Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Lehe1318 04 PDF

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Cat® 3516B

Dynamic Gas Blending™ (DGB™) Generator Sets

Bore – mm (in) 170 (6.69)


Stroke – mm (in) 190 (7.48)
Displacement – L (in )
3
69 (4210.64)
Compression Ratio 14.0:1
Aspiration TA
Fuel System EUI
Governor Type ADEM™ A4
Image shown may not reflect actual configuration

Prime Continuous Emissions Performance


50 Hz kVA (ekW) 50 Hz kVA (ekW)

2000 (1600) 1750 (1400) Optimized for Low Fuel Consumption or Low Emissions

Features
Dynamic Gas Blending™ (DGB™) System Cooling System
• DGB system automatically activates when gas • Cooling systems available to operate in ambient
supply is detected temperatures up to 50°C (122°F)
• Reduces diesel consumption by up to 70% • Tested to ensure proper generator set cooling
using gas substitution while maintaining safe EMCP 4 Control Panels
engine operation • EMCP 4.3/4.4 control panel is the single-point
• Control system enables maximum substitution interface for the engine, generator, and DGB
over the widest load range in the industry functions
• Maintains traditional diesel generator set power • User-friendly interface and navigation
and transient response performance • Scalable system to meet a wide range of
• Accepts a wide range of gas quality and installation requirements
automatically adjusts to fuel quality changes, • Expansion modules and site specific
eliminating the need for field calibration programming for specific customer requirements
• Maintains existing diesel maintenance and
overhaul intervals Warranty
• 24
 months/1000-hour warranty for standby and
Cat® Diesel Engine mission critical ratings
• Designed and optimized for low emissions or • 12
 months/unlimited hour warranty for prime
low fuel consumption and continuous ratings
• Reliable performance proven in thousands of • Extended
 service protection is available to
applications worldwide provide extended coverage options
Generator Set Package Worldwide Product Support
• Accepts 100% block load in one step and meets • Cat dealers have over 1,800 dealer branch
NFPA 110 loading requirements stores operating in 200 countries
• Conforms to ISO 8528-5 G2 load acceptance • Your local Cat dealer provides extensive
requirements post-sale support, including maintenance and
• Reliability verified through torsional vibration, fuel repair agreements
consumption, oil consumption, transient Financing
performance, and endurance testing • Caterpillar offers an array of financial products
Alternators to help you succeed through financial service
• Superior motor starting capability minimizes the excellence
need for oversizing the generator • Options include loans, finance lease,
• Designed to match the performance and output operating lease, working capital, and revolving
characteristics of Cat diesel engines line of credit
• Contact your local Cat dealer for availability in
your region
Page 1 of 4
3516B DGB Generator Sets
Electric Power

Standard and Optional Equipment


Engine Power Termination Vibration Isolators
Air Cleaner Type q Rubber
 Single element q Bus bar q Spring
 Dual element q Circuit breaker q Seismic rated
q 1600A q 2000A
Muffler Cat Connect
q 2500A q 3000A
 Industrial grade (15 dB) q 3200A q 4000A Connectivity
Starting q 5000A
 Ethernet
q UL q IEC
q Standard batteries  Cellular
q 3-pole q 4-pole
q Oversized batteries
q Manually operated
q Standard electric starter(s) Extended Service Options
q Electrically operated
q Heavy duty electric starter(s)
q Air starter(s) Trip Unit Terms
q Jacket water heater q LSI q LSI-G q 2 year (prime)
q LSIG-P q 3 year
Alternator q 5 year
Control System q 10 year
Output voltage
q 380V q 6600V q EMCP 4.3 Coverage
q 400V q 6900V q EMCP 4.4 q Silver
q 415V q 10000V q Gold
Attachments
q 3300V q 10500V q Platinum
q 6300V q 11000V q Local annunciator module q Platinum Plus
q Remote annunciator module
Temperature Rise q Expansion I/O module Ancillary Equipment
(over 40°C ambient) q Remote monitoring software
q 150°C q Automatic transfer switch
q 125°C/130°C Charging (ATS)
q 105°C  Paralleling switchgear
q Battery charger – 10A  Paralleling controls
q 80°C
q Battery charger – 20A
Winding type q Battery charger – 35A
q Random wound
q Form wound
Excitation
q Internal excitation (IE)
q Permanent magnet (PM)
Attachments
q Anti-condensation heater
q Stator and bearing temperature
monitoring and protection

Note: Some options may not be available on all models. Certifications may not be
available with all model configurations. Consult factory for availability.

Page 2 of 4
3516B DGB Generator Sets
Electric Power

Package Performance
Low Emissions and Low Fuel Consumption (60°C SCAC) based on 100% Diesel, except *
Performance Prime Continuous Prime Continuous
Frequency 50 Hz 50 Hz 50 Hz 50 Hz
Genset power rating with fan 1600 ekW 1400 ekW 1600 ekW 1400 ekW
Genset power rating with fan @ 0.8 power factor 2000 kVA 1750 kVA 2000 kVA 1750 kVA
Emissions Low Emissions Low Emissions Low Fuel Low Fuel
Performance number EM2594-00 EM2598-00 EM2592-00 EM2596-00
Aftercooler (separate circuit) – °C (°F) 60 (140) 60 (140) 60 (140) 60 (140)
Fuel Consumption
100% load with fan – L/hr (gal/hr) 426.3 (112.6) 372.4 (98.4) 397.2 (104.9) 351.1 (92.7)
75% load with fan – L/hr (gal/hr) 315.9 (83.4) 281.5 (74.4) 301.0 (79.5) 269.3 (71.1)
50% load with fan – L/hr (gal/hr) 217.9 (57.6) 196.7 (52.0) 211.7 (55.9) 192.3 (50.8)
25% load with fan – L/hr (gal/hr) 123.9 (32.7) 115.2 (30.4) 125.2 (33.1) 116.6 (30.8)
*Gas Fuel Flow (Pressure range before regulating: 0.83-6.89 bar (12-100 psi)
Maximum @ 85 MN – MJ/hr (Btu/min) 10974 (173356) 9785 (154573) 10841 (171255) 9593 (151540)
Cooling System
Radiator air flow restriction (system) – kPa (in. water) 0.12 (0.48) 0.12 (0.48) 0.12 (0.48) 0.12 (0.48)
Radiator air flow – m3/min (cfm) 1841 (65014) 1841 (65014) 1841 (65014) 1841 (65014)
Engine coolant capacity – L (gal) 233.0 (61.6) 233.0 (61.6) 233.0 (61.6) 233.0 (61.6)
Radiator coolant capacity – L (gal) 236.0 (62.0) 236.0 (62.0) 236.0 (62.0) 236.0 (62.0)
Total coolant capacity – L (gal) 469.0 (123.6) 469.0 (123.6) 469.0 (123.6) 469.0 (123.6)
Inlet Air
Combustion air inlet flow rate – m3/min (cfm) 141.4 (4682.1) 120.9 (4269.1) 122.4 (4320.3) 111.7 (3944.3)
Exhaust System
Exhaust stack gas temperature – °C (°F) 520.6 (919.0) 470.6 (879.1) 476.2 (889.1) 463.6 (866.5)
Exhaust gas flow rate – m3/min (cfm) 395.3 (12606) 315.8 (11151.4) 321.2 (11340.6) 288.0 (10169.7)
Exhaust system backpressure (maximum allowable)
6.7 (27) 6.7 (27) 6.7 (27) 6.7 (27)
– kPa (in. water)
Heat Rejection
Heat rejection to jacket water – kW (Btu/min) 718 (37534) 596 (33894) 624 (35502) 568 (32302)
Heat rejection to exhaust (total) – kW (Btu/min) 1846 (92410) 1407 (80016) 1446 (82224) 1280 (72794)
Heat rejection to aftercooler – kW (Btu/min) 465 (21894) 301 (17118) 299 (17023) 235 (13365)
Heat rejection to atmosphere from engine –
168 (8643) 140 (7962) 138 (7850) 131 (7450)
kW (Btu/min)
Heat rejection from alternator – kW (Btu/min) 68 (3890) 64 (3662) 68 (3890) 64 (3662)
Emissions** (Nominal)
NOx mg/Nm3 (g/hp-h) 2061.9 (4.67) 2304.9 (4.87) 4265.2 (8.49) 4351.6 (8.65)
CO mg/Nm3 (g/hp-h) 135.1 (0.27) 168.3 (0.36) 206.6 (0.41) 180.2 (0.36)
HC mg/Nm3 (g/hp-h) 63 (0.16) 78.1 (0.16) 58.2 (0.12) 60.4 (0.12)
PM mg/Nm (g/hp-h)
3
17.2 (0.04) 19.1 (0.04) 22.7 (0.05) 23.4 (0.05)
Emissions** (Potential Site Variation)
NOx mg/Nm3 (g/hp-h) 2474.3 (5.61) 2765.9 (5.84) 5118.3 (10.19) 5221.9 (10.38)
CO mg/Nm (g/hp-h)
3
243.3 (0.49) 302.9 (0.64) 371.9 (0.74) 324.4 (0.64)
HC mg/Nm3 (g/hp-h) 83.8 (0.21) 103.9 (0.22) 77.4 (0.15) 80.3 (0.16)
PM mg/Nm (g/hp-h)
3
24 (0.05) 26.7 (0.06) 31.8 (0.06) 32.8 (0.07)
**mg/Nm3 levels are corrected to 5% O2. Contact your local Cat dealer for further information.
Page 3 of 4
3516B DGB Generator Sets
Electric Power

Weights and Dimensions

Dim “A” Dim “B” Dim “C” Dry Weight


mm (in) mm (in) mm (in) kg (lb)

7066 (278.2) 2286 (90.0) 2360 (92.9) 15 135 (33,300)


Note: For reference only. Do not use for installation design. Contact your local Cat dealer for precise weights and dimensions.

Ratings Definitions
Prime Applicable Codes and Standards
Output available with varying load for an unlimited time. AS 1359, IBC, IEC 60034-1, ISO 3046, ISO 8528,
Average power output is 70% of the prime power rating. NEMA MG1-22, NEMA MG1-33, 2014/35/EU,
Typical peak demand is 100% of prime rated ekW 2006/42/EC, 2014/30/EU and facilitates
with 10% overload capability for emergency use for a compliance to NFPA 37, NFPA 70, NFPA 99,
maximum of 1 hour in 12. Overload operation cannot NFPA 110.
exceed 25 hours per year
Note: Codes may not be available in all model
Continuous configurations. Please consult your local Cat
Output available with non-varying load for an unlimited dealer for availability.
time. Average power output is 70-100% of the
Data Center Applications
continuous power rating. Typical peak demand is 100%
• ISO 8528-1 Data Center Power (DCP)
of continuous rated kW for 100% of the operating hours.
compliant per DCP application of Cat diesel
generator set prime power rating.
• All ratings Tier III/Tier IV compliant per Uptime
Institute requirements.
• All ratings ANSI/TIA-942 compliant for Rated-1
through Rated-4 data centers.
Fuel Rates
Fuel rates are based on fuel oil of 35º API [16°C (60ºF)]
gravity having an LHV of 42,780 kJ/kg (18,390 Btu/lb)
when used at 29ºC (85ºF) and weighing 838.9 g/liter
(7.001 lbs/U.S. gal.)

www.cat.com/electricpower
©2020 Caterpillar
All rights reserved.
Materials and specifications are subject to change without notice.
The International System of Units (SI) is used in this publication.
CAT, CATERPILLAR, LET'S DO THE WORK, their respective logos, “Caterpillar Corporate Yellow”,
3516 PGFL the “Power Edge” and Cat “Modern Hex” trade dress as well as corporate and product identity
LEHE1318-04 (10/20) used herein, are trademarks of Caterpillar and may not be used without permission.

You might also like