 4P 3P 4P 3P 4P
Type of terminals Front connections supplied with the device.
For vertical busbar Connection Must be made according to the busbar drawings supplied by Schneider Electric.
Linergy BS Joint - - Order one joint per phase: 1 joint for busbars, W = 50/60 mm (LVS04640),
1 joint for busbars, W = 80/100 mm (LVS04641).
Free support 2 x LVS04662
DD385818.eps
For vertical busbar Connection LVS04493 LVS04494 must be made according to the busbar drawings supplied by Schneider Electric.
Linergy LGY Joint LVS04683 LVS04684 -
Free support - - 2 x LVS04662
DD385817.eps
(1) For LGYE 08/25, use a duct W = 150 mm. For LGYE 32/40, use a duct W = 300 mm.
(2) One additional module is required, select LVS03806 plain front plate for downstream.
Version : 14 - 15/12/2023
160E5100 TOC E-3
PrismaSeT P Active - Functional units www.se.com
MasterPacT MTZ2 08 to 32
Canalis connection
Fixed, withdrawable
Circuit breakers
Mounting Front connection
60 150 60 300
0 650 0 650
Dd383686.eps
Devices Fixed device Withdrawable device
MTZ2 08/16 MTZ2 20/32 MTZ2 08/16 MTZ2 20/32
Number of devices per row 1 1 1 1
No. of vertical modules (1) 27 28 27 28
Mounting plates LVS03500 LVS03500 LVS03500 LVS03500
Front plates upstream LVS03805 [5] 2 x LVS03805 [10] 3 x LVS03804 [12] LVS03805 [5]
[No. of vertical 2 x LVS03804 [8] LVS03804 [4] 2 x LVS03804 [8]
modules] with cut-out LVS03711 [9] LVS03711 [9] LVS03710 [10] LVS03710 [10]
downstream LVS03805 [5] LVS03805 [5] LVS03805 [5] LVS03805 [5]
40 40
0
60 150 0
60 300
0 650 0 650
Dd383686.eps
Dd383683.eps
E-4 TOC
Version : 14 - 15/12/2023
160E5100
PrismaSeT P Active - Functional units www.se.com
MasterPacT MTZ2 08 to 32
Canalis connection
Fixed, withdrawable
Circuit breakers
Distribution Downstream on Linergy LGY, LGYE or BS busbars
DD385815.eps
G
FE
D
C
B
A
For vertical busbar Connection LVS04493 LVS04494 must be made according to the busbar drawings supplied by Schneider Electric.
Linergy LGY Joint LVS04683 LVS04684 -
Free support - - 2 x LVS04662
For Icw u 75 kA rms, add an additional free support LVS04662.
DD385817.eps
For vertical busbar Connection - - LVS04495 LVS04496 LVS04497 (2) LVS04498 (2)
Linergy LGYE (1)
(1) For LGYE 08/25, use a duct W = 150 mm. For LGYE 32/40, use a duct W = 300 mm.
(2) One additional module is required, select LVS03806 plain front plate for downstream.
Version : 14 - 15/12/2023
160E5100 TOC E-5
PrismaSeT P Active - Functional units www.se.com
MasterPacT MTZ2 08 to 40
Dedicated cubicle - W = 650 mm
Fixed, withdrawable
Circuit breakers
Mounting Dedicated cubicle
Dd384530.eps
60
0 650
E-6 TOC
Version : 14 - 15/12/2023
160E5100
PrismaSeT P Active - Functional units www.se.com
MasterPacT MTZ2 08 to 40
Dedicated cubicle - W = 650 mm
Fixed, withdrawable
Circuit breakers
Distribution Downstream up links on horizontal busbars
Linergy LGYE Linergy BS
Dd384529.eps
Fixed / withdrawable devices MTZ2 08/16 MTZ2 20/25 MTZ2 32 MTZ2 40 (1) MTZ2 08/25 MTZ2 32 MTZ2 40 (1)
Type of Front connection Front connection
terminals
E
(4)
Accessories
DD381316.eps
DD381581.eps
Cross-members
Catalog number LVS03584 LVS03586
Characteristics Set of 2 Set of 2
For 650 mm wide and 400 mm deep cubicle W = 200 mm, can be added to the 400 mm cross-members
for frameworks that are 600 mm deep. They can also be
installed separately
(1) Contact Schneider Electric for 4000 A dedicated cubicle.
(2) Connection to be made according to the busbar drawings supplied by Schneider Electric.
(3) Catalog number LVS04637 includes 1 connection only. Order 1 connection per phase.
(4) The cover is compulsory behind front plates designed for measurement devices.
Version : 14 - 15/12/2023
160E5100 TOC E-7
PrismaSeT P Active - Functional units www.se.com
MasterPacT MTZ2 08 to 32
Partial front plate support frames
Withdrawable
Circuit breakers
Mounting Front connection with cables in dedicated cubicle
Dd383723.eps
60
0 650
DD385539.eps
60
0 650
DD385539.eps
E-8 TOC
Version : 14 - 15/12/2023
160E5100
PrismaSeT P Active - Functional units www.se.com
MasterPacT MTZ2 08 to 32
Partial front plate support frames
Withdrawable
Circuit breakers
Mounting Rear connection with cables
Dd383682.eps
40
0
60
0 650
DD385539.eps
`
Devices Withdrawable device
MTZ2 08/32
No. of vertical modules 15 (3)
Mounting plates LVS03500
Front plates upstream -
[No. of vertical with cut-out LVS03709 [10]
modules]
downstream LVS03804 [4]
1/3 front plate support frame LVS08560 (1) + 2 x LVS08562 (2)
(1) 1/3 front plate support frame 10 modules.
(2) 1/3 front plate support frame 12 modules.
(3) Modularity includes the space of one module between each front plate support frame.
Version : 14 - 15/12/2023
160E5100 TOC E-9
PrismaSeT P Active - Functional units www.se.com
MasterPacT MTZ1 06 to 16
Cables connection
Toggle, motor mechanism - Fixed, withdrawable
Circuit breakers
Mounting Front connection with cables
40 150
0 650
Dd380794.eps
Devices Fixed device Withdrawable device
MTZ1 06/10 MTZ1 12/16 MTZ1 06/10 MTZ1 12/16
Number of devices per row 1 1 1 1
No. of vertical modules 12 14 13 15
Mounting plates LVS03484 LVS03484 LVS03483 LVS03483
Front plates upstream LVS03802 [2] LVS03804 [4] LVS03802 [2] LVS03804 [4]
[No. of vertical with cut-out LVS03692 [7] LVS03692 [7] LVS03691 [8] LVS03691 [8]
modules] downstream LVS03803 [3] LVS03803 [3] LVS03803 [3] LVS03803 [3]
40
150
Dd380796.ai
04
00 650
E-10 TOC
Version : 14 - 15/12/2023
160E5100
PrismaSeT P Active - Functional units www.se.com
MasterPacT MTZ1 06 to 16
Canalis connection
Toggle, motor mechanism - Fixed, withdrawable
Circuit breakers
Mounting Canalis front connection
40 150
0 650
Dd380795.eps
Devices Fixed device Withdrawable device
MTZ1 06/12 MTZ1 16 MTZ1 06/12 MTZ1 16
Number of devices per row 1 - 1 -
No. of vertical modules 17 - 18 -
Mounting plates LVS03484 - LVS03483 -
Front plates upstream LVS03804 [4] + LVS03803 [3] - LVS03804 [4] + LVS03803 [3] -
[No. of vertical modules] with cut-out LVS03692 [7] - LVS03691 [8] -
downstream LVS03803 [3] - LVS03803 [3] -
40
04 150
00 650 Dd383683.eps
Version : 14 - 15/12/2023
160E5100 TOC E-11
PrismaSeT P Active - Functional units www.se.com
MasterPacT MTZ1 06 to 16
Dedicated cubicle 3P - W = 400 mm
Fixed, withdrawable
Circuit breakers
Mounting
Dd382506.eps
400
Measurement-device installation
Measurement devices are installed on a front plate (LVS03723) using plastic mounting plates with cut-outs. The front plate can hold:
b six 72 x 72 mm cases
b or four 96 x 96 mm cases + 2 switches
b or two 96 x 96 mm cases + 2 switches (2)
Number and type of devices Metal front plate with No. of Plastic Blanking plate
per row cut-out vertical mounting or device support
modules plates
with
cut-out
Mounting on interface with plastic mounting plates
To blank-off or install:
DD385465.eps
DD385466.eps
- from 1 to 4 buttons Ø 16 or 22 mm
Dd382670.eps
- 1 device 45 x 45
Vigirex and other
3x 72 x 72 devices 72 x 72
without switch
LVS03902 LVS03900
60
13
To blank-off or install:
40
DD385467.eps
DD385468.eps
60
40 10 A
0
A
- 1 to 4 buttons Ø 16 or 22 mm
10
2x
devices 96 x 96 - 1 device 45 x 45
or 96 x 96 - 1 device 72 x 72
1x For PM200, 200P, PM5
(2) & PM8 series meters
LVS03723 LVS03903 LVS03901
Characteristics b Installation of three devices (72 x 72 mm cases) using plastic mounting plates (LVS03902) and two devices (96 x 96
mm cases) + a switch using plastic mounting plates (LVS03903) on a hinged front plate (LVS03723)
b The plain mounting plates have knock-outs for lamps, pushbuttons, switches or devices.
Knock-outs for LVS03900: 4 Ø 16 mm, 5 Ø 22 mm or one for a 45 x 45 mm device.
Knock-outs for LVS03901: 4 Ø 16 mm, 5 Ø 22 mm or one for a 45 x 45 or 72 x 72 mm device.
(1) Hinged or reversible (left or right-hand opening) front plates connect directly to the framework, without a front-plate support frame.
(2) For PM200, 200P, PM5 & PM 8 series meters, use 1 no. blank-off sheet with each meter in a row.
E-12 TOC
Version : 14 - 15/12/2023
160E5100
PrismaSeT P Active - Functional units www.se.com
MasterPacT MTZ1 06 to 16
Dedicated cubicle 3P - W = 400 mm
Fixed, withdrawable
Circuit breakers
Connection Upstream on incomer
Dd382672_1.eps
Dd382669.eps
Devices Fixed device Withdrawable device
MTZ1 06 to MTZ1 16
Type of Front connection Front connection
terminals
Arc-chute 47335 -
cover
Accessories
Dd382513.eps
Dd382514.eps
W = 400
4 cable tie supports for framework LVS08774
D = 400
LVS08794
D = 600
LVS08794 + LVS08796
E
(1) Vertical connection adapters and cable-lug adapters are not compatible with input voltage u 500 V.
DD383814.eps
DD385890.eps
Support 2 x LVS04692 For MTZ1 H1 & H2 2 x LVS04692 For MTZ1 H1 & H2 LVS04662
3 x LVS04692 For MTZ1 H3 3 x LVS04692 For MTZ1 H3
Barrier (1) LVS04855 LVS04855 LVS04855
Version : 14 - 15/12/2023
160E5100 TOC E-13
PrismaSeT P Active - Functional units www.se.com
150
Dd385439.eps
40
650 60 150
0 0 650
NS1600b NS2000/3200
E-14 TOC
Version : 14 - 15/12/2023
160E5100
PrismaSeT P Active - Functional units www.se.com
40 150
0 650
DD383692.ai
Devices Fixed device Withdrawable device
NS630b/1000 NS1250/1600 NS630b/1000 NS1250/1600
Number of devices per row 1 1 1 1
No. of vertical modules 12 14 13 15
Mounting plates LVS03482 LVS03482 LVS03483 LVS03483
Front plates upstream LVS03802 [2] LVS03804 [4] LVS03802 [2] LVS03804 [4]
[No. of vertical modules] with cut-out LVS03690 or LVS03701 (1) [7] LVS03691 [8] LVS03691 [8]
downstream LVS03803 [3] LVS03803 [3] LVS03803 [3] LVS03803 [3]
40
04 150 DD383694.ai
00 650
Version : 14 - 15/12/2023
160E5100 TOC E-15
PrismaSeT P Active - Functional units www.se.com
40 150
0 650
DD383693.ai
Devices Fixed device Withdrawable device
NS630b/1250 NS1600 NS630b/1250 NS1600
Number of devices per row 1 - 1 -
No. of vertical modules 17 - 18 -
Mounting plates LVS03482 - LVS03483 -
Front plates upstream LVS03804 [4] + LVS03803 [3] - LVS03804 [4] + LVS03803 [3] -
[No. of vertical modules] with cut-out LVS03690 or LVS03701 (1) [7] - LVS03691 [8] -
downstream LVS03803 [3] - LVS03803 [3] -
40
04 150
00 650
Dd383702.eps
E-16 TOC
Version : 14 - 15/12/2023
160E5100
PrismaSeT P Active - Functional units www.se.com
40 150
0 650
Dd383551.eps
Devices Fixed device
NS630b/1000
Number of devices per row 1
No. of vertical modules 7 (1)
Mounting plates LVS03480
Front plates with cut-outs LVS03687
40
04 150
00 650
Dd383551.eps
Version : 14 - 15/12/2023
160E5100 TOC E-17
PrismaSeT P Active - Functional units www.se.com
DD382506.eps
40
0 400
Measurement-device installation
Measurement devices are installed on a front plate (LVS03723) using plastic mounting plates with cut-outs. The front plate can hold:
b six 72 x 72 mm cases
b or four 96 x 96 mm cases + 2 switches.
Number and type of Metal front plate with No. of Plastic Blanking plate
devices per row cut-out vertical mounting or device support
modules plates
with
cut-out
Mounting on an interface with plastic mounting plates
To blank-off or install:
DD385465.eps
DD385466.eps
Dd382670.eps
- from 1 to 4 buttons Ø 16 or 22 mm
- 1 device 45 x 45
Vigirex and other
3 x 72 x 72 devices 72 x 72 without
switch
LVS03902 LVS03900
60
13
To blank-off or install:
40
60
DD385467.eps
DD385468.eps
40 10 A
0
10 A
- from 1 to 4 buttons Ø 16 or 22 mm
0
- 1 device 45 x 45
Power Meter and other
- 1 device 72 x 72
2 x 96 x 96 devices 96 x 96 with
switch
E-18 TOC
Version : 14 - 15/12/2023
160E5100
PrismaSeT P Active - Functional units www.se.com
Dd382672.ai
Devices Fixed device Withdrawable device
NS630b/1600
3P 4P 3P
Type of terminals Front connection Front connection
Accessories
Dd382513.eps
Dd382514.eps
E
W =400 D = 400 D = 600
4 cable tie supports for framework LVS08774 LVS08794 LVS08794 + LVS08796
(1) Vertical connection adapters and cable-lug adapters are not compatible with input voltage u 500 V.
DD383814.eps
DD385890.eps
Version : 14 - 15/12/2023
160E5100 TOC E-19
PrismaSeT P Active - Functional units www.se.com
DD383868.eps
40 150
0 650
Devices Toggle
NSX (1) / NSX Vigi (ELCB) (1) / Vigi NSX NSX (1) / NSX Vigi (ELCB) (1) Vigi NSX
100/160/250 400/630 400/630
3P 4P 3P 4P 3P 4P
Number of devices per row 1 1 1 1 1 1
PowerTag NSX compatibility - -
No. of vertical modules 3 4 4 5 4 5
Mounting plates LVS03411 LVS03412 LVS03451 LVS03452 LVS03451 LVS03452
Front plates with cut-out LVS03604 (2) LVS03606 (2) LVS03643 LVS03644 LVS03643 LVS03644
Fixed devices NSX / NSX Vigi (ELCB) Vigi NSX100/250 NSX / NSX Vigi (ELCB) Vigi NSX400/630
100/250 400/630
3P 4P 3P 4P 3P 4P 3P 4P
Front connection long terminal shields LV429517 LV429518 LV429517 LV429518 LV432593 LV432594 LV432593 LV432594
Connection connection LVS04425 LVS04426 LVS04429 (5) LVS04430 (5) LVS04455 LVS04456 LVS04459 (5) LVS04460 (5)
transfer assembly connection with LVS04425 LVS04426 - - LVS04459 (5) LVS04460 (5) - -
PowerTag NSX
long terminal shields - - LV429517 LV429518 - - LV432593 LV432594
Rear connection short terminal shields LV429515 (4) LV429516 (4) LV429515 (4) LV429516 (4) LV432591 (4) LV432592 (4) LV432591 (4) LV432592 (4)
short rear connectors LV429235 LV429235 LV432475 LV432475
long rear connectors LV429236 LV429236 LV432476 LV432476
(1) Metering and signaling features (ammeter…) can be added. Mounted on a ComPacT NSX, it has the same size than a ComPacT Vigi NSX. Refer to the
corresponding column.
(2) Compatible with FDM121.
(3) Connections must be made with insulated flexible bars > page G-20.
(4) Compatible with Linergy LGYE vertical busbar.
(5) Complete the connection with insulated flexible bars (not supplied).
E-20 TOC
Version : 14 - 15/12/2023
160E5200
PrismaSeT P Active - Functional units www.se.com
DD383869.eps
40 150
0 650
Devices Toggle
NSX (1) / NSX Vigi (ELCB) (1) / Vigi NSX NSX (1) / NSX Vigi (ELCB) (1) / Vigi NSX
100/160/250 400/630
3P 4P 3P 4P
Number of devices per row 1 1 1 1
No. of vertical modules 3 4 4 5
Mounting plates LVS03413 (5) LVS03414 (5) LVS03453 LVS03454
Front plates with cut-out LVS03604 (2) LVS03606 (2) LVS03643 LVS03644
Connection must be made with insulated flexible bars > page G-20.
Connection adapter for plug-in base LV429306 LV429307 LV432584 LV432585
Long terminal shields on plug-in base LV429517 LV429518 LV432593 LV432594
Short terminal shields on device LV429515 LV429516 LV432591 LV432592
Plug-in devices NSX / NSX Vigi (ELCB) / Vigi NSX 100/160/250 NSX / NSX Vigi (ELCB) / Vigi NSX 400/630
3P 4P 3P 4P
Front connection adapter for plug-in base LV429306 LV429307 LV432584 LV432585
connection short terminal shields on device LV429515 LV429516 LV432591 LV432592
long terminal shields on plug-in base LV429517 LV429518 LV432593 LV432594
Connection connection LVS04429 (4) LVS04430 (4) LVS04459 (4) LVS04460 (4)
transfer connection adapter for plug-in base LV429306 LV429307 LV432584 LV432585
assembly short terminal shields LV429515 LV429516 LV432591 LV432592
long terminal shields LV429517 LV429518 LV432593 LV432594
Rear short terminal shields 2 x LV429515 2 x LV429516 2 x LV432591 2 x LV432592
connection short rear connectors LV429235 LV429235 LV432475 LV432475
long rear connectors LV429236 LV429236 LV432476 LV432476
connection adapter for plug-in base LV429306 LV429307 LV432584 LV432585
(1) Metering and signaling features (ammeter…) can be added. Mounted on a ComPacT NSX, it has the same size than a ComPacT Vigi NSX. Refer to the
corresponding column.
(2) Compatible with FDM121.
(3) Compatible with Linergy LGYE vertical busbar.
(4) Complete the connection with insulated flexible bars (not supplied).
(5) Precut not to be removed for rotary handle & motor mechanism.
Version : 14 - 15/12/2023
160E5200 TOC E-21
PrismaSeT P Active - Functional units www.se.com
Dd383562.eps
40 150
0 650
Connection LVS04427 (3) LVS04428 (3) must be made with insulated flexible bars > page G-20 (4).
Long terminal shields - LV432593 LV432594
Linergy BS, LGYE
Dd383564.eps
Connection must be made with insulated flexible bars > page G-20.
Long terminal shields LV429517 LV429518 LV432593 LV432594
E-22 TOC
Version : 14 - 15/12/2023
160E5200
PrismaSeT P Active - Functional units www.se.com
40 150
0 650
DD383869-plug-in.eps
Devices Rotary handle, motor mechanism
NSX (1) / Vigi NSX NSX (1) / Vigi NSX 400/630
NSX Vigi (ELCB) (1) 100/160/250 NSX Vigi (ELCB) (1) rotary handle
100/160/250 400/630 NSX400/630
motor mechanism
3P 4P 3P 4P 3P 4P 3P 4P
Number of devices per row 1 1 1 1 1 1 1 1
No. of vertical modules 3 4 3 4 4 5 4 5
Mounting plates LVS03413 (7) LVS03414(7) LVS03413(7) LVS03414 (7) LVS03453 (2) LVS03454 (2) LVS03453 (2) LVS03454 (2)
Front plates with cut-out LVS03604 (3) LVS03606 (3) LVS03604 (3) LVS03606 (3) LVS03643 LVS03644 LVS03643 LVS03644
Collar - - LV429285 LV429285 - - LV429285 LV429285
E
Connection LVS04427 (4) LVS04428 (4) must be made with insulated flexible bars > page G-20 (5)
Short terminal shields LV429515 LV429516 LV432591 LV432592
Long terminal shields - LV432593 LV432594
Connection adapter for plug-in base LV429306 LV429307 LV432584 LV432585
Linergy BS, LGYE
Dd383564.eps
Connection must be made with insulated flexible bars > page G-20.
Short terminal shields LV429515 LV429516 LV432591 LV432592
Long terminal shields LV429517 LV429518 LV432593 LV432594
Connection adapter for plug-in base LV429306 LV429307 LV432584 LV432585
Plug-in devices NSX / NSX Vigi (ELCB) / Vigi NSX 100/160/250 NSX / NSX Vigi (ELCB) / Vigi NSX 400/630
3P 4P 3P 4P
Front long terminal shields LV429517 LV429518 LV432593 LV432594
connection short terminal shields LV429515 LV429516 LV432591 LV432592
connection adapter LV429306 LV429307 LV432584 LV432585
for plug-in base
Connection connection LVS04429 (6) LVS04430 (6) LVS04459 (6) LVS04460 (6)
transfer long terminal shields LV429517 LV429518 LV432593 LV432594
assembly short terminal shields LV429515 LV429516 LV432591 LV432592
Rear short terminal shields 2 x LV429515 2 x LV429516 2 x LV432591 2 x LV432592
connection short rear connectors LV429235 LV432475
long rear connectors LV429236 LV432476
connection adapter LV429306 LV429307 LV432584 LV432585
for plug-in base
(1) Metering and signaling features (ammeter…) can be added. Mounted on a ComPacT NSX, it has the same size than a ComPacT Vigi NSX. Refer to the
corresponding column.
(2) Catalog number LVS03460 is recommended when installing an NSX with a motor mechanism.
(3) Compatible with FDM121.
(4) Compatible with Linergy LGYE vertical busbar.
(5) To be made according to the busbar drawings supplied by Schneider Electric.
(6) Complete the connection with insulated flexible bars (not supplied).
(7) Precut not to be removed for rotary handle & motor mechanism.
Version : 14 - 15/12/2023
160E5200 TOC E-23
PrismaSeT P Active - Functional units www.se.com
40 150
0 650
DD383870.eps
Devices All controls
NSX / NSX Vigi (ELCB) Vigi NSX NSX / NSX Vigi (ELCB) Vigi NSX
100/160/250 (1) 100/160/250 400/630 (1) 400/630
Number of devices per row 1 1 1 1
No. of vertical modules (1) 5 5 6 6
Mounting plates LVS03415 LVS03415 LVS03462 (2) LVS03462 (2)
Front plates with cut-out LVS03618 LVS03618 LVS03657 LVS03657
Collar LV429284 LV429285 LV432534 LV429285
Locking kit (3) LV429286 LV429286 LV429286 (4) LV429286 (4)
G
F
E
D
C
B
Dd383571.eps
G
F
E
D
C
B
A
Connection must be made with insulated flexible bars > page G-20.
Connection adapter for plug-in base LV429306 LV429307 LV432584 (7) LV432585 (7)
Short terminal shields LV429515 LV429516 LV432591 LV432592
Long terminal shields LV429517 LV429518 LV432593 (7) LV432594 (7)
Withdrawable devices NSX / NSX Vigi (ELCB) / Vigi NSX 100/160/250 NSX / NSX Vigi (ELCB) / Vigi NSX 400/630
3P 4P 3P 4P
Front connection adapter for plug-in base LV429306 LV429307 LV432584 LV432585
connection long terminal shields LV429517 LV429518 LV432593 LV432594
short terminal shields LV429515 LV429516 LV432591 LV432592
Connection connection LVS04429 (8) LVS04430 (8) LVS04459 (8) LVS04460 (8)
transfer connection adapter for plug-in base LV429306 LV429307 LV432584 LV432585
assembly long terminal shields LV429517 LV429518 LV432593 LV432594
short terminal shields LV429515 LV429516 LV432591 LV432592
Rear short terminal shields 2 x LV429515 2 x LV429516 2 x LV432591 2 x LV432592
connection short rear connectors LV429235 LV429235 LV432475 LV432475
long rear connectors LV429236 LV429236 LV432476 LV432476
connection adapter for plug-in base LV429306 LV429307 LV432584 LV432585
(1) Metering and signaling features (ammeter…) can be added. Mounted on a ComPacT NSX, it has the same size than a ComPacT Vigi NSX. Refer to the
corresponding column.
(1) Catalog number LVS03460 is recommended when installing an NSX with a motor mechanism.
(3) If mounting several above one another chassis + form 3b + chassis locking kit LV429286, the number of vertical modules must be increased by 2 ; it is
necessary to add a 2 modules front plate LVS03802.
(4) Not compatible with NSX630.
(5) Compatible with Linergy LGYE vertical busbar.
(6) To be made according to the busbar drawings supplied by Schneider Electric.
(7) Only for Rotary handle and motor mechanism.
(8) Complete the connection with insulated flexible bars (not supplied).
E-24 TOC
Version : 14 - 15/12/2023
160E5200
PrismaSeT P Active - Functional units www.se.com
Dd383554.eps
40 150
0 650
Devices Toggle
NSX / NSX Vigi (ELCB) Vigi NSX NSX / NSX Vigi (ELCB) Vigi NSX
400 (1) 400 630 (1) 630
Number of devices per row 1 2 1 2 1 2 1 2
PowerTag NSX compatibility
No. of vertical modules 11 or 13 13 or 15 13 or 15 15 or 17
Mounting plates LVS03461 LVS03461 LVS03461 LVS03461
Front plates upstream LVS03801 LVS03802 [2] - LVS03802 LVS03802 LVS03803 [3] LVS03801 LVS03803
[No. of [1] [2] [2] [1] [3]
vertical with cut-out LVS03275 LVS03663 [7] LVS03297 LVS03666 LVS03275 LVS03663 [7] LVS03297 LVS03666
modules] [9] [11] [9] [9] [11] [9]
downstream LVS03801 LVS03802 [2] LVS03802 LVS03802 LVS03802 LVS03803 [3] LVS03803 LVS03803
[1] [2] [2] [2] [3] [3]
downstream with PowerTag NSX LVS03803 LVS03804 [4] LVS03804 LVS03804 LVS03804 LVS03805 [5] LVS03805 LVS03805
[3] [4] [4] [4] [5] [5]
E
Fixed devices NSX / NSX Vigi (ELCB) / Vigi NSX 400 NSX / NSX Vigi (ELCB) / Vigi NSX 630
3P 4P 3P 4P
Front connection must be made with insulated flexible bars > page G-20. (2)
connection long terminal shields LV432593 LV432594 LV432593 LV432594
Rear short terminal shields LV432591 LV432592 LV432591 LV432592
connection short rear connectors LV432475 LV432475
long rear connectors LV432476 LV432476
Fixed devices NSX / NSX Vigi (ELCB) / Vigi NSX 400 NSX / NSX Vigi (ELCB) / Vigi NSX 630
3P 4P 3P 4P
Front long terminal shields LV432593 LV432594 LV432593 LV432594
connection
Rear short terminal shields LV432591 LV432592 LV432591 LV432592
connection (3) short rear connectors LV432475 LV432475
long rear connectors LV432476 LV432476
(1) Metering and signaling features (ammeter…) can be added. Mounted on a ComPacT NSX, it has the same size than a ComPacT Vigi NSX. Refer to the
corresponding column.
(2) Connection to be made according to the busbar drawings supplied by Schneider Electric.
(3) Size reduced to one module downstream.
Version : 14 - 15/12/2023
160E5200 TOC E-25
PrismaSeT P Active - Functional units www.se.com
Dd383554.eps
40 150
0 650
Devices Toggle
NSX / NSX Vigi (ELCB) Vigi NSX 400 NSX / NSX Vigi (ELCB) Vigi NSX 630
400 (1) 630 (1)
Number of devices per row 1 2 1 2 1 2 1 2
Mounting plates LVS03461 LVS03461 LVS03461 LVS03461
Front plates upstream LVS03801 LVS03802 [2] - LVS03802 LVS03802 LVS03803 [3] LVS03801 LVS03803
[No. of [1] [2] [2] [1] [3]
vertical with cut-out LVS03275 LVS03663 [7] LVS03297 LVS03666 LVS03275 LVS03663 [7] LVS03297 LVS03666
modules] [9] [11] [9] [9] [11] [9]
downstream LVS03801 LVS03802 [2] LVS03802 LVS03802 LVS03802 LVS03803 [3] LVS03803 LVS03803
[1] [2] [2] [2] [3] [3]
Plug-in devices NSX / NSX Vigi (ELCB) / Vigi NSX 400 NSX / NSX Vigi (ELCB) / Vigi NSX 630
3P 4P 3P 4P
Front connection must be made with insulated flexible bars > page G-20.(2)
connection long terminal shields LV432593 LV432594 LV432593 LV432594
short terminal shields LV432591 LV432592 LV432591 LV432592
connection adapter for plug-in base LV432584 LV432585 LV432584 LV432585
Rear short terminal shields 2 x LV432591 2 x LV432592 2 x LV432591 2 x LV432592
connection short rear connectors LV432475 LV432475
long rear connectors LV432476 LV432476
connection adapter for plug-in base LV432584 LV432585 LV432584 LV432585
Plug-in devices NSX / NSX Vigi (ELCB) / Vigi NSX 400 NSX / NSX Vigi (ELCB) / Vigi NSX 630
3P 4P 3P 4P
Front connection adapter for plug-in base LV432584 LV432585 LV432584 LV432585
connection short terminal shields on device LV432591 LV432592 LV432591 LV432592
long terminal shields on plug-in base LV432593 LV432594 LV432593 LV432594
Rear short terminal shields 2 x LV432591 2 x LV432592 2 x LV432591 2 x LV432592
connection (3) short rear connectors LV432475 LV432475
long rear connectors LV432476 LV432476
connection adapter for plug-in base LV432584 LV432585 LV432584 LV432585
(1) Metering and signaling features (ammeter…) can be added. Mounted on a ComPacT NSX, it has the same size than a ComPacT Vigi NSX. Refer to the
corresponding column.
(2) Connection to be made according to the busbar drawings supplied by Schneider Electric.
(3) Size reduced to one module downstream.
E-26 TOC
Version : 14 - 15/12/2023
160E5200
PrismaSeT P Active - Functional units www.se.com
40 150
0 650
Dd383567.eps
Devices Rotary handle, motor mechanism
NSX / NSX Vigi (ELCB) Vigi NSX 400 NSX / NSX Vigi (ELCB) Vigi NSX 630
400 (1) Rotary handle 630 (1) Rotary handle
Number of devices per row 1 2 1 2 1 2 1 2
PowerTag NSX compatibility
No. of vertical modules 11 or 13 13 or 15 13 or 15 15 or 17
Mounting plates LVS03461 (2) LVS03461 LVS03461 (2) LVS03461
Front plates upstream LVS03801 LVS03802 [2] - LVS03802 LVS03802 LVS03803 [3] LVS03801 LVS03803
[No. of [1] [2] [2] [1] [3]
vertical with cut-out LVS03275 LVS03663 [7] LVS03297 LVS03666 LVS03275 LVS03663 [7] LVS03297 LVS03666
modules] [9] [11] [9] [9] [11] [9]
downstream LVS03801 LVS03802 [2] LVS03802 LVS03802 LVS03802 LVS03803 [3] LVS03803 LVS03803
[1] [2] [2] [2] [3] [3]
downstream with PowerTag NSX LVS03803 LVS03804 [4] LVS03804 LVS03804 LVS03804 LVS03805 [5] LVS03805 LVS03805
[3] [4] [4] [4] [5] [5]
Collar
IP40 escutcheons
-
-
LV429285
LV429316 (3)
-
-
LV429285
LV429316 (3) E
Connection Upstream from lateral busbars - Linergy LGY, BS, LGYE
Version : 14 - 15/12/2023
160E5300 TOC E-27
PrismaSeT P Active - Functional units www.se.com
40 150
0 650
Dd383567.eps
Devices Rotary handle, motor mechanism
NSX / NSX Vigi (ELCB) Vigi NSX400 NSX / NSX Vigi (ELCB) Vigi NSX630
400 (1) Rotary handle 630 (1) Rotary handle
Number of devices per row 1 2 1 2 1 2 1 2
No. of vertical modules 11 13 13 15
Mounting plates LVS03461 (2) LVS03461 LVS03461 (2) LVS03461
Front plates upstream LVS03801 LVS03802 [2] - LVS03802 LVS03802 LVS03803 [3] LVS03801 LVS03803
[No. of [1] [2] [2] [1] [3]
vertical with cut-out LVS03275 LVS03663 [7] LVS03297 LVS03666 LVS03275 LVS03663 [7] LVS03297 LVS03666
modules] [9] [11] [9] [9] [11] [9]
downstream LVS03801 LVS03802 [2] LVS03802 LVS03802 LVS03802 LVS03803 [3] LVS03803 LVS03803
[1] [2] [2] [2] [3] [3]
Collar - LV429285 - LV429285
IP40 front-panel escutcheons - LV429316 (3) - LV429316 (3)
E-28 TOC
Version : 14 - 15/12/2023
160E5300
PrismaSeT P Active - Functional units www.se.com
Dd383574.eps
40 150
0 650
Withdrawable devices NSX / NSX Vigi (ELCB) / Vigi NSX 100/160/250 NSX / NSX Vigi (ELCB) / Vigi NSX 400/630
3P 4P 3P 4P
Front connection adapter LV429306 LV429307 LV432584 LV432585
conn. for plug-in base
short on device LV429515 LV429516 LV432591 LV432592
terminal on plug-in LV429517 LV429518 LV432593 LV432594
shields base
Rear short terminal shields 2 x LV429515 2 x LV429516 2 x LV432591 2 x LV432592
conn. short rear connectors LV429235 LV429235 LV432475 LV432475
long rear connectors LV429236 LV429236 LV432476 LV432476
connection adapter LV429306 LV429307 LV432584 LV432585
for plug-in base
(1) Metering and signaling features (ammeter…) can be added. Mounted on a ComPacT NSX, it has the same size than a ComPacT Vigi NSX. Refer to the
corresponding column.
(2) Catalog number LVS03460 is recommended when installing an NSX with a motor mechanism.
(3) For devices with toggle only.
Version : 14 - 15/12/2023
160E5300 TOC E-29
PrismaSeT P Active - Functional units www.se.com
DD383879.eps
400
E-30 TOC
Version : 14 - 15/12/2023
160E5300
PrismaSeT P Active - Functional units www.se.com
DD380506.eps
40 150
0 650
Devices Toggle
NSX/ NSX Vigi (ELCB) Vigi NSX NSX/ NSX Vigi (ELCB) Vigi NSX
100/160 (1) 100/160 250 (1) 250
Number of devices per row 3 x 4P or 4 x 3P 3 x 4P or 4 x 3P 3 x 4P or 4 x 3P 3 x 4P or 4 x 3P
PowerTag 250/ 630 Acompatibility
No. of vertical modules 6 or 7 8 7 or 8 9
Mounting plates LVS03420 LVS03420 LVS03420 LVS03420
Front plates with cut-out LVS03243 [5] LVS03241 [7] LVS03243 [5] LVS03241 [7]
[No. of downstream LVS03801 [1] LVS03801 [1] LVS03802 [2] LVS03802 [2]
vertical
modules] downstream with PowerTag 250/ LVS03802 [2] LVS03802 [2] LVS03803 [3] LVS03803 [3]
630 A
Version : 14 - 15/12/2023
160E5300 TOC E-31
PrismaSeT P Active - Functional units www.se.com
Dd383559.eps
40 150
0 650
Devices Toggle
NSX / NSX Vigi (ELCB) Vigi NSX 100/160 NSX / NSX Vigi (ELCB) 250 Vigi NSX 250
100/160 (1) (1)
Number of devices per row 3 x 4P or 4 x 3P 3 x 4P or 4 x 3P 3 x 4P or 4 x 3P 3 x 4P or 4 x 3P
No. of vertical modules 9 7 11 9 10 8 12 10
Mounting plates LVS03421 (2) LVS03423 (3) LVS03421 (2) LVS03423 (3) LVS03421 (2) LVS03423 (3) LVS03421 (2) LVS03423
(3)
Front plates upstream LVS03801 [1] LVS03801 [1] LVS03801 [1] LVS03801 [1] LVS03801 [1] LVS03801 [1] LVS03801 [1] LVS03801 [1]
[No. of + LVS03802 [2] + LVS03802 [2] + LVS03802 [2] + LVS03802 [2]
vertical with cut-out LVS03243 [5] LVS03243 [5] LVS03241 [7] LVS03241 [7] LVS03243 [5] LVS03243 [5] LVS03241 [7] LVS03241 [7]
modules] downstream LVS03801 [1] LVS03801 [1] LVS03801 [1] LVS03801 [1] LVS03802 [2] LVS03802 [2] LVS03802 [2] LVS03802 [2]
E-32 TOC
Version : 14 - 15/12/2023
160E5300
PrismaSeT P Active - Functional units www.se.com
40 150
0 650
Dd383566.eps
Devices Rotary handle, motor mechanism
NSX / NSX Vigi (ELCB) Vigi NSX NSX / NSX Vigi Vigi NSX
100/160 (1) 100/160 (ELCB) 250
250 (1)
Number of devices per row 3 x 4P or 4 x 3P 3 x 4P or 4 x 3P 3 x 4P or 4 x 3P 3 x 4P or 4 x 3P
PowerTag 250/ 630 A compatibility
No. of vertical modules (2) 6 or 7 8 or 9 7 or 8 9 or 10
Mounting plates LVS03422 LVS03422 LVS03422 LVS03422
Front with cut-out LVS03243 [5] LVS03244 [7] LVS03243 [5] LVS03244 [7]
plates downstream LVS03801 [1] LVS03801 [1] LVS03802 [2] LVS03802 [2]
[No. of
vert. mod.] downstream with PowerTag 250/ 630 A LVS03802 [2] LVS03802 [2] LVS03803 [3] LVS03803 [3]
Collar - LV429285 - LV429285
IP40 front-panel escutcheons - LV429316 (3) - LV429316 (3)
E
Fixed devices NSX / NSX Vigi (ELCB) / Vigi NSX100/160/250
3P 4P
Linergy FC connection to busbars
Linergy LGY Linergy FC distribution blocks LVS04405 (4) LVS04406 (4)
(with connection)
Linergy BS, Linergy FC distribution blocks LVS04407 LVS04408
LGYE (without connection) (5)
Accessories
Linergy FC tooth-caps LVS04809
Divisible blanking plate LVS03249
Blanking plate fract. + electronic trip unit LVS03222
Version : 14 - 15/12/2023
160E5300 TOC E-33
PrismaSeT P Active - Functional units www.se.com
40 150
0 650
Dd383567.eps
Devices Rotary handle, motor mechanism - plug-in
NSX / NSX Vigi (ELCB) (1) Vigi NSX NSX / NSX Vigi (ELCB) (1) Vigi NSX
100/160 100/160 250 250
Number of devices per row 3 x 4P or 4 x 3P 3 x 4P or 4 x 3P 3 x 4P or 4 x 3P 3 x 4P or 4 x 3P
No. of vertical modules (2) 7 9 8 10
Mounting plates LVS03421 LVS03421 LVS03421 LVS03421
Front plates upstream LVS03801 [1] LVS03801 [1] LVS03801 [1] LVS03801 [1]
[No. of vertical with cut-out LVS03243 [5] LVS03244 [7] LVS03243 [5] LVS03244 [7]
modules]
downstream LVS03801 [1] LVS03801 [1] LVS03802 [2] LVS03802 [2]
Collar - LV429285 - LV429285
IP40 escutcheons - LV429316 (3) - LV429316 (3)
E-34 TOC
Version : 14 - 15/12/2023
160E5300
PrismaSeT P Active - Functional units www.se.com
DD386147.ai
DD386146.ai
40 150
0 650
DD386151.ai
E
Devices Toggle Direct rotary handle
NSXm, NSXm Vigi (ELCB) NSXm
3P 4P 3P 4P
Connection Connections must be made Connections must be made
Long terminal shields LV426912 LV426913 LV426912 LV426913
Busbars Linergy BW > page G-14 LVS04191 + copper bars > page G-25
Prefabricated connection LVS04021, LVS04145, LVS04146, LVS04148 LVS04030
Busbars / Distribution block LVS04192 + copper bars > pages G-10, G-11 LVS04038, LVS04039 > page G-15
Prefabricated connection Connection must be made
Version : 14 - 15/12/2023
160E5400 TOC E-35
PrismaSeT P Active - Functional units www.se.com
D
C
150
B
D
DD386148.ai
A
DD386149.ai
C
40
B
650
A
0
Everl
E
Everl
Everl
SD
E
Everl
Everl
OF
SD
SD
Everl D
Everl
OF
SD
C
OF
SD
Everl
B Everl
D
OF
SD
OF
SD
A C
Everl B
OF
SD
OF
SD
A
OF
OF
SD
OF
Devices Toggle Direct rotary handle
NSXm NSXm Vigi (ELCB) NSXm
Number of devices per row 5 x 3P or 4 x 4P 4 x 3P or 4P 5 x 3P or 4 x 4P
No. of vertical modules(1) 5 5 5
Mounting plates LVS03410 LVS03406 LVS03410
Front plates With cut-out LVS03205 [5] LVS03205 [5] LVS03226 [5] - 3P
[No. of vertical LVS03227 [5] - 4P
modules]
Upstream LVS03802 [2] LVS03802 [2] LVS03802 [2]
Downstream LVS03801 [1] LVS03801 [1] LVS03801 [1]
DD435628.eps
DD435628.eps
DD435627.eps
DD435629.eps
E E
E
E
D D
D C C
D C B B
C B A A
B A
A
E E
E
E
D D
D C C
C B B
D
B A A
C A
B
A
Devices NSXm, Toggle/Direct rotary handle - with Everlink NSXm Vigi (ELCB), Toggle/Direct rotary
lug handle - with Everlink lug
Number of poles 3P 4P 3P 4P
Number of devices per row 5 x 3P 4 x 4P 4 x 3P 4 x 4P
Linergy FC connection to busbars
(With Linergy LGY LVS04410 LVS04411 LVS04416 LVS04411
connection) Linergy BS, LVS04412 LVS04413 LVS04417 LVS04413
LGYE
(Without Linergy BS, LVS04419 LVS04420 LVS04418 LVS04420
connection) LGYE, LGY
Mounting plates LVS03416 LVS03416 LVS03416 LVS03416
Front plates With cut-out LVS03205 [5] LVS03205 [5] LVS03205 [5] LVS03205 [5]
[No. of vertical Downstream LVS03802 [2] LVS03802 [2] LVS03802 [2] LVS03802 [2]
modules]
Tooth-caps [No. of tooth-caps] LVS04810 [12] LVS04810 [12] LVS04810 [12] LVS04810 [12]
Accessories
DD386153.ai
E
DD386152.ai
D
C
B
D
A
C
B
A
Everl
E
Everl
Everl
E
SD
Everl Everl
OF
SD
SD
Everl
Everl D
OF
SD
OF
SD
Everl
D C
Everl
OF
SD
C B
OF
SD
Everl B A
OF
SD
A
OF
SD
OF
SD
OF
OF
DD380761.eps
Busbars Linergy BW LVS04191 + copper bars > page G-9 LVS04192 + copper bars > pages G-10, G-11
Connection LVS04030, LVS04145, LVS04146, LVS04147, LVS04148 LVS04145, LVS04146 (centred device) Must be made
(1) For ComPacT NSXm up to 160, the number of modules indicated is for supply via a Linergy FC distribution block. For supply via cables, two additional
modules are required; add an upstream plain front plate (LVS03802).
E-36 TOC
Version : 14 - 15/12/2023
160E5400
PrismaSeT P Active - Functional units www.se.com
Dd383300.eps
Dd383301.eps
DD435632.ai
Distribution block LVS04031> page G-22 LVS04045 > page G-22 LVS04046 > page G-22 LVS04038, LVS04039 > page G-15
Connection LVS04149 LVS04047 included
Rail LVS03402 (W650)
40 150
0 650
Everl
SD
OF
Devices Toggle
NSXm NSXm Vigi (ELCB)
Number of devices per row 5 x 3P or 4 x 4P 4 x 3P or 4P
No. of vertical modules 5 (1) 5 (2)
Rail [48 module of 9mm] LVS03402 (adjustable) (3) LVS03402 (adjustable) (3)
Modular front plates With cut out LVS03205 LVS03205
Blanking plate Strip LVS03220 LVS03220
Divisible LVS03221 LVS03221
Connection
DD435632.ai
Version : 14 - 15/12/2023
160E5400 TOC E-37
PrismaSeT P Active - Functional units www.se.com
40
0 400
Everl
Everl
SD
DD386155.ai
SD
DD386272.ai
OF
OF
Devices Toggle Direct rotary handle
NSXm NSXm Vigi (ELCB) NSXm
Number of devices per row 1 x 3P or 4P 1 x 3P or 4P 1 x 3P or 4P
No. of vertical modules 8 8 8
Mounting plates LVS03405 LVS03405 LVS03405
Front plates With cut out LVS03225 [5] LVS03225 [5] LVS03225 [5]
[No. of vertical modules] Upstream LVS03812 [2] LVS03812 [2] LVS03812 [2]
Downstream LVS03811 [1] LVS03811 [1] LVS03811 [1]
E-38 TOC
Version : 14 - 15/12/2023
160E5400
PrismaSeT P Active - Functional units www.se.com
Dd383581.eps
40 150
0 650
Version : 14 - 15/12/2023
160E5400 TOC E-39
PrismaSeT P Active - Functional units www.se.com
DD380543.eps
DD380546.eps
40 150
0 650
DD380547.eps
Prefabricated connection LVS04427 (2) LVS04428 (2) must be made (3) - must be made (3)
Distribution block Linergy FC - LVS04404 -
Long terminal shields - LV432594 - LV432594
Linergy BS, LGYE
DD381423.eps
DD380548.eps
DD380549.eps
E-40 TOC
Version : 14 - 15/12/2023
160E5400
PrismaSeT P Active - Functional units www.se.com
Source-changeover
Possible combinations ComPacT NSX100/630, NS630b/1600,
MasterPact MTZ1 06/16, MTZ2 08/32
Source-changeover
Manual source-changeover
Dd383703.eps
Type of device Type of interlocking
Complete Toggle Keylock Rotary On base plate Cable-type Cable-type Cable-type
assembly handle with 2 with 3 with 2 devices
devices devices one above
side-by-side side-by-side another
(2) (2)
INS250 (rating 100 to 250)
INV100 to INV250 (1)
INS320 to INS630
INV320 to INV630 (1)
NSX100 to NSX250
NSX400 to NSX630
NS630b to NS1600
NT06 to 16
NW08 to 32
Possible combinations.
Version : 14 - 15/12/2023
160E5500 TOC E-41
PrismaSeT P Active - Functional units www.se.com
Source-changeover
Mounting Front connection with cables
DD385442.eps
60 150
0 650
Connection
S1 device
Upstream connection Front connections supplied with the device
Connection must be made (1)
S2 device
Downstream connection Front connections supplied with the device
Connection must be made (1)
60 150
0 650
MERLIN GERIN
MERLIN GERIN
Devices
UA or BA controller
Number of devices per row 1
Number of vertical modules 4
Mounting plates LVS03417
Front plates with cut-out LVS03671 [4]
[No. of vertical mod.]
Characteristics When a UA, BA or UA150 automatic controller is added together with an ACP mounting plate, the sources can be controlled
automatically according to a number of programmed operating modes.
(1) Connection to be made according to the busbar drawings supplied by Schneider Electric.
E-42 TOC
Version : 14 - 15/12/2023
160E5500
PrismaSeT P Active - Functional units www.se.com
Source-changeover
Mounting Rear connection with cables
DD385443.eps
60 150
0 650
Connection
E
Devices Fixed device Withdrawable device
S1 device
NW08/16 NW20/32 NW08/16 NW20/32
Upstream connection Vertical rear connections supplied with the device
Connection must be made (1)
S2 device
NW08/16 NW20/32 NW06/10 NW20/32
Downstream connection Vertical rear connections supplied with the device
Connection must be made (1)
S1 device
Upstream connection Front connections supplied with the device
Connection must be made (1)
S2 device
Downstream connection Front connections supplied with the device
Connection must be made (1)
60 150
0 650
MERLIN GERIN
MERLIN GERIN
Devices
UA or BA controller
Number of devices per row 1
Number of vertical modules 4
Mounting plates LVS03417
Front plates with cut-out LVS03671 [4]
[No. of vertical mod.]
Characteristics When a UA, BA or UA150 automatic controller is added together with an ACP mounting plate, the sources can be controlled
automatically according to a number of programmed operating modes.
(1) Connection to be made according to the busbar drawings supplied by Schneider Electric.
Version : 14 - 15/12/2023
160E5500 TOC E-43
PrismaSeT P Active - Functional units www.se.com
Source-changeover
Mounting Front connection with cables
DD385442.eps
60 150
0 650
Connection
S1 device
Upstream connection Front connections supplied with the device
Connection must be made (1)
S2 device
Downstream connection Front connections supplied with the device
Connection must be made (1)
150
DD383813.eps
60
0 650
MERLIN GERIN
MERLIN GERIN
Devices
UA or BA controller
Number of devices per row 1
Number of vertical modules 4
Mounting plates LVS03417
Front plates with cut-out LVS03671 [4]
[No. of vertical mod.]
Characteristics When a UA, BA or UA150 automatic controller is added together with an ACP mounting plate, the sources can be controlled
automatically according to a number of programmed operating modes.
(1) Connection to be made according to the busbar drawings supplied by Schneider Electric.
E-44 TOC
Version : 14 - 15/12/2023
160E5500
PrismaSeT P Active - Functional units www.se.com
Source-changeover
Mounting Rear connection with cables
DD385443.eps
60 150
0 650
Connection
E
Devices Fixed device Withdrawable device
S1 device
MTZ2 08/16 MTZ2 20/32 MTZ2 08/16 MTZ2 20/32
Upstream connection Vertical rear connections supplied with the device
Connection must be made (1)
S2 device
MTZ2 08/16 MTZ2 20/32 MTZ2 06/10 MTZ2 20/32
Downstream connection Vertical rear connections supplied with the device
Connection must be made (1)
S1 device
Upstream connection Front connections supplied with the device
Connection must be made (1)
S2 device
Downstream connection Front connections supplied with the device
Connection must be made (1)
150
DD383813.eps
60
0 650
MERLIN GERIN
MERLIN GERIN
Devices
UA or BA controller
Number of devices per row 1
Number of vertical modules 4
Mounting plates LVS03417
Front plates with cut-out LVS03671 [4]
[No. of vertical mod.]
Characteristics When a UA, BA or UA150 automatic controller is added together with an ACP mounting plate, the sources can be controlled
automatically according to a number of programmed operating modes.
(1) Connection to be made according to the busbar drawings supplied by Schneider Electric.
Version : 14 - 15/12/2023
160E5500 TOC E-45
PrismaSeT P Active - Functional units www.se.com
Source-changeover
Mounting Front connection with cables
DD385441.eps
60 150
0 650
Connection
S1 device
Upstream connection Front connections supplied with the device
Connection must be made
S2 device
Downstream connection Front connections supplied with the device
Connection must be made
150
DD383813.eps
60
0 650
MERLIN GERIN
MERLIN GERIN
Devices
UA or BA controller
Number of devices per row 1
Number of vertical modules 4
Mounting plates LVS03417
Front plates with cut-out LVS03671 [4]
[No. of vertical mod.]
Characteristics When a UA, BA or UA150 automatic controller is added together with an ACP mounting plate, the sources can be
controlled automatically according to a number of programmed operating modes.
E-46 TOC
Version : 14 - 15/12/2023
160E5500
PrismaSeT P Active - Functional units www.se.com
Source-changeover
Mounting Rear connection with cables
Dd380796.ai
40
04 150
00 650
Connection
S1 device
Upstream connection Front connections supplied with the device
Connection must be made
S2 device
Downstream connection Front connections supplied with the device
Connection must be made
40 150
650
DD383813.eps
0
MERLIN GERIN
MERLIN GERIN
Devices
UA or BA controller
Number of devices per row 1
Number of vertical modules 4
Mounting plates LVS03417
Front plates with cut-out LVS03671 [4]
[No. of vertical mod.]
Characteristics When a UA, BA or UA150 automatic controller is added together with an ACP mounting plate, the sources can be controlled
automatically according to a number of programmed operating modes.
Version : 14 - 15/12/2023
160E5500 TOC E-47
PrismaSeT P Active - Functional units www.se.com
Source-changeover
Mounting Front connection with cables
DD385441.eps
40 150
0 650
Connection
S1 device
Upstream connection Front connections supplied with the device
Connection must be made
S2 device
Downstream connection Front connections supplied with the device
Connection must be made
40 150
0 650
MERLIN GERIN
MERLIN GERIN
Devices
UA or BA controller
Number of devices per row 1
Number of vertical modules 4
Mounting plates LVS03417
Front plates with cut-out LVS03671 [4]
[No. of vertical mod.]
Characteristics When a UA, BA or UA150 automatic controller is added together with an ACP mounting plate, the sources can be controlled
automatically according to a number of programmed operating modes.
E-48 TOC
Version : 14 - 15/12/2023
160E5500
PrismaSeT P Active - Functional units www.se.com
Source-changeover
Mounting Horizontal
Dd381534.eps
40 150
0 650
Devices
NS630b/1000
3P 4P
Number of devices per row 2
Number of vertical modules 13
Mounting plates LVS03491
Front plates upstream -
[No. of vertical with cut-out LVS03695 [13]
modules]
downstream -
Mechanical interlock 33890 33890
Characteristics Interlocking of direct rotary handles.
The devices are equipped with a direct rotary handle.
Version : 14 - 15/12/2023
160E5500 TOC E-49
PrismaSeT P Active - Functional units www.se.com
Manual source-changeover
ComPacT NSX100/630
Source-changeover
Mounting Vertical Horizontal
DD381529.eps
DD383810.eps
40 150
650
A
0
ON
I
reset
O
OFF
Devices
NSX100/250 NSX400/630
3P 4P 3P 4P
Number of devices per row 2 2
Number of vertical modules 10 10
Mounting plates LVS03428 LVS03458
Front plates upstream LVS03802 [2] -
[No. of vertical with cut-out LVS03245 [5] LVS03659 [10]
modules]
downstream LVS03803 [3] -
Mechanical interlock LV429369 LV429369 LV432621 LV432621
Characteristics Interlocking of rotary handles
The devices are equipped with a rotary handle.
They are mounted on a dedicated mounting plate.
E-50 TOC
Version : 14 - 15/12/2023
160E5600
PrismaSeT P Active - Functional units www.se.com
Remote-operated source-changeover
ComPacT NSX100/630
Source-changeover
Mounting Horizontal
DD383811.eps
DD383812.eps
40 150
0 650
Devices
NSX100/250 NSX400/630
Number of devices per row 2 2
Number of vertical modules 8 10
Mounting plates LVS03417 (1) LVS03457 (2)
Front plates with LVS03616 [8] LVS03656 [10]
[No. of vertical cut-out
mod.]
Characteristics The devices are equipped with motor mechanisms.
E
for spreader - - LV432595 LV432596
Coupling accessory LV429358 LV429359 LV432619 LV432620
Rear short terminal LV429515 LV429516 LV432591 LV432592
connection shields
Mounting Controller
DD383813.eps
40 150
0 650
MERLIN GERIN
MERLIN GERIN
Devices
UA or BA controller
Number of devices per row 1
Number of vertical modules 4
Mounting plates LVS03417
Front plates LVS03671 [4]
[No. of vertical with cut-out
mod.]
When a UA, BA or UA150 automatic controller is added together with an ACP mounting plate, the sources can be controlled
Characteristics automatically according to a number of programmed operating modes.
(1) Order mounting plate + IVE electrical interlocking unit for NSX100/250 (cat. no. 29350 for AC or 29351 for DC version).
(2) Order mounting plate + IVE electrical interlocking unit for NSX400/630 (cat. no. 32610 for AC or 32611 for DC version).
Incoming and busbar connections to be made.
Version : 14 - 15/12/2023
160E5600 TOC E-51
PrismaSeT P Active - Functional units www.se.com
Manual source-changeover
ComPacT INS-INV250 to 630
Front direct rotary handle
Source-changeover
Mounting Front vertical rotary handle Front horizontal rotary handle
DD381537.eps
Dd383707.eps
40 150
0 650
Distribution
E-52 TOC
Version : 14 - 15/12/2023
160E5600
PrismaSeT P Active - Functional units www.se.com
Manual source-changeover
ComPacT INS-INV250 to 630
Complete assembly device
Source-changeover
Mounting Vertical complete assembly Horizontal complete assembly
Dd381539.eps
Dd383708.eps
40 150
0 650
Distribution
Version : 14 - 15/12/2023
160E5600 TOC E-53
PrismaSeT P Active - Functional units www.se.com
650
DD435632_TR.eps
tic
Automa
PE
S0634T
TA10D4 Active
Active
Icw:5KA
the controller.
rPacT test
will damage
Transfe
dielectirc
in factoryˈwrong
150
is done
test
Insulation
Auto
SII
SI
650
1
mm
in.
2
Cable Transfer
PacT
SII
Auto
4
13
SI
TPSISO30
Auxiliary
TPSAUX32 TPSAUX33
E-54 TOC
Version : 14 - 15/12/2023
160E5600
PrismaSeT P Active - Functional units www.se.com
650
DD435633_TR.eps
tic Insulation
test is
done
150
No:203120
uto
SII
SI
650
Ø
mm
in.
A ≤ 20 1
E
≤ 0.78
Ø B ≤ 10 1
≤ 0.39 2
C ≤6
B C
B ≤ 0.24 2 tic test is
done
≥8
Insulation
Automa
Cable/Busbars
test will
in factory,wrong
C
dielectircthe controller.
TPE transition
damage
Ø
4S1604
ATSE
Open 0V~440V
TA16D Ue:AC38
Ie:160A /0.1s
T
2
Icw:10kA
erPac 050020
Transf
≥ 0.31
No:20312
== 12 14
uto
T
10 6 7 16
84
5 8 SII
U 9 18
6 3 20 SI
8±0.8 N•m
done ) 10
tic Insulation
test is
f 4 2 (
5 10
Automa test will
in factory,wrong 240 3
==
20
dielectircthe controller. 60Hz 230 415 2
PE transition
damage
50Hz 400 250
t
30
T
S1604T Open V~440V
f 5s 220
440
(N
A) 1
0 (s)
60
ATSE Ue:AC380
TA16D4 0s 380 5 10
Ie:160A 0.1s 3 20
T t Off
G
2
Icw:10kA/ Ue(V)
erPac
2 30
70.8±7.08 lb-in.
050020 t
Transf No:20312 Mode SII (A
N)1
0 (min)
60
SI
N Non
Prio.
A
Auto Return
uto Return
12 14
10 6 7 16
5 8 SII
T
84 9 18
U
6 3 20 SI
A
) 10
f 4 2 (
5 10
240 3 20
60Hz 230 415 2
M8
400 250 30
50Hz t
440 A) 1 60
f 5s 220 (N 0 (s)
5 10
0s 380 3 20
t Off
G
Ue(V) 2 30
t
N)1 60
Mode SII (A 0 (min)
1
SI
N Non
Prio.
Auto Return
Return
6
1
TPSISO31
Auxiliary
TPSAUX32 TPSAUX33
Version : 14 - 15/12/2023
160E5600 TOC E-55
PrismaSeT P Active - Functional units www.se.com
DD439632_TR.eps
650 150
650
SII
SI
ic
Automat
2504TPE
TA25D4S 50/60Hz
kA/0.1s
Ue: AC380-440V
10kA/0.5s,15
Ie: 250A Icw:
2
AC-33B 60947-6-1
1 IEC/EN
No. 22040301000
GB/T14048.1
PE
S2504T
LV429253
TA25D4 V 50/60Hz
x3 x2
5kA/0.1s
1
14 Ue: AC380-440
7 16 10kA/0.5s,1
8
Ie: 250A Icw:
9 18 002 60947-6-1
10 20
AC-33B
.11 IEC/EN
No. 220403010
10
20 GB/T14048
30
150 mm2
60
f
10
20
t Off 30
60
(min)
Mode
N
Prio.
LV429257 x4 x3 LV429506 x3 x2
185 mm2
LV429254 x3 x2 LV429507 x4 x3
185 mm2
LV429258 x4 x3
Busbar
SII
SI
tic
Automa
PE
S2504T
TA25D4 V 50/60Hz
5kA/0.1s
1
14 Ue: AC380-440
7 16 10kA/0.5s,1
8
Ie: 250A Icw:
9 18 002 60947-6-1
10 20
AC-33B
.11 IEC/EN
No. 220403010
10
20 GB/T14048
30
60
f
10
20
t Off 30
60
(min)
Mode
N
Prio.
LGY LGYE
Linergy SI
SII
1
14
7 16
10
60
10
60
8
9 18
0 20
10
20
30
20
30
TA25D4S250
Ie: 250A
AC-33B
GB/T14048.11
4TPE
Ue: AC380-440V
Icw:
IEC/EN
No. 220403010002
50/60Hz
10kA/0.5s,15kA/0
60947-6-1
.1s
Autom
atic
Accessories
Insulating
Bare Cable Connector Long Terminal Shield Available Options
Screen
Cable Size TransferPacT NSX Solution Long Terminal Shield
3P: TPSCON47 LV429248
1.5 to 35 mm 2
4P: TPSCON48 LV429249
120 to 240 3P: TPSCON49 LV429244
+ LV429518
mm2 4P: TPSCON50 LV429245
3P: TPSCON51 LV429218
50 to 120 mm2
4P: TPSCON52 LV429219 TPSISO66
Auxiliary
Coupling Auxiliary Module Power Tag
E-56 TOC
Version : 14 - 15/12/2023
160E5600
PrismaSeT P Active - Functional units www.se.com
DD439633_TR.eps
650 150
650 < S II
<SI
OF/AUX
SII c
Automati
SI
6304TPE
TA63D4S 50/60Hz
A/0.1s
Ue: AC380V-440V
20kA/0.5s,25k
Ie: 630A Icw:
AC-33B
IEC/EN
60947-6-1 < Load
12 14
6 7 16
No. 220403010005
8
GB/T14048.11
9 18
20
( ) 10
5 10
20
30
60
(s)
5 10
20
30
60
(min)
<SI
Cable
f
Mode
t Off
Prio.
N
SI
Return
SII
TA63D4S6
Ie: 630A
AC-33B
304TPE
Ue: AC380V-440V
Icw:
GB/T14048.11
20kA/0.5s,25kA
IEC/EN
No. 220403010005
60947-6-1
50/60Hz
/0.1s
Automatic
< Load
OF/AUX
TPSCON57 LV432500 x3 x2
240 mm2
TPSCON61 LV432504 x3 x2
240 mm2
E
TPSCON58 LV432501 x4 x3 TPSCON62 LV432505 + x4 x3
+ TPSISO65
TPSCON59 LV432502 x3 x2 TPSCON63 LV432506 TPSISO65 x3 x2
300 mm2 300 mm2
TPSCON60 LV432503 x4 x3 TPSCON64 LV432507 x4 x3
< S II
<SI
Busbar
OF/AUX
SII
tic
Automa
SI
PE
S6304T
TA63D4 0V
50/60Hz
5kA/0.1s
Ue: AC380V-44
20kA/0.5s,2
Ie: 630A Icw:
005
AC-33B 60947-6-1 < Load
.11 IEC/EN
No. 220403010
GB/T14048
f
t Off
Mode
N
Prio.
Return
LGY LGYE
< S II
<SI
Linergy
OF/AUX
SII
atic
Autom
SI
TPE
TA63D4S6304 50/60Hz
s
Ue: AC380V-440V
20kA/0.5s,25kA/0.1
Ie: 630A Icw:
AC-33B
IEC/EN
60947-6-1 < Load
0
10
12 14
1
6 7 16
No. 220403010005
5 8
84
GB/T14048.11
U 9 18
6 3 0 20
) 10
f 4 2 (
5 10
240
Accessories
Bare Cable Connector Long Terminal Shield Available Options Insulating Screen
Cable Size TranferPacT NSX Solution Long Terminal Shield
+ TPSISO42
35 to 300 mm 2
4P: TPSCON54 LV432480
TPSISO67
Auxiliary
Coupling Auxiliary Module
TPSAUX43 TPSAUX44
(1) Must use fixed frame LVS03371.
(2) Connection to be made according to the busbar drawings supplied by Schneider Electric.
Version : 14 - 15/12/2023
160E5600 TOC E-57
PrismaSeT P Active - Functional units www.se.com
Fupact ISFL
Vertical / 3P
Determining the busbars
Fusegear
Mounting Through cut-out front plate Through a 2/3 cut-out front plate Accessories
DD384443.EPS
DD384444.EPS
DD384445.EPS
40 150
0 650
Devices
ISFL160 ISFL160 ISFL250/400/630 ISFL 1250
Number of devices per row 9 10 5 2 -
Number of vertical modules 11 24 24 24 -
Mounting plates LVS03545 + (1) LVS03546 + (1) LVS03546 (1) + (2) LVS03546 + (2) -
Length adapter - + 5 x LV480870 (2) - - -
Conversion kit for direct conn. - + 5 x LV480854 (2) - - -
Front plates with cut-out LVS03736 [11] - - - -
[No. of vertical FAV 2/3 - LVS03735 [24 + 12] LVS03735 [24 + 12] LVS03735 [24 +12] -
mod.]
Side frame door cut-out LV480868 LV480868 LV480868 LV480868 -
LV480869 LV480869 LV480869 LV480869
Blanking plate LVS03740 LVS03740 LVS03741 (3) 2 x LVS03741 -
Busbars cover - - - - LVS04860
Characteristics b The fuses are installed on the b The fuses are installed on the horizontal bars which are in turn
horizontal bars which are in turn supported by a mounting plate
supported by a mounting plate b The front of the cubicle is made up of two parts:
b The front plates are secured to the v 2/3 cut-out front plate allowing introduction of the fuses
hinged front plate support frame. v 1/3 front plate support frame (12 modules) cat. number LVS08562
b The front may be covered either by on which the functional units are mounted
a cover frame or a plain or transparent b The front may be covered either by a cover frame or a plain or
door. transparent door.
b Current transformers can be b Current transformers can be installed behind ISFL fuse-switch-
installed behind ISFL fuse-switch- disconnectors.
disconnectors.
Connection Direct
Devices
ISFL160/630
Connection By cables or directly on the busbars with clamp fixing or pressure fixing
Distribution
Devices
ISFL160/630
Downstream connection With cable
(1) The bars are made by the customer: for choice of bars > pages G-2 to G-13.
(2) Adaptation accessories LV480870 + LV480855 used to:
b install two ISFL160 devices on a mounting plate LVS03546
b mix ISFL devices.
(3) Use 2 blanking plates per device.
Note:
b for ISFL160, by fixing screws only.
b for determining the busbar > page I-60.
E-58 TOC
Version : 14 - 15/12/2023
160E5600
PrismaSeT P Active - Functional units www.se.com
Fupact ISFT
Vertical / 3P
Installation on mounting plate or busbars
Determining the busbars Fusegear/Switch-disconnector
Mounting On base plate On busbars
Dd383589.eps
Dd383590.eps
40 150
0 650
Devices
ISFT100 ISFT100N ISFT160 ISFT250 ISFT400 ISFT630 ISFT100N ISFT160
Number of devices per row 5 8 4 2 2 1 6 4
Number of vertical modules 6 8 6 9 9 10 8 6
Mounting plates LVS03554 LVS03553 LVS03556 LVS03557 LVS03557 LVS03557 LVS03555 LVS03555
Front plates with cut-out LVS03320 [6] LVS03325 [8] LVS03321 [6] LVS03322 [9] LVS03323 [9] LVS03324 [8] LVS03325 [8] LVS03321 [6]
[No. of vertical downstream - - - - - LVS03802 [2] - -
mod.]
Connection Direct
Devices
Connection
ISFT100
must be made
ISFT100N ISFT160 ISFT250 ISFT400 ISFT630 ISFT100N ISFT160
E
Downstream, with cable or flexible bars
Long terminal shields - LV480756 LV480819 LV480824 LV480827 LV480831 - LV480819
Distribution
Version : 14 - 15/12/2023
160E5600 TOC E-59
PrismaSeT P Active - Functional units www.se.com
Fupact GS
Horizontal / Vertical
Extended rotary handle
Fusegear/Switch-disconnector
Mounting Horizontal
650+150
DD384452.EPS
40 150
0 650
Devices
GS32 GS63 GS100 (1) GS160 (1) GS250 GS400
3P or 4P
Number of devices per row 1
Number of vertical modules 3 5 7 8
Mounting plates LVS03559 LVS03560 LVS03560 LVS03564 LVS03566
Front plates with cut-out LVS03308 LVS03309 LVS03309 LVS03346 LVS03347
Nb of vertical downstream - - LVS03801 [1M]
modules
Upstream connection
Terminal 3P - - GS1AP33 GS1AP43
Cover 4P - - GS1AP34 GS1AP44
Mounting Vertical
650 + 150
DD381858.EPS
DD381859.eps
40 150
0 650
Devices
GS32 GS63 GS100 (1) GS160 (1) GS250 GS400
3P or 4P
Number of devices per row 3 2 1
Number of vertical modules 3 5 6
Mounting plates LVS03559 LVS03563 LVS03565 LVS03567
Front plates with cut-out LVS03308 LVS03309 LVS03349 LVS03349
Nb of vertical
modules downstream - - - -
Upstream connection
Terminal 3P - - GS1AP33 GS1AP43
Cover 4P - - GS1AP34 GS1AP44
DD381860.EPS
E-60 TOC
Version : 14 - 15/12/2023
160E5600
PrismaSeT P Active - Functional units www.se.com
Others
Mounting Door with cut-outs Mounting plate
DD385372.eps
DD385426.eps
40 150
0 650
60 150
0 650
Cover panels Roof with cut-out Fan + top hood Top hood without Outlet grill Fan with filter Spare filter
D = 400 mm D = 600 mm fan
Catalog number LVS08478 LVS08678 NSYCVF575M230MB NSYCAC228RMB NSYCAG291LPF NSYCVF850M230PF NSYCAF228R
Characteristics A roof with a cut-out Fan characteristics b Material: steel b Material: b P ower: 150/195 W For outlet grill
ensures natural b Power: 85 W b Finishing parts: Injected b Input voltage: or filter IP54,
ventilation of the b Input voltage: 230 V painted with thermoplastic 207 V... 244 V cut-out
equipment. b Throughput via outlet grill: epoxy-polyester (ASA PC). (230 V) 228 x 228 mm
It can also be equipped v with 1 outlet grill: 350 m3/hr resin, textured self- b Throughput via
with two fans. v Free with filter: 575 m3/hr RAL 7035 grey extinguishing outlet grill:
b Noise level: 64 dB. b IP54 according to v with 1 outlet grill
Top hood characteristics b Fixing to the top UL 94 V-0 (m3/h):
b Material: steel by means of b RAL 9003, 718 (50 Hz)
b Finishing parts: painted with caged nuts and white 568 (60 Hz)
epoxy-polyester resin, textured special screws b IP54 b Free with filter:
RAL 9003, white 838 (50 Hz)
b IP54 803 (60 Hz)
b Fixing to the top by means of b Noise level:
caged nuts and special screws 76/75 dB
Version : 14 - 15/12/2023
160E5700 TOC E-61
PrismaSeT P Active - Functional units www.se.com
Others
Mounting On a modular rail
DD381159.eps
Dd381166.eps
Dd381164.eps
Dd381165.eps
40 150
0 650
DD383817.eps
Dd381169.eps
DD383842.eps
40 150
0 650
DB421198.eps
DB421195.eps
DB421194.eps
E-62 TOC
Version : 14 - 15/12/2023
160E5700
PrismaSeT P Active - Functional units www.se.com
Modular devices
Acti 9 y 63 A
Compatible with PowerTag Energy
Circuit breakers
Mounting Horizontal distances between centres: Horizontal distances between centres: 150 mm
200 mm
Dd380771.eps
Dd385399.eps
Dd385400.eps
40 150
0 650
Mounting Horizontal distances between centres: Horizontal distances between centres: 150 mm
200 mm
Dd382519.eps
650
400
E
Devices All modular devices Modular devices 40 A
Rail length (modules of 9 mm) 20 20
No. of vertical modules 4 3
Rail (20 modules of 9 mm) LVS03404 (adjustable) LVS03404 (adjustable)
Modular front plates LVS03214 [4] LVS03213 [3]
Blanking plate strip LVS03220 LVS03220
divisible LVS03221 LVS03221
DD384088.EPS
EnerlinX devices
IFM I/O module IFE ComX200 ComX510
I6
C
I5
I4
vC
IFM.eps
+24V
IFE.eps
I3 0V
I2
IO.eps
Comx200.eps
C
I1
I6
C
I5
I4
C
I3
C
I2 Eth2
I1
+ Eth1
C
24VD
ER
POW
230V
100- ER
Turn off all power before working on this equipment.
POW
Failure to follow these instructions will result in death
HAZARD OF ELECTRIC SHOCK,
DANGER
A1
EXPLOSION, OR ARC FLASH
ER
POW
O1
EB
X2
100
-230
00
24V V
~
50/6 1.2A 0.6A
0 Hz
’X 200
Com
or serious injury.
Mad
e in
GER
MAN
Y
A1
T2
O3 T1
34
O2 33
24
O1 23
14
13
Version : 14 - 15/12/2023
160E5700 TOC E-63
PrismaSeT P Active - Functional units www.se.com
DD380769.eps
DD380770.eps
400
650
Dd382522.eps
650
400
Connection Insulated Rear Linergy BS Linergy BS Linergy DP 1P, Linergy DX 4P, Linergy DS
Linergy BW busbars multi-stage 160 A 160 A multi-stage
busbars busbars distribution distribution distribution
block block
Dd382578.eps
Dd382628.eps
Dd383648.eps
DD381402.eps
Dd381308.eps
DD385267.eps
Type of connected devices All type All type All type All type All type All type
Distribution block / busbars > page G-9 > page G-11 > page G-14 > page G-22 > page G-26
Connection must be made must be made > page G-14 > page G-22 must be made
(1) Can be completed by a rail + raiser (cat. no. LVS04227) to instal modular devices on.
Note: width of NG160 circuit breakers: NG160 3P: 10 modules / NG160 4P: 14 modules
Vigi NG160 3P: 24 modules / Vigi NG160 4P: 27 modules
width of NG125 circuit breakers: NG125 3P: 9 modules / NG125 4P: 12 modules
Vigi NG125 3P y 63 A: fixed sensitivity 18 modules
adjustable sensitivity 20 modules
> 63 A : fixed sensitivity 20 modules
adjustable sensitivity 20 modules
Vigi NG125 4P y 63 A : fixed sensitivity 21 modules
adjustable sensitivity 23 modules
> 63 A : fixed sensitivity 23 modules
adjustable sensitivity 23 modules
C120 or iC120 3P: 9 modules / C120 or iC120 4P: 12 modules
Vigi C120 or iC120 3P: 19 modules / Vigi C120 or iC120 4P: 22 modules
width of devices: INS-INV40/80: width 10 modules
INS-INV100/160: width 15 modules.
(2) Can be completed by a rail + raiser (LVS04227) to instal modular devices on.
Note: to mix an NSA125/160 circuit breaker with Multi 9 or Acti 9 modular devices, order (with the device) the symmetrical rail + raiser set (28041).
Width of devices: NSA125/160 3P: 10 modules / NSA125/160 4P: 14 modules.
E-64 TOC
Version : 14 - 15/12/2023
160E5700
PrismaSeT P Active - Functional units www.se.com
Metering
Single-phase and 3-phase kilowatt-hour meters
Class 1 & 2
Others
Mounting With 1 mounting plate
DD383114.eps
DD383112.eps
DD383113.eps
40 150
0 650
DD383117.eps
40 150
0 650
DD382952.eps
40 150
0 650
Version : 14 - 15/12/2023
160E5700 TOC E-65
PrismaSeT P Active - Functional units www.se.com
Others
Dd381689.eps
PowerLogic range of meters help manage all energy assets,
every second of the day.
front plate.
> Blanking plates are available to blank off any
unused locations.
> Economical solution.
1
The ideal fit for cost management applications,
the PowerLogic™ PM5000 power meter provides : > In the device zone of enclosures and
> Sub-billing/tenant metering cubicles, like a front plate
> Equipment sub-billing
> Energy cost allocation
> Track real-time power conditions
> Monitor control functions
> Provide basic power quality values
> Monitor equipment and network status.
A
60
10 A
0
> Bill checking to verify that you are only charged for the 40
A
60
60
10 A
0
including WAGES
> Aggregation of energy consumption, including WAGES, and
allocating costs per area, per usage, per shift, or per time within
the same facility
> Basic metering of electrical parameters to better understand The degree of protection for installed devices is
the behavior of your electrical distribution system. IP30.
Combined with communication systems, like Smart Link, the Acti
9 iEM2000 & iEM3000 series makes it easy to integrate electrical Notes:
distribution measurements into facility management systems. • To maintain the IP55 degree of protection, the
It’s the right energy meter at the right price for the right job. measurement devices must be installed behind a
transparent door. If they are installed on a plain door, use
the corresponding mounting plates.
• With a power voltage > SELV (12 V), devices on front plates
Possible installation must be mounted with a front plate hinge kit (cat no.
Cat. number LVS LVS LVS LVS LVS LVS LVS LVS08585). The earthing braid must be connected to the
03904 03928 03910 03911 03913 03912 03914
front plate frame support (cat no. LVS08566, LVS08564,
Front plate frame b b b b b b b
LVS08560, LVS08562 or else).
support (LVS08566)
L300/L400 with b b b b b - - • With a power voltage > SELV (12 V) and a supply
cut-out (LVS08593, protection > 16 A, in addition to the preceding rule, the front
LVS08594) plate frame support (cat no. LVS08566, LVS08564,
Note: device mounting on door: earthing braid (cat. no. LVS08910) or earthing LVS08560, LVS08562 or else) must be connected to the
wire (cat. no. LVS08911) mandatory. cubicle frame, using an earthing braid (cat no. LVS08910 or
LVS08911). (standard NF / EN 61439-1 2011 edition).
E-66 TOC
Version : 14 - 15/12/2023
160E5700
PrismaSeT P Active - Functional units www.se.com
Others
Number and type of Metal front plate with
No. of Plastic Blanking plate or devices support
devices per row cut-out vertical mounting
mod. plates with
cut-out
W650 Mounting on an interface with plastic mounting plates
To blank-off or install:
DD385465.eps
DD385466.eps
- 1 to 4 Ø 16 or 22 mm buttons
Vigirex and others
DD385458.eps
5 x 72 x 72 - 1 device, 45 x 45
devices 72 x 72
LVS03902 LVS03900
3
Power Meter and others To blank-off or install:
DD385467.eps
DD385468.eps
4x
devices 96 x 96 -1 to 4 Ø 16 or 22 mm buttons
or 96 x 96 - 1 device, 45 x 45
2x For PM200, 200P, PM5 - one 72 x 72 device
(2) & PM8 series meters LVS03904 LVS03903 LVS03901
W650 Mounting on an inclined visor by 30° with plastic mounting plates
To blank-off or install:
DD385465.eps
DD385466.eps
- 1 to 4 Ø 16 or 22 mm buttons
Vigirex and others - 1 device, 45 x 45
DD385459.eps
5 x 72 x 72
devices 72 x 72
LVS03902 LVS03900
3
Power Meter and others To blank-off or install:
DD385467.eps
DD385468.eps
4x
devices 96 x 96 -1 to 4 Ø 16 or 22 mm buttons
or 96 x 96 - 1 device, 45 x 45
2x - one 72 x 72 device
For PM200, 200P, PM5
(2) & PM8 series meters LVS03928 (1) LVS03903 LVS03901
W650 Direct mounting on a metal front plate with cut-outs
72 x 72 device
Direct mounting To blank-off or install: E
DD385460.eps
DD385469.eps
- 1 or 2 Ø 22 mm buttons
- 1 device, 45 x 45
Vigirex and others
6 x 72 x 72 3
devices 72 x 72
LVS03910 - LVS03907
96 x 96 device
Direct mounting To blank-off or install:
DD119465.eps
DD385470.eps
- 1 or 2 Ø 22 mm buttons
- 1 device, 45 x 45
Power Meter and others
3x 96 x 96 3 - one 72 x 72 device
devices 96 x 96
LVS03911 - LVS03908
Direct mounting To blank-off or install:
DD385462.eps
DD385470.eps
- 1 or 2 Ø 22 mm buttons
- 1 device, 45 x 45
Power Meter and others
1 x 96 x 96 3 - one 72 x 72 device
devices 96 x 96
LVS03913 - LVS03908
144 x 144 device + 72 x 72 devices
Direct mounting To blank-off or install:
DD385469.eps
144
1x x - 1 or 2 Ø 22 mm buttons
144 - 1 device, 45 x 45
144 x 144 device -
+ + 4
devices 72 x 72
4 x 72 x 72
- - LVS03907
W650 Pushbuttons and lamps Ø 22 mm
Direct mounting
DD385464.eps
12 x Ø 22 mm 2
LVS03914 - -
W400 Front plate
Direct mounting To blank-off or install:
DD385860.eps
DD385470.eps
- 1 or 2 Ø 22 mm buttons
Power Meter and others - 1 device, 45 x 45
1 x 96 x 96 3
devices 96 x 96 - one 72 x 72 device
LVS03923 - LVS03908
(1) The visor (cat. no. LVS03928) can be installed on a plain door with cut-out.
(2) For PM200, 200P, PM5 & PM 8 series meters, use 2 no. blank off sheets between each meter.
Version : 14 - 15/12/2023
160E5700 TOC E-67
PrismaSeT P Active - Functional units www.se.com
DD380769-iEM300.eps
Dd383019-modif.eps
150
Mounting_FDM128_L600.eps
40
0 650
1
1
t
s
m
Devices
FDM121, PM5000 & PM8000 series (2) PM3000 series, FDM128 (1) PM5RD, PM89RD96,
1 device 3 devices IEM2000 & iEM3000 series PM5563RD (3)
Number of vertical mod. 3 3 3 or 4 4 4
DIN rail - - LVS03402 - LVS03402
Front plates transparent - LVS03342 [4] - -
[No. of vert. plain - - LVS03804 [4] LVS03804 [4]
modules] with cut-out LVS03913 [3] LVS03911 [3] LVS03203 [3] - -
Front plate with cut-out for devices 96 x 96 hole ø 22 mm to be hole ø 30 mm to be
stamped stamped
50
400 6
1
1
t
s
m
Devices
FDM121, PM5000 series, FDM128 (1) PM5RD, PM89RD96,
PM8000 series (2) PM5563RD (3)
Number of vertical mod. 3 4 4
DIN rail - - LVS03404
Front plates with cut-out LVS03923 [3] - -
[No. of vert. plain - LVS03814 [4] LVS03814 [4]
modules]
Front plate with cut-out for devices 96 x 96 hole ø 22 mm to be stamped hole ø 30 mm to be stamped
Mounting Vigilohm
Dd381754.eps
Dd381720.eps
Dd383019-IM10.eps
40 150
0 650
10
9
8
7
Vigirex
RM12
GERIN
MERLIN
Vigirex
RH10M
on
Reset
fault
Test
no trip
Test
Devices
IM400 IM10, IM10H, IM20, IM20H IM10 / IM10H
with 3 XD301 or with 1 or 2 IFL12 HV-IM20, HV-IM400, IM9, IM9-OL IM20 / IM20H
Number of vertical mod. 6 3 3
Modular rail - LVS03401 -
Mounting plates LVS03930 - -
Front plates with cut-outs LVS03932 LVS03203 LVS03911
Characteristics Installation in the device compartment
Dd381722.eps
Dd381720.eps
40 150
0 650
4 5
3
2
MERLIN
GERIN
3
4 5 A MERLIN
GERIN
Vigirex 2 Vigirex
RH10M RH10M
on A on
Reset Reset
fault fault
Test Test
no trip no trip
Test Test
Devices
RH10/RH21/RH99/RH197M relays Lamps, pushbuttons Ammeter, voltmeter
Number of vertical mod. 3 2 3
Modular rail LVS03401 LVS03401 LVS03401
Front plates with cut-outs LVS03203 LVS03202 LVS03203
Blanking strip LVS03220 LVS03220 LVS03220
plate divisible LVS03221 LVS03221 LVS03221
Characteristics Installation in the device compartment
(1) For 72 x 72 mm cases > page E-66.
(2) Only for flush-mounted versions of PM5000 series and PM8000 series.
(3) Only for remote-display versions of PM5000 series and PM8000 series.
E-68 TOC
Version : 14 - 15/12/2023
160E5700
www.se.com
Version : 14 - 15/12/2023
160E5700 TOC E-69
Cubicles
PrismaSeT P Active - Cubicles www.se.com
Contents
Enclosures
Cover panels F-2
Cubicles
Frameworks F-5
Dimensions
Cubicles F-7
Enclosures
Cubicles
IP30/31 cover panels F-14
IP55 cover panels F-17
Plinth F-19
Cubicle handling and Lifting reinforcement kit F-20
Installation accessories F-21
Front plate accessories F-22
Others
Reserve space F-23
Fixing accessories F-24
Universal adapter
PrismaSeT G Active adapter - Mounting on a plain backplate F-25
Others devices
Mounting on a slotted plate - Mounting on a modular rail F-26
Cable running F-27
Connection accessories
Cable-tie supports, lateral and longitudinal cross-members F-28
Door handles and locks F-29
Ventilation accessories F
Panel installation F-30
Roof installation F-32
Heat F-33
Regulating F-34
Switchboard lighting F-35
Version : 14 - 15/12/2023
160E6000 TOC F-1
PrismaSeT P Active - Cubicles www.se.com
Cover panels
Enclosures
400 mm deep switchboard
DD385980.eps
For switchboards with front connections.
b front panels
Any of the following can be installed in front of the hinged
front plate frame support:
v a transparent door (IP30 or IP55)
v a plain door (IP30 or IP55)
v a fixed cover frame (IP30)
b rear panel = screw-on panel
b side panels = set of two panels
b plain roof
b gland plates (plain or in two parts).
Parts list for switchboard 1
1 LVS08406: framework, W = 650, D = 400, H = 2000
2 LVS08566: front plate frame support, W = 650
3 LVS08576: cover frame, W = 650
4 LVS08736: rear panel,W= 650 (two half panels)
LVS08751D: PrismaSeT P Active Green Cover + Wireless
5
Panel Server W650 +lateral panels D400
6 LVS08436: plain roof, W = 650, D = 400
7 LVS08486: plain gland plate, W = 650, D = 400
DD380607.eps
F-2 TOC
Version : 14 - 15/12/2023
160E6100
PrismaSeT P Active - Cubicles www.se.com
Cover panels
Enclosures
800 mm deep switchboard
DD386036.eps
Made up of two cubicles back-to-back.
Rear connections are possible.
b front panels
Any of the following can be installed in front of the hinged front
plate frame support:
v a transparent door (IP30 or IP55)
v a plain door (IP30 or IP55)
v a fixed cover frame (IP30)
b rear panel = screw-on panel
b side panels = set of two panels
b plain roof
b gland plates (plain or in two parts).
Version : 14 - 15/12/2023
160E6100 TOC F-3
PrismaSeT P Active - Cubicles www.se.com
Cover panels
Enclosures
1000 mm deep switchboard
DD386035.eps
Made up of two cubicles back-to-back.
Rear connections are possible.
b front panels
Any of the following can be installed in front of the hinged front
plate frame support:
v a transparent door (IP30 or IP55)
v a plain door (IP30 or IP55)
v a fixed cover frame (IP30)
b rear panel = screw-on panel
b side panels = set of two panels
b plain roof
b gland plates (plain or in two parts).
F-4 TOC
Version : 14 - 15/12/2023
160E6100
PrismaSeT P Active - Cubicles www.se.com
Cubicles
Frameworks
Enclosures
Mounting Frameworks
DD380572.ai
DD380575.ai
DD380577.ai
DD380573.ai
DD380574.ai
DD380576.ai
Width (mm) 300 400 650 800 800 300 400 650 800 800
(650 + 150) (650 + 150)
Depth 400 mm Depth 600 mm
Cat. no. LVS08403 LVS08404 LVS08406 LVS08408 LVS08407 LVS08603 LVS08604 LVS08606 LVS08608 LVS08607
Composition 2 frames 3 frames
- + 2 additional equipped with intermediate uprights for the mounting plates
uprights
b 4 cross-pieces.
b Mounting hardware.
b Framework combinations
Characteristics b Cubicles can be combined side-by-side and back-to-back.
b Can be equipped with IP30 or IP55 cover panels.
Note: for the 800 mm width, the busbar compartment can be on the left or right
Mounting Hinged front plate frame support Fixed front plate frame support
Dd381324.ai
Dd381325.ai
DD383935.eps
DD385530.eps
Version : 14 - 15/12/2023
160E6200 TOC F-5
PrismaSeT P Active - Cubicles www.se.com
Cubicles
Frameworks
Enclosures
Framework combinations
DD380751.eps
DD380752.eps
x6
Dd381325.eps
x6
Accessories
Dd381327.eps
Dd383048.eps
Type Commodities
Fixing screws and nuts
Cat. no. LVS08921 LVS08718
Characteristics Set of 20 screws + wing nuts for framework Set of 10 screws + combination accessories
F-6 TOC
Version : 14 - 15/12/2023
160E6200
PrismaSeT P Active - Cubicles www.se.com
Cubicles
Dimensions
Frameworks, D = 400 mm
Dd381875.eps
Dd381822.eps
Dd381823.eps
Frameworks, D = 600 mm
Dd381824.eps
Dd381825.eps
Dd381826.eps
F
Dd381827.eps
Dd381893.eps
Fixing to floor
Without plinth With plinth
Dd381829.eps
Dd381830.eps
A B
300 262.5
400 362.5
650 612.5
800 762.5
Version : 14 - 15/12/2023
160E6200 TOC F-7
PrismaSeT P Active - Cubicles www.se.com
Cubicles
Dimensions
Cubicle with cover panels
Height Width
Dd381831.eps
Dd385515.eps
Dd385516.eps
DD385518.eps
aSeT
Prism
1927
30
A + 60 A + B + 60
Depth
Door in front and panel in rear Doors front and rear
Dd382322.eps
Dd382323.eps
Dd382324.eps
Dd382325.ai
876/
1076
Door
IP30 door IP55 door
Dd381834.eps
Dd381835.eps
Dd381836.eps
Dd381837.eps
Dd381828.eps
F-8 TOC
Version : 14 - 15/12/2023
160E6200
PrismaSeT P Active - Cubicles www.se.com
Cubicles
Dimensions
Linergy LGYE busbars
630 A - 1600 A 2000 A - 2500 A 3200 A - 4000 A
60 100
DD384597.eps
DD384598.eps
DD384599.eps
150
23
31
31
2000 2000 2000
DD384601.eps
DD384589.eps
DD384590.eps
Layout of vertical Linergy LGYE busbars
630 A - 1600 A
DD384591.eps
DD384592.eps
DD384593.eps
DD384594.eps
F
99 99 99
99
2000 A - 2500 A 3200 A - 4000 A
DD384595.eps
DD384596.eps
121,5
99 211,5
300
Dd386498.ai
10
Dd386499.ai
50/60/80
100/120
Dd381851.eps
Dd381852.eps
Dd381853.eps
Version : 14 - 15/12/2023
160E6200 TOC F-9
PrismaSeT P Active - Cubicles www.se.com
Cubicles
Dimensions
Vertical Linergy LGY busbars
Dd381855.eps
Dd381856.eps
Dd381857.eps
Dd381858.eps
630 A. 800 A. 1000 A.
DD385497.eps
DD385498.eps
1250 A. 1600 A.
Dd381862.eps
Dd381863.eps
Dd381864.eps
Dd381865.eps
D = 400 mm B 284
C 242
D = 600 mm B 484
C 442
F-10 TOC
Version : 14 - 15/12/2023
160E6200
PrismaSeT P Active - Cubicles www.se.com
Cubicles
Dimensions
Vertical Linergy BS busbars
Dd119384.ai
Dd381866.eps
10
Dd119385.ai
50/60/80
100/120
Dd381869.eps
Dd381870.eps
Dd381871.eps
Dd381872.eps
A
50 60 80
D = 400 mm B 284 274 254
C 250 240 220
D = 600 mm B 484 474 454
C 450 440 420
Version : 14 - 15/12/2023
160E6200 TOC F-11
PrismaSeT P Active - Cubicles www.se.com
Cubicles
Dimensions
Plain gland plates
Dd381838.eps
A C
300 110
400 210
650 460
800 610
Dd384558.eps
Dd381840.eps
Dd384559.eps
Dd381842.eps
F-12 TOC
Version : 14 - 15/12/2023
160E6200
PrismaSeT P Active - Cubicles www.se.com
Cubicles
Dimensions
Two-part gland plates
Dd381838.eps
Dd381843.eps
Dd381844.eps
Dd381845.eps
Dd381846.eps
Dd381847.eps
Dd381848.eps
Version : 14 - 15/12/2023
160E6200 TOC F-13
PrismaSeT P Active - Cubicles www.se.com
Cubicles
IP30/31 cover panels
Enclosures
Mounting Front doors
DD385485.eps
DD119390.ai
DD119388.ai
DD119389.ai
Dimensions (mm) W = 300 W = 400 W = 650 W = 800
Plain door LVS08513 LVS08514 LVS08516 LVS08518
Transparent door - LVS08534 LVS08536 LVS08538
Door with cut-out LVS08593 LVS08594 - -
Reinforced plain door - LVS01224 LVS01225
Characteristics b Reversible for left or right-hand opening IP31.
b Equipped with a handle and keylock (key 405).
b Plain door are IK10 with 3 hinges.
b Reinforced plain door are IK10 with 3 hinges.
b Transparent door are IK10 with 3 hinges.
For other possibilities > page F-29.
Note: the door with cut-out can be equipped with front plates for 72 x 72 or 96 x 96 instruments > page E-66.
The 800 mm door is supplied with a 150 mm barrier for the side compartment, plus a finishing accessory to improve the
appearance of the upright.
Cover frame - LVS08574 LVS08576 LVS08578 (1)
Dd385486.eps
(1) For 800 mm wide frameworks, the 650 mm frame is supplied with a plain wicket door, 150 mm wide.
F-14 TOC
Version : 14 - 15/12/2023
160E6200
PrismaSeT P Active - Cubicles www.se.com
Cubicles
IP30/31 cover panels
Enclosures
Mounting Kit: Side Panels + Voltage Presence Mounting Roof
Indicator/Wireless Panel Server +
DD380601.eps
adapted Green Cover
Version : 14 - 15/12/2023
160E6200 TOC F-15
PrismaSeT P Active - Cubicles www.se.com
Cubicles
IP30/31 cover panels
Right angle kit
DD385532.eps
40 65
0 650 0 400
40 65
0 650 0 400
F-16 TOC
Version : 14 - 15/12/2023
160E6200
PrismaSeT P Active - Cubicles www.se.com
Cubicles
IP55 cover panels
Enclosures
Mounting Front doors
DD119389.ai
DD119388.ai
DD119390.ai
DD385485.eps
Dd385488.eps
Version : 14 - 15/12/2023
160E6200 TOC F-17
PrismaSeT P Active - Cubicles www.se.com
Cubicles
IP55 cover panels
Enclosures
Mounting Kit: Side Panels + Voltage Presence
Indicator/Wireless Panel Server + Mounting Roof
adapted Green Cover
DD380601.eps
Dimensions (mm) W = 300 W = 400 W = 650 W = 800
Dimensions (mm) D = 400 D = 600
Plain roof D = 400 mm LVS08453 LVS08454 LVS08456 LVS08458
W 400 LVS08755D LVS08765D
Plain roof D = 600 mm LVS08653 LVS08654 LVS08656 LVS08658
W 650 LVS08756D LVS08766D
Characteristics b Supplied with quarter-turn fasteners for mounting on
W 800 LVS08757D LVS08767D the framework
Rear side panels LVS08763 - b With markings for cut-outs, if necessary.
Characteristics Supplied with quarter-turn fasteners.
b IP31 sealing kit LVS08711
Voltage Presence Indicator to be installed on
b Characteristics The kit is made up of a self-adhesive gasket that
main incomer section. attaches to the roof and a deflector.
It ensures the IP31 degree of protection for a 650 or 800
mm wide cubicle, or for two cubicles (800 + 400) when
they are equipped with plain or transparent front doors.
Green Cover to fix on top of each frame
Rear Side panels
Characteristics For combinations of two cubicles with different
b
depths like 800 (400+400) and 1000
(400+600).
These panels cannot be installed on the front
b
cubicles.
Dd381328.eps
F-18 TOC
Version : 14 - 15/12/2023
160E6200
PrismaSeT P Active - Cubicles www.se.com
Cubicles
Plinth
Enclosures
Mounting Two-part gland plates IP55, gland plates
Dd381335.eps
Dd381334.eps
Degree of protection IP30/IP31 IP55
Dimensions (in mm) D400 D600 D400 D600
W = 300 mm LVS08493 LVS08693 LVS08483 LVS08683
W = 400 mm LVS08494 LVS08694 LVS08484 LVS08684
W = 650 mm LVS08496 LVS08696 LVS08486 LVS08686
W = 800 mm (650 + 150) LVS08497 LVS08697 LVS08487 LVS08687
W = 800 mm LVS08498 LVS08698 LVS08488 LVS08688
F
Dimensions (mm) W = 300 W = 400 W = 650 W = 800 D = 400 D = 600
Four corner posts + two LVS08723 LVS08724 LVS08726 LVS08728 - -
cross-pieces (front and rear)
Two side plates - - - - LVS08720 LVS08721
Characteristics The plinth is made up of two Catalog numbers:
b one Catalog number comprising four corner posts + two cross-pieces (front and rear), that can be used in side-by-side
combinations or stacked to form a plinth 200 mm high (maximum)
b one Catalog number comprising two side plates (400 or 600 mm).
Each Catalog number is supplied with the necessary hardware.
Examples
Dd381331.eps
Dd381333.eps
Dd385527.eps
200 max.
Side-by-side combination of two cubicles Two stacked plinths. The front and rear cross-pieces can be
with a plinth. easily removed for a pallet-mover.
Version : 14 - 15/12/2023
160E6200 TOC F-19
PrismaSeT P Active - Cubicles www.se.com
Cubicles
Cubicle handling and Lifting reinforcement kit
Enclosures
Mounting Cubicle handling and rolling base
DD383845.eps
LVS08716
DD380652.eps
50
Dimensions (mm) D = 400 D = 600 L1200 to L1900 L2000 to L2550 L2650 to L3050
2 cubicle handling base end-pieces LVS08714 LVS08716 - - -
Cubicle handling - - - LVS08706 -
Characteristics This type of base is designed to avoid any risk of cubicle deformation during transport and handling.
Five different Catalog numbers offer 27 width possibilities (1200 to 3050 mm) for 400 and 600 mm deep cubicles.
b Two Catalog numbers each include 2 end-pieces for handling bases for 400 and 600 mm deep cubicles respectively and
the corresponding mounting hardware.
b Three Catalog numbers each include 2 lengths for the sides of handling bases for 1200 to 3050 mm wide cubicles
respectively and the corresponding mounting hardware.
Handling bases can be used for both side-by-side and back-to-back cubicle combinations.
In this case, the mounting hardware for one of the sets is used.
DD383839.eps
650 400 800 800 800 300
650 300
400 400 650 300
400 400
u M10
F-20 TOC
Version : 14 - 15/12/2023
160E6200
PrismaSeT P Active - Cubicles www.se.com
Installation accessories
Enclosures
Mounting Lifting rings Framework stabiliser kit
Dd381541.ai
DD383846.ai
Cat. no. LVS08700 LVS08701
Characteristics b Set of four lifting rings screwed to the framework. b Made up of four blocks under the framework
b Use a set of lifting rings for each framework (W = 650 and b Suitable for all types of cubicles, whatever the width and depth
800 mm) containing devices. b Increases the stability of the cubicle during mounting of devices
b When two cubicles with devices have been combined, use a b Makes possible cubicle handling using a pallet mover or a forklift
lifting beam. b Protects the front, side and rear cover panels during handling
b can be installed and removed without removing the roof b Can be reused.
b even if they are left attached, the switchboard conserves its
original degree of protection.
Dd381542.eps
Dd381543.eps
Mounting Levelling kit False floor fixing kit Floor/wall fixing kit
Dd381549.eps
Dd381547.ai
Dd381548.ai
F
Dd381550.ai
Dd381553.ai
Dd381554.eps
Dd381552.ai
Version : 14 - 15/12/2023
160E6200 TOC F-21
PrismaSeT P Active - Cubicles www.se.com
DD383950.eps
DD384030.eps
DD384029.eps
OK
A
B
Identification labels
Used for Clip-on labels Engraving plates
Dd383975.eps
DD383974.eps
T
LIGH LIGH
T
DD381753.eps
Accessories
Used for Switchboard identification plate Drawing holder Touch-up accessories
DD385306.eps
DD381208.eps
DD381721.eps
F-22 TOC
Version : 14 - 15/12/2023
160E6200
PrismaSeT P Active - Cubicles www.se.com
Reserve space
Others
Reserve space
DB417928.eps
400
Reserve space
DB417926.eps
650
Version : 14 - 15/12/2023
160E6200 TOC F-23
PrismaSeT P Active - Cubicles www.se.com
Fixing accessories
Others
Clip-nuts
Mounting For slotted mounting plates For modular rails For lateral and longitudinal
cross-members
Dd381313.eps
DD381312.eps
Dd381612.eps
M4 LVS03180 LVS03164 -
M5 LVS03181 LVS03165 -
M6 LVS03182 LVS03166 LVS03194
Characteristics Set of 20 Set of 20 Set of 20
Mounting of various devices Mounting of various devices Mounting in cubicles
Pratic raiser
Raiser
DD381576.eps
DD381314.eps
Hexagonal spacers
Hexagonal spacers
Dd380828.eps
Dd380828.eps
Dd380828.eps
Dd380828.eps
Dd380828.eps
DD381577.eps
DD382920.eps
DD383078.eps
F-24 TOC
Version : 14 - 15/12/2023
160E6200
PrismaSeT P Active - Cubicles www.se.com
Universal adapter
PrismaSeT G Active adapter
Mounting on a plain backplate
Others
PrismaSeT G Active adapter
W = 500 W = 250
DD381603.eps
Catalog number LVS03595 LVS03596
Characteristics For installation in a device compartment W = 650 mm For installation in a device compartment W = 400 mm
Kit with four lateral and two longitudinal cross-members that can be depth adjusted.
Installation of components, notably the functional mounting plates, the Linergy BW insulated busbars and the 400 A rear
Linergy BS busbars.
Dd381309.ai
40 150
0 650
Note: the adapter LVS03595 can be used for all mounting plates, except LVS03030.
The Linergy BW busbars can be positioned to the left, middle or right of the modular row.
Depth adjustable, the busbars can be supplied by a ComPacT INS-INV switch-disconnector or a fixed/withdrawable ComPacT NSX circuit breaker, whatever the
type of operating system (toggle, rotary handle, motor mechanism).
For Linergy BW busbars, order two adapters (LVS03595 x 2).
Version : 14 - 15/12/2023
160E6200 TOC F-25
PrismaSeT P Active - Cubicles www.se.com
Others devices
Mounting on a slotted plate
Mounting on a modular rail
Others
Mounting on a slotted plate
Mounting Slotted mounting plates + lateral cross-members Slotted mounting plate
without lateral cross-
members
Dd381178.eps
Dd381175.eps
Dd381176.ai
40 150
0 650
Dd381187.eps
Dd381310.eps
Dd381186.ai
40 150
0 650
(1) Example of a Linergy busbars installed in a busbar compartment, on a modular rail cat. no. LVS04226 + LVS03581 + LVS08794: > page G-38.
Dd381185.ai
F-26 TOC
Version : 14 - 15/12/2023
160E6200
PrismaSeT P Active - Cubicles www.se.com
Cable running
Others
Straps and covers
Type Vertical cable straps Covers for vertical Horizontal cable Covers for horizontal
cable straps straps cable straps
Dd381622_R.eps
Dd381632.ai
DD381629.eps
Dd381633.eps
Dd381618.eps
Dd381621.eps
Catalog number LVS04262 LVS04263 LVS04239 LVS04243
Characteristics Set of 12 Set of 2 x 1 m Set of 12 Set of 4 covers of 430 mm
Horizontal cable straps have
the same capacity as
60 x 30 mm trunking.
Trunking supports
Type Horizontal trunking supports Adaptable support for horizontal trunking
Dd382924.eps
Dd382320.eps
Dd381626.eps
Dd382922.eps
Trunkings
Type Vertical trunkings 80 x 60 mm Horizontal trunkings 60 x 30 mm Cable trunkings for doors 30 x 30 mm
Dd381640.eps
Dd381639.eps
Dd381641.eps
DD384168.eps
Connection accessories
Cable-tie supports, lateral and longitudinal cross-members
Others
Mounting Longitudinal cable-tie supports Lateral cable-tie supports
DD381557.ai
DD381556.ai
Dd381638.ai
Catalog number LVS08773 LVS08774 LVS08776 LVS08778 LVS08794 LVS08796
Characteristics W = 300 W = 400 W = 650 W = 800 D = 400 mm D = 200 mm
mm mm mm mm
Set of 4, supplied with the necessary hardware for For frameworks that are 400 mm deep, assign a 400 mm deep
connection to the framework. Cable-tie supports are support to a 200 mm deep support.
used to correctly position the cables in the connection
compartment.
Dd383425.ai
Catalog number LVS08783
Characteristics C-shaped 1600 mm long support, supplied with hardware for mounting on universal angle brackets and modular rails, that
can be cut to length as needed.
Can be secured to:
b universal angle bracket LVS03581 (for the longitudinal support)
b universal angle bracket LVS03582 (for the lateral support)
b modular rail LVS03593 (for depth adjustment).
DD381581.eps
150
Dd381580.eps
40
0 650
F-28 TOC
Version : 14 - 15/12/2023
160E6200
PrismaSeT P Active - Cubicles www.se.com
Others
Handles and padlocking
EURO handle
Dd119386.ai
ASSA/ABLOY handle RAL 7016 rotary handle Padlocking
nnz3131101_1.eps
Dd119387.ai
nnz3131101-p_2.eps
Cat. no. LVS07932 LVS07933 LVS07931 LVS07938
Characteristics Supplied without barrel Supplied without barrel Supplied with barrel lock (key no. For new rotary handle
405) RAL 7016
Earthing braid
Earthing braid is used to earth a door or wicket door with devices.
Earthing braid, 6 mm2 Earthing wire, 6 mm2
DD384368.eps
DD384368.eps
Version : 14 - 15/12/2023
160E6200 TOC F-29
PrismaSeT P - Cubicles www.se.com
Ventilation accessories
Panel installation
Others
Front plate Ventilated front plate
Dd381676.eps
Cat. no. LVS03891 LVS03895
Height 1 vertical module, 3 vertical modules,
H = 50 mm H = 150 mm
Characteristics Degree of protection: IP30.
Located at the top and bottom of the switchboard, ventilated front plates facilitate natural convection in the switchboard.
Surface area of the 80 cm2 250 cm2
openings
Forced-air 38 m3/hr 85 m3/hr 165 m3/hr 300 m3/hr 560 m3/hr 850 m3/hr
ventilation
PB501050_R.eps
PB501051_R.eps
PB501052_R.eps
PB501052_R.eps
PB501053_35.eps
PB501053_35.eps
Cat. no. NSYCVF38M230PF NSYCVF85M230PF NSYCVF165M230PF NSYCVF300M230PF NSYCVF560M230PF NSYCVF850M230PF
Unimpeded 50 Hz 38 85 165 300 562 838
throughput via 60 Hz 39 98 193 350 586 803
filter (m3/hr)
Throughput via 50 Hz 25 63 153 (1) 260 473 718
outlet grill (m3/hr) 60 Hz 26 72 171 (1) 307 477 568
Power drawn (W) 4,5/4,8 17/15 16.3/14.3 36/37 68/85 150/195
(max. intensity (A)) (0,16/0,17) (0.121/0.097) (0.12/0.94) (0.171/0.16) (0.52/0.370) (0.65/0.85)
Noise level (dB (A)) 40/41 46/49 50/51 55/56 59/59 76/75
External dimensions 137 x 117 x 49 170 x 150 x 62 268 x 248 x 104 268 x 248 x 116 336 x 316 x 161 336 x 316 x 162
(cutting) (92 x 92) (125 x 125) (223 x 223) (223 x 223) (291 x 291) (291 x 291)
Weight (kg) 0,220 0.780 1.140 1.3 3.2 4.1
Operating temperature -10...+70 °C -20...+60 °C -20...+60 °C -10...+70 °C -15...+60 °C -15...+60 °C
Outlet grill
Cat. no. NSYCAG92LPF NSYCAG125LPF NSYCAG223LPF NSYCAG223LPF NSYCAG291LPF NSYCAG291LPF
EMC cover
F-30 TOC
Version : 14 - 15/12/2023
160E6300
PrismaSeT P - Cubicles www.se.com
Ventilation accessories
Panel installation
Others
Dimensions
NSYCVF38M230PF
13
DB300459.eps
DB300460.eps
DB300461.eps
137
92 x 92
91,85
80
117
49 9
NSYCVF85M230PF
15
DB300463.eps
DB300464.eps
DD385568.eps
170
124,85
119
125 x 125
150
62 9
NSYCVF165M230PF
18
DB300467.eps
DB300468.eps
DB300469.eps
268
222,7
119
223 x 223
248 F
104 9,5
NSYCVF300M230PF
18
DB300471.eps
DB300472.eps
DB300469.eps
268
222,7
172
223 x 223
248
116 9,5
NSYCVF560M230PF - NSYCVF850M230PF
A B Cat. no. 18 18
DB300475EN.eps
DD385319.eps
DB300474.eps
DB300476.eps
291 x 291
316
B 9.5 9.5
Version : 14 - 15/12/2023
160E6300 TOC F-31
PrismaSeT P - Cubicles www.se.com
Ventilation accessories
Roof installation
Others
Roof ventilation Width 650, IP31 Width 800, IP54
NSYCVF575M230MB 2 x NSYCVF575M230MB
DD385540.eps
DD385819.eps
or NSYCAC228RMB or 2 x NSYCAC228RMB
LVS08476 LVS08478 or
or LVS08678
LVS08676
F-32 TOC
Version : 14 - 15/12/2023
160E6300
PrismaSeT P - Cubicles www.se.com
Ventilation accessories
Heat
Others
Resistors
Resistors prevent condensation, corrosion and superficial leakage currents.They
maintain a positive temperature in the enclosures and cubicles when external
temperatures drop very low.
b Install heaters according to the desired power level at the bottom of the enclosure
b Respect a safety area of a least 10 cm around the device
b The heaters must be installed with a thermal controller to control the temperature
or the humidity inside the enclosure.
b The enclosure must be sealed to prevent the entry of air from the outside.
b An electrical protection device must be installed on the supply side of the unit.
b Surface temperature limited to 75 °C when the ambient temperature is -5 °C.
b Heaters equipped with a power cable with a length of 500 mm with silicon
insulation, or with a connection terminal block.
PB501025.eps
Power cord Terminal block Terminal block
Cat. no. NSYCR10WU2 NSYCR20WU2 NSYCR55WU2 NSYCR100WU2 NSYCR150WU2 NSYCR250W230VV NSYCR400W230VV
Power rating (W) 10 25 55 90 150 250 400
Voltage (V) 110-250 AC 110-250 AC 110-250 AC 110-250 AC 110-250 AC 230 AC 230 AC
Characteristics b Vertical mounting. b Vertical mounting.
b Aluminium case with fins. b Aluminium case with fins.
b Temperature: b Temperature:
v turns off at 60 °C, v turns off at 60 °C,
F
v turns on at 25-30 °C (temperature of the resistor itself). v turns on at 25-30 °C (temperature of the
b Equipped with a symetrical resistor itself).
b Equipped with a symetrical
Thermofan
Thermofan
PB501154_R.eps
Terminal block
Cat. no. NSYCRP1W230VTVC
Power rating (W) 400/550
Voltage (V) 230 AC
Characteristics b Combination of a resistance heater and an axial motor to ensure uniform heating of the enclosure.
b Fixing by clip on a DIN rail.
b Thermostat adjustable from 0…+60 °C.
b Visual operation indicator.
Version : 14 - 15/12/2023
160E6300 TOC F-33
PrismaSeT P - Cubicles www.se.com
Ventilation accessories
Regulating
Others
Regulating
The thermostat can control the temperature inside electrical switchboards in
conjunction with heating resistors and fans.
This thermostat can control the activation of a fan and a heater and regulate their
temperature independently.
Mecanical thermostats Electronical thermostats
PB501172_R.eps
PB501162_30.eps
PB502513.eps
Thermostat Double thermostat Electronical Electronic Electronic hygrostat
with OF contact thermostat hygrotherm
Cat. no. NSYCCOTHI NSYCCOTHD NSYCCOTH230VID NSYCCOHYT230VID NSYCCOHY230VID
Colour of the button Black b Red: with normally closed - - -
contact (NC) for controlling
the resistance heaters.
b Blue: with normally open
contact (NO) for controlling
the fans, signalling systems
or alarms.
Contact Inverse, forced rupture 1 with normally closed Free with zero potential
contact (NC),
1 with normally open contact
(NO),
forced rupture
Internal sensor Bimetal Internal temperature - Internal humidity sensor
element sensor
Switching capacity 250 V AC ; 10 A (resistive 250 V AC ; 10 A - - -
load) 120 V AC ; 15 A
250 V AC/120 V AC : 2 A
(inductive load cos Ø= 0,6)
30 W DC
Max interrupting 250 V AC 4 A - - - -
capacity with direct (charge inductive Ø = 0,6)
current 30 W DC
Connection Four 2.5 mm² terminals Six 2.5 mm² terminals 2 x 2.5 mm² (input voltage) 2 x 2.5 mm² (input voltage) 2 x 2.5 mm² (input voltage)
+ 2 relays (2 x 2.5 mm² + 2 relays (2 x 2.5 mm² + 1 relay (2 x 2.5 mm²)
+ 2 x 2.5 mm²) + 2 x 2.5 mm²)
Dimensions (mm) 67 x 50 x 44 60 x 33 x 43 - - -
Weight (g) 100 40 - - -
Hysteresis 7° K 7° K Programmed 2 °K 3% 3%
Temperature setting +5...+60 °C 0...+60 °C -40 °C…+80 °C -40 °C…+80 °C -40 °C…+80 °C, humidity
range setting range:20 %…80 %
Characteristics b Ingress protection rating: IP20. b Ingress protection rating: IP20.
b Contact resistance: < 10 mW. b Certification : UL/UR.
b Service life: > 100 000 cycles. b Fixing: 4 different methods: on DIN rail, Spacial SF profile, on VDI cross-rail or on
b Fixing:by clip on a 35-mm DIN rail mounting plate
b Case : plastic UL 94 V-0, light grey. b Boîtier : plastique UL 94 V-0, gris clair.
b Operating temperature : -20...+80 °C (-4...+176 °F). b Operating temperature : -40 °C…+80 °C.
b Display : °C/°F. b Display : °C/°F.
b Max. command intensity: (NC) 5 A (NO) 10 A. b Max. command intensity: 8 (5) A 230 V AC / 5 A 30 V DC.
F-34 TOC
Version : 14 - 15/12/2023
160E6300
PrismaSeT P - Cubicles www.se.com
Switchboard lighting
Others
Lighting system
Fixed lighting
DD384098.eps
650
Version : 14 - 15/12/2023
160E6300 TOC F-35
Linergy
distribution
systems
PrismaSeT P Active - Linergy distribution systems www.se.com
Contents
Power busbars
Linergy LGYE
Horizontal profiles up to 4000 A G-2
Linergy BS
Horizontal busbars up to 4000 A G-3
Linergy LGY
Lateral profiles up to 3200 A G-4
Linergy LGYE
Lateral profiles up to 4000 A G-5
Linergy BS
Lateral flat busbars up to 4000 A G-6
Linergy LGY
Rear profiles up to 1600 A G-7
Linergy BS
Rear busbars up to 1600 A G-8
Linergy BS
Rear busbars up to 630 A G-9
Multi-stage busbars up to 630 A G-10
Multi-stage distribution block up to 630 A G-11
Incomer accessories up to 630 A G-12
Linergy Busbars
Accessories G-13
Distribution blocks
Linergy DP
Quick distribution blocks - ComPacT NSX and INS-INV up to 250 A G-14
Quick distribution blocks - ComPacT NSXm up to 160 A G-15
Device feeders
Linergy FC
Feeders for ComPacT NSX and INS-INV up to 250 A G-16
Feeders for ComPacT NSXm up to 160 A G-18
Secondary distribution
Insulated flexible bars G-20
Distribution blocks
Linergy DX
Quick distribution blocks G-22
Device feeders
Linergy FM
Quick device feeders G-24
Distribution blocks
Linergy DS G
Screw distribution blocks G-26
Device feeders
Linergy FH
Comb busbar for 27 mm pitch for C120, NG125 G-28
Comb busbar for 18 mm pitch for Acti 9 G-29
Comb busbar for 9 mm pitch for Acti 9, C60 G-31
Comb busbar for 9 mm pitch for Acti 9 G-32
Horizontal comb busbar for 18 mm pitch for Domae G-33
Horizontal biconnect comb busbar for 18 mm pitch G-34
Terminal blocks and lines
Linergy TA
Auxiliary connections G-35
Linergy TB
Earth bars G-36
PE conductor G-37
Secondary distribution
Linergy TB terminal block support G-38
Electrical characteristics
Designing connection y 630 A
Auxiliary connections G-39
Linergy TR
Terminal blocks G-40
Version : 14 - 15/12/2023
160E7000 TOC G-1
PrismaSeT P Active - Linergy distribution systems www.se.com
Linergy LGYE
Horizontal profiles up to 4000 A
400 mm deep installation
Power busbars
Linergy LGYE profiles
Installation Up to 1600 A Up to 2500 A Up to 4000 A
Linergy profiles, 2000 mm length
DD385350.eps
DD385354.eps
DD385355.eps
DD385356.eps
DD385357.eps
DD385349.eps
DD385352.eps
DD385353.eps
DD385351.eps
60 60 60 60 60 100 100
150 150
23 23 23 23 23 31 31
31 31
DD381225-LIN.eps
DD381226-LIN.eps
DD385514.eps
DD385513.eps
DD384520-LIN.eps
Fixed support LVS04664 Free support LVS04662 Fixed support LVS04665 Free support LVS04678
Characteristics Two fixed supports for 650 mm or 650 + 150 mm wide PrismaSeT P Active frameworks and one fixed support for 300/400
mm wide PrismaSeT P Active frameworks are mandatory. If more supports are required, use free supports.
Note: in case of 600 mm depth with 115 mm between centers, replace LVS04664 fixed support by LVS04665 and
LVS04662 free support by LVS04678.
In cubicle Number of y 15 2
W = 650 or supports y 25 2
W= depending on y 30 2
650+150 Icw (kA rms/1 s) y 40 - 2
busbar y 50 - 2
supports y 60 - 2+1 2
75 mm y 65 - 2+1
between y 75 - 2+1
centres y 85 - 2+1
y 100 - 2+3
Catalog Fixed LVS04664 LVS04664 + LVS04671 (1) (hardware) LVS04664 + LVS04646 (2)
numbers support (hardware)
Free LVS04662 LVS04662 + LVS04671 (1) (hardware) LVS04662 + LVS04646 (2)
support (hardware)
In cubicle Number of y 100 2 + 4 (3)
W = 800 supports
busbar depending on
supports Icw (kA rms/1 s)
75 mm Catalog Fixed LVS04664 LVS04664 + LVS04671 (1) (hardware) LVS04664 + LVS04646 (2)
between numbers support (hardware)
centres Free LVS04662 LVS04662 + LVS04671 (1) (hardware) LVS04662 + LVS04646 (2)
support (hardware)
In duct Number of y 60 1
W = 300 supports y 85 1+1
busbar depending on y 100 - 1+1
supports Icw (kA rms/1 s)
75 mm Catalog Fixed LVS04664 LVS04664 + LVS04671 (1) (hardware) LVS04664 + LVS04646 (2)
between numbers support (hardware)
centres Free LVS04662 LVS04662 + LVS04671 (1) (hardware) LVS04662 + LVS04646 (2)
support (hardware)
In duct Number of y 50 1
W = 400 supports y 85 1+1
busbar depending on
supports Icw (kA rms/1 s) y 100 - 1+1
75 mm Catalog Fixed LVS04664 LVS04664 + LVS04671 (1) (hardware) LVS04664 + LVS04646 (2)
between numbers support (hardware)
centres Free LVS04662 LVS04662 + LVS04671 (1) (hardware) LVS04662 + LVS04646 (2)
support (hardware)
Joints
Up to 1600 A Up to 2500 A Up to 4000 A
630 A 800 A 1000 A 1250 A 1600 A 2000 A 2500 A 3200 A 4000 A
DD384535-LIN.ai
DD384615-LIN.eps
DD384588-LIN.eps
Linergy BS
Horizontal busbars up to 4000 A
400 mm deep installation
Power busbars
Flat bars
Installation Up to 1600 A Up to 4000 A
Permissible current for an ambient IP y 31 800 A 1000 A 1400 A 1800 A 1200 A 1400 A 1800 A 2050 A 2300 A 2820 A 3300 A 3760 A
temperature of 35 °C around the
IP > 31 750 A 900 A 1250 A 1600 A 1080 A 1250 A 1600 A 1850 A 2000 A 2500 A 2900 A 3340 A
switchboard
Size of bars (mm) 60 x 5 80 x 5 60 x 5 80 x 5 50 x 10 60 x 10 80 x 10 50 x 10 60 x 10 80 x 10 100 x 10 120 x 10
Number of bars per phase 1 1 2 2 1 1 1 2 2 2 2 2
Total number of vertical modules (50 mm) 3 4
Catalog numbers LVS04536 LVS04538 LVS04536 LVS04538 LVS04545 LVS04546 LVS04548 LVS04545 LVS04546 LVS04548 LVS04550 LVS04552
Busbar supports
DD381226-LIN-15.eps
DD381225-LIN-15.eps
DD385513.eps
spe.03-NIL-922183DD
DD385514.eps
Fixed support LVS04664 Free support LVS04662 Fixed support LVS04665 Free support LVS04678
Characteristics Two fixed supports for 650 mm, 650 + 150 mm wide frameworks and one fixed support for 300/400 mm wide
PrismaSeT P Active frameworks are mandatory. If more supports are required, use free supports.
Note: in case of 600 mm depth with 115 mm between centers, replace LVS04664 fixed support by LVS04665
and LVS04662 free support by LVS04678.
In cubicle Number of supports y 15 2
W = 650 or depending on Icw y 25 2+1 2
W = 650+150 (kA rms/1 s) y 30 2+1 2
busbar supports
y 40 2+1
75 mm between
centres y 50 - 2+1 2
y 60 - 2+1
y 65 - 2+1
y 75 - 2+2 2+1
y 85 - - 2+1
Catalog Fixed support LVS04664 LVS04664 LVS04664 + LVS04671 (1) (hardware)
numbers Free support LVS04662 LVS04662 LVS04662 + LVS04671 (1) (hardware)
In cubicle Number of y 100 2 + 4 (2)
W = 800 supports
busbar supports depending on
75 mm between Icw (kA rms/1 s)
centres Catalog Fixed support LVS04664 LVS04664 + LVS04671 (1) LVS04664 + LVS04646 (2) (hardware)
numbers
Free support LVS04662
(hardware)
LVS04662 + LVS04671 (1) LVS04662 + LVS04646 (2) (hardware) G
(hardware)
In duct Number of supports y 30 1
W = 300 depending on Icw y 50 1+1 1
busbar (kA rms/1 s) y 85 - 1+1
supports
75 mm between Catalog Fixed support LVS04664 LVS04664 LVS04664 + LVS04671 (1) (hardware)
centres numbers Free support LVS04662 LVS04662 LVS04662 + LVS04671 (1) (hardware)
In duct Number of supports y 25 1
W = 400 depending on Icw y 40 1+1 1
busbar (kA rms/1 s)
supports y 50 1+1
75 mm between y 85 - 1+1
centres Catalog Fixed support LVS04664 LVS04664 LVS04664 + LVS04671 (1) (hardware)
numbers Free support LVS04662 LVS04662 LVS04662 + LVS04671 (1) (hardware)
Joints
Installation Up to 1600 A Up to 4000 A
1 bar per phase 2 bars per phase 1 bar per 2 bars per phase
phase
Size of bars (mm) 60 x 5 80 x 5 60 x 5 80 x 5 80 x 10 50 x 10 60 x 10 80 x 10 100 x 10 120 x 10
Sliding joints with torque nut
DD381227-LIN.eps
DD381231-LIN.eps
DD385358.eps
Linergy LGY
Lateral profiles up to 3200 A
400 mm deep installation
Power busbars
Linergy LGY profiles
Up to 1600 A (simple busbars) Up to 3200 A (double busbars)
In duct W150 2 x W150
Linergy profiles, 1670 mm length
Dd381233-LIN-7.eps
DD381234-LIN-7.eps
DD381235-LIN-7.eps
DD385495.eps
DD385496.eps
DD381235-LIN-7.eps
DD385495.eps
DD385496.eps
630 A 800 A 1000 A 1250 A 1600 A 2 x 1000 A 2 x 1250 A 2 x 1600 A
Permissible current for an ambient IP y 31 680 A 840 A 1040 A 1290 A 1650 A 2000 A 2500 A 3200 A
temperature of 35 °C around the IP > 31 590 A 760 A 950 A 1170 A 1480 A 1820 A 2260 A 2920 A
switchboard
Number of profiles per phase 1 2
Catalog numbers LVS04502 LVS04503 LVS04504 LVS04505 LVS04506 LVS04504 LVS04505 LVS04506
Busbar supports
DD381509.eps
DD380741-LIN.eps
387,5 mm
maxi
700 mm
maxi
DD382576-LIN-30.eps
Dd382327R-20.ai
y 1600 A
Characteristics Supplied with mounting hardware.
Catalog numbers include 1 connection only: 1 connection per phase.
Cat. no. according to horizontal busbar size LVS04602 (vertical connection)
LVS04603 (vertical shifted connection) (1)
(1) Dedicated connection LVS04603 for Linergy LGYE busbar in 150 mm duct with horizontal jointing
(2) LVS04642: mounting hardware for bars > 80 mm. Comprises 2 threaded rods.
G-4 TOC
Version : 14 - 15/12/2023
160E7100
PrismaSeT P Active - Linergy distribution systems www.se.com
Linergy LGYE
Lateral profiles up to 4000 A
400 mm deep installation
Power busbars
Linergy LGYE profiles
Linergy profile, 2000 mm length (1) Linergy profile, 1625 mm length
In duct W150 W150 W300
Linergy profile
DD385350.eps
DD385357.eps
DD385349.eps
DD385352.eps
DD385354.eps
DD385355.eps
DD385353.eps
DD385356.eps
DD385351.eps
60 60 60 60 60
100 100
23 23 23 23 23
150 150
31 31
31 31
DD380829-LIN_1.eps
DD381650-LIN_1.eps
DD384851_L13.ai
Fixed support LVS04661 Free support LVS04662 Bottom support LVS04666
Characteristics Attach directly to the framework.
Three fixed supports are required to maintain the busbars.
If more than three supports are required, use additional free supports.
The bottom support maintains the bars in position.
It is not considered a busbar support.
Note: in case of 600 mm depth with 115 mm between centers, replace LVS04661 fixed support by LVS04668,
free support LVS04662 by LVS04678 and bottom support LVS04663 or LVS04666 by LVS04673.
Number y 30 3
depending y 40 - 3+2 3
on Icw y 50 - 3+2 3
(kA rms/1 s)
y 60 - 3+2 3
y 65 - 3+2
y 75 - 3+4 3+2
y 85 - 3+4
y 100 - 3+6
In duct Catalog Fixed support LVS04661 LVS04661 + LVS04671 LVS04661 + LVS04646
W150, W = 300
busbar supports
75 mm between
numbers
Free support LVS04662
(2)
LVS04662 + LVS04671
(2)
(3)
LVS04662 + LVS04646
(3)
G
centres
Busbars chocks
DD384577-LIN_1.eps
DD384576-LIN_1.eps
Chocks installed on a bottom support LVS04658 Chocks installed on a bottom support LVS04659
Characteristics The bottom support maintains the sections in position.
It is not considered a busbar support.
In duct Catalog Bottom support LVS04663 LVS04666 + LVS04661
W150, W = 300 numbers Chocks LVS04658 LVS04659
Connections to the horizontal Linergy LGYE busbars
DD385751.eps
DD384575-4vis-LIN_1.eps
DD384575-LIN_1.eps
Version : 14 - 15/12/2023
160E7100 TOC G-5
PrismaSeT P Active - Linergy distribution systems www.se.com
Linergy BS
Lateral flat busbars up to 4000 A
400 mm deep installation
Power busbars
Flat bars
Up to 1600 A Up to 4000 A
In duct W150 W150 2 x W150 W300
Copper with holes, 1675
DD381505-LIN.eps
mm length
Permissible current for an ambient IP y 31 800 A 1000 A 1400 A 1800 A 1200 A 1400 A 1800 A 2050 A 2300 A 2820 A 3200 A 3200 A 3760 A
temperature of 35 °C around the IP > 31 750 A 900 A 1250 A 1600 A 1080 A 1250 A 1600 A 1850 A 2000 A 2500 A 2820 A 2820 A 3340 A
switchboard
Size of bars (mm) 60 x 5 80 x 5 60 x 5 80 x 5 50 x 10 60 x 10 80 x 10 50 x 10 60 x 10 80 x 10 80 x 10 100 x 10 120 x 10
Number of bars per phase 1 2 1 2
Catalog numbers LVS04516 LVS04518 LVS04516 LVS04518 LVS04525 LVS04526 LVS04528 LVS04525 LVS04526 LVS04528 LVS04528 LVS04550 (1) LVS04552 (1)
Busbar supports
Description Drilled bars.
DD385999.eps
IL[HG
Three fixed supports are required to maintain the busbars. If more than three supports are required, use additional free
supports.
The bottom support maintains the bars in position.
It is not considered a busbar support.
IUHH Note: In case of 600 mm depth with 115 mm between centers, replace LVS04661 fixed support by LVS04668 and
LVS04662 free support by LVS04678 and LVS04663 or LVS04666 bottom support by LVS04673.
IL[HG
Number of y 15 3 3 2x3
supports y 25 3+2 3 3 2x3
depending
y 30 3+2 3+2 3 2x3
on Icw
IUHH
(kA rms/1 s) y 40 3+4 3+2 3+2 2x3
y 50 - 3+4 3+2 2x3
y 60 - 3+4 3+2 2 x 3+2
IL[HG
y 65 - 3+4 3+2 2 x 3+2
FKRFNV y 75 - - 3+6 3+4 2 x 3+2
y 85 - - 3+4 2 x 3+2
DD385418.eps
Characteristics For busbars with 75 mm between Catalog numbers LVS04636 and LVS04637 include 1 connection only.
centres, the bars must fully overlap. Order 1 connection per phase.
To satisfy safety clearances, the Reference LVS04642 consists of 2 M8 x 140 screws which can replace the original M8
assembly points on adjacent x 120 screws.
bars must be staggered as shown
above.
DD383399_R-LIN.eps
1 bar per phase 2 bars per phase 1 bar per phase 2 bars per phase
double 2 bars per phase
BB
Size of vertical bars (mm) 60 x 5 80 x 5 60 x 5 80 x 5 50 x 10 60 x 10 80 x 10 50 x 10 60 x 10 80 x 10 80 x 10 100 x 10 120 x 10
Catalog number of the connecting part y 80 mm LVS04782 LVS04636 LVS04637 LVS04637 2 x LVS04637 LVS04645 LVS04645
according to the size of the horizontal 2 x LVS04637
bars LVS04636 + LVS04637
100 mm LVS04782 LVS04637 + LVS04642 +2x LVS04645 LVS04645
LVS04642 + LVS04642
LVS04642
120 mm LVS04782 LVS04638 LVS04638 LVS04638 2 xLVS04638 LVS04645 LVS04645
(1) Copper plain bars, 2000 mm length.
Drilling diagram for horizontal busbars, Drilling diagram for horizontal busbars,
5 mm thick. 10 mm thick.
12,5
DD384320-LIN.eps
DD383398-LIN.eps
50/60/80/100
35 35 12,5
55 11 55
75 75
111 111
50/60
80
100
G-6 TOC
Version : 14 - 15/12/2023
160E7100
PrismaSeT P Active - Linergy distribution systems www.se.com
Linergy LGY
Rear profiles up to 1600 A
Power busbars
Linergy LGY profiles
Up to 1600 A
At the rear of the cubicle W650
Linergy profile, 1670 mm length
DD381234-LIN-7.eps
DD381235-LIN-7.eps
DD385495.eps
DD385496.eps
Dd381233-LIN-7.eps
630 A 800 A 1000 A 1250 A 1600 A
Permissible current for an ambient IP y 31 680 A 840 A 1040 A 1290 A 1650 A
temperature of 35 °C around the switchboard IP > 31 590 A 760 A 950 A 1170 A 1480 A
Number of profiles per phase 1
Catalog numbers LVS04502 LVS04503 LVS04504 LVS04505 LVS04506
Busbar supports
DD381242-LIN.eps
DD381241New_modif-LIN.eps
387,5 mm
maxi
350 mm
maxi
Fixed support LVS04652
Number of y 25 3
350 mm
maxi
supports y 30 - 4
depending
y 40 - 5
on Icw
350 mm (kA rms/1 s) y 50 - 7
maxi
Characteristics Stop to be installed on the bottom support. LVS01109
DD381243-LIN.eps
(set of 12).
350 mm
maxi
9C-DD381245-ret-LIN.eps
G
Connection LVS04635 to horizontal Connection LVS04636 to horizontal busbars
busbars 5 mm thick. 10 mm thick.
Characteristics Mounting hardware supplied, order 1 connection per phase.
For part of the connection, flexible insulated busbars are needed.
Cat. no. according Thickness 5 mm LVS04635
to horizontal
Thickness W y 80 mm LVS04636
busbar size
10 mm
W > 80 mm LVS04636 + LVS04642
Connections to the horizontal Linergy LGYE flat busbars
DD384611.EPS
Version : 14 - 15/12/2023
160E7100 TOC G-7
PrismaSeT P Active - Linergy distribution systems www.se.com
Linergy BS
Rear busbars up to 1600 A
Power busbars
Flat bars
Up to 1600 A
At the rear of the cubicle L650
Copper with holes,
DD381505-LIN.eps
1670 mm length
DD380732-LIN.eps
DD381652-LIN.eps
DD380734.eps
Fixed busbar supports LVS04653 Free busbar supports
Mounting chocks
LVS04669
Characteristics Three fixed supports cat. no. LVS04653 are required to maintain the busbars.
DD381503New_modif-LIN.eps
If more than three supports are required, use additional free supports cat. no. LVS04662.
PP A metal mounting chock, cat. no. LVS04669 (set of 100) 5 mm thick, is screwed to the bar. It rests on
PD[L a fixed support and maintains the position of the bar.
DD380815-LIN.eps
PP
PD[L
PP
PD[L
Chock: 1 bar/phase
DD380733-LIN.eps
PP
PD[L
Chock: 2 bars/phase
PP
PD[L
Number of y 15 3 3
supports y 25 3+2 3 3
depending
y 30 3+2 3+2
PP on Icw
PD[L (kA rms/1 s) y 40 3+4 3+2 3+2
y 50 - 3+4 3+2
y 60 - 3+4
y 65 - 3+4
y 75 - - 3+6
y 85 - -
Catalog numbers LVS04653 (fixed) + LVS04662 (free) + LVS04669 (chock)
Connections to the horizontal Linergy BS flat busbars
DD380730.eps
Linergy BS
Rear busbars up to 630 A
Power busbars
IEC 61439-1 & 2
Dd382628.eps
Description
The busbar can be 3-pole or 4-pole with ratings between 160 A and 630 A.
2 lengths are available: 1000 and 1400 mm, which can be cut as required.
The number of supports depends on the installation maximum rated current.
The insulating supports can receive a fifth bar, 15 x 5 mm or 20 x 5 mm, to create an
earth bar.
DD381388-LIN.eps
160 A 250 A 400 A 630 A
Rated peak withstand current (Ipk) 30 k 40 k 55 k 77 kÂ
Rated insulation voltage (Ui) 1000 V AC 1000 V AC 1000 V AC 1000 VAC
Rated short-time current (Icc) 150 kA 150 kA 150 kA 150 kA
Thermal stress (I².t) 1.000 x 108 2.250 x 108 6.250 x 108 1.225 x 109
Conductor cross-section 15 x 5 mm 20 x 5 mm 32 x 5 mm 32 x 8 mm
Installation Threaded M6 holes every 25 mm all the way up
Connection by: 16 to 50 mm2 flexible cables with crimped lugs
Set of 4
Length (mm) 1000 1400 1000 1400 1000 1400 1400
Catalog numbers LVS04161 LVS04171 LVS04162 LVS04172 LVS04163 LVS04173 LVS04174
G
Distance between supports y 10 kA eff / 1 s 450 mm 450 mm 450 mm 450 mm
depending on Icw/lpk (1) y 13 kA eff / 1 s - 450 mm 450 mm 450 mm
y 15 kA eff / 1 s - 450 mm 450 mm 450 mm
y 20 kA eff / 1 s - - 300 mm 300 mm
y 25 kA eff / 1 s - - 225 mm 225 mm
y 30 kA eff / 1 s - - - 225 mm
y 35 kA eff / 1 s - - - 175 mm
Installation On the rear uprights
Screwed onto a solid or pre-slotted plate (fixing centres 450 x 200 mm)
Catalog numbers LVS04191 LVS04191 LVS04191 LGY4193
Length 470 mm
Height 100 mm
Composition Supplied with fixings.
Catalog numbers LVS04198
Note: electrical characteristics > page G-39.
(1) Linergy FM 200 A distribution blocks with connections ref. LVS04029 can act as intermediate supports (max. distance apart 200 mm) in addition to the support
ref. LVS04191 at the top and bottom.
Version : 14 - 15/12/2023
160E7100 TOC G-9
PrismaSeT P Active - Linergy distribution systems www.se.com
Linergy BS
Multi-stage busbars up to 630 A
Power busbars
IEC 61439-1 & 2
Dd383648.eps
Description
Multi-stage busbars are installed in a sheath W = 400 mm.
We strongly recommend dividing the current between 2 cubicles or enclosures
joined on either sides.
All the connection points are easily accessible from the front.
The busbar orientation makes them easier to tighten and facilitates running the cables
between them.
The current can be 3-pole or 4-pole with ratings between 160 A and 630 A.
2 lengths are available: 1000 and 1400 mm, which can be cut as required.
The number of supports depends on the installation maximum rated current.
160 to 630 A copper busbars
DD381388-LIN.eps
Width 250 mm
Height 1500 mm
Composition Fixing accessories supplied with support cat. no. LVS04192.
Catalog numbers LVS04197
G-10 TOC
Version : 14 - 15/12/2023
160E7100
PrismaSeT P Active - Linergy distribution systems www.se.com
Linergy BS
Multi-stage distribution block up to 630 A
Power busbars
IEC 61439-1 & 2
PB502514_60.eps
Description
The distribution block can be installed horizontally in the device zone or vertically in
the 300 mm wide duct of enclosures and cubicles.
The distribution block is made up of:
b two staggered supports made of an insulating material
b four slanted copper bars with holes every 25 mm.
Dd383647-SE.eps
Installation Screwed onto a solid or pre-slotted plate (fixing centres 450 x 200 mm)
Screwed to an adapter cat. no. LVS03595.
Composition 2 multi-stage supports made of an insulating material
4 slanted copper busbars, with holes every 25 mm
1 pack of 36 M6 x 16 screws + contact washers
1 IPxxB front insulating shield
Catalog numbers LVS04052 LVS04053 LVS04054 LVS04055
Version : 14 - 15/12/2023
160E7100 TOC G-11
PrismaSeT P Active - Linergy distribution systems www.se.com
Linergy BS
Incomer accessories up to 630 A
Power busbars
Incomer accessories
E56852-15.eps
E56851-15.eps
E56850-15.eps
Connectors for copper or aluminium cables
Rated operational current at 40 °C (Ie) 160 A 250 A 400 A
Supply at incoming terminals 70 mm2Cables 16 - 185 mm2Cables 70 - 300 mm2Cables
Composition Supplied with fixings at busbar end.
Set of 4
Catalog numbers LVS07051 LVS07052 LVS07053
Outgoer accessories
DD381398-LIN.eps
G-12 TOC
Version : 14 - 15/12/2023
160E7100
PrismaSeT P Active - Linergy distribution systems www.se.com
Linergy Busbars
Accessories
Power busbars
Accessories
DD385390.eps
DD381219-LIN-15.eps
DD381222-LIN-10.eps
DD385489.eps
DD385391.eps
DD385392.eps
M8 bolts
DD380737.eps
Torque nuts
DD380735.eps
20 M8 torque Characteristics Can be used to obtain the correct tightening torque (28 Nm) recommended by the manufacturer, without
nuts using a torque wrench. Torque nuts may be used for all electrical connections.
Catalog numbers LVS04759
Voltage tap-offs G
DD380736.eps
20 Voltage Characteristics For small lugs (on low-current cables or measurement tap-offs), insert a conducting washer (cat. no.
tap-offs M10 LVS04775) between the busbar and the lug.
pour 2 clips 6.35 Catalog numbers LVS04229
Note: Jointing between 2 busbars (horizontal/vertical or horizontal/horizontal) must be mandatory done with studs plates.
Version : 14 - 15/12/2023
160E7100 TOC G-13
PrismaSeT P Active - Linergy distribution systems www.se.com
Linergy DP
Quick distribution blocks - ComPacT NSX and INS-INV up to 250 A
Distribution blocks
IEC 60947-7-1, IEC 61439-1 and 2
PB111455_50.eps
Description
b The Linergy DP quick distribution block is designed for installation directly
downstream of ComPacT NSX and INS-INV up to 250 A. It can also be clipped onto
a modular rail.
Advantages
b It is quick to mount in the horizontal position. Electrical connections are made
directly to the device terminals.
b It is the same width as the devices and does not take up any additional space in
the switchboard.
b The connection terminals are slanted to facilitate cable entry and avoid exceeding
the bending radius of the flexible and rigid cables.
PB502519-11_r.eps
PB111455-15-r.eps
PB111454-15-r.eps
DD385533.eps
Rated operational current (Ie) 250 A 250 A 250 A
Rated peak withstand current (Ipk) 30 kA 30 kA 30 kA
Rated short-time current (Icw) 8.5 kA rms/1 s 8.5 kA rms/1 s
Thermal stress (I².t) 7.225 x 107 7.225 x 107
Total connection capacity, outgoing terminals 27 connections: 36 connections: 2 connections:
6 x 10²/phase 6 x 10²/phase 2 x 35²/pole
3 x 16²/phase 3 x 16²/phase
Incomer terminals 1 cable lug 120 mm² per pole
Dimensions (H x W x D) 105 x 138 x 63 140 x 138 x 64
Installation On mounting plate or DIN rail On mounting plate
Product certifications ASEFA
Standard for installation inside PrismaSeT IEC 61439-1-2
Glow-wire 60695-2-11 960 °C
Catalog numbers LVS04033 LVS04034 LVS04155 (3P)
LVS04156 (4P)
G-14 TOC
Version : 14 - 15/12/2023
160E7300
PrismaSeT P Active - Linergy distribution systems www.se.com
Linergy DP
Quick distribution blocks - ComPacT NSXm up to 160 A
Distribution blocks
IEC 60947-7-1, IEC 61439-1 and 2
DD435603.eps
Description
b The Linergy DP quick distribution block is designed for installation directly
downstream of ComPacT NSXm up to 160 A. It can also be clipped onto a modular
rail.
Advantages
b It is quick to mount in the horizontal position. Electrical connections are made
directly to the device terminals.
b It is the same width as the devices and does not take up any additional space in
the switchboard.
b The connection terminals are slanted to facilitate cable entry and avoid exceeding
the bending radius of the flexible and rigid cables.
DD435605.eps
DD435604.eps
G
Technical Data Installation
Common characteristics It can also be mounted downstream of
DD435606.eps
Version : 14 - 15/12/2023
160E7300 TOC G-15
PrismaSeT P Active - Linergy distribution systems www.se.com
Linergy FC
Feeders for ComPacT NSX and INS-INV up to 250 A
Device feeders
IEC 61439-1 and 2
Description
PB502507-48_r.eps
DD435608.eps
PB502507-48_r.eps
PB502508-32_r.eps
Linergy FC with prefabricated Linergy FC with prefabricated Linergy FC without prefabricated
connections by insulated flexible bars (1) connections (1) connections (1)
Number of poles 3P 4P 3P 4P 3P 4P
Linergy BS, Linergy LGY or Linergy LGYE Linergy BS, Linergy LGY or Linergy
Connection to Linergy LGY busbars
busbars LGYE busbars
Number of devices 4 3 4 3 4 3
Composition Self-adhesive labels to mark the phases for connections to the busbars.
Mounting plates
Toggle, Fixed, NSX100/250 LVS03420 LVS03420 - - LVS03420 LVS03420
Toggle, Plug-in, NSX100/250 - - LVS03423 LVS03423 LVS03423 LVS03423
Rotary handle, motor
mechanism - plug-in, Fixed, - - LVS03422 LVS03422 LVS03422 LVS03422
NSX100/250
Cat. no. LVS04403 LVS04404 LVS04405 LVS04406 LVS04407 (2) LVS04408 (2)
Implementation
DD381251-LIN-30.eps
DD381252-LIN-30.eps
DD381250-LIN.eps
Auxiliary wires running in the built-in trunking. Phase marking on the front of the distribution
block.
(1) The connection of a Linergy FC distribution block using pre-wired connectors or insulated flexible bars is not compatible with Form 2 partitioning (LVS04922).
In this case, use the form 2 restoration kit (LVS04924).
(2) For the connection, use insulated flexible bars, 32 x 8 mm cat. no. LVS04753; Each connection must not be longer than 500 mm. This size is validated with
Schneider Electric insulated flexible bars.
G-16 TOC
Version : 14 - 15/12/2023
160E7300
PrismaSeT P Active - Linergy distribution systems www.se.com
Linergy FC
Feeders for ComPacT NSX and INS-INV up to 250 A
Device feeders
Accessories
DD383594-LIN-100.eps
PB502509-18_r.eps
Tooth caps
The caps block off the reserve terminals on a
Linergy FC distribution block.
Made of an insulating material, they simply clip on
from the front.
Catalog numbers LVS04809
Characteristics
Common characteristics
Rated operational current at 40° (Ie) Distribution-block derating follows the normal derating curves of ComPacT NSX and INS-INV
Rated conditional short-circuit current of an assembly (Isc) The reinforced breaking capacity due to cascading in circuit breaker combinations is
maintained.
The worst-case situations have been tested.
The electrical characteristics are perfectly compatible with the connected devices.
Neither the temperature derating curves nor the performance levels of the circuit breakers and
switch-disconnectors are altered.
Rated insulation voltage (Ui) 750 V AC
Rated operational voltage (Ue) 690 V AC
Rated impulse withstand voltage (Uimp) 8 kV
Rated peak withstand current (Ipk) 50 kA rms
Rated short-time current (Icc) 85 kA
with upstream protection of 85 kA Icc
Thermal stress (I².t) 2.500 x 107
Rated conditional short-circuit current of an assembly Short-circuit withstand current compatible with the breaking capacity of the ComPacT NSX
circuit breakers connected to the distribution block.
(A) Rated operational current as a function of the temperature inside the switchboard
Temperature (°C) 40 45 50 55 60 65 70
G
Inc (A) 3P 800 800 775 750 725 700 675
4P 675 675 655 635 615 595 570
To obtain the maximum permissible current for the linergy FC, apply the diversity factor K:
b Linergy FC 3P: K = 0.8
b Linergy FC 4P: RDF = 0.9.
Version : 14 - 15/12/2023
160E7300 TOC G-17
PrismaSeT P Active - Linergy distribution systems www.se.com
Linergy FC
Feeders for ComPacT NSXm up to 160 A
Device feeders
IEC 61439-1 and 2
Description
Linergy FC is an insulated horizontal distribution block. It connects directly to the mounting
plate and can supply:
DD435609.eps
b Four 4P and five 3P ComPacT NSXm circuit breakers (four 3P and 4P for ComPacT
NSXm Vigi), whatever the ratings (63, 100 or 160 A) with toggle and direct rotary handle
operating mechanism.
b The design and small size blend thoroughly with the devices.
DD435610.eps
b It can be supplied by Linergy BS, Linergy LGYE and Linergy LGY busbars positioned to
the left or right.
b Fully insulated, Linergy FC helps to protect life and property. Numerous and well
distributed vents ensure natural convection and optimum cooling of the conductors.
b The circuit breakers can be easily connected from the front. It is simple to interchange a
device or to add a device in a reserve slot.
b There are markings (N, L1, L2, L3) on the front and the sides for the phases.
b The running of auxiliary cables between the devices and the corresponding terminal
blocks is also considered. Spacious trunking is built into the blocks for the auxiliary wiring.
DD435610.eps
DD435611.eps
DD435609.eps
Linergy FC with prefabricated connections Linergy FC with prefabricated Linergy FC without prefabricated
by insulated flexible bars (1) connections (1) connections (1)
Number of poles 3P 4P 3P 4P 3P 4P
Connection to Linergy LGY busbars Linergy BS and Linergy LGYE busbars
Number of devices 5 (2) 4 5 (2) 4 5 (2) 4
Mounting plates LVS03416 LVS03416 LVS03416 LVS03416 LVS03416 LVS03416
LVS04410 LVS04412 LVS04419 (3)
Cat. no. LVS04411 LVS04413 LVS04420 (3)
LVS04416 (3) LVS04417 LVS04418 (3) (4)
Implementation
DD435612.eps
DD435613.eps
D
C
B
A D
m
FC NSX C
Linergy B
A
E
E
D
C
B
A
D
C
B
A
G-18 TOC
Version : 14 - 15/12/2023
160E7300
PrismaSeT P Active - Linergy distribution systems www.se.com
Linergy FC
Feeders for ComPacT NSXm up to 160 A
Device feeders
Accessories
DD435614
C
DD435615
B
A
D
C
B
A
Tooth caps
The caps block off the reserve terminals on a Linergy
FC distribution block.
Made of an insulating material, they simply clip on and
install the screw from the front.
Characteristics
Common characteristics
Rated operational current at 40° (Ie) Distribution-block derating follows the normal derating curves of ComPacT NSXm
Rated conditional short-circuit current of an assembly (Isc) The reinforced breaking capacity due to cascading in circuit breaker combinations is
maintained.
The worst-case situations have been tested.
The electrical characteristics are perfectly compatible with the connected devices.
Neither the temperature derating curves nor the performance levels of the circuit breakers and
switch-disconnectors are altered.
Rated insulation voltage (Ui) 800 V AC
Rated operational voltage (Ue) 690 V AC
Rated impulse withstand voltage (Uimp) 8 kV
Rated peak withstand current (Ipk) 18 kA
Rated short-time current (Icc) 50 kA
with upstream protection of 85 kA Icc
Thermal stress (I².t) 4.5 x 106 A2S
Rated conditional short-circuit current of an assembly Short-circuit withstand current compatible with the breaking capacity of the ComPacT NSXm
circuit breakers connected to the distribution block.
Version : 14 - 15/12/2023
160E7300 TOC G-19
PrismaSeT P Active - Linergy distribution systems www.se.com
Secondary distribution
The insulated flexible bars are tested in a type-tested switchboard environment.
DD381659.eps
Their design takes into account the switchboard architecture where they are often in
close proximity to a protection device (circuit breaker or fuse) with significant heat
losses.
The sizes for the flexible bars indicated below take into account the heat losses of
Schneider Electric devices in a PrismaSeT switchboard.
Characteristics
Length 1800 mm
Rated insulation voltage (Ui) 1000 V
Maximum withstand temperature for the insulating material 125 °C
(1) To connect a ComPacT NSX250 and NSX150 ELCB to Linergy BW busbars, use a
24 x 5 mm flexible bar (LVS04746).
(2) The insulated flexible bars is not compatible with Form 2 partitioning (LVS04922).
In this case, use the form 2 restoration kit LVS04924 > page H-5.
(3) In case of use of 32 x 6 insulated flexible bar, please contact Schneider Electric.
(4) Max length 500 mm per connection
The references 87646 (3P) and 87647 (4P) can be used up to 250 A, when binding of
DD385905.eps
Nota : For NSXm connection, there is no flat insulated flexible bar available. Choose a cable
prefabricated connection > page E-35 and page E-36
G-20 TOC
Version : 14 - 15/12/2023
160E7300
PrismaSeT P Active - Linergy distribution systems www.se.com
Secondary distribution
Connection between busbars
DD382008.eps
Copper flexible bars are designed for connections between busbars taking into
account the following characteristics:
b a maximum temperature of 60 °C inside the switchboard. This corresponds to the
average temperature inside a switchboard for an ambient temperature of 35 °C
b the maximum withstand temperature for the insulating material is 125 °C.
Designing connections
> page G-20.
Version : 14 - 15/12/2023
160E7300 TOC G-21
PrismaSeT P Active - Linergy distribution systems www.se.com
Linergy DX
Quick distribution blocks
Distribution blocks
IEC 60947-7-1, CEI 61439-2
Description
PB104499-7.eps
PB111415-19_r.eps
PB104500-6.eps
PB104499-6.eps
Rated operational current at 40° (Ie) 63 A 63 A
Rated conditional short-circuit current of an (Isc) The reinforced breaking capacity due to cascading in circuit breaker combinations is maintained.
assembly The worst-case situations have been tested.
150 kA with upstream protection of 150 kA Icc
Rated peak withstand current (Ipk) 10 kA 10 kA
Rated insulation voltage (Ui) 500 V AC 500 V AC
Rated operational voltage (Ue) 440 V AC 440 V AC
Rated impulse withstand voltage (Uimp) 6 kV 6 kV
Rated short-time current (Icc) 150 kA 150 kA
Thermal stress (I².t) 9.03 x 106 9.03 x 106
Rated operational frequency 50/60 Hz 50/60 Hz
Degree of protection IPxxB IPxxB
Incoming terminals 1 tunnel terminal 25²/phase 1 tunnel terminal 25²/phase
Accessories
Catalog numbers - -
G-22 TOC
Version : 14 - 15/12/2023
160E7300
PrismaSeT P Active - Linergy distribution systems www.se.com
Linergy DX
Quick distribution blocks
Distribution blocks
Advantages
b A reliable electrical connection, no maintenance required (tightness guaranteed
over time).
b Quick connection.
b Easy phase balancing.
b Ease of rewiring if the switchboard is expanded or modified.
4P 1P
PB111415-19_r.eps
DD386251.eps
PB111453-8-r.eps
125 A 160 A 160 A
The reinforced breaking capacity due to cascading in circuit breaker combinations is maintained.
The worst-case situations have been tested.
150 kA with upstream protection of 150 kA Icc
20 kA 20 kA 24 kA
750 V AC 750 V AC 750 V AC
690 V AC 690 V AC 690 V AC
8 kV 8 kV 8 kV
150 kA 150 kA 150 kA
2.025 x 107 2.025 x 107 3.025 x 107
50/60 Hz 50/60 Hz 50/60 Hz
IPxxB IPxxB IPxxB
1 tunnel terminal 35²/phase Supplied with a prefabricated flexible connection 1 tunnel terminal 70²/phase
equipped with tunnel terminals (for INS-INV100/160
use adaptator 28947 (3P) 28948 (4P)
52 connections: 52 connections: 6 connections:
7 x 4²/phase 7 x 4²/phase 6 x 16²/phase
3 x 6²/phase 3 x 6²/phase
2 x 10²/phase 2 x 10²/phase
1 x 16²/phase (screw terminal) 1 x 16²/phase (screw terminal)
127 x 108 x 48 127 x 108 x 48 95 x 36 x 70
12 x 9 mm pitch 12 x 9 mm pitch 4 x 9 mm pitch
Screwed to plain or slotted backplate or onto DIN rail Screwed to plain or slotted backplate or onto DIN rail
Possible to combine 2 terminal blocks
(2nd terminal block supplied from enclosed terminals
Onto DIN rail
G
in the 1st, Imax of 2nd terminal block: 80 A)
IEC 61439-2 IEC 61439-2 IEC 61439-2
960 °C 960 °C 960 °C
3 3 3
LVS04045 LVS04046 (1) LVS04031
Linergy FM
Quick device feeders
Device feeders
Description
PB104505-50.eps
Distribution blocks
Number of poles 4P 4P
PB104501-52-r.eps
63 A PB502496-31_r.eps 80 A
Rated peak withstand current (Ipk) 12 kA 13 kA
The cascading reinforced breaking capacity when combining circuit breakers is maintained. The worst-case
Rated conditional short-circuit current of scenarios have been tested. The characteristics are exactly right for the connected devices. Circuit breakers
(Isc)
an assembly and switches still have their temperature derating curves, and their whole performance is maintained.
150 kA with upstream protection of 150 kA Icc
Rated insulation voltage (Ui) 500 V AC 500 V AC
Rated voltage (Ue) 440 V AC 440 V AC
Rated impulse withstand voltage (Uimp) 6 kV 8 kV
Maximum current (Imax) - -
Thermal stress (I².t) 9.03 x 106 9.03 x 106
Rated operational frequency 50/60 Hz 50/60 Hz
Degree of protection IPxxB IPxxB
9 mm modules 24 48
Width
18 mm modules 12 24
Supply at incoming terminals Enclosed terminals for cables up to 25 mm2 Enclosed terminals for cables up to 25 mm2
Phase 6 7
Downstream Max. 4 mm2
Neutral 4 13
connection Phase 2 2
capacity, cable to Max. 6 mm 2
Installation
DB124196-LIN.eps
DD381664-LIN.eps
DB124195-LIN.eps
Clipped onto the back of a modular rail, or screw Clipped onto the back of a modular rail. Clipped onto the back of a modular rail, or screw fixing.
fixing.
G-24 TOC
Version : 14 - 15/12/2023
160E7300
PrismaSeT P Active - Linergy distribution systems www.se.com
Linergy FM
Quick device feeders
Device feeders
PD390661R.eps
4P 1P+N 3P 4P 4P
PB502500-18_r.eps
PB502499-23_r.eps
PB502501-27_r.eps
PB502498-27_r.eps
PB502497-27-r.eps
160 A 200 A 200 A 200 A 200 A
20 kA 20 kA 20 kA 20 kA 20 kA
The cascading reinforced breaking capacity when combining circuit breakers is maintained. The worst-case
scenarios have been tested. The characteristics are exactly right for the connected devices. Circuit breakers
and switches still have their temperature derating curves, and their whole performance is maintained.
150 kA with upstream protection of 150 kA Icc
750 V AC 750 V AC 750 V AC 750 V AC
690 V AC 690 V AC 690 V AC 690 V AC
8 kV 8 kV 8 kV 8 kV
50 A for feeder for 10 mm2 cable/63 A for feeder for 2 10 mm2 cables
3600 x 107 3600 x 107 3600 x 107 3600 x 107
50/60 Hz
IPxxB
24 48 72
12 24 36
Direct onto the row by cable 50 mm2 with crimped lug, or flexible bar 20 x 3 from busbar with prefabricated connection -
- - -
- - -
- - -
- - -
6 12 -
6 18 -
12 x 10 mm2 24 x 10 mm2 24 x 10 mm2 24 x 10 mm2 36 x 10 mm2
4
2
LVS04018 (1)
2
4
LVS04012 (1) (2)
3
4
LVS04013 (1)
4
4
LVS04014 (1) (2)
4
6
LVS04026 (1)
G
Connections to the distribution block
DD385348.eps
Dd383655.eps
Spare parts
PB502502-8_r.eps
Linergy DS
Screw distribution blocks
Distribution blocks
IEC/EN 60947-7-1, IEC/EN 61439-1 & 2
PB111254-30_1.eps
Description
b Single-pole or four-pole distribution block that can be installed on a standard DIN
rail or on a mounting plate.
b Compatible with PrismaSeT G Active and PrismaSeT P Active, Pragma, Mini
Pragma and Resbo series switchboards.
b Incomers and feeders are connected to screw terminals that accept rigid or
flexible cables with ferrule.
b Optional: additional neutral terminal strip for four-pole distribution block.
PB111253-30_1.eps
Avantages
b Simplified power supply for main incomers.
b Easy phase balancing.
b Easy, effortless cabling due to excellent accessibility.
b Visible cabling.
b Insulation between phases.
b The single-pole distribution blocks are adjacent and bridgeable via the second
incoming hole for parallel connection.
PB111251-20_1.eps
PB111243-20_1.eps
PB111252-20_1.eps
G-26 TOC
Version : 14 - 15/12/2023
160E7400
PrismaSeT P Active - Linergy distribution systems www.se.com
Linergy DS
Screw distribution blocks
Distribution blocks
Technical data
Common characteristics
In compliance with IEC/EN 60947-7-1 and IEC/EN 61439-1 & 2
Rated insulation voltage (Ui) 500 V AC
Rated operational voltage (Ue) 230 V AC (L/N)
440 V AC (L/L)
Rated impulse withstand voltage (Uimp) 8 kV
Rated conditional short-circuit current of an Up to the breaking capacity of
DB406005_1.eps
PB111245-20_1.eps
PB111246-20_1.eps
PB111247-20_1.eps
PB111248-20_1.eps
PB111249-20_1.eps
125 A 160 A 100 A 125 A
4 x 12 4 x 15 4 x 12 7 12 15
G
26 k 28 k 36 k - - -
36 kA 36 kA 36 kA - - -
14 20 18 7 14 17
100 x 126 x 50.5 100 x 162 x 50.5 100 x 174 x 50.5 20 x 70 x 35 20 x 125 x 35 20 x 155 x 35
390 559 567 63 111 149
LGYN12512 LGYN12515 LGYN12512 - - -
Ø y 15 mm
Version : 14 - 15/12/2023
160E7400 TOC G-27
PrismaSeT P Active - Linergy distribution systems www.se.com
Linergy FH
Comb busbar for 27 mm pitch for C120, NG125
Device feeders
IEC 60664-1
030920d-30.eps
Description
Comb busbars make it easier to install C120 and NG125 circuit breaker.
b Supplied with 2 lateral end-caps, to reinforce copper bars insulating (IP2).
b Allowing circuit identification.
b Easy cut to length thanks to cutting marks on the insulating material and copper
bars.
030920d-60.eps
Each com busbar reference includes:
b 1 x single or 2 pole comb busbar + 8 tooth-caps + 2 side plates
b 1 x 3 or 4 pole comb busbar + 4 tooth-caps + 2 side plates
To insulate teeth that have been left free can be insulated by tooth-caps
Rated operational current to (Ie) 125 A (63 A max by outgoer)
40 °C
Rated conditional short-circuit (Isc) Compatible with the breaking capacity of C120 and NG125 circuit breakers
current of an assembly
Rated insulation voltage (Ui) 620 V AC
Rated voltage (Ue) 500 V AC
Degree of pollution 3
Fire resistance to IEC 695-2-1 Self-extinguishing 960 °C, 30 s
Colour RAL 7016 (anthracite grey)
Use
Power supply by connector recommended
Number of 27 mm modules 16 16 15 16
Set of 1
Catalog numbers 14811 14812 14813 14814
Installation
DB105974-LIN-20.eps
1 2
Accessories
Number of poles 1P, 2P, 3P, 4P
PB502505.eps
030921d-15.eps
DB105976-30.eps
G-28 TOC
Version : 14 - 15/12/2023
160E7400
PrismaSeT P Active - Linergy distribution systems www.se.com
Linergy FH
Comb busbar for 18 mm pitch for Acti 9
Device feeders
IEC 60947-7-1, IEC 61439-2
PB502379-30.eps
Description
Comb busbars make it easier to install Acti 9 circuit breakers.
b Can be sawn and cut in a single pass, with a metal saw (the end-caps are compulsory
after cutting).
b Supplied with two lateral end-caps to reinforce copper bars insulating (IP2) except for
57 module references.The side plates are compulsory after cutting.
b Easy cut to length thanks to cutting marks on the insulating material and copper bars.
b The phases are identified by symbols on each side of the comb busbar for installation
in all positions.
b The special comb busbars for circuit breakers with 9 mm auxiliaries have a 9 mm gap
for inserting iOF and iSD.
PB110252-65.eps
Rated operational (Ie) 100 A
current at 40 °C
Rated conditional (Isc) Compatible with the breaking capacity of Acti 9 circuit breakers
short-circuit current
of an assembly
Rated insulation (Ui) 500 V AC
voltage
Rated voltage (Ue) 415 V AC
Degree of pollution 3
Fire resistance to Self-extinguishing 960 °C, 30 s
IEC 695-2-1
Colour RAL 7016 (anthracite grey)
Use
Power supply by connector recommended
Type L1… L1L2… L1L2L3... NL1L2L3… NL1NL2… AuxL1... AuxL1L2… AuxL1L2L3 AuxNL1… AuxL1… AuxL1…
…NL3 …L2L3 …AuxL2… …AuxL2…
…AuxL3 …AuxL3
Set of 1 1 1 1 1 1 1 1 1 1 1
Catalog numbers
6 modules of 18 mm A9XPH106 - - - - - - - - - -
12 modules of 18 mm A9XPH112 A9XPH212 A9XPH312 A9XPH412 A9XPH512 (1) - - - - - -
18 modules of 18 mm
24 modules of 18 mm
- - - - A9XPH518 (1) -
A9XPH124 A9XPH224 A9XPH324 A9XPH424 A9XPH524 (1) -
-
-
-
-
-
-
-
-
-
- G
57 modules of 18 mm A9XPH157 A9XPH257 A9XPH357 A9XPH457 A9XPH557 (1) A9XAH157 A9XAH257 A9XAH357 A9XAH457 A9XAH657 A9XAH557 (1)
(1) This comb busbar is only compatible in top feeding for simple lug devices and bottom feeding on double lug devices.
Installation
PB110290-20.eps
PB110793-20.eps
Accessories
Number of poles 1P 2P 3P 4P - - -
DB404806.eps
DB404808.eps
PB110258-7.eps
PB110259-7.eps
Set of 10 10 10 10 20 4 4
Catalog numbers A9XPE110 A9XPE210 A9XPE310 A9XPE410 A9XPT920 A9XPCM04 A9XPCD04
Version : 14 - 15/12/2023
160E7400 TOC G-29
PrismaSeT P Active - Linergy distribution systems www.se.com
Linergy FH
Comb busbar for 18 mm pitch for Acti 9
Device feeders
IEC 60947-7-1, IEC 61439-2
Description
PB502380-30.eps
PB110231-15.eps
Rated operational current to 40 °C (Ie) 100 A
Rated conditional short-circuit (Isc) Compatible with the breaking capacity of Acti 9 circuit breakers
current of an assembly
Rated insulation voltage (Ui) 500 V AC
Rated voltage (Ue) 415 V AC
Degree of pollution 3
Fire resistance to IEC 695-2-1 Self-extinguishing 960 °C, 30 s
Colour RAL 7016 (anthracite grey)
Use
Power supply by connector recommended
Type L1 L1L2 L1L2L3 NL1L2L3 NL1NL2NL3
Set of 1 1 1 1 1
Catalog numbers - A9XPM212 - A9XPM412 A9XPM512 (1)
12 modules of 18 mm
Installation
PB110290-25.eps
PB110793-25.eps
Accessories
PB110257-10.eps
PB110258-7.eps
PB110259-7.eps
PB108164-35.eps
(1) This comb busbar is only compatible in top feeding for simple lug devices and bottom feeding on double lug devices.
G-30 TOC
Version : 14 - 15/12/2023
160E7400
PrismaSeT P Active - Linergy distribution systems www.se.com
Linergy FH
Comb busbar for 9 mm pitch for Acti 9, C60
Device feeders
IEC 60439-1
Description
Comb busbars ensure:
PB502382-70.eps
b Easy, reliable mounting of 1P+N and 3P+N, TL, CT, ID, V, BP and Cm switchgear:
tooth positioning opposite the device terminals is ensured by indexing of copper
parts.
C60/ID Group Feeder comb busbars contain two different parts:
b connection of Group Feeder switchgear: C60 (3P + N) or ID (3P + N) circuit
breaker in 18 mm modules, powered by cables, through the bottom, directly by the
terminals
b connection of Acti 9 switchgear in 9 mm modules.
DB123729.eps
DB123730.eps
21501 21505
Complete comb busbars (supplied with 4 side plates and 1 tooth cap)
Rated operational current to 40 °C (Ie) 80 A
Rated conditional short-circuit (Isc) Compatible with the breaking capacity of Acti 9 C60 and circuit breakers
current of an assembly
Rated insulation voltage (Ui) 440 V AC
Rated voltage (Ue) 230 V AC (P + N) - 400 V AC (3P + N)
Rated impulse withstand voltage (Uimp) 6 kV
Degree of protection IP20
Degree of pollution 3
Fire resistance to IEC 695-2-1 Self-extinguishing 960 °C, 30 s
Colour RAL 7035
Number of 18 mm modules Comb busbar 12 18 24 12 18 24
Tooth cap 3 3 6 3 3 6
Catalog numbers 21501 19512 21503 21505 19516 21507
Comb busbars alone
Number of 18 mm modules Comb 48 48
busbar
Catalog numbers 21089 21093
Accessories
Number of poles 1P + N 3P + N
DB123733.eps
DB123731.eps
DB123732.eps
Version : 14 - 15/12/2023
160E7400 TOC G-31
PrismaSeT P Active - Linergy distribution systems www.se.com
Linergy FH
Comb busbar for 9 mm pitch for Acti 9
Device feeders
IEC 60439-1
PB502383-10.eps
Description
b Connection of Clario, Prodis and Librio switchgear in 9 mm modules.
b The special comb busbars for circuit breaker have a gap of 9 mm for inserting OF,
SD, OF-SD/OF auxiliaries.
b The comb busbars for 3P + N circuit breakers and auxiliaries are compatible with
PrismaSeT switchboard.
b 1P+N comb busbars are compatible with PrismaSeT and Pragma 24.
PB110801-10.eps
A9N21036
Comb busbars DPN Vigi comb busbars
Rated operational current to 40 °C (Ie) 63 A
Rated conditional short-circuit (Isc) Compatible with the breaking capacity of Acti 9 circuit breakers
current of an assembly
Rated insulation voltage (Ui) 500 V AC
Rated voltage (Ue) 230 V AC (P + N) - 400 V AC (3P + N)
Degree of protection IP20
Degree of pollution 3
Fire resistance to IEC 695-2-1 Self-extinguishing 960 °C, 30 s
Colour RAL 7035
Number of 18 mm modules 56 56 56 56
Catalog numbers A9N21035 A9N21036 A9N21037 A9N21038
Accessories
Number of poles 1P + N 3P + N
PB110805-10.eps
PB110806-10.eps
PB110807-10.eps
PB110804-10.eps
Side plates Connectors (grey) Neutral connectors (blue) Tooth cap (1 x 18 mm module)
Set of 20 10 10 10
Catalog numbers A9N21039 A9N21040 A9N21041 A9N21042 A9N21050
G-32 TOC
Version : 14 - 15/12/2023
160E7400
PrismaSeT P Active - Linergy distribution systems www.se.com
Linergy FH
Horizontal comb busbar for 18 mm pitch for Domae
Device feeders
IEC 60439-1, IEC 60664
Description
PB101626-30.eps
Comb busbars:
b Comb busbars ensure: Easy, reliable mounting of 1P+N and 3P+N, TL, CT, ID, V,
BP and Cm switchgear: tooth positioning opposite the device terminals is ensured by
indexing of copper parts
b Can be sawn and cut in a single pass, with a metal saw (the end-caps are
compulsory after cutting).
b A re supplied with 2 (IP20) lateral end-caps (mandatory).
b Teeth that have been left free can be insulated by tooth-caps.
PB502372.eps
Rated operational (Ie) 63 A
current to 40 °C
Rated conditional (Isc) Compatible with the breaking capacity of circuit breakers
short-circuit current
of an assembly
Rated insulation voltage (Ui) 500 V AC
Rated voltage (Ue) L/N 230 V AC
L/L 400 V AC
Degree of pollution 3
Fire resistance to IEC 695-2-1 Auto-extinguible to 850 °C 30 secondes
Colour RAL 7035
Power supply By 16 mm2 semi-rigid cables or 10 mm2 flexible cables
By connector
Number of 18 mm modules 12 57 12 57 12 57 12 57 57
Catalog numbers 10387 10388 10389 10390 10391 10392 10393 10394 10395
Installation
PB101630_SE-45.eps
Accessories
PB502373.eps
PB101632-10.eps
PB502376-40.eps
PB110898-25.eps
Type Connectors Side plates (2 phases) Side plates (3 phases) Side plates (4 phases) Tooth caps
(4 x 35 mm²)
Set of 1 10 10 10 10
Catalog numbers 10397 10398 10399 10405 10396
Version : 14 - 15/12/2023
160E7400 TOC G-33
PrismaSeT P Active - Linergy distribution systems www.se.com
Linergy FH
Horizontal biconnect comb busbar for 18 mm pitch
Device feeders
IEC 60664-1
PB502381-30.eps
Description
b Distribution and sub-distribution of the electric power supply.
b Fast assembly and disassembly of connected devices.
PB110876-25.eps
PB110879-25.eps
PB110882-25.eps
PB110885-25.eps
Rated operational current to (Ie) 63 A
40 °C
Rated conditional (Isc) Compatible with the breaking capacity of circuit breakers
short-circuit
current of an assembly
Rated insulation voltage (Ui) 500 V AC
Rated voltage (Ue) L/N 230 V AC
L/L 400 V AC
Degree of pollution 3
Fire resistance to IEC 695-2-1 Self-extinguishing 960 °C, 30 s
Colour RAL 7035 (grey)
Use
Power supply: directly on terminal (25 mm² rigid or 16 mm² flexible) or by connector (35 mm² rigid or 25 mm² flexible with
ferrule)
Type L1 L1L2 L1L2L3 L1L2L3L4
Number of 18 mm modules 12 18 57 12 18 57 12 18 57 12 18 57
Set of 1 1 1 1 1 1 1 1 1 1 1 1
Catalog numbers R9XFH112 R9XFH118 R9XFH157 R9XFH212 R9XFH218 R9XFH257 R9XFH312 R9XFH318 R9XFH357 R9XFH412 R9XFH418 R9XFH457
Installation
DB405995-20.eps
PB110889-30.eps
Installation
DB405995-20.eps
Accessories
Number of poles 1P 2P 3P 4P
PB110895-10.eps
PB110898-25.eps
PB110899-10.eps
G-34 TOC
Version : 14 - 15/12/2023
160E7400
PrismaSeT P Active - Linergy distribution systems www.se.com
Linergy TA
Auxiliary connections
Description Panel-mounted USB and RJ45 ports in 22.5 mm hole with notch
Interface type USB interface, Ethernet interface, Plastic Rigid plastic Metal
jack type A RJ45 jack protection protection protection
cover IP65/ cover IP65/ cover IP65/
IP67 IP67 IP67/IP69K
Connection type USB port 3.0 A-A RJ45 port Cat. 6 Ø 22 mm/0.866 in.
USB and RJ45 ports
Others characteristics IP20 Black Transparent Silver
ZBSP2_24.ai
Version : 14 - 15/12/2023
160E7500 TOC G-35
PrismaSeT P Active - Linergy distribution systems www.se.com
Linergy TB
Earth bars
DD381560-LIN.eps
Copper earth bar
Cross-section (mm) 12 x 3
Effective length (mm) 330
Total length (mm) 450
Composition Copper bar with 1 terminal 16 to 35 mm2
Rated short time withstand current 9 kA rms/0.5 s
(Icw)
Catalog numbers LVS04201
Accessories
75 mm 37 mm
DD381560-LIN.eps
DD381560-LIN.eps
Earth blocks with terminals
Spring-fixing (clip onto the earth bar)
Total connection capacity 12 x 4 mm2 3 x 16 mm2
Composition 4 earth blocks 4 earth blocks
Rated short time withstand current 1 kA rms/0.5 s 4 kA rms/0.5 s
(Icw)
Catalog numbers LVS04214 LVS04215
Accessories
DD381516-LIN.eps
Accessories
DD381519-LIN-45.eps
Dd381517-LIN.eps
G-36 TOC
Version : 14 - 15/12/2023
160E7500
PrismaSeT P Active - Linergy distribution systems www.se.com
Linergy TB
PE conductor
PE conductor
DD381183-LIN.eps
DD381182-LIN.eps
DD381184-LIN.eps
Vertical PE conductor Vertical PE conductor Horizontal PE conductor
with Linergy LGY profile with Linergy BS busbar with Linergy BS busbar
(W = 1670 mm) (W = 1675 mm)
Rated short-time (Isc) y 65 > 65... y 80 = 100 y 40 > 40 y 40 > 40
current
Permissible current (A) 630 800 1250 400 600 400 600
Bar size (mm) 25 x 5 50 x 5 25 x 5 50 x 5
Characteristics Drilled flat bar Ø10.6 Drilled flat bar Ø10.6
mm (one 10.6 mm mm (two 10.6 mm
hole every 25 mm hole every 25 mm
along the entire along the entire
length) length)
Catalog numbers LVS04502 LVS04503 LVS04505 LVS04512 LVS04515 LVS04512 LVS04515
Support selection
Composition Three supports for one vertical PE Three supports for one vertical PE Two supports for one horizontal PE
(supplied with PE marking) to secure to the (supplied with PE marking) to secure to the
framework framework
Catalog numbers LVS04657 LVS04657 LVS04667
G
Connection plates for horizontal/vertical PE bars Linergy connection hardware
Composition 2 copper angle brackets 20 M8 bolts (W = 25 mm) + 20 nuts + 20 contact washers for
connection to cable lugs or flexible bars
Catalog numbers LVS04672 LVS04766
PEN conductor
DD384616.eps
Linergy TB PEN installation kit with 1600 A connection 10 mm horizontal Linergy LGYE vertical connection
LGY vertical profile busbar with Linergy LGY profile 1600 A
Catalog numbers LVS04656 (1) LVS04636 LVS04602
Note: for further details > page I-12.
(1) For LGYE HBB, additional fish plate need to be manufactured as per the drawing supplied by Schneider Electric.
Version : 14 - 15/12/2023
160E7500 TOC G-37
PrismaSeT P Active - Linergy distribution systems www.se.com
Secondary distribution
Introduction
In PrismaSeT P Active cubicles, terminal blocks are commonly installed in a lateral
Dd383711.eps
Dd381513.ai
Dd381514.ai
Modular rail, depth adjustable (W = 432 mm)
LVS03402 - -
2 modular rails W = 1600 mm
LVS04226 LVS04226 -
2 universal angle brackets
LVS03581 LVS03581 -
Set of two lateral cross-members W = 400 mm
LVS03584 - -
Characteristics Terminal blocks are grouped on The terminal block is generally Terminal blocks can be directly
modular rails that can be depth installed in the cable installed on the mounting plates
adjusted behind a plain front plate. compartment, W = 300 or for horizontally mounted
400 mm. ComPacT NSX100/630 and
The terminal blocks clip onto a vertically mounted ComPacT
modular rail. The rail is secured to NS630b/1600 for connection of
cable-tie supports using universal auxiliary wires.
angle brackets for precise
positioning of the terminal blocks.
G-38 TOC
Version : 14 - 15/12/2023
160E7500
PrismaSeT P Active - Linergy distribution systems www.se.com
Electrical characteristics
Device
Ambient temperature around the switchboard
25°C 30°c 35°C 40°C 45°C 50°C
IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
Rated current of a circuit Inc (A)
Linergy BW
Insulated bus bar Linergy BW 125A 134 125 129 120 125 116 120 111 116 106 110 b
Insulated bus bar Linergy BW 160A 171 160 166 154 160 148 154 142 148 135 142 b
Insulated bus bar Linergy BW 250 267 250 259 241 250 231 241 222 231 211 222 b
Insulated bus bar Linergy BW 400A 428 400 414 385 400 370 385 355 370 338 355 b
Insulated bus bar Linergy BW 630A 673 630 652 607 630 583 607 558 583 532 558 b
Linergy BS
Rear flat busbars 160 A 171 160 166 154 160 148 154 142 148 135 142 b
Rear flat busbars 250 A 267 250 259 241 250 231 241 222 231 211 222 b
Rear flat busbars 400 A 428 400 414 385 400 370 385 355 370 338 355 b
Rear flat busbars 630 A 673 630 652 607 630 583 607 558 583 532 558 b
Linergy BS
Multi-stage busbars 160 A 171 160 166 154 160 148 154 142 148 135 142 b
Multi-stage busbars 250 A 267 250 259 241 250 231 241 222 231 211 222 b
Multi-stage busbars block 400A 428 400 414 385 400 370 385 355 370 338 355 b
Multi-stage busbars block 630 A 673 630 652 607 630 583 607 558 583 532 558 b
Linergy BS
Multi-stage distribution block 160 A 171 160 166 154 160 148 154 142 148 135 142 b
Multi-stage distribution block 250 A 267 250 259 241 250 231 241 222 231 211 222 b
Multi-stage distribution block 400A 428 400 414 385 400 370 385 355 370 338 355 b
Multi-stage distribution block 630 A 673 630 652 607 630 583 607 558 583 532 558 b
Linergy DX
Quick distribution block 134 125 129 120 125 116 120 111 116 106 111 b
Linergy DX 4P 125A
Quick distribution block 171 160 166 154 160 148 154 142 148 135 142 b
Linergy DX 4P 160A
Quick distribution block 171 160 166 154 160 148 154 142 148 155 142 b
Linergy DX 1P 1P 160A
Linergy DP
Quick distribution block
Linergy DP 3P-4P 160A
160 160 155 155 150 150 145 145 140 140 135 b G
Quick distribution block 267 250 259 241 250 231 241 222 231 211 222 b
Linergy DP 3P-4P 250A
Linergy FM
Quick device feeders 67 63 65 61 63 58 61 56 58 53 56 b
Linergy FM 4P 63A
Quick device feeders 86 80 83 77 80 74 77 71 74 68 71 b
Linergy FM 4P 80A
Quick device feeders 171 160 166 154 160 148 154 142 148 135 142 b
Linergy FM 4P 160A
Quick device feeders 214 200 207 193 200 185 193 177 185 169 177 b
Linergy FM 2P 200A
Quick device feeders 214 200 207 193 200 185 193 177 185 169 177 b
Linergy FM 3P 200A
Quick device feeders 214 200 207 193 200 185 193 177 185 169 177 b
Linergy FM 4P 200A
Quick device feeders 214 200 207 193 200 185 193 177 185 169 177 b
Linergy FM 4P 200A (36 modules)
b Check the concordance between Linergy derating value and upstream protection device derating value.
Version : 14 - 15/12/2023
160E7500 TOC G-39
PrismaSeT P Active - Linergy distribution systems www.se.com
Linergy TR
Terminal blocks
Secondary distribution
Connection technology
Type of Cross section Color Screw tech Spring tech Push-in tech Miniature Miniature Miniature
terminal area screw for 15 spring for 15 spring for
block mm DIN rail mm DIN rail direct mount
Passthrough 2.5 mm² (2 pts) Grey NSYTRV22 NSYTRR22 NSYTRP22 NSYTRV22M NSYTRR22M NSYTRR22MF
Blue NSYTRV22BL NSYTRR22BL NSYTRP22BL NSYTRV22MBL NSYTRR22MBL NSYTRR22MFBL
Orange NSYTRV22AR NSYTRR22AR NSYTRP22AR - - NSYTRR22MFF *
2.5 mm² (3 pts) Grey NSYTRV23 NSYTRR23 NSYTRP23 - - -
Blue NSYTRV23BL NSYTRR23BL NSYTRP23BL - - -
Orange - NSYTRR23AR NSYTRP23AR - - -
2.5 mm² (4 pts) Grey NSYTRV24 NSYTRR24 NSYTRP24 - NSYTRR24M NSYTRR24M
Blue NSYTRV24BL NSYTRR24BL NSYTRP24BL - NSYTRR24MBL NSYTRR24MBL
2.5 mm² Grey NSYTRV24D NSYTRR24D NSYTRP24D - - -
(4 pts, 2 levels) Blue NSYTRV24DBL NSYTRR24DBL NSYTRP24DBL - - -
2.5 mm² Grey NSYTRV26T NSYTRR26T NSYTRP26T - - -
(6 pts, 3 levels) Blue NSYTRV26TBL NSYTRR26TBL NSYTRP26TBL - - -
4 mm² (2 pts) Grey NSYTRV42 NSYTRR42 NSYTRP42 NSYTRV42M - -
Blue NSYTRV42BL NSYTRR42BL NSYTRP42BL NSYTRV42MBL - -
Orange NSYTRV42AR NSYTRR42AR - - - -
4 mm² (3 pts) Grey NSYTRV43 NSYTRR43 NSYTRP43 - - -
Blue NSYTRV43BL NSYTRR43BL NSYTRP43BL - - -
4 mm² (4 pts) Grey NSYTRV44 NSYTRR44 NSYTRP44 - - -
Blue NSYTRV44BL NSYTRR44BL NSYTRP44BL - - -
4 mm² Grey NSYTRV44D NSYTRR44D - - - -
(4 pts, 2 levels) Blue NSYTRV44DBL NSYTRR44DBL - - - -
6 mm² (2 pts) Grey NSYTRV62 NSYTRR62 - - - -
Blue NSYTRV62BL NSYTRR62BL - - - -
10 mm² (2 pts) Grey NSYTRV102 NSYTRR102 - - - -
Blue NSYTRV102BL NSYTRR102BL - - - -
16 mm² (2 pts) Grey NSYTRV162 NSYTRR162 - - - -
Blue NSYTRV162BL NSYTRR162BL - - - -
Earth 2.5 mm² (2 pts) Green/Yellow NSYTRV22PE NSYTRR22PE NSYTRP22PE NSYTRV22MPE NSYTRR22MPE -
protection 2.5 mm² (3 pts) Green/Yellow NSYTRV23PE NSYTRR23PE NSYTRP23PE - - -
2.5 mm² (4 pts) Green/Yellow NSYTRV24PE NSYTRR24PE NSYTRP24PE - - -
4 mm² (2 pts) Green/Yellow NSYTRV42PE NSYTRR42PE NSYTRP42PE NSYTRV42MPE - -
4 mm² (3 pts) Green/Yellow NSYTRV43PE NSYTRR43PE NSYTRP43PE - - -
4 mm² (4 pts) Green/Yellow NSYTRV44PE NSYTRR44PE NSYTRP44PE - - -
6 mm² (2 pts) Green/Yellow NSYTRV62PE NSYTRR62PE - - - -
10 mm² (2 pts) Green/Yellow NSYTRV102PE NSYTRR102PE - - - -
16 mm² (2 pts) Green/Yellow NSYTRV162PE NSYTRR162PE - - - -
Knife 2.5 mm² (2 pts) Grey NSYTRV22SC NSYTRR22SC NSYTRP22SC - - -
Disconnect Orange NSYTRV22ST (1) NSYTRR22SCAR - - - -
2.5 mm² (3 pts) Grey - NSYTRR23SC NSYTRP23SC - - -
Orange - NSYTRR23SCAR - - - -
2.5 mm² (2 levels) Grey NSYTRV24SCD NSYTRR24SCD - - - -
Fuse 4 mm² (2 pts) Black NSYTRV42SF5 - - - - -
Disconnect 5 x 20 mm fuse Black (12 V) NSYTRV42SF5LD (2) - - - - -
Black (230 V) NSYTRV42SF5LA (2) - - - - -
Basic 4 mm² (2 pts) Grey NSYTRV42TB NSYTRR42TB NSYTRP42TB - - -
Disconnect (3)
Measuring 6 mm² (2 pts) Grey NSYTRV62TTD - - - - -
transducer Disconnect
6 mm² (2 pts) Grey NSYTRV62TT - - - - -
6 mm² (2 pts) Green/Yellow NSYTRV62TTPE - - - - -
* Grey terminal with flange. (1) Grey disconnect terminal with 2 test points.
(2) With light indicator.
(3) Fuse or component carrier not supplied.
G-40 TOC
Version : 14 - 15/12/2023
160E7500
PrismaSeT P Active - Linergy distribution systems www.se.com
Linergy TR
Terminal blocks
Secondary distribution
- NSYTRACT22 - -
- NSYTRACT22 - -
- NSYTRACT22 - -
Version : 14 - 15/12/2023
160E7500 TOC G-41
Functional
www.se.com
partitioning
2 Version : 14 - 15/12/2023
160E8000
PrismaSeT P Active - Partitioning www.se.com
Contents
Main distribution
IS Service Indices
Presentation H-2
Form partitioning
Presentation H-3
Form 1 partitioning
Covering the supply terminals on the incoming device H-4
Form 2 partitioning H-5
Form 3 partitioning H-6
Form 4 partitioning H-7
Other partitions H-8
Version : 14 - 15/12/2023
160E8000 TOC H-1
PrismaSeT P Active - Partitioning www.se.com
IS Service Indices
Presentation
How is it characterized?
b The SI is a value expressed in a three digits format (from 1 to 3) which respectively
translate the level of:
v operation,
v maintenance,
v and evolution of the LV switchboard
b The value 1 offers the lowest service index and the value 3 the highest service
index.
b The minimum index is 111 and the maximum is 333.
Note: The service index may be different in the same switchboard, for incomers or outgoings,
in order to meet the customer needs.
2 I want this operation to result only in the complete I want a limited interruption to the functional
shutdown of the only functional unit (1) unit (1) concerned only. The refitting will be done
I want that the possible interruption be limited to
the functional unit (1) concerned only.
concerned. by an intervention on the connections. A stock of some predefined functional units is
assured.
3 I want that this operation only stops the power of I want a limited interruption to the functional
the functional unit (1) concerned, but enables unit (1) concerned only. The refitting will be done
I want an operation limited to the functional
unit (1) concerned, with no interruption of the
automation tests that allow testing the installation without any intervention on the connections. switchboard.
in full size before restarting. The evolution is free, within the limits imposed by
the switchboard manufacturer.
(1) Functional unit: part of an assembly comprising all the mechanical and electrical
components that contribute to the performance of a single feature.
H-2 TOC
Version : 14 - 15/12/2023
160E8100
PrismaSeT P Active - Partitioning www.se.com
Forms partitioning
Presentation
PrismaSeT P Active offers solutions for forms 1, 2a, 2b, 3a, 3b, 4a, 4b.
Form 1 Form 2
No internal separation Separation between horizontal busbars, vertical busbars
and functional units
Form 3 Form 4
Form 2 + separation of functional units from one another Form 3 + separation of the terminals of the functional units
from one another
Version : 14 - 15/12/2023
160E8100 TOC H-3
PrismaSeT P Active - Partitioning www.se.com
Form 1 partitioning
Covering the supply terminals on the incoming device
Main distribution
Dd382019.eps
Dd382020.eps
40 60
0 650 0 650
Dd382022.eps
40 40
0 0
60 40
0 650 0 650
H-4 TOC
Version : 14 - 15/12/2023
160E8100
PrismaSeT P Active - Partitioning www.se.com
Form 2 partitioning
Main distribution
Lateral partitioning
b Made of:
v four supports that clip to the framework
v five extruded slats that clip to the supports
v two metal plates at the top and bottom that can be cut out to pass a PE or PEN
conductor, or one or two 30 x 60 mm trunking sections
b Compliance with standard IEC 695.2.1 concerning withstand to fire.
DD385402.eps
Dd383714.eps
Dd381588.eps
DD382528.eps
Dd381589.eps
W = 150 mm W = 300 mm
Characteristicsb Vertical barrier made of b This kit enables passage of the Can be installed in the front and rear of the busbar compartment.
insulating slats connection between a device > Protects against direct contact with the busbars.
b can be installed on both sides of 1600 A (MTZ2, INS-INV) and b For 800 mm cubicles :
Linergy BS or Linergy LGY lateral vertical busbars. v the door is systematically supplied with a barrier.
busbars b It is made up of an insulated v the cover frame is supplied with a wicket door, W = 150 mm, on
b The space between the slats is plate (six modules high = 300 mm) which devices can be mounted. A front barrier is indispensable.
sufficient for prefabricated that can be cut as required, b A barrier is required at the rear of the busbar compartment in
connections (one copper bar, 5 or supplied with supports and the cubicles that are 600,800 and 1000 mm deep.
10 mm thick, or insulated flexible necessary hardware.
bars) or for cables up to 35 mm², b Has to be use with MTZ2
while maintaining the degree of interlocking mounting plate
protection IP2X
Catalog number LVS04922 LVS04924 LVS04921 LVS04920
Horizontal partitioning
DD384521.EPS
b Set of two barriers (front and rear), plus a slotted rear panel for efficient natural
convection in the switchboard.
b The set can be used to partition horizontal busbars installed at the top or bottom
of the cubicle.
b The space required for the busbars is not increased.
LVS04976
H
Linergy LGYE Linergy BS
Top position Bottom position Top position Bottom position
In y 2500 A u 3200 A y 2500 A u 3200 A y 3200 A 4000 A y 3200 A
Nb of module 3 4 3 4 3 4 3
D400
Cover W = 300 LVS04973 LVS04963 LVS04973 + LVS04915 LVS04963 + LVS04915 LVS04973 LVS04963 LVS04973 + LVS04915
W = 400 LVS04974 LVS04964 LVS04974 + LVS04915 LVS04964 + LVS04915 LVS04974 LVS04964 LVS04974 + LVS04915
W650 LVS04976 LVS04966 LVS04976 + LVS04919 LVS04966 + LVS04919 LVS04976 LVS04966 LVS04976 + LVS04919
W650 + 150 LVS04976 LVS04966 LVS04976 + LVS04919 LVS04966 + LVS04919 LVS04976 LVS04966 LVS04976 + LVS04919
W800 LVS04978 LVS04968 LVS04978 + LVS04919 LVS04968 + LVS04919 LVS04978 LVS04968 LVS04978 + LVS04919
D600
Cover W = 300 LVS04983 LVS04963 LVS04983 + LVS04915 LVS04963 + LVS04915 LVS04983 LVS04963 LVS04983 + LVS04915
W = 400 LVS04984 LVS04964 LVS04984 + LVS04915 LVS04964 + LVS04915 LVS04984 LVS04964 LVS04984 + LVS04915
W650 LVS04986 LVS04966 LVS04986 + LVS04919 LVS04966 + LVS04919 LVS04986 LVS04966 LVS04986 + LVS04919
W650 + 150 LVS04986 LVS04966 LVS04986 + LVS04919 LVS04966 + LVS04919 LVS04986 LVS04966 LVS04986 + LVS04919
W800 LVS04988 LVS04968 LVS04988 + LVS04919 LVS04968 + LVS04919 LVS04988 LVS04968 LVS04988 + LVS04919
Note: when the busbars are at the bottom of the cubicle, gland plates are mandatory > page F-19.
Note: to protect horizontal busbars installed at the bottom of the cubicle, the slotted horizontal panel must be replaced by a plain barrier.(LVS04915 or
LVS04919) and add a free support LVS04662.
Version : 14 - 15/12/2023
160E8100 TOC H-5
PrismaSeT P Active - Partitioning www.se.com
Form 3 partitioning
Main distribution
Form 3 partitioning
Front connection Rear connection
DD383107.eps
DD385525.eps
DD385526.eps
Dd383081.eps
Rear support for partitions 6 universal angle brackets Horizontal metal partition Rear connection
W = 650 mm W = 650 mm
Characteristics Two uprights secured to the A set of brackets can be used to A horizontal metal partition can be Vertical partitions (two cat. no. per
framework (400 mm install partial Form 3 partitioning in used to physically separate functional unit)
deep) or to the intermediate the cubicle.It does not take up any functional units from one another.
uprights (600 mm deep useful space in the switchboard. It does not take up any useful 3 to 4 modules 5 to 6 modules
frameworks). space in the switchboard.
Catalog LVS04943 LVS03583 LVS04901 LVS04955 LVS04956
numbers
H-6 TOC
Version : 14 - 15/12/2023
160E8100
PrismaSeT P Active - Partitioning www.se.com
Form 4 partitioning
Main distribution
Form 4a partitioning
Form 4 - direct connection to the device
Front connection Rear connection
DD385406.eps
DD385407.eps
DD385407.eps
DD385405.eps
DD385406.eps
Backplate Gland plate
Characteristics b a backplate (one cat. no. per b a plastic gland plate that can be easily cut out (one b a gland plate at the rear of each functional unit. It is
cubicle) made up to two metal for each functional unit) and is mounted on the connected directly to the rear supports for Form 3
half panels mounted on the rear framework. partitions
supports for Form 3 partitions.
This backplate is not 3 to 4 modules 5 to 6 modules 3 to 5 modules 4 to 6 modules
indispensable for 400 mm deep
frameworks
Catalog LVS04946 LVS04951 LVS04952 LVS04951 LVS04952
numbers
Form 4b partitioning
Forme 4b - connection transfer
In a lateral compartment At the rear of the cubicle
Dd383604.eps
DD385405.eps
Dd383090.eps
Dd382035.eps
Dd382036.eps
Dd382039.eps
Dd382038.eps
Backplate Cover
H
Characteristics b a backplate (one cat. no. per b a cover with plastic gland plates that can be easily b It comprises two height-adjustable metal flanges
cubicle) made up to two metal cut out on the side and bottom. and plastic gland plates that can be easily cut out at
half panels mounted on the rear the rear and bottom.
supports for Form 3 partitions. 3 to 5 modules W150 4 to 6 modules W200 3 to 5 modules 4 to 6 modules
This backplate is not
indispensable for 400 mm deep
frameworks
Catalog LVS04946 LVS04953 LVS04954 LVS04953 LVS04954
numbers
Version : 14 - 15/12/2023
160E8100 TOC H-7
www.se.com
PrismaSeT P Active - Partitioning
Other partitions
Main distribution
Inter-cubicle partition
DD383720.eps
Dd383722.eps
D400 D600
Characteristics Metal partition, used to separate two adjacent cubicles.
It is made up of two panels, each 850 mm high.
The top and bottom ends have knock-outs for busbars, PE/PEN conductors or auxiliary wiring.
Supplied with the necessary supports and hardware, the partition is mounted on the framework and does not hinder installation of
the functional mounting plates.
Catalog numbers LVS04911 LVS04911 + LVS04931
H-8 TOC
Version : 14 - 15/12/2023
160E8100
www.se.com
Version : 14 - 15/12/2023
160E8100 TOC H-9
Additional
information
PrismaSeT P Active - Additional information www.se.com
Contents
Spare parts
After-sales accessories I-4
Optimise electrical networks
Improving power quality I-9
Additional equipment to optimise electrical installations I-10
Electrical characteristics
Designing PrismaSeT P Active power circuits
Presentation and approach I-11
Designing horizontal busbars
Linergy LGYE I-14
Linergy BS I-15
Designing vertical busbars
Linergy LGY I-16
Linergy LGYE I-17
Linergy BS I-18
Designing rear busbars
Linergy LGYE, Linergy BS I-19
Designing connections between a device and busbars
Prefabricated connections for ComPacT NS630b to NS1600 I-20
Prefabricated connections for MasterPacT 06-16 I-21
Prefabricated connections for ComPacT NS630b to NS1000 I-22
Fixed MasterPacT 08-16 I-23
Fixed MasterPacT 08-32 I-24
Drawout MasterPacT 08-16 I-25
Drawout MasterPacT 08-32 I-26
Designing connections between a device and busbars
Dedicated cubicle
Fixed MasterPacT 08-32 I-27
Drawout MasterPact 08-32 I-28
Designing horizontal busbars
Linergy LGYE I-29
Linergy BS I-30
Designing vertical busbars
Linergy LGY I-31
Linergy LGYE I-32
Linergy BS I-33
Designing rear busbars I-34
Designing connections between a device and busbars
Prefabricated connections for ComPacT NS630b to NS1600 I-35
Prefabricated connections for MasterPacT 06-16 I-36
Prefabricated connections for ComPacT NS630b to NS1000 I-37
Fixed MasterPacT 08-16 I-38
Fixed MasterPacT 08-32 I-39
Drawout MasterPacT 08-16 I-40
Drawout MasterPacT 08-32 I-41
I
Version : 14 - 15/12/2023
160E9000 TOC I-1
PrismaSeT P Active - Additional information www.se.com
Contents
Enclosure characteristics
Selection of enclosures according to the premises I-63
Enclosure characteristics
Designing connections between a device and busbars
Dedicated cubicle - W = 400 mm I-72
I-2 TOC
Version : 14 - 15/12/2023
160E9000
www.se.com
Version : 14 - 15/12/2023
160E9000 TOC I-3
PrismaSeT P Active - Additional information www.se.com
After-sales accessories
Spare parts
Linergy BW busbar accessories
Linergy BW accessories, 160/400 A LVS01210
2 end plugs
DD385483.eps
Framework accessories
Framework accessories LVS01104
4 top sealing components
DD384562.EPS
4 bottom sealing components
4 bottom cross-piece plugs
2 adjacent mounting spacer tubes
2 mounting hardware
12 conical washers
I-4 TOC
Version : 14 - 15/12/2023
160E9100
PrismaSeT P Active - Additional information www.se.com
After-sales accessories
Spare parts
Front-plate accessories
10 sets of 2 grips quarter turn LVS01094
DD384582.eps
Accessory
Plain wicket door, W = 150 mm LVS01110
DD384565.EPS
4 flat plates for 3200 - 4000 A connection
16 conical contact washer Ø8
16 torque nut M8
Rear accessories
Accessories IP55 LVS01101
4 IP55 framework plugs
DD385379.eps
1 2 3 4
4 stop doors
base + screw + washer + nut
8 cage nuts
5 6 7 3 white grommet plugs
2 IP55 roof and rear panel fixing systems
6 IP55 rear panel fixing systems
Version : 14 - 15/12/2023
160E9100 TOC I-5
PrismaSeT P Active - Additional information www.se.com
After-sales accessories
Spare parts
Side panel accessories
Side panel accessories LVS01100
16 fixing system IP30
DD385979.eps
1 2
16 cage nuts
3
6 cage nuts
6 mounting sets of screw fixing IP55 for roof
Roof accessories
Roof accessories LVS01112
4 lifting ring plugs
DD385978.eps
x4
300-700-900
I-6 TOC
Version : 14 - 15/12/2023
160E9100
PrismaSeT P Active - Additional information www.se.com
After-sales accessories
Spare parts
Framework accessories
Framework accessories
Frame bottom cross-member W650 to use with LVS08566 LVS01120 (1)
DD384572.EPS
Door accessories
Closing accessories LVS01105
4 screws THF M6 x 16
DD384617.eps
4 door strikes
1 2 3
3 1/4 turn studs
2 stop doors
3 hinge pins
7 captive nuts for frame
4 5 6
3 4
Version : 14 - 15/12/2023
160E9100 TOC I-7
PrismaSeT P Active - Additional information www.se.com
After-sales accessories
Cover accessories
Cover accessories
Set of 2 side panels D400 PrismaSeT P Active LVS08755
Set of 2 side panels D600 PrismaSeT P Active LVS08765
Set of 2 side panels D400 PrismaSeT P Active LVS08750
Set of 2 side panels D600 PrismaSeT P LVS08760
Green Cover W400 P for Wireless PaS LVS01126
Green Cover W650 P for Wireless PaS LVS01127
Green Cover W800 P for Wireless PaS LVS01128
Connectivity accessories
Connectivity accessories
Cable Extender for LoRa Antenna SMT10015
Cables for Wireless Panel Server 2m 3P + N SMT10016
PrismaSeT Wireless Panel Server electronic part (without cables) SMT10019
I-8 TOC
Version : 14 - 15/12/2023
160E9100
PrismaSeT P Active - Additional information www.se.com
Spare parts
To improve power quality, Schneider Electric proposes
two power-factor correction systems, VarplusCan.
Both are designed for optimum installation in
PrismaSeT P Active.
PrismaSeT P Active enclosures are designed for installation of the new VarplusCan
DD385373.eps
power factor correction modules that improve the quality of the electrical distribution
system and reduce consumption of reactive energy.
The modules are made up of capacitors, contactors and devices protecting against
internal faults.
Installation
> page F-21 for information on installation in the enclosure.
Version : 14 - 15/12/2023
160E9100 TOC I-9
PrismaSeT P Active - Additional information www.se.com
Spare parts
During design or during subsequent operation,
electrical installations are increasingly outfitted with
components designed to optimise energy
consumption.
With PrismaSeT P Active, most of these products can
already be added to the switchboard.
By limiting the temperature within the switchboard, it is
possible to extend the life of the equipment and
optimise its use.
In addition, electricity consumption is reduced because
equipment in good condition has lower losses.
Dd381667.eps
Fans Several types of fans are available: enclosure wall or roof-mount versions. They are
particularly useful for switchboards installed in temperate environments or when the
DD381703.eps
DD385819.eps
Thermostat Thermostats are used to limit the temperature inside switchboards when heaters and
fans are installed, thus reducing heat losses.
Dd381668.eps
I-10 TOC
Version : 14 - 15/12/2023
160E9100
PrismaSeT P Active - Additional information www.se.com
Electrical characteristics
PrismaSeT P Active takes into account the installation In the following pages you will find a number of examples, validated for PrismaSeT P
and connection conditions of Schneider Electric Active switchboards, intended to assist in determining the busbars as well as the
devices. upstream and downstream connections for the installation.
The entire installation complies with standard The examples assume that the devices have already been selected.
IEC 60439-1. The result is a type tested switchboard. A complete process involves a number of steps before making final choices
(transformer, conductors, protection, etc.).
Schneider Electric offers a number of tools to assist in designing a complete
installation (technical guides, software).
PB116588.eps
Busbar sizing The factors that must be taken into account in determining the size of busbars include:
b the diversity factor.
Not all the loads supplied by a set of busbars are used at full rated load or at the
same time. The diversity factor is the means to determine the maximum load current
used to size the busbars.
Standard IEC 61439-1 and 2 §4.7 specifies the table below.
Number of circuits Diversity factor
2 and 3 0,9
4 and 5 0,8
6 and 9 0,7
10 and more 0,6
Version : 14 - 15/12/2023
160E9100 TOC I-11
PrismaSeT P Active - Additional information www.se.com
Electrical characteristics
Busbars The maximum load current for a set of busbars is a function of the thermal
environment.
DD381459.eps
The type and the size of the conductors must be determined in view of carrying the
required currents taking into account the temperatures reached in the switchboard.
These conductors are subjected to additional heat rise caused by the flowing current
(joule effect) and the connected devices.
The temperatures reached by the conductors and the insulating materials, etc. must
not exceed the maximum temperatures for which the products were designed.
Schneider Electric busbars and distribution blocks are sized to operate without any
particular constraints for the assemblies in PrismaSeT P Active switchboards
operating under normal environmental conditions (standard switchboard
configuration, 35 °C outside the switchboard, etc.).
Connection of devices u 630 A To determine the size of upstream and downstream connections for devices
> page I-42.
and busbar connections They can be used to determine:
b the size of copper busbars
b the maximum permissible current.
As a function of:
b the type of circuit breaker
b the IP value
b the ambient temperature around the switchboard
b the type of installation.
I-12 TOC
Version : 14 - 15/12/2023
160E9100
PrismaSeT P Active - Additional information www.se.com
Electrical characteristics
Designing the PE protective The protective conductor must be sufficiently sized and securely installed in the
switchboard to accept the thermal and electrodynamic constraints of the fault
conductor current.
It must be connected to the exposed conductive parts of the switchboard.
DD381471.eps
l 2t
SPE=
k
b SPE: cross-sectional area of the PE in mm²
b I: value of the phase-to-earth fault current = 60 % of the value of the phasetophase
fault current (IEC 61439-1 §8.2.4.2)
b t: time the fault current flows in seconds
b k: coefficient that depends on the type of metal, k = 143 for a copper conductor
with PVC insulation.
Example:
v IIsc = 36 kA rms C the value of the phase-to-earth fault current = 60 % of the value
of the phase-to-phase fault current (standard IEC 61439-1 and 2 § 8.4.3.2.3 and
10.11.5.6), i.e.: 36 x 0.6 = 21.6 kA
v maximum time delay for the control unit: 0,5 s
v k = 143 for copper conductors with PVC insulation.
The calculation is therefore:
2
21600 x 0,5 2
SPE = 143
= 106,8 mm
Implementing the PEN protective The size of the PEN is determined in the same manner as a neutral conductor, i.e.:
b for copper single-phase circuits or sized y 16mm², it must be the same size as the
conductor phase conductors
b for copper three-phase circuits sized > 16 mm², it can be:
v the same size as the phase conductors
DD384616.eps
Version : 14 - 15/12/2023
160E9100 TOC I-13
PrismaSeT P Active - Additional information www.se.com
Electrical characteristics
Permissible current and selection of Linergy LGYE busbars
Up to 4000 A
Linergy LGYE section
Type of bars Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40 °C 45 °C 50 °C
Size per phase IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
Linergy LGYE 630 680 580 650 550 630 530 590 500 550 470 520 b
Linergy LGYE 800 860 740 830 710 800 680 750 630 700 600 660 b
Linergy LGYE 1000 1080 920 1040 884 1000 850 940 790 880 750 830 b
Linergy LGYE 1250 1350 1150 1300 1100 1250 1050 1170 1000 1100 930 1020 b
Linergy LGYE 1600 1730 1580 1690 1530 1650 1480 1550 1380 1450 1300 1350 b
Linergy LGYE 2000 2200 1810 2100 1730 2000 1650 1900 1560 1810 1480 1720 b
Linergy LGYE 2500 2640 2230 2540 2160 2440 2100 2310 2000 2240 1930 2120 b
Linergy LGYE 3200 3400 3020 3300 2900 3200 2800 3040 2660 2890 2520 2750 b
Linergy LGYE 4000 3800 3510 3710 3430 3620 3350 3450 3180 3280 3020 3120 b
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
DD384545.eps
DD384546.eps
DD384547.eps
DD384548.eps
DD384549.eps
Section 630 A. Section 800 A. Section 1000 A. Section 1250 A. Section 1600 A.
Cat. No. LVS04560. Cat. No. LVS04561. Cat. No. LVS04562. Cat. No. LVS04563. Cat. No. LVS04564.
DD384550.eps
DD384551.eps
DD384552.eps
DD384553.eps
I-14 TOC
Version : 14 - 15/12/2023
160E9200
PrismaSeT P Active - Additional information www.se.com
Electrical characteristics
Permissible current and selection of horizontal busbar
The goal is to optimise busbar size according to the installation and operating criteria.
Up to 1600 A
Linergy BS bars, 5 mm thick
Type of bars Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40 °C 45 °C 50 °C
Size per phase IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
1 Linergy BS bar, 60 x 5 890 840 850 790 800 750 760 700 710 650 660 b
1 Linergy BS bar, 80 x 5 1130 1050 1080 990 1000 900 970 870 910 810 860 b
2 Linergy BS bars, 60 x 5 1580 1420 1500 1350 1400 1250 1350 1180 1260 1090 1180 b
2 Linergy BS bars, 80 x 5 2010 1820 1920 1720 1800 1600 1720 1510 1610 1390 1510 b
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Up to 3200 A
Linergy BS bars, 10 mm thick
Type of bars Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40 °C 45 °C 50 °C
Size per phase IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
1 Linergy BS bar, 50 x 10 1330 1220 1260 1160 1200 1080 1130 1010 1060 940 990 b
1 Linergy BS bar, 60 x 10 1550 1400 1470 1320 1400 1250 1320 1160 1240 1070 1160 b
1 Linergy BS bar, 80 x 10 1990 1800 1890 1700 1800 1600 1700 1500 1600 1390 1500 b
2 Linergy BS bars, 50 x 10 2270 2090 2160 1980 2050 1850 1930 1740 1810 1610 1690 b
2 Linergy BS bars, 60 x 10 2550 2270 2420 2140 2300 2000 2170 1870 2030 1720 1900 b
2 Linergy BS bars, 80 x 10 3110 2820 2970 2660 2820 2500 2660 2330 2500 2160 2330 b
2 Linergy BS bars, 100 x 10 3650 3280 3490 3100 3300 2900 3130 2720 2950 2510 2750 b
2 Linergy BS bars, 120 x 10 4160 3760 3960 3550 3760 3340 3560 3100 3340 2880 3120 b
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Example:
Two 50 x 10 mm bars can be used for a 2160 A current with an IP y 31 and an ambient temperature
of 30 °C around the switchboard.
Where possible, use of 10 mm bars is worthwhile in terms of the In/Isc:
b gain in time during switchboard mounting given, where applicable, the lesser number of bars
installed
b for short-circuits, the rigidity of the bars means fewer busbar supports.
Recommendation:
Use 5 mm bars for In y 1600 A and low Icw values (40 kA rms).
Use 10 mm bars for In > 1600 A and medium to high Icw values (> 40 kA rms).
Note: the values indicated above have been validated for PrismaSeT P Active switchboards.
Version : 14 - 15/12/2023
160E9200 TOC I-15
PrismaSeT P Active - Additional information www.se.com
Electrical characteristics
Permissible current and selection of Linergy LGY busbars
The goal is to optimise busbar size according to the installation and operating criteria.
Up to 3200 A
Linergy LGY section
Type of bars Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40 °C 45 °C 50 °C
IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
Linergy LGY 630 750 680 710 630 680 590 630 550 590 530 550 b
Linergy LGY 800 920 840 880 800 840 760 800 720 760 680 720 b
Linergy LGY 1000 1140 1040 1090 990 1040 950 990 900 950 850 900 b
Linergy LGY 1250 1410 1290 1350 1230 1290 1170 1230 1100 1170 1050 1100 b
Linergy LGY 1600 1800 1650 1720 1580 1650 1480 1580 1390 1480 1320 1390 b
Linergy LGY 2000 (2 x 1000) 2200 2000 2100 1900 2000 1820 1900 1720 1820 1620 1720 b
Linergy LGY 2500 (2 x 1250) 2740 2500 2620 2380 2500 2260 2380 2120 2260 2020 2120 b
Linergy LGY 3200 (2 x 1600) 3480 3200 3340 3060 3200 2920 3060 2780 2920 2640 2780 b
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Example:
A Linergy LGY channelled bar can be used for a 1650 A current with an IP y 31 and an ambient temperature around the switchboard of 35 °C.
DD381233.eps
DD381234.eps
DD381235.eps
DD385507.eps
Section 1600 A.
Cat. No. LVS04506.
Note: the values indicated above have been validated for PrismaSeT P Active switchboards.
I-16 TOC
Version : 14 - 15/12/2023
160E9200
PrismaSeT P Active - Additional information www.se.com
Electrical characteristics
Permissible current and selection of Linergy LGYE busbars
Up to 4000 A
Linergy LGYE section
Type of bars Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40 °C 45 °C 50 °C
Size per phase IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
Linergy LGYE 630 680 580 650 550 630 530 590 500 550 470 520 b
Linergy LGYE 800 860 740 830 710 800 680 750 630 700 600 660 b
Linergy LGYE 1000 1080 920 1040 884 1000 850 940 790 880 750 830 b
Linergy LGYE 1250 1350 1150 1300 1100 1250 1050 1170 1000 1100 930 1020 b
Linergy LGYE 1600 1730 1580 1690 1530 1650 1480 1550 1380 1450 1300 1350 b
Linergy LGYE 2000 2200 1810 2100 1730 2000 1650 1900 1560 1810 1480 1720 b
Linergy LGYE 2500 2640 2230 2540 2160 2440 2100 2310 2000 2240 1930 2120 b
Linergy LGYE 3200 3400 3020 3300 2900 3200 2800 3040 2660 2890 2520 2750 b
Linergy LGYE 4000 3800 3510 3710 3430 3620 3350 3450 3180 3280 3020 3120 b
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
DD384545.eps
DD384546.eps
DD384547.eps
DD384548.eps
DD384549.eps
Section Section 800 A. Section 1000 A. Section 1250 A. Section 1600 A.
630 A. Cat. No. LVS04561. Cat. No. LVS04562. Cat. No. LVS04563. Cat. No. LVS04564.
Cat. No. LVS04560.
DD384550.eps
DD384551.eps
DD384552.eps
DD384553.eps
Version : 14 - 15/12/2023
160E9200 TOC I-17
PrismaSeT P Active - Additional information www.se.com
Electrical characteristics
Permissible current and selection of vertical busbar
The goal is to optimise busbar size according to the installation and operating criteria.
Up to 1600 A
Linergy BS bars, 5 mm thick
Type of bars Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40 °C 45 °C 50 °C
Size per phase IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
1 Linergy BS bar, 60 x 5 890 840 850 790 800 750 760 700 710 650 660 b
1 Linergy BS bar, 80 x 5 1130 1050 1080 990 1000 900 970 870 910 810 860 b
2 Linergy BS bars, 60 x 5 1580 1420 1500 1350 1400 1250 1350 1180 1260 1090 1180 b
2 Linergy BS bars, 80 x 5 2010 1820 1920 1720 1800 1600 1720 1510 1610 1390 1510 b
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Up to 3200 A
Linergy BS bars, 10 mm thick
Type of bars Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40 °C 45 °C 50 °C
Size per phase IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
1 Linergy BS bar, 50 x 10 1330 1220 1260 1160 1200 1080 1130 1010 1060 940 990 b
1 Linergy BS bar, 60 x 10 1550 1400 1470 1320 1400 1250 1320 1160 1240 1070 1160 b
1 Linergy BS bar, 80 x 10 1990 1800 1890 1700 1800 1600 1700 1500 1600 1390 1500 b
1 Linergy BS bar, 100 x 10 2370 2150 2260 2030 2150 1900 2030 1780 1900 1650 1780 b
2 Linergy BS bars, 50 x 10 2270 2090 2160 1980 2050 1850 1930 1740 1810 1610 1690 b
2 Linergy BS bars, 60 x 10 2550 2270 2420 2140 2300 2000 2170 1870 2030 1720 1900 b
2 Linergy BS bars, 80 x 10 3110 2820 2970 2660 2820 2500 2660 2330 2500 2160 2330 b
2 x 1 Linergy BS bar, 80 x 10 3540 3200 3370 3020 3200 2820 3020 2650 2840 2450 2650 b
2 Linergy BS bars, 100 x 10 3650 3280 3490 3100 3300 2900 3130 2720 2950 2510 2750 b
2 Linergy BS bars, 120 x 10 4160 3760 3960 3550 3760 3340 3560 3100 3340 2880 3120 b
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Example
Two 80 x 10 mm bars can be used for a 2820 A current with an IP y 31 and an ambient
temperature of 35°C around the switchboard.
Two 80 x 10 mm bars installed separately in two busbar compartments can be used for a 3200 A
current with an IP y 31 and an ambient temperature of 35°C around the switchboard.
Note: the values indicated above have been validated for PrismaSeT P Active switchboards.
I-18 TOC
Version : 14 - 15/12/2023
160E9200
PrismaSeT P Active - Additional information www.se.com
Electrical characteristics
Permissible current and selection of vertical busbar
The goal is to optimise busbar size according to the installation and
operating criteria.
Up to 1600 A
Linergy LGY section
Type of bars Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40 °C 45 °C 50 °C
IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
Linergy LGY 630 750 680 710 630 680 590 630 550 590 530 550 b
Linergy LGY 800 920 840 880 800 840 760 800 720 760 680 720 b
Linergy LGY 1000 1140 1040 1090 990 1040 950 990 900 950 850 900 b
Linergy LGY 1250 1410 1290 1350 1230 1290 1170 1230 1100 1170 1050 1100 b
Linergy LGY 1600 1800 1650 1720 1580 1650 1480 1580 1390 1480 1320 1390 b
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Up to 1600 A
Linergy BS bars, 5 mm thick
Up to 3200 A
Linergy BS bars, 10 mm thick
Version : 14 - 15/12/2023
160E9200 TOC I-19
PrismaSeT P Active - Additional information www.se.com
Electrical characteristics
ComPacT NS630b to NS1600
DD383537.eps
Vertical mounting
Front or rear connection
Top or bottom incoming
Vertical busbars on the left or right
Linergy LGY busbars
Using the data below, it is possible to determine the permissible current for a
prefabricated connection between a vertical ComPacT NS630b/NS1600, fixed or
withdrawable, and Linergy LGY busbars depending on the ambient temperature
around the switchboard and the IP value.
Fixed
Prefabricated connection
Device and cat. no. Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40 °C 45 °C 50 °C
IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
NS630b 3P cat. no. LVS04485 630 630 630 630 630 630 630 630 630 630 630 b
4P cat. no. LVS04486
NS800 3P cat. no. LVS04485 800 800 800 800 800 800 800 800 800 800 800 b
4P cat. no. LVS04486
NS1000 3P cat. no. LVS04485 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 b
4P cat. no. LVS04486
NS1250 3P cat. no. LVS04485 1250 1250 1250 1250 1250 1250 1250 1200 1250 1150 1200 b
4P cat. no. LVS04486
NS1600 3P cat. no. LVS04487 1600 1550 1600 1500 1550 1450 1500 1400 1450 1350 1400 b
4P cat. no. LVS04488
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Withdrawable
Prefabricated connection
Device and cat. no. Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40 °C 45 °C 50 °C
IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
NS630b 3P cat. no. LVS04477 630 630 630 630 630 630 630 630 630 630 630 b
4P cat. no. LVS04478
NS800 3P cat. no. LVS04477 800 800 800 800 800 800 800 800 800 800 800 b
4P cat. no. LVS04478
NS1000 3P cat. no. LVS04477 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 b
4P cat. no. LVS04478
NS1250 3P cat. no. LVS04477 1250 1250 1250 1250 1250 1250 1250 1200 1250 1150 1200
4P cat. no. LVS04478
NS1600 3P cat. no. LVS04491 1560 1480 1520 1430 1480 1380 1430 1330 1380 1280 1330 b
4P cat. no. LVS04492
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Example:
For a fixed ComPacT NS1600, 4P, where the ambient temperature around
the switchboard is 35°C and the IP > 31:
the maximum permissible current for the prefabricated connection (LVS04488) is 1450 A.
I-20 TOC
Version : 14 - 15/12/2023
160E9200
PrismaSeT P Active - Additional information www.se.com
Electrical characteristics
MasterPact MTZ106 to 16
Dd383666.eps
MasterPacT MTZ1 06 to 16
Vertical mounting
Front or rear connection
Top or bottom incoming
Vertical busbars on the left or right
Linergy LGY busbars
Using the data below, it is possible to determine the permissible current for a
prefabricated connection between a vertical MasterPact MTZ1 06/NT16, fixed or
drawout, and Linergy LGY busbars depending on the ambient temperature around
the switchboard and the IP value.
Fixed
Prefabricated connection
Device and cat. no. Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40 °C 45 °C 50 °C
IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
NT06 3P cat. no. LVS04475 630 630 630 630 630 630 630 630 630 630 630 b
& MTZ1 4P cat. no. LVS04476
NT08 3P cat. no. LVS04475 800 800 800 800 800 800 800 800 800 800 800 b
& MTZ1 4P cat. no. LVS04476
NT10 3P cat. no. LVS04475 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 b
& MTZ1 4P cat. no. LVS04476
NT12 3P cat. no. LVS04475 1250 1250 1250 1250 1250 1250 1250 1200 1250 1150 1200 b
& MTZ1 4P cat. no. LVS04476
NT16 3P cat. no. LVS04489 1600 1570 1600 1520 1570 1470 1520 1420 1470 1370 1420 b
& MTZ1 4P cat. no. LVS04490
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Withdrawable
Prefabricated connection
Device and cat. no. Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40 °C 45 °C 50 °C
IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
NT06
& MTZ1
3P cat. no. LVS04477 630
4P cat. no. LVS04478
630 630 630 630 630 630 630 630 630 630 b
I
NT08 3P cat. no. LVS04477 800 800 800 800 800 800 800 800 800 800 800 b
& MTZ1 4P cat. no. LVS04478
NT10 3P cat. no. LVS04477 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 b
& MTZ1 4P cat. no. LVS04478
NT12 3P cat. no. LVS04477 1250 1250 1250 1250 1250 1250 1250 1200 1250 1150 1200 b
& MTZ1 4P cat. no. LVS04478
NT16 3P cat. no. LVS04491 1560 1480 1520 1430 1480 1380 1430 1330 1380 1280 1330 b
& MTZ1 4P cat. no. LVS04492
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Example:
For a drawout MasterPact MTZ1 16 , 4P, where the ambient temperature around the switchboard
is 35°C and the IP > 31: the maximum permissible current for the prefabricated connection
(LVS04492) is 1380 A.
Note: the values indicated above have been validated for PrismaSeT P Active switchboards.
Version : 14 - 15/12/2023
160E9200 TOC I-21
PrismaSeT P Active - Additional information www.se.com
Electrical characteristics
ComPacT NS630b à NS1000
Dd383538.eps
Horizontal mounting
Front or rear connection
Left or right incoming
Linergy LGY vertical busbars
Using the data below, it is possible to determine the permissible current for a
prefabricated connection between a horizontal ComPacT NS630b/NS1600, fixed
or withdrawable, and Linergy LGY busbars depending on the ambient temperature
around the switchboard and the IP value.
Fixed
Prefabricated connection
Device and cat. no. Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40 °C 45 °C 50 °C
IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
NS630b 3P cat. no. LVS04473 630 630 630 630 630 630 630 630 630 630 630 b
4P cat. no. LVS04474
NS800 3P cat. no. LVS04473 800 800 800 800 800 800 800 800 800 800 800 b
4P cat. no. LVS04474
NS1000 3P cat. no. LVS04473 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 b
4P cat. no. LVS04474
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Note: the values indicated above have been validated for PrismaSeT P Active switchboards.
I-22 TOC
Version : 14 - 15/12/2023
160E9200
PrismaSeT P Active - Additional information www.se.com
Electrical characteristics
MasterPact MTZ208 to 16
DD385984.eps
MasterPacT MTZ2 08 to 16
Fixed
Vertical busbars on the left or right
Linergy LGY, BS busbars
Connections drawings supplied by
Schneider Electric
1 Liaison
2 Horizontal link.
Using the data below, it is possible to determine the size of the copper bars and
the maximum permissible currents when making the connections to busbars for a
vertical, fixed MasterPacT NW08/16, front or rear connection, taking into account the
ambient temperature around the switchboard and the IP value.
Connection
Flat bars, 5 mm thick
Device Permissible current (A)
Ambient temperature around the switchboard (1)
25 °C 30 °C 35 °C 40 °C 45 °C 50 °C
IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
NW08 & Size per phase 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 b
MTZ2 I (A) 800 800 800 800 800 800 800 800 800 800 800
NW10 & Size per phase 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 b
MTZ2 I (A) 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
NW12 & Size per phase 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 b
MTZ2 I (A) 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250
NW16 & Size per phase 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 b
MTZ2 I (A) 1600 1600 1600 1570 1600 1520 1570 1470 1520 1420 1470
Horizontal link
Flat bars, 5 mm thick
Device Permissible current (A)
I
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40 °C 45 °C 50 °C
IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
NW08 & Size per phase 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 b
MTZ2 I (A) 800 800 800 800 800 800 800 800 800 800 800
NW10 & Size per phase 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 b
MTZ2 I (A) 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
NW12 & Size per phase 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 b
MTZ2 I (A) 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250
NW16 & Size per phase 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 b
MTZ2 I (A) 1600 1600 1600 1570 1600 1520 1570 1470 1520 1420 1470
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
(1) In the case of a door mounted at the rear of cubicle, add 10 °C.
Note: the values indicated above have been validated for PrismaSeT P Active switchboards.
Version : 14 - 15/12/2023
160E9200 TOC I-23
PrismaSeT P Active - Additional information www.se.com
Electrical characteristics
MasterPact MTZ208 to 32
DD385985.eps
MasterPacT MTZ2 08 to 32
Fixed
Vertical busbars on the left or right
Linergy LGYE, LGY, BS busbars
Connections drawings supplied by
Schneider Electric
1 Connection.
2 Horizontal link.
Using the data below, it is possible to determine the size of the copper bars and
the maximum permissible currents when making the connections to busbars for a
vertical, fixed MasterPact MTZ2 08/32, front or rear connection, taking into account
the ambient temperature around the switchboard and the IP value.
Connection
Flat bars, 10 mm thick
Device Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40 °C 45 °C 50 °C
IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
NW08 & Size per phase 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 b
MTZ2 I (A) 800 800 800 800 800 800 800 800 800 800 800
NW10 & Size per phase 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 b
MTZ2 I (A) 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
NW12 & Size per phase 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 b
MTZ2 I (A) 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250
NW16 & Size per phase 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 b
MTZ2 I (A) 1600 1600 1600 1570 1600 1520 1570 1470 1520 1420 1470
NW20 & Size per phase 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 b
MTZ2 I (A) 2000 2000 2000 2000 2000 2000 2000 1950 2000 1900 1950
NW25 & Size per phase 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 b
MTZ2 I (A) 2500 2500 2500 2500 2500 2460 2500 2380 2500 2300 2460
NW32 & Size per phase 3b 80 x 10 3b 80 x 10 3b 80 x 10 3b 80 x 10 3b 80 x 10 3b 80 x 10 3b 80 x 10 3b 80 x 10 3b 80 x 10 3b 80 x 10 3b 80 x 10 b
MTZ2 I (A) 3200 3000 3170 2910 3080 2820 3000 2730 2910 2630 2820
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Horizontal link
Flat bars, 10 mm thick
Device Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40 °C 45 °C 50 °C
IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
NW08 & Size per phase 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 b
MTZ2 I (A) 800 800 800 800 800 800 800 800 800 800 800
NW10 & Size per phase 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 b
MTZ2 I (A) 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
NW12 & Size per phase 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 b
MTZ2 I (A) 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250
NW16 & Size per phase 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 b
MTZ2 I (A) 1600 1600 1600 1570 1600 1520 1570 1470 1520 1420 1470
NW20 & Size per phase 2b 60 x 10 2b 60 x 10 2b 60 x 10 2b 60 x 10 2b 60 x 10 2b 60 x 10 2b 60 x 10 2b 60 x 10 2b 60 x 10 2b 60 x 10 2b 60 x 10 b
MTZ2 I (A) 2000 2000 2000 2000 2000 2000 2000 1950 2000 1900 1950
NW25 & Size per phase 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 b
MTZ2 I (A) 2500 2500 2500 2500 2500 2460 2500 2380 2500 2300 2460
NW32 & Size per phase 2b 100 x10 2b 100 x10 2b 100 x10 2b 100 x10 2b 100 x10 2b 100 x10 2b 100 x10 2b 100 x10 2b 100 x10 2b 100 x10 2b 100 x10 b
MTZ2 I (A) 3200 3000 3170 2910 3080 2820 3000 2730 2910 2630 2820
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Note: the values indicated above have been validated for PrismaSeT P Active switchboards.
I-24 TOC
Version : 14 - 15/12/2023
160E9200
PrismaSeT P Active - Additional information www.se.com
Electrical characteristics
MasterPact MTZ208 to 16
DD385986.eps
MasterPacT MTZ2 08 to 16
Drawout
Vertical busbars on the left or right
Linergy LGY, BS busbars
Connections drawings supplied by
Schneider Electric
1 Connection.
2 Horizontal link.
Using the data below, it is possible to determine the size of the copper bars and
the maximum permissible currents when making the connections to busbars for
a vertical, drawout MasterPact MTZ2 08/16, front or rear connection, taking into
account the ambient temperature around the switchboard and the IP value.
Connection
Flat bars, 5 mm thick
Device Permissible current (A)
Ambient temperature around the switchboard (1)
25 °C 30 °C 35 °C 40 °C 45 °C 50 °C
IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
NW08 & Size per phase 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 b
MTZ2 I (A) 800 800 800 800 800 800 800 800 800 800 800
NW10 & Size per phase 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 b
MTZ2 I (A) 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
NW12 & Size per phase 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 b
MTZ2 I (A) 1250 1250 1250 1250 1250 1230 1250 1200 1230 1160 1200
NW16 & Size per phase 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 b
MTZ2 I (A) 1560 1480 1520 1430 1480 1380 1430 1330 1380 1280 1330
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Horizontal link
Flat bars, 5 mm thick
Device Permissible current (A)
Ambient temperature around the switchboard
I
25 °C 30 °C 35 °C 40 °C 45 °C 50 °C
IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
NW08 & Size per phase 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 b
MTZ2 I (A) 800 800 800 800 800 800 800 800 800 800 800
NW10 & Size per phase 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 b
MTZ2 I (A) 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
NW12 & Size per phase 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 b
MTZ2 I (A) 1250 1250 1250 1250 1250 1230 1250 1200 1230 1160 1200
NW16 & Size per phase 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 b
MTZ2 I (A) 1560 1480 1520 1430 1480 1380 1430 1330 1380 1280 1330
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
(1) In the case of a door mounted at the rear of cubicle, add 10 °C.
Note: the values indicated above have been validated for PrismaSeT P Active switchboards.
Version : 14 - 15/12/2023
160E9200 TOC I-25
PrismaSeT P Active - Additional information www.se.com
Electrical characteristics
MasterPact MTZ208 to 32
DD385987.eps
MasterPacT MTZ2 08 to 32
Drawout
Vertical busbars on the left or right
Linergy LGYE, LGY, BS busbars
Connections drawings supplied by
Schneider Electric
1 Connection.
2 Horizontal link.
Using the data below, it is possible to determine the size of the copper bars and
the maximum permissible currents when making the connections to busbars for
a vertical, drawout MasterPact MTZ2 08/32, front or rear connection, taking into
account the ambient temperature around the switchboard and the IP value.
Connection
Flat bars, 10 mm thick
Device Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40 °C 45 °C 50 °C
IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
NW08 & Size per phase 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 b
MTZ2 I (A) 800 800 800 800 800 800 800 800 800 800 800
NW10 & Size per phase 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 b
MTZ2 I (A) 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
NW12 & Size per phase 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 b
MTZ2 I (A) 1250 1250 1250 1210 1250 1180 1210 1140 1180 1100 1140
NW16 & Size per phase 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 b
MTZ2 I (A) 1560 1480 1520 1430 1480 1380 1430 1330 1380 1280 1330
NW20 & Size per phase 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 b
MTZ2 I (A) 2000 2000 2000 1950 2000 1900 1950 1830 1900 1760 1830
NW25 & Size per phase 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 b
MTZ2 I (A) 2470 2280 2410 2210 2350 2140 2280 2070 2210 2000 2140
NW32 & Size per phase 3b 80 x 10 3b 80 x 10 3b 80 x 10 3b 80 x 10 3b 80 x 10 3b 80 x 10 3b 80 x 10 3b 80 x 10 3b 80 x 10 3b 80 x 10 3b 80 x 10 b
MTZ2 I (A) 2960 2730 2890 2630 2820 2530 2730 2450 2630 2370 2530
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Horizontal link
Flat bars, 10 mm thick
Device Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40 °C 45 °C 50 °C
IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
NW08 & Size per phase 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 b
MTZ2 I (A) 800 800 800 800 800 800 800 800 800 800 800
NW10 & Size per phase 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 b
MTZ2 I (A) 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
NW12 & Size per phase 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 b
MTZ2 I (A) 1250 1250 1250 1210 1250 1180 1210 1140 1180 1100 1140
NW16 & Size per phase 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 b
MTZ2 I (A) 1560 1480 1520 1430 1480 1380 1430 1330 1380 1280 1330
NW20 & Size per phase 2b 60 x 10 2b 60 x 10 2b 60 x 10 2b 60 x 10 2b 60 x 10 2b 60 x 10 2b 60 x 10 2b 60 x 10 2b 60 x 10 2b 60 x 10 2b 60 x 10 b
MTZ2 I (A) 2000 2000 2000 1950 2000 1900 1950 1830 1900 1760 1830
NW25 & Size per phase 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 b
MTZ2 I (A) 2470 2280 2410 2210 2350 2140 2280 2070 2210 2000 2140
NW32 & Size per phase 2b 100 x10 2b 100 x10 2b 100 x10 2b 100 x10 2b 100 x10 2b 100 x10 2b 100 x10 2b 100 x10 2b 100 x10 2b 100 x10 2b 100 x10 b
MTZ2 I (A) 2960 2730 2890 2630 2820 2530 2730 2450 2630 2370 2530
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Note: the values indicated above have been validated for PrismaSeT P Active switchboards.
I-26 TOC
Version : 14 - 15/12/2023
160E9200
PrismaSeT P Active - Additional information www.se.com
DD385988.eps
MasterPacT MTZ2 08 to 32
Fixed
Dedicated cubicle
Linergy LGYE, BS busbars
Connections drawings supplied by
Schneider Electric
Connection
Flat bars, 10 mm thick
Device Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40 °C 45 °C 50 °C
IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
NW08 & Size per phase 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 b
MTZ2 I (A) 800 800 800 800 800 800 800 800 800 800 800
NW10 & Size per phase 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 b
MTZ2 I (A) 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
NW12 & Size per phase 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 b
MTZ2 I (A) 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250
NW16 & Size per phase 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 b
MTZ2 I (A) 1600 1600 1600 1570 1600 1520 1570 1470 1520 1420 1470
NW20 & Size per phase 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 b
MTZ2 I (A) 2000 2000 2000 2000 2000 2000 2000 1950 2000 1900 1950
NW25 & Size per phase 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 b
MTZ2 I (A) 2500 2500 2500 2500 2500 2460 2500 2380 2500 2300 2460
NW32 & Size per phase 3b 80 x 10 3b 80 x 10 3b 80 x 10 3b 80 x 10 3b 80 x 10 3b 80 x 10 3b 80 x 10
MTZ2 I (A) 3200 3000 3170 2910 3080 2820 3000
3b 80 x 10
2730
3b 80 x 10
2910
3b 80 x 10
2630
3b 80 x 10
2820
b
I
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Note: contact Schneider Electric for 4000 A dedicated cubicle
Version : 14 - 15/12/2023
160E9200 TOC I-27
PrismaSeT P Active - Additional information www.se.com
DD385989.eps
MasterPact MTZ2 08 to 32
Drawout
Dedicated cubicle
Linergy LGYE, BS busbars
Connections drawings supplied by
Schneider Electric
Connection
Flat bars, 10 mm thick
Device Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40 °C 45 °C 50 °C
IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
NW08 & Size per phase 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 b
MTZ2 I (A) 800 800 800 800 800 800 800 800 800 800 800
NW10 & Size per phase 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 b
MTZ2 I (A) 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
NW12 & Size per phase 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 b
MTZ2 I (A) 1250 1250 1250 1210 1250 1180 1210 1140 1180 1100 1140
NW16 & Size per phase 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 b
MTZ2 I (A) 1560 1480 1520 1430 1480 1380 1430 1330 1380 1280 1330
NW20 & Size per phase 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 b
MTZ2 I (A) 2000 2000 2000 1950 2000 1900 1950 1830 1900 1760 1830
NW25 & Size per phase 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 b
MTZ2 I (A) 2470 2280 2410 2210 2350 2140 2280 2070 2210 2000 2140
NW32 & Size per phase 3b 80 x 10 3b 80 x 10 3b 80 x 10 3b 80 x 10 3b 80 x 10 3b 80 x 10 3b 80 x 10 3b 80 x 10 3b 80 x 10 3b 80 x 10 3b 80 x 10 b
MTZ2 I (A) 2960 2730 2890 2630 2820 2530 2730 2450 2630 2370 2530
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Note: contact Schneider Electric for 4000 A dedicated cubicle
I-28 TOC
Version : 14 - 15/12/2023
160E9300
PrismaSeT P Active - Additional information www.se.com
Electrical characteristics
Permissible current and selection of Linergy LGYE busbars
Up to 4000 A
Linergy LGYE section
Type of bars Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40 °C 45 °C 50 °C
Size per phase IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
Linergy LGYE 630 680 580 650 550 630 530 590 500 550 470 520 b
Linergy LGYE 800 860 740 830 710 800 680 750 630 700 600 660 b
Linergy LGYE 1000 1080 920 1040 884 1000 850 940 790 880 750 830 b
Linergy LGYE 1250 1350 1150 1300 1100 1250 1050 1170 1000 1100 930 1020 b
Linergy LGYE 1600 1730 1580 1690 1530 1650 1480 1550 1380 1450 1300 1350 b
Linergy LGYE 2000 2200 1810 2100 1730 2000 1650 1900 1560 1810 1480 1720 b
Linergy LGYE 2500 2640 2230 2540 2160 2440 2100 2310 2000 2240 1930 2120 b
Linergy LGYE 3200 3400 3020 3300 2900 3200 2800 3040 2660 2890 2520 2750 b
Linergy LGYE 4000 3800 3510 3710 3430 3620 3350 3450 3180 3280 3020 3120 b
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
DD384545.eps
DD384546.eps
DD384547.eps
DD384548.eps
DD384549.eps
Section 630 A. Section 800 A. Section 1000 A. Section 1250 A. Section 1600 A.
Cat. No. LVS04560. Cat. No. LVS04561. Cat. No. LVS04562. Cat. No. LVS04563. Cat. No. LVS04564.
DD384550.eps
DD384551.eps
DD384552.eps
DD384553.eps
Version : 14 - 15/12/2023
160E9300 TOC I-29
PrismaSeT P Active - Additional information www.se.com
Electrical characteristics
Permissible current and selection of horizontal busbar
The goal is to optimise busbar size according to the installation and operating criteria.
Up to 1600 A
Linergy BS bars, 5 mm thick
Type of bars Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40 °C 45 °C 50 °C
Size per phase IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
1 Linergy BS bar, 60 x 5 890 840 850 790 800 750 760 700 710 650 660 b
1 Linergy BS bar, 80 x 5 1130 1050 1080 990 1000 900 970 870 910 810 860 b
2 Linergy BS bars, 60 x 5 1580 1420 1500 1350 1400 1250 1350 1180 1260 1090 1180 b
2 Linergy BS bars, 80 x 5 2010 1820 1920 1720 1800 1600 1720 1510 1610 1390 1510 b
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Up to 3200 A
Linergy BS bars, 10 mm thick
Type of bars Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40 °C 45 °C 50 °C
Size per phase IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
1 Linergy BS bar, 50 x 10 1330 1220 1260 1160 1200 1080 1130 1010 1060 940 990 b
1 Linergy BS bar, 60 x 10 1550 1400 1470 1320 1400 1250 1320 1160 1240 1070 1160 b
1 Linergy BS bar, 80 x 10 1990 1800 1890 1700 1800 1600 1700 1500 1600 1390 1500 b
2 Linergy BS bars, 50 x 10 2270 2090 2160 1980 2050 1850 1930 1740 1810 1610 1690 b
2 Linergy BS bars, 60 x 10 2550 2270 2420 2140 2300 2000 2170 1870 2030 1720 1900 b
2 Linergy BS bars, 80 x 10 3110 2820 2970 2660 2820 2500 2660 2330 2500 2160 2330 b
2 Linergy BS bars, 100 x 10 3650 3280 3490 3100 3300 2900 3130 2720 2950 2510 2750 b
2 Linergy BS bars, 120 x 10 4160 3760 3960 3550 3760 3340 3560 3100 3340 2880 3120 b
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Example:
Two 50 x 10 mm bars can be used for a 2160 A current with an IP y 31 and an ambient temperature
of 30 °C around the switchboard.
Where possible, use of 10 mm bars is worthwhile in terms of the In/Isc:
b gain in time during switchboard mounting given, where applicable, the lesser number of bars
installed
b for short-circuits, the rigidity of the bars means fewer busbar supports.
Recommendation:
Use 5 mm bars for In y 1600 A and low Icw values (40 kA rms).
Use 10 mm bars for In > 1600 A and medium to high Icw values (> 40 kA rms).
Note: the values indicated above have been validated for PrismaSeT P Active switchboards.
I-30 TOC
Version : 14 - 15/12/2023
160E9300
PrismaSeT P Active - Additional information www.se.com
Electrical characteristics
Permissible current and selection of Linergy LGY busbars
The goal is to optimise busbar size according to the installation and operating criteria.
Up to 3200 A
Linergy LGY section
Type of bars Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40 °C 45 °C 50 °C
IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
Linergy LGY 630 750 680 710 630 680 590 630 550 590 530 550 b
Linergy LGY 800 920 840 880 800 840 760 800 720 760 680 720 b
Linergy LGY 1000 1140 1040 1090 990 1040 950 990 900 950 850 900 b
Linergy LGY 1250 1410 1290 1350 1230 1290 1170 1230 1100 1170 1050 1100 b
Linergy LGY 1600 1800 1650 1720 1580 1650 1480 1580 1390 1480 1320 1390 b
Linergy LGY 2000 (2 x 1000) 2200 2000 2100 1900 2000 1820 1900 1720 1820 1620 1720 b
Linergy LGY 2500 (2 x 1250) 2740 2500 2620 2380 2500 2260 2380 2120 2260 2020 2120 b
Linergy LGY 3200 (2 x 1600) 3480 3200 3340 3060 3200 2920 3060 2780 2920 2640 2780 b
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Example:
A Linergy LGY channelled bar can be used for a 1650 A current with an IP y 31 and an ambient temperature around the switchboard of 35 °C.
DD381233.eps
DD381234.eps
DD381235.eps
DD385507.eps
Section 1600 A.
Cat. No. LVS04506.
Note: the values indicated above have been validated for PrismaSeT P Active switchboards.
Version : 14 - 15/12/2023
160E9300 TOC I-31
PrismaSeT P Active - Additional information www.se.com
Electrical characteristics
Permissible current and selection of Linergy LGYE busbars
Up to 4000 A
Linergy LGYE section
Type of bars Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40 °C 45 °C 50 °C
Size per phase IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
Linergy LGYE 630 680 580 650 550 630 530 590 500 550 470 520 b
Linergy LGYE 800 860 740 830 710 800 680 750 630 700 600 660 b
Linergy LGYE 1000 1080 920 1040 884 1000 850 940 790 880 750 830 b
Linergy LGYE 1250 1350 1150 1300 1100 1250 1050 1170 1000 1100 930 1020 b
Linergy LGYE 1600 1730 1580 1690 1530 1650 1480 1550 1380 1450 1300 1350 b
Linergy LGYE 2000 2200 1810 2100 1730 2000 1650 1900 1560 1810 1480 1720 b
Linergy LGYE 2500 2640 2230 2540 2160 2440 2100 2310 2000 2240 1930 2120 b
Linergy LGYE 3200 3400 3020 3300 2900 3200 2800 3040 2660 2890 2520 2750 b
Linergy LGYE 4000 3800 3510 3710 3430 3620 3350 3450 3180 3280 3020 3120 b
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
DD384545.eps
DD384546.eps
DD384547.eps
DD384548.eps
DD384549.eps
Section Section 800 A. Section 1000 A. Section 1250 A. Section 1600 A.
630 A. Cat. No. LVS04561. Cat. No. LVS04562. Cat. No. LVS04563. Cat. No. LVS04564.
Cat. No. LVS04560.
DD384550.eps
DD384551.eps
DD384552.eps
DD384553.eps
I-32 TOC
Version : 14 - 15/12/2023
160E9300
PrismaSeT P Active - Additional information www.se.com
Electrical characteristics
Permissible current and selection of vertical busbar
The goal is to optimise busbar size according to the installation and operating criteria.
Up to 1600 A
Linergy BS bars, 5 mm thick
Type of bars Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40 °C 45 °C 50 °C
Size per phase IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
1 Linergy BS bar, 60 x 5 890 840 850 790 800 750 760 700 710 650 660 b
1 Linergy BS bar, 80 x 5 1130 1050 1080 990 1000 900 970 870 910 810 860 b
2 Linergy BS bars, 60 x 5 1580 1420 1500 1350 1400 1250 1350 1180 1260 1090 1180 b
2 Linergy BS bars, 80 x 5 2010 1820 1920 1720 1800 1600 1720 1510 1610 1390 1510 b
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Up to 3200 A
Linergy BS bars, 10 mm thick
Type of bars Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40 °C 45 °C 50 °C
Size per phase IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
1 Linergy BS bar, 50 x 10 1330 1220 1260 1160 1200 1080 1130 1010 1060 940 990 b
1 Linergy BS bar, 60 x 10 1550 1400 1470 1320 1400 1250 1320 1160 1240 1070 1160 b
1 Linergy BS bar, 80 x 10 1990 1800 1890 1700 1800 1600 1700 1500 1600 1390 1500 b
1 Linergy BS bar, 100 x 10 2370 2150 2260 2030 2150 1900 2030 1780 1900 1650 1780 b
2 Linergy BS bars, 50 x 10 2270 2090 2160 1980 2050 1850 1930 1740 1810 1610 1690 b
2 Linergy BS bars, 60 x 10 2550 2270 2420 2140 2300 2000 2170 1870 2030 1720 1900 b
2 Linergy BS bars, 80 x 10 3110 2820 2970 2660 2820 2500 2660 2330 2500 2160 2330 b
2 x 1 Linergy BS bar, 80 x 10 3540 3200 3370 3020 3200 2820 3020 2650 2840 2450 2650 b
2 Linergy BS bars, 100 x 10 3650 3280 3490 3100 3300 2900 3130 2720 2950 2510 2750 b
2 Linergy BS bars, 120 x 10 4160 3760 3960 3550 3760 3340 3560 3100 3340 2880 3120 b
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Example
Two 80 x 10 mm bars can be used for a 2820 A current with an IP y 31 and an ambient
temperature of 35°C around the switchboard.
Two 80 x 10 mm bars installed separately in two busbar compartments can be used for a 3200 A
current with an IP y 31 and an ambient temperature of 35°C around the switchboard.
Note: the values indicated above have been validated for PrismaSeT P Active switchboards.
Version : 14 - 15/12/2023
160E9300 TOC I-33
PrismaSeT P Active - Additional information www.se.com
Electrical characteristics
Permissible current and selection of vertical busbar
The goal is to optimise busbar size according to the installation and
operating criteria.
Up to 1600 A
Linergy LGY section
Type of bars Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40 °C 45 °C 50 °C
IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
Linergy LGY 630 750 680 710 630 680 590 630 550 590 530 550 b
Linergy LGY 800 920 840 880 800 840 760 800 720 760 680 720 b
Linergy LGY 1000 1140 1040 1090 990 1040 950 990 900 950 850 900 b
Linergy LGY 1250 1410 1290 1350 1230 1290 1170 1230 1100 1170 1050 1100 b
Linergy LGY 1600 1800 1650 1720 1580 1650 1480 1580 1390 1480 1320 1390 b
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Up to 1600 A
Linergy BS bars, 5 mm thick
Up to 3200 A
Linergy BS bars, 10 mm thick
Note: the values indicated above have been validated for PrismaSeT P Active switchboards.
I-34 TOC
Version : 14 - 15/12/2023
160E9300
PrismaSeT P Active - Additional information www.se.com
Electrical characteristics
ComPacT NS630b to NS1600
DD383537.eps
Vertical mounting
Front or rear connection
Top or bottom incoming
Vertical busbars on the left or right
Linergy LGY busbars
Using the data below, it is possible to determine the permissible current for a
prefabricated connection between a vertical ComPacT NS630b/NS1600, fixed or
withdrawable, and Linergy LGY busbars depending on the ambient temperature
around the switchboard and the IP value.
Fixed
Prefabricated connection
Device and cat. no. Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40 °C 45 °C 50 °C
IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
NS630b 3P cat. no. LVS04485 630 630 630 630 630 630 630 630 630 630 630 b
4P cat. no. LVS04486
NS800 3P cat. no. LVS04485 800 800 800 800 800 800 800 800 800 800 800 b
4P cat. no. LVS04486
NS1000 3P cat. no. LVS04485 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 b
4P cat. no. LVS04486
NS1250 3P cat. no. LVS04485 1250 1250 1250 1250 1250 1250 1250 1200 1250 1150 1200 b
4P cat. no. LVS04486
NS1600 3P cat. no. LVS04487 1600 1550 1600 1500 1550 1450 1500 1400 1450 1350 1400 b
4P cat. no. LVS04488
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Withdrawable
Prefabricated connection
Device and cat. no. Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40 °C 45 °C 50 °C
IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
NS630b 3P cat. no. LVS04477 630 630 630 630 630 630 630 630 630 630 630 b
4P cat. no. LVS04478
NS800 3P cat. no. LVS04477 800
4P cat. no. LVS04478
800 800 800 800 800 800 800 800 800 800 b
I
NS1000 3P cat. no. LVS04477 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 b
4P cat. no. LVS04478
NS1250 3P cat. no. LVS04477 1250 1250 1250 1250 1250 1250 1250 1200 1250 1150 1200
4P cat. no. LVS04478
NS1600 3P cat. no. LVS04491 1560 1480 1520 1430 1480 1380 1430 1330 1380 1280 1330 b
4P cat. no. LVS04492
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Example:
For a fixed ComPacT NS1600, 4P, where the ambient temperature around
the switchboard is 35°C and the IP > 31:
the maximum permissible current for the prefabricated connection (LVS04488) is 1450 A.
Version : 14 - 15/12/2023
160E9300 TOC I-35
PrismaSeT P Active - Additional information www.se.com
Electrical characteristics
MasterPact MTZ106 to 16
Dd383666.eps
MasterPacT MTZ1 06 to 16
Vertical mounting
Front or rear connection
Top or bottom incoming
Vertical busbars on the left or right
Linergy LGY busbars
Using the data below, it is possible to determine the permissible current for a
prefabricated connection between a vertical MasterPact MTZ1 06/NT16, fixed or
drawout, and Linergy LGY busbars depending on the ambient temperature around
the switchboard and the IP value.
Fixed
Prefabricated connection
Device and cat. no. Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40 °C 45 °C 50 °C
IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
NT06 3P cat. no. LVS04475 630 630 630 630 630 630 630 630 630 630 630 b
& MTZ1 4P cat. no. LVS04476
NT08 3P cat. no. LVS04475 800 800 800 800 800 800 800 800 800 800 800 b
& MTZ1 4P cat. no. LVS04476
NT10 3P cat. no. LVS04475 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 b
& MTZ1 4P cat. no. LVS04476
NT12 3P cat. no. LVS04475 1250 1250 1250 1250 1250 1250 1250 1200 1250 1150 1200 b
& MTZ1 4P cat. no. LVS04476
NT16 3P cat. no. LVS04489 1600 1570 1600 1520 1570 1470 1520 1420 1470 1370 1420 b
& MTZ1 4P cat. no. LVS04490
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Withdrawable
Prefabricated connection
Device and cat. no. Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40 °C 45 °C 50 °C
IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
NT06 3P cat. no. LVS04477 630 630 630 630 630 630 630 630 630 630 630 b
& MTZ1 4P cat. no. LVS04478
NT08 3P cat. no. LVS04477 800 800 800 800 800 800 800 800 800 800 800 b
& MTZ1 4P cat. no. LVS04478
NT10 3P cat. no. LVS04477 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 b
& MTZ1 4P cat. no. LVS04478
NT12 3P cat. no. LVS04477 1250 1250 1250 1250 1250 1250 1250 1200 1250 1150 1200 b
& MTZ1 4P cat. no. LVS04478
NT16 3P cat. no. LVS04491 1560 1480 1520 1430 1480 1380 1430 1330 1380 1280 1330 b
& MTZ1 4P cat. no. LVS04492
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Example:
For a drawout MasterPact MTZ1 16 , 4P, where the ambient temperature around the switchboard
is 35°C and the IP > 31: the maximum permissible current for the prefabricated connection
(LVS04492) is 1380 A.
Note: the values indicated above have been validated for PrismaSeT P Active switchboards.
I-36 TOC
Version : 14 - 15/12/2023
160E9300
PrismaSeT P Active - Additional information www.se.com
Electrical characteristics
ComPacT NS630b à NS1000
Dd383538.eps
Horizontal mounting
Front or rear connection
Left or right incoming
Linergy LGY vertical busbars
Using the data below, it is possible to determine the permissible current for a
prefabricated connection between a horizontal ComPacT NS630b/NS1600, fixed
or withdrawable, and Linergy LGY busbars depending on the ambient temperature
around the switchboard and the IP value.
Fixed
Prefabricated connection
Device and cat. no. Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40 °C 45 °C 50 °C
IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
NS630b 3P cat. no. LVS04473 630 630 630 630 630 630 630 630 630 630 630 b
4P cat. no. LVS04474
NS800 3P cat. no. LVS04473 800 800 800 800 800 800 800 800 800 800 800 b
4P cat. no. LVS04474
NS1000 3P cat. no. LVS04473 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 b
4P cat. no. LVS04474
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Note: the values indicated above have been validated for PrismaSeT P Active switchboards.
Version : 14 - 15/12/2023
160E9300 TOC I-37
PrismaSeT P Active - Additional information www.se.com
Electrical characteristics
MasterPact MTZ208 to 16
DD385984.eps
MasterPacT MTZ2 08 to 16
Fixed
Vertical busbars on the left or right
Linergy LGY, BS busbars
Connections drawings supplied by
Schneider Electric
1 Liaison
2 Horizontal link.
Using the data below, it is possible to determine the size of the copper bars and
the maximum permissible currents when making the connections to busbars for a
vertical, fixed MasterPacT NW08/16, front or rear connection, taking into account the
ambient temperature around the switchboard and the IP value.
Connection
Flat bars, 5 mm thick
Device Permissible current (A)
Ambient temperature around the switchboard (1)
25 °C 30 °C 35 °C 40 °C 45 °C 50 °C
IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
NW08 & Size per phase 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 b
MTZ2 I (A) 800 800 800 800 800 800 800 800 800 800 800
NW10 & Size per phase 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 b
MTZ2 I (A) 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
NW12 & Size per phase 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 b
MTZ2 I (A) 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250
NW16 & Size per phase 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 b
MTZ2 I (A) 1600 1600 1600 1570 1600 1520 1570 1470 1520 1420 1470
Horizontal link
Flat bars, 5 mm thick
Device Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40 °C 45 °C 50 °C
IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
NW08 & Size per phase 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 b
MTZ2 I (A) 800 800 800 800 800 800 800 800 800 800 800
NW10 & Size per phase 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 b
MTZ2 I (A) 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
NW12 & Size per phase 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 b
MTZ2 I (A) 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250
NW16 & Size per phase 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 b
MTZ2 I (A) 1600 1600 1600 1570 1600 1520 1570 1470 1520 1420 1470
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
(1) In the case of a door mounted at the rear of cubicle, add 10 °C.
Note: the values indicated above have been validated for PrismaSeT P Active switchboards.
I-38 TOC
Version : 14 - 15/12/2023
160E9300
PrismaSeT P Active - Additional information www.se.com
Electrical characteristics
MasterPact MTZ208 to 32
DD385985.eps
MasterPacT MTZ2 08 to 32
Fixed
Vertical busbars on the left or right
Linergy LGYE, LGY, BS busbars
Connections drawings supplied by
Schneider Electric
1 Connection.
2 Horizontal link.
Using the data below, it is possible to determine the size of the copper bars and
the maximum permissible currents when making the connections to busbars for a
vertical, fixed MasterPact MTZ2 08/32, front or rear connection, taking into account
the ambient temperature around the switchboard and the IP value.
Connection
Flat bars, 10 mm thick
Device Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40 °C 45 °C 50 °C
IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
NW08 & Size per phase 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 b
MTZ2 I (A) 800 800 800 800 800 800 800 800 800 800 800
NW10 & Size per phase 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 b
MTZ2 I (A) 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
NW12 & Size per phase 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 b
MTZ2 I (A) 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250
NW16 & Size per phase 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 b
MTZ2 I (A) 1600 1600 1600 1570 1600 1520 1570 1470 1520 1420 1470
NW20 & Size per phase 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 b
MTZ2 I (A) 2000 2000 2000 2000 2000 2000 2000 1950 2000 1900 1950
NW25 & Size per phase 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 b
MTZ2 I (A) 2500 2500 2500 2500 2500 2460 2500 2380 2500 2300 2460
NW32 & Size per phase 3b 80 x 10 3b 80 x 10 3b 80 x 10 3b 80 x 10 3b 80 x 10 3b 80 x 10 3b 80 x 10 3b 80 x 10 3b 80 x 10 3b 80 x 10 3b 80 x 10 b
MTZ2 I (A) 3200 3000 3170 2910 3080 2820 3000 2730 2910 2630 2820
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Horizontal link
Flat bars, 10 mm thick
Device Permissible current (A)
Ambient temperature around the switchboard
25 °C
IP y 31 IP > 31
30 °C
IP y 31 IP > 31
35 °C
IP y 31 IP > 31
40 °C
IP y 31 IP > 31
45 °C
IP y 31 IP > 31
50 °C
IP y 31 IP > 31
I
NW08 & Size per phase 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 b
MTZ2 I (A) 800 800 800 800 800 800 800 800 800 800 800
NW10 & Size per phase 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 b
MTZ2 I (A) 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
NW12 & Size per phase 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 b
MTZ2 I (A) 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250
NW16 & Size per phase 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 b
MTZ2 I (A) 1600 1600 1600 1570 1600 1520 1570 1470 1520 1420 1470
NW20 & Size per phase 2b 60 x 10 2b 60 x 10 2b 60 x 10 2b 60 x 10 2b 60 x 10 2b 60 x 10 2b 60 x 10 2b 60 x 10 2b 60 x 10 2b 60 x 10 2b 60 x 10 b
MTZ2 I (A) 2000 2000 2000 2000 2000 2000 2000 1950 2000 1900 1950
NW25 & Size per phase 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 b
MTZ2 I (A) 2500 2500 2500 2500 2500 2460 2500 2380 2500 2300 2460
NW32 & Size per phase 2b 100 x10 2b 100 x10 2b 100 x10 2b 100 x10 2b 100 x10 2b 100 x10 2b 100 x10 2b 100 x10 2b 100 x10 2b 100 x10 2b 100 x10 b
MTZ2 I (A) 3200 3000 3170 2910 3080 2820 3000 2730 2910 2630 2820
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Note: the values indicated above have been validated for PrismaSeT P Active switchboards.
Version : 14 - 15/12/2023
160E9300 TOC I-39
PrismaSeT P Active - Additional information www.se.com
Electrical characteristics
MasterPact MTZ208 to 16
DD385986.eps
MasterPacT MTZ2 08 to 16
Drawout
Vertical busbars on the left or right
Linergy LGY, BS busbars
Connections drawings supplied by
Schneider Electric
1 Connection.
2 Horizontal link.
Using the data below, it is possible to determine the size of the copper bars and
the maximum permissible currents when making the connections to busbars for
a vertical, drawout MasterPact MTZ2 08/16, front or rear connection, taking into
account the ambient temperature around the switchboard and the IP value.
Connection
Flat bars, 5 mm thick
Device Permissible current (A)
Ambient temperature around the switchboard (1)
25 °C 30 °C 35 °C 40 °C 45 °C 50 °C
IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
NW08 & Size per phase 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 b
MTZ2 I (A) 800 800 800 800 800 800 800 800 800 800 800
NW10 & Size per phase 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 b
MTZ2 I (A) 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
NW12 & Size per phase 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 b
MTZ2 I (A) 1250 1250 1250 1250 1250 1230 1250 1200 1230 1160 1200
NW16 & Size per phase 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 b
MTZ2 I (A) 1560 1480 1520 1430 1480 1380 1430 1330 1380 1280 1330
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Horizontal link
Flat bars, 5 mm thick
Device Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40 °C 45 °C 50 °C
IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
NW08 & Size per phase 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 b
MTZ2 I (A) 800 800 800 800 800 800 800 800 800 800 800
NW10 & Size per phase 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 b
MTZ2 I (A) 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
NW12 & Size per phase 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 b
MTZ2 I (A) 1250 1250 1250 1250 1250 1230 1250 1200 1230 1160 1200
NW16 & Size per phase 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 b
MTZ2 I (A) 1560 1480 1520 1430 1480 1380 1430 1330 1380 1280 1330
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
(1) In the case of a door mounted at the rear of cubicle, add 10 °C.
Note: the values indicated above have been validated for PrismaSeT P Active switchboards.
I-40 TOC
Version : 14 - 15/12/2023
160E9300
PrismaSeT P Active - Additional information www.se.com
Electrical characteristics
MasterPact MTZ208 to 32
DD385987.eps
MasterPacT MTZ2 08 to 32
Drawout
Vertical busbars on the left or right
Linergy LGYE, LGY, BS busbars
Connections drawings supplied by
Schneider Electric
1 Connection.
2 Horizontal link.
Using the data below, it is possible to determine the size of the copper bars and
the maximum permissible currents when making the connections to busbars for
a vertical, drawout MasterPact MTZ2 08/32, front or rear connection, taking into
account the ambient temperature around the switchboard and the IP value.
Connection
Flat bars, 10 mm thick
Device Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40 °C 45 °C 50 °C
IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
NW08 & Size per phase 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 b
MTZ2 I (A) 800 800 800 800 800 800 800 800 800 800 800
NW10 & Size per phase 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 b
MTZ2 I (A) 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
NW12 & Size per phase 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 b
MTZ2 I (A) 1250 1250 1250 1210 1250 1180 1210 1140 1180 1100 1140
NW16 & Size per phase 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 b
MTZ2 I (A) 1560 1480 1520 1430 1480 1380 1430 1330 1380 1280 1330
NW20 & Size per phase 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 b
MTZ2 I (A) 2000 2000 2000 1950 2000 1900 1950 1830 1900 1760 1830
NW25 & Size per phase 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 b
MTZ2 I (A) 2470 2280 2410 2210 2350 2140 2280 2070 2210 2000 2140
NW32 & Size per phase 3b 80 x 10 3b 80 x 10 3b 80 x 10 3b 80 x 10 3b 80 x 10 3b 80 x 10 3b 80 x 10 3b 80 x 10 3b 80 x 10 3b 80 x 10 3b 80 x 10 b
MTZ2 I (A) 2960 2730 2890 2630 2820 2530 2730 2450 2630 2370 2530
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Horizontal link
Flat bars, 10 mm thick
Device Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40 °C 45 °C 50 °C I
IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
NW08 & Size per phase 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 b
MTZ2 I (A) 800 800 800 800 800 800 800 800 800 800 800
NW10 & Size per phase 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 b
MTZ2 I (A) 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
NW12 & Size per phase 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 b
MTZ2 I (A) 1250 1250 1250 1210 1250 1180 1210 1140 1180 1100 1140
NW16 & Size per phase 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 b
MTZ2 I (A) 1560 1480 1520 1430 1480 1380 1430 1330 1380 1280 1330
NW20 & Size per phase 2b 60 x 10 2b 60 x 10 2b 60 x 10 2b 60 x 10 2b 60 x 10 2b 60 x 10 2b 60 x 10 2b 60 x 10 2b 60 x 10 2b 60 x 10 2b 60 x 10 b
MTZ2 I (A) 2000 2000 2000 1950 2000 1900 1950 1830 1900 1760 1830
NW25 & Size per phase 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 b
MTZ2 I (A) 2470 2280 2410 2210 2350 2140 2280 2070 2210 2000 2140
NW32 & Size per phase 2b 100 x10 2b 100 x10 2b 100 x10 2b 100 x10 2b 100 x10 2b 100 x10 2b 100 x10 2b 100 x10 2b 100 x10 2b 100 x10 2b 100 x10 b
MTZ2 I (A) 2960 2730 2890 2630 2820 2530 2730 2450 2630 2370 2530
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Note: the values indicated above have been validated for PrismaSeT P Active switchboards.
Version : 14 - 15/12/2023
160E9300 TOC I-41
PrismaSeT P Active - Additional information www.se.com
Electrical characteristics
Flexible copper bars Switchboards that comply with standard
with an insulating sheath IEC 61439-1/2
It is imperative to use the values indicated below that have been validated for the installation
of devices in PrismaSeT switchboards.
The parameters determining the size of flexible bars are:
b the environment in which the devices are installed:
v position in the enclosure
v dimensions of other conductors in the circuit
v ambient temperature around the switchboard
b the characteristics of the connected devices:
v device heat losses
v the type of installation (horizontal or vertical)
v the type of device (fixed or withdrawable).
Note: The values indicated above have been validated for PrismaSeT P Active switchboards.
I-42 TOC
Version : 14 - 15/12/2023
160E9400
PrismaSeT P Active - Additional information www.se.com
To connect a ComPacT NSX250 and NSX Vigi 250 ELCB to a Linergy BW busbars, use a 24 x 5 flexible bar cat. no. LVS04746.
Version : 14 - 15/12/2023
160E9400 TOC I-43
PrismaSeT P Active - Additional information www.se.com
I-44 TOC
Version : 14 - 15/12/2023
160E9400
PrismaSeT P Active - Additional information www.se.com
Version : 14 - 15/12/2023
160E9400 TOC I-45
PrismaSeT P Active - Additional information www.se.com
Electrical characteristics
Tubular lugs for incoming connection Maximum size of lugs for connection to the different incoming connection blocks.
Incoming connection block for 150 mm² 240 mm² 185 mm²
ComPacT NSX-INS-INV250 supplied via the top or
the bottom, cat. no. LVS04066 et LVS04067
In-duct incoming connection block for 240 mm² 300 mm² 300 mm²
ComPacT NSX630 supplied via the top or the
bottom cat. no. LVS04076
Customer connection Maximum size and number of cables for connection to terminal extension bars
(according to busbar drawing supplied) for customer connection of ComPacT NSX
of devices u 630 A and MasterPact MTZ1 /MTZ2 and NT devices.
Cable size Quantity
(mm²)
Size and number of cables
Copper lugs 300 12
Bimetal lugs 240 12
I-46 TOC
Version : 14 - 15/12/2023
160E9400
PrismaSeT P Active - Additional information www.se.com
Electrical characteristics
ComPacT NS630b to NS1600
DD383540.eps
Vertical mounting
Front or rear connection
Incoming via top or bottom
Using the data below, it is possible to determine the permissible current for a
prefabricated connection between a vertical ComPacT NS630b/NS1600, fixed or
withdrawable, and Linergy busbars depending on the ambient temperature around
the switchboard and the IP value.
Fixed
Prefabricated connections
Device and cat. no. Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40 °C 45 °C 50 °C
IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
NS630b 3P cat. no. 33642 630 630 630 630 630 630 630 630 630 630 630 b
4P cat. no. 33643
NS800 3P cat. no. 33642 800 800 800 800 800 800 800 800 800 800 800 b
4P cat. no. 33643
NS1000 3P cat. no. 33642 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 b
4P cat. no. 33643
NS1250 3P réf.33642 + 33644 1250 1250 1250 1250 1250 1250 1250 1200 1250 1150 1200 b
4P réf.33643 + 33645
NS1600 3P réf.33642 + 33644 1600 1550 1600 1500 1550 1450 1500 1400 1450 1350 1400 b
4P réf.33643 + 33645
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Withdrawable
Prefabricated connections
Device and cat. no. Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40 °C 45 °C 50 °C
Version : 14 - 15/12/2023
160E9400 TOC I-47
PrismaSeT P Active - Additional information www.se.com
Electrical characteristics
MasterPact MTZ106 to 16
Dd383673.eps
Vertical mounting
Front or rear connection
Incoming via top or bottom
Using the data below, it is possible to determine the permissible current for a
prefabricated connection between a vertical MasterPact MTZ1 06/16, fixed or
drawout, and Linergy busbars depending on the ambient temperature around the
switchboard and the IP value.
Fixed
Prefabricated connections
Device and cat. no. Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40 °C 45 °C 50 °C
IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
NT06 3P cat. no. 33642 630 630 630 630 630 630 630 630 630 630 630 b
4P cat. no. 33643
NT08 3P cat. no. 33642 800 800 800 800 800 800 800 800 800 800 800 b
4P cat. no. 33643
NT10 3P cat. no. 33642 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 b
4P cat. no. 33643
NT12 3P réf.33642 + 33644 1250 1250 1250 1250 1250 1250 1250 1200 1250 1150 1200 b
4P réf.33643 + 33645
NT16 3P réf.33642 + 33644 1600 1570 1600 1520 1570 1470 1520 1420 1470 1370 1420 b
4P réf.33643 + 33645
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Withdrawable
Prefabricated connections
Device and cat. no. Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40 °C 45 °C 50 °C
IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
NT06 3P cat. no. 33642 630 630 630 630 630 630 630 630 630 630 630 b
4P cat. no. 33643
NT08 3P cat. no. 33642 800 800 800 800 800 800 800 800 800 800 800 b
4P cat. no. 33643
NT10 3P cat. no. 33642 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 b
4P cat. no. 33643
NT12 3P réf.33642 + 33644 1250 1250 1250 1250 1250 1250 1250 1200 1250 1150 1200 b
4P réf.33643 + 33645
NT16 3P réf.33642 + 33644 1560 1480 1520 1430 1480 1380 1430 1330 1380 1280 1330 b
4P réf.33643 + 33645
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Note: the values indicated above have been validated for PrismaSeT P Active switchboards.
I-48 TOC
Version : 14 - 15/12/2023
160E9400
PrismaSeT P Active - Additional information www.se.com
Electrical characteristics
ComPacT NS630b to NS1000, fixed
Dd383541.eps
Horizontal mounting
Front or rear connection
Installation on the left or right
Using the data below, it is possible to determine the permissible current for a
prefabricated connection between a horizontal, fixed ComPacT NS630b/NS1000
and Linergy busbars depending on the ambient temperature around the switchboard
and the IP value.
Version : 14 - 15/12/2023
160E9400 TOC I-49
PrismaSeT P Active - Additional information www.se.com
Electrical characteristics
MasterPact MTZ208 to 16
Dd383674.eps
Fixed
Vertical mounting
Front or rear connection
Incoming via top or bottom
Busbar drawings supplied by
Schneider Electric
Using the data below, it is possible to determine the size of the copper bars and the
maximum permissible currents when making a front or rear customer connection for
a vertical, fixed MasterPact MTZ1 06/16, taking into account the ambient
temperature around the switchboard and the IP value.
Connection to be made according to the busbar drawings supplied.
For connection cable cross-sections and quantities > page I-46.
Customer connection
Flat bars, 5 mm thick
Device Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40°C 45 °C 50 °C
IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
NW08 Size per phase 2b 60 x 5 2b 60 x 5 2b 60 x 5 2b 60 x 5 2b 60 x 5 2b 60 x 5 2b 60 x 5 2b 60 x 5 2b 60 x 5 2b 60 x 5 2b 60 x 5 b
I (A) 800 800 800 800 800 800 800 800 800 800 800
NW10 Size per phase 2b 60 x 5 2b 60 x 5 2b 60 x 5 2b 60 x 5 2b 60 x 5 2b 60 x 5 2b 60 x 5 2b 60 x 5 2b 60 x 5 2b 60 x 5 2b 60 x 5 b
I (A) 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
NW12 Size per phase 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 b
I (A) 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250
NW16 Size per phase 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 b
I (A) 1600 1600 1600 1570 1600 1520 1570 1470 1520 1420 1470
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Note: the values indicated above have been validated for PrismaSeT P Active switchboards.
I-50 TOC
Version : 14 - 15/12/2023
160E9400
PrismaSeT P Active - Additional information www.se.com
Electrical characteristics
MasterPact MTZ208 to 40
Dd383675.eps
Fixed
Vertical mounting
Front or rear connection
Incoming via top or bottom
Busbar drawings supplied by
Schneider Electric
Customer connection
Flat bars, 10 mm thick
Device Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40°C 45 °C 50 °C
IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
NW08 Size per phase 1b 60 x 10 1b 60 x10 1b 60 x 10 1b 60 x10 1b 60 x 10 1b 60 x10 1b 60 x 10 1b 60 x10 1b 60 x 10 1b 60 x10 1b 60 x 10 b
I (A) 800 800 800 800 800 800 800 800 800 800 800
NW10 Size per phase 1b 60 x 10 1b 60 x10 1b 60 x 10 1b 60 x10 1b 60 x 10 1b 60 x10 1b 60 x 10 1b 60 x10 1b 60 x 10 1b 60 x10 1b 60 x 10 b
I (A) 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
NW12 Size per phase 1b 60 x 10 1b 60 x10 1b 60 x 10 1b 60 x10 1b 60 x 10 1b 60 x10 1b 60 x 10 1b 60 x10 1b 60 x 10 1b 60 x10 1b 60 x 10 b
I (A) 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250
NW16 Size per phase 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 b
I (A) 1600 1600 1600 1570 1600 1520 1570 1470 1520 1420 1470
NW20 Size per phase 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 b
I (A) 2000 2000 2000 2000 2000 2000 2000 1950 2000 1900 1950
NW25 Size per phase 2b100 x 10 2b100 x 10 2b100 x 10 2b100 x 10 2b100 x 10 2b100 x 10 2b100 x 10 2b100 x 10 2b100 x 10 2b100 x 10 2b100 x 10 b
I (A) 2500 2500 2500 2500 2500 2460 2500 2380 2500 2300 2460
NW32 Size per phase 2b120 x 10 2b120 x 10 2b120 x 10 2b120 x 10 2b120 x 10 2b120 x 10 2b120 x 10 2b120 x 10 2b120 x 10 2b120 x 10 2b120 x 10 b
I (A) 3200 3000 3170 2910 3080 2820 3000 2730 2910 2630 2820
NW40 Size per phase (2) (2) (2) (2) (2) (2) (2) (2) (2) (2) (2) b
I (A) (1)
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Canalis connection For Canalis connections, apply the appropriate derating coefficient K.
Electrical characteristics
MasterPact MTZ208 to 16
Dd383676.eps
Drawout
Vertical mounting
Front or rear connection
Incoming via top or bottom
Busbar drawings supplied by
Schneider Electric
Using the data below, it is possible to determine the size of the copper bars and the
maximum permissible currents when making a front or rear customer connections to
busbars for a vertical, drawout MasterPacT MTZ1 08/16, taking into account the
ambient temperature around the switchboard and the IP value.
Connection to be made according to the busbar drawings supplied.
For connection cable cross-sections and quantities > page I-46.
Customer connection
Flat bars, 5 mm thick
Device Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40 °C 45 °C 50 °C
IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
NW08 Size per phase 2b 60 x 5 2b 60 x 5 2b 60 x 5 2b 60 x 5 2b 60 x 5 2b 60 x 5 2b 60 x 5 2b 60 x 5 2b 60 x 5 2b 60 x 5 2b 60 x 5 b
I (A) 800 800 800 800 800 800 800 800 800 800 800
NW10 Size per phase 2b 60 x 5 2b 60 x 5 2b 60 x 5 2b 60 x 5 2b 60 x 5 2b 60 x 5 2b 60 x 5 2b 60 x 5 2b 60 x 5 2b 60 x 5 2b 60 x 5 b
I (A) 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
NW12 Size per phase 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 b
I (A) 1250 1250 1250 1250 1250 1230 1250 1200 1230 1160 1200
NW16 Size per phase 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 b
I (A) 1560 1480 1520 1430 1480 1380 1430 1330 1380 1280 1330
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Note: the values indicated above have been validated for PrismaSeT P Active switchboards.
I-52 TOC
Version : 14 - 15/12/2023
160E9400
PrismaSeT P Active - Additional information www.se.com
Electrical characteristics
MasterPact MTZ208 to 40
Dd383677.eps
Drawout
Vertical mounting
Front or rear connection
Incoming via top or bottom
Busbar drawings supplied by
Schneider Electric
Customer connection
Flat bars, 10 mm thick
Device Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40 °C 45 °C 50 °C
IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
NW08 Size per phase 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 b
I (A) 800 800 800 800 800 800 800 800 800 800 800
NW10 Size per phase 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 b
I (A) 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
NW12 Size per phase 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 b
I (A) 1250 1250 1250 1210 1250 1180 1210 1140 1180 1100 1140
NW16 Size per phase 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 b
I (A) 1560 1480 1520 1430 1480 1380 1430 1330 1380 1280 1330
NW20 Size per phase 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 b
I (A) 2000 2000 2000 1950 2000 1900 1950 1830 1900 1760 1830
NW25 Size per phase 2b100 x 10 2b100 x 10 2b100 x 10 2b100 x 10 2b100 x 10 2b100 x 10 2b100 x 10 2b100 x 10 2b100 x 10 2b100 x 10 2b100 x 10 b
I (A) 2470 2280 2410 2210 2350 2140 2280 2070 2210 2000 2140
NW32 Size per phase 2b120 x 10 2b120 x 10 2b120 x 10 2b120 x 10 2b120 x 10 2b120 x 10 2b120 x 10 2b120 x 10 2b120 x 10 2b120 x 10 2b120 x 10 b
I (A) 2960 2730 2890 2630 2820 2530 2730 2450 2630 2370 2530
NW40 Size per phase (2) (2) (2) (2) (2) (2) (2) (2) (2) (2) (2) b
I (A) (1)
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Canalis connection
For Canalis connections, apply the appropriate derating coefficient K. I
Device NW08 NW10 NW12 NW16 NW20 NW25 NW32
Version : 14 - 15/12/2023
160E9400 TOC I-53
PrismaSeT P Active - Additional information www.se.com
Electrical characteristics
MasterPact MTZ106 to 16
Dd383678.eps
Fixed
Rear connection
Incoming via top or bottom
Busbar drawings supplied by
Schneider Electric
Using the data below, it is possible to determine the size of the copper bars and the
maximum permissible currents when making a front or rear customer connections to
busbars for a vertical, fixed MasterPact MTZ1 06/16, taking into account the ambient
temperature around the switchboard and the IP value.
Connection to be made according to the busbar drawings supplied.
For connection cable cross-sections and quantities > page I-46.
Customer connection
Flat bars, 5 mm thick
Device Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40°C 45 °C 50 °C
IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
NT06 Size per phase 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5 b
I (A) 630 630 630 630 630 630 630 630 630 630 630
NT08 Size per phase 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 b
I (A) 800 800 800 800 800 800 800 800 800 800 800
NT10 Size per phase 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 b
I (A) 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
NT12 Size per phase 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 b
I (A) 1250 1250 1250 1250 1250 1250 1250 1250 1250 1200 1250
NT16 Size per phase 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5 b
I (A) 1600 1570 1600 1520 1570 1470 1520 1420 1470 1370 1420
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Customer connection
Flat bars, 10 mm thick
Device Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40°C 45 °C 50 °C
IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
NT06 Size per phase 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 b
I (A) 630 630 630 630 630 630 630 630 630 630 630
NT08 Size per phase 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 b
I (A) 800 800 800 800 800 800 800 800 800 800 800
NT10 Size per phase 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 b
I (A) 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
NT12 Size per phase 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 b
I (A) 1250 1250 1250 1250 1250 1250 1250 1250 1250 1180 1230
NT16 Size per phase 1b100 x 1b100 x 1b100 x 1b100 x 1b100 x 1b100 x 1b100 x 1b100 x 1b100 x 1b100 x 1b100 x b
10 10 10 10 10 10 10 10 10 10 10
I (A) 1600 1570 1600 1520 1570 1470 1520 1420 1470 1370 1420
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Canalis connection
For Canalis connections, apply the appropriate derating coefficient K.
Device NT06b NT08 NT10 NT12 NT16
Derating coefficient K 1 1 1 1 0,98
Note: the values indicated above have been validated for PrismaSeT P Active switchboards.
I-54 TOC
Version : 14 - 15/12/2023
160E9500
PrismaSeT P Active - Additional information www.se.com
Electrical characteristics
MasterPact MTZ106 to 16
Dd383679.eps
Rear connection
Incoming via top or bottom
Busbar drawings supplied by
Schneider Electric
Using the data below, it is possible to determine the size of the copper bars and the
maximum permissible currents when making a customer connections to busbars for
a vertical, drawout MasterPact MTZ1 06/16, taking into account the ambient
temperature around the switchboard and the IP value.
Connection to be made according to the busbar drawings supplied.
For connection cable cross-sections and quantities > page I-46.
Customer connection
Flat bars, 5 mm thick
Device Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40°C 45 °C 50 °C
IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
NT06 Size per phase 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5 b
I (A) 630 630 630 630 630 630 630 630 630 630 630
NT08 Size per phase 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 b
I (A) 800 800 800 800 800 800 800 800 800 800 800
NT10 Size per phase 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 b
I (A) 1000 1000 1000 1000 1000 1000 1000 1000 1000 960 1000
NT12 Size per phase 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 b
I (A) 1250 1250 1250 1250 1250 1230 1250 1180 1230 1130 1180
NT16 Size per phase 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5 b
I (A) 1560 1430 1520 1430 1480 1380 1430 1330 1380 1280 1330
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Customer connection
Flat bars, 10 mm thick
Device Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40°C 45 °C 50 °C
IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
NT06 Size per phase 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 b
I (A) 630 630 630 630 630 630 630 630 630 630 630
NT08 Size per phase
I (A)
1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10
800 800 800 800 800
1b 50 x 10
800
1b 50 x 10
800
1b 50 x 10
800
1b 50 x 10
800
1b 50 x 10
800
1b 50 x 10
800
b
I
NT10 Size per phase 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 b
I (A) 1000 1000 1000 1000 1000 1000 1000 1000 1000 960 1000
NT12 Size per phase 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 b
I (A) 1250 1250 1250 1250 1250 1210 1250 1160 1210 1110 1160
NT16 Size per phase 1b100 x 1b100 x 1b100 x 1b100 x 1b100 x 1b100 x 1b100 x 1b100 x 1b100 x 1b100 x 1b100 x b
10 10 10 10 10 10 10 10 10 10 10
I (A) 1560 1430 1520 1430 1480 1380 1430 1330 1380 1280 1330
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Canalis connection
For Canalis connections, apply the appropriate derating coefficient K.
Device NT06 NT08 NT10 NT12 NT16
Note: the values indicated above have been validated for PrismaSeT P Active switchboards.
Version : 14 - 15/12/2023
160E9500 TOC I-55
PrismaSeT P Active - Additional information www.se.com
Electrical characteristics
ComPacT NS1600b/3200 fixed
Dd383542.eps
Front or rear connection
Incoming via top or bottom
Busbar drawings supplied by
Schneider Electric
Using the data below, it is possible to determine the size of the copper bars and the
maximum permissible currents when making a front or rear customer connections to
busbars for a vertical, fixed ComPacT NS1600b/NS3200, taking into account the
ambient temperature around the switchboard and the IP value.
Connection to be made according to the busbar drawings supplied.
For connection cable cross-sections and quantities > page I-46.
Customer connection
Flat bars, 10 mm thick
Device Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40°C 45 °C 50 °C
IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP>31
NS1600b Size per phase 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 b
I (A) 1560 1480 1520 1430 1480 1380 1430 1330 1380 1280 1330
NS2000 Size per phase 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 b
I (A) 2000 2000 2000 1950 2000 1900 1950 1830 1900 1760 1830
NS2500 Size per phase 2b100 x 10 2b100 x 10 2b100 x 10 2b100 x 10 2b100 x 10 2b100 x 10 2b100 x 10 2b100 x 10 2b100 x 10 2b100 x 10 2b100 x 10 b
I (A) 2470 2280 2410 2210 2350 2140 2280 2070 2210 2000 2140
NS3200 Size per phase 2b120 x 10 2b120 x 10 2b120 x 10 2b120 x 10 2b120 x 10 2b120 x 10 2b120 x 10 2b120 x 10 2b120 x 10 2b120 x 10 2b120 x 10 b
I (A) 2860 2630 2790 2530 2720 2430 2630 2350 2530 2270 2430
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Note: the values indicated above have been validated for PrismaSeT P Active switchboards.
I-56 TOC
Version : 14 - 15/12/2023
160E9500
PrismaSeT P Active - Additional information www.se.com
Electrical characteristics
ComPacT NS630b to NS1600
Dd383543.eps
Fixed
Rear connection
Incoming via top or bottom
Busbar drawings supplied by
Schneider Electric
Using the data below, it is possible to determine the size of the copper bars and the
maximum permissible currents when making a rear customer connection for a
vertical, fixed ComPacT NS630b/NS1600, taking into account the ambient
temperature around the switchboard and the IP value.
Connection to be made according to the busbar drawings supplied.
For connection cable cross-sections and quantities > page I-46.
Customer connection
Flat bars, 5 mm thick
Device Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40°C 45 °C 50 °C
IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
NS630b Size per phase 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5 b
I (A) 630 630 630 630 630 630 630 630 630 630 630
NS800 Size per phase 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 b
I (A) 800 800 800 800 800 800 800 800 800 800 800
NS1000 Size per phase 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 b
I (A) 1000 1000 1000 1000 1000 1000 1000 1000 1000 970 1000
NS1250 Size per phase 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 b
I (A) 1250 1250 1250 1250 1250 1250 1250 1200 1250 1150 1200
NS1600 Size per phase 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5 b
I (A) 1600 1550 1600 1500 1550 1450 1500 1400 1450 1350 1400
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Customer connection
Flat bars, 10 mm thick
Device Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40°C 45 °C 50 °C
IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
NS630b Size per phase 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 b
I
I (A) 630 630 630 630 630 630 630 630 630 630 630
NS800 Size per phase 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 b
I (A) 800 800 800 800 800 800 800 800 800 800 800
NS1000 Size per phase 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 b
I (A) 1000 1000 1000 1000 1000 1000 1000 1000 1000 970 1000
NS1250 Size per phase 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 b
I (A) 1250 1250 1250 1250 1250 1250 1250 1180 1230 1130 1180
NS1600 Size per phase 1b100 x 10 1b100 x 10 1b100 x 10 1b100 x 10 1b100 x 10 1b100 x 10 1b100 x 10 1b100 x 10 1b100 x 10 1b100 x 10 1b100 x 10 b
I (A) 1600 1550 1600 1500 1550 1450 1500 1400 1450 1350 1400
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Canalis connection
For Canalis connections, apply the appropriate derating coefficient K.
Device NS630b NS800 NS1000 NS1250 NS1600
Derating coefficient K 1 1 1 1 0,98
Note: the values indicated above have been validated for PrismaSeT P Active switchboards.
Version : 14 - 15/12/2023
160E9500 TOC I-57
PrismaSeT P Active - Additional information www.se.com
Electrical characteristics
DD383807.eps
Withdrawable
Rear connection
Incoming via top or bottom
Busbar drawings supplied by
Schneider Electric
Using the data below, it is possible to determine the size of the copper bars and the
maximum permissible currents when making a rear customer connection for a
vertical, withdrawable ComPacT NS630b/NS1600, taking into account the ambient
temperature around the switchboard and the IP value.
Connection to be made according to the busbar drawings supplied.
For connection cable cross-sections and quantities > page I-46.
Customer connection
Flat bars, 5 mm thick
Device Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40°C 45 °C 50 °C
IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
NS630b Size per phase 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5 1b 60 x 5 b
I (A) 630 630 630 630 630 630 630 630 630 630 630
NS800 Size per phase 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 b
I (A) 800 800 800 800 800 800 800 800 800 800 800
NS1000 Size per phase 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 b
I (A) 1000 1000 1000 1000 1000 1000 1000 1000 1000 960 1000
NS1250 Size per phase 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 b
I (A) 1250 1250 1250 1250 1250 1230 1250 1180 1230 1130 1180
NS1600 Size per phase 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5 2b 100 x 5 b
I (A) 1560 1430 1520 1430 1480 1380 1430 1330 1380 1280 1330
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Customer connection
Flat bars, 10 mm thick
Device Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40°C 45 °C 50 °C
IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
NS630b Size per phase 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 b
I (A) 630 630 630 630 630 630 630 630 630 630 630
NS800 Size per phase 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 b
I (A) 800 800 800 800 800 800 800 800 800 800 800
NS1000 Size per phase 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 b
I (A) 1000 1000 1000 1000 1000 1000 1000 1000 1000 960 1000
NS1250 Size per phase 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 b
I (A) 1250 1250 1250 1250 1250 1210 1250 1160 1210 1110 1160
NS1600 Size per phase 1b100 x 10 1b100 x 10 1b100 x 10 1b100 x 10 1b100 x 10 1b100 x 10 1b100 x 10 1b100 x 10 1b100 x 10 1b100 x 10 1b100 x 10 b
I (A) 1560 1430 1520 1430 1480 1380 1430 1330 1380 1280 1330
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Canalis connection
For Canalis connections, apply the appropriate derating coefficient K.
Device NS630b NS800 NS1000 NS1250 NS1600
Derating coefficient K 1 1 1 1 0,98
Note: the values indicated above have been validated for PrismaSeT P Active switchboards.
I-58 TOC
Version : 14 - 15/12/2023
160E9500
PrismaSeT P Active - Additional information www.se.com
Electrical characteristics
ComPacT NS630b to NS1000
Dd383545.eps
Horizontal mounting
Front connection
Incoming via top or bottom
Installation on the left or right
Using the data below, it is possible to determine the size of the copper bars and the
maximum permissible currents when making the connections to busbars for a
horizontal, fixed ComPacT NS630b/NS1600, taking into account the ambient
temperature around the switchboard and the IP value.
Connection to be made according to the busbar drawings supplied.
Customer connection
Flat bars, 5 mm thick
Device Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40°C 45 °C 50 °C
IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
NS630b Size per phase 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 b
I (A) 630 630 630 630 630 630 630 630 630 630 630
NS800 Size per phase 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 b
I (A) 800 800 800 800 800 800 800 800 800 800 800
NS1000 Size per phase 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 2b 50 x 5 b
I (A) 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
Version : 14 - 15/12/2023
160E9500 TOC I-59
PrismaSeT P Active - Additional information www.se.com
Designing busbars
Fupact GS, ISFT, ISFL Linergy BS busbars
Electrical characteristics
Permissible current and selection of horizontal Linergy BS busbars
The goal is to optimise busbar size according to the installation and operating
criteria.
I-60 TOC
Version : 14 - 15/12/2023
160E9500
PrismaSeT P Active - Additional information www.se.com
Designing busbars
Fupact GS, ISFT Vertical Linergy LGYE, LGY busbars
Electrical characteristics
Permissible current and selection of Linergy LGYE busbars
The goal is to optimise busbar size according to the installation and operating criteria.
Version : 14 - 15/12/2023
160E9500 TOC I-61
PrismaSeT P Active - Additional information www.se.com
Designing busbars
Fupact GS, ISFT Vertical Linergy BS busbars
Electrical characteristics
Lateral Linergy BS busbars
Fupact GS/ISFT
Linergy BS bars, 5 mm thick
Type of bars Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40 °C 45 °C 50 °C
Size per phase IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
1 Linergy BS bar, 60 x 5 800 750 760 700 710 650 660 600 610 550 560 b
1 Linergy BS bar, 80 x 5 1000 910 970 860 910 810 860 750 810 700 750 b
2 Linergy BS bars, 60 x 5 1400 1250 1320 1160 1250 1070 1160 980 1070 880 980 b
2 Linergy BS bars, 80 x 5 1700 1500 1600 1400 1500 1280 1400 1160 1280 1030 1160 b
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
I-62 TOC
Version : 14 - 15/12/2023
160E9500
PrismaSeT P Active - Additional information www.se.com
<SI
Front Connection SI
SII
Autom
atic
SII
OF/AUX
atic
Autom
SI
Outgoing connection
Flexible Busbar Flat 3 mm (250A) & 8 mm (630A) Thick
Device Permissible current (A)
Ambient temperature around the switchboard
25 °C 30 °C 35 °C 40 °C 45 °C 50 °C
Cable Size IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
TransferPacT 250A Size per phase (mm2) 1b 20X3 1b 20X3 1b 20X3 1b 20X3 1b 20X3 1b 20X3 1b 20X3 1b 20X3 1b 20X3 1b 20X3 1b 20X3 1b 20X3
I(A) 250 250 250 250 250 240 250 230 240 220 225 208
TransferPacT 630A Size per phase (mm2) 1b 32X8 1b 32X8 1b 32X8 1b 32X8 1b 32X8 1b 32X8 1b 32X8 1b 32X8 1b 32X8 1b 32X8 1b 32X8 1b 32X8
I(A) 580 545 565 525 545 505 525 490 505 475 490 430
Note: The values indicated above have been validated for PrismaSeT P Active switchboards.
(1) We recommend insulated flexible copper bars instead of copper cable for TransferPacT 250A to 630A outgoing connection.
Version : 14 - 15/12/2023
160E9500 TOC I-63
PrismaSeT P Active - Additional information www.se.com
Enclosure characteristics
The IP and IK degrees of protection provided by an enclosure must be specified as a
function of the various external influences defined by standard IEC 30364-5-51, in
particular:
b presence of foreign solid bodies (code AE)
b presence of water (code AD)
b mechanical stress (code not specified)
b capability of persons (code BA)
b ...
PrismaSeT P Active switchboards are designed for indoor installation.
Unless the rules, standards and regulations of a specific country stipulate otherwise,
Schneider Electric recommends the following IP and IK values based on French
guide UTE C 15-103 (March 2004).
Using the table 1 Opposite the relevant premises, read the recommended IP and IK values.
2 The b symbol indicates the enclosure or cubicle satisfying the criteria of the UTE
guide.
Any enclosure or cubicle with a higher degree of protection can also be used.
3 If several degrees of protection are possible (refer to the standard for more
details) and the v and b symbols are indicated (e.g. 24v/25b), enclosures that
correspond to the higher degree of protection (b) are suitable for the lower degree
of protection (v).
No applicable
I-64 TOC
Version : 14 - 15/12/2023
160E9600
PrismaSeT P Active - Additional information www.se.com
Enclosure characteristics
Type of premises Enclosure
Cubicle
with fixed frame with door + IP30 with door + gasket with door + IP55
cover + IP30 cover cover
Min. IP/IK IP30/IK07 IP30/IK08 IP31/IK08 IP43/IK08 IP55/IK10
required
IP IK
Washrooms, rooms volume 0 27 02
containing a bathtub or volume 1 24 02 b
shower
volume 2 23 02 b
volume 3 21 02 b
Lounges, living rooms, etc 20 02 b
Drying rooms 21 02 b
Covered terraces 21 02 b
WCs 20 02 b
Verandas 20 02 b
Crawl spaces 23 07
Commercial premises and adjoining areas
Gunsmiths (storage area, workshop) 30 08 b
Laundries (wash room) 24 07 b
Butchers shop 24 07 b
cold room 23 07 b
y -10 °C
Bakers, cake shops (kitchens) 50 07 b
Coffee roasters 21 02 b
Coal, wood, oil 20 08 b
Delicatessen (production) 24 07 b
Sweets (production) 20 02 b
Shoe repair shops 20 02 b
Dairies 24 02 b
Hardware stores (storage areas for 33 07 b
chemicals and paint)
Wood workers 50 07 b
Art galleries 20 02/07 b
Florists 24 07 b
Furriers 20 07 b
Fruit and vegetable merchants 24 07 b
Grain shops 50 07 b
Bookshops, stationers 20 02 b
Motorcycle and bicycle repairs and 20 08 b
accessories
Messenger services 20 08 b
Furniture shops (antiques, 20 07 b
secondhand)
Glass and mirror merchants 20 07 b
(workshop)
Wallpaper shop (storage area) 20 07 b
Cosmetics shop (storage area) 20 02 b
Chemists (storage area) 20 02 b
Photographers (dark room) 23 02 b
Plumbers (storage area)
Fishmongers
20
25
08
07
b
b
I
Dry cleaners 23 02 b
Hardware stores (without paint, 20 07 b
chemicals, etc.)
Locksmiths 20 07v/08b b b
Vintners, spirits 20 07 b
Interior decorator (carding) 50 07 b
Tailors, clothing retailers (storage 20 02 b
area)
Pet care 35 07 b
No applicable
Version : 14 - 15/12/2023
160E9600 TOC I-65
PrismaSeT P Active - Additional information www.se.com
Enclosure characteristics
Type of premises Enclosure
Cubicle
with fixed frame with door + with door + gasket with door +
IP30 cover + IP30 cover IP55 cover
Min. IP/IK IP30/IK07 IP30/IK08 IP31/IK08 IP43/IK08 IP55/IK10
required
IP IK
linen rooms 20 02 b
laundry rooms 24 07 b
misc. shops 21 07/08 b
kitchens (large)
J Reception old and handicapped 20 02 b
people
L Lecture halls, halls 20 02/07 b
meeting rooms, stage areas 20 08 b
auditoriums,
halls used for scenery storage 20 08 b
several purposes rooms
costume rooms 20 07 b
Y Museums 20 02 b
PA Covered open air facilities 23v/25b 08v/10b b b
CTS Marquees and tents 44 08 b
SG Inflatable structures 44 08 b
PS Covered parking lots 21 08v/10b b b
I-66 TOC
Version : 14 - 15/12/2023
160E9600
PrismaSeT P Active - Additional information www.se.com
Enclosure characteristics
Type of premises Enclosure
Cubicle
with fixed frame with door + IP30 with door + gasket with door + IP55
cover + IP30 cover cover
Min. IP/IK IP30/IK07 IP30/IK08 IP31/IK08 IP43/IK08 IP55/IK10
required
IP IK
Technical premises
Battery rooms 23 02/07 b
Lifts (machine rooms and pulley 20 07v/08b b b
rooms)
Electrical rooms 20 07 b
Control rooms 20 02 b
Workshops 21v/23b 07v/08b b b
Laboratories 21v/23b 02v/07b b b
Air conditioning washers 24 07 b
Garages (used exclusively for 21 07 b
parking vehicles) of an area not
exceeding 100 m2
Machine rooms 31 07/08 b
Water pressurisers 23 07/08 b
Boiler houses and adjoining premises (power in excess of 70 kW)
Boiler rooms coal fuel 51v/61b 07v/08b b
other fuel 21 07/08 b
electrical 21 07/08 b
Fuel coal 50v/60b 08 b
storage areas
oil 20 07v/08b b b
liquefied gas 20 07v/08b b b
Cinder tips 50 08 b
Pump rooms 21v/23b 07v/08b b b
Pressure reduction rooms (gas) 20 07v/08b b b
Steam or hot water facilities 21v/23b 07v/08b b b
Lubrication areas 23 08 b
Battery recharging areas 23 07 b
Workshops 21 08 b
Public building (other than for the general public)
Offices 20 02 b
Libraries 20 02 b
Archives 20 02 b
Computer rooms 20 02 b
Design offices 20 02 b
Rooms containing reprographic 20 02 b
machines
Sorting rooms 20 07 b
I
Refectories in restaurants or 21 07 b
canteens
Large kitchens
Sports rooms 20 07v/08b b b
Barracks 20 07 b
Meeting rooms 20 02 b
Waiting rooms, lounges, halls 20 02 b
Medical consulting rooms, not fitted 20 02 b
with specific equipment
No applicable
Version : 14 - 15/12/2023
160E9600 TOC I-67
PrismaSeT P Active - Additional information www.se.com
Enclosure characteristics
Type of premises Enclosure
Cubicle
with fixed frame with door + IP30 with door + gasket with door + IP55
cover + IP30 cover cover
Min. IP/IK IP30/IK07 IP30/IK08 IP31/IK08 IP43/IK08 IP55/IK10
required
IP IK
Farm premises or locations
Alcohol (storage) 23 07 b
Closed cattle sheds 35 07 b
Laundries 24 07 b
Wood storage rooms 30 10 b
Threshing floors 50 07 b
Distilling cellars 23 07 b
Vat rooms (wine) 23 07 b
Courtyards 35 07 b
Poultry barns 35 07 b
Stables 35 07 b
Fertiliser (storage) 50 07 b
Stables 35 07 b
Manure heaps 24 07 b
Haylofts 50 07 b
Haystacks, forage (storage) 50 07 b
Granaries, barns 50 07 b
Straw (storage) 50 07 b
Greenhouses 23 07 b
Grain silos 50 07 b
Milking rooms 35 07 b
Pig sties 35 07 b
Chicken houses 35 07 b
Miscellaneous installations
Fair facilities 33 08 b
Water treatment facilities 24/25 07/08 b
Thermodynamic installations, air-conditioned rooms and cold rooms
Height from 0 to 1.10 m 25 07 b
above from 1.10 to 2 m 24 07 b
ground
above 2 m under 21 07 b
evaporator or water
drain pipe
ceiling and up to 10 23 07 b
cm underneath
Temperature y -10 °C 23 07 b
Compressor room 21 08 b
integral unit located 34 08
outside or on a terrace
No applicable
I-68 TOC
Version : 14 - 15/12/2023
160E9600
PrismaSeT P Active - Additional information www.se.com
Enclosure characteristics
Type of premises Enclosure
Cubicle
with fixed frame with door + IP30 with door + gasket with door + IP55
cover + IP30 cover cover
Min. IP/IK IP30/IK07 IP30/IK08 IP31/IK08 IP43/IK08 IP55/IK10
required
IP IK
Industrial facilities
Slaughter houses 55 08 b
Batteries (manufacture) 33 07 b
Acid (manufacture and storage) 33 07 b
Alcohol (manufacture and storage) 33 07 b
Aluminium (manufacture and 51 08 b
storage)
Livestock (raising, fattening and sale) 45 07 b
Asphalt and bitumen storage 53 07 b
Wool beating and carding 50 08 b
Industrial laundry 24/25 07 b
Wood (processing) 50 08 b
Meat packers 24/25 07 b
Bakeries 50 07 b
Breweries 24 07 b
Brickworks 53 08 b
Rubber (production and processing) 54 07 b
Version : 14 - 15/12/2023
160E9600 TOC I-69
PrismaSeT P Active - Selection table www.se.com
Enclosure characteristics
Type of premises Enclosure
Cubicle
with fixed frame with door + IP30 with door + gasket with door + IP55
cover + IP30 cover cover
Min. IP/IK IP30/IK07 IP30/IK08 IP31/IK08 IP43/IK08 IP55/IK10
required
IP IK
Industrial establishments (continued)
Dairies 25 07 b
Public wash-houses 25 07 b
Liqueurs (production) 21 07 b
Halogenated liquids (use) 21 08 b
Inflammable products 21 08 b
(storage and workshops where they
are used)
Magnesium (production, storage 31 08 b
and use)
Machine rooms 20 08 b
Plastics (production) 51 08 b
Cabinet makers 50 08 b
Metals (processing) 31v/33b 08 b b
Combustion engines (testing of) 30 08 b
Ammunition storage 33 08 b
Nickel (or processing) 33 08 b
Household waste (processing) 54 07 b
Paper (production) 33v/34b 07 b b b
Paper (storage) 31 07 b
Perfume (production and storage) 31 07 b
Pulp mill 34/35 07 b b
Paint (production and storage) 33 08 b
Plaster (processing and storage) 50 07 b
Gunpowder factory 55 08 b
Chemicals (production) 30v/50b 08 b b
Oil refineries 34/35 07 b
Salt preserve factories 33 07 b
Soap (production) 31 07 b
Saw mills 50 08 b
Metalwork shops 30 08 b
Grain or sugar silos 50 07 b
Silk and artificial hair factories 50 08 b
Sodium carbonate (processing and 33 07 b
storage)
Sulphur (processing) 51 07 b
Spirits (storage) 33 07 b
Sugar mills 55 07 b b
Tanners 35 07 b
Dye works 35 07 b
Textile and fabric (production) 51 08 b
Varnish (production and application) 33 08 b
Glass works 33 08 b
Zinc works 31 08 b
No applicable
I-70 TOC
Version : 14 - 15/12/2023
160E9600
www.se.com
Version : 14 - 15/12/2023
160E9600 TOC I-71
www.se.com
PrismaSeT P Active - Selection table
1 Connection
Connection
Flat bars, 10 mm thick
Device Permissible current (A)
Ambient temperature (°C)
Fixed NS, MTZ1/NT 25 °C 30 °C 35 °C 40 °C 45 °C 50 °C
IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
NS 630, Size per b
1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10
NT 630 phase
& MTZ1 Fixed I
630 630 630 630 630 630 630 630 630 630 630 630
(A)
NS 800, Size per b
1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10
NT 800 phase
& MTZ1 Fixed I
800 800 800 800 800 800 800 800 800 800 800 800
(A)
NS 1000, Size per b
1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10
NT 1000 phase
& MTZ1 Fixed I
1000 1000 1000 1000 1000 980 940 960 920 940 900 920
(A)
NS 1250, Size per b
1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10
NT 1250 phase
& MTZ1 Fixed I
1250 1240 1080 1200 1050 1160 1020 1125 980 1085 950 1040
(A)
NS 1600, Size per 2b 50x10 2b 50x10 2b 50x10 2b 50x10 2b 50x10 2b 50x10 2b 50x10 2b 50x10 2b 50x10 2b 50x10 2b 50x10 b
NT 1600 phase
& MTZ1 Fixed I
1600 1525 1380 1490 1345 1450 1310 1415 1275 1375 1240 1330
(A)
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
I-72 TOC
Version : 14 - 15/12/2023
160E9600
PrismaSeT P Active - Selection table www.se.com
1 Connection
Connection
Flat bars, 10 mm thick
Device Permissible current (A)
Ambient temperature (°C)
Drawout NS, MTZ1/NT 25 °C 30 °C 35 °C 40 °C 45 °C 50 °C
IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31 IP y 31 IP > 31
NS 630, Size per b
1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10
NT 630 phase
&MTZ1 Drawout A
630 630 630 630 630 630 630 630 630 630 630 630
(I)
NS 800, Size per b
1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10
NT 800 phase
& MTZ1 Drawout A
800 800 800 800 800 800 800 800 800 800 800 800
(I)
NS 1000, Size per b
1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10
NT 1000 phase
& MTZ1 Drawout A
1000 1000 1000 1000 1000 980 940 960 920 940 900 920
(I)
NS 1250, Size per b
1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10 1b 50x10
NT 1250 phase
& MTZ1 Drawout A
1250 1230 1070 1190 1040 1155 1005 1115 970 1075 935 1030
(I)
NS 1600, Size per 2b 50x10 2b 50x10 2b 50x10 2b 50x10 2b 50x10 2b 50x10 2b 50x10 2b 50x10 2b 50x10 2b 50x10 2b 50x10 b
NT 1600 phase
& MTZ1 Drawout A
1600 1515 1340 1480 1305 1440 1270 1400 1235 1355 1200 1315
(I)
b Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.
I
Version : 14 - 15/12/2023
160E9600 TOC I-73
After sales tools
www.se.com
2 TOC
Version : 14 - 15/12/2023
160E10000
PrismaSeT P Active - After sales tools www.se.com
Contents
Practical information
Tools required for mounting and connection J-2
Connection of horizontal to vertical busbars J-3
Installation of the current transformer J-4
Installation of source changeover systems J-6
Storage recommendations J-8
Packing information J-9
Handling on the site J-10
Transport J-12
Cubicle handling and rolling base Lifting reinforcement kit
for combined cubicles J-13
Connection of busbar trunking J-14
Connection of power cables J-15
Maintenance
Preventive maintenance J-18
Corrective maintenance J-20
Version : 14 - 15/12/2023
160E10000 TOC J-1
PrismaSeT P Active - After sales tools www.se.com
Practical information
b Vacuum cleaner to clean the switchboards
DD383904.eps
J-2 TOC
Version : 14 - 15/12/2023
160E10100
PrismaSeT P Active - After sales tools www.se.com
Practical information
Horizontal busbars can be connected to vertical busbars (Linergy LGY or Linergy BS)
in two ways:
b in a duct (by a direct connection ordered from the Catalog)
b in the rear (with part of the connection to be fabricated by the installer).
DD383906.eps
connection plate LVS04634 (y 1000 A) or LVS04635 (> 1000 A) after drilling holes in
the horizontal bars.
10 mm thick horizontal busbars can be connected to vertical busbars in
2 ways:
b using connection plate LVS04636 (y 1600 A) or 1600 A < LVS04637 < 2820 A
without drilling holes in the horizontal bars
b or with a screw and socket assembly (LVS04645) designed for assembly on a
busbar that has already been mounted.
Screw + socket
(cat. no. LVS04645). This bolted solution requires:
Connection plate b holes drilled in the bars (Ø16 mm) for diagonal mounting of the sockets and
(cat. no. LVS04635).
screws
b conformity with the following mounting rules:
v respect the overlap length (2.5 to 5 times the bar thickness)
v tighten to a torque of 50 Nm
v fit the recommended number of screws, depending on the bar width as explained
below.
DD385820.eps
10
Ø16 50/60/80/100
100
80
50/60
100 120
60 80 100 60 80
50 50
50/60 x2 50 x2
_ x2 _
80 x3 60
x3 _ _
100 x4 _ _ 80
100
x4 _ _ _
x4 _ _ _
120
In practice, the real contact area is limited to regions in which the pressure is applied effectively.
In a bolted overlap assembly, these areas are made up of the areas adjacent to the bolts, and more precisely under the washers.
Salt spray tests have demonstrated these contact areas. J
The number of screws thus determines the effective cross-sectional area through which the current flows, which corresponds to the area under
the washer (minus the screw hole).
This cross-section area must be close to that of the bar.
Controlled temperature rise
Whatever the connection solution used, the quality and reliability of the contact is guaranteed, in particular with respect to temperature rise, as
long as assembly is carried out according to our recommendations.
Version : 14 - 15/12/2023
160E10100 TOC J-3
PrismaSeT P Active - After sales tools www.se.com
Practical information
Choice of a CT model depends on the type of installation:
PD391279.eps
b insulated cables
b PrismaSeT P Active vertical busbars
b insulated flexible busbars
b Linergy LGY vertical busbars
b rigid busbars.
When installing a CT, we recommend that you comply with the following mounting
rules:
b install current transformers:
v on an easily dismountable busbars or copper connections
v between 2 connection points, by joints or bolted connection
b place the current transformer so that the identification markings remain readable.
For large current transformers, a staggered installation is recommended to prevent
arcing on fixing screws or excessive spacing between phase conductors.
If they are installed on vertical busbars, secure the current transformers in place to
prevent them from slipping downwards (for example using a bolt or a pin)
b when there are several busbars per phase, fit spacers between the busbars in
order to:
v resist the tightening forces when installing the current transformer
v avoid vibrations that lead to current transformer breakdowns.
PD391281.eps
J-4 TOC
Version : 14 - 15/12/2023
160E10100
PrismaSeT P Active - After sales tools www.se.com
Practical information
Our circuit breakers have trip units with a built-in ammeter
(see Micrologic Catalog).
Their use eliminates the need for installing a CT on the busbars.
DD383909.eps
Version : 14 - 15/12/2023
160E10100 TOC J-5
PrismaSeT P Active - After sales tools www.se.com
Practical information
Principle of the PrismaSeT P Active solution
PD391283.eps
Note that our configuration software can be used to produce the switchboard front
panel drawings.
Source changeover system in the same cubicle.
For each source changeover configuration, various combinations of normal and
replacement source circuit breakers and switch-disconnectors are possible:
b 1 normal source/1 replacement source:
DD381617.eps
Tables in the Catalog indicate the possible combinations “normal” and “replacement”
devices according to the rating as well as the types of interlocking available for the
different types of devices.
Source changeover system in 2 combined cubicles.
Highly economical vertical configurations are possible even for the largest devices.
In this case, interlocking may be:
b mechanical by cable + motor mechanism
PD391284.eps
To define the number of modules required to install superimposed devices, all you
have to do is add up the number of modules required for each device with:
b its connections
b its cover and its partitioning.
J-6 TOC
Version : 14 - 15/12/2023
160E10100
PrismaSeT P Active - After sales tools www.se.com
Practical information
DD383910.eps
1 normal source
1 replacement source
DD210440.eps
2 normal sources
1 replacement source and coupling on busbars
Version : 14 - 15/12/2023
160E10100 TOC J-7
PrismaSeT P Active - After sales tools www.se.com
Storage recommendations
Practical information
Cubicles must be stored in upright position in a dry and ventilated location, sheltered
from rain, weather, dripping and running water, dust and chemical agents.
Apart from IP55 cubicles, never store enclosures outdoors, even under an awning or
tarp.
The cubicles should if possible be left in their packing until they are installed. In this
way they are protected against all risks that may be encountered on the site
(impacts, splashes, etc.).
Acceptable storage temperatures are -25 °C to +55 °C (or up to +70 °C for short
periods not exceeding 24 hours).
Given their heavy weight, cubicles should be stored on a stable, rigid and flat floor to
avoid any risk of tipping during storage or handling.
J-8 TOC
Version : 14 - 15/12/2023
160E10100
PrismaSeT P Active - After sales tools www.se.com
Packing information
Practical information
Receiving the switchboard
On receipt of the equipment and before handling it, check that the cases and packing
materials used for transportation have not been damaged and that all items on the
packing list have been effectively delivered.
b Even if the packing appears to be in good condition, do not hesitate to unpack the
equipment in the presence of an authorised transport agent.
b Check the contents and weights of the shipping units. Thoroughly check the
equipment to make sure that no damage or shocks have occurred that could impair
insulation or operation.
b If necessary, check that the information on the switchboard nameplate, located on
the incoming cubicle, complies with the information indicated on the delivery slip.
b In case of damage or missing parts, inform the transport agent by registered mail.
b After this inspection, refit the plastic protective cover.
transport units comprising 2 cubicles side by side. Shipping units may exceptionally
comprise 3 cubicles (see precautions given in the "On-site handling" chapter).
Each shipping unit is marked with:
b project number
b weight
b packing unit information (packing unit number and total quantity)
b position of the centre of gravity
b storage and handling instructions.
Standard packing
The cubicles are protected by a plastic cover in a crate.
The following accessories are attached inside the switchboard:
b installation accessories (lifting/fixing cross-members and external fixing lugs)
b preliminary installation accessories: plinth raisers
b horizontal busbar joints (if required)
b additional nuts and bolts and other mounting hardware
b panels to be fitted after on-site connection: canopies, roof panels, gland plates
b a set of drawings
b device user manuals
DD383912.eps
Version : 14 - 15/12/2023
160E10100 TOC J-9
PrismaSeT P Active - After sales tools www.se.com
Practical information
Final unpacking of the equipment will preferably take place just before the
DD383914.eps
As a general guideline, the weight of an average 3200 A cubicle is around 400 kg.
Cubicles should always be handled in the upright position with care, if possible
by 2 persons. There is a risk of overtipping the cubicle due to the high position of
the centre of gravity.
When moving the cubicles, always turn slowly and smoothly, avoiding all bumps and
jerks. Enclosures moved using a forklift truck must be lifted carefully and held in
Wooden beams (or framework stabilizers) are generally attached to the base of the
cubicle framework. This allows the cubicles to be moved using a pallet mover or
forklift truck.
d The forks must be placed symmetrically with respect to the cubicle's axis so as
not to distort the base of the frame.
Dd381333.eps
For cubicles fitted with a plinth, the front and rear base panels must be removed to
allow insertion of the pallet mover forks.
Cubicles must be lifted with care and held in place during transport by strapping
them onto the handling machine, especially for large distances or bumpy terrain.
J-10 TOC
Version : 14 - 15/12/2023
160E10100
PrismaSeT P Active - After sales tools www.se.com
Practical information
Handling by the top
Dd381541.eps
If cranes or overhead hoists are used, only slings that are sufficiently strong
and in good condition should be used.
b The slings must be attached to the 4 cubicle lifting lugs.
b Adjust the length of the slings according to the switchboard dimensions so that the
angle formed does not exceed the angle indicated below depending on the
switchboard weight. When 2 switchgear cubicles are combined, a lifting beam must
be used.
b Never tilt the cubicle during handling.
b Take care to equally distribute the load on the 4 rings.
DD383915.eps
DD210574.eps
In the special case of an assembly with more than 2 cubicles, you must:
b first of all move the assembly in its original packing as close as possible to where
it is to be installed
b use a lifting beam and slings to support the switchboard from underneath.
Version : 14 - 15/12/2023
160E10100 TOC J-11
PrismaSeT P Active - After sales tools www.se.com
Transport
Practical information
The cubicles must be loaded vertically (stacking strongly discouraged).
After loading, check that the equipment is firmly secured in the truck to avoid any risk
of damage during transport.
DD383917.eps
J-12 TOC
Version : 14 - 15/12/2023
160E10100
PrismaSeT P Active- After sales tools www.se.com
Five different Catalog numbers offer 27 width possibilities (1200 to 3050 mm) for 400
50 and 600 mm deep cubicles.
b Two Catalog numbers each include 2 end-pieces for handling bases for 400 and
600 mm deep cubicles respectively and the corresponding mounting hardware.
b Three Catalog numbers each include 2 lengths for the sides of handling bases for
L 1200 to 3050 mm wide cubicles respectively and the corresponding mounting
hardware.
Handling bases can be used for both side-by-side and back-to-back cubicle
LVS08714 combinations.
In this case, the mounting hardware for one of the sets is used.
Designation Cat. no.
DD383849.eps
LVS08716
DD380652.eps
Lifting reinforcement kit b Kit LVS08722 is recommended for lifting combined cubicles and can be used
together with handling base end-pieces LVS08714 for severe transport or handling
DD383838.eps
conditions.
b Catalog number LVS08722 includes 3 reinforcement brackets for 400 or 600 mm
deep cubicles and the corresponding mounting hardware.
Designation Cat. no.
Lifting reinforcement kit for combined cubicles W = 400/600 mm LVS08722
Version : 14 - 15/12/2023
160E10200 TOC J-13
PrismaSeT P Active- After sales tools www.se.com
Practical information
PrismaSeT P switchboards come equipped with a special interface that allows them
to be directly connected to Canalis KT trunking.
The electrical connection between the Canalis KT trunking and the PrismaSeT P
switchboard is just as easy to carry out as jointing between two busbar trunking
sections.
The Canalis KT interface is totally integrated in the PrismaSeT P switchboard
volume.
It comprises a Canalis KT joint block and interface/circuit breaker connection
terminals.
DD383919.eps
b A red plastic washer that is ejected when the head breaks provides visual
evidence that the joint tightening operation has been carried out correctly.
b For dismantling or maintenance operations, a second head is available on the nut
and can be retightened using a conventional torque wrench. The recommended
tightening torque is then 60 Nm.
b Reassemble the roof.
Sealing kit
b In order to retain the original IP index, use the roof sealing kit ordered with the
busbar trunking. This kit guarantees an IP52 degree of protection at the trunking
passage.
b The kit is installed by cutting out the roof of the PrismaSeT P switchboard.
This cut-out, which is the same dimension for all Canalis KT busbar trunking ratings,
is made using the template delivered with the sealing kit.
J-14 TOC
Version : 14 - 15/12/2023
160E10200
PrismaSeT P Active- After sales tools www.se.com
Practical information
To ensure protection of persons, first connect the switchboard protective conductor
to the earth electrode.
b Tie the cables as close as possible to the connections to avoid any mechanical
stresses on the device terminals. When not using cable glands, also attach the
cables near to the cubicle entry point.
b Cables must never be in contact with or passed between live conductors.
b Sharp edges of the framework must be protected where cables pass to avoid
b damaging the conductors.
b Comply with a minimum radius of curvature of 6 to 8 times the cable outside
b diameter.
b All power connections must be made with class 8.8 mounting hardware and
b elastic contact washers, tightened to the torque indicated in the table below.
b When connecting aluminium cables to copper terminals, use bimetal lugs or
b interfaces.
b Separate the different types of circuits into separate cable bundles (power, control,
b 48 V, 24 V, DC, AC, etc).
Cable bundles
Version : 14 - 15/12/2023
160E10200 TOC J-15
PrismaSeT P Active- After sales tools www.se.com
Practical information
Connection via the top
DD383380.eps
of protection (IP).
b Refit the bottom plate.
b Run the cables through the glands or grommets.
b Run the cables in the intended compartments and secure them to cable tie-bars
every 400 mm.
b If cable glands are not used, it may be easier to prepare the cable terminations
outside the switchboard (e.g. lug crimping) and then to drop them inside the cubicle
having first disassembled the bottom removable cross-member.
Covering an incomer
For MasterPact MTZ2 / MTZ1 /NS1600b-3200 / ComPacT NS630b-1600
b Disassemble the cover plate to access to the device connection terminals.
b Connect the cables, respecting the required electrical clearances.
b Cut out the part of the cover disassembled in order to let the cables pass through
it, while preserving the necessary degree of protection.
J-16 TOC
Version : 14 - 15/12/2023
160E10200
PrismaSeT P Active- After sales tools www.se.com
Practical information
Connecting to terminal extension bars
Dd380794.eps
Version : 14 - 15/12/2023
160E10200 TOC J-17
PrismaSeT P Active- After sales tools www.se.com
Preventive maintenance
Maintenance
Frequency
b The frequency of preventive maintenance depends primarily on the operating
conditions of the electrical switchboard.
b For operating conditions found in normal environments, the frequency should be
as indicated in the recommended calendar.
b It may be extended if the switchboard is used in a particularly clean environment
and not in an intensive manner.
b It must be reduced if the switchboard is used in a particularly aggressive
environment (dust, humidity, corrosive vapours, heat) or is used intensively.
b Recommended calendar
Type Action Frequency
General inspection Visual checks and general Once a year
cleaning.
Visual check of busbars.
Running tests
Maintenance on functional units Inspection of the connections Every 5 years
Maintenance of ventilation Cleaning of filters Every 6 months
system
Maintenance of devices According to the respective handbooks
General recommendations
Before any intervention on the connections, switch off the functional unit, remove the
protective screens and the partitioning sheets and boxes.
b For interventions on the connections, refer to chapter "Connections", profession
Install.
b When reassembling the connections:
v use new screws, washers, nuts of the same type (class 8.8)
v tighten to the defined torque (refer to the tightening torques table in the chapter
"Connection/Tools required")
v apply varnish.
Method of inspection of the electrical connections
b Connections by lugs or screwed bars: presence of varnish, colour changes of a
copper bar.
b Connections by cage type terminals: if necessary, re-screw to the torque defined
by the manufacturer to compensate for a possible creep.
Please ensure that you consult the "General" chapter section dealing with
safety instructions.
J-18 TOC
Version : 14 - 15/12/2023
160E10200
PrismaSeT P Active- After sales tools www.se.com
Preventive maintenance
Maintenance
General inspection
DD382159.eps
Version : 14 - 15/12/2023
160E10200 TOC J-19
PrismaSeT P Active- After sales tools www.se.com
Corrective maintenance
Maintenance
General
General recommendations
b Before any intervention on the connections, switch off the cubicle, remove the
protective screens and the partitioning sheets and boxes.
b When reassembling the connections:
b use new screws, washers, nuts of the same type (class 8.8)
b tighten to the defined torque (refer to the tightening torque table in chapter
"Connection/Connection of power cables")
b apply varnish.
Hot point
Screwed connection
b Identify the cause: generally a loosening connection.
b Dismantle the assembly.
b Clean and rub down surfaces in contact (e.g. sandpaper N° 400).
b Set the connection up.
J-20 TOC
Version : 14 - 15/12/2023
160E10200
PrismaSeT P Active- After sales tools www.se.com
Version : 14 - 15/12/2023
160E10200 TOC J-21
Schneider Electric Industries SAS
12-2023
DESW026EN