Easypact CVS Power Connection
Easypact CVS Power Connection
Easypact CVS Power Connection
Contents
Installation in switchboards
Power supply and weights B-3
Safety clearances and minimum distances B-4
Installation example B-5
B-1
Installation Operating conditions and temprature
recommendations derating
2000
Vibrations
CVS devices resist electromagnetic or mechanical vibrations.
Tests are carried out in compliance with standard IEC 60068-2-6 for the levels
required by merchant-marine inspection organisations (Veritas, Lloyds, etc.):
b 2 to 13.2 Hz: amplitude ±1 mm
b 13.2 to 100 Hz: constant acceleration 0.7 g.
Excessive vibration may cause tripping, breaks in connections or damage to
mechanical parts.
Degree of protection
CVS circuit breakers have been tested for degree of protection (IP) and mechanical
impact protection (IK). See page A-3.
The overload protection is calibrated at 40 °C in the lab. This means that when the
ambient temperature is less than or greater than 40 °C, the Ir protection pick-up is
(A) device), corrected for the ambient temperature as indicated in the tables below.
110
Settings of CVS100 to 630 equipped with TM-D trip units as a
100 function of the temperature
The table indicates the real Ir (A) value for a given rating and temperature.
90
Rat. Temperature (°C)
80
(A) 10 15 20 25 30 35 40 45 50 55 60 65 70
16 18.4 18 18 18 17 16.6 16 15.6 15.2 14.8 14.5 14 13.8
10 20 30 40 50 60 70 (°C) 25 28.8 28 27.5 27 26.3 25.6 25 24.5 24 23.5 23 22 21
Temperature derating curve for CVS100. 32 36.8 36 35.2 34.4 33.6 32.8 32 31.3 30.5 30 29.5 29 28.5
40 46 45 44 43 42 41 40 39 38 37 36 35 33.5
50 57.5 56 55 54 53 51 50 49 47 46 44 43 41
63 73 72 70 68 67 65 63 61 59 57 55 53 50
DB400102
10 000
DB40010
5 000
80 92 90 88 86 84 82 80 78 75.5 73 70.7 68 65
2 000
1 000 100 114 112 110 107 105 102.5 100 97 95 92.0 89 86 83
500
125 144 141 138 134 131 128 125 122 119 116 113 109 106
200
100
160 184 180 176 172 168 164 160 156 152 148 144 140 136
50 200 230 225 220 215 210 205 200 195 190 185 180 175 170
20
250 288 281 277 269 263 256 250 244 238 231 225 219 213
10
5 320 364.9 357.8 350.5 343.2 335.6 327.9 320 311.9 303.6 295 286.2 277.1 267.7
t(s)
2 400 456.6 447.7 438.6 429.2 419.7 410
TM80D : Im = 10 x In 400 390 379.3 368.5 357.3 345.8 333.9
1
.5 500 558.6 549.2 539.7 530.1 520.3 510.2 500 489.6 478.9 468 456.8 445.4 433.6
TM100D : Im = 10 x In
.2 600 672 660.5 648.9 637 624.9 612.6 600 587.2 574 560.6 546.8 532.7 518.2
.1
.05
.02
.01 t < 10 ms
.005
.002
.001
.5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300
I / Ir
B-2
Installation in switchboards
Power supply and weights
CVS circuit breakers can be supplied from either the top or the bottom, even when
equipped with a Vigi earth-leakage protection module, without any reduction in
performance. This capability facilitates connection when installed in a switchboard.
All connection and insulation accessories can be used on circuit breakers supplied
either from the top or bottom.
Weight
The table below presents the weights (in kg) of the circuit breakers and Vigi module.
B-3
Installation Installation in switchboards
recommendations Safety clearances and minimum distances
General rules
:KHQLQVWDOOLQJDFLUFXLWEUHDNHUPLQLPXPGLVWDQFHV VDIHW\FOHDUDQFHV PXVW
EHPDLQWDLQHGEHWZHHQWKHGHYLFHDQGSDQHOVEDUVDQGRWKHUSURWHFWLRQGHYLFHV
LQVWDOOHGQHDUE\7KHVHGLVWDQFHVZKLFKGHSHQGRQWKHXOWLPDWHEUHDNLQJFDSDFLW\
DUHGHÀQHGE\WHVWVFDUULHGRXWLQDFFRUGDQFHZLWKVWDQGDUG,(&
,ILQVWDOODWLRQFRQIRUPLW\LVQRWFKHFNHGE\W\SHWHVWVLWLVDOVRQHFHVVDU\WR
b use insulated bars for circuit-breaker connections
b segregate the busbars using insulating screens.
)RU&96WRGHYLFHVWHUPLQDOVKLHOGVDQGLQWHUSKDVHEDUULHUVDUH
UHFRPPHQGHGDQGPD\EHPDQGDWRU\GHSHQGLQJRQWKHRSHUDWLQJYROWDJHRIWKH
GHYLFHDQGW\SHRILQVWDOODWLRQ À[HGZLWKGUDZDEOHHWF
Power connections
7KHWDEOHEHORZLQGLFDWHVWKHUXOHVWREHUHVSHFWHGIRU&96WRGHYLFHVWR
HQVXUHLQVXODWLRQRIOLYHSDUWVIRUÀ[HGGHYLFHV
DB400040
Possible, recommended or mandatory accessories: No insulating Interphase Long terminal Short terminal
accessory barriers shields (1) shields
DB115059
DB115060
DB115061
:LWK
Extension terminals
Possible
Cables + crimp lugs Mandatory
No (instead of ph. Recommended
(supplied)
barriers)
(1) Long terminal shields provide a degree of protection of IP40 (ingress) and IK07 (mechanical
impact).
%
Installation in switchboards
Installation example
Safety clearance
Minimum distance between two Minimum distance between circuit
adjacent circuit breakers breaker and front or rear panels
DB400046
DB400047
Front F
panel
A1
B=0 F
Bare or painted sheet metal Note: if F < 8 mm: an insulating screen or long
terminal shield is mandatory.
Minimum distance between circuit breaker and top, bottom or side panels
DB400048
DB400049
DB400050
D1 D1 D1
D2 C1
Devices without accessories. Devices with interphase barriers or long terminal shields.
Bars
Bars
Live busbars.
B-5