Features
• Activation of 2-way and 3-way valves of the VQD/BQD and VQE/BQE series, as well as VUG/BUG,
VUS/BUS, VUP, V6R/B6R and VDL
• For controllers with constant output (0...10 V or 4...20 mA) or switching output (2-point or 3-point
control) AVM234SF132
• Stepping motor with SAUTER Universal Technology (SUT) electronic control unit and electronic,
force-dependent cut-off
• Simple assembly with valve; spindle is automatically connected after control voltage is applied
(patented system)
• Automatic detection of applied control signal (constant or switched); indicated by two LEDs
• Coding switches for selecting characteristic and running time
• Type of characteristic (linear/quadratic/equal-percentage) can be set on the actuator
• Automatic adaptation to the stroke of the valve (min. valve stroke 8 mm, max. valve stroke 49 mm).
The measured stroke is saved and is not lost even in the event of a power failure
• Direction of operation can be selected via screw terminals when making the electrical connection
• Crank handle for external manual adjustment with motor cut-off and as trigger for a re-initialisation
• Numerous adapters enable the unit to be fitted onto non-SAUTER valves
• Power supply 230 V with module or direct connection for 24 VAC / 24 VDC; continuous activation
also admissible with 230 V
• Maintenance-free gear unit made of sintered steel; gearbox base-plate made of steel
• Mounting column made of stainless steel; mounting bracket made of cast light alloy for fitting the
valve
• Electrical connections (max. 2.5 mm²) with screw terminals
• Three pre-scored cable inlets for M20 × 1.5 (2×) and M16 × 1.5
• Fitting vertically upright to horizontal, not suspended
Technical data
Power supply
Power supply 24 VAC ±20%, 50…60 Hz
Power supply 24 VDC ±15%
Power supply 230 VAC ±15%, 50...60 Hz (with accessories)
Power consumption1) 24 VAC/24 VDC
10 W/20 VA
230 VAC (with accessories)
13 W/28 VA
ValveDim app
Parameters
Running time 2/4/6 s/mm
Actuator stroke 0...49 mm
Response time for 3-point 200 milliseconds
Positioner Control signal 1 0...10 V, Ri >100 kΩ
Control signal 2 4...20 mA, Ri = 50 Ω
Position feedback signal 0...10 V, load > 10 kΩ
Starting point U0 0 or 10 V
Control span ΔU 10 V
Switching range Xsh 300 mV
Ambient conditions
Ambient temperature −10…55 °C
Ambient humidity < 95% rh, no condensation
Media temperature2) Max. 120 °C
Construction
Weight 4.1 kg
Housing Two-part, yellow
Housing material Flame-retardant plastic
Standards, directives
Type of protection IP66 (EN 60529)
Protection class III (IEC 60730)
Over-voltage categories III
Degree of contamination III
CE/UKCA conformity3) LV-D 2014/35/EU (CE) EN 60730-1, EN 60730-2-14
EESR-2016 (UKCA) EN 60730-1, EN 60730-2-14
EMC-D 2014/30/EU (CE) EN 61000-6-2, EN 61000-6-4
EMC-2016 (UKCA)4) EN 61000-6-2, EN 61000-6-4
RoHS-D 2011/65/EU & EN IEC 63000:2018
2015/863/EU (CE)
RoHS-2012 (UKCA) EN IEC 63000:2018
Overview of types
Accessories
Type Description
0313529001 Split-range unit for setting sequences
Modules can be added for 2-point/3-point and continuous activation; additional power 2 VA
Type Description
0372332001 230 V ±15%, supply voltage
0372332002 100 V ±15%, supply voltage
Potentiometers
Type Description
0372334001 Potentiometer, 2000 Ω, 1 W, 24 V
0372334006 Potentiometer, 1000 Ω, 1 W, 24 V
Mounting set for AVM234SF132 on SAUTER valves (no adapter needed for 0372338 002)
Type Description
0372338001 V/B6 to DN 50, V/BXD, V/BXE, to DN 50, stroke 14 mm
0372338002 V/B6 DN 65...150, V/BXD, V/BXE from DN 65, stroke 40 mm
3) Explanation of abbreviations in the “Additional technical information” section of the product data sheet and in
the appendix to SAUTER product catalogues
4) EN 61000-6-2: (HF immunity limitation. Feedback signal between 80 MHz and 1000 MHz criterion B, otherwise
criterion A)
Type Description
0372338003 Conversion kit from AV*2*4SF132-5 to standard actuator AV*2*4SF132
0372338004 Conversion kit from AV*2*4SF132-6 to standard actuator AV*2*4SF132
Description of operation
This valve actuator may only be used for activation of 2- or 3-way valves from SAUTER or with non-
SAUTER valves compatible with the adapter set. Other applications are not permitted.
Depending on the type of connection (see connection diagram), the actuator can be used as a
continuous (0...10 V and/or 4...20 mA), 2-point (OPEN/CLOSE) or 3-point actuator
(OPEN/STOP/CLOSE).
The running time of the actuator can be set with switches S1 and S2 according to the relevant
requirements. Switches S3 and S4 are used to configure the characteristic (equal-percentage, linear
or quadratic).
The external crank handle enables manual positional setting. When the crank handle is folded out,
the motor is switched off. After the crank handle is folded back, the actuator moves to the target
position again (without initialisation). When the crank handle is folded out, the actuator remains in this
position.
Intended use
This product is only allowed to be used in HVAC building systems for control and regulation purposes.
Other uses require the prior consent of the manufacturer.
The section “Description of operation” and all product instructions in this data sheet must be
observed.
Modifying or converting the product is not permitted.
Improper use
The actuator is not suitable for:
• Safety applications
• Transport applications and at altitudes above 2000 metres
• Use in areas where there is a risk of condensation
• Use in plants with high pressure surges
) The product contains lead. To be marketed in North America, the appropriate warnings must be affixed to
the product or packaging.
Notice
) Extreme pressure surges in the system can lead to gear damage and must be prevented by using anti-
surge valves.
Outdoor installation
If installed outside buildings, the devices must be additionally protected from the weather.
Valve design
Abbreviations used
Abbreviation Directive
LV-D Low-Voltage Directive 2014/35/EU
EESR-2016 Electrical Equipment (Safety) Regulations 2016
EMC-D Electromagnetic Compatibility Directive 2014/30/EU
EMC-2016 Electromagnetic Compatibility Regulations 2016
RoHS-D RoHS Directives 2011/65/EU and 2015/863/EU
RoHS-2012 Restriction of Hazardous Substances (RoHS) Regulations 2012
CAUTION
! Hot surfaces - if there is a high media temperature in the valve, the actuator columns and the spindle can
attain similarly high temperatures.
►Avoid touching the device during operation.
NOTICE!
! If damage may occur if the control unit fails, additional protective measures must be implemented.
percentage
On
=%
Equal
Off
v Stroke v
Quadratic 1 2 3 4
On 2
x
Off
v Stroke v
1 2 3 4
Linear
On
lin
Off
v Stroke v
1 2 3 4
percentage
On =%
Equal
Off
v Stroke v
1 2 3 4
Linear
On
lin
Off
= factory setting
Run time Run time for Run time for Run time for Run time for
per mm Switch coding 14 mm stroke 20 mm stroke 40 mm stroke 43 mm stroke
1 2 3 4
2s On
28 s ± 1 40 s ± 1 80 s ± 4 86 s ± 4.5
Off
1 2 3 4
4s On
56 s ± 2 80 s ± 4 160 s ± 4 172 s ± 4.5
Off
1 2 3 4
On
Off
6s 84 s ± 4 120 s ± 4 240 s ± 8 258 s ± 4.5
On
Off
= factory setting
A AVM234SF132-7 with 43 mm stroke for VDL flange, DN 100...200, Siemens VPF44, Frese Optima flange
with 40/43 mm stroke
Disposal
When disposing of the product, observe the currently applicable local laws.
More information on materials can be found in the Declaration on materials and the environment for
this product.
Connection diagram
Continuous
24 V~/=
mC
3u 3i 44
0% 0V 4mA 0V M
2a 100%
S1 S2 S3 S4 10V 20mA 10V
On
0% 10V 20mA 0V
2b Spindle
100% 0V 4mA 10V
Off 0%
S1; S2 = Drivetime
S3; S4 = Characteristic 100%
2pt 3pt
24 V~/= 24 V~/=
1 2a 2b 3u 3i 44 1 2a 2b 3u 3i 44
Accessories
0372332001
III
3u 3i 44
0% 0V 4mA 0V M N 2a 2b
2a 100%
S1 S2 S3 S4 10V 20mA 10V
On
0% 10V 20mA 0V
2b Spindle Module
100% 0V 4mA 10V
Off 0% 230V~
S1; S2 = Drivetime
S3; S4 = Characteristic 100%
2pt 3pt
L L
230V~ 230V~
N N
N 2a 2b N 2a 2b
Module Module
230V~ 230V~
AVM234S AVM234S
24V~
y
0...10 V
1 2 3 33 1 2a 3u
^ MM 01/02/LS 03
A/B ^
AVM . . .S
AVF . . . S
Uo ASF . . . S
DU AXM . . .S
ASM . . .S
AKM . . .S
372333 372334
4 5 6 7 8 9 10 11 12
0%
Dimension drawings
18,5 57 60 230
b
a 90
Type a b c
AVM234SF132 64 289 44
AVM234SF132-5 58 289 38
AVM234SF132-6 78 382 60
AVM234SF132-7 64 287 44
Accessories
0372336 180
0372336 240
a