Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

AVM 234S: SUT Valve Actuator With Positioner: How Energy Efficiency Is Improved

Download as pdf or txt
Download as pdf or txt
You are on page 1of 9

Product data sheet 15.1 51.

377

AVM 234S: SUT valve actuator with positioner

How energy efficiency is improved


Automatic adaptation to valve, precision activation and high energy efficiency with minimal operating
noise

Features
• Activation of 2-way and 3-way valves of the VQD/BQD and VQE/BQE series, as well as VUG/BUG,
VUS/BUS, VUP, V6R/B6R and VDL
• For controllers with constant output (0...10 V or 4...20 mA) or switching output (2-point or 3-point
control) AVM234SF132
• Stepping motor with SAUTER Universal Technology (SUT) electronic control unit and electronic,
force-dependent cut-off
• Simple assembly with valve; spindle is automatically connected after control voltage is applied
(patented system)
• Automatic detection of applied control signal (constant or switched); indicated by two LEDs
• Coding switches for selecting characteristic and running time
• Type of characteristic (linear/quadratic/equal-percentage) can be set on the actuator
• Automatic adaptation to the stroke of the valve (min. valve stroke 8 mm, max. valve stroke 49 mm).
The measured stroke is saved and is not lost even in the event of a power failure
• Direction of operation can be selected via screw terminals when making the electrical connection
• Crank handle for external manual adjustment with motor cut-off and as trigger for a re-initialisation
• Numerous adapters enable the unit to be fitted onto non-SAUTER valves
• Power supply 230 V with module or direct connection for 24 VAC / 24 VDC; continuous activation
also admissible with 230 V
• Maintenance-free gear unit made of sintered steel; gearbox base-plate made of steel
• Mounting column made of stainless steel; mounting bracket made of cast light alloy for fitting the
valve
• Electrical connections (max. 2.5 mm²) with screw terminals
• Three pre-scored cable inlets for M20 × 1.5 (2×) and M16 × 1.5
• Fitting vertically upright to horizontal, not suspended

Technical data
Power supply
Power supply 24 VAC ±20%, 50…60 Hz
Power supply 24 VDC ±15%
Power supply 230 VAC ±15%, 50...60 Hz (with accessories)
Power consumption1) 24 VAC/24 VDC
10 W/20 VA
230 VAC (with accessories)
13 W/28 VA
ValveDim app

Parameters
Running time 2/4/6 s/mm
Actuator stroke 0...49 mm
Response time for 3-point 200 milliseconds
Positioner Control signal 1 0...10 V, Ri >100 kΩ
Control signal 2 4...20 mA, Ri = 50 Ω
Position feedback signal 0...10 V, load > 10 kΩ
Starting point U0 0 or 10 V
Control span ΔU 10 V
Switching range Xsh 300 mV

Ambient conditions
Ambient temperature −10…55 °C
Ambient humidity < 95% rh, no condensation
Media temperature2) Max. 120 °C

1) Choose transformers for this value, otherwise malfunctions may occur


2) For higher temperatures of the medium (180 °C or 240 °C), use an adapter (see accessories)

Right of amendment reserved © 2023 Fr. Sauter AG 1/9


Product data sheet 15.1 51.377

Construction
Weight 4.1 kg
Housing Two-part, yellow
Housing material Flame-retardant plastic

Standards, directives
Type of protection IP66 (EN 60529)
Protection class III (IEC 60730)
Over-voltage categories III
Degree of contamination III
CE/UKCA conformity3) LV-D 2014/35/EU (CE) EN 60730-1, EN 60730-2-14
EESR-2016 (UKCA) EN 60730-1, EN 60730-2-14
EMC-D 2014/30/EU (CE) EN 61000-6-2, EN 61000-6-4
EMC-2016 (UKCA)4) EN 61000-6-2, EN 61000-6-4
RoHS-D 2011/65/EU & EN IEC 63000:2018
2015/863/EU (CE)
RoHS-2012 (UKCA) EN IEC 63000:2018

Overview of types

/ Actuator for valves: VQD/BQD, VQE/BQE, VUG/BUG, VUP, VUS/BUS


/ Actuator with mounting set (see accessories) for valves: V6R, B6R
Type Voltage Actuating power Running time Power consumption
AVM234SF132 24 VAC/DC 2500 N 2/4/6 s/mm 10 W, 20 VA
AVM234SF132-5 24 VAC/DC 2500 N 2/4/6 s/mm 10 W, 20 VA
AVM234SF132-6 24 VAC/DC 2500 N 2/4/6 s/mm 10 W, 20 VA
AVM234SF132-7 24 VAC/DC 1700 N 2/4/6 s/mm 10 W, 20 VA

Accessories
Type Description
0313529001 Split-range unit for setting sequences

Modules can be added for 2-point/3-point and continuous activation; additional power 2 VA
Type Description
0372332001 230 V ±15%, supply voltage
0372332002 100 V ±15%, supply voltage

Auxiliary change-over contacts (2 each) 12...250 VAC


Type Description
0372333001 Auxiliary change-over contacts (sets of 2), 12...250 VAC, infinitely variable, min. 100 mA and
12 V permissible load 6(2) A
0372333002 Auxiliary change-over contacts (sets of 2), 12...250 VAC, gold-plated contacts, from 1 mA, to
max. 30 V, wider range 3(1) A

Potentiometers
Type Description
0372334001 Potentiometer, 2000 Ω, 1 W, 24 V
0372334006 Potentiometer, 1000 Ω, 1 W, 24 V

Adapters for high temperatures


Type Description
0372336180 Adapter (required when temperature of the medium is 130...150 °C)
0372336240 Adapter (required when temperature of the medium is 180...200 °C)

Mounting set for AVM234SF132 on SAUTER valves (no adapter needed for 0372338 002)
Type Description
0372338001 V/B6 to DN 50, V/BXD, V/BXE, to DN 50, stroke 14 mm
0372338002 V/B6 DN 65...150, V/BXD, V/BXE from DN 65, stroke 40 mm

3) Explanation of abbreviations in the “Additional technical information” section of the product data sheet and in
the appendix to SAUTER product catalogues
4) EN 61000-6-2: (HF immunity limitation. Feedback signal between 80 MHz and 1000 MHz criterion B, otherwise
criterion A)

2/9 Right of amendment reserved © 2023 Fr. Sauter AG


Product data sheet 15.1 51.377

Type Description
0372338003 Conversion kit from AV*2*4SF132-5 to standard actuator AV*2*4SF132
0372338004 Conversion kit from AV*2*4SF132-6 to standard actuator AV*2*4SF132

Adapter set for non-SAUTER valves


Type Description
0372376010 Siemens with 20 mm stroke or 10 mm spindle diameter
0372376014 Siemens with 40 mm stroke or 14 mm spindle diameter
0372376015 Siemens VXF32, PN 10, DN 100…150; VXF22, PN 6, DN 100
0372377001 Johnson Controls DN 15…150, 14, 25, 40 mm stroke, spindle diameter 10, 12, 14 mm
0372378001 Honeywell with 20 mm stroke
0372378002 Honeywell with 38 mm stroke
0372386001 LDM type RY113 R/M
0372389001 ITT-Dräger, DN 15…32
0372389002 ITT-Dräger, DN 40…50
0378263001 End stop (needed for V/BXD, V/BXE DN 15…50, V/B6 DN 15 with kvs ≤ 1 m³/h)
0386263001 Cable gland M16 × 1.5
0386263002 Cable gland M20 × 1.5
0372461001 Forced operation for AV×2×4S
0372387001 SAUTER Satchwell VZF1727 mounting set
0510390052 Adapter set for non-SAUTER valves (Frese), stroke 20 mm
0510390053 Adapter set for non-SAUTER valves (Frese), stroke 40/43 mm

A Adapter: Not needed for version AV*2*4SF132-6

Description of operation
This valve actuator may only be used for activation of 2- or 3-way valves from SAUTER or with non-
SAUTER valves compatible with the adapter set. Other applications are not permitted.
Depending on the type of connection (see connection diagram), the actuator can be used as a
continuous (0...10 V and/or 4...20 mA), 2-point (OPEN/CLOSE) or 3-point actuator
(OPEN/STOP/CLOSE).
The running time of the actuator can be set with switches S1 and S2 according to the relevant
requirements. Switches S3 and S4 are used to configure the characteristic (equal-percentage, linear
or quadratic).
The external crank handle enables manual positional setting. When the crank handle is folded out,
the motor is switched off. After the crank handle is folded back, the actuator moves to the target
position again (without initialisation). When the crank handle is folded out, the actuator remains in this
position.

Intended use
This product is only allowed to be used in HVAC building systems for control and regulation purposes.
Other uses require the prior consent of the manufacturer.
The section “Description of operation” and all product instructions in this data sheet must be
observed.
Modifying or converting the product is not permitted.

Improper use
The actuator is not suitable for:
• Safety applications
• Transport applications and at altitudes above 2000 metres
• Use in areas where there is a risk of condensation
• Use in plants with high pressure surges

Notice in accordance with California Proposition 65

) The product contains lead. To be marketed in North America, the appropriate warnings must be affixed to
the product or packaging.

Right of amendment reserved © 2023 Fr. Sauter AG 3/9


Product data sheet 15.1 51.377

Engineering and fitting notes


Condensate, dripping water, etc. must be prevented from entering the actuator along the valve
spindle.
The valve is mounted directly on the actuator and fixed with screws (no further adjustments are
required). The actuator is connected with the valve spindle automatically. As delivered ex works, the
actuator spindle is in the middle position. The housing contains three break-out cable inlets which are
broken out automatically when the cable inlet is screwed in. The concept of stepping
motor/electronics enables parallel operation of multiple valve actuators of the same type. The cross-
section of the power cable must be selected based on the cable length and the number of actuators.
With five actuators wired in parallel and a cable length of 50 m, we recommend a cable cross-section
of 1.5 mm2 (power consumption of the actuator × 5).
The maximum equipment for the actuator is one 230 V module, one additional accessory component
(auxiliary contact or potentiometer) and the split-range unit.

Notice

) Extreme pressure surges in the system can lead to gear damage and must be prevented by using anti-
surge valves.

Outdoor installation
If installed outside buildings, the devices must be additionally protected from the weather.

Initialisation and feedback signal


The actuator initialises itself autonomously when it is connected as a continuous actuator. Once a
voltage is applied to the actuator for the first time, the actuator moves to the lower limit stop of the
valve and thus enables automatic connection with the valve spindle. Then it moves to the upper stop
and the value is detected and saved via a travel measurement system. The control signal and the
feedback are adjusted to this effective stroke. In case of a power failure or the removal of the power
supply, no re-initialisation is carried out. The values remain saved.
For a re-initialisation, the actuator must be connected to the power supply and there must be a
constant input signal at 3u or 3i. An initialisation is triggered by folding the crank handle out and back
twice within 4 seconds. Then the two LEDs flash red.
During initialisation, the feedback signal is inactive or equal to the value “0”. Initialisation is carried out
with the shortest running time. The re-initialisation is only valid when the whole process is complete.
Folding the crank handle out again interrupts this process.
If the valve actuator detects jamming, it will report this by setting the feedback signal to 0 V after
about 90 seconds. During this time, the actuator tries to overcome the jamming. If the jamming can
be overcome, the normal control function is activated again and the feedback signal is restored.
With 2-point or 3-point control, no initialisation is performed. The feedback signal is inactive.

Connection as 2-point valve actuator (24 V)


This activation (OPEN/CLOSE) can be performed via two wires. The voltage is applied to terminals 1
and 2a. When voltage (24 V) is applied to terminal 2b, the actuator spindle moves out. After this
voltage is switched off, the actuator moves to the opposite end position. In the end positions (valve
limit stop or maximum stroke reached) or in the case of an overload, the electronic motor cut-off is
activated (no limit switches).
The running times can be set using the coding switch. The characteristic cannot be selected here (the
result is the characteristic of the valve). Terminals 3i, 3u and 44 must not be connected.

Connection as 3-point valve actuator (24 V)


If voltage is applied to terminal 2a (or 2b), the valve can be moved to any desired position. If voltage
is applied to terminals 1 and 2b, the actuator spindle moves out. It moves in when the electrical circuit
is closed via terminals 1 and 2a.
In the end positions (valve limit stop or maximum stroke reached) or in the case of an overload, the
electronic motor cut-off is activated (no limit switches). The direction of the stroke can be changed by
swapping the connections.
The running times are set using the coding switch. The characteristic cannot be selected here (the
result is the characteristic of the valve). Terminals 3i, 3u and 44 must not be connected.

4/9 Right of amendment reserved © 2023 Fr. Sauter AG


Product data sheet 15.1 51.377

Connection with 230 V or 100…110 V as 2-point/3-point or with continuous activation of valve


actuator (accessory 0372332)
The built-in positioner controls the actuator depending on controller’s output signal y.
A voltage signal (0...10 V–) at terminal 3u or a current signal at terminal 3i serves as the control
signal. If there is a control signal on both terminals (3u (0...10 V) and 3i (4...20 mA)) at the same time,
the input with the higher value has priority.
Direction of operation 1 (mains power supply on internal connection 2a):
When the positioning signal is increasing, the actuator spindle extends.
Direction of operation 2 (mains power supply on internal connection 2b):
When the positioning signal is increasing, the actuator spindle retracts.
The starting point and control span are fixed. A split-range unit (only for voltage input 3u) designed for
installation in the actuator is available as an accessory for adjusting partial ranges (see split-range
unit function).
After the connection of the power supply and the initialisation, the actuator moves to every valve
stroke between 0% and 100%, depending on the control signal. Thanks to the electronics and the
travel measurement system, no stroke is lost, and the actuator does not require periodic re-
initialisation. When the end positions are reached, this position is checked, corrected if necessary,
and saved again. It is thus possible to operate multiple actuators of the SUT type in parallel. The
feedback signal y0 = 0...10 V corresponds to the effective valve stroke of 0...100 %.
If the control signal 0...10 V or 4...20 mA is interrupted with direction of operation 1, the actuator
spindle moves in completely, or moves out completely with direction of operation 2.
The coding switch can be used to set the characteristic of the valve. An equal-percentage or
quadratic characteristic can only be generated when the actuator is used as a continuous actuator.
Additional switches can be used to select the running times (with the 2-point, 3-point or continuous
functions).
Continuous actuation can also be used with a power supply of 230 V or 110 V (accessory required).
You must ensure that the neutral wire of the controller is connected to the control voltage. The neutral
wire of the power supply may only be used for the module.

LED indicator: The indicator consists of bi-colour LEDs (red/green).

Both LEDs flash red Initialisation


Top LED lights up red Top limit stop or “CLOSED” position reached
Bottom LED lights up red Bottom limit stop or “OPEN” position reached
Top LED flashes green Actuator is running, moving to “CLOSED” position
Top LED lights up green Actuator is stopped, last direction of travel “CLOSED”
Bottom LED flashes green Actuator is running, moving to “OPEN” position
Bottom LED lights up green Actuator is stopped, last direction of travel “OPEN”
No LED lights up No power supply (terminal 2a or 2b)
Both LEDs flash red and green Actuator is in manual mode

Valve design

) SAUTER provides various tools for valve design and engineering:


• ValveDim smartphone app
• ValveDim PC program
• ValveDim slide rule
You can find the tools under the link www.sauter-controls.com/en/performance/valve-calculation/
or scan the QR code

Split-range unit (accessory 0313529)


This accessory can be built into the actuator or externally housed in an electrical junction box.
Starting point U0 and control span ∆U can be set with the potentiometer. In this way, several control
units can be operated in sequence or cascade by the control signal of the controller. The input signal
(partial range) is converted into an output signal of 0...10 V.

Right of amendment reserved © 2023 Fr. Sauter AG 5/9


Product data sheet 15.1 51.377

Additional technical information


The yellow housing, consisting of the front part, rear part and connecting lid, only serves as a cover.
The DC motor, electronic control unit, load-bearing section and maintenance-free gear unit are
located in the housing. The actuator spindle and the column are made of rust-proof material. The
inner printed circuit boards and the gear unit are made of steel. The valve spindle guide and the valve
neck coupling are made of die-cast aluminium.
Note on ambient temperatures: With a media temperature of up to 110 °C in the valve, the ambient
temperature is allowed to reach 60 °C. With a media temperature above 110 °C, the ambient
temperature must not exceed 55 °C. Otherwise, the intermediate piece accessory 0372336180 must
be fitted.

Abbreviations used
Abbreviation Directive
LV-D Low-Voltage Directive 2014/35/EU
EESR-2016 Electrical Equipment (Safety) Regulations 2016
EMC-D Electromagnetic Compatibility Directive 2014/30/EU
EMC-2016 Electromagnetic Compatibility Regulations 2016
RoHS-D RoHS Directives 2011/65/EU and 2015/863/EU
RoHS-2012 Restriction of Hazardous Substances (RoHS) Regulations 2012

Auxiliary change-over contacts


0372333 Switch rating max. 250 VAC, current min. 250 mA at 12 V (or 20 mA at 20 V)
001 Switch rating max. 12...30 VDC, current max. 100 mA
0372333 Switch rating max. 250 VAC, current min. 1 mA at 5 V
002 Switch rating max. 0.1...30 VDC, current 1...100 mA
If it is used once in the range up to 10 mA or up to 50 V, the gold plating is eliminated. The switch
can then only be used for a higher switch rating.

CAUTION

! Hot surfaces - if there is a high media temperature in the valve, the actuator columns and the spindle can
attain similarly high temperatures.
►Avoid touching the device during operation.

NOTICE!

! If damage may occur if the control unit fails, additional protective measures must be implemented.

6/9 Right of amendment reserved © 2023 Fr. Sauter AG


Product data sheet 15.1 51.377

Desired Characteristic Characteristic


character. Switch coding Effective on valve
curve curve for valve curve for drive
v Stroke v
1 2 3 4

percentage
On
=%

Equal
Off

Stroke Signal Signal

v Stroke v
Quadratic 1 2 3 4
On 2
x
Off

Stroke Signal Signal

v Stroke v

1 2 3 4
Linear

On
lin
Off

Stroke Signal Signal

v Stroke v

1 2 3 4
percentage

On =%
Equal

Off

Stroke Signal Signal

v Stroke v
1 2 3 4
Linear

On
lin
Off

Stroke Signal Signal

= factory setting

Run time Run time for Run time for Run time for Run time for
per mm Switch coding 14 mm stroke 20 mm stroke 40 mm stroke 43 mm stroke
1 2 3 4
2s On
28 s ± 1 40 s ± 1 80 s ± 4 86 s ± 4.5
Off

1 2 3 4
4s On
56 s ± 2 80 s ± 4 160 s ± 4 172 s ± 4.5
Off

1 2 3 4
On

Off
6s 84 s ± 4 120 s ± 4 240 s ± 8 258 s ± 4.5
On

Off

= factory setting

A AVM234SF132-7 with 43 mm stroke for VDL flange, DN 100...200, Siemens VPF44, Frese Optima flange
with 40/43 mm stroke

Disposal
When disposing of the product, observe the currently applicable local laws.
More information on materials can be found in the Declaration on materials and the environment for
this product.

Right of amendment reserved © 2023 Fr. Sauter AG 7/9


Product data sheet 15.1 51.377

Connection diagram

Continuous
24 V~/=

y=0...10V y=4...20mA yo=0...10V


1 2a 2b 3u 3i 44

mC

3u 3i 44
0% 0V 4mA 0V M
2a 100%
S1 S2 S3 S4 10V 20mA 10V
On
0% 10V 20mA 0V
2b Spindle
100% 0V 4mA 10V
Off 0%
S1; S2 = Drivetime
S3; S4 = Characteristic 100%

2pt 3pt

24 V~/= 24 V~/=

1 2a 2b 3u 3i 44 1 2a 2b 3u 3i 44

Accessories
0372332001

III

y=0...10V y=4...20mA yo=0...10V


1 2a 2b 3u 3i 44
L
230V~
mC N

3u 3i 44
0% 0V 4mA 0V M N 2a 2b
2a 100%
S1 S2 S3 S4 10V 20mA 10V
On
0% 10V 20mA 0V
2b Spindle Module
100% 0V 4mA 10V
Off 0% 230V~
S1; S2 = Drivetime
S3; S4 = Characteristic 100%

2pt 3pt
L L
230V~ 230V~
N N

N 2a 2b N 2a 2b

Module Module
230V~ 230V~

AVM234S AVM234S

8/9 Right of amendment reserved © 2023 Fr. Sauter AG


Product data sheet 15.1 51.377

24V~

y
0...10 V
1 2 3 33 1 2a 3u
^ MM 01/02/LS 03
A/B ^
AVM . . .S
AVF . . . S
Uo ASF . . . S
DU AXM . . .S
ASM . . .S
AKM . . .S

372333 372334

4 5 6 7 8 9 10 11 12

0%

Dimension drawings

18,5 57 60 230
b

a 90

Type a b c
AVM234SF132 64 289 44
AVM234SF132-5 58 289 38
AVM234SF132-6 78 382 60
AVM234SF132-7 64 287 44

Accessories

0372336 180
0372336 240
a

0372336 T (°C) a (mm) b (mm)


Fr. Sauter AG
180 180 69,4 60 Im Surinam 55
240 240 109,4 100 CH-4058 Basel
Tel. +41 61 - 695 55 55
www.sauter-controls.com

Right of amendment reserved © 2023 Fr. Sauter AG 9/9