Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

FF - FA Works - MS - T2

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 27

Main substation & Transformer 2 BOQ - Firefighting

Rev.0 -10.07.2023
Specs Description Qty Unit Rate
No. EGP
Fire Protection
FIRE‐SUPPRESSION PIPING
Supplying, installing, connecting, testing and commissioning
of Galvanized Electric Resistance Welded (ERW) schedule
40 black steel fire protection piping system where all piping
shall be surface prepared thoroughly sand blast cleaning from
dirt, grease, loose rust & other contaminations and to be
13915
provided with threaded Fittings, Welded Joints, supports,hangers, sleeve
s, inserts, couplings, adapters and all necessary
accessories as per ASTM. A-53,A-106 & API5L

A 25 dn 84 m 300.00
B 32 dn 36 m 380.00
C 40 dn 18 m 470.00
D 100 dn 72 m 1,700.00
E 150 dn 72 m 3,000.00
Supplying, installing, connecting and testing of sprinkler head to be installed all as specified and as shown on drawings.

F SN-01 42 Nr 3,200.00
Supplying, installing, connecting and testing of Deluge Valve (DV) to be installed C/W diaphragm chamber supply control
valve, water supply pressure gauge, diaphragm chamber pressure gauge, system drain valve, diaphragm chamber automatic shu
off valve, waterflow pressure switch, water motor alarm gongs, valve trim, solenoid valve and all
accessories as specified and as shown on drawings

G DV-01-100 dn 1 Nr 170,000.00
Accessories
H OS&Y Gate Valve; 100 mm dia.with tamper switch 1 Nr 22,000.00

I Automatic Air Vent; 25 mm dia. 1 Nr 9,000.00


J Ball Valve; 25 mm dia. 1 Nr 1,000.00
10520 FIRE‐PROTECTION SPECIALTIES
Supplying, installing, connecting and testing of portable fire extinguishers to be installed all as specified and as shown on draw

K FE-02, CO2 - 45 kg 1 Nr
48,000.00
To Collection

Main substation & Transformer 2


BOQ - Firefighting
Rev.0 -10.07.2023

Specs Unit Rate


Description EGP
No.
13969 CARBON DIOXIDE EXTINGUISHING SYSTEMS
1- Battery Room (Ground Floor)
Supplying, installing, connecting and testing of CO2 system Including cylinders ,sectional valves, manifolds, nozzles,
pipes, panels, smoke detectors, abort switch, manual release,and all accessories

A CO2 system to cover a volume-Battery Room

A1 100 lb CO2 cylinder c/w Two Booster Actuator, Two Solenoid 3 Nr


140000
Actuator & Two Mechanical Manual Release
A2 Smoke detector 1 Nr 1500
A3 Heat detector 1 Nr 1500
A4 Manual Pull station c/w outdoor enclosure 1 Nr 2100
A5 Strobe/Light 1 Nr 3200
A6 6'' Fire Bell 1 Nr 2000
A7 Key-Maintenance Switch 1 Nr 2000

A8 Control Panel c/w outdoor enclosure 1 Nr 35000

Seamless Galvanize pipe Schedule 40 pipe network (3∕4 in.


A9 (20 mm) and smaller pipe) & Schedule 80 pipe network (1 in.(25 1 LS 7000
A10 Shielded cables,mm)EMT through 4 in).
conduits and electric boxes 1 LS 4000
A11 Connection from the CO2 Control panel to the fire alarm control 1 LS 10000
A12 panelSystem
Weighing 1 LS
A13 360 Radial Nozzle 1 Nr
A14 Enclosure for Cylinders 1 LS
10520 FIRE‐PROTECTION SPECIALTIES
Supplying, installing, connecting and testing of portable fire
extinguishers to be installed all as specified and as shown on drawings.

B FE-02, CO2 - 6 kg 1 Nr 4500


To Collection
page-2of13
Main substation & Transformer 2
BOQ - Firefighting
Specs Description Qty Unit Rate
No. EGP
CARBON DIOXIDE EXTINGUISHING SYSTEMS
13969
2- Communication Battery Room (Ground Floor)

Supplying, installing, connecting and testing of CO2 system,Including cylinders ,sectional valves, manifolds, nozzles,pipes, pa
moke detectors, abort switch, manual release,and all accessories
A1 CO2 system to cover a volume-Communication Battery Room
100 lb CO2 cylinder c/w Two Booster Actuator, Two Solenoid Actuator
& Two Mechanical Manual Release 3 Nr 140000

A2 Smoke detector 1 Nr

1500
A3 Heat detector 1 Nr 1500
A4 Manual Pull station c/w outdoor enclosure 1 Nr 2100
A5 Strobe/Light 1 Nr
3200

A6 6'' Fire Bell 1 Nr 2000

A7 Key-Maintenance Switch 1 Nr 2000

A8 Control Panel c/w outdoor enclosure 1 Nr 35000

Seamless Galvanize pipe Schedule 40 pipe network (3∕4 in.

A9 (20 mm) and smaller pipe) & Schedule 80 pipe network (1 in. 1 LS

7000
(25 mm) through 4 in).
A10 Shielded cables, EMT conduits and electric boxes 1 LS 4000
A11 Connection from the CO2 Control panel to the fire alarm control 1 LS 10000
A12 panel
Weighing System 1 LS
A13 360 Radial Nozzle 1 Nr

A14 Enclosure for Cylinders 1 LS


10520 FIRE‐PROTECTION SPECIALTIES
Supplying, installing, connecting and testing of portable fire
extinguishers to be installed all as specified and as shown on
drawings.
B FE-02, CO2 - 6 kg 1 Nr 4500
To Collection
page-3of13
Main substation & Transformer 2
BOQ - Firefighting
Rev.0 -10.07.2023

Specs Description Qty Unit Rate


No. EGP
13969 CARBON DIOXIDE EXTINGUISHING SYSTEMS
3- Communication Room (Ground Floor)

Supplying, installing, connecting and testing of CO2 system,Including cylinders ,sectional valves, manifolds, nozzles,pipes, pa
moke detectors, abort switch, manual release,and all accessories

A CO2 system to cover a volume-Communication Room


A1 100 lb CO2 cylinder c/w Two Booster Actuator, Two Solenoid 7 Nr 98571.428571
A2 Actuator & Two Mechanical
Smoke detectorManual Release 4 Nr 1500
A3 Heat detector 4 Nr 1500
A4 Manual Pull station c/w outdoor enclosure 1 Nr 2100
A5 Strobe/Light
1 Nr 3200

A6 6'' Fire Bell 2000


1 Nr

A7 Key-Maintenance Switch 2000


1 Nr

A8 Control Panel c/w outdoor enclosure 35000


1 Nr

Seamless Galvanize pipe Schedule 40 pipe network (3∕4 in.


A9 (20 mm) and smaller pipe) & Schedule 80 pipe network (1 in. 1 LS 15000
(25 mm) through 4 in). LS

A10 Shielded cables, EMT conduits and electric boxes 1 LS 10000


A11 Connection from the CO2 Control panel to the fire alarm 1 LS 10000
control panel
A12 Weighing System 1 LS
A13 360 Radial Nozzle 4 Nr
A14 Enclosure for Cylinders 1 LS
10520 FIRE‐PROTECTION SPECIALTIES
Supplying, installing, connecting and testing of portable fire
extinguishers to be installed all as specified and as shown on
drawings.
B FE-02, CO2 - 6 kg 1 Nr 4500
To Collection
page-4of13

Main substation & Transformer 2


BOQ - Firefighting
Specs Description Qty Unit Rate
No.
13969 CARBON DIOXIDE EXTINGUISHING SYSTEMS
4- Charger Room (Ground Floor)
Supplying, installing, connecting and testing of CO2 system,
Including cylinders ,sectional valves, manifolds, nozzles,
pipes, panels, smoke detectors, abort switch, manual release,
and all accessories
A CO2 system to cover a volume-Charger Room
A1 100 lb CO2 cylinder c/w Two Booster Actuator, Two 4 Nr 125000
Solenoid Actuator & Two Mechanical Manual Release

A2 Smoke detector 2 Nr
1500
A3 Heat detector 2 Nr 1500
A4 Manual Pull station c/w outdoor enclosure 1 Nr 2100
A5 Strobe/Light 1 Nr 3200
A6 6'' Fire Bell 1 Nr 2000

A7 Key-Maintenance Switch 1 Nr 2000

A8 Control Panel c/w outdoor enclosure 1 Nr 35000


Seamless Galvanize pipe Schedule 40 pipe network (3∕4 in.

A9 (20 mm) and smaller pipe) & Schedule 80 pipe network (1 in. 1 LS 10000
(25 mm) through 4 in). 7000
A10 Shielded cables, EMT conduits and electric boxes 1 LS
10000

A11 Connection from the CO2 Control panel to the fire alarm 1 LS
control panel
A12 Weighing System 1 LS
A13 360 Radial Nozzle 2 Nr
A14 Enclosure for Cylinders 1 LS
10520 FIRE‐PROTECTION SPECIALTIES
Supplying, installing, connecting and testing of portable fire
extinguishers to be installed all as specified and as shown on
drawings.
B FE-02, CO2 - 6 kg 1 Nr 4500
To Collection
page-5of13

Main substation & Transformer 2


BOQ - Firefighting

Specs Description QTY Unit Rate


No. EGP

CARBON DIOXIDE EXTINGUISHING SYSTEMS


13969
5- Back Room (Ground Floor) & Main Raised Floor Room
Supplying, installing, connecting and testing of CO2 system,

Including cylinders ,sectional valves, manifolds, nozzles,

pipes, panels, smoke detectors, abort switch, manual release,


and all accessories

A 2-CO2 systems to cover volume - Back Room (Ground


Floor) & Main Raised Floor Room 24 Nr 87500
A1 100 lb CO2 cylinder c/w Two Booster Actuator, Two
Solenoid Actuator & Two Mechanical Manual Release
A2 Smoke detector 18 Nr 1500
A3 Heat detector 18 Nr 1500
A4 Manual Pull station c/w outdoor enclosure 1 Nr
2100
A5 Strobe/Light 2 Nr
3200
A6 6'' Fire Bell 2 Nr 2000
A7 Key-Maintenance Switch 2 Nr
2000
A8 Control Panel c/w outdoor enclosure 2 Nr
35000
A9 Selector Valve 2 Nr 50000
Seamless Galvanize pipe Schedule 40 pipe network (3∕4 in.

A10 (20 mm) and smaller pipe) & Schedule 80 pipe network (1 in. 1 LS

40000
(25 mm) through 4 in).
A11 Shielded cables, EMT conduits and electric boxes 1 LS
35000

A12 Connection from the CO2 Control panel to the fire alarm control panel 1 LS
10000
A13 Weighing System 1 LS
A14 360 Radial Nozzle 18 Nr
A15 Enclosure for Cylinders 1 LS
10520 FIRE‐PROTECTION SPECIALTIES

Supplying, installing, connecting and testing of portable fire


extinguishers to be installed all as specified and as shown on
drawings.
B FE-02, CO2 - 6 kg 1 Nr 4500
To Collection
page-6of13

Main substation & Transformer 2


BOQ - Firefighting
Rev.0 -10.07.2023
Specs Description Qty Unit Rate
No. EGP

13969 CARBON DIOXIDE EXTINGUISHING SYSTEMS


7- Back Raised Floor Room
Supplying, installing, connecting and testing of CO2 system,
Including cylinders ,sectional valves, manifolds, nozzles,
pipes, panels, smoke detectors, abort switch, manual release,

and all accessories


A CO2 system to cover a volume-Back Raised Floor Room
A1 100 lb CO2 cylinder c/w Two Booster Actuator, Two 13 Nr
96153.846154
Solenoid Actuator & Two Mechanical Manual Release

A2 Smoke detector 6 Nr
1500
A3 Heat detector 6 Nr 1500
A4 Manual Pull station c/w outdoor enclosure 1 Nr
2100
A5 Strobe/Light 1 Nr 3200
A6 6'' Fire Bell 1 Nr 2000
A7 Key-Maintenance Switch 1 Nr 2000
A8 Control Panel c/w outdoor enclosure 1 Nr
35000
Seamless Galvanize pipe Schedule 40 pipe network (3∕4 in.

A9 (20 mm) and smaller pipe) & Schedule 80 pipe network (1 in. 1 LS

40000
(25 mm) through 4 in).
A10 Shielded cables, EMT conduits and electric boxes 1 LS 35000
A11 Connection from the CO2 Control panel to the fire alarm 1 LS
10000
control panel
A12 Weighing System 1 LS
A13 360 Radial Nozzle 6 Nr
A14 Enclosure for Cylinders 1 LS
10520 FIRE‐PROTECTION SPECIALTIES
Supplying, installing, connecting and testing of portable fire
extinguishers to be installed all as specified and as shown on
drawings.
B FE-02, CO2 - 6 kg 1 Nr 4500
To Collection

page-7of13

Main substation & Transformer 2 BOQ - Firefighting


Rev.0 -10.07.2023
Specs Description Qty Unit Rate
No. EGP

13967 Clean-Agent Extinguishing Systems


8- Control Room (Ground Floor)
Supplying, installing, connecting and testing of FM-200
system, Including cylinders ,Control head, electrical actuator,
manual lever actuator, low pressure switch, flexible activation
hose, bleed connecting valves, pressure gauge, manifolds,
nozzles, pipes, panels, Smoke sense detectors, Heat sense
detectors,abort switch, manual release, and all accessories,
System to be UL Listed & FM Approved.
A FM-200 system to cover a volume of Control Room
A1 196 KG FM-200 cylinder C/W protected enclosure 2 Nr
675000
A2 Smoke detector 8 Nr
1500
A3 Heat detector 8 Nr 1500
A4 Manual Pull station c/w outdoor enclosure 1 Nr
2100
A5 Strobe/Light 1 Nr
3200
A6 6'' Fire Bell 1 Nr

2000
A7 Abort Switch 1 Nr
5000
A8 Control Panel c/w outdoor enclosure 1 Nr 35000
A9 Seamless Black Steel pipe Schedule 40 pipe network 1 LS 40000
A10 360 Radial FM-200 nozzle 8 Nr
A11 Shielded cables, EMT conduits and electric boxes 1 LS
30000
A12 Interface between FM-200 Control panel and the fire alarm 1 LS
10000
control panel
A13 Relief Damper of 1.0 sq.m. c/w gravity shutter 1 Nr 90000
Contractor to study all pipe/cable penetrations through
A14 Control Room walls and advise the appropriate fire sealant 1 Item 12000
material; to with stand 60 minutes & UL listed
A15 Interlock Control Panel for A/C Shutoff incase of fire. 1 Item 10000
10520 FIRE‐PROTECTION SPECIALTIES

Supplying, installing, connecting and testing of portable fire

extinguishers to be installed all as specified and as shown on


drawings.
B FE-02, CO2 - 6 kg 1 Nr 4500
To Collection
Main
substatio page-8of13
n&
Transfor
mer 2
BOQ -
Firefighti
ng
Rev.0 -
10.07.20
23
Specs
No.
Specs Description Qty Unit Rate
No. EGP

16000 Electrical
The Contractor has to refer to the specifications and drawings for all
details related to the works of this division and he is to include for
complying with all the requirements contained therein, whether or not
they are specifically mentioned within the items description.
13851 FIRE ALARM
DETECTION AND ALARM INTELEGENT INTIATING DEVICES:
Supplying, installing, connecting and testing alarm Fire Alarm Cables
including hot dip galvanized steel conduits for exposed installation, upvc
fire retardant conduit for embedded installation, conduit fittings, back

boxes, Unshielded (105)°C (2.5)mm2 wiring, and all necessary ancillary

works and material for complete installation starting from the outlet and
back to the main fire alarm panel as specified and as indicated on the

drawings:

Fire Alarm Cables including hot dip galvanized steel conduits complete

A with all required accessories, (2x2.5mm2) fire retardant 105°C copper Nr


conductor as shown per drawings and specs).

B Ditto as above but for Fire alarm manual station 1 Nr


C Ditto as above but (2x2.5mm2) for Fire alarm Horn with strobe light and
abort switch

D Conventional Horn Strobe IP54 1 Nr

E Conventional Manual Pull Station and Complete With all Accessories 1 Nr

Double Action-IP54- C/W with protective cover. 1 Nr


FG Conventional
Conventional Abort
UV/IRSwitch
Flame IP54
Detector. 2 Nr
Conventional Fire Alarm Linear Heat Detector for Transformer Is a line Type fixed
temperature heat detector for indoor and outdoor use consists of control unit and
heat detecting cable
including PC modulator. 1 LS
H

-Temperature Ratings (85°C) to be adjusted at 85°C


-Cable Length from 20m to 200m
-UL Listed / FM Approved.
To Collection
Specs Description Qty Unit Rate
No. EGP
Double Knock System as Following 1 Item
1ST NOCK FROM THE CONSIDERED FIRE ALARM CONVENTIONAL FIRE
A
LINEAR HEAT DETECTOR SET AT SPECIFIC TEMPERATURE (ACCORDING
TO DATA SHEET OF TRANSFORMER)

B 2ND NOCK FROM THE CONSIDERED FIRE ALARM CONVENTIONAL UV/IR FLAME 1 Nr
DETECTOR
C Power Supply, 10 Amp, C/W DC cables, outlets, conduits, etc,…. 1 Nr
D Electrical outlet (3x3mm2) for external power supply control panel from
the nearest emergency source 2 Nr

To Collection

page-11of13
Rate Amount
EGP EGP

300.00 25,200.00
380.00 13,680.00
470.00 8,460.00
1,700.00 122,400.00

3,000.00 216,000.00
hown on drawings.

3,200.00 134,400.00
amber supply control
m chamber automatic shut

170,000.00 170,000.00

22,000.00 22,000.00

9,000.00 9,000.00
1,000.00 1,000.00

ied and as shown on drawings

48,000.00 48,000.00
770,140.00

Rate Amount
EGP EGP

nifolds, nozzles,

140000 420000

1500 1500
1500 1500

2100 2100
3200 3200
2000 2000
2000 2000
35000 35000
0
7000 7000
4000 4000
10000 10000
0
0
0
0
0
0
0
4500 4500
492800

Rate Amount
EGP EGP
nifolds, nozzles,pipes, panels, s

140000 420000

1500
1500
1500 1500
2100 2100

3200 3200

2000
2000
2000
2000

35000
35000

7000
7000
0
4000 4000
10000 10000
0
0
0
0
0

4500 4500
492800
Rate Amount
EGP EGP

nifolds, nozzles,pipes, panels, s

98571.428571 690000
6000
1500
6000
1500
2100 2100
3200
3200

2000 2000

2000 2000

35000 35000

0
15000 15000
0

10000 10000

10000 10000
0
0
0

0
0
0
0
0
4500 4500
785800

Rate Amount

125000 500000
0

3000
1500
1500 3000
2100 2100
3200 3200
2000 2000
2000 2000

35000 35000

10000 10000
7000 0
10000
10000
4500
570300

Amount
EGP

2100000
0
27000
27000

2100

6400
4000

4000

70000
100000

40000

0
35000

10000
0

2425500

Rate Amount
EGP EGP

96153.846154 1250000

1500 9000
1500 9000

2100 2100

3200 3200
2000 2000
2000 2000

35000 35000
0

40000
40000
0
35000 35000

10000
10000
0

0
0
0
0

0
0
0
4500 4500
1401800

Rate Amount
EGP EGP
675000 1350000

1500 12000
1500 12000

2100 2100

3200 3200

2000 2000

5000 5000
35000 35000
40000 40000
0

30000 30000

10000 10000
0
90000 90000
0
12000 12000
0
10000 10000

4500 4500
1617800