Technical data

2.1.3 Block diagram BUS 61 (in principle)

Mono Power Unit/Power Module BUM 61/BUS 61 13


Baumüller Nürnberg GmbH 5.97028.09
Technical data

2.2 Technical data

BUS 61 - 20 / 30 BUS 61 - 30 / 45 BUS 61 - 40 / 60


BUM 61 - 20 / 30 BUM 61 - 30 / 45 BUM 61 - 40 / 60
Connection voltage (mains) 1) 3 x 400 - 460 VAC -15% +15%, 48 - 62 Hz
Supply voltage 2) + 24 VDC - 20% / +20% (max. 55 W)
Input power 15 kVA 23 kVA 29 kVA
Rated DC link voltage3) 540 VDC
DC link capacity (internal) 925 F 1160 F 1395 F
DC link capacity (external) - - -
Output voltage4) 3 x 0 VAC... 95 % of the connection voltage
Output frequency5) 0 Hz. ...400 Hz
Continuous output power at 4kHz 10) max. 13 kVA max. 20 kVA max. 27 kVA
Continuous output power at 8kHz 10) max. 10,5 kVA max. 16 kVA max. 21 kVA
max. continuous motor power at 4kHz 10) 9 kW 14 kW 18 kW
Max. continuous motor output at 8kHz 10) 7.2 kW 11 kW 14.5 kW
6) 7) 8) 10)
Rated output current at 4kHz 20 A 30 A 40 A
6) 7) 8) 10)
Rated output current at 8kHz 16 A 24 A 32 A
6) 7) 9) 10)
Peak output current at 4kHz 30 A 45 A 60 A
Peak output current 6) 7) 9) at 8kHz 10) 30 A 45 A 60 A
Ballast current (external) max. 40 A
(BUM 61 / BUS 61 with ballast only)
Connected load via DC link bar connection max. 14 kW
(BUM 61 only)
Ballast resistor, internal 32 / 150 W (short-term 18 kW (0.1 s))
(BUM 61 / BUS 61 with ballast only)
Ballast resistor, external > 20
(BUM 61 / BUS 61 with ballast only) continuous output as required up to max. 15 kW
Ballast resistor cut-in threshold 780 V
(BUM 61 / BUS 61 with ballast only)
40 °C (rated temperature)
Ambient temperature 11)
55 °C (maximum temperature)
Power loss 3) Connection 245 W 350 W 460 W
Supply max. 55 W max. 55 W max. 55 W
Degree of protection IP 20
Site altitude 12) max. 1000 m a.m.s.l.
Relative humidity 15% ... 85% no condensation
Temperature range for storage -30 °C ... +70 °C
Dimensions (W x H x D) 132 x 490 x 300 mm
Weight including standard V controller 18.6 kg

1. Inter-phase voltage deviation must be max. +/-3.0 %.


2. According to DIN 19240.
Low-voltage supply at voltages < 24 V reduce the fan power. It may therefore be necessary to reduce
the output currents as well.
3. All rated values refer to a connection voltage of 400 V and a supply voltage of 24 V.

14 Mono Power Unit/Power Module BUM 61/BUS 61


5.97028.09 Baumüller Nürnberg GmbH
Technical data

4. The output voltage is an impulse-commutated direct voltage. The setting range refers to the r.m.s.
value of the fundamental wave.
5. The output frequency depends on the controller used.
6. R.m.s. value at an ambient temperature of 40 °C.
7. The unit provides the rated/maximum output currents up to the connection voltage. When the input
voltage exceeds the rated voltage, reduce the output currents at constant output power
proportionally.
Characteristic 1: Output currents in relation to the connection voltage.

8. The rated output current must be reduced between 40 °C and 55 °C. The rated output current is
calculated according to the following formula:

IA = IA 1 – Ambient temperature – 40 C
40 C ---------------------------------------------------------------------------------- 0, 03
C
Example: Rated output current = 30A, ambient temperature = 47 °C:

47 C – 40 C
I A = 30A 1 – ---------------------------------- 0, 03 = 30A 0, 79
C

The rated output current must therefore be reduced to: 23.7 A


9. The peak output current is available for periods 1s. Rate the load cycle in such a way that the
resulting output current r.m.s. value does not exceed the rated current.
10. Chopping frequency of the inverter.
(see description parameter P103 in the description of the V-controller)

Mono Power Unit/Power Module BUM 61/BUS 61 15


Baumüller Nürnberg GmbH 5.97028.09
Technical data

11. The ambient temperature is determined as follows:

Determine several measuring points


covering the entire area as illustrated at
a distance of 10 cm.
Measure the temperature at these
measuring points.

The highest value is


the ambient temperature.

12. Characteristic 2: Values in relation to the site altitude.

16 Mono Power Unit/Power Module BUM 61/BUS 61


5.97028.09 Baumüller Nürnberg GmbH
Technical data

2.3 Type key

Mono Power Unit/Power Module BUM 61/BUS 61 17


Baumüller Nürnberg GmbH 5.97028.09
Technical data

18 Mono Power Unit/Power Module BUM 61/BUS 61


5.97028.09 Baumüller Nürnberg GmbH