Protection Unit 2
Protection Unit 2
Protection Unit 2
PROTECTION
UNIT 2
INDEX
1.1 Introduction
1.2 D.C. Wire Pilot Relaying
1.3 A.C. Wire Pilot Relaying
1.4 Power Line Carrier Pilot
1.5 Microwave or Radio Pilots
2 Distance Protection
2.1 Introduction
a Impedance Type Distance Protection
b Phase Comparison Protection
2.2 Zones and Distance Protection
2.3 Distance Protection Using Carrier Intertripping and Remote
Tripping
a Non-interlocked transfer tripping
b Interlocked or permissive transfer tripping
c Carrier Blocking
2.4 Distance Measurement Problems
a Fault Resistance
b Overloads and Power Swings
c Transient Conditions
1 TRANSMISSION LINE AND FEEDER PROTECTION
1.1 Introduction
Wire pilots consist of d.c. and a.c, two-wire circuit, power line carrier
pilot is one in which low voltage, high frequency currents are
transmitted along a conductor of a power line to a receiver at the remote
end. A micro-wave pilot is an ultra-high frequency radio signal system.
Scores of different wire pilot relaying equipment have been devised where
d.c. signals in one form or another have been transmitted over pilot wire.
For certain applications some such arrangements have advantages,
particularly where the distances are short. However, d.c. pilot
relaying is nearly obsolete for other than very special applications.
First, we should become acquainted with two new terms to describe the principle
CTs and the pilot, and in the 'opposed voltage', current does not normally
Short circuits or open circuits in the pilot wires have opposite effects
the two types of relaying equipment as the accompanying table shows.
Where it is stated that tripping will be caused on the magnitude of the
power 1 current being high enough to pick up the relays.
Figure 3
Both the opposed voltage and the circulating current principles permit
tripping at both ends of a line for short circuit current flow into one
end only. However, the application of either principle may involve
certain feature! provide tripping only at the end having short circuit
current flow, as will be seen when actual equipments are considered.
As has been said before, the feature that makes a.c. wire pilot relaying
economically feasible for the distances over which it is applied is that
two pilot wires are used. In order to use only two wires, some means are
required to derive a representative single phase sample from the three-
phase currents at the ends of a transmission line, so as these samples
can be compared over the pilot.
In this scheme, under normal conditions and during an external fault, the
current circulates around the pilot wire loop because the line current
flows in at one end and out the other. When an internal fault occurs,
the cur: tends to flow inwards from both ends so that it no longer
circulates and different current flows in the operating coils of the
relay.
In this system the currents at the two ends are turned into voltages by ]
them through reactors with secondary windings (transactors). These
secondary windings are connected so that their output voltage is opposed
during normal conditions and no current flows in the pilot wire
neglecting pilot capacitance.
4
During an external fault the voltages are nearly in phase and current
flows in the pilot and in the relay operating coils which are in serie3
with them. The relays compare the pilot wire current with the current in
the local restraint
circuits.
Each carrier current receiver receives carrier current from its local trans-
mitter as well as from the transmitter at the other end of the line. In
effect, the receiver converts the received carrier current into a d.c. volt
that can be used in a relay or other circuit to perform any desired function
This voltage is zero when carrier current is not being received.
6
Figure 8
Beamed radio pilots may be used for all forms of protection based on
power carrier pilots. Such application is, of course, subject to
technical
and economic considerations and to the particular limiting
characteristics of a radio link.
Frequency bands available lie in the region of 80 - 7500 MHz. Beamed radio
links in these frequency ranges may be directional and can contain a large
number of functional channels within the band width. The link is not
greatly subject to interference, particularly at such high frequencies
because these are beyond man-made interference range.
7
Transmission is generally by line of sight and this must take into account the
curvature of the earth and the type of route over which transmission is taking
place. The range, as shown in Figure 9, is about 60 - 75 km under favorable
conditions.
Figure 9
Radio or microwave links have been widely used, particularly as wide band
communications, control and protection links between generating positions.
They have been used where the route of the line crosses difficult country. In
many cases, the effective range of a single stage is inadequate and this then
requires repeaters, or reflectors, or both in order to achieve longer
distances as shown in Figure 10.
DISTANCE PROTECTION
1 Introduction
The relays are so constructed such that the torque produced by a current
element is opposed by the torque produced by a voltage element. Therefore,
we call the current element the operating torque and the voltage element the
restraining torque, under 'healthy' conditions, it could be said that the
restraining torque is equal to the operating torque.
It should be noted that this radio of does not directly imply that the
The scheme simply examines the phase relationship between the line
currents entering and leaving the protected line. The relationship does
not take account current magnitudes.
can now predict the current waveforms at both ends, A and B, which are awn
below.
Now at end B, the CT connections are reversed relative to end A so that at any
given instant under normal operating conditions the CT secondary will be in
opposition. This is shown in Figure 13.
Therefore, the scheme acts to trip the c.bs. at both terminal stations,
when the signals are displaced in time and tripping will occur whenever
there is sufficient fault current flowing.
For example, if we have a fault on the line, the current will rise,
voltage will fall, altering the ratio of The relay recognizes this
A fault which occurs within the first 80% of a transmission line is said
to be a Zone 1 fault. Similarly, a fault located in the last 20% of the
line is said to be a Zone 2 fault. Zone 2 extends from 80% to 120% of
the line A further zone, referred to as Zone 3, covers from 120% of the
line upwards.
14
The time delay used would ensure that this incorrect tripping does not
occur. The subsection A C generally encompasses about 80% of the protected
section.
Considering the protection at end B, the distance relays associated with the
section A B protect BOX of the length of the protected section from B
towards A as shown in Figure 18.
16
One further feature is added to the protection scheme described above. Because
of the time delay feature applied to Zones 2 and 3 elements of the distance
relays, these relays may be used to back-up the primary protection on the next
section. For example, referring to Figure 18, the distance relays at A may
back-up the primary protection on the section B D. The purpose of this
feature is to ensure clearance of a fault on the section B D, even though the
primary protection, or the circuit breaker at B, fails.
This is termed back-up protection. To achieve this feature, the Zone 2 and
Zone 3 settings of the distance relays at A would be increased to enable
these relays to measure faults in the section B D. This is shown in Figure 19
Figure 19
Note that for a fault on the section B D, the distance relays associated
section A B, and which are located at B, should not be able to operate
because the fault is not in the tripping direction.
c Carrier Blocking
The main feature recommending this scheme is that signaling only occurs a
healthy line, when a fault occurs external to the protected section.
distance protection is equipped with the usual Zone 1 feature and Zone 2
two time features - one 'fast' and the other 'slow'. If a fault is
measured as being within the Zone 2 setting of the relay, the relay will
operate in fast Zone 2 time unless the blocking signal is received from
that end of the protected section closest to the fault.
If the signal is received, clearance will occur after the slow Zone 2 has
elapsed.
ice that the fast Zone 2 clearance of the c.b. at A will only apply for
faults between D and B. For faults beyond B, but still within Zone 2 reach,
slow Zone 2 clearance is applicable.
Now, if fast Zone 2 protection was not employed, a fault in the section B G
would cause the c.b. at A to operate, removing the bus A B from service
which not wanted. Therefore, a 'fast' Zone 2 is employed so that as soon as
a fault occurs in the Zone 2 setting, it will be removed by fast Zone 2
protection unless a signal is sent from B to A to stop the c.b. at A
operating.
a fault occurs between B and G, as you can see from Figure 20, slow Zone 2
employed so a signal is sent from B to A to stop operation of c.b. at A.
This gives time for the distance protection at B to C to operate.
a Fault resistance
b Overloads and power swings
c Transient conditions
a Fault Resistance
21 (b)), then the impedance measured by the relay exceeds the Zone 1 :ting
and the relay will operate in Zone 2 time, even though the fault is actually
in Zone 1.
During a power swing the point L may penetrate the impedance relay
characteristic to a point such as M. Power swings are inherently high
power factor and, therefore, can be represented in Figure 22 by a
characteristic which is a very nearly coincident with the +R axis.
Figure 22 shows that for the distance setting, or reach, along a
transmission line, the Mho type relay is more insensitive than the simple
impedance relay. In general, the Mho type relay is more insensitive
than the simple impedance relay. In general, Mho relay relay will not
trip on any overload or power swing from which system can recover.
c Transient Conditions
Figure 23 indicates that during the transient period, the current waveform
is symmetrical about some axis other than the horizontal time axis. The
d i s placement of the axis of symmetry is, at all instants, above the time
axis, and is therefore said to be a d.c. component. These conditions
affect the relay operation so that it may 'over-reach', i.e. operate for a
larger value of impedance.