DN 60979

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

DN-60979:A

NP-200 Series
Addressable Photoelectric
Detectors
Addressable Devices

General
The NOTIFIER NP-200 Series intelligent plug-in smoke detectors
are designed for both performance and aesthetics. A new modern,
sleek, contemporary design and enhanced optical sensing chamber
is engineered to sense smoke produced by a wide range of combus-
tion sources in accordance with more stringent code standards.
Exclusively for use with NOTIFIER’s FireWarden Series Addressable
Fire Alarm Control Panels, the NP-200 Series point ID capability
allows each detector’s address to be set with rotary, decimal
address switches, providing exact detector location for emergency
personnel quickly locate a fire during its early stages, potentially
saving precious rescue time while also reducing property damage.
Two LEDs on each sensor light to provide a local, visible sensor indi-
cation. Dual electronic thermistors add 135°F (57°C) fixed tempera-
ture thermal sensing on the NP-200T. The NP-200R is a remote test
capable detector for use with DNR Series duct detector housings.

Features
NP-200 in B300-6 Base
SLC LOOP
• Two-wire loop connection. Mount base (all base types) on an electrical backbox which is at
• Unit uses base for wiring. least 1.5" (3.81 cm) deep. For a chart of compatible junction boxes,
see DN-60054.
ADDRESSING NOTE: Because of the inherent supervision provided by the SLC loop,
• Addressable by device. end-of-line resistors are not required. Wiring “T-taps” or branches are
• Rotary, decimal addressing: Please refer to the FireWarden panel permitted for Style 4 (Class B) wiring. NP-200R mounts in a DNR/DNRW
duct detector housing.
manuals for device capacity.
ARCHITECTURE Operation
• New modern profile for improved aesthetics. Each NP-200 Series detector uses one possible addresses on the
• Unique single-source design to respond quickly and dependably FireWarden Signaling Line Circuit (SLC). It responds to regular polls
to a broad range of fires. from the system and reports its type and status.
• Integral communications and built-in type identification.
• Built-in tamper-resistant feature. Detector Sensitivity Test
• Removable cover and insect-resistant screen for simple field Each detector can have its sensitivity tested (required per NFPA 72,
cleaning. Chapter 14 on Inspection, Testing and Maintenance) when installed/
connected to an FireWarden Series addressable fire alarm control
OPERATION panel. The results of the sensitivity test can be printed off the Fire-
• Designed to meet UL 268 7th Edition. Warden Series for record keeping.
• Factory preset at 1.5% nominal sensitivity for panel alarm thresh-
old level. Specification
• Visible LED “blinks” when the unit is addressed (communicating Voltage range: 15 – 32 VDC (peak).
with the fire panel) and latches on in alarm.
Standby current: 200 μA @ 24 VDC.
• Low standby current.
Max current: 4.5 mA @ 24 VDC (latched “ON”).
MECHANICALS
Air velocity: 4,000 ft./min. (20 m/sec.) maximum.
• Sealed against back pressure.
Sensitivity: UL Applications: 0.5% to 4.0% per foot obscuration
• Mounts to: single-gang box, 3.5" (8.89 cm) or 4.0" (10.16 cm)
octagonal box, or 4.0" (10.16 cm) square electrical box (with or Size: 2.0" (5.3 cm) high; base determines diameter.
without a mud ring - not included). – B300-6: 6.1" (15.6 cm) diameter.
OPTIONS – B501: 4" (10.2 cm) diameter.
• Remote LED output connection, RA100Z. For a complete list of detector bases see DN-60981.
Shipping weight: 3.4 oz. (95 g).
Installation Operating temperature range:
NP-200 series plug-in detectors use a detachable mounting base to • NP-200: 0°C to 50°C (32°F to 122°F);
simplify installation, service and maintenance. • NP-200T: 0°C to 38°C (32°F to 100°F).
• NP-200R: installed in a DNR(A)/DNRW -20°C to 70°C (-4°F to
158°F).

DN-60979:A • 3/29/18 — Page 1 of 3


Relative humidity: 10%-93%, non-condensing. B200S-WH: White, Intelligent addressable sounder base capable of
producing sound output in high or low volume with ANSI Temporal 3,
Listings ANSI Temporal 4, continuous tone, marching tone, and custom tone.
Uses FlashScan protocol. (CSFM: 7300-1653:0213 Pending)
Listings and approvals below apply to the NP200 Series detectors.
In some cases, certain detectors may not be listed by certain B200S-IV: Ivory, Intelligent addressable sounder base capable of
approval agencies, or listing may be in process. Consult factory for producing sound output in high or low volume with ANSI Temporal 3,
latest listing status. ANSI Temporal 4, continuous tone, marching tone, and custom tone.
Uses FlashScan protocol. . (CSFM: 7300-1653:0213 Pending)
• UL/ULC Listed: S911
B200SA-WH: Same as B200S-WH, ULC listing.
• CSFM: 7272-0028:0503
B200SA-IV: Same as B200S-IV, ULC listing.
• FM Approved
B200SCOA-WH: White, Intelligent, programmable sounder base in
Product Line Information English/French (required in Canada for ULC applications with SO
Series detector applications.
NOTE: Detectors must be mounted to one of the Intelligent Bases listed
below. B200SCOA-IV: Ivory Intelligent, programmable sounder base in
English/French (required in Canada for ULC applications with SO
NOTE: “IV” suffix indicates FlashScan® and CLIP device. Series detector applications, ULC listing.
NP-200: White, Addressable photoelectric detector; B300-6 base B200S-LF-WH: White, Low Frequency Intelligent, programmable
included. FlashScan only. sounder base. Produces a fundamental frequency of 520 Hz +/-
NP-200-IV: Ivory, Addressable photoelectric detector; B300-6 base 10% with a square wave or its equivalent; designed to meet the
included. NFPA 72 sleeping space requirement. (CSFM: 7300-1653:0238
Pending)
NP-200T: White, Same as NP-200 but with thermal element; B300-6
base included. FlashScan only. B200S-LF-IV: Ivory, Low Frequency Intelligent, programmable
sounder base. Produces a fundamental frequency of 520 Hz +/-
NP-200T-IV: Ivory, Same as NP-200 but with thermal element;
10% with a square wave or its equivalent; designed to meet the
B300-6 base included.
NFPA 72 sleeping space requirement. (CSFM: 7300-1653:0238
NP-200R: White, Remote test capable addressable photoelectric Pending)
detector for use with DNR(A)/DNRW. FlashScan only.
B200SR-WH: White, Intelligent sounder base capable of producing
NP-200R-IV: Ivory, Remote test capable addressable photoelectric sound output with ANSI Temporal 3 or continuous tone. Intended for
detector; for use with DNR(A)/DNRW. retrofit applications. (CSFM: 7300-1653:0213 Pending)
INTELLIGENT BASES B200SR-IV: Ivory, Intelligent sounder base capable of producing
sound output with ANSI Temporal 3 or continuous tone. Intended for
NOTE: For details on intelligent bases, see DN-60981.
retrofit applications. (CSFM: 7300-1653:0213 Pending)
B300-6: White, 6” base, standard flanged low-profile mounting base.
(CSFM: 7300-1653:0109 Pending) B200SRA-WH: Same as B200SR-WH with, ULC listing.

B300-6-IS: White, 6” base isolator. (CSFM: 7300-1653:0109 Pend- B200SRA-IV: Same as B200SR-IV in Ivory color, ULC listing.
ing) B200SR-LF-WH: White, Low Frequency Intelligent, programmable
B300-6-IV: Ivory,6” base, standard flanged low-profile mounting sounder base. Produces a fundamental frequency of 520 Hz +/-
base. (CSFM: 7300-1653:0109 Pending) 10% with a square wave or its equivalent; designed to meet the
NFPA 72 sleeping space requirement. Intended for retrofit applica-
B300A-6: Same as B300-6, ULC listed. tions. (CSFM: 7300-1653:0238 Pending)
B300A-6-IV: Ivory, 6” standard flanged low-profile mounting base, B200SR-LF-IV: Ivory, Low Frequency Intelligent, programmable
ULC listed. sounder base. Produces a fundamental frequency of 520 Hz +/-
B300-6-BP: Bulk pack of B300-6, package contains 10 10% with a square wave or its equivalent; designed to meet the
NFPA 72 sleeping space requirement. Intended for retrofit applica-
B501-WHITE: White, 4” standard European flangeless mounting tions. (CSFM: 7300-1653:0238 Pending)
base. UL/ULC listed. (CSFM: 7300-1653:0109 Pending)
B501-BL: Black, 4” standard European flangeless mounting base. MOUNTING KITS AND ACCESSORIES
UL/ULC listed. (CSFM: 7300-1653:0109 Pending) TR300: White, replacement flange for B210LP(A) base.
B501-IV: Ivory color, 4” standard European flangeless mounting TR300-IV: Ivory, replacement flange for B210LP(A) base.
base. UL/ULC listed. (CSFM: 7300-1653:0109 Pending) RA100Z(A): Remote LED annunciator. 3 – 32 VDC. Mounts to a
B501BP: Bulk pack of B501-WHITE contains 10. U.S. single-gang electrical box. For use with B501(A) and B300-
6(A).
B224RB-WH: White, relay base. (CSFM: 7300-1653:0216 Pending)
M02-04-00: Test magnet.
B224RB-IV: Ivory, relay base. (CSFM: 7300-1653:0216 Pending)
M02-09-00: Test magnet with telescoping handle.
B224RBA-WH: White, relay base, ULC listing.
B224RBA-IV: Ivory, relay base, ULC listing.
B224BI-WH: White, isolator detector base. (CSFM: 7300-
1653:0216 Pending)
B224BI-IV: Ivory isolator detector base. (CSFM: 7300-1653:0216
Pending)
B224BIA-WH: White, isolator detector base, ULC listing.
B224BIA-IV: Ivory isolator detector base, ULC listing.

DN-60979:A • 3/29/18 — Page 2 of 3


NOTIFIER® and FIREWARDEN® are a registered trademark of Honeywell
International Inc.

©2018 by Honeywell International Inc. All rights reserved. Unauthorized use of this
document is strictly prohibited.

This document is not intended to be used for installation purposes.


We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.

For more information, contact Notifier. Phone: (800) 627-3473, FAX: (203) 484-7118.
www.notifier.com

Page 3 of 3 — DN-60979:A • 3/29/18