Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

EMS Smartcell

Download as pdf or txt
Download as pdf or txt
You are on page 1of 80

Intelligent Wireless Zone Monitor

FIRE

FAULT

POWER

FUNCTION 1
1

4 2
FUNCTION 2

Intelligent Wireless Zone Monitor


Programming Guide

©2020 EMS Ltd. All rights reserved. MK067-0001-99 (Issue 1) 04/11/2020 AJM
Welcome
to

©2020 EMS Ltd. All rights reserved. Page 2 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
Table of contents
Introduction 5
General warnings 6 WZM fascia 16
Handling precautions 6 WZM status LEDs 17
Packaging 6 WZM buttons 17
PIN numbers 6 WZM display 18
Equipment familiarisation 7 Access level 1 entry 18
System overview 8 Access level 3 entry 19
System design 9 Example menu display 19
Device log on methods 12 Fault event display 20
Device log on points 13 Fire event display 20
WZM connections 15 How to view more information 20

System setup 21
System setup introduction 22 Set time & date 30
Important system setup notes 22 Install devices 31
Side cover removal 22 Add devices to the system 32
Open WZM 23 Device attributes 33
Optional door removal 23 Device location text 35
Cable entry 24 Text entry 36
Fix WZM to wall 24 Set the panel type 37
Addressable fire system wiring 25 Sounder tones 38
Conventional fire system wiring 26 Sounder duration 39
Re-fit door 28 Sounder activation method 40
Connect backup battery 28 Pulsed output 41
Remove 3V battery tab 29 Device indicator operation 43
Apply power 29

©2020 EMS Ltd. All rights reserved. Page 3 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
System testing 45
Test devices 46 Device battery levels 48
Device signal levels 47

Diagnostics 49
Fault rectification 50 How to improve device signal levels 52
Signal level requirements 51

WZM menus 55
Access level 3 tree view 54 WZM information 68
Access level 3 menu options 57 Language 71
Maintenance/test 59 Reports 72
Device options 61 Access level 4 73
WZM settings 66 Logout 73

Product conformance 75
Device listing 76

©2020 EMS Ltd. All rights reserved. Page 4 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
Introduction

©2020 EMS Ltd. All rights reserved. Page 5 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
! General warnings
The system should only be installed and programmed by a fully trained competent person.

The procedures outlined in this programming guide and associated instructions must be carefully followed.

All of the options detailed within this programming manual are available via the SmartCell configuration
tool. See the configuration tool’s inbuilt engineer manual for operational details.

Handling precautions
General: care should be taken when handling this wireless fire system. Avoid dropping any of the parts on
to hard surfaces, as damage may occur to the case and internal circuitry.

ESD precautions: This wireless fire system includes components that are susceptible to damage from
Electrostatic Discharge (ESD). Permanent damage may be caused to these components through routine
handling if precautions are not observed. To reduce the risk of damage from ESD, the following precautions
should be observed.

Minimise the handling of PCBs which contain static sensitive components.

Where handling is unavoidable, always ensure that you have taken adequate earthing precautions. An
earthed wrist strap is recommended.

When storing or transporting a “loose” PCB, always use a container, which has been designed and
manufactured with ESD protective properties.

Avoid placing static sensitive devices on any surfaces, which may increase the risk of a static discharge

Packaging
Products should be kept in their packaging until they are due to be installed, to minimise the risk of damage.
Retain all packaging until the installation activities have been completed. Should any product be found to
be surplus to requirements, or require returning to your supplier, the original packaging should be used.

PIN numbers
It is advised that you change the default PIN immediately on first installation and consider changing
frequently to prevent unauthorised access.

©2020 EMS Ltd. All rights reserved. Page 6 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
INTRODUCTION

Equipment familiarisation
It is important to establish which devices have been supplied for the installation. Examples of each of the
systems products are shown below:

Wireless zone monitor

Wireless fire devices

Wireless dual smoke / Wireless dual smoke / Wireless dual smoke / Wireless manual
heat detector heat detector & heat detector & combined fire call point
combined sounder sounder beacon
LOG ON POINT

STATUS

DUAL INPUT/OUTPUT DEVICE

Wireless Wireless sounder & Wireless sounder & Wireless input /


sounder ceiling beacon wall beacon output device

©2020 EMS Ltd. All rights reserved. Page 7 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
System overview
The Intelligent Wireless Zone Monitor (WZM) allows for 16 SmartCell wireless devices to be added to
conventional or addressable fire system.

Typical addressable fire system connection


Up to 16x SmartCell
wireless devices
SmartCell WZM

LOG ON POINT

STATUS

DUAL INPUT/OUTPUT DEVICE

F1 F2

F3 F4

Example addressable panel

Typical conventional fire system connection


Up to 16x SmartCell
wireless devices
SmartCell WZM

Zone 1
LOG ON POINT

STATUS

Sound 1
DUAL INPUT/OUTPUT DEVICE

Zone 2

Sound 2

Example Conventional panel

The WZM is programmed for operation with Conventional or Addressable fire control panels in the ‘WZM
Settings’ menu. The default setting is ‘Conventional’. See page 35 for more information.

©2020 EMS Ltd. All rights reserved. Page 8 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
INTRODUCTION

System design
All installation work should be carried out in accordance with the system design.

Wireless zone monitor (WZM)


230 VAC and 24 VDC powered WZMs are available.

Communication between devices and the WZM is bidirectional and operates in the European harmonised
868 MHz frequency band. The WZM’s features are detailed in the ‘Controls and Displays’ section.

The WZM can be connected to conventional and addressable fire systems. See pages 25 to 26 for wiring
configurations.

Wireless dual smoke and heat detectors


Detectors are available as standalone devices and alternatively with integrated sounders or integrated
sounder and beacons. Their fire detection can be configured for smoke, heat or dual smoke and heat.

Available sensitivities are listed below. When configuring as dual detectors, one smoke and one heat
sensitivity is selected. If either of these settings is reached, the detector will send an alarm condition to the
WZM. The detectors are programmable via the WZM.

Smoke Heat
sensitivities sensitivities

Normal 58˚c static (A2S) * Alarm Verification Feature (AVF). Upon receipt of a fire
alarm condition, the WZM waits to check that the device
Normal + AVF * 58˚c rate of rise (A2R)
remains alarm, before acting on the event.
72˚c static (BS)
72˚c rate of rise (BR)

Wireless fire sounders and beacons


Sounders can be set to high or low volume, whilst sounder or beacons can also be independently
enabled or disabled. The default fire sounder tone is tone 5.

Sounders have 31 tones available, that can be played on the configuration tool for verification.

Available tones are shown overleaf:

©2020 EMS Ltd. All rights reserved. Page 9 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
TONE TONE TYPE TONE DESCRIPTION / APPLICATION
1. 970Hz
2. 800Hz/970Hz at 2Hz
3. 800Hz - 970Hz at 1Hz
4. 970Hz 1s OFF / 1s ON
5. 970Hz, 0.5s / 630Hz at 1 Hz **Default fire tone**
6. 554Hz, 0.1s / 440Hz, 0.4s (AFNOR NF S 32 001)
7. 500 - 1200Hz, 3.5s / 0.5s OFF (NEN 2575:2000 Dutch slow whoop)
8. 420Hz 0.6s ON / 0.6s OFF (Australia AS1670 Alert tone)
9. 1000 - 2500Hz, 0.5s/ 0.5s OFF x 3/1.5s OFF (AS1670 Evacuation)
10. 550Hz / 440Hz at 0.5Hz
11. 970Hz, 0.5s ON / 0.5s OFF x 3 / 1.5s OFF (ISO 8201)
12. 2850Hz, 0.5s ON / 0.5s OFF x 3 / 1.5s OFF (ISO 8201)
13. 1200Hz - 500Hz at 1Hz (DIN 33 404)
14. 400Hz
15. 550Hz, 0.7s / 1000Hz, 0.33s
16. 1500Hz - 2700Hz at 3Hz
17. 750Hz
18. 2400Hz
19. 660Hz
20. 660Hz 1.8s ON / 1.8s OFF
21. 660Hz 0.15s ON / 0.15s OFF
22. 510Hz, 0.2s / 610Hz, 0.2s
23. 800 / 1000Hz 0.5s each (1Hz)
24. 250Hz - 1200Hz at 12Hz
25. 500Hz - 1200Hz at 0.33Hz
26. 2400Hz - 2900Hz at 9Hz **Default information tone**
27. 2400Hz - 2900Hz at 3Hz
28. 500 - 1200Hz, 0.5s/ 0.5s OFF x 3/1.5s OFF ( AS1670 Evacuation)
29. 800Hz - 970Hz at 9Hz
30. 800Hz - 970Hz at 3Hz
31. 800Hz, 0.25s ON / 1s OFF
32. 500Hz - 1200Hz, 3.75s / 0.25s OFF (AS2220)
Note: Tones 1, 4, 5 and 7 are EN54-3 approved tones.

Note: Default sounder operation is global. Alternative operation, such as zonal and two stage, plus
sounder and output delays are also available, via the SmartCell configuration tool.

©2020 EMS Ltd. All rights reserved. Page 10 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
INTRODUCTION
Input / output devices
Input / output devices have two resistor monitored fire inputs and two fire relay outputs. Both fire relay
outputs are rated 1 A at 30 VDC.

The device’s two relay outputs are programmable. Upon a fire condition, both outputs will automatically
change state. The outputs can be independently programmed to return to their normal state upon either,
when the control panel’s ‘Silence’ button is pressed, or when the control panel’s ‘Reset’ button is pressed.

©2020 EMS Ltd. All rights reserved. Page 11 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
Device log on methods
Wireless devices can be programmed to the WZM in two ways, for maximum flexibility. They are as follows:

Method 1 ‘at WZM’


This method is accessed at the WZM and involves powering the device
at the WZM, by inserting the device’s batteries. Devices can therefore be
added to the system, prior to installing them into location.

Method 2 ‘at device location’


This method is accessed at the WZM and involves applying the supplied
magnet to the device. Devices can therefore be added to the system,
with device batteries already fitted. E.g. when fitted in its final device
location.

The magnet must be held in place (on the device log on point) for 4
seconds. The device’s LED will flash by way of confirmation.

Refer to the ‘Device log on points’ section for details on each device’s
log on point.

©2020 EMS Ltd. All rights reserved. Page 12 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
INTRODUCTION

Device log on points


Detector (incl. sounder and
beacon variants)

Sounder (incl. beacon


variants)

Call Point

©2020 EMS Ltd. All rights reserved. Page 13 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
Dual input dual output device

LOG ON POINT
STATUS

LOG ON POINT
STATUS

DUAL INPUT/OUTPUT DEVICEDUAL INPUT/OUTPUT DEVICE

©2020 EMS Ltd. All rights reserved. Page 14 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
INTRODUCTION

WZM connections
The WZM has a number of connections and features, as detailed below:

Conventional control 80 character


panel connections LCD display

START

SLIDE TO
Intelligent
STATUS Wireless
REMOVE Zone Monitor
For additional information refer to TSD042

FIRE
FAULT
MAINS / CHARGER FAIL
BATTERY LOW
FAULT BATTERY FAIL

SOUNDER A POWER
ZONE EN54-4 UNIVERSAL PSU
EOL L1 L1 L2 EOL ALARM L1 L1 L2 SC-60-1000
IN OUT RES IN OUT INPUT: 220-240VAC, 50Hz, 0.3A
(+) (-) (+) (+) (-) (+) (-) (+) (-) (+) (+) (-) OUTPUT: 5.0-8.5VDC, 0.8A MAX

15 0359
0359-CPR-00267
INPUT
L N E
A ACTIVE ACTIVE FUNCTION 1
B
C
FAULT
INPUT1
FAULT
INPUT2 FIRE FAULT 1
D A B A B NC C NO NC C NO

4 2
FUNCTION 2

Addressable control panel 230 VAC 48 hr battery back up


connections powered*

* An alternative 24 VDC version WZM is also available for use with a seperate power supply for extended
battery standby time.

©2020 EMS Ltd. All rights reserved. Page 15 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
WZM fascia
The WZM provides status information via the display and status lamps. The WZM’s functions are achieved via
the entry of a user access code.

The WZM’s features are shown below.

Intelligent Wireless Zone Monitor


FIRE
1 FAULT

POWER 2

FUNCTION 1
1

4 2
FUNCTION 2

3
3

1 Status LEDs

2 80 character display

3 Function buttons

4 Navigation & confirmation buttons

©2020 EMS Ltd. All rights reserved. Page 16 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
INTRODUCTION

WZM Status LEDs


LED Indicator LED Colour Function
FIRE Illuminates when any device is in fire alarm condition.

FAULT Illuminates when any fault condition is present at the


WZM itself or if an associated device is in fault.

POWER Indicates a good power supply.

WZM buttons

Button Function
This button is always active and is used for number entry (number 1) and for
1 upwards menu navigation.

This button is always active and is used for number entry (number 2) and for
2 forwards menu navigation.

This button is always active and is used for number entry (number 3) and for
3 downwards menu navigation.

This button is always active and is used for number entry (number 4) and for
4 backwards menu navigation.

This button is always active and is used as a menu entry button.

FUNCTION 1 When a valid User PIN has been entered, pressing the Function 1 button will
switch between the first and second language selected for the system.

When a valid User PIN has been entered, pressing the Function 2 button for
FUNCTION 2
2-3 seconds will send a resynchronisation signal to the WZM’s wireless
devices.

START
©2020 EMS Ltd. All rights reserved. Page 17 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
SLIDE TO
STATUS REMOVE
042
WZM display
Once the WZM has been fully installed and powered up, the WZM will show the following alternating default
‘System Normal’ displays.

SmartCell WZM SmartCell WZM

System Normal System Normal


12:12 Access 10/01/20 Access
This is described in full below.

Programmable text that


SmartCell WZM
can be changed as
required, e.g. site name
Current system status
System Normal
The set time and date 12:12 Access Access to other options
are alternatively shown
here
Entry to the menu and then into the required menu options can be achieved by entering a valid access code
and using the WZM’s navigation buttons. Exiting from a menu option is achieved automatically via a
time-out period, by pressing the 4 button or by selecting the logout menu option.

Access level 1 entry


No valid access code is required for access level 1. To view events on the WZM, the 2
button can be pressed
to select the type of event to be viewed i.e. faults, disablements etc. The 1 and 3 buttons can be used
to scroll through these events.

©2020 EMS Ltd. All rights reserved. Page 18 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
INTRODUCTION

Access level 3 entry


A valid user access code is required for access level 3. One entered the full service menu access structure is
available at this level. This is shown and detailed fully in this programming manual.

To enter access level 3 press the button. The display will change to show:

For Access
Enter Code:

Press To Complete
Press the relevant numbered arrows to enter the access level 3 access code required ( 1= 1 , 2= 2 , 3= 3 ,
4= 4 ). Access level 3 default access code is 333333. On completion of the last number entered, press the .
button. The display will change to briefly show the display below, then the relevant menu options will be
available. During this display all buttons are immediately active.

* Welcome Service *
Access Level 3
Now Available
All Buttons Active
By selecting the access level 3 option and entering the correct access 3 entry code additional menus will be
available.

Example menu display


An example display is shown below:

View System Status


Maintenance/Test
Device Options
WZM Settings

The menus can be navigated by pressing the 1 and 3 buttons until the desired option to be entered has
the arrow ( ) adjacent to it. Pressing the button enters this option.

Exiting from a menu option is achieved automatically after two minutes, or by pressing the 4 button.

©2020 EMS Ltd. All rights reserved. Page 19 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
Fault event display
DEVICES IN FAULT-01 Number of devices
currently in a fire
condition

View> Option to view more


information *
* See the ‘How to view more information’ section below for further details on this feature.

Fire event display


An example fire event screen is detailed below.

DEVICES IN FIRE -02 Number of devices


currently in a fire
condition

View> Option to view more


information *
* See the ‘How to view more information’ section below for further details on this feature.

How to view more information


Whilst fire events or fault conditions are present on the system, pressing the 2 button, will allow the user
to view more information:

Fire Alarms 002


Faults 001

View>
Press the 1 and 3 buttons so that the arrow ( ) is highlighting the desired event type, then press the
@2 button. The LCD display will change to show more information as detailed below:

Device Address A20 FIRE Event type


Device type and Dual Detector
location text * Entrance Lobby
Indicating the current 01/02 Option to scroll is only
event and the total available whilst multiple
events present. events are present

* Note; refer to ‘System Setup’ section for details on location text programming.

©2020 EMS Ltd. All rights reserved. Page 20 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
System Setup

©2020 EMS Ltd. All rights reserved. Page 21 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
System setup introduction
This system setup section will show you how to configure the WZM and connect it to a fire alarm panel. The
‘at WZM’ (via power-up) method of adding devices to the WZM will be used. For advanced programming,
refer to the ‘Panel Menus’ section of this document.

Important system setup notes


The installation must conform to applicable local installation codes and should only be
! installed by a fully trained competent person.

Always select an appropriate device type for the application as per local codes of practice,
or as advised by a qualified professional.

The procedures outlined in this installation guide must be carefully followed.

SmartCell devices contain electronics that may be susceptible to damage from Electro
Static Discharge (ESD). Take appropriate precautions when handling electronic boards.

To ensure correct operation, products must be used within the specified environmental
operating conditions.

Side cover removal


The following steps illustrate how to remove the side covers:

1. 2. 3.
(B)

(A)

Slide the side cover sideways, Position your fingers behind Press the cover’s releasing clip
creating a gap as shown. the cover’s protruding edge. with your thumb (A), and
simultaneously rotate the side
cover anti-clockwise (B), as
viewed overhead to remove the
cover.
©2020 EMS Ltd. All rights reserved. Page 22 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
SYSTEM SETUP

Open WZM
1. Unclip side cover. 2. Loosen screws. 3. Open door.

START
SLIDE TO
STATUS REMOVE

For additional information refer to TSD042


FAULT
MAINS / CHARGER FAIL
BATTERY LOW
BATTERY FAIL

SOUNDER A ZONE
EN54-4 UNIVERSAL PSU
EOL L1 L1 L2 EOL ALARM L1 L1 L2
IN OUT RES IN OUT SC-60-1000
INPUT: 220-240VAC, 50Hz, 0.3A
(+) (-) (+) (+) (-) (+) (-) (+) (-) (+) (+) (-)
OUTPUT: 5.0-8.5VDC, 0.8A MAX

15 0905
0359-CPR-00267
INPUT
A ACTIVE ACTIVE
B FAULT FAULT
C INPUT1 INPUT2 FIRE FAULT
D A B A B NC C NO NC C NO

230 VAC variant shown


Refer to the ‘Side cover removal’
section for details.

Optional door removal


Disconnect the ribbon cable, then turn and release the door hinges.

1. 2.

3. 4.

START
SLIDE TO
For additional information refer to

STATUS REMOVE
Installation Instructions

FAULT
MAINS / CHARGER FAIL

©2020 EMS Ltd. All rights reserved. Page 23 of 80 BATTERY LOW


BATTERY FAIL
MK067-0001-99 (Issue 1) 04/11/2020 AJM

UNIVERSAL PSU EMS-PSU-001


Cable entry
Select cable entry points as required, before fitting to the wall.

NO CABLE ACCESS AT THE


Rear side view
TOP OF THE UNIT!

= Available entry
point

Under side view

Fix WZM to wall


Key hole Spirit level

START
SLIDE TO
STATUS REMOVE

FAULT
MAINS / CHARGER FAIL
BATTERY LOW
BATTERY FAIL START

SLIDE TO
STATUS REMOVE
For additional information refer to TSD042

FAULT
MAINS / CHARGER FAIL
NIVERSAL PSU EMS-PSU-001 BATTERY LOW

Fixing
INPUT: 220-240VAC, 50Hz

Fixing
BATTERY FAIL
OUTPUT: 5.0-8.5VDC, 1.0A MAX
SOUNDER A ZONE

14 EN54-4 UNIVERSAL PSU

positions
EOL L1 L1 L2 EOL ALARM L1 L1 L2

positions
IN OUT RES IN OUT SC-60-1000
05 0359-CPR-XXXX
(+) (-) (+) (+) (-) (+) (-) (+) (-) (+) (+) (-) INPUT: 220-240VAC, 50Hz, 0.3A
OUTPUT: 5.0-8.5VDC, 0.8A MAX

INPUT 15 0905
L N E 0359-CPR-00267
A INPUT
B ACTIVE ACTIVE L N
C FAULT FAULT
D INPUT1 INPUT2 FIRE FAULT
A B A B NC C NO NC C NO

START

STATUS
FAULT
SLIDE TO
REMOVE ! Note: the supplied back box mounting template can be used to drill the fixing positions.

MAINS / CHARGER FAIL


BATTERY LOW
BATTERY FAIL
©2020 EMS Ltd. All rights reserved. Page 24 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM

UNIVERSAL PSU EMS-PSU-001


SYSTEM SETUP

Addressable fire system wiring


SKIP THIS STEP IF CONNECTING TO A CONVENTIONAL FIRE SYSTEM.

Wire the inputs as shown below, using the resistor pack provided.

If an input is not being used, leave the 20 kΩ resistor as factory fitted.

Both outputs are voltage free and rated 30 V @ 1 A.

The maximum cable length to connected devices is 10 m.

FAULT FAULT
ACTIVE ACTIVE 230 VAC variant shown
INPUT1 INPUT2 FIRE FAULT
A B A B NC C NO NC C NO
AERIAL A ATTENTION AERIAL B
ELECTROSTATIC
SENSITIVE DEVICE

RESET

TAMPER START

SLIDE TO
STATUS REMOVE

For additional information refer to TSD042


FAULT
MAINS / CHARGER FAIL
BATTERY LOW
SOUNDER A ZONE
BATTERY FAIL
EOL L1 L1 L2 EOL ALARM L1 L1 L2
IN OUT RES IN OUT
(+) (-) (+) (+) (-) (+) (-) (+) (-) (+) (+) (-)
EN54-4 UNIVERSAL PSU
SC-60-1000
INPUT: 220-240VAC, 50Hz, 0.3A
OUTPUT: 5.0-8.5VDC, 0.8A MAX
RS232

FAULT FAULT
15 0905
0359-CPR-00267
A
B ACTIVE ACTIVE INPUT
C INPUT1 INPUT2 FIRE FAULT L N
BAT
ENABLE D A B A B NC C NO NC C NO

*
† †

20k 4k7 20k 4k7

NO C NC NO C NC NO C NO C
FIRE OUTPUT 1 FIRE OUTPUT 2 FIRE INPUT FAULT INPUT
(to clear when (to clear when
panel silenced) panel reset)

Addressable fire system connections

FOOTNOTES

* Optional cabling, required only when the following SmartCell devices are added to the WZM;
detectors, call points and I/O Units (I/O units when set to ‘Off When Reset’) - see page 30 for details on
this feature.
† Wiring can be normally open or normally closed operation as required.
©2020 EMS Ltd. All rights reserved. Page 25 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
Conventional fire system wiring
SKIP THIS STEP IF CONNECTING TO AN ADDRESSABLE FIRE SYSTEM.

The WZM must be connected to a dedicated zone and sounder output.

The maximum cable length to connected devices is 10 m.

SOUNDER ZONE
EOL L1 L1 L2 EOL ALARM L1 L1 L2 AERIAL A ATTENTION
ELECTROSTATIC
SENSITIVE DEVICE
AERIAL B

IN OUT RES IN OUT


RESET

TAMPER START

SLIDE TO
STATUS REMOVE

(+) (-) (+) (+) (-) (+) (-) (+) (-) (+) (+) (-)

For additional information refer to TSD042


FAULT
MAINS / CHARGER FAIL
BATTERY LOW
SOUNDER A ZONE
BATTERY FAIL
EOL L1 L1 L2 EOL ALARM L1 L1 L2
IN OUT RES IN OUT
(+) (-) (+) (+) (-) (+) (-) (+) (-) (+) (+) (-)
EN54-4 UNIVERSAL PSU
SC-60-1000
INPUT: 220-240VAC, 50Hz, 0.3A
OUTPUT: 5.0-8.5VDC, 0.8A MAX
RS232

FAULT FAULT
15 0905
0359-CPR-00267
A
B ACTIVE ACTIVE INPUT
C INPUT1 INPUT2 FIRE FAULT L N
BAT
ENABLE D A B A B NC C NO NC C NO

R1 R2 R3

R1 = Sounder circuit EOL *


R2 = Zone circuit EOL *
R3 = Alarm resistor *
ACTIVE
FAULT
INPUT1 INPUT2 FIRE FAULT
A B A B NC C NOACTIVE NC C NO
FAULT
INPUT1 INPUT2 FIRE
A B A B NC C NO

+ - + -
SOUNDER ZONE

Conventional fire system connections

FOOTNOTES

* Ensure that the manufacturer’s specified end of line components and triggering resistors are fitted. See
the control panel’s instructions for more information.

©2020 EMS Ltd. All rights reserved. Page 26 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
BATTERY LOW

For additional information ref


SYSTEM SETUP
BATTERY FAIL

EN54-4 UNIVERSAL PSU


SC-60-1000
Make mains power connections: INPUT: 220-240VAC, 50Hz, 0.3A
OUTPUT: 5.0-8.5VDC, 0.8A MAX
230 VAC WZMs only.
15 0905
0359-CPR-00267
INPUT
L N

ANTENNA A ATTENTION ANTENNA B


ELECTROSTATIC
SENSITIVE DEVICE

RESET

TAMPER START

SLIDE TO
STATUS REMOVE

For additional information refer to TSD042


FAULT
MAINS / CHARGER FAIL
BATTERY LOW
BATTERY FAIL

220 to
SOUNDER A ZONE
EN54-4 UNIVERSAL PSU
EOL L1 L1 L2 EOL ALARM L1 L1 L2 SC-60-1000
IN OUT RES IN OUT
(+) (-) (+) (+) (-) (+) (-) (+) (-) (+) (+) (-) INPUT: 220-240VAC, 50Hz, 0.3A
OUTPUT: 5.0-8.5VDC, 0.8A MAX
RS232
15 0905
0359-CPR-00267

Live wire
A
INPUT
B ACTIVE ACTIVE L N
BAT FAULT FAULT
ENABLE C
INPUT1 INPUT2 FIRE FAULT

240 VAC
D
A B A B NC C NO NC C NO

mains Neutral wire


input Earth wire

Make 24 VDC power connections:


24 VDC WZMs only.

The 24 VDC SmartCell WZM is designed to be powered from 2x 24 VDC power sources, to meet country
specific requirements.

Connect both power


2

inputs.
B
FAULT

2
GEN
2
B
FAULT
GEN

SOUNDER A ZONE
A

EOL L1 L1 L2 EOL ALARM L1 L1 L2


FAULT
V+

IN OUT RES IN OUT

There are also general


FAULT

(+) (-) (+) (+) (-) (+) (-) (+) (-) (+) (+) (-)
GEN
M

OV V+
POWER
DC

0V

A
ACTIVE ACTIVE
B FAULT FAULT DC M GEN
C 1
INPUT1 INPUT2
A

FIRE FAULT POWER FAULT FAULT


D 0V V+ OV V+ A B
A B A B NC C NO NC C NO

fault inputs (GEN FAULT)


B
MAINS
FAULT

*
and mains fault (M FAULT)
A

B
FAULT
M

available.
A
V+
POWER

V+
0V

POWER
DC

M
The fault inputs are NC
0V

1 DC GEN
POWER FAULT FAULT and voltage free.
0V V+ A B 1A DCB M GEN
FAULT POWER FAULT FAULT
NC C NO 0V V+ A B A B If a fault input (GEN

* Additional mains
fault input
FAULT or M FAULT) is not
being used, leave the link
as factory fitted.

- + N/C C N/O - + N/C C N/O


24V Out Fault 24V Out Fault
OUTPUT 1 OUTPUT 2
- + C NO NC - + NC C NO
24V Out Fault 24V Out Fault
OUTPUT 1 OUTPUT 2
24 VDC dual
output PSU

©2020 EMS Ltd. All rights reserved. Page 27 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
Re-fit door
Re-connect the ribbon cable and re-fit the door hinges.

1. 2. 3. 4.

START START
SLIDE TO SLIDE TO

For additional information refer to


For additional information refer to

For additional information refer to


STATUS REMOVE STATUS REMOVE

Installation Instructions
Installation Instructions

Installation Instructions
FAULT FAULT
MAINS / CHARGER FAIL MAINS / CHARGER FAIL
BATTERY LOW BATTERY LOW
BATTERY FAIL BATTERY FAIL

U
UNIVERSAL PSU EMS-PSU-001 UNIVERSAL PSU EMS-PSU-001
INPUT: 220-240VAC, 50Hz INPUT: 220-240VAC, 50Hz
OUTPUT: 5.0-8.5VDC, 1.0A MAX OUTPUT: 5.0-8.5VDC, 1.0A MAX

14 14 0
0905 0359-CPR-XXXX 0905 0359-CPR-XXXX
INPUT INPUT
L N E L N E

Connect backup battery


230 VAC WZMs only.

! Warning
Observe battery polarity!

- (BLACK) PSU lead - (BLACK)


battery
connector
+ (RED) PSU lead

+ (RED) battery
connector

©2020 EMS Ltd. All rights reserved. Page 28 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
SYSTEM SETUP

Remove 3 V battery tab.

ANTENNA A ATTENTION ANTENNA B


ELECTROSTATIC
SENSITIVE DEVICE

RESET

TAMPER START

SLIDE TO
STATUS REMOVE

For additional information refer to TSD042


FAULT
MAINS / CHARGER FAIL
PULL

BATTERY LOW
BATTERY FAIL

SOUNDER A ZONE
EN54-4 UNIVERSAL PSU
EOL L1 L1 L2 EOL ALARM L1 L1 L2
IN OUT RES IN OUT SC-60-1000
(+) (-) (+) (+) (-) (+) (-) (+) (-) (+) (+) (-) INPUT: 220-240VAC, 50Hz, 0.3A

BAT
OUTPUT: 5.0-8.5VDC, 0.8A MAX
RS232
15 0905
0359-CPR-00267

ENABLE A
INPUT
B
ACTIVE ACTIVE L N
BAT FAULT FAULT
ENABLE C
INPUT1 INPUT2 FIRE FAULT
D
A B A B NC C NO NC C NO

SLIDE TO
REMOVE

RGER FAIL
W
L

EMS-PSU-001

Apply power
AC, 50Hz
DC, 1.0A MAX

14
0359-CPR-XXXX

The power supply to the WZM can now be switched on.

SmartCell WZM
POWER System Normal
01/01/00 Access

Note: If mains supply is unavailable at this point, the WZM can be temporarily powered by the

! back-up battery.

To achieve this, simply press the PSU’s


‘START’ button.
START

SLIDE TO
STATUS REMOVE
For additional information refer to TSD042

FAULT
MAINS / CHARGER FAIL
BATTERY LOW
BATTERY FAIL

EN54-4 UNIVERSAL PSU


SC-60-1000
INPUT: 220-240VAC, 50Hz, 0.3A
OUTPUT: 5.0-8.5VDC, 0.8A MAX

15
0359-CPR-00267
0905
©2020 EMS Ltd. All rights reserved. Page 29 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
INPUT
L N E
Set time & date
From access level 3 (refer to the ‘Access Level 3’ section for WZM Information
details), press the 3 button until the screen displays: Language
Factory Access
Reports

Press the button and the screen will display:


Edit Users
WZM Options
System Options

Press the 3 button once. The screen will display: Edit Users
WZM Options
System Options

Press the button and the screen will display: Set Time & Date
Lamp Test
Front Screen Text
WZM LED Disable

Press the button and the screen will display:


??:?? TIME
??/??/?? DATE
DD/MM/YY FORMAT
Press To Select

To change the time, press the button and the screen ??:?? TIME
will display:

Edit To Select
The following buttons are required to set the time:

Button(s) Action
1 3 Increases and decreases the selected value.

4 2 Moves the cursor between the hour and minute selections.

Saves the changes and returns to the previous screen.

!
Note: the same process is used for changing the date.

©2020 EMS Ltd. All rights reserved. Page 30 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
SYSTEM SETUP

Install devices

! Note: Refer to the associated device installation guide for full details.

©2020 EMS Ltd. All rights reserved. Page 31 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
Add devices to system
From access level 3 (refer to the ‘Access Level 3’ section for View System Status
details), press the 3 button until the screen displays: Maintenance/Test
Device Options
WZM Settings
Press the button and the screen will display: Add New Device
Remove Device
Edit Settings
Signal Level Test

Press the button and the screen will display*: At WZM


At Device Location
Configure Devices

Press the button and the screen will display: Insert Batteries
Into Device
NOW

Insert the device’s batteries and the screen will change to


Add Fire Device ?
show: Sounder Detector
ID:001234
Add <Exit
New FIRE
Check that the device ident on-screen matches the device
ident shown on the barcode label. Press to confirm, Device Added
or 4 to cancel. If accepted, the screen will display: ID:001234
Address 01
Add Another
Followed by:
Either continue adding new devices (by inserting batteries, Device ?
or press 4 until the front screen is displayed.
Continue <Exit

* Refer to the ‘WZM menus’ section for alternative programming methods.

©2020 EMS Ltd. All rights reserved. Page 32 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
0905 0359-CPR-XXXX
INPUT

SYSTEM SETUP
L N E

Device attributes
From access level 3 (refer to the ‘Access Level 3’ section for View System Status
details), press the 3 button until the screen displays: Maintenance/Test
Device Options
WZM Settings
Press the button and the screen will display: Add New Device
Remove Device
Edit Settings
Signal Level Test

Press the 3 button until the screen displays: Add New Device
Remove Device
Edit Settings
Signal Level Test

Press the button and the screen will display:


A01 ID:001234
Sounder Detector
ID:001234
Devices Change>
A03 ID:001236
Press the 3 button until the device to configure is
shown. Press the button and the screen will display: Sounder Detector
Beacon ID:001236
Devices Change>
Text Description
Press the button and the screen will display:
Detection- Dual
Smoke Sen- Normal
Heat Sen- 58C S
Available options for each device type are shown overleaf.

©2020 EMS Ltd. All rights reserved. Page 33 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
905 0359-CPR-XXXX
INPUT
L N E

Menu Selection Available options

Text Description Refer to the ‘Device location text’ section overleaf for details.

Detection Detection selection of ‘Dual’ (smoke & heat), ‘Smoke Only’ or ‘Heat Only’.

Smoke Sen Smoke sensitivity selection of; ‘Normal*†’ and ‘Normal + AVF’. (The AVF
option allows additional verification of the alarm condition before
reporting).

Heat Sen Heat sensitivity selection of; ‘58 °C Static*†’, ‘58 °C Rate Of Rise*’, ‘72 °C
Static*’, ‘72 °C Rate Of Rise*’.

Sound Volume Allows device sounder levels of; ‘High’ or ‘Low’.

Self Sound When enabled, the will device sound upon local alarm detection, whilst
wireless communication with the WZM is lost.

Audio/Visual Allows device sounder and beacon selection of; sounder & beacon, sounder
only and beacon only.

O/P 1 OFF Choose to switch the device’s ‘Output 1’ off, when either the ‘silence’ or
‘reset’ button is pressed.

O/P 2 OFF Choose to switch the device’s ‘Output 2’ off, when either the ‘silence’ or
‘reset’ button is pressed.

* EN54 approved sensitivities † Default dual sensitivities

©2020 EMS Ltd. All rights reserved. Page 34 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
SYSTEM SETUP

Device location text


From access level 3 (refer to the ‘Access Level 3’ section for View System Status
details), press the 3 button until the screen displays: Maintenance/Test
Device Options
WZM Settings
Press the button and the screen will display: Add New Device
Remove Device
Edit Settings
Signal Level Test

Press the 3 button until the screen displays: Add New Device
Remove Device
Edit Settings
Signal Level Test

Press the button and the screen will display the first
A01 ID:001234
device logged on to the system: Sounder Detector
ID:001234
Devices Change>

Press the 3 button to scroll through the devices until


the required device is shown. Press the button:

Text Description
Press the button and the screen will display:
Detection- Dual
Smoke Sen- Normal
Heat Sen- 58C S
Press the button and the screen will display: Dual Detector
ID:001234

F1 ABC F2 Delete
Refer to the ‘Text entry’ section overleaf.

©2020 EMS Ltd. All rights reserved. Page 35 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
Text entry
The following buttons will be required to enter new text descriptions:

Button Action

1 Moves the selected character through the alphabet


(forwards), one character at a time.

Moves the selected character through the alphabet


3 (backwards), one character at a time.

Moves the cursor (selected character) left, one character at


4 a time.

Moves the cursor (selected character) right, one character


2 at a time.

FUNCTION 1 Used to toggle character entry format between; upper


case, lower case and number.

FUNCTION 2 Provides a delete function; press for single character


deletion, or press and hold to delete all text.

Exits from the current screen. The user is asked whether to


save the changes ( button for yes and 4 button for no).

©2020 EMS Ltd. All rights reserved. Page 36 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
SYSTEM SETUP

Set the panel type


Default panel type is ‘Conventional’. If the WZM is to be View System Status
connected to a conventional type fire panel, skip this section. Maintenance/Test
Otherwise, to change the panel type to ‘Addressable’, from
access level 3 (refer to the ‘Access level 3’ section for details), Device Options
press the 3 button until the screen displays: WZM Settings
Press the button and the screen will display: Panel Type
Sounder Options
Device Indicator

Press the 3 button and the screen will display: Conventional


Addressable

Press the button and the screen will display: Conventional


Addressable

Press the button and the screen will display: Addressable Panel
Selected

©2020 EMS Ltd. All rights reserved. Page 37 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
Sounder tones
To change the fire tone, from access level 3 (refer to the View System Status
‘Access level 3’ section for details), press the 3 Maintenance/Test
button until the screen displays:
Device Options
WZM Settings
Press the button and the screen will display: Panel Type
Sounder Options
Device Indicator

Press the 3 button until the screen displays: Panel Type


Sounder Options
Device Indicator

Press the button and the screen will display:


Default Tone Select
Sounder Duration
Sounder Activation
Pulsed Output

Press the button and the screen will display:


Fire Tone - 05

970Hz - 630Hz, @1Hz


Press the button and the screen will display :

05
Tone To Select
800Hz - 970Hz, @1Hz
Press the 1 and 3 buttons to view the available
tones and press the button to select the required tone:
03
Tone To Select

©2020 EMS Ltd. All rights reserved. Page 38 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
SYSTEM SETUP

Sounder duration
As default, wireless sounders automatically switch off after 30 minutes, to conserve battery life. Sounders
can also be configured for continuous uninterrupted operation, until switched off by the control panel.

If the sounder duration is to be changed to continuous View System Status


operation, from access level 3 (refer to the ‘Access level 3’ Maintenance/Test
section for details), press the 3 button until the screen Device Options
displays:
WZM Settings
Panel Type
Press the button and the screen will display:
Sounder Options
Device Indicator

Press the 3 button until the screen will displays: Panel Type
Sounder Options
Device Indicator

Press the button and the screen will display: Default Tone Select
Sounder Duration
Sounder Activation
Pulsed Output
Press the 3 button until the screen will displays: Default Tone Select
Sounder Duration
Sounder Activation
Pulsed Output
Press the button and the screen will display: 30 Mins Auto Off
Continuous

Press the 3 button until the screen will displays: 30 Mins Auto Off
Continuous

Press the button and the screen will display: Sounder Duration
Set To
Continuous

©2020 EMS Ltd. All rights reserved. Page 39 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
Sounder activation method
As default, wireless sounders will only operate upon activation of the WZM’s fire input. This however can be
changed to ‘immediate mode’, so that sounders also operate upon the activation of one of the WZM’s
wireless devices.

If the sounder activation method is to be changed to View System Status


immediate mode, from access level 3 (refer to the ‘Access level Maintenance/Test
3’ section for details), press the 3 button until the screen Device Options
displays:
WZM Settings
Panel Type
Press the button and the screen will display:
Sounder Options
Device Indicator

Press the 3 button until the screen will displays: Panel Type
Sounder Options
Device Indicator

Press the button and the screen will display: Default Tone Select
Sounder Duration
Sounder Activation
Pulsed Output
Press the 3 button until the screen will displays: Default Tone Select
Sounder Duration
Sounder Activation
Pulsed Output
Press the button and the screen will display: Panel Mode
Immediate Mode

Press the 3 button until the screen will displays: Panel Mode
Immediate Mode

Press the button and the screen will display: Sounder Activation
Set To
Immediate Mode

©2020 EMS Ltd. All rights reserved. Page 40 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
SYSTEM SETUP

Pulsed output
As default, the pulsed output, for the fire and the fault relays, is set to latched. Upon an activation, the relay
will remain latched in alarm until the WZM is reset. This however can be changed to pulse into alarm for a
pre-defined period of time, before automatically clearing. Permitted times range from 5-60 seconds.

If the pulsed out is to be changed , from access level 3 (refer to View System Status
the ‘Access level 3’ section for details), press the 3 button Maintenance/Test
until the screen displays: Device Options
WZM Settings
Panel Type
Press the button and the screen will display:
Sounder Options
Device Indicator

Press the 3 button until the screen will displays: Panel Type
Sounder Options
Device Indicator

Press the button and the screen will display: Default Tone Select
Sounder Duration
Sounder Activation
Pulsed Output
Press the 3 button until the screen will displays: Default Tone Select
Sounder Duration
Sounder Activation
Pulsed Output
Press the button and the screen will display: Fire Relay- LATCH
Fault Relay- LATCH

Press the 1 and 3 buttons, until the screen displays Fire Relay- LATCH
the required relay type: Fault Relay- LATCH
In this example, the fault relay has been chosen.

Press the button and the screen will display: Fault Relay

00 LATCH
Secs To Select
©2020 EMS Ltd. All rights reserved. Page 41 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
Press the 1 and 3 buttons, until the required time is Fault Relay
displayed:
In this example, 20 seconds has been chosen.
20 Seconds
Secs To Select
Press the button and the screen will display: Fire Relay- LATCH
Fault Relay- 15
Note: the same options are available for the fire and fault
relays.

©2020 EMS Ltd. All rights reserved. Page 42 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
SYSTEM SETUP

Device indicator operation


This feature is only available when the ‘Panel Type’ is set to ‘Addressable’. As default, the device LED
indicators are switched ‘Off When Silenced’ (upon receipt of a silence command signal from the control
panel). Alternatively ‘Off When Reset’ can be selected (where the device LED indicators switch off upon the
receipt of a reset command signal from the control panel .

If the indicators are to be switched ‘Off When Reset’, from View System Status
access level 3 (refer to the ‘Access level 3’ section for details), Maintenance/Test
press the 3 button until the screen displays: Device Options
WZM Settings
Panel Type
Press the button and the screen will display:
Sounder Options
Device Indicator

Press the 3 button until the screen will displays: Panel Type
Sounder Options
Device Indicator

Press the button and the screen will display: Off When Silenced
Off When Reset

Press the 3 button until the screen will displays: Off When Silenced
Off When Reset

Press the button and the screen will display: Fire Status
Turned Off
When Reset

©2020 EMS Ltd. All rights reserved. Page 43 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
©2020 EMS Ltd. All rights reserved. Page 44 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
System testing

©2020 EMS Ltd. All rights reserved. Page 45 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
This section shows how to test the systems devices along with checking device signal and battery levels to
ensure they are operating within the correct parameters. This section can be used as a guide. Local fire
alarm maintenance procedures should be followed to comply with the relevant standards.

Test devices
Every device should be function tested, to ensure correct functionality.

Smoke detectors should be tested using a smoke detector tester and in accordance with local codes of
practice.

Heat detectors should be tested using a heat detector tester and in accordance with local codes of practice.

Call Points should be tested in accordance with local codes of practice.

Sounder operation should also be tested in accordance with local codes of practice.

Input / Output devices should also be tested in conjunction with associated 3rd party equipment and in
accordance with local codes of practice.

©2020 EMS Ltd. All rights reserved. Page 46 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
SYSTEM TESTING

Device signal levels


From access level 3 (refer to the ‘Access Level 3’ section for View System Status
details), press the 3 button until the screen displays: Maintenance/Test
Device Options
WZM Settings
Press the button and the screen will display: Sounder.O/P Test
Device Signal List
Device Battery List
Edit Service Code

Press the 3 button until the screen displays: Sounder.O/P Test


Device Signal List
Device Battery List
Edit Service Code

Press the button and the screen will display:


Good Signal 08
Low Signal 00
No Signal 00

Pressing the button will provide more information on A08 80dB


the category highlighted: Dual Detector
First Floor Landing
GOOD Signal

Note: It is important that all devices have ‘GOOD’ signal levels to ensure the maximum

! robustness of wireless signalling.

If a device does not achieve a good signal level, refer to the ‘How to improve device signal levels’ section for
additional guidance.

©2020 EMS Ltd. All rights reserved. Page 47 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
Device battery levels
From access level 3 (refer to the ‘Access Level 3’ section for View System Status
details), press the 3 button until the screen displays: Maintenance/Test
Device Options
WZM Settings
Press the button and the screen will display: Sounder.O/P Test
Device Signal List
Device Battery List
Edit Service Code

Press the 3 button until the screen displays: Sounder.O/P Test


Device Signal List
Device Battery List
Edit Service Code

Press the button and the screen will display:


Battery Ok 10
Battery Low 01
Battery Missing 01
More>
To view individual devices within specific battery level Z01 A20
categories, press the 2 button, whilst the arrow ( ) is Dual Detector
adjacent to the category to be viewed. Example displays
for a device in each category are shown: First Floor Landing
BATTERY OK
Z01 A25
Dual Detector
Basement Area
BATTERY LOW
Z01 A22
Dual Detector
Reception
BATT MISSING

©2020 EMS Ltd. All rights reserved. Page 48 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
Diagnostics

©2020 EMS Ltd. All rights reserved. Page 49 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
Fault rectification
Device type Fault displayed Rectification process
All device types Battery Missing Check all batteries are inserted correctly. Check voltage on
batteries. Replace batteries if necessary or re-insert correctly.
WZM Mains Fail Check the mains supply to the unit.

Detector Head Fault It is recommended that the detection device be replaced due to
a fault with the head being reported.
Detector Head Dirty Clean with compressed air if necessary, as the device is
reporting that the chamber is dirty. Check the device is in a
clean environment and is free from smoke, dust and dirt.
All device types Tamper Check the device is assembled correctly.
Input/output Open Circuit / Short Circuit Check the 20 kΩ end of line resistor is in place and that
connections are secure.
All device types Radio signal strength Check the devices location to ensure no visible cause can be
No Signal Fault seen. Check that the device is still powered and has been added
to the system. (See the ‘How to improve device signal levels’
section for more information).
All device types Battery Low Replace all device batteries with specified batteries - see the
associated device installation guide and replace within 30 days.
WZM Battery Supply Failure Check the integrity of the battery and it‘s connection.

All device types Low signal Note: no fault will be indicated as communication is still taking
place, albeit at a low signal level. Check the device’s location to
ensure there is no obvious cause. (See the ‘How to improve
device signal levels’ section for more information).

All device types Good signal No action required.


Call point Fire Check the device’s resettable element is correctly in place and
that the yellow area is not being displayed. If shown, reset the
device using the reset key.
Detector Fire Ensure that the environment in the device’s location is free of
smoke, residue and dust.

©2020 EMS Ltd. All rights reserved. Page 50 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
DIAGNOSTICS

Signal level requirements


To ensure the signal levels for each device are at an acceptable level, the ‘Device Signal List’ menu should be
checked. This menu will display the signal level in two formats. The first format is a system overview that
will detail how many devices have a ‘GOOD’ or ‘LOW’ signal, or have ‘NO SIGNAL’. This can be used as a guide,
so if you have a system with ten devices and the overview shows ten ‘GOOD’ signal levels, then there is no
need to view the devices individually. The second format allows you to view each individual device. A
pictorial representation coupled with Signal Level Test, is displayed for each device on the system. This is
listed in address number order. If any devices are under the signal level requirements, check the ‘How to
improve device signal levels’ section for guidance.

An example system with all devices showing acceptable signal levels is shown below:

Wireless system setup Device number Shown on menu display Acceptable level
Dual detector Device 01 Z1 A01 GOOD
Dual detector Device 02 Z1 A02 GOOD
Dual detector Device 03 Z1 A03 GOOD
Manual call point Device 04 Z1 A04 GOOD
Dual detector/ sounder Device 05 Z2 A05 GOOD
Dual detector/ sounder Device 06 Z2 A06 GOOD
Dual detector/ sounder Device 07 Z3 A07 GOOD
Manual call point Device 08 Z4 A08 GOOD
Manual call point Device 09 Z4 A09 GOOD
Dual detector Device 10 Z4 A10 GOOD
Dual detector Device 11 Z4 A11 GOOD
Dual detector/ sounder beacon Device 12 Z4 A12 GOOD
Sounder Device 13 Z4 A13 GOOD

An example system with devices showing both acceptable and unacceptable signal levels is shown below:

Wireless system setup Device Number Shown on Menu Display Acceptable Level
Dual detector Device 01 Z1 A01 NO SIGNAL
Dual detector Device 02 Z1 A02 LOW
Dual detector Device 03 Z1 A03 GOOD
Manual call point Device 04 Z1 A04 GOOD
Dual detector/ sounder Device 05 Z2 A05 LOW
Dual detector/ sounder Device 06 Z2 A06 LOW
Dual detector/ sounder Device 07 Z3 A07 GOOD
Manual call point Device 08 Z4 A08 NO SIGNAL
Manual call point Device 09 Z4 A09 GOOD
Dual detector Device 10 Z4 A10 GOOD
Dual detector Device 11 Z4 A11 GOOD
Dual detector/ sounder beacon Device 12 Z4 A12 GOOD
Sounder Device 13 Z4 A13 GOOD

Meeting the acceptable signal levels shown ensures immunity to site attenuation (path loss) is met, as
required in clause 4.2.1 and annexe B of EN54-25.

©2020 EMS Ltd. All rights reserved. Page 51 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
How to improve device signal levels

START

Have the WZM


YES and the device been NO
installed in the correct
location as per the
survey?
Is there
metalwork /
Reposition the device in
electrical equipment near YES the correct location and
the unit, contrary to the device
re-check the signal levels.
installation
instructions?

NO Are the
Return to signal levels ok
the start NO now?

YES
Carry out a signal level check to
determine site range. Signal levels successfully
improved.

©2020 EMS Ltd. All rights reserved. Page 52 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
WZM menus

Intelligent Wireless Zone Monitor


FIRE
* Welcome Service *
FAULT Access Level 3
POWER
Now Available
All Buttons Active

FUNCTION 1
1

4 2
FUNCTION 2

©2020 EMS Ltd. All rights reserved. Page 53 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
Access level 3 tree view
View System Status Event History

Fire Alarms

Faults

Total Devices

Maintenance/Test Sounder. O/P Test

Device Signal List

Device Battery List

Edit Service Code

Clear Event Log

Device Options Add New Device

Remove Device

Edit Settings

Signal Level Test

Device Identifier

View All Devices

WZM Settings Panel Type

Sounder Options

Device Indicator

Continued overleaf...

©2020 EMS Ltd. All rights reserved. Page 54 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
WZM MENUS

WZM Information WZM Options Set Time & Date

Lamp Test

Front Screen Text

WZM LED Disable

System Options Healthy Indicator

Radio Channels

Language Español

Select Primary

Select Secondary

Factory Access View Firmware

Reports Output Format

Full Event Log

Alarm Only Events

Fault Only Events

Signal Strength

Current Status

Configuration

Continued overleaf...

©2020 EMS Ltd. All rights reserved. Page 55 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
Access Level 4

Logout

©2020 EMS Ltd. All rights reserved. Page 56 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
WZM MENUS

Access level 3 menu options


View system status
The view system status menu allows the engineer to view the historical event log, along with viewing the
status of individual devices on the system and current disablements/test states. This menu option is
shown in detail below:

View System Status Event History Fire Only

Fault Only

All Events

Fire Alarms

Faults

Event history
When entered, options are available to view filtered ‘Fire’, or ‘Information’ events only or alternatively, ‘All
Events’ can be viewed. A total number of events for each option is also indicated. When the event option is
entered, the display will show the latest event first. The events can then be scrolled through by using the 1 .
and 3 buttons. Each log entry records the event type, the device’s zone (at the time of the event), the
device address (text description if allocated) and time and date at which the event occurred. The event log
is a scrolling log, shown in chronological order and will automatically overwrite the oldest events when the
1000 event capacity is reached. The log can however be cleared using an access level 3 code and entering
the relevant menu if required. Note: the default access level 3 code is 333333.

The example below shows a historical event, logged for a ‘TAMPER’ fault on a device.

Device address A20 TAMPER Event type


Dual Detector
Device’s text description
First Floor Landing
Time & date of the event 12:05 10/01/20

©2020 EMS Ltd. All rights reserved. Page 57 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
Fire only
This menu displays the total number of fire alarms that are currently on the system. The total number is
shown next to the fire alarm text. Pressing the button details the individual devices in fire alarm. The
devices in fire alarm condition can then be scrolled through, using the 1 and 3 buttons.

Fault only
This menu displays the total number of faults that are currently on the system. The total number is shown
next to the fault text. Pressing the button will show individual devices in a fault condition. The devices
which can be either information or fire devices can be scrolled through, using the  1 and 3 buttons. A
fault description will be associated with any devices.

All events
This menu displays the total number of devices on the system. When entered, the individual device details
along with it’s current status are shown. The device list starts at the lowest address fire and these can be
scrolled through, using the 1 and 3 buttons. When all of the fire devices have been scrolled through,
the list will subsequently show all of the information devices, again in address number order.

©2020 EMS Ltd. All rights reserved. Page 58 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
WZM MENUS

Maintenance/test
This menu option enables the engineer to test devices and to view their test statuses. Additionally, in this
menu, individual sounders can be tested and device signal and battery levels can be viewed.

This menu option is fully shown and detailed below:

Maintenance / Test Sounder. O/P Test Sounder Test


Device Output Test

Device Signal Test Good Signal


Low Signal
No Signal

Device Battery List Battery OK


Battery Low
Battery Missing

Edit Service Code

Clear Event Log

©2020 EMS Ltd. All rights reserved. Page 59 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
Sounder O/P Test
This menu option allows the engineer to send individual sounder devices a command to switch its sounder
elements on and off. Individual output devices can also be selected to turn the units relay outputs on and
off.

Note: If the unit is a dual output device, both outputs will operate.

Device Signal List


This menu option allows the engineer to view signal information for all devices on the system. You can
scroll through the list using the 1 and 3 buttons. The signal levels will be shown as GOOD, LOW and NO
SIGNAL.

Device Battery List


This menu option allows the engineer to view battery information for all devices on the system. You can
scroll through the list using the 1 and 3 buttons. The battery levels will be displayed for each device
using BATTERY OK, BATTERY LOW and BATTERY MISSING icons.

Edit Service Code


This menu option allows the engineer to change the four digit service code, that is required for entry to
access level 3.

Clear event log


This menu option allows the event log to be cleared.

©2020 EMS Ltd. All rights reserved. Page 60 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
WZM MENUS

Device options
This menu allows the engineer to add, remove and replace devices. The user can also edit the devices
programming parameters, view device information and identification modes of test operation.

This menu option is fully shown and detailed below:-

Device options Add New Device At WZM

At Device Location

Configure Devices

Remove Device

Edit Settings Device Display Text

Detection *
* Option available
Smoke Sen* dependant upon
device type
Heat Sen*

Signal Path

Sound Volume *

Self Sound *

Audio/Visual *

O/P 1 OFF *

O/P 2 OFF *

Signal Level Test Individual Device

ALL Devices

Device Identifier Individual Device

ALL Devices

View All Devices

©2020 EMS Ltd. All rights reserved. Page 61 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
Add new device
This menu allows all wireless device types to be added to the system. The function allows the device to be
added in two different ways. Both methods are shown in more detail below:-

At WZM
This option is used when devices are logged onto the system prior to the devices being installed. The step
by step process is shown below:

A) Log on /adding is undertaken whilst standing in front of the WZM with each device.
B) This involves entering the ‘Add WZM’ menu, then fit the device’s batteries.
C) The device details are then received and displayed on the WZM.
D) Check the device ident number shown on screen against the ident shown on the device’s barcode
label. If correct and details are accepted, the device is added to the WZM.
E) The device can then be installed in the required location.

Add Device Location


This option is usually used when the devices have already been installed and the user requires them to be
added to the system via the devices magnetic log on switch. The step by step process is shown below:

A) Log on /adding is undertaken by visiting each installed device.


B) This involves entering the ‘Add Device Location’ menu and then placing a magnet against the
devices magnetic log on switch. See the ‘Magnet log on points’ section for device log on points.
C) The device’s LED will flash to indicate that the device has successfully communicated with the
WZM.
D) The device details are then received and displayed on the WZM.
E) It is possible to accept the new device, or add another device in the same fashion, therefore creating
a list at the WZM.
F) When these details are accepted, the device is added to the WZM.

©2020 EMS Ltd. All rights reserved. Page 62 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
WZM MENUS
Remove device
This section allows wireless devices to be removed from the system. A list of devices already allocated to the
system are shown, these can be scrolled through by using the 1 and 3 buttons. The required device to
be removed can be selected by using the button.

Edit settings
This menu allows the user to change device text descriptions, allocate the device to a zone, allocate
detection type, select detector sensitivity settings, change sounder volume and I/O operation for inputs and
outputs. All of the above will have default settings. The available options and the default settings are shown
in the following tables for each device type;

Dual detector

Attribute Type Default setting

Address number Next available address number on system

Device Display Text The device type followed by the devices unique ident number
(where xx = represents the ident number of the device)

Detection Dual

Smoke Sen Normal

Heat Sen 58°C static

Fire manual call point

Attribute type Default setting

Address number Next available address number on system

Device Display Text The device type followed by the devices unique ident number
(where xx = represents the ident number of the device)

Sounder

Attribute type Default setting

Address number Next available address number on system

Device Display Text The device type followed by the devices unique ident number
(where xx = represents the ident number of the device)

Sounder volume High

©2020 EMS Ltd. All rights reserved. Page 63 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
Sounder beacon

Attribute Type Default setting

Address number Next available address number on system

Device Display Text The device type followed by the devices unique ident number
(where xx = represents the ident number of the device)

Sounder volume High

Audio/Visual On

Detector sounder

Attribute type Default setting

Address number Next available address number on system

Device Display Text The device type followed by the devices unique ident number
(where xx = represents the ident number of the device)

Detection Dual

Smoke Sen Normal

Heat Sen 58°C static

Sound volume High

Detector sounder and beacon

Attribute type Default setting

Address number Next available address number on system

Device Display Text The device type followed by the devices unique ident number
(where xx = represents the ident number of the device)

Detection Dual

Smoke Sen Normal

Heat Sen 58°C static

Sound volume High

Audio/Visual On

©2020 EMS Ltd. All rights reserved. Page 64 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
WZM MENUS
Dual input / output device

Attribute type Default setting

Address number Next available address number on system

Device Display Text The device type followed by the devices unique ident number
(where xx = represents the ident number of the device)

O/P 1 OFF Reset

O/P 2 OFF Reset

Signal level test


This mode of operation allows the signal strength of a single device on the system or all devices globally on
the system to be indicated via the devices on board LEDs. The signal strength level is shown by flashing the
individual devices LED to ascertain the devices signal strength level. This is split into two colours :- green for
‘GOOD’ signal and red for ‘LOW’ signal. The signal strength status LED would update periodically to allow an
updated reading to be shown.

View all devices


When entered the screen will show the current settings for the devices on the system. The device listings
can be scrolled through by using the 1 and 3 buttons.

©2020 EMS Ltd. All rights reserved. Page 65 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
WZM settings
The ‘WZM settings’ menu allows an engineer to program various WZM options. The available options are
explained in more detail below.

WZM Settings Panel Type Conventional


Addressable

Sounder Options Default Tone Select


Sounder Duration
Sounder Activation
Pulsed Output

Device Indicator * Off When Silenced * Option only available


Off When Reset when ‘Panel Type’ is
set to ‘Addressable’

Panel type
This menu option changes the operation of the WZM; to work in conjunction with either a conventional fire
control panel, or an addressable fire control panel. The default setting is ‘Conventional’.

The LCD front display will state whether conventional mode or addressable mode is selected.

Sounder Options
The operation of the wireless sounders to be programmed in this menu. Available options are as follows:

Default Tone Select


This menu option allows the selection of the default sounder fire alarm tone.

Sounder Duration
This menu option allows has two available options. They are as follows:

Continuous ‘Upon a fire event, wireless sounders will continue to ring, until they are silenced.

30 Min Cut Off ’Upon a fire event, wireless sounders will be automatically switch off after 30 minutes,
to conserve battery life. Subsequent fire alarm activations will re-activate the sounders.

The default setting is 30 min cut off.

©2020 EMS Ltd. All rights reserved. Page 66 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
WZM MENUS
Sounder Activation
As default, the WZM’s wireless sounders will only operate upon the WZM’s Fire Input being triggered. This
however can be changed, so that sounders operate, upon the activation of one of the WZM’s wireless
devices.

Pulsed Output
This menu option allows has two available options. They are as follows:

Fire Relay ‘Allows the relay output to change state upon a fire event for a preset period of time.
Available durations in seconds are 0 (output off ), or 5-60 seconds (in 5 second increments).

Fault Relay ‘Allows the relay output to change state upon a fault event for a preset period of time.
Available durations in seconds are 0 (output off ), or 5-60 seconds (in 5 second increments).

The default setting is 0 seconds (output off).

Device Indicator
This menu allows the programming of the wireless devices alarm indicator led operation. If the devices led
operation is required to be controlled by a separate Reset input (Input 2) then this function should be
selected (EN requirement). A change of state will be required on Input 2 when the system is reset. This will
allow the Wireless Zone Monitor to send a reset signal to the wireless devices to extinguish their alarm
indicator LED’s if they have been triggered.

Off When Silenced


This menu allows the method of control for the wireless devices individual alarm indicator to be selected.
The options are for the devices indicator which has alarmed and is in the on state to turn off on receipt of a
SILENCE command signal. This is generated when the fire input clears (Input 1) and will therefore work the
same as sounders on the Zone Monitor.

Off When Reset


This menu allows the method of control for the wireless devices individual alarm indicator to be selected.
Alternatively the devices indicator can be selected so it extinguishes only after a RESET command (Input 2
clear) has been activated. This requires a reset input wired from the control panel to Input 2 on the Wireless
Zone Monitor. When this input is activated and subsequently clears a reset signal can be sent. This can be
therefore be wired into a relay which changes state on a reset event or returns to a normal state when the
panel is reset. The default operation is to turn off on a Silence command when the fire input clears (Input 1).

©2020 EMS Ltd. All rights reserved. Page 67 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
WZM information
The ‘WZM information’ menu allows an engineer to program various WZM options. The available options are
explained in more detail below.

WZM Information WZM Options Set Time & Date Time

Date

Format

Lamp Test

Front Screen Text

WZM LED Disable

System Options Healthy Indicator ON/OFF

Radio Channels 5 Channels

©2020 EMS Ltd. All rights reserved. Page 68 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
WZM MENUS
WZM Options

Set time & date


The ‘Set Time & Date’ menu allows an engineer to program the systems time and date. The time will be
displayed on the WZM display and the time and date is also used for time stamping events in the event log.
This menu option also allows the date format to be changed.

If the time and date is not set on the WZM the following display will be shown:

SmartCell WZM SmartCell WZM

Set Time & Date Set Time & Date


00:00 Access 00/00/00 Access

Lamp Test
This option when entered performs a lamp test on the WZM.

Front Screen Text


The front screen text can be edited in this menu.

WZM LED Disable


This menu option allows the engineer to disable the WZM’s external status LEDs.

©2020 EMS Ltd. All rights reserved. Page 69 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
System Options

Healthy Indicator
The system has the capability of showing on each individual device a health indication LED. This menu
allows this functionality for the devices to be selected. The default setting is for the LED to flash on a device
every poll, which is every 2 minutes. If the device is in a fault free healthy condition this will flash green, if the
device is in any fault condition the flash will be a yellow flash. Once the device is fault free the indicator LED
will return to green. This indication feature can be turned ‘ON’ or ‘OFF’ from this menu.

Radio Channels
This menu allows you to view the frequency channels currently used by the system. The radio channels used
for the system are factory set. Any monitoring and channel changes can be undertaken using the
configuration tool.

©2020 EMS Ltd. All rights reserved. Page 70 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
WZM MENUS

Language
The ‘Language’ menu allows an engineer to display the WZM’s menus in a secondary language, plus the
ability to program the WZM’s primary and secondary languages.

Language Español *

Select Primary

Select Secondary

* Example showing Spanish as the secondary language.

Secondary language select


The language option which has been programmed as the secondary language for the WZM is shown on the
top line of the display. Once selected the menu structure will be displayed in this language for the time
duration that the user has menu access to the WZM. When the menu structure has been exited to the front
display and after a further 30 seconds of inactivity, the system will revert back to the primary language.

Select primary
When this option is entered the languages that are available for use as the WZM’s primary language are able
to be selected.

Select secondary
When this option is entered the languages that are available for use as the WZM’s secondary language are
able to be selected.

©2020 EMS Ltd. All rights reserved. Page 71 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
Reports
A number of reports are available to be written to a USB memory stick, connected to the WZM’s USB-A
connection. These can be saved or printed out accordingly thereafter. The available options are explained
in more detail below.

Reports Output Format

Full Event Log

Alarm Only Events

Fault Only Events

Signal Strength

Current Status

Configuration

Output format
When selected, exported data can be downloaded in ‘CSV’, ‘JSON’ and ‘XML’ formats.

Full event log


When selected, the full event log will be downloaded.

Alarm Only Events


When selected, an event log containing alarm events only will be downloaded.

Fault Only Events


When selected, an event log containing fault events only will be downloaded.

Signal strength
When selected, all device signal levels including current, minimum and maximum levels will be
downloaded. These are displayed as ‘GOOD’, ‘LOW’, ‘NO SIGNAL’, along with their associated level in dB.

Current status
When selected, the current status information from all devices will be downloaded.

Configuration
When selected details of the full system setup including all zone, device details and WZM programmed
parameters will be downloaded.

©2020 EMS Ltd. All rights reserved. Page 72 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
WZM MENUS

Access level 4
This option allows the ability for an access level 4 factory access code to be entered. At access level 4, all the
WZM’s controls are functional and the WZM’s factory menu is fully accessible allowing full software
configuration. Access level 4 access is reached by entering the factory access code.

Access Level 4

Logout
When selected the logout option will return the user to the front display immediately. Access to the WZM’s
menus would need to be re-started I.e. access code re-entered.

Logout

©2020 EMS Ltd. All rights reserved. Page 73 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
©2020 EMS Ltd. All rights reserved. Page 74 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
Product conformance

©2020 EMS Ltd. All rights reserved. Page 75 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
Compatible wireless fire products and details of their conformance and part numbers are listed below:

Wireless Zone Monitor


CPR certificate DoP:
0359-CPR-00427

Approved to:
EN54-13, EN54-18 and EN54-25.

Part numbers: Variation:


SC-13-1100-0001-99 Intelligent Wireless Zone Monitor (230 VAC version)
SC-13-2100-0001-99 Intelligent Wireless Zone Monitor (24 VDC version)

Wireless dual smoke / heat detector


CPR certificate DoP:
0359-CPR-00265

Approved to:
EN54-5, EN54-7, EN54-13 and EN54-25.

Part number: Variation:


SC-21-0200-0001-99 Dual smoke / heat detector

Wireless dual smoke / heat detector and combined sounder


CPR certificate DoP:
0359-CPR-00268

Approved to:
EN54-3, EN54-5, EN54-7, EN54-13 and EN54-25.

Part number: Variation:


SC-22-0200-0001-99 Dual smoke / heat detector and combined sounder

Wireless dual smoke / heat detector & combined sounder beacon


CPR Certificate DOP:
0359-CPR-00268

Approved to:
EN54-3, EN54-5, EN54-7, EN54-13, EN54-23 and EN54-25.

Part Numbers: Variation:


SC-23-0220-0001-99 Dual smoke / heat detector and combined sounder-beacon (VAD white flash)

©2020 EMS Ltd. All rights reserved. Page 76 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
PRODUCT CONFORMANCE

Wireless fire manual call point


CPR certificate DoP:
0359-CPR-00266

Approved to:
EN54-11, EN54-13 and EN54-25.

Part number:
SC-51-0100-0001-99

Wireless sounder
CPR certificate DoP:
0359-CPR-00428

Approved to:
EN54-3, EN54-13 and EN54-25.

Part numbers: Variation:


SC-31-0100-0001-99 RED sounder
SC-31-0200-0001-99 WHITE sounder

Wireless sounder and ceiling beacon


CPR certificate DoP:
0359-CPR-00428

Approved to:
EN54-3, EN54-13, EN54-23 and EN54-25.

Part numbers: Variation:


SC-33-0120-0001-99 RED sounder and ceiling beacon (VAD white flash)
SC-33-0220-0001-99 WHITE sounder and ceiling beacon (VAD white flash)

Wireless sounder and wall beacon


CPR certificate DoP:
0359-CPR-00428

Approved to:
EN54-3, EN54-13, EN54-23 and EN54-25.

Part numbers: Variation:


SC-32-0120-0001-99 RED sounder and wall beacon (VAD white flash)
SC-32-0220-0001-99 WHITE sounder and wall beacon (VAD white flash)

©2020 EMS Ltd. All rights reserved. Page 77 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
Wireless dual input dual output device
CPR certificate DoP:
0359-CPR-00269

LOG ON POINT
STATUS

DUAL INPUT/OUTPUT DEVICE

Approved to:
EN54-13, EN54-18 and EN54-25.

Part number:
SC-41-0200-0001-99

©2020 EMS Ltd. All rights reserved. Page 78 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
PRODUCT CONFORMANCE

©2020 EMS Ltd. All rights reserved. Page 79 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM
www.mysmartcell.co.uk

The information contained within this literature is correct at time of publishing. EMS reserves the right to change any information regarding products as part of its
continual development enhancing new technology and reliability. EMS advises that any product literature issue numbers are checked with its head office prior to
any formal specification being written.

©2020 EMS Ltd. All rights reserved. Page 80 of 80 MK067-0001-99 (Issue 1) 04/11/2020 AJM

You might also like