18 - Sikafloor - 264 - SG
18 - Sikafloor - 264 - SG
18 - Sikafloor - 264 - SG
Sikafloor®-264 SG
2-part High-build Solvent Free Epoxy Coating
DESCRIPTION FEATURES
Sikafloor®-264 SG is a two-part, high-build, solvent ▪ Good chemical and mechanical resistance
free, coloured epoxy resin. ▪ Easy application
Suitable for use in hot and tropical climatic conditions. ▪ Economical
▪ Liquid proof
USES ▪ Gloss finish
▪ High Slip resistant surface when broadcasted
Sikafloor®-264 SG may only be used by experienced
professionals. SUSTAINABILITY
Sikafloor®-264 SG can be used as a: ▪ Sikafloor®-264 SG is certified according "Low Emit-
▪ Roller coat for concrete and cement screeds with ting Materials as per Al Sa'fat - Dubai Green Building
normal up to medium heavy wear for example stor- Evaluation System" by Dubai Central Laboratory
age and assembly halls, maintenance workshops, (DCL), certificate No. CL17020432
garages and loading ramps. ▪ LEED Raiting: Sikafloor®-264 SG conforms to the re-
▪ A broadcast system for multi-storey and under- quirements of LEED EQ Credit 4.2: Low-Emitting Ma-
ground car parks, maintenance hangars and for wet terials: Paints and Coatings with VOC Content <100
process areas, for example beverage and food in- g/l
dustry. ▪ California Department of Public Health (CDPH) Meth-
od - VOC emission test: PASS
1/6
PRODUCT INFORMATION
Composition Pigmented epoxy resin
Packaging Please refer to local country price list for available packaging sizes:
Part A (container) 4.12 kg 19.80 kg 23.10 kg
Part B (container) 0.88 kg 4.20 kg 4.90 kg
Part A + B (set) 5.00 kg 24.00 kg 28.00 kg
TECHNICAL INFORMATION
Shore D Hardness ~80 (7 d / +23 °C) (ASTM D2240-15)
Abrasion resistance <50 mg (CS 17/1000/1000) (28 d / +23 °C) (ASTM D4060-14)
(Taber Abraser Test)
Tensile adhesion strength > 1.5 N/mm2 (failure in concrete) (BS 1881 Part 207)
Chemical resistance Resistant to many chemicals. Please contact Sika's Technical Department
for chemical resistance table.
2/6
SYSTEM INFORMATION
Systems Roller coating:
Primer*: 1 - 2 x Sikafloor®-161 (optional)
Coating: 2 x Sikafloor®-264 SG
Broadcast system:
Primer*: 1 - 2 x Sikafloor®-161 (optional)
Base coat: 1 x Sikafloor®-264 SG
Broadcasting: Sikadur®-507 / Sikadur®-509
Sealer coat: 1 x Sikafloor®-264 SG
*Note: In cases of limited exposure and good sound low absorbent con-
crete substrates, priming with Sikafloor®-161 is not mandatory. It is recom-
mended to check the absorbency in case pinholes will occur.
Consumption Coating System Product Consumption
Primer 1 - 2 x Sikafloor® -161 0.25 - 0.40 kg/m2 per
coat
Levelling (optional) Sikafloor® PS or, Refer to relevant PDS
Sikafloor®-161 levelling
mortar
Roller coating 2 x Sikafloor®-264 SG 0.25 - 0.35 kg/m2 per
coat
Textured roller coating 1 - 2 x Sikafloor®-264 SG 0.5 - 0.8 kg/m2 per coat
+ Extender T 2-3%
Textured roller coating 10 pbw Sikafloor®-264 0.5 - 0.8 kg/m2
with improved slip res- SG + Extender T + 1 pbw 2 - 3 %
istance Sikadur®-504 0.05 - 0.07 kg/m2
Broadcast system Sikafloor®-264 SG + 0.25 - 0.30 kg/m2
broadcasting Sikadur®- 0.50 - 2.00 kg/m2
507 / Sikadur®-509 + 0.35 - 0.40 kg/m2
Sealcoat Sikafloor®-264
SG
These figures are theoretical and do not allow for any additional material
due to surface porosity, surface profile, variations in level and wastage etc.
Ambient air temperature +10 °C min. / +35 °C max.
Relative air humidity 80 % r.h. max.
Dew point Beware of condensation!
The substrate and uncured floor must be at least 3 °C above dew point to
reduce the risk of condensation or blooming on the floor finish.
Note: Low temperatures and high humidity conditions increase the prob-
ability of blooming.
Substrate temperature +10 °C min. / +35 °C max.
Substrate moisture content < 4 % pbw moisture content.
Test method: Sika®-Tramex meter, CM - measurement or Oven-dry-meth-
od.
No rising moisture according to ASTM (Polyethylene-sheet).
3/6
Pot Life Temperature Time
+10 °C ~60 min
+20 °C ~30 min
+30 °C ~15 min
4/6
ECOLOGY, HEALTH AND SAFETY APPLICATION
Prior to application, confirm substrate moisture con-
User must read the most recent corresponding Safety tent, relative air humidity and dew point. If > 4 % pbw
Data Sheets (SDS) before using any products. The SDS moisture content, Sikafloor® EpoCem® may be applied
provides information and advice on the safe handling, as a T.M.B. (temporary moisture barrier) system.
storage and disposal of chemical products and con- Primer:
tains physical, ecological, toxicological and other Make sure that a continuous, pore free coat covers
safety-related data. the substrate. If necessary, apply two priming coats.
Apply Sikafloor®-151, Sikafloor®-161 and Sikafloor®-
APPLICATION INSTRUCTIONS 161 G by brush, roller or squeegee. Preferred applica-
tion is by using a squeegee and then backrolling cross-
SUBSTRATE QUALITY / PRE-TREATMENT wise.
▪ The concrete substrate must be sound and of suffi-
cient compressive strength (minimum 25 N/mm2) Levelling:
with a minimum pull off strength of 1.5 N/mm2. Rough or unlevelled surfaces need to be levelled first.
▪ The substrate must be clean, dry and free of all con- Use Sikafloor®-161 levelling mortar or Sikafloor® PS
taminants such as dirt, oil, grease, coatings and sur- (see Product Data Sheet) for minor thickness surface
face treatments, etc. leveling. For higher thickness leveling, use Sikafloor®-
▪ Concrete substrates must be prepared mechanically 190 Screed.
using abrasive blast cleaning or scarifying equipment Coating:
to remove cement laitance and achieve an open tex- Sikafloor®-264 SG as coating, can be applied by short-
tured surface. piled roller (crosswise).
▪ Weak concrete must be removed and surface defects Seal coat:
such as blow holes and voids must be fully exposed. Sealer coats can be applied by squeegee and then
▪ Repairs to the substrate, filling of blowholes/voids back-rolled (crosswise) with a short-piled roller.
and surface levelling must be carried out using ap-
propriate products from the Sikafloor®, Sikadur® and CLEANING OF EQUIPMENT
Sikagard® range of materials.
▪ All dust, loose and friable material must be com- Clean all tools and application equipment with Thinner
pletely removed from all surfaces before application C immediately after use. Hardened and/or cured ma-
of the product, preferably by brush or vacuum. terial can only be removed mechanically.
MIXING MAINTENANCE
Prior to mixing, stir part A mechanically. When all of CLEANING
part B has been added to part A, mix continuously for
3 minutes until a uniform mix has been achieved. To maintain the appearance of the floor after applica-
When parts A and B have been mixed, add the quartz tion, Sikafloor®-264 SG must have all spillages re-
sand and if required the Extender T and mix for a fur- moved immediately and must be regularly cleaned us-
ther 2 minutes until a uniform mix has been achieved. ing rotary brush, mechanical scrubbers, scrubber dry-
To ensure thorough mixing pour materials into anoth- er, high pressure washer, wash and vacuum tech-
er container and mix again to achieve a consistent mix. niques etc. using suitable detergents and waxes. For
Over mixing must be avoided to minimise air entrain- further details please refer to the Method Statement
ment. "Cleaning & Maintenance of Sikafloor® Systems".
5/6
LEGAL NOTES
The information, and, in particular, the recommenda-
tions relating to the application and end-use of Sika
products, are given in good faith based on Sika's cur-
rent knowledge and experience of the products when
properly stored, handled and applied under normal
conditions in accordance with Sika's recommenda-
tions. In practice, the differences in materials, sub-
strates and actual site conditions are such that no war-
ranty in respect of merchantability or of fitness for a
particular purpose, nor any liability arising out of any
legal relationship whatsoever, can be inferred either
from this information, or from any written recom-
mendations, or from any other advice offered. The
user of the product must test the product’s suitability
for the intended application and purpose. Sika re-
serves the right to change the properties of its
products. The proprietary rights of third parties must
be observed. All orders are accepted subject to our
current terms of sale and delivery. Users must always
refer to the most recent issue of the local Product
Data Sheet for the product concerned, copies of which
will be supplied on request.
Sikafloor-264SG-en-AE-(10-2023)-4-4.pdf
6/6