F51 450 FP Accessories
F51 450 FP Accessories
F51 450 FP Accessories
450
Date: august 15, 2005
Supersedes: new
Date: new
Consult engine data sheet for minimum raw water flow rate. hose valve
nfpa standards require that one approved 2K" hose valve shall
commercial discharge fittings be provided for each 250 gpm of flow.
Standard commercial pipe fittings are utilized to provide a con- The primary purpose of the hose valve is for field testing of the
venient mounting location for the main relief valve and to adapt pump, but on occasion they may be used for actual fire fight-
the pump discharge size to the minimum required discharge ing. Without this hose connection it would not be possible to
pipe size. The basic arrangement consists of a discharge tee field test the units on some installations without flooding the
(reducing) and a relief valve tee. protected area.
Hose valve manifold cast Fabricated steel hose valve The relief valve should be set to open at a pressure slightly
brass (typical for two or manifold (typical for four or higher than the normal operating pressure of the pump. When
three valves) more valves) so set, it should be capable of passing all of the water dis-
charged by the pump without developing excessive pressure.
The valve should discharge through a cone or funnel into an air release valve
open pipe in plain sight of the operator. If there will be back
nfpa Standards require all vertical fire pumps to have installed
pressure on the valve, an enclosed cone with sight glasses must
at the highest point of the discharge line a 1 K" or larger auto-
be used and the local insurance inspector should be consulted
matic air release valve. The purpose of this valve is to vent the
prior to making the installation. If the valve discharges into an
air from the column and head upon starting the pump, and to
underground drain, care should be taken that no steam enters
admit air to dissipate the vacuum when the pump is stopped.
near enough to work through the cone and into the pump room.
To satisfy this requirement it will be necessary to install an or-
dinary 1 K" swing check valve which is mounted vertically in an
inverted position. Air will not close the valve but water pressure
will; thus it permits the rapid exit of air upon starting and the
rapid entry of air uponstopping, while remaining closed at all
times when the discharge line is under pressure.
The open cones have openings strategically placed to curtail flow meters
splashing while permitting the operator to see any water be- Flow meters can be used with local approval in lieu of hose
ing wasted through them. Open cones should be used only valves for testing purpose.
when there is no possibility of back pressure; if so, an enclosed
cone should be used. The enclosed cones are fitted with sight
glasses to permit the operator to see any waste through them.
4 5
3 6
2 7
1 8
0 9
100
80 120
60 140
40 160
20 180
0 200
buffalo
93 east avenue
north tonawanda, new york
u.s.a.
14120 -6594
+1 716 693 8813
birmingham
heywood wharf, mucklow hill
halesowen, west midlands
united kingdom
b62 8dj
+44 (0) 8444 145 145
manchester
wenlock way
manchester
united kingdom
m12 5jl
+44 (0) 8444 145 145
bangalore
#59, first floor, 3rd main
margosa road, malleswaram
bangalore, india
560 003
+91 (0) 80 4906 3555
shanghai
no. 1619 hu hang road, xi du township
feng xian district, shanghai
p.r.c.
201401
+86 21 3756 6696
a r m s t r o n g f lu i d t e c h n o lo g y
established 1934 a r m s t r o n g f lu i d t e c h n o lo g y. c o m
tm