13
13
13
13
Dealloying
General Description
Dealloying occurs when one or more alloy components are preferen-
tially removed from the metal. This depletion phenomenon differenti-
ates dealloying from other forms of corrosion. Dealloying is also
sometimes referred to as selective leaching or parting. The specific ter-
minology used comes from the alloying element removed. For example,
the preferential leaching of zinc from brass is called dezincification. If
nickel is removed, the process is called denickelification, and so forth.
Dealloyed areas are structurally altered. Corroded areas are weak
and porous, causing fracture and weeping leaks.
Dezincification
Admiralty brass (70% Cu, 29% Zn, 1% Sn, 0.05% As or Sb) and arseni-
cal aluminum brass (76% Cu, 22% Zn, 2% Al, 0.05% As) are resistant
to dezincification in most cooling water environments. In the recent
past, heat exchangers have virtually always been tubed with inhibited
grades of brass. Brasses containing 15% or less zinc are almost
immune to dezincification. Dezincification is common in uninhibited
brasses containing more than 20% zinc. Inhibiting elements include
arsenic, antimony, and phosphorus. Without inhibiting elements,
admiralty and aluminum brasses are subject to attack. Brasses con-
taining more than about 32% zinc are quite susceptible to attack.
Dezincification is explained by two theories. The first is that the
alloy dissolves, with a preferential redeposition of copper. The other
proposes a selective leaching of the zinc, leaving the copper behind.
There is evidence that both mechanisms may operate, depending on
the specific environment.
Denickelification
Selective removal of nickel from copper alloys is common. However,
denickelification does not commonly cause the affected component to
fail. Rather, the liberated nickel may deposit downstream and/or be
released into the environment.
Locations
As the word dealloying implies, attack occurs only in metals contain-
ing two or more alloying elements. Various alloys are susceptible to
corrosion. Copper alloys such as brasses, cupronickels, and bronzes
are particularly susceptible in cooling water environments. Most
other alloys, with the exception of gray and nodular cast iron (see
Chap. 17, "Graphitic Corrosion"), are attacked when exposed to high
temperatures, molten salts, acids, sulfides, or other very aggressive
environments.
Because of excellent thermal conductivities, suitable mechanical
properties, and superior corrosion resistance, brasses, cupronickels,
and to a lesser extent bronzes are often used in heat exchangers. Thus,
heat exchangers and condensers experience attack. Piping and plumb-
ing fittings, especially threaded unions carrying both hot and cold
water, as well as strainers, screens, and gasketed components are fre-
quently affected. Copper-alloy castings containing high concentrations
of zinc are susceptible to attack.
Many copper alloys are also used in pumps as bushings, bearings,
impellers, and gaskets. Bronzes, brasses, and other copper alloys are
frequently used. Thus, pump components are often corroded.
Critical Factors
Dealloying is influenced by many factors. In general, any process that
increases general corrosion will promote dealloying. However, specific
acceleration factors may be further classified into one of three cate-
gories: metallurgy, environment, and water chemistry.
Metallurgy
Zinc brasses containing phosphorus, antimony, and/or arsenic dezinc-
ify much less readily than brasses free of these elements. Brasses con-
taining less than 15% zinc are virtually immune to attack, and those
containing more than 32% zinc are readily dealloyed.
Denickelification generally produces less wastage in cupronickels
than dezincification in brasses. Wastage decreases as nickel content
increases, becoming very slight in alloys containing 30% or more nickel.
Environment
Stagnant conditions, deposits, heat transfer, high temperature, crevice
conditions, and stress accelerate dealloying. Porous or granular
deposits further attack. Surface shielding produced by deposition and
crevices promotes differential concentration cell corrosion and allows
aggressive chemical concentration. High metal temperatures acceler-
ate chemical corrosion processes, and thermal gradients directly
increase local metal dissolution (in the case of many copper alloys).
Stagnant conditions usually worsen all the above. Thus, frequent or
prolonged outages contribute to severe attack.
Water chemistry
Soft waters, high concentrations of dissolved carbon dioxide, acidic or
high pH conditions, and high chloride concentrations promote dezinci-
fication. Calcium-carbonate precipitation in many instances reduces
corrosion on yellow metals, including dealloying. Acid waters generally
accelerate corrosion on a variety of alloys. Very high pH can also accel-
erate corrosion and thus promote attack. High chloride concentration
has a particularly deleterious effect on brasses and cupronickels
(though less so on cupronickels). Hence, brasses and cupronickel com-
ponents contacting brackish waters or sea water are at special risk.
Highly stressed components are more susceptible to all forms of attack.
Identification
Dezincification
The two major forms of dezincification are "layer" and "plug." The
names are taken from characteristic corrosion-product morphologies. In
layer-type dezincification, the entire component surface is converted to
corrosion product to a roughly uniform depth (Figs. 13.1 through 13.3).
Plug-type dezincification produces small pockets or plugs of almost pure
copper (Figs. 13.4 and 13.5). Surfaces may have to be cleaned of deposits
Figure 13.1 Layer-type dezincification on a brass casting. The red layers are uniformly
corroded regions. The original yellow of the brass is visible in between.
Figure 13.2 Layer-type dezincification of a thin brass plate. The 0.019-in. (0.048-cm)
plate is shown in cross section. The dezincified layers converge toward the plate edge.
Note the porosity of the dezincified metal.
Figure 13.3 Layer-type dezincification on the internal surface of a
cast brass pipe 90° elbow.
mental copper (Figs. 13.6A and B). The corroded metal has little
mechanical strength, and if stressed it fractures easily.
Plug-type dezincification is common on horizontal pipe sections.
Attack is usually confined to areas beneath deposits lying along tube
bottoms (Figs. 13.4 and 13.7). Plugs are sometimes blown out of tube
walls due to internal pressure; holes are produced. More often, fluids
weep through the porous plugs, leaving stains or mounds of dissolved
Figure 13.4 A large plug of dezincified metal beneath a deposit. Plugs often form on the
bottom of horizontal pipes, beneath deposits.
Figure 13.5 Plug-type dezincification on the internal surface of a brass condenser tube.
Note the extreme porosity of the copper plugs. Tube wall thickness was 0.040 in. (0.10
cm). Compare to Fig. 13.13. (Courtesy of National Association of Corrosion Engineers,
Corrosion '89 Paper No. 197 by H. M. Herro.)
Figure 13.6/4 Red, dezincified gasketed surface of a cast valve throat. Note the partial
spalling of the copper corrosion product.
Figure 13.68 Cross section through the valve throat in Fig. 13.6A.
Note how the dezincification is confined to the gasket region.
Figure 13.7 Brass tube wall in longitudinal cross section. Plugs of dezincified metal are
present on the bottom of the horizontally oriented tube, beneath deposits. Stratification
within the copper plugs is evident.
Denickelification
Because wastage is usually slight, identification by visual observation
alone is difficult; microscopic examination is usually required. Layer-
type dealloying commonly occurs. Plug-type denickelification attack
has never been observed at this laboratory. Surfaces have a reddish
color due to the accumulation of denickelified metal.
Elimination
Dealloying can be reduced (as can any other form of corrosion) by good
system operation and the judicious use of appropriate materials and
chemical treatment. Specific categories needing attention follow.
Materials substitution
In any specific environment, only certain alloys are affected. Substitu-
tion of more resistant materials does not always necessitate major
alloy compositional changes. Adding as little as a few hundredths of a
percent of arsenic, for example, can markedly reduce dezincification in
cartridge brass. Antimony and phosphorus additions up to 0.1% are
similarly efficacious.
Surface cleanliness
The propensity toward dealloying decreases as surface cleanliness
increases. Flow should be maintained at rates high enough to prevent
settling of particulates and to reduce biological attachment and growth
(in some cases). Also, chemical treatment effectiveness increases with
flow. Surfaces on which fouling is apparent should be regularly
cleaned. The use of abrasive sponge balls in condensers has sometimes
been effective in keeping tubes clean.
Chemical treatment
Chemical corrosion inhibition can reduce all forms of corrosion includ-
ing dealloying. In particular, filmers such as tolyltriazole are effective
in reducing corrosion of yellow metals.
Biological control
Any deposit can increase dealloying. Biological accumulations, such
as slime layers, are no exception to this rule. In the age of increasing
public concern regarding pollution, biological control via chemical
treatment can be difficult. However, good biological control is always
beneficial.
Cautions
Identifying dealloying involves recognizing the variation of alloy com-
position caused by corrosion. Redeposition of alloy elements can occur
during acid cleaning, misleading the examiner. Frequently, copper is
redeposited on brasses, bronzes, and similar copper alloys during acid
cleaning of deposits.
Related Problems
See also Chap. 2, "Crevice Corrosion"; Chap. 4, "Underdeposit Corro-
sion"; and Chap. 17, "Graphitic Corrosion."
CASE HISTORY 13.1
Industry: Mining
Specimen Location: Turbine condenser
Specimen Orientation: Horizontal
Environment: Shell side: Condensing steam
Tube side: Cooling water, 60-8O0F (16-270C), high
hardness and silica, treated with a dispersant and zinc
Time in Service: 6 years
3
Sample Specifications: A in. (1 .9 cm) outer diameter, CDA 442 uninhibited
brass tubing
Figure 13.1 OyA A hole emanating from the internal surface of a brass condenser tube. The
hole was caused by plug-type dezincification (see Fig. 13.11).
Figure 13.1 OB A transverse cross section through the tube wall in Fig. 13.1OA. Note the
through-wall plug-type dezincification.
Industry: Refinery
Specimen Location: Overhead condenser
Specimen Orientation: Horizontal
Environment: Shell Side: Atmospheric pressure, pH 5.5-6.5 (ammonia
used to control pH), 240-11O0F (116-430C), overhead
vapors
Tube side: Pressure 30 psi (207 kPa), pH 8.0, 87-12O0F
(30-490C), cooling water (no treatment)
Time in Service: 1 year
3
Sample Specifications: A in. (1 .9 cm) outer diameter, uninhibited brass, 72%
copper, 26.7% zinc, 1 .3% tin
Severe wastage was evident on both external and internal surfaces of the
tube section. There were two round holes on one side. Deep pockets of
internal surface corrosion penetrated to the external surface (Fig.
13.ILA). The depressions contained sulfides, mainly concentrated near
external surfaces. Below were large amounts of porous elemental copper
(Fig. 13.115).
Internal surfaces were covered with a tan deposit layer up to 0.033 in.
(0.084 cm) thick. The deposits were analyzed by energy-dispersive
spectroscopy and were found to contain 24% calcium, 17% silicon, 16%
zinc, 11% phosphorus, 7% magnesium, 2% each sodium, iron, and sulfur,
1% manganese, and 18% carbonate by weight. The porous corrosion
product shown in Fig. 13.ILB contained 93% copper, 3% zinc, 3% tin, and
1% iron. Traces of sulfur and aluminum were also found. Near external
surfaces, up to 27% of the corrosion product was sulfur.
The holes and depressions on external surfaces were caused by deep
dezincification on internal surfaces. The porous corrosion product plugs
had enough structural integrity so that only a few holes formed due to
internal pressurization.
The dezincification was caused by underdeposit corrosion. The fact that
the brass was not an inhibited grade was a major contributing factor.
Chemical cleaning had not been done since this exchanger was installed.
No chemical treatment was used on either external or internal surfaces.
Figure 13.11 B Porous copper corrosion products filling an internal surface depression.
The edge of one crater seen in Fig. 13.1L4. is to the right.
CASE HISTORY 13.3
Industry: Utility
Specimen Location: Main condenser
Specimen Orientation: Horizontal
Environment: Tube side: 60-8O0F (16-270C), pH 8.3-8.7; treatment—
tolyltriazole, dispersant; brackish water
Time in Service: 3 years
7
Sample Specifications: /s in. (2.2 cm) outer diameter, 90:10 cupronickel, 0.031
in. (0.079 cm) wall thickness
Industry: Utility
Specimen Location: Condenser tubes
Specimen Orientation: Horizontal
Environment: Tube side: 62-8O0F (17-270C), pH 8.3-8.6; treatment—
tolyltriazole, dispersant
Time in Service: 1 year and 12 years (two different samples)
Sample Specifications: ASTMB395 (71.4% copper, 0.97% tin, <0.005% phos-
phorus, <0.01% arsenic,others total <0.15%, balance zinc)
Two sections of utility condenser tubing were received. One of the sections
had deep plug-type dezincification on internal surfaces (Fig. 13.5); the
other showed only superficial corrosion on internal surfaces (Fig. 13.13).
Sections were removed from two similar condensers. Both condensers
were fed with a common cooling water source, were of identical design, and
experienced virtually identical operating conditions. However, the first
exchanger had been in service for 12 years, whereas the other was only on
line for 1 year. The dezincified tube (Fig. 13.5) was from the exchanger
seeing short-term service. The dezincified tube was fabricated from an
uninhibited grade of brass. The older, superficially corroded section
contained 0.021% arsenic, an inhibiting agent.
This case history dramatically illustrates the value of proper alloy
choice. It was found that the failed exchanger had been ordered many
years ago but was not installed until recently. Today, uninhibited grades of
brass are almost never used for condenser and heat exchanger service in
the United States.
Figure 13.13 An inhibited-brass condenser tube in cross section, showing only superfi-
cial wastage on internal surfaces. This tube was exposed to virtually identical conditions
as the tube shown in Fig. 13.5. However, because of the inhibition, dezincification did not
occur on this tube. (Courtesy of National Association of Corrosion Engineers, Corrosion
'89 Paper No. 197 by H. M. Herro.)
CASE HISTORY 13.5
Industry: Hotel
Specimen Location: Pump impeller and shaft bushing
Specimen Orientation: Vertical impeller, horizontal bushing
Environment: Cooling water (brine well), chloride 22,000 ppm, sulfate
2400 ppm, calcium 1700 ppm, magnesium 4300 ppm, iron
0.05 ppm, silica 14 ppm, pH 7.4, 7O0F (210C), pressure
60-70 psi (0.4-0.5 MPa)
Time in Service: ~1 year
Sample Specifications: 61/2 in. (16.5 cm) diameter, bronze impeller, 1 in. (2.5 cm)
diameter, leaded brass bushing
A pump impeller and a shaft bushing from a small cooling water pump
assembly were generally corroded. Reddish surface discoloration revealed
layer-type dezincification (Figs. 13.14 and 13.15).
Attack occurred because of substantial idle periods in which flow was
limited. Also, very high concentrations of chloride and sulfate in cooling
waters accelerated attack.