Automatic Transfer Switch (ATS) Controller: B37944 DTSC-200A

Download as pdf or txt
Download as pdf or txt
Download as pdf or txt
You are on page 1/ 4

Released

Product Specification
B37944

DTSC-200A Unique Features


DTSC-200A  Built on field proven DTSC-200
 New face plate with tactile buttons
 Large LCD display
 Programmable from HMI panel or ser-
vice tool (USB connection)
 Shorter lead time

 Premium ATS control for


complex transfer switch
applications for critical
power assets. Supports,
 Circuit breakers or
latching contactors
Automatic Transfer Switch (ATS) Controller  Open, delayed, or closed
transition transfer
DESCRIPTION
 Make-before-break
The DTSC-200A (Digital Transfer Switch Control) controls the transfer of electrical power from one source to (<100ms) transfer or
another for hospitals, data centers, office buildings, manufacturing plants and similar where lights out is not an extended indefinitely for
option. The extremely versatile DTSC-200A ATS controller is easily configured for a wide range of automatic
transfer switch applications including Main-Gen, Gen-Gen or Main-Main systems using circuit breakers or latch- paralleling
ing contactors. Source transfer can be performed as open, delayed, or closed transition with in-phase monitor-
ing (synch check) that can be enabled for all transition types to ensure safe transfer. The closed transition over-
 In-phase monitoring
lap time can be limited to less than 100ms for momentary, make-before-break transfers, or extended indefinitely (synch check) for all
for paralleling via discrete input. “Custom” features like transfer inhibit, source selection, load shed/restore, ele- transition types
vator pre-signal and engine test programs come standard.
 Engine exerciser
LogicsManagerTM - Programmable Boolean logic functions along with ample, expandable discrete I/O allows
for complex transfer schemes without using external relay logic or a separate PLC!
(load/no-load) routine
with fully adjustable
FlexAppTM - Easily configures the DTSC-200A for: Utility-to-Generator, Generator-to-Generator or Utility-to-Util- interval
ity applications
 Load shed and restore
DynamicsLCDTM - The adaptive and interactive 4.3”, 480 x 272-pixel TFT LC display with tactile buttons and a
clear menu structure ensure intuitive user operation and navigation.  Elevator pre-signal
FEATURES  Transfer/return inhibit
 True R.M.S. 3-phase voltage measuring for both Source 1 and Source 2
 Adjustable timers and
 True R.M.S. 3-phase load current/power bypass
 Software configurable for wide range of ATS applications:
 Utility-to-Generator: Utility is preferred with a generator as emergency source  Priority source selection
 Generator-to-Generator: One genset is preferred with a second genset as backup
 Utility-to-Utility: Utility is preferred with second utility as the emergency source  Freely configurable,
 Incorporates several monitoring features for a secure transfer: Source, Load, Switch, Battery, In-phase, and expandable discrete I/O
parallel time monitor
 Intelligent limit switch feedback monitoring to ensure plausibility before initiating a transfer  CANopen / Modbus RTU
 Fully configurable transfer command pulse configuration
 Inhibit transfer to S1, S2, both or start emergency source but initiate no transfer  PC and/or front display
 Elevator pre-signal with timer before carrying out a transfer
 Motor load disconnect signal with timer and possibility to daisy chain multiple MLDs for load sequencing
configuration with
 Source priority selection configurable via LogicsManager password protection
 Load test and engine test to initiate routine health check of the emergency source
 In-phase monitoring ensures a transfer occurs within a phase angle difference of 70 or less  CE marked
 Extended parallel time enables soft loading applications
 Vector group adjustment if transformers are used in the ATS system  UL/cUL 1008
 Shunt trip enable signal ensures both sources are not paralleled for more than desired time
 Remote control via interface (CANopen, Modbus RTU) and via discrete inputs
 I/O expansion capability (additional 16x DI and 16x DO supported via IKD1M or 3rd party modules)
 Adjustable display backlight shutdown to reduce power consumption
 Woodward ToolKit™ software for flexible setup from a single connection to the network. Supports settings
file created from the DTSC-200
 Multi-lingual capability: English, German, Spanish, Polish, Russian, other languages upon request
Released

SPECIFICATIONS
Power supply ..........................................................12/24 VDC (8 to 35 VDC) Discrete outputs group A [R 2-4] .................................................... isolated
Intrinsic consumption ................................ max. 6 W (standby max. 5 W) ...................................................... Rated 7 ADC, 24 VDC running standalone
Ambient temperature (operation) .................... -25 to 70 °C / -13 to 158 °F ............ Rated 3 ADC, 24 VDC when running in parallel with other two relays
Ambient temperature (storage) ...................... -25 to 70 °C / -13 to 158 °F ...............................................3 ADC, 24 VDC resistive GP (according to UL)
Ambient humidity..................................................... 93%, non-condensing Discrete output [R 5] ........................................................................ isolated
Voltage .................................................................................................. / ................................ Rated 7 AAC, 250 VAC voltage free output, resistive GP
Rated (Vrated) .......................................... 277/480 V AC Discrete outputs group B [R 6-7] .................................................... isolated
Max. value (Vmax).......................................... 358/620 V AC .................................................... Rated 10 ADC, 24 VDC running standalone
Max. value (Vmax) according to UL ............... 173/300 VAC .............. Rated 5 ADC, 24 VDC when running in parallel with the other relay
Accuracy ........................................................................................ Class 1 .................................................... 2 ADC, 24 VDC inductive (according to UL)
Linear measuring range ................................................................. 1×V rated Discrete output group C [R 8-9] ...................................................... isolated
Measuring frequency ............................................ 50/60 Hz (40 to 85 Hz) ................................ Rated 7 AAC, 250 VAC voltage free output, resistive GP
High Impedance Input; Resistance per path ................................. 4.0 M Interfaces ........................................................................................................
Max. power consumption per path ............................................... < 0.2 VA USB service port ............................................................................................
Current (Isolated) Rated (Irated)…...…...………………...……...……….5A Max. allowed cable length ....................................................................1.5 m
Linear measuring range ...................................................... Igen = 2.0×Irated RS-485 interface ............................................................................... isolated
Imains/ground = 1.5×Irated Insulation voltage .............................................................................. 500 V AC
Rated short-time overcurrent (1 s) ................................................ 10×I rated Max. allowed cable length .................................................................1000 m
Accuracy ....................................................................................... Class 1
Discrete inputs group A [DI 1-7] ........................................... non isolated CAN bus interface ............................................................................. isolated
Low level threshold ....................................................... Approx.… 1.3 V DC Insulation voltage .............................................................................. 500 V AC
High level threshold........................................................................ 1.7 V DC Internal line termination .................................................................. 120 Ohm
Max. input voltage ........................................................................... 60 V DC Housing Front panel flush mounting ...................................... Plastic housing
Min. input voltage .............................................................................. 0 V DC Dimensions WxHxD .......................................... 237 × 172 × 45 mm
Discrete inputs group B [DI 8-12] ......................................... non isolated Front cutout WxH ................................................ 214.5 × 160.5 mm
Low level threshold ....................................................... Approx.… 1.3 V DC Connection ..................................................... screw/plug terminals 2.5 mm²
High level threshold........................................................................ 1.7 V DC Front.................................................................................. insulating surface
Max. input voltage ........................................................................... 24 V DC Sealing Front .................................. IP65 (with screw fastening)
Min. input voltage .............................................................................. 0 V DC Back ...................................................................... IP20
Display ........................................................................................................ Weight .................................................................................. approx. 0,850 g
............................................................ 480 × 272 TFT LCD with backlight Disturbance test (CE) ............ tested according to applicable IEC standards
....... Wear resistant and scratch resistant LCD due to hard acrylic screen Listings .......................................................CE, UL1008 (File No: E527936)

DIMENSIONS
Released

TERMINAL DIAGRAM

microSD USB RS232 Ethernet


Not used Device Not used Not used

B(-)
35

61
A(+) RS485 *1
[DI 12]
34

60
Discrete Input [DI 12]

*1
NC [DI 11]
33

59
Discrete Input [DI 11]

*1
[DI 10]
32

58
Discrete Input [DI 10]

*1
[DI 09]

57
Discrete Input [DI 09]

*1
[DI 08]
30

56
Discrete Input [DI 08]
Not used
29
28

55
27

Not used

54
NC
26

53
CAN-L
25

GND

52
CAN
CAN-H
24

L3

51
Load current
23

NC L2

50
22

L1

49
*1
Relay [R05]
21

[R05] Engine start contact


DTSC-200A
20

*1
[DI 07] Discrete Input [DI 07] Source 2 voltage N 300 Vac ph-ph
19

48
Source 2 voltage L3 300 Vac
18

47
ph-ph

Not used Source 2 voltage L2 300 Vac


17

46
ph-ph

Source 2 voltage L1 300 Vac


16

45
ph-ph
*1
[DI 06] Discrete Input [DI 06]
15

*1
Discrete Input [DI 05]
[DI 05]
14

Inhibit ATS
Discrete Input [DI 04] Source 1 voltage N 300 Vac

44
[DI 04] Reply ATS limit switch: Breaker in Source 2 open position (N.C.) ph-ph
13

Discrete Input [DI 03] Source 1 voltage L3 300 Vac ph-ph

43
[DI 03]
12

Reply ATS limit switch: Breaker in Source 1 open position (N.C.)


Discrete Input [DI 02] Source 1 voltage L2 300 Vac ph-ph

42
[DI 02]
11

Reply ATS limit switch: Breaker in Source 2 position (N.C.)


Discrete Input [DI 01] Source 1 voltage L1 300 Vac ph-ph

41
[DI 01]
10

Reply ATS limit switch: Breaker in Source 1 position (N.C.)

Not used R5, R8, R9: 7Aac AC250Vac voltage free output, resistive GP
9

R6, R7: 2Adc 24Vdc, inductive


R2, R3, R4: 3Adc 28Vdc, resistive GP
[R04] Relay [R04]* 1
8

AC-measurement:
Relay [R03]* 1 AC30V - AC300V (ph-ph) according to UL
[R03]
7

U(PH-PH); 300VACmax according to UL


U(PH-GROUND); 173VACmax according to UL
[R02] Relay [R02]* 1
6

Relay [R07]* 1
40

[R07] Relay [R09] isolated* 1


5

Command: Close to source 2 position [R09]


Command: Open from source 2 position
*1
Relay [R06] to neutral position
39

[R06]
4

Command: Close to source 1 position


38
3

Relay [R08] isolated* 1


+ Power supply [R08]
37

Command: Open from source 1 position


2

8 to 35 Vdc to neutral position

- Reverse polarity protected


36
1

terminals
terminals

Screw
Screw

Subject to technical modifications *1 configurable via LogicsManager DTSC-200A Diagram

RELATED PRODUCTS
 I/O Expansion Board IKD1 (Product spec. # 37171)
 ToolKit (Product spec. # 03366)
 Genset controller easYgen-3200XT & easYgen-3500XT (Product spec. # 37582 and #37583)
 Circuit breaker controller easYgen | LS-6XT (Product spec. #37913)
 CANbus to Fiber Optic Converters (Application note # 37598):
DL-CAN P/N 8445-1049 and DL-CAN-R P/N 8445-1048
 Remote Access Gateway (with HMS Netbiter EasyConnect EC250 and EC350)
 Phoenix expansion CAN Couplers
Released

Digital Transfer Switch Controller


DTSC-200A

Measuring
CONTACT True R.M.S. Source voltage (3phase/4-wire) Source 1 
Source 2 
North & Central America Load current (3phase/4-wire, true RMS) .../5 A 
Tel.: +1 (208) 278 3370
Breaker Control
South America Open transition (break-before-make) 
Tel.: +55 19 3708 4800 Delayed transition (break-before-make) + timed neutral position 
Closed transition (make-before-break) #1 
Europe Application FlexAppTM
Tel.: +49 711 78954 510
Utility to generator 
Middle East & Africa Utility to utility (configurable phase angle) 
Tel.: +971 2 678 4424 Generator to generator (2 start signals) 
Features
Russia Programmable elevator pre-signal 
Tel.: +49 711 78954 515 Programmable motor load disconnect signal 
Transfer commit 
China
Test modes #2 
Tel.: +86 512 8818 5515
Transfer mode selector #2 
India Load shed #2 
Tel.: +91 124 4399 500 Shunt trip enable #2 
Extended parallel time #2 
ASEAN & Oceania Automated display backlight shutdown selectable 
Tel.: +49 711 78954 510 Daylight saving time 
 Source priority selection #2 
SALES SUPPORT Vector group adjustment for in-phase monitoring 
 industrial.sales PG@woodward.com Fully adjustable timers #3 
Status LEDs for source availability and breaker state 
TECHNICAL SUPPORT
Accessories
 industrial.support@woodward.com
Tactile keys (advanced LC display) DynamicsLCDTM 
www.woodward.com Configuration via PC #4 
Event recorder with real time clock 300
Flush-mounting (screw or clamp fastening) 
Subject to alterations, errors excepted. Monitoring ANSI#
Source: voltage 59/27 
Subject to technical modifications.
Source: frequency 81O/81U 
This document is distributed for informa- Source: voltage asymmetry 47 
tional purposes only. It is not to be con- Source: rotation field 
strued as creating or becoming part of
any Woodward Company contractual or Load: overload 32 
warranty obligation unless expressly Load: overcurrent 50/51 
stated in a written sales contract. Switch: plausible switch position 
We appreciate your comments about the Switch: transition failure 
content of our publications. Please send Battery: voltage 
comments including the document num-
ber below to
Synch check (in-phase monitoring) 25 
marketing_pg@woodward.com Parallel time monitoring 
© Woodward I/Os
All Rights Reserved
Discrete inputs (configurable) 12
Discrete outputs (configurable) LogicsManagerTM 8
USB service port #4 
CANopen communication bus (isolated) 
For more information contact:

RS-485 Modbus RTU Slave half-duplex (isolated) 


Listings/Approvals
UL/cUL 1008 Listed 
CE Marked 
Part numbers
Front panel mounting with display, 5A CT input#5 8440-2297
Spare connector kit 10-004-675
Spare mounting kit 10-062-608
#1 Optimized to achieve short parallel (< 100ms) or extended long parallel as per LM status
#2 via internal conditions or remote command
#3 neutral delay timers (1 to 6500 s), elevator pre-signal timers (1 to 6500 s), motor load disconnect timers (1 to 6500 s), stable timers (1 to 6500 s),
outage timers (0.1 to 10.0 s), engine start delay timers (1 to 300 s)
#4 Configuration software ‘Toolkit’ available free at Woodward.com or at product documentation site, http://wwdmanuals.com/dtsc-200a
B37944 – Rev. C #5 a screw and a clamp kit are delivered with the unit for fastening