Example of Fault Calculations
Example of Fault Calculations
Below is a single line diagram for an equivalent system taken from [1]. This example makes a
few typical assumptions such ignoring resistance, load, etc. The flow of current is assumed
towards the fault. Most of the calculations are from [1] except for some added steps for clarity.
The network sequences are different from the ones in [1].
Point ‘F’ is the fault location which will be used later.
• 80MVA
• 13.8kV delta/115kV grounded wye
• 𝑍1 = 𝑍2 = 𝑍0 = 11% on transformer rating as a base
100
• 𝑍1 = 𝑍2 = 𝑍0 = 11% ∗ = 13.75% on 100MVA base
80
• Length: 30 miles
• 115kV
• X1 = X2 = 24Ω
• X0 = 82Ω
kV2 1152
• Zbase = 𝑀𝑉𝐴LL = = 132.25 Ω
𝑏𝑎𝑠𝑒 100
24
• X1 = X2 = 100% ∗ 132.25 = 18.147% on 100MVA, 115kV base
82
• X0 = 100% ∗ 132.25 = 62.0% on 100MVA, 115kV base
Transformer (T2):
• 150MVA
• 230kV grounded wye/115kV grounded wye/13.2kV delta
• H: 230kV
• L: 13.2kV
• M: 115kV
• XHM = 5.5% on transformer rating base
• XHL = 36% on transformer rating base
• XML = 28% on transformer rating base
100
• XHM = 5.5% ∗ 150 = 3.667% on 100MVA base
100
• XHL = 36% ∗ 150 = 24% on 100MVA base
100
• XML = 28% ∗ 150 = 18.667% on 100MVA base
1 1
• 𝑋𝐻 = 2 ∗ (𝑋𝐻𝑀 + 𝑋𝐻𝐿 − 𝑋𝑀𝐿 ) = 2 ∗ (3.667 + 24 − 18.667) = 4.50%
1 1
• 𝑋𝑀 = 2 ∗ (𝑋𝐻𝑀 + 𝑋𝑀𝐿 − 𝑋𝐻𝐿 ) = 2 ∗ (3.667 + 18.667 − 24) = −0.833%
1 1
• 𝑋𝐿 = 2 ∗ (𝑋𝐻𝐿 + 𝑋𝑀𝐿 − 𝑋𝐻𝑀 ) = 2 ∗ (24 + 18.667 − 3.667) = 19.50%
Equivalent System:
• 230kV
• X1 = X2 = 3% on 100MVA, 230kV base
• X0 = 4% on 100MVA, 230kV base
This circuit can be simplified by summing up (combining) series elements as shown below:
Equivalent positive sequence impedance at bus G:
(𝑗𝑋’’𝑑 + 𝑗𝑋𝑇1 ) 𝑖𝑛 𝑝𝑎𝑟𝑎𝑙𝑙𝑒𝑙 𝑤𝑖𝑡ℎ (𝑗𝑋1𝐺𝐻 + 𝑗𝑋𝐻𝑀 + 𝑗𝑋1𝑆 ), so equivalent positive sequence
impedance:
(𝑗𝑋’’ +𝑗𝑋 )∗(𝑗𝑋 +𝑗𝑋 +𝑗𝑋 ) 𝑗0.3375∗𝑗0.2481
𝑍1 = (𝑗𝑋’’ 𝑑+𝑗𝑋 𝑇1)+(𝑗𝑋1𝐺𝐻 +𝑗𝑋𝐻𝑀 +𝑗𝑋1𝑆 ) = 𝑗0.3375+𝑗0.2481
𝑑 𝑇1 1𝐺𝐻 𝐻𝑀 1𝑆
𝑍1 = 𝑗0.1430 𝑝𝑢
Equivalent negative sequence impedance at bus G:
𝑍2 = 𝑗0.1430 𝑝𝑢 (same as positive sequence except no voltage source)
𝑍0 = 𝑗0.1141 𝑝𝑢
Redrawing with the equivalent sequence networks:
For clarity, meshes (K), (s), (m), (n), (p), and (q) are depicted on the circuit above, which are used to
calculate various currents.
0.1375 0.1375
= 0.8084 = 0.1701𝑝𝑢 flow through mesh (q)
0.1375+0.6709
𝑰𝑲 + 𝑰𝒎 + 𝑰𝒑 = 𝟒. 𝟏𝟗𝟑 𝒑𝒖
𝑰𝒔 + 𝑰𝒏 + 𝑰𝒒 = 𝟑. 𝟑𝟎𝟕 𝒑𝒖
B-phase current:
𝐼𝑏 = 𝑎2 𝐼1 + 𝑎𝐼2 + 𝐼0 = 𝑎2 𝐼1 + 𝑎𝐼1 + 𝐼0 = (𝑎2 + 𝑎)𝐼1 + 𝐼0 = −𝐼1 + 𝐼0
C-phase current:
𝐼𝑐 = 𝑎𝐼1 + 𝑎2 𝐼2 + 𝐼0 = 𝑎𝐼1 + 𝑎2 𝐼1 + 𝐼0 = (𝑎2 + 𝑎)𝐼1 + 𝐼0 = −𝐼1 + 𝐼0
𝑰𝒃 = 𝑰𝒄 = −𝟏. 𝟎𝟏𝟓𝟓 𝒑𝒖
Current flow into T1 neutral: 𝐼𝑛,𝑇1 = 3 ∗ 2.07475 = 6.224 𝑝𝑢
𝑋 ∗(𝑋 +𝑋 ) 0.195∗(0.04+0.045)
{𝑋𝐿 𝑖𝑛 𝑝𝑎𝑟𝑎𝑙𝑙𝑒𝑙 𝑤𝑖𝑡ℎ (𝑋0𝑆 + 𝑋𝐻 )} = 𝑋 𝐿+(𝑋0𝑆 +𝑋𝐻 ) = 0.195+(0.04+0.045)
𝐿 0𝑆 𝐻
0.195 ∗ 0.085
= = 0.0592 𝑝𝑢
0.28
0.195
𝐼𝐻 = *0.42525=0.2961 pu will flow through the system neutral and H
0.28
0.085
𝑰𝑳 = *0.42525=0.1291 pu will flow through transformer (T2) tertiary (13.2kV winding). This
0.28
is the portion of the zero-sequence current that the delta winding should carry. Note that
system impedances are important in sizing these delta windings (stabilizing). While ignoring
system impedances could lead to over-sizing the primary and secondary winding (main
windings), this could lead to under-sizing the stabilizing delta winding. One can experiment with
this exercise by changing the system impedances and recalculating the various currents
(through high side winding, low side winding, and delta). The system impedances play a big
factor in the current distribution.
[1] Protective Relaying, Principles and Applications 4th Edition, 4.11, p.91.