I-DE-3010.2G-5425-944-HG4-001 - 0 - IFD Keppel Comments
I-DE-3010.2G-5425-944-HG4-001 - 0 - IFD Keppel Comments
I-DE-3010.2G-5425-944-HG4-001 - 0 - IFD Keppel Comments
Please add the supply for the local activation on this panel.
details like cable tag the counter flange/end connection as
& local/Remote DBR to provide the tag shown in detail "A".
number, source, AC/ selection ? numbers to all these
DC supply
PN-5425001
MODULE M-01 items.
P78 - CO2 SNUFFING SYSTEM CONTROL PANEL
1) Vendor to provide the details of items like A13, A06, A03 etc
XSH-5425980 YS-5425980 2) As per the Technical specification the Manual selector switch is required
XSH-5425981 YS-5425981 to set the Co2 battery as Main. Vendor to check.
3) Vendor to indicate the Set pressure of all Safety valves. Vendor to indicate the
YS-5425982B
XYH-1350518
YS-5425982A
alarm values, set values of all Instruments.
XYH-1350521
YS-5425991
YS-5425992 4) How the Automatic actuation occurs? Thermal detection instruments are
USM-5425990 mentioned on this document ? Vendor to check.
When common fault 5) How the system locally operated. Push buttons are not shown ?
DETAIL "A"
NOT USED. will be activating ? 6) Vendor to provide the details of signals and when they are activating?
Make it Spare
JBIF-1411-980 Also the types like NO/NC, Normally Energized / De-Energized, 24VDC etc.
Inhibit of the Automatic ZSL-5425980 7) All components of the system shall be suitable for operating in a marine
Activation signals environment. Vendor to check.
mentioned on Cause & 8) Area classification: Hazardous Area (Zone 2, Gr. IIA, T3). Vendor to check
Effect, Does it really
required?
DETAIL "C" DETAIL "B"
INJECTION NOZZLE: CN-5425504A/B INJECTION NOZZLE: CN-5425002A/B & CN-5425004A/B
PG-5425980
PSV-5425980
Piping to provide the PIT-5425980
No. Qty UOM Descriptions
A
1 5 PC
CO2 SNUFFING SYSTEM
Air / Shore Connection, 3/4" BSPT
counter connection
2 16 PC CO2 Cylinder, 45kg, w/ Pressure Operated Valve
3
4
5
6
8
3
5
16
PC
LOT
PC
PC
End Plug, F/CO2 Pressure Operated Valve
Cylinder Fastening (4 Cabinets)
CO2 Pressure Gauge, 1/2" NPT Male
Discharge Hose, type 10/330mm
details
7 5 SET CO2 Manifold, Carbon Steel
8 5 PC Pressure Relief Valve
9 5 PC Pressure Transmitter, EX Proof, Suitable for Zone 2, IIA, T3 installation
10 10 PC Block & Bleed Valve, SS316, 1/2" NPT
11 8 PC 2 Way Solenoid Valve, Normally Closed, EX Proof, Suitable for Zone 2, IIA, T3 installation
12 5 PC Bleeder
13 16 PC Manifold Check Valve 3/4" BSP T
14 8 PC Connection Hose
15 6 PC CO2 INJECTION NOZZLE, FLANGE CONNECTION
16 8 PC Connection Hose
17 5 PC Ball Valve, 1", Carbon Steel
18 5 PC Limit Switch, EX Proof, Suitable for Zone 2, IIA, T3 installation
Check Valve, 1", Carbon Steel
XY-5425980B
19 8 PC
XY-5425980A
B ELECTRICAL PANELS
CO2 Control Panel, SS316, with Main / Standby Battery Selection Switches;
After Solenoid valve
1 1 PC
2
C
3 PC
EX Proof, Suitable for Zone 2, IIA, T3 installation
Junction Box, SS316 , EX Proof, Suitable for Zone 2, IIA, T3 installation
CYLINDER CABINET
activated by Electrical
CO2 Cylinder Cabinet for CO2 Cylinders , C.S Material Structure, Offshore Painting;
D
1
1 3
1
SET
PC
Screen Type Door (See Through), c/w Ventilation Louver
SPECIAL TOOLS
Manual Handle for Cylinder Top Valve
signal, how the Co2
2 1 PC Weighing Device for CO2 Cylinder
E
1 3 PC
INSTRUCTION SIGN
Sign CO2 Cylinder Cabinet
from the Batteries feed
2 3 LOT Sign Operation Instruction
3 3 LOT Sign Equipment
to the Pipe ?
VENT POST
the counter flange/end connection as
shown in detail "A". INFORMATION IN THIS DOCUMENT IS PROPERTY OF PETROBRAS, BEING PROHIBITED
OUTSIDE OF THEIR PURPOSE
FORM OWNED TO PETROBRAS N-381 REV.L
SRGE
PG-5425982A PG-5425982B
PIT-5425982A PIT-5425982B
PSV-5425981B
PSV-5425982A PSV-5425982B
PIT-5425981B CLIENT:
PG-5425981B E&P
JOB:
PSV-5425981A BUZIOS FIELD AREA DEVELOPMENT
PIT-5425981A AREA: