Power System Stabilizers Design For Multimachine Power Systems Using Local Measurements
Power System Stabilizers Design For Multimachine Power Systems Using Local Measurements
Power System Stabilizers Design For Multimachine Power Systems Using Local Measurements
Abstract—In this paper, a technique for designing fixed param- with all shaft dynamics disabled], agree closely with P-Vr
eter decentralized power system stabilizers (PSSs) for intercon- TF [ with all rotor shaft dynamics disabled].
nected power systems is proposed. In the proposed method, local It is also shown that for the purpose of phase compensation,
information available at each machine in the multimachine en-
the method of residue also agree closely with the P-Vr phase
vironment, is used to tune parameters of PSS. Conventional de-
sign techniques such as P-Vr frequency response approaches, and response. However, this formulation of PSS design is not
the method of residues are based on complete system information, adequate for very large interconnected power systems. In [10],
wherein phase angles of residues are consistent with the P-Vr phase a decentralized PSS design technique is presented using local
response and can be used with confidence for design purposes. It plant information; wherein, system dynamics of the th machine
is shown that magnitude and phase information of the proposed in a multimachine system is linearized by taking secondary
GEP TF agrees closely with that of P-Vr TF and yields a robust bus voltage of the step-up transformer as reference. However,
stabilizer. Nonlinear simulation and eigenvalue analysis show the
efficacy of the proposed stabilizer to damp out the interarea and owing to aforestated premise, magnitude and phase response of
local modes of oscillations effectively over a wide range of oper- the modified GEP TF differ markedly from P-Vr TF synthesized
ating conditions. Superiority of the proposed approach over the in [12]. Recently in [11], a phase compensation method for PSS
conventional approaches is demonstrated with simulation studies design is described for machine in a multimachine system,
on two widely used multimachine systems. by varying external reactance of generator connected to infinite
Index Terms—Eigenvalue, multimachine systems, power system bus. Authors have introduced a synthetic system, wherein
dynamic stability, power system stabilizer, small signal stability. the maximum value of external reactance is determined by
the lowest desired values for interarea frequencies, while the
minimum is set by the step-up transformer of generating unit.
I. INTRODUCTION However, this optimization routine is fairly time consuming
I N the absence of natural damping, power systems can expe- for large interconnected network, particularly under various
rience low-frequency dynamic problem due to increased ef- generation dispatch conditions.
forts to transfer electric power over vast geographical and elec- Lam et al. [4] pointed out that the expression for calculating
trical distances. Auxiliary controller called power system sta- the frequency response of GEP TF of a given generator in a mul-
bilizer (PSS) provides additional damping to the synchronous timachine environment has two components; the first compo-
generator rotor oscillations by modulating the generator excita- nent depends only on the associated generator, while the second
tion. PSS design has been well studied in the literature over the component depends on the external network. Attributed by diag-
past few decades [1]–[11], [17], [18], [22]. onal dominance of network admittance matrix, the second com-
The basis of PSS design was presented in the classic paper ponent is largely unaffected by the dynamics of the generators
by deMello et al. [1] for a single machine infinite bus (SMIB) in the external network [4]. More importantly, phase responses
system. In this approach, phase-compensation of the transfer of the second component are usually leading and render lesser
function (GEP(s)) (i.e., the ratio of electrical torque developed gain of GEP TF over the range of oscillation frequencies.
on the shaft of the generator and the voltage reference input to The method in this paper advances the PSS design technique
the AVR) is provided by the PSS transfer function. of [10], using local plant information by incorporating external
A theoretical analysis by Lam et al. [4] showed that in reactance originating from generating unit step-up transformer.
the multimachine environment, GEP TF computed for SMIB Thus as aforementioned, phase response of GEP TF of the
system is adequate for PSS design. Investigation in prior works proposed method—incorporating external network—adds
by Gibbard [9], Gurrala [10], and Marco [11] are motivated phase lead to the phase response obtained from [10] and is in
by frequency analysis cited in [4]. Gibbard [9] observes that close agreement with phase response of P-Vr TF [12], which is
the phase response of GEPSDD [measured TF from voltage obtained by complete system information. Additionally, gain
reference to the terminal voltage , of GEP TF of the proposed method is lesser than [10], and is
also in close agreement with gain of P-Vr TF [12]. Thus, the
proposed method provides information of critical PSS gain
Manuscript received November 27, 2014; revised March 10, 2015, May 05,
2015, and July 01, 2015; accepted July 14, 2015. Paper no. TPWRS-01629- ( ) more accurately and higher than[10]; while P-Vr design
2014. technique does not provide any information regarding .
The author is with the Department of Electrical Engineering, Indian Institute In essence, the main contribution of this paper is to determine
of Science, Bangalore 560012, India (e-mail: ajit.kum01@gmail.com).
Color versions of one or more of the figures in this paper are available online
relatively truthful value of phase lead compensation and
at http://ieeexplore.ieee.org. than [10] for designing PSS using local measurements. The
Digital Object Identifier 10.1109/TPWRS.2015.2460260 PSS designed using proposed technique have shown improved
0885-8950 © 2015 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
where .
The stator equations in the algebraic form are given as where , , and .
is the power factor angle at the high voltage bus w.r.t .
(5)
III. PROPOSED APPROACH
(6)
The authoritative linearized model of SMIB system, formally
The variables used above employ conventional notations [13], known as Heffron-Phillip's model ( -constant), was introduced
[14]. The rotor angle with respect to the high voltage bus of first in [15]. Recently, a modified Heffron-Phillip's model
transformer ( ) is denoted as . The angle (G-constant [10]) has been proposed for interconnected power
and voltage are given in (7) and (8), respectively [3]: systems. Accordingly, we follow the line of investigation used
in [10] (i.e., to replace stiff bus voltage phasor of SMIB system
(7) with a non-stiff secondary bus voltage phasor of step-up
transformer), for establishing a linearized model of a single
machine in a multimachine environment using local informa-
(8)
tion. Firstly, we consider two lossless ( ) transmission
lines having reactance , and terminal voltage
Here, , , and can be evaluated from the secondary bus and respectively (see Fig. 3). Stator currents and
of the step-up transformer[10]. Intonation for and are given are given as
in (9) and (10), respectively:
(9) (13)
(10)
where ;
and .
Locally procurable data ( ) for the trans- (14)
mission line originating from the secondary bus of step-up trans-
where .
former [shown in Fig. 1(a)] are put to evaluate and (i.e.,
Posterior little algebraic manipulations (13) and (14) can be
(see Fig. 2), they are given as
rewritten as
(11) (15)
(12) (16)
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
KUMAR: POWER SYSTEM STABILIZERS DESIGN FOR MULTIMACHINE POWER SYSTEMS USING LOCAL MEASUREMENTS 3
(21)
where .
The subscripts and refer to the and axis respectively
in Kron's reference frame, and and refers to the and axis,
respectively, in Park's reference frame. In the preceding works
[10] and [16], wherein infinite bus is replaced with a
non-stiff bus for designing PSS and a nonlinear voltage
regulator for interconnected power systems, respectively. In the
same spirit, in this work we will examine quid pro quo of
with the equivalent bus for designing PSS. The modified
equation, after replacing with is given as
(22)
Fig. 4. Linearized model of a single machine in a connected network.
-constants [given in (23)] are evaluated using (1)–(6) and
(22) for a lossless network ( ) on the stator side, by lin-
where earization of the th machine. In essence, constants to are
analogous to the classical HP constants to [15], while
to represents the non-stiffness property of the equiv-
alent bus . It must be pointed out at the very outset that,
as in the preceding work [10], to can also be obtained
in real time by locally measured data. Reader is referred to [1],
(17) for a detail discussion regarding computation of constants to
for a systems with transmission loss:
(18)
(19)
(20)
(23)
Thus, for lossless transmission lines emanating from sec-
ondary bus of the step-up transformer to the external network where .
[see Fig. 1(a)], its equivalent bus voltage magnitude and The linearized scheme of the proposed model of a single ma-
reactance are given in (18) and (19), respectively. The chine in a connected network is shown in Fig. 4. The linearized
angle difference between the rotor angle and the equivalent state equations for each generator in a connected network has
bus , denoted as , is given in (20). It is noteworthy to the form
mention that the angle is obtained from local quantification
of power and voltage measurements at the secondary bus of (24)
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
Fig. 5. Electromechanical and exciter modes loci with pole residues shown in black arrow limited by cyan dots ( : Nominal operating condition).
TABLE I
ELECTROMECHANICAL MODE SENSITIVITY OF SMIB SYSTEM
overcompensation is often preferred due to its damping perfor-
mance—ignoring the gain modification of lead compensation
[17]. Its associated risks in PSS tuning are 1) negative synchro-
nizing torque component and 2) faster instability of susceptible
modes, leading to a much reduced gain margin. Additionally,
a prerequisite [18] of phase lag to nullify overcompensation at
frequency below 0.5 Hz for case C will be less than case A. Re-
lated to Fig. 5, note that in contrast with case A, exciter mode
of case C is much closer to case E. Observe that EM mode for
where .
nominal operating condition, shown in square ( ), of the plant
The matrices , , and can be easily obtained from the
model proposed in [10] (i.e., case A) is in the left half of the
linearized model shown in Fig. 4.
-plane; while for case C, it is in the right half and is in the
IV. ROBUSTNESS ASSESSMENT close proximity of case E. Stein[19] posited that “unstable sys-
tems are quantifiably and fundamentally more difficult to con-
In this section, we will examine the robustness of the pro-
trol than stable systems”; under this premise, case C plant model
posed plant model for SMIB power system. As an SMIB system
is more difficult to control than case A:
qualitatively reveal important outlook of the behavior of a mul-
timachine system and is very relevant in interpreting the general (25)
concepts of power systems stability [1]. Data of system ren-
dered in [13] is put to use here. Nominal real power input of Next, a mixed sensitivity—control effort optimization and
the machine , and line reactance of the system as shown output disturbance rejection—based robust damping con-
in Fig. 3 is 1.0 p.u. and 0.3 p.u., respectively. For the discussed troller is designed for all three cases, to analyze the closed
plant model, five different cases A-E are shown in Table I; for loop performance with additional pole-placement constraints
the sake of brevity, we only present results of cases A, C, and (shown in Fig. 5) expressed as linear matrix inequalities (LMIs).
E and are shown in blue, red, and black color, respectively. It Weighting low-pass filter, , for output disturbance rejec-
is to be observed that case A is tantamount to the plant model tion and a high-pass filter, , to optimize the control effort
proposed in [10]. in the high frequency range, are given in (25) for an mixed
The loci of the exciter and electromechanical (EM) modes sensitivity design [20].
(poles) are plotted in Fig. 5 by varying from 0.4 p.u. to Damping controllers for cases A, B, C, and E are designed at
1.3 p.u. in steps of 0.05 p.u. Additionally, pole residues of the the nominal operating condition. Change in closed-loop transfer
transfer function ( ), associated with cases function ( ), due to the fractional change in open-loop
A, C, and E are depicted as black-colored arrows and limited plant transfer function ( ) is given as
by cyan-colored dots. Related to Fig. 5, angle and moduli of the
EM mode sensitivity for cases A-E are rendered in Table I, for (26)
three different operating conditions. It must be mentioned that
the highest moduli of EM modes corresponds to case A for all where is sensitivity and is complementary sensitivity of the
operating conditions (for similar findings, refer to [11]). Note closed-loop plant.
that for PSS design, the ideal phase compensation (IPC)—en- For the nominal operating condition bode magnitude plot,
ables departure angle of EM mode for the compensated system of the ratio of, the change in closed-loop transfer function and
equal to 180 —for the EM mode of case A is higher than cases the fractional change in open-loop transfer function ( ), is
C and E across all operating conditions. However, phase lead shown in Fig. 6. It is evident that the closed-loop plant variation
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
KUMAR: POWER SYSTEM STABILIZERS DESIGN FOR MULTIMACHINE POWER SYSTEMS USING LOCAL MEASUREMENTS 5
Fig. 6. Close loop plant variation with fractional change in open loop plant
of single machine system at the nominal operating condition.
TABLE III
PSS AND SENSITIVITY DATA FOR 9-BUS SYSTEM [GEN-1; GEN-2; GEN-3]
B. Fourteen-Machine System
Simplified model of the southern and eastern Australian net-
work shown in Fig. 14 has been endorsed as an IEEE benchmark
for stability studies. Attributed by closely coupled areas 1 and
2 it has three interarea modes as well as ten local-area modes.
In [12], a detailed description of the test system including exci-
tation system, network, machine, and P-Vr PSS parameters are
center frequency 4.1 Hz is selected to enable departure angle given including six different operating conditions. P-Vr PSS is
at the pole close to 180 : designed for each generator—which is in fact equivalent rep-
resentation of identical power station of 2 to 12 units. In [8],
design of PSSs for identical units in a multigenerator station is
(27) discussed to ensure that intra-station, local, and exciter modes
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
KUMAR: POWER SYSTEM STABILIZERS DESIGN FOR MULTIMACHINE POWER SYSTEMS USING LOCAL MEASUREMENTS 7
Fig. 13. Heavy loading: System responses of Gen 3 for a fault for 10 ms
duration at bus 7. –––: Proposed; – – –: [10].
TABLE IV
CLEARING TIME COMPARISON FOR A TO GROUND FAULT
Fig. 15. GEP and P-Vr characteristics of Gen-9 for all the six cases, in p.u. on
the machine rating (–––: Proposed; –––: [10]).
TABLE V
PSS DATA OF 14-MACHINE SYSTEM
Fig. 17. Close-loop poles of 59-bus system for all the six cases ( : All PSS in
service, : Four PSSs are OFF).
Fig. 16. Root locus of Gen-9 for case 6, 14-generator 59-bus system ( –––:
Proposed; –––: [10]).
the proposed plant model is 51, while for an equal phase com-
pensation, for the method proposed in[10] is 36. Note that
for the proposed method is closer to the plant instability
gain 49 (47 with all PSS in service). Minimum values of
across all six operating conditions for each generator are given
in Table V. Observe that in comparison to [10], evaluated
using proposed method is reasonably closer to instability gain
of plant.
Related to the above discussion, we consider a contingency
scenario by taking transmission line 18–20 out of service for
maintenance purpose. Oscillatory behavior of plant is observed
when PSS gain of Gen-3 is increased to 21 (with all PSS in
service). Note that posterior to the structural change, is
14 and 22 for Gen-3 for the plant model discussed in [10] and
Section III, respectively.
In order to demonstrate robust performance over a wide range
of operating conditions, eigenvalues of 59-bus system are pre-
Fig. 18. Case 2: Slip speed of GEN 3, 6, 9, and 14 and field voltage response
sented in Fig. 17, for 726 different operating scenarios by dis- of GEN 14; for a step change in at GEN-14, lasting for 100 ms
abling four PSS from each area, wherein proposed and P-Vr and then returning to the original value. PSS of GEN 3, 6, and 9 are OFF.
PSS are shown red and blue color, respectively. The overall
performance of the P-Vr PSS is not satisfactory as the system
becomes highly oscillatory under several operating conditions To visualize this, slip speed ( ) responses of Gen 3, 6, 9, and
when compared with proposed PSS. 14 and field voltage ( ) response of GEN 14 are presented in
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
KUMAR: POWER SYSTEM STABILIZERS DESIGN FOR MULTIMACHINE POWER SYSTEMS USING LOCAL MEASUREMENTS 9
Fig. 18, for a step change in at Gen-14, lasting [2] E. V. Larsen and D. A. Swann, “Applying power system stabi-
for 100 ms and then returning to the original value, for case lizers: Part I-III,” IEEE Trans. Power App. Syst., vol. PAS-100, pp.
3017–3046, Jun. 1981.
2 operating condition with PSS at generators 3, 6, and 9 are
[3] M. Nambu and Y. Ohsawa, “Development of an advanced power
out-of-service. From Figs. 17 and 18, it is clearly evident that the system stabilizer using a strict linearization approach,” IEEE Trans.
system exhibits superior damping performance with proposed Power Syst., vol. 11, no. 2, pp. 813–818, May 1996.
method when compared with P-Vr PSS. [4] D. M. Lam and H. Yee, “A study of frequency responses of gener-
ator electrical torques for power system stabilizer design,” IEEE Trans.
Power Syst., vol. 13, no. 3, pp. 1136–1142, Aug. 1998.
[5] G. Rogers, Power System Oscillations. Norwell, MA, USA: Kluwer,
VI. CONCLUSIONS 2000.
[6] P. S. Rao and I. Sen, “Robust pole placement stabilizer design using
The objective of this work is to design a PSS based on the con- linear matrix inequalities,” IEEE Trans. Power Syst., vol. 15, no. 1, pp.
ventional design technique for interconnected power systems. 3003–3008, Feb. 2000.
Of specific interest, this work advances the method of [10] for [7] M. A. Abido, “Optimal design of power-system stabilizers using par-
designing PSS parameters by proposing a synthesized equiva- ticle swarm optimization,” IEEE Trans. Energy Convers., vol. 17, no.
3, pp. 406–413, Sep. 2002.
lent bus using local measurements available at power station. In [8] M. J. Gibbard and D. J. Vowles, “Design of power system stabilizers for
contrast, here we linearize the system dynamics by taking this a multi-generator power station,” Proc. IEEE Int. Conf. Power System
equivalent bus as reference instead of the high voltage bus of the Technology, 2000 (PowerCon 2000), vol. 3, pp. 1167–1171, 2000.
step-up transformer. Towards this end, the robustness and per- [9] M. J. Gibbard and D. J. Vowles, “Reconciliation of methods of compen-
sation for PSSs in multimachine systems,” IEEE Trans. Power Syst.,
formance of the PSS designed for the proposed model are tested vol. 19, no. 1, pp. 463–472, Feb. 2004.
through close loop eigenvalue plots and nonlinear time domain [10] G. Gurrala and I. Sen, “Power system stabilizers design for intercon-
simulations for single, 3-, and 14-machine systems. The find- nected power systems,” IEEE Trans. Power Syst., vol. 25, no. 2, pp.
ings can be summarized as follows. 1042–1051, May 2010.
[11] F. D. Marco, N. Martins, and J. C. R. Ferraz, “An automatic method
1) For SMIB system, it is found that the controller de-
for power system stabilizers phase compensation design,” IEEE Trans.
signed for the proposed method renders robust close loop Power Syst., vol. 28, no. 2, pp. 997–1007, May 2013.
behavior. [12] M. J. Gibbard and D. J. Vowles, Simplified 14-Generator Model of
2) Applicability of the proposed method is reasonably sup- SE Australian Power System, 2010 [Online]. Available: http://www.
ported by closer resemblance of P-Vr TF [12] and proposed eleceng.adelaide.edu.au/groups/PCON/PowerSystems/IEEE
[13] K. R. Padiyar, Power System Dynamics Stability and Control. New
GEP TF—which is derived using local measurements. York, NY, USA: Wiley, 1996.
3) Importantly, critical PSS gain of the proposed model is [14] P. S. Kundur, Power System Stability and Control. New York, NY,
found closer to instability gain of the system. USA: McGraw-Hill, 1994.
The investigation identifies some important avenues for fu- [15] W. G. Heffron and R. A. Phillips, “Effect of a modern amplidyne
voltage regulator on underexcited operation of large turbine genera-
ture investigations as follows. tors,” Trans. Amer. Inst. Elect. Eng. Power App. Syst., Part III, vol.
1) A 2-channel PSS structure [22] to damp the aggregate and 71, no. 1, pt. III, pp. 692–697, 1952.
intraplant modes, in a multigenerator power station using [16] G. Gurrala and I. Sen, “A nonlinear voltage regulator with one tunable
local measurements presented here is under investigation. parameter for multimachine power systems,” IEEE Trans. Power Syst.,
vol. 26, no. 3, pp. 1186–1195, Aug. 2011.
2) PSS design as affected by load dynamics connected at the [17] C. T. Tse, K. W. Wang, X. Y. Bian, and J. F. Zhang, “Is lead compen-
secondary bus of step-up transformer also calls for a de- sation appropriate to PSS design?,” in Proc. 4th Int. Conf. Advances
tailed investigation. in Power System Control, Operation and Management, Nov. 2009, pp.
3) Identify the prominent damping sources as the installing 1–6.
[18] P. Kundur, G. R. Berube, L. M. Hajagos, and R. E. Beaulieu, “Prac-
locations in the large power systems.
tical utility experience with and effective use of power system stabi-
4) Proposed method can be further extended to take into ac- lizers,” in Proc. 2003 IEEE Power Eng. Soc. General Meeting, vol. 3,
count the nearby generator interactions for PSS design. pp. 1777–1785.
[19] G. Stein, “Respect the unstable,” IEEE Control Syst. Mag., vol. 23, no.
4, pp. 12–25, Aug. 2003.
ACKNOWLEDGMENT [20] B. Pal and B. Chaudhuri, Robust Control in Power Systems. New
York, NY, USA: Springer, 2005.
The author would like to thank Dr. I. Sen, Dr. G. Gurrala, and [21] P. W. Sauer and M. A. Pai, Power System Dynamics and Stability.
Upper Saddle River, NJ, USA: Pearson Education, 1998.
reviewers for their valuable suggestions. [22] N. Martins and T. H. S. Bossa, “A modal stabilizer for the independent
damping control of aggregate generator and intraplant modes in multi-
generator power plants,” IEEE Trans. Power Syst., vol. 29, no. 6, pp.
REFERENCES 2646–2661, Nov. 2014.
[1] F. P. de Mello and C. Concordia, “Concept of synchronous machine Ajit Kumar received the M.Sc. degree in Power Systems from the Indian In-
stability as affected by excitation control,” IEEE Trans. Power App. stitute of Science, Bangalore, India, in 2010, where he is currently pursuing the
Syst., vol. PAS-88, pp. 316–329, Apr. 1969. Ph.D. degree in electrical engineering.