Design of Automatic Fire Sprinkler System
Design of Automatic Fire Sprinkler System
Design of Automatic Fire Sprinkler System
An Automatic Fire Sprinkler System is designed to contain and control an unfriendly fire
allowing your family the precious time needed to escape from danger and decrease the
amount of damage to your valuables from heat and smoke. An Automatic Fire Sprinkler
System is a network of water-filled pipes which starts at your domestic water service
line and ends with strategically spaced fire sprinkler heads located throughout your
home. The sprinkler heads are frangible bulbs filled with a liquid that, when heated,
expand causing the bulb(s) to break and the system to release water. The water from
the sprinkler head will cover the area where the fire is located and will continue to
operate until the fire department can fully extinguish the fire.
Almost all newly built commercial or industrial buildings require automatic fire sprinkler
systems for life safety, the protection of the property, the safety of the firefighters, and to
minimize business interruption. These systems are designed and installed as
prescribed in the National Fire Protection Association (NFPA) Standard for the
Installation of Sprinkler Systems or NFPA 13. In the simplest form, these systems
include a series of connected pipes and fittings, with valves, alarm initiating devices,
and automatic sprinklers that are supplied by a reliable water supply.
The four primary systems are the wet pipe system, the dry pipe system, the preaction
system and the deluge system.
Wet Pipe System
The wet pipe sprinkler system is, in general, the most cost-effective, the most versatile
as far as protection strategies and pipe installation are concerned, and the easiest to
maintain. Its cost effectiveness is based on its having fewer components, requiring less
maintenance and testing and having fewer design restrictions than any of the other
three types of systems. Wet pipe systems are installed where temperatures will not fall
below 40°F (4°C) and where one of the design objectives is to put water on a relatively
small fire as quickly as possible.
In a wet pipe system, components are arranged in such a manner that, as soon as the
heat from a fire operates the heat responsive element of an automatic sprinkler, the
water is discharged through the sprinkler to the fire. It is possible to design these
systems for fire control – controlling a fire to the room or area of origin until the fire
department arrives and extinguishes the fire; fire suppression – actually suppressing the
fire; or life safety protection – as in residential occupancies. The wet pipe system can
also include additives such as antifreeze or foam concentrate.
Design issues relative to the wet pipe sprinkler systems would include the following:
Is there a possibility or potential for freezing anywhere the water-filled
components are installed?
Is interior or exterior corrosion a factor to be concerned about?
What are the appropriate materials for a wet pipe system?
Dry Pipe System
When sprinkler systems are required in buildings, or areas of buildings, where the
ambient temperature will not be maintained above 40°F (4°C) dry pipe systems are an
option. The dry pipe system is more expensive than the wet pipe system; requires more
maintenance and testing (weekly, monthly, annually, and over its lifetime); and has
additional design requirements beyond those of the basic wet pipe system.
Preaction System
The preaction system is similar to a dry pipe system. It has a similar valve, and in
general the same pipe, fittings, alarm initiating devices, and automatic sprinklers. In
addition to the sprinkler system, however, the preaction system incorporates a detection
system. Preaction systems areusually less cost-effective than the dry pipe systems and
require additional maintenance and testing as well as maintenance and testing of the
detection system.
There are many types of detectors and detection systems that can be used with the
preaction systems. It is in the system designer’s best interest to work closely with the
owner and the architect to utilize the type of detection system that is appropriate for
each specific area or system. An example of such an area is the data or computer
room, where the products of combustion can do as much damage to sensitive
equipment as the thermal damage from a fire or the resultant application of water. In
these rooms, an air sampling detection system may be more appropriate than smoke
detectors. The air sampling system may detect particles of combustion before the
human eye or nose does and can send signals or warnings before there is actual smoke
damage or a fire or before water is necessary.
Deluge System
Deluge systems are similar to preaction systems, in most cases utilizing the same
valves, pipe, fittings, alarm initiating devices, automatic sprinklers, and detectors,
although all of the sprinklers are open and do not include the heat responsive element.
Spray nozzles can be used in deluge systems instead of the open automatic sprinklers.
The difference between preaction and deluge systems is that with the sprinklers open at
all times, neither air nor water can be maintained in the piping. The deluge system
requires a detection system to operate and signal the deluge valve, opening the valve
and allowing water to flow through the piping and discharge through all of the sprinklers
or nozzles simultaneously.
Deluge systems can be installed in warm or cold very high hazard areas and the
primary objective is to put as much water on a fire as is required to contain or control a
severe fire hazard as quickly as possible. These systems are utilized where a large
amount of water is necessary quickly such as in flammable and combustible dispensing
operations, aircraft hangars, and transformers. The deluge systems frequently include
foam concentrates.
The type of sprinkler system must be determined early in the design process. That
decision in turn has implications on the remainder of the system design, from hydraulic
criteria to water supply and system components. The owner’s or client’s operations,
processes, and overall needs must be included in determining the type of system for a
specific project.
Finally, long-term effects such as the cost of inspection, testing, and maintenance of the
sprinkler and detection systems, as well as life expectancy of the pipe, fittings, and
other components must be included in the overall evaluation.
Looped Sprinkler System
A sprinkler system in which multiple cross mains are tied together so as to provide more
than one path for water to flow to an operating sprinkler and branch lines are not tied
together.
Branch Lines: The pipes supplying sprinkler, either directly or through or through
springs, drops, return bends, or arm-overs.
Arm - Over: A horizontal pipe that extends from the branch line to a single sprinkler or a
sprinkler above and below a ceiling.
Cross Mains: The pipes supplying the branch lines, either directly or through risers.
Feed Mains: The pipes supplying cross mains, either directly or through risers.
Riser Nipple : Vertical piece of pipe between the main and branch line.
Refer to Table 6.2.5.1 for Sprinkler Temperature Ratings, Classifications and Color
Coding's of Sprinklers
The maximum floor area on any floor to be protected by sprinklers supplied by any one
sprinkler system riser or combined system riser shall be as follows:
Protection Areas and Maximum Spacing for CMSA (Control Mode Specific
Application) Sprinklers. Table 8.11.2.2.1
Protection Areas and Maximum Spacing for ESFR (Early Suppression Fast-
Response) Sprinklers. Table 8.12.2.2.1
Two layer sprinkler heads when false ceiling height is more than 80 cm.
Install one sprinkler below any duct or cable tray when width is more than 80 cm
below.
Installation Control Valve (Also called Alarm Check Valve)
An alarm check valve is basically a check valve with an alarm port. The main purpose of
the alarm check valve is to ring a mechanical bell called a water motor gong. The valve
should, (if properly maintained), help hold the system pressure steady and reduce the
possibility of false alarms.
The alarm check valve is a water flow alarm device designed for vertical installation in
the main supply to a wet pipe sprinkler system. When a flow of water from the system
equals or exceeds that of a single sprinkler, the valve is to actuate a fire alarm.
Local alarms shall be provided on all sprinklers system having more than 20 sprinklers.
WET PIPE SPRINKLER MANUAL
Fire Department Connection
A fire department connection shall be provided as described in accordance with Figure
8.17.2.1. Pipe size shall be a minimum 4 in (100 mm) for fire engine connections and 6
in 9150 mm ) for fire boat connections.
The FDC shall be on the system side of the water supply check valve.
The FDC shall be on the street side of the building. A listed check valve shall be
installed in each fire department connection.
A) Basement used as a car parks or storage occupancy if the area exceed 200 m2.
B) Multilevel basements.
D) Departmental stores or shops, if the aggregate covered area exceed 500 m2.
E) All non-domestic floors of mixed occupancy which constitute a hazard and are not
provided with staircase independent of the remainder of the buildings.
F) Godowns and warehouses as considered necessary.
International Experience:
A) 55% of fires were extinguished by the operation of two or less sprinkler heads.
D) Sprinkler coverage for the fire protection of occupancies has full legislative as well as
insurance supports.