DN 60979
DN 60979
DN 60979
NP-200 Series
Addressable Photoelectric
Detectors
Addressable Devices
General
The NOTIFIER NP-200 Series intelligent plug-in smoke detectors
are designed for both performance and aesthetics. A new modern,
sleek, contemporary design and enhanced optical sensing chamber
is engineered to sense smoke produced by a wide range of combus-
tion sources in accordance with more stringent code standards.
Exclusively for use with NOTIFIER’s FireWarden Series Addressable
Fire Alarm Control Panels, the NP-200 Series point ID capability
allows each detector’s address to be set with rotary, decimal
address switches, providing exact detector location for emergency
personnel quickly locate a fire during its early stages, potentially
saving precious rescue time while also reducing property damage.
Two LEDs on each sensor light to provide a local, visible sensor indi-
cation. Dual electronic thermistors add 135°F (57°C) fixed tempera-
ture thermal sensing on the NP-200T. The NP-200R is a remote test
capable detector for use with DNR Series duct detector housings.
Features
NP-200 in B300-6 Base
SLC LOOP
• Two-wire loop connection. Mount base (all base types) on an electrical backbox which is at
• Unit uses base for wiring. least 1.5" (3.81 cm) deep. For a chart of compatible junction boxes,
see DN-60054.
ADDRESSING NOTE: Because of the inherent supervision provided by the SLC loop,
• Addressable by device. end-of-line resistors are not required. Wiring “T-taps” or branches are
• Rotary, decimal addressing: Please refer to the FireWarden panel permitted for Style 4 (Class B) wiring. NP-200R mounts in a DNR/DNRW
duct detector housing.
manuals for device capacity.
ARCHITECTURE Operation
• New modern profile for improved aesthetics. Each NP-200 Series detector uses one possible addresses on the
• Unique single-source design to respond quickly and dependably FireWarden Signaling Line Circuit (SLC). It responds to regular polls
to a broad range of fires. from the system and reports its type and status.
• Integral communications and built-in type identification.
• Built-in tamper-resistant feature. Detector Sensitivity Test
• Removable cover and insect-resistant screen for simple field Each detector can have its sensitivity tested (required per NFPA 72,
cleaning. Chapter 14 on Inspection, Testing and Maintenance) when installed/
connected to an FireWarden Series addressable fire alarm control
OPERATION panel. The results of the sensitivity test can be printed off the Fire-
• Designed to meet UL 268 7th Edition. Warden Series for record keeping.
• Factory preset at 1.5% nominal sensitivity for panel alarm thresh-
old level. Specification
• Visible LED “blinks” when the unit is addressed (communicating Voltage range: 15 – 32 VDC (peak).
with the fire panel) and latches on in alarm.
Standby current: 200 μA @ 24 VDC.
• Low standby current.
Max current: 4.5 mA @ 24 VDC (latched “ON”).
MECHANICALS
Air velocity: 4,000 ft./min. (20 m/sec.) maximum.
• Sealed against back pressure.
Sensitivity: UL Applications: 0.5% to 4.0% per foot obscuration
• Mounts to: single-gang box, 3.5" (8.89 cm) or 4.0" (10.16 cm)
octagonal box, or 4.0" (10.16 cm) square electrical box (with or Size: 2.0" (5.3 cm) high; base determines diameter.
without a mud ring - not included). – B300-6: 6.1" (15.6 cm) diameter.
OPTIONS – B501: 4" (10.2 cm) diameter.
• Remote LED output connection, RA100Z. For a complete list of detector bases see DN-60981.
Shipping weight: 3.4 oz. (95 g).
Installation Operating temperature range:
NP-200 series plug-in detectors use a detachable mounting base to • NP-200: 0°C to 50°C (32°F to 122°F);
simplify installation, service and maintenance. • NP-200T: 0°C to 38°C (32°F to 100°F).
• NP-200R: installed in a DNR(A)/DNRW -20°C to 70°C (-4°F to
158°F).
B300-6-IS: White, 6” base isolator. (CSFM: 7300-1653:0109 Pend- B200SRA-IV: Same as B200SR-IV in Ivory color, ULC listing.
ing) B200SR-LF-WH: White, Low Frequency Intelligent, programmable
B300-6-IV: Ivory,6” base, standard flanged low-profile mounting sounder base. Produces a fundamental frequency of 520 Hz +/-
base. (CSFM: 7300-1653:0109 Pending) 10% with a square wave or its equivalent; designed to meet the
NFPA 72 sleeping space requirement. Intended for retrofit applica-
B300A-6: Same as B300-6, ULC listed. tions. (CSFM: 7300-1653:0238 Pending)
B300A-6-IV: Ivory, 6” standard flanged low-profile mounting base, B200SR-LF-IV: Ivory, Low Frequency Intelligent, programmable
ULC listed. sounder base. Produces a fundamental frequency of 520 Hz +/-
B300-6-BP: Bulk pack of B300-6, package contains 10 10% with a square wave or its equivalent; designed to meet the
NFPA 72 sleeping space requirement. Intended for retrofit applica-
B501-WHITE: White, 4” standard European flangeless mounting tions. (CSFM: 7300-1653:0238 Pending)
base. UL/ULC listed. (CSFM: 7300-1653:0109 Pending)
B501-BL: Black, 4” standard European flangeless mounting base. MOUNTING KITS AND ACCESSORIES
UL/ULC listed. (CSFM: 7300-1653:0109 Pending) TR300: White, replacement flange for B210LP(A) base.
B501-IV: Ivory color, 4” standard European flangeless mounting TR300-IV: Ivory, replacement flange for B210LP(A) base.
base. UL/ULC listed. (CSFM: 7300-1653:0109 Pending) RA100Z(A): Remote LED annunciator. 3 – 32 VDC. Mounts to a
B501BP: Bulk pack of B501-WHITE contains 10. U.S. single-gang electrical box. For use with B501(A) and B300-
6(A).
B224RB-WH: White, relay base. (CSFM: 7300-1653:0216 Pending)
M02-04-00: Test magnet.
B224RB-IV: Ivory, relay base. (CSFM: 7300-1653:0216 Pending)
M02-09-00: Test magnet with telescoping handle.
B224RBA-WH: White, relay base, ULC listing.
B224RBA-IV: Ivory, relay base, ULC listing.
B224BI-WH: White, isolator detector base. (CSFM: 7300-
1653:0216 Pending)
B224BI-IV: Ivory isolator detector base. (CSFM: 7300-1653:0216
Pending)
B224BIA-WH: White, isolator detector base, ULC listing.
B224BIA-IV: Ivory isolator detector base, ULC listing.
©2018 by Honeywell International Inc. All rights reserved. Unauthorized use of this
document is strictly prohibited.
For more information, contact Notifier. Phone: (800) 627-3473, FAX: (203) 484-7118.
www.notifier.com