SERVICE VOLTAGE : 230 VOLTS, 60 HERTZ, 2-WIRE, SINGLE PHASE

2 )

ELECTRICAL SPECIFICATIONS
SIZE OF WIRE & TYPE (mm CONDUIT SIZE
CIRCUIT NO. OF VOLTAGE VOLTAGE CURRENT PROTECTION
LOAD DESCRIPTION
NOS. OUTLETS (Volts) AMPERE (Amperes) Per Circuit EGC (mm)
FEEDER CONDUCTOR
2-2.00mm 2THHN
1 LIGHTING OUTLETS (1ST FLOOR) 9 230 900 3.91 15 AT - 15mmØ uPVC
STRANDED COPPER WIRE

2-2.00mm 2THHN
-
GENERAL NOTES 2 LIGHTING OUTLETS (2ND FLOOR) 9 230 900 3.91 15 AT 15mmØ uPVC
STRANDED COPPER WIRE

A B C D A B C D 3 CONVENIENCE OUTLETS (1ST FLOOR) 7 230 1260 5.48 20 AT


2-3.50mm 2THHN
STRANDED COPPER WIRE
1-3.50mm 2THHN
STRANDED COPPER WIRE
15mmØ uPVC

2-3.50mm 2THHN 1-3.50mm 2THHN


1. ALL ELECTRICAL WORKS HEREIN SHALL BE EXECUTED IN ACCORDANCE 4 CONVENIENCE OUTLETS (2ND FLOOR) 9 230 1620 7.04 20 AT
STRANDED COPPER WIRE STRANDED COPPER WIRE
15mmØ uPVC

WITH THE 2009 EDITION OF THE PHILIPPINE ELECTRICAL CODE (PEC), THE 11800 11800
2-3.50mm 2THHN 1-3.50mm 2THHN
5 LAUNDRY CIRCUIT 1 230 1500 6.52 20 AT 15mmØ uPVC
NEW ELECTRICAL ENGINEERING LAW (RA 7920), LAWS AND ORDINANCES 4000 3800 4000 4000 3800 4000
STRANDED COPPER WIRE STRANDED COPPER WIRE

OF THE LOCAL GOVERNMENT UNIT AND RULES AND REGULATIONS OF THE TOTAL 6180
LOCAL ELECTRICAL POWER UTILITY COMPANY. 2400 1600 2200 1600 2400 1600 1000 3000 1000 2800 1000 3000
2. SERVICE VOLTAGE SHALL BE 230 V, 60 Hz, 2-WIRE, SINGLE PHASE. LOAD COMPUTATION SERVICE ENTRANCE CONDUCTOR
3. NO BRANCH CIRCUIT CONDUCTORS SHALL BE LOADED MORE THAN 80% OF LIGHTINGS T O T A L = 1800 VA TOTAL COMPUTED CURRENT:
ITS RATED AMPACITY. I t = N VA = N Amps.

1000

1000
4. ALL CONDUIT SIZES ARE BASED ON INSIDE DIAMETERS. = 230 Volts
CONVENIENCE OUTLETS T O T A L 2880 VA
5. PROVIDE 15mmØ STUB-UP WITH CAP INSIDE CEILING FOR ALL 20 AMP. USE 2- 14.0mm2THW STRANDED COPPER WIRE IN
4 4

2150
SPARE BRANCH CIRCUIT ON FLUSH MOUNTED PANEL BOARD. = 32mmØ PVC PIPE
S1 S1 S1 LAUNDRY CIRCUIT T O T A L 1500 VA

1150

1300
6. PANELBOARD SHALL BE READILY ACCESSIBLE, THAT NO OBSTACLE 6180 VA
GROUNDING CONDUCTOR
SHOULD BLOCK ACESS TO THE PANEL. USE 1-8.0mm2 TW STRANDED COPPER WIRE(GREEN COLOR)

2500
APPLICATION OF DEMAND FACTORS
7. WIRE NUTS SHALL BE USED FOR SPLICING OF WIRE NOT MORE THAN 8.0

3150

3150
S1 S1 S1
sq.mm. FOR LARGER WIRED SOLDERLESS CONNECTOR SHALL BE USED LIGHTING & CONVENIENCE OUTLETS MAIN DISCONNECTING MEANS

1500

1200
FIRST 3,000 @ 100% = N VA
INSULATED WITH RUBBER AND PLASTIC TAPES. REMAINDER @ 35% = N VA INVERSE TIME CIRCUIT BREAKER:
S1 S1 S1 OTHER LOADS
8. ALL ELECTRICAL EQUIPMENT TO BE USED HEREIN SHALL BE EQUIPPED NONE = 0 VA I t = N VA = N Amps.

3250
WITH PROPER GROUNDING. ALL GROUND WIRED SHALL BE PROPERLY

650
230 Volts
S2 S2 S2 N VA
IDENTIFIED.
3 S1
1
S1
1
S1
1
3 2 S1
DOWN
S3W 2 S1
DOWN
S3W 2 S1
DOWN
S3W
USE 1-60A, 2PST, 240V MOLDED CASE CIRCUIT BREAKER

2100
1850
9. UNLESS OTHERWISE SPECIFIED MOUNTING HEIGHTS SHALL BE MEASURED
FROM LINE OF REFERNECE TO CENTER OF DEVICE AS FOLLOWS:
UP UP UP
a. LIGHT CONTROL SWITCH - 1.40m ABOVE FLOOR @ S2 S1
S3W S2 S1
S3W S2 S1S3W

11500

11500
b. CONVENIENCE OUTLET CENTER

3200

3200
- 0.30m ABOVE FLOOR @
C. SPECIAL PURPOSE SCHEDULE OF LOADS COMPUTATIONS

1950
CENTER FOR NON-WEATHER
OUTLET PROOF OUTLET
d. WALL TELEPHONE - 0.20m ABOVE COUNTER @ N T S
e.
f.
BELL AND BUZZER
PUSH BUTTON -
CENTER FOR KITCHEN
1.40m ABOVE FLOOR LINE FOR
2 2 S1 S1 S1

5000
g PANELBOARDS, FIRE BATHROOMS
ALARM,

5900
- AS REQUIRED BY EQUIPMENT
CONTROL PANEL

3150

3150
- 0.30m ABOVE FLOOR @
CABINETS, CENTER

4150
NON-FUSIBLE - 2.20m ABOVE FLOOR FINISH
DISCONNECT - 1.40m ABOVE FLOOR FINISH
SWITCH. - 1.80m ABOVE FLOOR @
1 1
S2 S2 S2

CENTER UNLESS OTHERWISE

1000

1000
REQUIRED BY FIELD
RAMP UP RAMP UP RAMP UP
CONDITIONS
10. ELECTRICAL RUN SHALL BE DONE ON THE NEARES DISTANCE POSSIBLE
WITH ALL WIRING INSTALLATION CONCEALED FROM VIEW. PROVIDE
JUNCTION BOXED OR PULL BOXES OF PROPER SIZE ALTHOUGH NOT
INDICATED IN THE PLANS.
11. ALL ELECTRICAL WORK SHALL BE DONE UNDER THE IMMEDIATE
SUPERVISION OF A DULY LICENSED ELECTRICAL ENGINEER/
GROUND FLOOR LIGHTING LAYOUT SECOND FLOOR LIGHTING LAYOUT
PRACTITIONER IN CONFORMANCE WITH RA 7920.
SCALE: 1:100 SCALE: 1:100

MATERIAL SPECIFICATIONS
RISER DIAGRAM
1. ALL WIRING SHALL BE IN RIGID STEEL CODUIT (R.S.C.) FOR SERVICE LINES
AND UNPLASTICIZED POLYVYNIL CHLORIDE, RIGID UP.V.C.).
2. MINIMUM SIZE OF CONDUIT SHALL BE 15mmØ FOR RIGID STEEL CONDUIT A B C D A B C D M
(R.S.C) AND 15mmØ FOR UNPLASTICIZED POLYVYNIL CHLORIDE, RIGID
(UP.V.C.). 11800 11800
3. UNLESS OTHERWISE SPECIFIED, BRANCH CIRCUIT CONDUCTORS SHALL BE
COPPER TYPE THHN, 90°C, 600 VOLT INSULATION. 4000 3800 4000 4000 3800 4000
4. THE MINIMUM SIZE OF WIRE SHALL BE 3.5sq.mm. (#12 AWG) FOR POWER 2400 1600 2200 1600 2400 1600 1000 3000 1000 2800 1000 3000
AND 2.0sq.mm. (#14 AWG) FOR LIGHTING.
5. CIRCUIT BREAKERS SHALL BE U.S. MADE "G.E." OR "WESTINGHOUSE" OR
JAPAN MADE "FUJI" BRAND, BUT ONLY ONE BRAND THRU-OUT.
6. ALL CIRCUIT BREAKER FOR LIGHTING AND CONVENIENCE OUTLETS SHALL
1000

1000
BE COMMERCIAL BOLT-ON TYPE, 10KAIC FOR BRANCHES AND INDUSTRIAL WP WP WP

4 4

2150
TYPE 18KAIC FOR MAIN AND MOTORS.
7. GENERAL USE RECEPTACLE SHALL BE RATED 20A, 220 VOLT GROUNDING
1150

R R R

1300
TYPE PARALLEL SLOTS. RECEPTACLE USED BY WATER HEATER, ACU & 5 5 5 1
RANGE MUST HAVE GROUND FAULT CIRCUIT INTERRUPTOR (GFCI).

2500
3150

3150
8. ALL UTILITY, JUNCTION BOZES AND PULL BOXES SHALL BE PVC WITH
1500

1200
REQUIRED THICKNESS IN CONFORMANCE WITH THE LATEST EDITION OF
P.E.C. 2 3
9. PANELBOARDS AND OVERCURRENT PROTECTION ENCLOSURES SHALL BE

3250
650
NEMA-1 FOR INDOOR USE, UNLESS OTHERWISE SPECIFIED ON PLANS. 4 4 4

10. ALL MATERIALS TO BE USED SHALL BE BRAND NEW AND OF APPROVED 3 3 3 3


3 DOWN DOWN DOWN
4 5

2100
1850

TYPE FOR THE PURPOSE AND LOCATION WITH PROPER FITTINGS AND
SUPPORT. UP UP UP
11500

11500
3200

3200
WP WP WP

LEGEND

1950
ACU
2 WP WP WP 2
5000

T.V.

5900
TEL
3150

3150
B TYPICAL RISER DIAGRAM

4150
N T S

1 1
1000

1000
WP WP WP
2 RAMP UP RAMP UP RAMP UP

S1 PP

S2 LP

S3
GROUND FLOOR POWER LAYOUT SECOND FLOOR POWER LAYOUT
M
SCALE: 1:100 SCALE: 1:100

WP

ACU
G

R.A. 9266
SECTION 20 sa Arkitekto PREPARED: PROJECT TITLE AND LOCATION: APPROVED: SHEET NO.:
F.J.EBUENGA
D ARCHIT
TE E
I

Drawings and specifications duly signed, stamped or


CTS
UN

UNITED ARCHITECTS OF THE PHILIPPNES


The Integrated and Accredited Professional Organization of Architects
1975
OF

sealed, as instruments of service, are the intellectual UAP Hotline: +632 888 966 Website: https://www.united-architects.org ES
.
TH

EP
HILIPPIN
A R C H I T E C T U R E
properties and documents of the architect, whether the
#071, Brgy. 4, DM Nieves St. object for which they are made is executed or not. It shall PROPOSED THREE-DOOR 8
Centro Camalig, Albay be unlawful for any person, without the consent of the FOR YOUR PLANS AND DESIGNS
ebuengaflorjohnc@gmail.com architect or author of said documents, to duplicate or to ELECTRICAL ENGINEER APARTMENT BUILDING OWNER E1 8
09207695112
make copies of said documents for use in the repetition
of and for other projects or buildings, whether partly or
in whole.
GET AN ARCHITECT PRC NO.:
VALIDITY:
PTR NO.:
PLACE ISSUED:
DATE:
TIN:
SYSAM SUBDIVISION, PEŇAFRANCIA, DARAGA, ALBAY

You might also like