Instructions for Installation of Industrial and Commercial Inverters in Different
Scenarios
5 Flat Installation....................................................................... 25
5.1 Application scenario .............................................................................. 25
5.2 Rack preparation ................................................................................... 25
5.2.1 Rack requirements........................................................................ 25
5.2.2 Rack dimensions .......................................................................... 26
5.3 Installation spacing requirements ........................................................... 26
5.3.1 Spacing for installing an inverter ................................................... 27
5.3.2 Spacing for installing more than one inverter ................................. 27
6 Sunshade ................................................................................ 30
6.1 Top sunshade ....................................................................................... 30
6.1.1 Precautions .................................................................................. 30
6.1.2 Sunshade dimensions................................................................... 30
6.2 Flat Sunshade ....................................................................................... 33
6.2.1 Precautions .................................................................................. 33
6.2.2 Sunshade dimensions................................................................... 34
7 Appendix ................................................................................ 39
7.1 Uncovering ............................................................................................ 39
7.2 Fan Maintenance................................................................................... 39
7.3 Spacing requirements for installing other devices................................... 44
2
Instructions for Installation of Industrial and Commercial Inverters in Different
Scenarios
1 Document Overview
1.1 Introduction
1.2 Applicability
1
Instructions for Installation of Industrial and Commercial Inverters in Different
Scenarios
SG15CX-P2-LV
SG20CX-P2-LV
SG25CX-P2-LV
To ensure the safety of the persons and property of users when they use the product
and to make sure that the product is used in an optimal and efficient manner, this
manual provides users with the relevant safety information highlighted by the following
symbols.
The symbols used in this document are listed below. Please pay attention to them
while reading to make better use of this document.
Symbol Description
Indicates an imminently hazardous situation which, if
not avoided, will result in death or serious injury.
2
Instructions for Installation of Industrial and Commercial Inverters in Different
Scenarios
2 Installation Requirements
Danger
Before installing, check whether the inverter was damaged during
transportation and ensure that the inverter has no electrical connections.
Danger
Before making any electrical connections, make sure that the photovoltaic
string is covered with opaque materials or the circuit breaker on the DC side
is disconnected. Exposing the photovoltaic string to sunlight will generate
hazardous voltage!
Danger
Before performing any maintenance operations, the following steps must be
followed:
First, disconnect the AC circuit breaker on the grid side, and then
disconnect the DC switch.
Warning
The inverter can only be installed by professional technicians.
3
Instructions for Installation of Industrial and Commercial Inverters in Different
Scenarios
Caution
Danger of burns!
While the inverter is in operation, only the DC switch can be touched. Never
touch hot parts of the device (such as the radiator) during operation.
Caution
The inverter can be handled manually or by hoisting, depending on site
conditions.
Attention must be paid to the center of gravity of the inverter to avoid tilting
during handling.
When hoisting the inverter, always maintain its balance to avoid collision
with walls or other obstacles. In case of bad weather, such as heavy rain, fog,
or wind, hoisting shall be stopped.
Caution
Poor ventilation in the installation environment will affect system
performance!
The heat sink of the device must not be covered to ensure sufficient
cooling inside the device.
All electrical connections must comply with local and national electrical
standards.
The inverter can be connected to the grid only after obtaining the permission
of the local electricity department.
The inverter can be restarted only after the faults affecting the safety
4
Instructions for Installation of Industrial and Commercial Inverters in Different
Scenarios
Touching the PCB or other static-sensitive devices may cause damage to the
device.
5
Instructions for Installation of Industrial and Commercial Inverters in Different
Scenarios
The inverter can be mounted directly on a vertical rack, or be installed on the column
by using a clamp.
Please select U-beams and clamps of appropriate strength based on the weight of the
6
Instructions for Installation of Industrial and Commercial Inverters in Different
Scenarios
inverter.
Mark and punch holes in the U-beam according to the dimensions shown below.
594mm
Xmm
180mm~260mm
594mm
Xmm
180mm~260mm
848mm
Xmm
310mm
7
Instructions for Installation of Industrial and Commercial Inverters in Different
Scenarios
PV module
d b
c
Ground
Bottom
Model Top (a) Right (b) Left (d)
(c)
SG25CX-SA
500 200 650 600*
SG30/33/40/50CX
SG100/110CX
600 400 450 800*
SG136TX
*The spacing can be reduced to 200mm according to site conditions. When the
spacing is less than that specified in the table, the inverter must be lifted off the rack
before fan maintenance operations.
8
Instructions for Installation of Industrial and Commercial Inverters in Different
Scenarios
3.2.2 Precautions
The inverter shall be sited in such a way that the inverter's shadow will not block the
modules under various lighting conditions.
We recommend that you add a sunshade to the inverter to avoid exposure to the sun.
This will increase the yield and extend the life of the inverter.
9
Instructions for Installation of Industrial and Commercial Inverters in Different
Scenarios
d b
Bottom
Model Top (a) Right (b) Left (d)
(c)
SG25CX-SA
500 200 650 600*
SG30/33/40/50CX
SG100/110CX
600 400 450 800*
SG136TX
*The spacing can be reduced to 200mm according to site conditions. When the
spacing is less than that specified in the table, the inverter must be lifted off the rack
before fan maintenance operations.
10
Instructions for Installation of Industrial and Commercial Inverters in Different
Scenarios
Table 3-4 Minimum Spacing Requirements for Back-to-back Installation (Unit: mm)
SG30/33/40/50CX 500
SG36/60CX-US 500
SG100/110CX 500
SG136TX 500
SG25/30/33/36/40/50CX-P2 200
SG15/20/25CX-P2-LV 200
SG75/110/125CX-P2 600
If the spacing requirements cannot be satisfied, a baffle shall be added between the
two inverters to create a heat dissipation channel (not recommended). The baffle is
placed horizontally between the two inverters and cannot block the air outlet.
11
Instructions for Installation of Industrial and Commercial Inverters in Different
Scenarios
3.4.2 Precautions
Pay attention to the installation of the floating platform for electrical equipment. Due to
the deadweight of the platform and electrical equipment and the limited water depth on
the shore, it is necessary to select a crane with the right tonnage and lifting radius
according to the site conditions.
During installation, pay attention to protecting the floating platform to avoid collision and
damage to the anticorrosive coating.
The shadow of the photovoltaic modules on the surrounding floating body should be
taken into consideration.
We recommend that you add a sunshade to the inverter to avoid exposure to the sun.
This will increase the yield and extend the life of the inverter.
12
Instructions for Installation of Industrial and Commercial Inverters in Different
Scenarios
330mm
247.5mm
155mm
13
Instructions for Installation of Industrial and Commercial Inverters in Different
Scenarios
370mm
270mm
155mm
330mm
247.5mm
155mm
14
Instructions for Installation of Industrial and Commercial Inverters in Different
Scenarios
370mm
270mm
155mm
600mm
250mm
210mm
15
Instructions for Installation of Industrial and Commercial Inverters in Different
Scenarios
322.5mm
259mm
210mm
322.5mm
259mm
210mm
16
Instructions for Installation of Industrial and Commercial Inverters in Different
Scenarios
470.5mm
362.5mm
205.5mm
≥200mm
17
Instructions for Installation of Industrial and Commercial Inverters in Different
Scenarios
≥200mm
≥200mm
18
Instructions for Installation of Industrial and Commercial Inverters in Different
Scenarios
200mm
200mm
In order to reduce the relative displacement of the cable, the support, and the floating
body, it is necessary to fix the cable on the floating body where the inverter is located.
19
Instructions for Installation of Industrial and Commercial Inverters in Different
Scenarios
4 Wall Mounting
The following spacing requirements are set out to meet the heat dissipation,
installation, and maintenance requirements. When electricity meters, small distribution
boxes, and other devices need to be installed near the inverter, the spacing can be
designed with reference to the space requirements in the appendix.
20
Instructions for Installation of Industrial and Commercial Inverters in Different
Scenarios
SG100/110CX
600 400 450 1000 800*
SG136TX
*The spacing can be reduced to 200mm according to site conditions. When the
spacing is less than that specified in the table, the inverter must be lifted off the wall
before fan maintenance operations.
21
Instructions for Installation of Industrial and Commercial Inverters in Different
Scenarios
d d d b
22
Instructions for Installation of Industrial and Commercial Inverters in Different
Scenarios
b
d
Table 4-3 Minimum spacing for top and twin-side bottom installation (unit: mm)
Left and
Top Top and bottom Bottom
Model right
(a) spacing (b) (c)
spacing (d)
SG25CX-SA
SG30/33/40/50CX 500 650 650 300
SG36/60CX-US
SG100/110CX
600 600 450 300
SG136TX
Considering that the inverter dissipates heat through the upper and lower air
outlets, the vertical stacking installation method only supports rack
installation (where the back of the inverter is not blocked) and does not
support wall-mounting scenarios.
23
Instructions for Installation of Industrial and Commercial Inverters in Different
Scenarios
b c c d
b c c d
Top and
Top Left Middle Right Bottom
Model bottom
(a) (b) (c) (d) (f)
spacing (e)
SG25CX-SA
SG30/33/40/50CX 500 450 450 200 650 650
SG36/60CX-US
SG100/110CX
600 800 800 400 650 400
SG136TX
SG25/30/33/36/40/50CX-P2 500 600 600 600 850 650
24
Instructions for Installation of Industrial and Commercial Inverters in Different
Scenarios
5 Flat Installation
This mounting method is common in scenarios such as concrete roofs or colored steel
tile roofs of the plant, where the inverter is nearly lying flat. In such cases, the inverter
shall be installed on a flat mounting rack to meet the installation angle requirements.
Flat installation is not suitable for floating power plants.
SUNGROW provides a flat mounting rack. You can order it from SUNGROW if
necessary, or design your own according to the rack requirements.
To order a rack from SUNGROW, please provide the product model or rack code.
Model Rack No.
SG30/33/40/50CX B-B-003150
SG36/60CX-US B-B-003742
SG100/110CX B-B-003140
SG75/110/125CX-P2 B-B-005721
25
Instructions for Installation of Industrial and Commercial Inverters in Different
Scenarios
Spacing above
ground 300mm
190mm
SG75/110/125CX-P2 348mm
The following spacing requirements are proposed to satisfy the requirements of heat
dissipation, installation, and maintenance.
26
Instructions for Installation of Industrial and Commercial Inverters in Different
Scenarios
b
a
Bottom
Model Top (a) Right (b) Left (d)
(c)
SG25CX-SA
500 200 650 600*
SG30/33/40/50CX
*The spacing can be reduced to 200mm according to site conditions. When the
spacing is less than that specified in the table, the inverter must be lifted off the rack
before fan maintenance operations.
27
Instructions for Installation of Industrial and Commercial Inverters in Different
Scenarios
b
a
d
d
c
SG100/110CX
600 400 450 800
SG136TX
28
Instructions for Installation of Industrial and Commercial Inverters in Different
Scenarios
b
a
c
b
d
e c
c
a
d f
Table 5-3 Minimum spacing for front and rear installation (unit: mm)
Top and
Top Right Middle Left Bottom
Model bottom
(a) (b) (c) (d) (f)
spacing (e)
SG25CX-SA
SG30/33/40/50CX 500 200 450 450 1000 650
SG36/60CX-US
SG100/110CX
600 400 800 800 1000 400
SG136TX
SG25/30/33/36/40/50CX-P2 500 600 600 600 850 650
29
Instructions for Installation of Industrial and Commercial Inverters in Different
Scenarios
6 Sunshade
The top sunshade is suitable for vertical rack mounting and wall-mounting scenarios.
6.1.1 Precautions
In order to ensure good shading, we recommend that the front of the inverter is not
exposed to the sun.
The inverter air outlet may not be blocked.
The sunshade design and selected materials should take wind, rain, snow, shock, and
corrosion resistance into consideration.
The sunshade can be fixed on the beam or wall where the inverter is mounted.
≥100* ≥100*
Air outlet
45°air outlet
direction
≥200 (rack mounting)
≥400 (wall mounting)
≥200*
30
Instructions for Installation of Industrial and Commercial Inverters in Different
Scenarios
45°air outlet
direction
≥200 (rack mounting)
≥400 (wall mounting)
≥200*
45°air outlet
direction
≥200 (rack mounting)
≥400 (wall mounting)
≥200*
31
Instructions for Installation of Industrial and Commercial Inverters in Different
Scenarios
160*
500*
280*
air outlet
160*
500*
280*
air outlet
32
Instructions for Installation of Industrial and Commercial Inverters in Different
Scenarios
≥100* ≥100*
45°air outlet
≥200
direction
≥280
*
Note: Values marked with * are recommended values. Those not marked with * are
mandatory values. Values can be adjusted according to the actual situation on site.
Flat sunshade is applicable to inverters installed flat. It should be mounted at the same
tilt angle as the inverter.
6.2.1 Precautions
The inverter air outlet may not be blocked.
The sunshade design and selected materials should take wind, rain, snow, shock, and
corrosion resistance into consideration.
The sunshade can be fixed on the support beam or base where the inverter is installed.
For ease of maintenance, the sunshade must be designed as a removable structure
and must not be welded to the mounting rack.
33
Instructions for Installation of Industrial and Commercial Inverters in Different
Scenarios
≥100
≥150
≥100* ≥100*
34
Instructions for Installation of Industrial and Commercial Inverters in Different
Scenarios
≥100*
≥150
≥100* ≥100*
35
Instructions for Installation of Industrial and Commercial Inverters in Different
Scenarios
≥100*
≥150
≥100* ≥100*
needed
100*
150*
100* 100*
36
Instructions for Installation of Industrial and Commercial Inverters in Different
Scenarios
50*
needed
100*
150*
100* 100*
≥60*
≥150
≥100* ≥100*
37
Instructions for Installation of Industrial and Commercial Inverters in Different
Scenarios
Note: Values marked with * are recommended values. Those not marked with * are
mandatory values. Values can be adjusted according to the actual situation on site.
38
Instructions for Installation of Industrial and Commercial Inverters in Different
Scenarios
7 Appendix
7.1 Uncovering
The electrical wiring of the following inverter models would be carried out in the
junction box. When installing the inverter, reserve sufficient space for electrical wiring
and maintenance.
560mm
660mm
155mm
120°
39
Instructions for Installation of Industrial and Commercial Inverters in Different
Scenarios
515mm
795mm
155mm
110°
For ease of fan maintenance, sufficient space must be reserved when installing the
inverter.
40
Instructions for Installation of Industrial and Commercial Inverters in Different
Scenarios
57mm 384.5mm
288mm
62.5mm
63mm
373mm
62.5mm
41
Instructions for Installation of Industrial and Commercial Inverters in Different
Scenarios
57mm 384.5mm
288mm
62.5mm
63mm
373mm
62.5mm
42
Instructions for Installation of Industrial and Commercial Inverters in Different
Scenarios
1087mm
375mm
64mm
655.8mm 130mm
58mm
129mm
1020mm
264mm
570mm
61mm
65mm
43
Instructions for Installation of Industrial and Commercial Inverters in Different
Scenarios
The air outlet is set on the back of the inverter. Therefore, if devices like meters and
small distribution boxes need to be installed near the inverter, you may position them
in the areas marked by "√", as shown in the figure below, and reserve space by
referring to the fan dimension drawing. Do not install any device in the area marked by
"X". Refer to the " Fan Maintenance" for the fan dimension drawing. No other devices
may be installed near the inverter fan.
44
Instructions for Installation of Industrial and Commercial Inverters in Different
Scenarios
Note: ⅹ indicates that no other devices can be installed at this location. √ indicates
that other devices can be installed at this location.