YT OptiView w/ Standard Starter ELINK YORK TALK 3 Micro Board: 031-01730 / 02430 -xxx
Item Version Rev Date YORK P N Chksum Baud COMMENTS
1 C.OPT.02.09.008 19.2K
2
3
4
5
6
7
8
9
10
Revision: YT OptiView (Rev K_03) Tab: Standard Property of York International York, PA Page: 1 of 16
9/24/2010
NOTES
LON SNVTS Used: SNVT_count (8), SNVT_lev_percent (81), SNVT_temp_p (105), SNVT_switch (95) , SNVT_time_minute (123) , SNVT_freq_hz (76) , SNVT_amp (01) , SNVT_elec_kwh (13) , SNVT_power_kilo (83) ,
1
SNVT_volt (44) , SNVT_volt_ac (138), SNVT_press_p (87)
2 Modbus Scaling indicated in BOLD with an (*) asterisk are User Configurable, if necessary, through the USER's Report. See a qualified JCI technician for details.
MODBUS scaling factors indicated in BOLD with an (*) asterisk are User Configurable, by a field technician if necessary. All Modbus values are of the type SIGNED with the exception of the User Configurabale values that are all
3
UNSIGNED. Modbus Function Types Supported (ENG P03-P06 = Types 03, 06, 16) , ( ENG P07- P10 = 01, 03, 05, 15, 06, 16), (ENG P11-P35, P56-P79) = 03, 04) , (ENG P36-P55, P80 -P84 = 01, 02, 03)
4 BACnet Engineering Units shown with an (*) Asterisk will be assigned a BACnet Eng Unit type of (95) ie NO UNITS.
5 Status Codes: Special Display characters such as (, ), [, ], {, },/,\,%,< and > are not compatible with Elink N2 formats. Substitute text strings , "-", PCT, GTN will be used .
6 Status Codes: Status Code Text string lengths are limited to 60 total characters (including spaces)
7
8
9
10
NOTE: The Appropriate Product Code Listing Summary Should Accompany Document
Revision: YT OptiView (Rev K_03) Tab: Standard Property of York International York, PA Page: 2 of 16
9/24/2010
ENG YTM Operational Code ENG YTM Safety Code ENG YTM Cycling Code
PAGE SC.1 PAGE SC.2 PAGE SC.3
P56 OPER.CODE P57 SAFETY.FLT P58 CYCLING.CODE
0 Unit Stopped - Ready To Start 0 No Abnormal Condition 0 No Abnormal Condition
1 Unit Stopped - Local Shutdown 1 Evaporator - Low Pressure 1 Multi-Unit Cycling - Contacts Open
2 Unit Stopped - Remote Shutdown 2 Evaporator - Transducer Or Leaving Liquid Probe 2 System Cycling - Contacts Open
3 Unit Stopped - Warning Active 3 Evaporator - Temperature Transducer 4 Oil - Low Temperature
4 Unit Stopped - Cycling Shutdown 4 Condenser - High Pressure Contacts Open 5 Control Panel - Power Failure
5 Unit Stopped - Safety Shutdown 5 Condenser - High Pressure 6 Leaving Chilled Liquid - Low Temperature
6 Unit Start Inhibit 6 Condenser - Pressure Transducer Out Of Range 7 Leaving Chilled Liquid - Flow Switch Open
7 Unit Starting 7 Auxiliary Safety - Contacts Closed 8 Condenser - Flow Switch Open
8 Unit Running - No Abnormal Condition 8 Discharge - Low Temperature 9 Motor Controller - Contacts Open
9 Unit Running - Warning Active 9 Discharge - High Temperature 10 Motor Controller - Loss Of Current
10 Unit Running - Chiller Unload Before Shutdown 10 Oil - High Temperature 11 Power Fault
11 Unit Coastdown 11 Oil - Low Differential Pressure 12 Control Panel - Schedule
12 Oil - High Differential Pressure 13 Starter - Low Supply Line Voltage
21 Control Panel - Power Failure 14 Starter - High Supply Line Voltage
23 Motor Or Starter - Current Imbalance
Revision: YT OptiView (Rev K_03) Tab: Standard Property of York International York, PA Page: 3 of 16
9/24/2010
Revision: YT OptiView (Rev K_03) Tab: Standard Property of York International York, PA Page: 4 of 16
9/24/2010
YT OptiView w/ SSS ELINK YORK TALK 3 Micro Board: 031-01730 / 02430 -xxx
Item Version Rev Date YORK P N Chksum Baud COMMENTS
1 C.OPT.02.09.008 19.2K
2
3
4
5
6
7
8
9
10
Revision: YT OptiView (Rev K_03) Tab: with SSS Property of JCI, York, PA Page: 5 of 16
9/24/2010
NOTES
LON SNVTS Used: SNVT_count (8), SNVT_lev_percent (81), SNVT_temp_p (105), SNVT_switch (95) , SNVT_time_minute (123) , SNVT_freq_hz (76) , SNVT_amp (01) , SNVT_elec_kwh (13) , SNVT_power_kilo (83) ,
1
SNVT_volt (44) , SNVT_volt_ac (138), SNVT_press_p (87)
2 Modbus Scaling indicated in BOLD with an (*) asterisk are User Configurable, if necessary, through the USER's Report. See a qualified JCI technician for details.
MODBUS scaling factors indicated in BOLD with an (*) asterisk are User Configurable, by a field technician if necessary. All Modbus values are of the type SIGNED with the exception of the User Configurabale values that are all
3
UNSIGNED. Modbus Function Types Supported (ENG P03-P06 = Types 03, 06, 16) , ( ENG P07- P10 = 01, 03, 05, 15, 06, 16), (ENG P11-P35, P56-P79) = 03, 04) , (ENG P36-P55, P80 -P84 = 01, 02, 03)
4 BACnet Engineering Units shown with an (*) Asterisk will be assigned a BACnet Eng Unit type of (95) ie NO UNITS.
5 Status Codes: Special Display characters such as (, ), [, ], {, },/,\,%,< and > are not compatible with Elink N2 formats. Substitute text strings , "-", PCT, GTN will be used .
6 Status Codes: Status Code Text string lengths are limited to 60 total characters (including spaces)
7
8
9
10
NOTE: The Appropriate Product Code Listing Summary Should Accompany Document
Revision: YT OptiView (Rev K_03) Tab: with SSS Property of JCI, York, PA Page: 6 of 16
9/24/2010
Revision: YT OptiView (Rev K_03) Tab: with SSS Property of JCI, York, PA Page: 7 of 16
9/24/2010
Revision: YT OptiView (Rev K_03) Tab: with SSS Property of JCI, York, PA Page: 8 of 16
9/24/2010
YT OptiView w/ VSD ELINK YORK TALK 3 Micro Board: 031-01730 / 02430 -xxx
Item Version Rev Date YORK P N Chksum Baud COMMENTS
1 C.OPT.02.09.008 19.2K
2
3
4
5
6
7
8
9
10
Revision: YT OptiView (Rev K_03) Tab: with VSD Property of JCI , York, PA Page: 9 of 16
9/24/2010
REF Type Instance Name Name Type Address Scale POINT LIST DESCRIPTION 1 2 3 4 5 6 7 8 9 10 REF
see notes 2, 3
P43 B BV12 BD 12 0072 N/A P43
P44 B BV13 BD 13 0073 N/A P44
P45 B BV14 BD 14 0074 N/A P45
P46 B BV15 BD 15 0075 N/A P46
P47 B BV16 BD 16 0076 N/A P47
P48 BV.42 BV17 ACC VALVE SURGE MAP nvoACCVSM SNVT_switch BD 17 0077 N/A 0/1 Adaptive Capacity Control Valid Surge Map (False =0, True =1) S P48
P49 BV.43 BV18 ACC NEW SURGE POINT nvoACCNSP SNVT_switch BD 18 0078 N/A 0/1 Adaptive Capacity Control New Surge Point (False =0, True =1) S P49
BV19
nvoVSDWtrPumpRly
P50 BO.30 VSD COOL PUMP RUN RELAY SNVT_switch BD 19 0079 N/A 0/1 Variable Speed Drive Water Pump Relay S P50
P51 BV.46 BV20 VSD HARMONIC FILTER INST nvoHarmonicFltr SNVT_switch BD 20 0080 N/A 0/1 Harmonic Filter Installed (False =0, True =1) S P51
P52 BV.44 BV21 ACC SURGE DETECTION TYPE nvoACCSurgeType SNVT_switch BD 21 0081 N/A 0/1 Adaptive Capacity Control Surge Type (Open = Delta P/P, Made=Current) S P52
P53 BV22 BD 22 0082 N/A
P54 BV23 BD 23 0083 N/A
P55 BV24 BD 24 0084 N/A
P56 SC.1 MV1 UNIT OPERATION CODE nvoOperCode SNVT_str_asc ADI 1 0030 X1 enum Operation Code S P56
P57 SC.2 MV2 UNIT SAFETY FAULT CODE nvoSafetyCode SNVT_str_asc ADI 2 0031 X1 enum Unit Safety Fault Code S P57
P58 SC.3 MV3 UNIT CYCLING FAULT CODE nvoCyclingFault SNVT_str_asc ADI 3 0032 X1 enum Unit Cycling Fault Code S P58
P59 SC.4 MV4 UNIT WARNING FAULT CODE nvoWarnFault SNVT_str_asc ADI 4 0033 X1 enum Unit Warning Fault Code S P59
P60 SC5 MV5 UNIT CONTROL SOURCE nvoUnitCtrlSrce SNVT_count ADI 5 0034 X1 enum Unit Control Source [0=Local, 1 = ISN, 2= Analog, 3 = Digital, 4 = Modem] S P60
P61 MV6 ADI 6 0035 X1 P61
P62 MV7 ADI 7 0036 X1 P62
P63 MV8 ADI 8 0037 X1 P63
P64 MV9 ADI 9 0038 X1 P64
P65 MV10 ADI 10 0039 X1 P65
P66 AV30 ADF 30 0040 X1 P66
P67 AV31 ADF 31 0041 X1 P67
P68 AV.19 AV32 ANTI RECYCLE TIME REMAIN nvoAntiRecycle SNVT_time_minute ADF 33 0042 X1 min Anti-Recycle Time Remaining P68
P69 AV.79 AV33 ACC MAP PRV POS nvoACCMapPRVPos SNVT_lev_percent ADF 33 0043 X1 % Adaptive Capacity Control Map PRV Position S P69
P70 AI.51 AV34 VSD OUTPUT VOLTAGE nvoVSDOutputVolt SNVT_volt ADF 34 0044 X 10 volt Variable Speed Drive OutputVoltage S P70
P71 AV.71 AV35 VSD INPUT KW nvoVSDInputPwr SNVT_power_kilo ADF 35 0045 X1 * kW Variable Speed Drive Input Power S P71
P72 AV.72 AV36 VSD INPUT MWH nvoVSDKWH SNVT_elec_kwh ADF 36 0046 X1 * kWH Variable Speed Drive Killowatt Hours S P72
P73 AI.56 AV37 VSD DC LINK VOLTAGE nvoVSDDCBusVolt SNVT_volt ADF 37 0047 X1 * volt Variable Speed Drive DC Bus Voltage S P73
P74 AI.57 AV38 VSD DC LINK CURRENT nvoVSDInvertCur SNVT_amp ADF 38 0048 X1 * amp Variable Speed Drive Inverter Link Current S P74
P75 AV.75 AV39 VSD SURGE COUNT nvoACCSurgeCnt SNVT_count ADF 39 0049 X1 * count Adaptive Capacity Control Surge Count S P75
P76 AI.52 AV40 VSD OUTPUT FREQUENCY nvoVSDOutFreq SNVT_freq_hz ADF 40 0050 X1 Hz Variable Speed Drive Output Frequency S P76
P77 AV.83 AV41 VSD MAX VOLTAGE THD nvoHFltrMaxVTHD SNVT_lev_percent ADF 41 0051 X1 % Harmonic Filter Maximum Voltage Total Harmonic Distortion S P77
P78 AV.84 AV42 VSD MAX CURRENT TDD nvoHFltrMaxATDD SNVT_lev_percent ADF 42 0052 X1 % Harmonic Filter Maximum Current Total Demand Distortion S P78
P79 AV.82 AV43 VSD HFILTER SUPPLY KVA nvoHFltrTotSKVA SNVT_count ADF 43 0053 X1 KVA Harmonic Filter Total Supply KVA S P79
P80 B BV25 BD 25 0085 N/A P80
P81 B BV26 BD 26 0086 N/A P81
P82 B BV27 BD 27 0087 N/A P82
P83 B BV28 BD 28 0088 N/A P83
P84 B BV29 BD 29 0089 N/A P84
NOTES
LON SNVTS Used: SNVT_count (8), SNVT_lev_percent (81), SNVT_temp_p (105), SNVT_switch (95) , SNVT_time_minute (123) , SNVT_freq_hz (76) , SNVT_amp (01) , SNVT_elec_kwh (13) , SNVT_power_kilo (83) ,
1
SNVT_volt (44) , SNVT_volt_ac (138), SNVT_press_p (87)
2 Modbus Scaling indicated in BOLD with an (*) asterisk are User Configurable, if necessary, through the USER's Report. See a qualified JCI technician for details.
MODBUS scaling factors indicated in BOLD with an (*) asterisk are User Configurable, by a field technician if necessary. All Modbus values are of the type SIGNED with the exception of the User Configurabale values that are all
3
UNSIGNED. Modbus Function Types Supported (ENG P03-P06 = Types 03, 06, 16) , ( ENG P07- P10 = 01, 03, 05, 15, 06, 16), (ENG P11-P35, P56-P79) = 03, 04) , (ENG P36-P55, P80 -P84 = 01, 02, 03)
4 BACnet Engineering Units shown with an (*) Asterisk will be assigned a BACnet Eng Unit type of (95) ie NO UNITS.
5 Status Codes: Special Display characters such as (, ), [, ], {, },/,\,%,< and > are not compatible with Elink N2 formats. Substitute text strings , "-", PCT, GTN will be used .
6 Status Codes: Status Code Text string lengths are limited to 60 total characters (including spaces)
7
8
9
10
NOTE: The Appropriate Product Code Listing Summary Should Accompany Document
Revision: YT OptiView (Rev K_03) Tab: with VSD Property of JCI , York, PA Page: 10 of 16
9/24/2010
YT OptiView with VSD ( extended) Section 2 ELINK YORK TALK 3 Micro Board: 031-01730 or 031-02430
ENG GPIC BACnet BACnet LON LON N2 ENG ENG
MODBUS
PAGE Object Object & Object Profile SNVT Metasys UNITS POINT LIST CODE: S = STANDARD O = OPTIONAL N = NOT AVAILABLE PAGE
REF Type Instance Name Name Type Address Address Scale Imperial POINT LIST DESCRIPTION 1 2 3 4 5 6 7 8 9 10 REF
see notes 2, 3
P03 A ADF 44 0101 Div 10 P03
P04 A ADF 45 0102 Div 10 P04
P05 A ADF 46 0103 Div 10 P05
P06 A ADF 47 0104 Div 10 P06
P07 B BD30 0161 N/A P07
P08 B BD31 0162 N/A P08
P09 B BD32 0163 N/A P09
P10 B BD33 0164 N/A P10
P11 A AV 105 ADF 48 0105 X 10 P11
P12 A AV 106 ADF 49 0106 X 10 P12
P13 A AV 107 ADF 50 0107 X 10 P13
P14 A AV 108 ADF 51 0108 X 10 P14
P15 A AV 109 ADF 52 0109 X 10 P15
P16 AI.58 AV 110 VSD INTERNAL AMBIEN TEMP nvoVSDInternalT SNVT_temp_p (105) ADF 53 0110 X10 F° VSD Internal Ambient Temp (Low voltage VSD only) S P16
P17 AI.59 AV 111 VSD CONVERTER HSINK TEMP nvoVSDHeatSinkT SNVT_temp_p (105) ADF 54 0111 X10 F° VSD Converter Heatsink Temp (Low voltage VSD only) S P17
P18 AI.50 AV 112 PRE ROTATIONAL VANE POS nvoPRVPosition SNVT_lev_percent (81) ADF 55 0112 X10 % Pre Rotation Vanes Position S P18
P19 AV.78 AV 113 ACC MAP OUTPUT FREQ nvoACCMapOutFreq SNVT_freq_hz (76) ADF 56 0113 X10 HZ ACC Map Output Frequency (Low Voltage VSD only) S P19
P20 AV.42 AV 114 REFRIGERANT LEVEL SP nvoRefLvlSP SNVT_lev_percent (81) ADF 57 0114 X10 % Refrigerant Level Setpoint S P20
P21 AI.10 AV 115 DROP LEG REFRIG TEMP nvoDropLegTemp SNVT_temp_p (105) ADF 58 0115 X10 F° Drop Leg Refrigerant Temperature S P21
P22 A AV 116 ADF 59 0116 X1 * P22
P23 A AV 117 ADF 60 0117 X1 * P23
P24 A AV 118 ADF 61 0118 X1 P24
P25 A AV 119 ADF 62 0119 X1 P25
P26 A AV 120 ADF 63 0120 X1 P26
P27 A AV 121 ADF 64 0121 X1 P27
P28 A AV 122 ADF 65 0122 X1 P28
P29 A AV 123 ADF 66 0123 X1 P29
P30 A AV 124 ADF 67 0124 X1 P30
P31 A AV 125 ADF 68 0125 X1 * P31
P32 A AV 126 ADF 69 0126 X1 * P32
P33 A AV 127 ADF 70 0127 X1 * P33
P34 A AV 128 ADF 71 0128 X1 P34
P35 A AV 129 ADF 72 0129 X1 P35
P36 B BV105 BD 34 0165 N/A P36
P37 B BV106 BD 35 0166 N/A P37
P38 B BV107 BD 36 0167 N/A P38
P39 B BV108 BD 37 0168 N/A P39
P40 B BV109 BD 38 0169 N/A P40
P41 B BV110 BD 39 0170 N/A P41
P42 B BV111 BD 40 0171 N/A P42
NOTES
11
12
13
14
15
16
17
18
19
20
Revision: YT OptiView (Rev K_03) Tab: with VSD Property of JCI , York, PA Page: 11 of 16
9/24/2010
NOTES
21
22
23
24
25
26
27
28
29
30
Revision: YT OptiView (Rev K_03) Tab: with VSD Property of JCI , York, PA Page: 12 of 16
9/24/2010
Revision: YT OptiView (Rev K_03) Tab: with VSD Property of JCI , York, PA Page: 13 of 16
9/24/2010
ENG YTM Cycling Code ENG YTM Cycling Code ENG YTM Warning Code
PAGE SC.3 PAGE SC.3 (continued) PAGE SC.4
9 Motor Controller - Contacts Open 54 Harmonic Filter - DC Current Transformer 1 12 Purge - Excess Purge
10 Motor Controller - Loss Of Current 55 Harmonic Filter - DC Current Transformer 2 14 Motor - High Current Limit
11 Power Fault 15 Vanes Uncalibrated
12 Control Panel - Schedule reserved 16 Vanes Uncalibrated - Fixed Speed Operation
13 Starter - Low Supply Line Voltage 73 VSD - Serial Communications 17 Harmonic Filter - Operation Inhibited
14 Starter - High Supply Line Voltage reserved 18 Harmonic Filter - Data Loss
17 VSD Initialization Failure 19 Harmonic Filter - Input Frequency Out Of Range
18 VSD Shutdown - Requesting Fault Data 26 External I/O Board Serial Communications
19 VSD - High Phase A Instantaneous Current
20 VSD - High Phase B Instantaneous Current
21 VSD - High Phase C Instantaneous Current
22 VSD - Phase A Gate Driver
23 VSD - Phase B Gate Driver
24 VSD - Phase C Gate Driver
25 VSD - Single Phase Input Power
26 VSD - High DC Bus Voltage
27 VSD - Logic Board Power Supply
28 VSD - Low DC Bus Voltage
29 VSD - DC Bus Voltage Imbalance
30 VSD - High Internal Ambient Temperature
31 VSD - Invalid Current Scale Selection
32 VSD - Low Phase A Inverter Heatsink Temperature
33 VSD - Low Phase B Inverter Heatsink Temperature
34 VSD - Low Phase C Inverter Heatsink Temperature
35 VSD - Low Converter Heatsink Temperature
36 VSD - Precharge - DC Bus Voltage Imbalance
37 VSD - Precharge - Low DC Bus Voltage
38 VSD - Logic Board Processor
39 VSD - Run Signal
40 VSD - Serial Communications
41 VSD - Stop Contacts Open
42 Harmonic Filter - Logic Board Or Communications
43 Harmonic Filter - High DC Bus Voltage
44 Harmonic Filter - High Phase A Instantaneous Current
Revision: YT OptiView (Rev K_03) Tab: with VSD Property of JCI , York, PA Page: 14 of 16
9/24/2010
Revision: YT OptiView (Rev K_03) Tab: with VSD Property of JCI , York, PA Page: 15 of 16
9/24/2010
Revision: YT OptiView (Rev K_03) Tab: with VSD Property of JCI , York, PA Page: 16 of 16