1
Testing the SEE software modifications to ensure a switch
off of the excitation equipment under abnormal conditions
Block number:
Test sequence
1. Switch off via low frequency
• Switch on SEE in automatic channel.
• Protection Off after 10s and deexcitation breaker switches off.
5. Normalize SEE
• Remove simulation 2: remove negation on F002/001 module 06, input 2
• Remove simulation 3: remove negation on F002/001 module 06, input 3
• Remove simulation 4: remove negation on F002/001 module 06, input 4
• Remove simulation 5: remove negation on F002/001 module 06, input 5
• Switch on MCB -Q113 and -Q114 and deexcitation breaker switches off.
• Remove temporary supply installed under chapter preconditions and normalize
power supply. Attention: Follow the safety rules!
• Put the SEE MV-Circuit Breaker (between station supply and excitation trans-
former) into operating position.