Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

53 TMSS 01 R0 Unlocked

Download as pdf or txt
Download as pdf or txt
You are on page 1of 57

Jul

y29,2006
TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

TABLE OF CONTENTS

1.0 SCOPE

2.0 CROSS REFERENCES

3.0 APPLICABLE CODES AND STANDARDS

4.0 DESIGN AND CONSTRUCTION REQUIREMENTS

4.1 General
4.2 Performance Characteristics and Ratings
4.3. Construction
4.4. Tap Changer
4.5 Temperature Control Devices
4.6 Outdoor Control Cabinet
4.7 Buchholz Relay
4.8 Pressure Relief Device
4.9 Outdoor Bushings (Oil/Air)
4.10 Radiator
4.11 Fans
4.12 Oil Pumps
4.13 Oil Preservation System
4.14 Breather
4.15 Drain, Filter and Sampling Valves
4.16 Inspection Facilities
4.17 Lifting, Moving and Jacking Facilities
4.18 Ladder
4.19 Grounding
4.20 External Terminal Markings and Location
4.21 Transformer Oil
4.22 Bushing Current Transformers
4.23 Terminations
4.24 Surge Arresters
4.25 On line monitoring
4.26 Nameplate

5.0 SHIPPING

5.1 Packing
5.2 Impact Recorder

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 2 OF 57


TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

6.0 TESTS

6.1 Type (Design) Tests


6.2 Routine Tests
6.3 Special Tests

7.0 DATA SCHEDULE

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 3 OF 57


TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

1.0 SCOPE

This SEC Transmission Material Standard Specification (TMSS) specifies the minimum
technical requirements for design, engineering, manufacture, inspection, testing and
performance of outdoor, three phase, mineral oil immersed power transformers, rated 2
MVA up to 100 MVA intended to be used in the system of the Saudi Electricity Company,
Saudi Arabia.

This TMSS does not cover Generator Transformers and associated auxiliary transformers.

2.0 CROSS REFERENCES

This Material Standard Specification shall always be read in conjunction with SEC General
Specification No. 01-TMSS-01, titled "General Requirements for All Equipment/Materials",
which shall be considered as an integral part of this TMSS.

This TMSS shall also be read in conjunction with SEC Purchase Order or Contract
Schedules for project, as applicable.

3.0 APPLICABLE CODES AND STANDARDS

The latest revision/amendments of the following Codes and Standards shall be applicable for
the equipment/material covered in this TMSS. In case of conflict, the vendor/manufacturer
may propose equipment/material conforming to one group of Industry Codes and Standards
quoted hereunder without jeopardizing the requirements of this TMSS.

3.1 IEC 60044-1 Instrument Transformers, Part 1: Current Transformers

3.2 IEC 60044-6 Instrument Transformers, Requirements for Protective Current


Transformers for Transient Performance

3.3 IEC 60076 Power Transformers

3.4 IEC 60137 Insulated Bushings for Alternating Voltages above 1000V

3.5 IEC 60214-1 Tap Changers Part 1: Performance Requirements and Test
Methods On-Load Tap Changers

3.6 IEC 60214-2 Tap Changers Part 2 : Application Guide

3.7 IEC 60507 Artificial Pollution Tests on High Voltage Insulators to be


used on AC systems

 3.8 IEC 60529 Degrees of Protection Provided by Enclosures (IP Code)

3.9 IEC 60616 Terminal and Tapping Markings for Power Transformers

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 4 OF 57


TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

3.10 IEC 60354 Loading Guide for Oil Immersed Power Transformers

3.11 ANSI C57.12.10 Requirements for Transformers, 230kV and below, 833/958
through 8333/10417 kVA, Single Phase; and 750/862 through
60 000/80 000/100 000 kVA, 3-Phase without Load Tap
Changing: and 3750/4687 through 60 000/80 000/100 000
kVA with Load Tap Changing – Safety Requirement

3.12 ANSI C57.12.70 Terminal Markings and Connections for Distribution and
Power Transformers

3.13 ANSI C57.12.90 Test Code for Liquid Immersed Distribution, Power and
Regulating Transformers and Guide for Short Circuit Testing
of Distribution and Power Transformers

3.14 ANSI C57.13 Requirements for Instrument Transformers

3.15 ANSI/NFPA 70 National Electrical Code

3.16 ANSI C57.19.00 General Requirements and Test Procedures for Outdoor
Apparatus Bushings
 
 3.17 IEEE C57.19.00 General Requirements and Test Procedure for Outdoor Power
Apparatus Bushings

3.18 IEEE C57.91 IEEE Loading Guide for Loading Mineral-Oil-Immersed


Transformers

3.19 NEMA-TR-1 Transformers, Regulators and Reactors.

3.20 SASO/SSA 421 Testing Methods of Power Transformers

3.21 SASO/SSA 422 Power Transformers

3.22 54-TMSS-01 Mineral Insulating Oil for Electrical Apparatus

3.23 50-TMSS-01 Current Transformer (CT) up to 380kV

3.24 Cigre WG 12.15 Guide For Customers Specifications For Transformers


100 MVA and 123 kV and Above

4.0 DESIGN AND CONSTRUCTION REQUIREMENTS

4.1 General

4.1.1 The transformer shall be core type.

4.1.2 Vector group designation shall be per IEC60076.


53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 5 OF 57
TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

4.1.3 The transformer shall be suitable for outdoor service.

4.2 Performance Characteristics and Ratings

4.2.1 Rating

a. The transformer specific ratings and requirements shall be as


specified in the Data Schedule at all tap positions

b. The transformer shall be capable of delivering its rated power


continuously with rated voltage on the secondary winding under the
ambient temperature specified in 01-TMSS-01.

4.2.2 Overloading Capability

a. The power transformer shall be designed to meet the overloading


requirements of the relevant IEC or IEEE Industry Standards adjusted
to ambient conditions specified in 01-TMSS-01.

b. All transformer accessories (tap changer, bushings, CTs, etc.) shall be


rated to carry 120% of the transformer current with tap changer on the
extreme minus tap.

4.2.3 Paralleling

The transformer shall meet the requirements for parallel operation, if


specified in Data Schedule.

  4.2.4 Losses

The manufacturer shall state the guaranteed transformer losses as part of the
proposal for natural cooling with tolerance per IEC or IEEE standards. The
guaranteed total losses shall not exceed 0.5% (Max.) of ONAN rating. The
factory measured total loss values shall not exceed guaranteed values.
Otherwise penalty shall be imposed per contract schedules for loss values up
to 5% above guaranteed value including tolerance. If the actual losses exceed
5% above guaranteed value, SEC shall have the right to reject the
transformer.

4.2.5 Operation at Higher than Rated Voltage/Frequency

a. The transformer shall be designed for the following over fluxing


requirements on any tap while carrying the rated current for that tap
without exceeding the temperature rise associated with temperature
rise test:

Continuous 110% of rated volts/Hz


1 minute 125% of rated volts/Hz
10 seconds 140% of rated volts/Hz

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 6 OF 57


TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

b. Over excitation curve for the transformer showing volts/Hz versus


time shall be submitted.

4.2.6 Short Circuit Withstand

a. The transformer shall be designed and constructed to withstand on


any tapping without damage, the thermal and mechanical effects of
short-circuit in accordance with IEC 60076 or ANSI C57.12.90.

b. Evidence regarding the thermal and dynamic withstand capability


shall be demonstrated by either type test or calculations. The
mechanical (dynamic) forces withstand capability shall also be
explained by the manufacturer by giving details of special
arrangements provided in the transformer.

4.2.7 Tertiary Winding (if applicable)

Tertiary winding shall be delta or star connected as specified in data


schedule. Delta connected winding shall meet the following requirements:

a. Tertiary winding rating shall be determined by the manufacturer with


calculation based on dynamic short circuit withstand capability. The
rating shall be guaranteed by the manufacturer and prove the same
with temperature rise test if specified in data schedule. The delta-
connected winding shall have at least a short time fault power rating
equal to one-third of the power rating of the secondary winding.

b. The tertiary winding shall be connected internally and all ends of the
windings shall be brought outside through three fully rated bushings
for connection to external circuit. The insulation level of the bushings
shall match with that of the winding. Series current limiting reactor
shall not be used in the tertiary winding.

c. The manufacturer shall investigate the transferred over voltage


phenomenon from the H.V winding to the tertiary winding and
furnish calculations for sizing of the tertiary surge arresters. As all
construction factors influencing the magnitude of transferred voltage
are difficult to calculate, transferred voltage shall be proved with tests
if stated in the data schedule.

d. Grounding of tertiary winding shall be per clause 4.19.3.

4.2.8 Cooling

a. The transformer shall be equipped with ONAN, ONAF etc., cooling


system as specified in data schedule.

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 7 OF 57


TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

b. Loss of 25% of forced air-cooling capacity shall not affect the


Continuous Maximum Rating of the transformer. Heat run test shall
be performed without 25% redundant cooling.

c. The start and stop impulses for fans shall be from winding
temperature indicator. Sufficient temperature difference between start
and stop signals shall be kept and frequent start/stop operation for
small temperature differences shall be avoided.

d. Control shall be suitable for both manual and automatic operation for
each group of fans and changeover from automatic to manual control
shall be possible.

e. For forced oil cooling, if applicable, pumps shall be provided with


100% redundancy, with automatic changeover to the healthy pump, in
case of any pump failure.

f. Each fan motor shall be protected by a separate MCB provided with


thermal over load and short circuit protection. Thermal over-load
protection shall be hand reset type.

g. The failure of any individual fan or failure of a pump or fan motor


MCB in off position shall initiate an alarm.

4.2.9 Noise Level and Vibration

a. Unless otherwise specified in data schedule, noise level, when


measured in accordance with IEC 60076-10 or ANSI C57.12.90, shall
not exceed the limits specified in NEMA TR-1.

Noise level shall be furnished for each stage of cooling. Positive


tolerance on noise level is not acceptable.

b. The design and clamping of the core and windings shall be such that
excessive vibrations shall not be transmitted from the magnetic
circuits to the tank and accessories. The maximum limit of vibration
shall be 100µm.

4.2.10 Inrush Current

Inrush harmonic contents and the duration of inrush currents for worst
energization criteria shall be provided on current versus time curve. All
relevant factors such as source impedance, remanence, damping, switching
instant, existence of already energized parallel transformer shall be
considered.

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 8 OF 57


TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

4.3 Construction

4.3.1 Tank

a. The tank shall be of conservator type construction.

b. The tank shall be made of formed and electrically welded high


strength steel-alloy plate. It shall be suitably braced to provide
sufficient strength for support of internal parts and to prevent damage
or distortion under service conditions or during transport or when the
complete transformer assembly filled with oil is lifted by crane or
jacks.

c. The tank and accessories shall be designed to withstand:

1. 25% higher than the maximum operating pressure i.e. pressure


from the oil preservation system comprising of oil in the tank and
conservator

2. Full vacuum

d. If the tap changer diverter switch enclosure is inside the main tank, it
shall be so designed that, in the event of full vacuum being applied in
the main tank, no oil can leak from diverter switch enclosure.

e. The base of the transformer shall have adequate strength to withstand


moving, shipping, handling of the transformer and supporting the
weight of the transformer on a concrete foundation in service.

f. Base structural members shall be so located that the center of gravity


shall not fall outside the points of support for 15 degrees tilt from the
horizontal, with or without oil in the transformer.

g. The main cover shall be welded. Openings in the form of manholes


or handholes with flanges or retainers shall be provided in the main
cover. Manhole shall be 60cm diameter or 40cmx60cm. The opening
covers shall be sealed with suitable gaskets. The gasket shall remain
oil and gas tight throughout the service life of the transformer and the
specified temperature conditions.

Surfaces forming part of gasketted joints shall be machine finished


and provided with gasket retainers and metal stops to ensure even
pressure and avoid overstressing the gasket. The gasket material shall
be Nitryle rubber or equivalent. The main cover design shall be such
that it will prevent the accumulation of water.

h. Core and coil assembly shall not be an integral part of the main cover.

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 9 OF 57


TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

i. Transformer tank and accessories shall be designed without pockets


where in gas may collect. Where pockets cannot be avoided, pipes
shall be provided to vent the gas into main expansion pipe. The vent
pipes shall have a minimum inside diameter of 20mm and shall be
protected against mechanical damage.

j. Provision for equalizing the main tank and OLTC shall be provided
by an equalizer pipe with valve. The equalizer pipe shall be tapped
from the pipe of main tank just before Buchholz relay or on the top
cover and connected to OLTC chamber.

4.3.2 Core

a. Core shall be manufactured from non-aging cold rolled silicon steel


laminations of high-permeability super oriented/laser-etched or
high-permeability normal oriented steels.

b. Each lamination shall be covered with insulating film. Cutting of


lamination shall be done in such a way that magnetic field is applied
in the direction of rolling.

c. The core and its mechanical parts shall be designed to withstand


forces produced during normal transportation, short-circuits and earth
quakes. The design shall avoid mechanical resonances at or near
multiples of the frequency of the network (60Hz).

d. Maximum flux density at 110% rated voltage shall be at least 10%


below saturation flux density and the core shall be designed to exhibit
linear magnetization characteristics up to 120% rated voltage.

e. The core earthing shall be brought out of the tank through insulated
bushing and shall have disconnecting link with protective cover. As a
second point of earth, yoke channel shall be grounded with similar
construction.

4.3.3 Windings

a. The minimum winding insulation requirements shall be as per 01-


TMSS-01.

b. Winding shall be Copper without microscopic burrs. Conductors shall


have rounded corners and insulated with Kraft paper or equivalent.
Clamping arrangement of windings shall not impede free circulation
of oil. Windings shall be designed to reduce out of balance forces.

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 10 OF 57


TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

4.4 Tap Changer

4.4.1 General

a. Unless otherwise specified in data schedule Tap-changer shall be


operated by an AC motor driven mechanism.

b. Unless otherwise specified, the transformer shall be equipped with an


On-Load Tap Changer located in the high voltage windings. The
tapping power at each tap shall be equal to the rated power.

c. The step voltage for on-load tap changer shall be 1.25% unless
otherwise specified in data schedule. Total number of taps and the
number of positive steps and negative steps shall be as specified in
data schedule.

d. The On-Load Tap Changer (OLTC) shall be in accordance with IEC


60214 or ANSI C57.12.10 with high speed resistor type tap changer
switch.

e. The OLTC diverter switch shall be housed in its own oil-tight vacuum
proof compartment supplied with oil from a separate section of the
main conservator tank, or from a separate conservator tank.

The diverter switch shall be capable of being withdrawn for


inspection and maintenance.

f. The OLTC shall be suitable for continuous operation in conjunction


with an automatic voltage regulating relay.

g. The OLTC diverter switch compartment shall be provided with the


following safety features:

1. Automatically self-resetting type pressure relief device with two


sets of alarm/trip contacts.

2. Oil/gas surge (pressure) relay located in the pipe leading from


diverter switch oil compartment to OLTC conservator with a set
of tripping contacts.

h. The OLTC Diverter Switch Oil compartment shall be fitted with two
filtration valves together with the facility for sampling the oil from
ground level.

i. Oil filter unit shall be provided on OLTC if specified in data


schedule.

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 11 OF 57


TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

4.4.2 OLTC Control and Indication Features

OLTC shall be provided with the following control and indication:

a. Local/Remote selector switch. When the switch is put in remote


position control shall be passed to remote tap changer panel. Alarm
contacts shall be provided when the switch is in local position.

b. A crank for emergency hand operation of the drive mechanism.

c. Facilities for electrical “raise” and “lower” operation by control


switch with intermediate off position or push buttons.

d. Mechanical tap position indictor. This shall be visible through the


window of the enclosure.

e. Non-resettable operation counter to register the accumulated number


of tap changing operations performed.

f. For parallel operation with similar transformer, if specified in the


Data Schedule.

4.4.3 OLTC Drive mechanism and Safety Features

a. Tap changer shall be driven by a motor operated mechanism


incorporating a stored energy device, which shall ensure that once a
change of tap begins, it is completed and so shall ensure that the
mechanism does not fail in an intermediate on loss of supply voltage
to motor. The motor drive control shall follow the step by step
principle to prevent runaway due to possible malfunction.

b. The emergency manual drive mechanism shall be electrically


interlocked to prevent electrical operation of the motor while the hand
crank is engaged.

c. Mechanically operated limit switches and mechanical stops shall be


provided in the driving mechanism to prevent over-travel beyond the
maximum raise and lower positions.

d. Overcurrent blocking at maximum current rating of the tap changer.

e. Electrical protection of motor and control circuits.

f. Alarm for loss of AC supply.

4.4.4 Enclosure

The control equipment and the drive mechanism shall be housed in corrosion
proof cabinet made of 2mm sheet steel with hinged door with provision for

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 12 OF 57


TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

padlocking. The enclosure shall be mounted on the transformer tank using


anti-vibration mountings. The degree of protection shall be per 01-TMSS-01.
Individual identification label on each equipment shall be provided.

4.5 Temperature Control Devices

4.5.1 Oil Temperature Indicator

a. The transformer shall be provided with dial type oil temperature


indicator (O.T.I) to indicate the top oil temperature.

b. The O.T.I. shall have a dark face dial with light markings, a light
colored indicating pointer and a hand resettable maximum indicating
pointer. The dial marking shall be 20 to 160°C with ± 0.5% accuracy.

c. Four (4) individually adjustable sets of micro switch type contacts


shall be provided for alarm and trip functions.

d. The words "Oil Temperature" shall be marked on the dial or on a


suitable nameplate mounted adjacent to the indicator.

e. O.T.I shall be mounted in outdoor control cabinet, so that its dial shall
be easily readable through a window by a person standing at the
ground level.

4.5.2 Winding Temperature Indicator

a. Each winding of the transformer shall be provided with one (1)


dedicated winding temperature indicator (W.T.I.) for indicating the
winding temperature. W.T.I sensing element shall be supplied by CTs
installed on the central phase bushing of each winding.

c. The W.T.I. shall have a dark face dial with light markings, a light
colored indicating pointer and a hand reset maximum indicating
pointer. The dial marking shall be 20 to 160°C with ± 0.5% accuracy.

d. The words “Winding Temperature” shall be marked on the dial or on


a suitable nameplate, mounted adjacent to the indicator.

e. The automatic control of fans (in one or two stages) and pumps shall
be accomplished by winding temperature indicator.

f. Four (4) individually adjustable sets of micro switch type contacts


shall be available for the control of fans/pumps, alarm and trip
functions. The contacts for the control of fans and pumps shall be
wired to available terminal points for future use.

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 13 OF 57


TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

g. W.T.I shall be mounted in outdoor control cabinet, so that its dial


shall be easily readable through a window by a person standing at the
ground level.

4.6 Outdoor Control Cabinet

4.6.1 Control cabinet shall be tank mounted using anti-vibration mountings and
accessible from finsihed ground level.

4.6.2 The cabinet shall be of the outdoor type. It shall be made from 2mm sheet
steel or 4mm thick anodized Aluminum and shall offer degree of protection
per 01-TMSS-01. It shall have a hinged door with provision for padlocking
and door switch operated interior lights. A thermostatically controlled anti-
condensation heater with overriding manual control shall be provided within
the cabinet. The cabinet shall be designed for bottom entry of the external
control and protection cables.

4.6.3 The outdoor control cabinet shall accommodate the following:

a. Oil and winding temperature indicators

b. Control, protective gear and indications for the cooling apparatus


including push buttons for manual operation of cooling system and
auto/manual selector switches for cooling equipment.

c. All terminal connections for CTs, alarm/trip contacts of accessories,


AC/DC incoming and outgoing cables, etc.

d. A gang operated switch to disconnect trip impulse emanating from


transformer mechanical trip devices. One contact of this switch shall
be wired to alarm when the switch is open.

4.6.4 All relays, switches, terminal blocks and lamps shall be identified by
permanent nameplates. Plates shall be laminated, bolted type. Adhesive
labels are not acceptable.

4.6.5 The door of the outdoor cabinet shall be provided with a suitable glass
window through which the temperature indicators can be easily observed.

4.6.6 Wiring and Capillaries

a. Electrical connection between accessories and control cabinet shall be


enclosed in metal raceways or rigid galvanized steel conduits and
safely fastened to transformer tank. Wires shall be of ample size
(subject to SEC approval). Steel armouring of cables is not
acceptable.

b. All wiring and cables shall comply with the requirements of


ANSI/NFPA 70.

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 14 OF 57


TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

c. All wires shall be minimum 1.5mm2 or equivalent, stranded copper,


rated 600/1000 volts. Current transformer wiring shall be minimum of
4mm2, and power wiring shall be sized as required. All wires shall be
moisture resistant, heat resistant and flame retardant and withstand a
minimum temperature of 90°C.

  d. All wires shall be permanently marked at each termination end with


oil resistant, heat shrinkable plastic sleeves.

e. Wires shall be terminated with hooked crimps or ring type


terminations. Termination of more than one conductor at one terminal
point is not acceptable.

f. All cable glands used for the attachment of cables shall be metallic
and not plastic.

g. All cables shall be properly bundled, clamped, or otherwise supported


and protected. Stainless steel ties with epoxy coverings, suitable to
bear the specified weather conditions shall be provided for the
exterior cablings.

h. Additional 20% spare terminals shall be provided on the terminal


blocks to accommodate future requirements.

i. Rigid pocket for storing the concerned circuit diagram inside the
cabinet shall be provided.

j. Color coding of the wires shall be as follows:

DC circuits : Grey
Alarm Circuits : Blue
CT Circuits : Yellow
Grounding : Green or Green with Yellow stripes
3-phase, 4-core AC power circuits: red, yellow, blue and black
(neutral).
2-phase, 3-core AC power circuits: red, white or yellow,
black(neutral).
1-phase, 2-core AC power circuits: red, black (neutral).

k. Terminal blocks shall be SEC approved spring loaded type and


suitable for size of wires to be terminated. If a common termination is
required between terminal blocks, preformed jumpers or
manufacturer’s own shorting device shall be used. CT circuits shall be
provided with shorting type terminal block with a disconnectable CT
shorting type terminal with ground link.

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 15 OF 57


TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

4.7 Buchholz Relay

4.7.1 General

A two stage Buchholz relay shall be provided for the main tank and located
in the pipe (with a slope of pipe not less than 1 in 12) between the
transformer and to the conservator. It shall be equipped with two contacts,
one for alarm and the other for tripping with 0.5amps, 125Vdc rating.

4.7.2. Gas Sampling Device and Test Connection

The gas release connection from the Buchholz relay shall be brought down to
a gas sampling device, which shall be accessible at ground level. Gas
sampling valve at the top shall be with an outlet approximately 3mm
diameter and shall be suitable to take rubber tube connection. The outlet shall
have a captive screwed cap A test connection from the Buchholz relay shall
be brought to the gas sampling device or may be terminated beside it.
Isolating valve shall be provided in the gas sampling and test connection
accessible at ground level.

4.7.3. The Buchholz relay shall be provided with reed switches (not mercury
switches) only. The relay shall be insensitive to vibrations and shocks with
accelerations up to 0.5g.

4.7.4. The pipes connecting the Buchholz relay shall have slide valves on the
conservator side to enable dismantling of the Buchholz relay without oil
leakage.

4.8 Pressure Relief Device

Self resetting type pressure relief device shall be provided for rapid release of over
pressure within the transformer, with oil collecting guard in order to direct or
disperse the oil only to ground level for personnel/equipment safety. The device
shall operate at a pressure less than the designed withstand pressure of the tank. The
pressure relief device shall be provided with two sets of alarm/trip contacts, rated 0.5
amps, 125 Vdc.

4.9 Outdoor Bushings (Oil/Air)

4.9.1 General

Outdoor bushings for overhead terminations shall be electrical grade wet-


processed porcelain, with oil impregnated paper insulation, brown in color, in
accordance with relevant IEC or equivalent ANSI/IEEE Standards. Bushing
shall be fitted with oil level gauge, which can be easily read from ground
level. Fittings made of steel shall be galvanized.

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 16 OF 57


TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

All outdoor bushings shall withstand a washing pressure of 3500 kPa without
permitting water ingress into the bushing turret and secondary terminal box
of the bushing CT's.

4.9.2 Creepage and ground clearances

Outdoor bushings shall be designed to have a minimum creepage distance per


01-TMSS-01. The minimum phase to ground clearances shall be as shown in
Table 1. The minimum insulation levels shall be per 01-TMSS-01.

Table - I
Nominal System Minimum Phase To Ground
voltage Clearance In Air
(kV rms) (mm)
13.8 200
33 400
34.5 400
69 720
110 1365
115 1365
132 1575
230 2260
380 3600

4.9.3 All phase bushings for system voltages 69kV and above shall have a test tap
brought out to a separate terminal. Power frequency withstand voltage of the
tap shall be minimum 2 kVac.

4.9.4 The dimensions of 69kV and 115kV bushings shall be per Figure 1.

4.9.5 Bushings for 34.5 kV and below

a. Unless otherwise specified in data schedule 34.5 kV and below phase


bushings shall be housed in a weatherproof enclosure and shall be
suitable for XLPE cable terminations onto bushings inside the
enclosure. The cable box for tertiary bushings shall be designed to
accommodate surge arresters, if specified.

b. The bushings shall have a minimum creepage distance per 01-TMSS-


01.

c. The neutral bushing shall be installed outside the enclosure.

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 17 OF 57


TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

4.10 Radiators

4.10.1 The tank shall have detachable radiators with flanged shut off valves at each
end.

4.10.2 The radiator fins shall be welded with stiffening rods (horizontally and
diagonally). In addition suitable ironwork shall be fitted to the radiator
groups to prevent vibration during operation of the transformers.

4.10.3 The design of the radiators shall be such that dust and sand cannot
accumulate and block or restrict circulation of the air.

4.10.4 Each radiator shall be provided with an air release vent and drain plug.

4.10.5 The radiators shall withstand the pressure and vacuum conditions specified
for the tank.

4.10.6 Radiator interior shall be with corrosion proof painting and outer surface
shall be either hot-dip galvanized or painted per 01-TMSS-01.

4.10.7 For shipping purposes, the radiator valves shall be furnished with a gasketted
blanking plate.

4.11 Fans

4.11.1 The fan blades shall be provided with galvanized wire mesh guards at top and
bottom with a degree of protection IP20 per IEC 60529 or equivalent. All
moving shafts and couplings shall be guarded. It shall be possible to remove
a fan unit without dismantling the radiators or the supporting structures.

4.11.2 Fans shall not over hang from coolers/radiator fins. They shall be mounted on
suitable structure members using anti-vibration mounts or mounted
independently.

4.11.3 The cooling fans and fan blades shall be made of noncorrosive material.

4.11.4 All motors shall have degree of protection per 01-TMSS-01. Fan motors shall
be mounted sufficiently above ground level for air in-take and space for
maintenance. Airflow shall be vertically upward and the direction shall be
marked on the fans.

4.12 Oil Pumps

4.12.1 Oil pumps shall be of submerged type. The design of the pumps shall be
such that the natural oil circulation through radiators is not impaired when the
oil pumps are not operating.

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 18 OF 57


TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

4.12.2 Each oil pump shall be so located and fitted with a shut off valve and bypass
arrangement such that it can be readily removed for repairs or replacement
without taking the transformer out of service.

4.12.3 A direct acting mechanical oil flow indicator shall be provided on each pump
indicating whether or not the oil is being pumped. Insufficient oil flow shall
initiate automatic change over to the standby pump along with an alarm.

4.12.4 Controls

The control equipment shall be mounted in the outdoor control cabinet and
all wiring between the outdoor control cabinet and the transformer shall be
mechanically protected.

4.13 Oil Preservation System

4.13.1 Transformer shall be provided with a conservator having two separate


compartments or two independent conservators for the main tank oil and the
OLTC diverter switch oil.

4.13.2 The conservator shall have the following accessories:

a. Drain valve for the main conservator compartment.

b. Drain valve for the OLTC diverter switch conservator compartment.

c. Shut-off valves in the pipes leading to the conservator from the main
tank and OLTC diverter switch compartment.

d. Oil level indicator.

1. Individual magnetic oil level indicators with micro switch


alarm contacts (mercury switches not acceptable) shall be
provided in the respective conservators or conservator
compartments to indicate oil level in the main tank and OLTC
diverter switch compartment respectively.
2. The indicators shall have a dark face dial with light markings,
a light colored indicating pointer. The diameter of the dial
shall be not less than 210mm. The dial markings shall show
25°C level as well as the high and low oil levels.
   3. The words "Oil Level" shall be marked on the dial or on a
suitable nameplate mounted adjacent to the indicator.
   4. Shall be provided with low and high level alarm and trip
contacts.

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 19 OF 57


TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

4.13.3 The main tank oil conservator shall be fitted with bellows or other suitable
expansion devices. The material used for these devices shall be Nitryle
Rubber or better material and shall have the same service life as of the
transformer. The failure of the membrane (puncture etc.) shall initiate an
alarm.

4.13.4 One end of the conservator shall be removable for cleaning purposes and the
drain valve shall be so situated that the conservator can be emptied
completely without dismantling.

4.14 Breather

Each section of the conservator or each conservator shall be vented to the


atmosphere through a silica gel or desiccant type, dehydrating breather with an oil
bath. The breather shall be of adequate size. The container shall be mounted
approximately 1.5m above ground level and arranged so that the tinted crystals may
be easily observed and replaced.

4.15 Drain, Filter and Sampling Valves

4.15.1 The transformer shall be fitted with the following valves:

a. One drain/filter valve.

b. One filter valve.

c. Two sampling valves.

4.15.2 The drain/filter valve shall be located such that the tank can be drained
completely. The size of the valve shall be 50mm diameter.

4.15.3 The filter valve shall be of 50mm diameter, and located at the top of the tank
diagonally opposite to the drain/filter valve.

4.15.4 Each oil drain and filter valve, shall be provided with the following SEC
standard connection fittings:

a. Coupler brass 1-1/2" N.P.T., Female plug connection rated 300 Psi

b. Dust plug for coupler with retention chain, 1-1/2" N.P.T., Brass plug
connection rated 300 Psi.

4.15.5 The sampling valves shall have 20mm diameter each and shall be located at
the bottom and top of the tank. The lower sampling valve may be integrated
with the drain/filter valve. The valves shall be of petcock type complete with
dust cover. The valves shall be readily accessible with the transformer in
service.

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 20 OF 57


TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

Drain/filter valve and lower sampling valve shall be provided at a minimum


height of one meter from the ground level, for easy access.

4.15.6 All valves shall be made of bronze or stainless steel materials. Means shall
be provided for locking valves. Each valve shall be provided with an
indicator clearly showing its position.

4.16 Inspection Facilities

4.16.1 Adequate space shall be provided for inspection, testing and carrying out
minor repairs in the interior of the transformer.

4.16.2 The covers shall have adequate handles to facilitate lifting.

4.17 Lifting, Moving and Jacking Facilities

4.17.1 Lifting Facilities

a. Suitable lifting arrangements for the balanced lifting of the completely


assembled transformers shall be provided. The bearing surfaces of the
lifting facilities shall be free from sharp edges and shall be provided with
suitable hole for guying purposes.

b. Adequate lifting lugs shall be provided for untanking the core and coil
assembly. Lifting eyes shall be provided for lifting the cover.

4.17.2 Moving Facilities

Transformers shall be with skid base or wheels as indicated in data schedule.

a. Transformer with wheels shall meet the following:

1. The base of the transformer shall be suitably designed to permit


rolling in the directions of both centerlines of the base segments.
At the base of the transformer four sets of single flanged
detachable wheels with locking arrangement shall be provided.
2. The road clearance of the wheels shall be minimum 150mm and
the wheels are set at 1500mm, 2000mm or 3000mm rail gauge in
the transverse direction and at 2000mm or 1500mm rail gauge in
the longitudinal direction. The rollers shall be capable of being
rotated through 90°. Width of rail shall be 100mm.

b. For transformers with skid base a set of anti-vibration pads as approved


by SEC shall be provided underneath the transformer tank.

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 21 OF 57


TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

4.17.3 Jacking Facilities

Jacking pads shall be provided at each of the four corners near the extreme
ends of the main tank and approximately 400mm above the lowest part of the
tank. These pads shall be designed to take the complete weight of transformer
with oil. Each pad shall be designed to take 50% of the total weight.

4.17.4 Safety Factor

Ultimate stress of lifting and moving facilities shall be designed for a safety
factor of 5.

4.18 Ladder

Ladder shall be fixed on the transformer if specified in data schedule.

4.19 Grounding

4.19.1 The transformer shall be provided with grounding provisions near the base on
two diagonally opposite sides.

4.19.2 Porcelain insulators for supporting the external grounding lead(s) to the
neutral bushing shall be mounted on suitable brackets on the transformer
tank.

4.19.3 One corner of the tertiary delta winding shall be grounded externally per
Appendix B, IEC 60076-3.

4.20 External Terminal Markings and Location

Unless otherwise specified in data schedule terminal markings and location shall be
as follows:

4.20.1 The primary (HV) bushings shall be marked H1, H2, H3. The secondary
(L.V) bushings shall be designated X1, X2, X3 and if tertiary winding is
provided, the corresponding bushing arrangement shall bear markings Y1,
Y2, Y3.

4.20.2 The neutral bushing of primary winding, if applicable, shall be marked H0,
whereas the neutral bushing of secondary winding shall be marked X0. The
neutral bushing of auto-transformer, which is common to both the primary
and secondary windings, shall be designated by the Letter 'N'.

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 22 OF 57


TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

4.20.3 The terminal markings shall be so applied, that the phase sequence of primary
winding shall be H1, H2, H3. The phase sequence of the secondary winding
shall be X1, X2, X3 and the phase sequence of the tertiary winding, if
applicable shall be Y1, Y2, Y3 respectively.

4.20.4 The H1 bushing shall be located on the right hand side of the case when
facing the primary (H.V) side. The H1, H2 and H3 terminals shall be arranged
in numerical order, reading from right to left. H0/N terminal, if applicable,
shall be located on the right of H1 terminal.

The X1 terminal shall be located on the left hand side of the case when facing
the secondary (L.V) side. The X1, X2, X3 terminals shall be arranged in
numerical order, reading from left to right. The X0 terminal shall be located
on the left of X1 terminal.

4.21 Transformer Oil

The transformer shall be filled with mineral insulating oil, which shall conform to
the latest revision of 54-TMSS-01.

4.22 Bushing Current Transformers

4.22.1 Power Transformer shall be provided with Bushing type current transformers
(BCTs). The short circuit withstand capability of BCT shall be equal to that
of power transformer.

4.22.2 Secondary leads of all BCTs shall be wired to terminal blocks with manual
shorting facility in the control cabinet. The blocks shall be marked clearly to
designate the BCT phase and tap number in use.

4.22.3 Magnetizing curve for CTs shall be furnished.

4.23 Terminations

4.23.1 The terminations may be of the following types, as applicable per Data
Schedule :

a. Oil/air terminations for overhead, bus duct or XLPE cable


connections with rated voltage 34.5kV and below.

b. Oil/oil terminations for connections to XLPE cables

c. Oil/SF6 terminations for GIS terminations

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 23 OF 57


TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

4.23.2 Cable Terminations

a. The cable entry shall be designed for bottom entry. Suitable metallic
cable glands with shrouds shall be provided for sealing all cable
entries at the enclosures.

b. Dry type cable enclosure shall be provided for rated voltage 34.5kV
and below, suitable for termination of single core, copper/aluminum
XLPE cable as specified in data schedule. Above 34.5kV, cable
termination shall be of oil filled type.

c. Flexible link shall be provided between cable and bushings in LV


cable box.

4.23.3 GIS Terminations

SF6/Oil bushings shall be provided, if specified in Data Schedule, for GIS


terminations.

4.24 Surge Arresters

If surge arresters are to be mounted on the transformer then the transformers shall be
provided with mounting brackets before and adjacent to the HV outdoor air bushing
connections.

4.25 On line analyzer

On line fault gas and moisture analyzer with alarm contacts shall be provided if
specified in data schedule

4.26 Nameplate

4.26.1 The transformer shall bear a nameplate permanently and legibly marked by
acid or laser etched in English per IEC 60076-1 or ANSI C57.12.00 along
with the following additional information:

a. SEC Purchase Order No. or Contract No. or J.O. No.

b. 53-TMSS-01

c. Volume of oil (liters)

d. Schematic diagram showing oil lines and valves

4.26.2 The nameplate material shall be stainless steel and shall be firmly affixed to
the tank by stainless steel screws or rivets.

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 24 OF 57


TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

4.26.3 Individual identification labels shall be provided for each equipment housed
inside the OLTC enclosure.

4.26.4 Stainless steel chart plate indicating oil level versus oil temperature for main
tank and OLTC shall be provided.

4.26.5 Transformer serial number shall be stamped on the body.

5.0 SHIPPING

5.1 Packing

Packing and shipping shall meet the requirements laid down in 01-TMSS-01.

5.2 Impact Recorder

5.2.1 The transformer with ONAN rating of 30MVA and above shall be provided
with two number three dimensional Impact Recorders (one mechanical and
one electronic type) and transformer below 30MVA ONAN rating shall be
provided with one number three dimensional “Mechanical Impact Recorder”
during shipment which shall remain charged until the transformer is delivered
to site.

5.2.2 The recorder shall be fixed on the top of transformer cover, shielded to
prevent damage.

5.2.3 The recorder shall have a minimum time scale of 60 days. Duration of shock
impulses recording shall be longer than 50 milli seconds.

The manufacturer shall state the safe limits of shock impact(s) with time
duration, which the transformer shall sustain without requiring any inspection
against damage and furnish necessary instructions for interpretation of
recorded data. In the event that the transformer is found to have been
subjected to excessive shock in transit, such examination as is necessary shall
be made in the presence of SEC.

5.2.4 In case Impact Recorder(s) are not installed on the transformer and/or not
been functional up to the delivery to the site, or excessive acceleration above
the manufacturer’s guaranteed value, SEC shall have the right to reject the
transformer and SEC decision is final.

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 25 OF 57


TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

6.0 TESTS

All test results shall be provided for review and approval by SEC.

6.1 Type (Design) Tests

6.1.1 All type tests prescribed in the relevant IEC or equivalent ANSI standard
shall be performed on the representative unit or on the first unit of every new
design or rating to be supplied to SEC.

6.1.2 Temperature rise test shall be performed at each stage of cooling. Test at
forced cooling rating(s) shall be carried out with 25% redundant cooling
equipment not operating.

6.1.3 In lieu of actual type tests, certified test reports of type tests performed on an
identical unit may be submitted to SEC for review and approval during
bidding stage.

6.1.4 Low leakage flux tests shall be performed per IEC 60044-6 at all taps for
class TPS CTs when the value of factor of construction Fc ≤ 1.1.

6.2 Routine (Production) Tests

All routine tests prescribed in the relevant IEC or equivalent ANSI standard shall be
performed on all transformers.

6.2.1 Zero sequence impedance measurement tests shall be conducted on all


transformers.

6.2.2 Impulse Tests

Lightning impulse test shall be carried out on all windings as a routine test on
all transformers. For orders of identical type transformers with voltage rating
lower than 230kV, this test shall be performed on at least one unit.

Switching impulse test shall be carried out on all transformers with a rated
voltage of 300kV and above.

6.2.3 Oil Leakage Test

Transformer tank and accessories shall with stand operating pressure due to
oil preservation system i.e. oil in tank and conservator, plus an additional
pressure of 35kPa for 24 hours. Oil leakage shall not be observed during this
period. Operating pressure (kPa) due to oil preservation system shall be
stated in the test report.

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 26 OF 57


TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

6.2.4 Pressure Test

Transformer tank and accessories shall withstand 25% higher than the
maximum operating pressure due to the oil preservation system i.e. oil in tank
and conservator, for 30 minutes. The permanent deflection after releasing
pressure shall not exceed 0.3%.

6.2.5 Vacuum Test

Completely assembled tank with its coolers, cable box, conservator and other
accessories shall be subjected to full vacuum for 30 minutes. The permanent
deflection, after releasing the vacuum, shall not exceed 0.3%.

6.2.6 Dissolved Gas Analysis (DGA) Test for Mineral Oil

DGA test shall be carried out before and after dielectric and heat run test.

6.2.7 Tank Vibration Measurement

Tank vibration measurement shall be carried out on one of the transformers


for each rating to be supplied to SEC. Measured vibration shall be less than
100µm.

6.3 Special Tests

6.3.1 The following special tests shall be carried out on all power transformers:

a. Insulation dissipation factor and capacitance tests for winding and


bushing.

b. Insulation resistance tests and polarization index.

c. Chopped impulse test shall be carried out on one of the 380kV SF6/Oil
bushings if specified in data schedule.

6.3.2 Special tests required per IEC/ANSI shall be carried out on one
representative transformer, if specified in Data Schedule:

6.4 On-Load Tap Changer

All routine and type tests on on-load tap changer and drive mechanism shall be
carried out in accordance with IEC 60214.

6.5 Bushings

All routine and type tests on bushings shall be carried out in accordance with IEC
60137 or ANSI/IEEE standards.

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 27 OF 57


TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

6.6 Bushing Current Transformers

6.6.1 All routine tests prescribed in the relevant IEC or equivalent ANSI
standards shall be performed.

6.6.2 The following additional tests shall be performed in accordance with IEC
60044-1/IEC60044-6 or equivalent at each tap for all CTs:

a. Turns ratio error


b. CT secondary resistance (Rct)
c. Excitation Characteristics

6.6.3 The following additional test shall be performed for CTs manufactured per
IEEE/IEC:

i. Determination of knee point voltage (Vk) for class C or K CTs


manufactured per IEEE C57.13.
ii. Determination of excitation limiting secondary voltage (Ual) for all
class TPS CTs manufactured per IEC 60044-6.

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 28 OF 57


TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 29 OF 57


TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

7.0 DATA SCHEDULE

POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA

SEC Enquiry No. Date:

SEC Purchase Order Date:


No.
or Contract No.

SEC PTS No./Project Title with J.O. No.

REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'

Power Transformer Model No./Type No. *

Type of System Grounding(Solidly


grounded, resistance grounded, other)
HV
LV
TV (if applicable)
Common Neutral (Auto Transformer)

3.0 Applicable Industry Standards *

4.0 DESIGN AND CONSTRUCTION REQUIREMENTS


4.1 Design Ambient Temperature (ºC) *

Number of Windings

Type of Cooling

Vector Group Designation

A'- SEC SPECIFIED DATA/PARAMETER.


'B'- BIDDER/SUPPLIER/VENDOR/CONTRACTOR PROPOSED DATA/PARAMETERS.
'C'- REMARKS SUPPORTING THE PROPOSED DEVIATION IN COLUMN 'B'.
(*)- DATA/PARAMETER TO BE PROVIDED/PROPOSED BY THE BIDDER/SUPPLIER/
VENDOR/CONTRACTOR IN COLUMN 'B'.

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 30 OF 57


TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

7.0 DATA SCHEDULE

POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'

4.2.1 Natural Cooling Rating


HV/LV/TV (MVA) / / / /
1st Stage Forced Cooling
HV/LV/TV (MVA) / /
/ /
2nd Stage Forced Cooling
HV/LV/TV (MVA) / / / /
Rated Voltage Transformation Ratio
HV/LV/TV (kV) / / / /

Temperature Rise Based on Ambient


Temperature Conditions Specified in 01-
TMSS-01

Winding °C *
Oil °C *
Winding maximum (hot spot)
*
Temperature (°C)

Design X/R ratio

HV *
LV *
TV *

Impedance Voltage natural cooling power


base and reference temp. of 75°C (%)
(Manufacturer shall indicate the value with
applicable tolerance)

1. At Principal Tap (Guaranteed values)


HV - LV
HV-TV (if applicable) *
LV-TV (if applicable) *

2. At Extreme Plus Tap


HV - LV *
HV-TV (if applicable) *
LV-TV (if applicable) *

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 31 OF 57


TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

7.0 DATA SCHEDULE

POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA

REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.2.1 (continued)
3. At Extreme Minus Tap
HV - LV *
HV-TV (if applicable) *
LV-TV (if applicable) *
Zero-sequence impedance on natural
cooling power base and reference temp. of
75°C (%)(Manufacturer shall indicate the
value with applicable tolerance)
1. At Principal Tap
HV - LV *
HV-TV (if applicable) *
LV-TV (if applicable) *

2. At Extreme Plus Tap


HV - LV *
HV-TV (if applicable) *
LV-TV (if applicable) *

3. At Extreme Minus Tap


HV - LV *
HV-TV (if applicable) *
LV-TV (if applicable) *

Highest Design Operating Voltage


for the tappings
continuous operation (%) 105
emergency operation (%) 110

Maximum Design Flux Density


at rated voltage (Tesla) *
at 110% rated voltage (Tesla) *
Saturation Voltage (%UN) *

No-load current when excited from LV side


as % of full load current
100% voltage (Guaranteed value) *
105% voltage *

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 32 OF 57


TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

7.0 DATA SCHEDULE

POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.2.1 (continued)
110% voltage *
No-load current harmonics
at 100% rated voltage (%)
3rd Harmonics *
5th Harmonics *
7th Harmonics *
at 110% rated voltage (%)
3rd Harmonics *
5th Harmonics *
7th Harmonics *

Basic Impulse Withstand Voltage (BIL)


HV winding (kVpeak) *
LV winding (kVpeak) *
HV neutral end (kVpeak) *
LV neutral end (kVpeak) *
Common neutral for auto
transformer winding (kVpeak) *
Tertiary winding (kVpeak) *
Tertiary neutral end (kVpeak)
*
(if applicable)

Switching Impulse Withstand Voltage


(BSL) if applicable (kVpeak) *

Separate Source Power Frequency


Withstand Voltage

HV winding (kVrms) *
LV winding (kVrms) *
HV neutral end (kVrms) *
LV neutral end (kVrms) *
Common neutral for auto
transformer winding (kVrms) *
Tertiary Winding (kVrms) *

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 33 OF 57


TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

7.0 DATA SCHEDULE

POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.2.1 (continued)
Tertiary neutral end (kVrms) *
(if applicable)

4.2.3 Requirement for parallel operation Yes/No

4.2.4 Guaranteed No-Load Losses at rated


frequency (kW)
- at 100% rated voltage *

No-Load Losses at rated frequency


- at 105% rated voltage *
- at 110% rated voltage *

Guaranteed Load Losses at 75°C at principal


tappings (kW) for Natural Cooling Rating
(ONAN)

- HV to LV *

Load Losses at 75°C at principal tapping


(kW) for Natural Cooling Rating
(ONAN)

- LV to TV at TV rated power *
- HV to TV at TV rated power *

Load Losses at 75°C at principal tappings


(kW) for Stage 1 Cooling Rating
- HV to LV *
- LV to TV at TV rated power *
- HV to TV at TV rated power *

Load Losses at 75°C at principal tappings


(kW) for Stage 2 Cooling Rating
- HV to LV *
- LV to TV at TV rated power *
- HV to TV at TV rated power *

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 34 OF 57


TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

7.0 DATA SCHEDULE

POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.2.4 (continued)

Load Losses at 75°C at tappings having


highest losses (kW)
- Tap Position No. *
- HV to LV *
- HV to TV *

Total losses of auxiliaries, pumps and fans


in service at full load (kW)
at Stage 1 cooling *
at Stage 2 cooling *

4.2.6 Maximum Symmetrical short


circuit current for which windings
are designed to thermally withstand

Duration (seconds) *
HV winding (kA) *
LV winding (kA) *
TV winding (kA) *

Maximum Asymmetrical short


circuit current for which the windings
are mechanically designed

HV winding (kApeak) *
LV winding (kApeak) *
TV winding (kApeak) *

Thermal and mechanical damage curve


per IEEE C57.109 enclosed * Yes/No

4.2.7 Temperature rise test to prove tertiary


winding rating required Yes/No

Transferred overvoltage calculation for


tertiary winding enclosed * Yes/No

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 35 OF 57


TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

7.0 DATA SCHEDULE

POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'

4.2.9 Noise level at rated voltage and frequency


- at Natural Cooling (dB)
- at Stage 1 Cooling (dB) *
- at Stage 2 Cooling (dB) *

4.3 Construction

4.3.1 Type of tank construction


Tank Cover Welded

Min. thickness of tank steel (mm)


- Sides *
- Base *
- Cover *

Min. Thickness of radiator plates (mm) *


Maximum Positive Withstand Pressure
of Tank and Radiators (kPa) *
Minimum Vacuum Withstand (milli bar) *

4.3.3 Winding Insulation


HV Winding * Uniform/
Graded
LV Winding * Uniform/
Graded
TV Winding Uniform

Winding Leakage Reactance (ohm) *

4.4 Tap Changer Type On load


Manufacturer *
Type Designation *
Number of steps
Step Voltage (%)
Tapping Range (%)
Rated Through Current (A) *
Short Circuit Current (kA) *

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 36 OF 57


TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

7.0 DATA SCHEDULE

POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.4 (continued)
Dynamic short circuit current (kApeak) *
Location (In-tank type fitted inside
transformer main tank/outside transformer
main tank or External mounted type) *

Voltage Class (kVrms) *


BIL (kVpeak) *
Type of transition impedance (high
resistance ) *

Time of transfer from one step to another


- motor-operated (seconds) *
- manually operated (Number of
revolution) *

Oil filter unit for OLTC Yes/No

Motor drive unit:


Type *
Power *
Rated Voltage (Vac)/(Vdc)
Number of phases
Control voltage (Vac or Vdc)
Space heater (Vac) 220
Heater Wattage (W) *

Provision of parallel operation alongwith


Supervisory Equipment Yes/No

Oil/Gas Surge Relay for OLTC


Manufacturer *
Type Designation *
Alarm Contact Current Rating at
125 Vdc (A) *

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 37 OF 57


TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

7.0 DATA SCHEDULE

POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.4 (continued)
Pressure Relief Device (OLTC)
Manufacturer *
Type Designation *
Number of Pressure Relief Device(s) *
Resealing Pressure (kPa) *
Number of alarm/trip contacts 2
Alarm Contact Current Rating
at 125 Vdc (A) *

4.5.1 Oil Temperature Indicator


Manufacturer *
Type Designation *
Type of Liquid Sensing Element *
Provision of maximum indicator Yes/No
Adjustment Range of Alarm and
Trip 20-160ºC
contacts (From to °C)
Adjustment Range of Forced cooling
contacts (From to °C) 20-160ºC
Contact Current Rating at 125 Vdc (A) *
Number of contacts 4

4.5.2 Winding Temperature Indicator

Manufacturer *
Type Designation *
Type of Liquid Sensing Element *
Provision of maximum indicator Yes/No
Adjustment Range of Alarm and
Trip contacts (From to °C) 20-160ºC
Adjustment Range of Forced
cooling contacts (From to °C) 20-160ºC
Contact Current Rating at
125 Vdc (A) *
Number of contacts 4

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 38 OF 57


TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

7.0 DATA SCHEDULE

POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'

4.7 Buchholz Relay


Manufacturer *
Type Designation *
Alarm/Trip Contact Current
Rating at 125 Vdc (A) *

4.8 Pressure Relief Device (Main Tank)


Manufacturer *
Type Designation *
Pressure Range for Operation *
(From to kPa)
Resealing Pressure (kPa) *
Number of alarm/trip contacts 2
Alarm Contact Current Rating at 125
Vdc (A) *

4.9 Bushings
High Voltage Bushings

Manufacturer *
Type designation *
Material *
Location (top, side, others)
Terminal take off angle
(vertical, horizontal, angle)
Number
Rated Voltage (kV)
Rated Maximum Voltage (kV)
Rated current (A) *
BIL (kVpeak) *
Switching Impulse Withstand Voltage,
if applicable (kVpeak) *
Power Frequency Dry/Wet *
Withstand Voltage (kVrms)
Creepage distance (mm) *
Cantilever strength (kN) *

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 39 OF 57


TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

7.0 DATA SCHEDULE

POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.9 (continued)
Mounting details
Hole circle diameter of the
flange (mm) *
Number of bolts *
Hole diameter (mm) *
Terminal *
Type *
Size *
No. of holes, if applicable *

Low Voltage Bushing


Manufacturer *
Type designation *
Material *
Location (top, side, others)
Terminal take off angle
(vertical, horizontal, angle)
Number
Rated Voltage (kV)
Rated Maximum Voltage (kV)
Rated current (A) *
BIL (kVpeak) *
Power Frequency Dry/Wet
Withstand Voltage (kVrms) *
Creepage distance (mm) *
Cantilever strength (kN) *
Mounting Details
Hole circle diameter of the
flange (mm) *
Number of bolts *
Hole circle diameter (mm) *
Terminal
Type *
Size *
No. of holes, if applicable *

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 40 OF 57


TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

7.0 DATA SCHEDULE

POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.9 (continued)
HV Neutral Bushing

Manufacturer *
Type designation *
Material *
Location (top, side, others)
Terminal take off angle
(vertical, horizontal, angle)
Rated Voltage (kV) *
Rated Maximum Voltage (kV) *
Rated current (A) *
BIL (kVpeak) *
Power Frequency Dry/Wet *
Withstand Voltage (kVrms)
Creepage distance (mm) *
Cantilever strength (kN) *
Mounting details
Hole circle diameter of the *
flange (mm)
Number of bolts *
Hole circle diameter (mm) *
Terminal
Type *
Size *
No. of holes, if applicable *

LV Neutral Bushing/Common Neutral


Bushing for Auto Transformer

Manufacturer *
Type designation *
Material *
Location (top, side, others)
Terminal take off angle
(vertical, horizontal, angle)
Rated Voltage (kV) *

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 41 OF 57


TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

7.0 DATA SCHEDULE

POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.9 (continued)
Rated Maximum Voltage (kV) *
Rated current (A) *
BIL (kVpeak) *
Power Frequency Dry/Wet
Withstand Voltage (kVrms) *
Creepage distance (mm) *
Cantilever strength (kN) *
Mounting details
Hole circle diameter of the
flange (mm) *
Number of bolts *
Hole circle diameter (mm) *
Terminal
Type *
Size *
No. of holes, if applicable *

Tertiary Bushing
Manufacturer *
Type designation *
Material *
Location (top, side, others)
Terminal take off angle
(vertical, horizontal, angle)
Rated Voltage (kV)
Rated Maximum Voltage (kV) *
Rated current (A) *
BIL (kVpeak) *
Power Frequency Dry/Wet *
Withstand Voltage (kVrms)
Creepage distance (mm) *
Cantilever strength (kN) *
Mounting details
Hole circle diameter of the *
flange (mm)
Number of bolts *
Hole circle diameter (mm) *

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 42 OF 57


TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

7.0 DATA SCHEDULE

POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.9 (continued)
Terminal
Type *
Size *
No. of holes, if applicable *

4.11 & Cooling Equipment


4.12

Fans
Number of cooling fans (main/spare) *
Number of cooling fan groups *
Power rating of each fan *
Supply Voltage (Vac) *
Number of phases *
Number of wires *
Total fan consumption at full load (kW) *
Degree of protection for fan blades *

Pumps
Number of oil pumps *
Type designation *
Motor rating (kW/HP) *
Supply Voltage (Vac) *
Number of phases *
Number of wires *
Degree of protection for motor pumps *
Total Power Consumption at
full load (kW) *

4.13 Conservator
4.13.2 Oil Level Indicator for the Main Tank
Manufacturer *
Type Designation *
Alarm Contact Current Rating at
125 Vdc (A) *

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 43 OF 57


TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

7.0 DATA SCHEDULE

POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.13.2 (continued)

Oil level indicator for OLTC

Manufacturer *
Type Designation *
Alarm Contact Current rating at
125 Vdc (A) *

Conservator Expansion Device Material *

4.15 Drain, Filter and Sampling Valves


(attach drawing for each type of valve)

Type & Size of Oil Drain Valve (mm) 50

Type and Size of Filtration Valve (mm) 50

Size of Oil Sampling Valve/s (mm) 20


Type & Size of Radiator Valves (mm) *

4.17 Transformer Moving Facilities

Transformer Base Type Skid/


Wheels
Wheel Details
Wheels Center to Center Distance
(1100/2100/3100mm) *

4.18 Ladder Yes/No


Cl. 4.20/
4.20 Transformer Terminal Markings IEC 60616
4.21 Transformer Mineral Oil
(Manufacturer shall fill up column “B’ of *
54-TMSS-01 Data Schedule)

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 44 OF 57


TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

7.0 DATA SCHEDULE

POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'

4.22 Bushing Current Transformer

High Voltage Bushing Current Transformers

Manufacturer *
Type Designation *
No. of CTs per phase
Continuous Thermal Current Rating Factor
Metering CT

Protection CT
Multi Ratio CTs (MRCT)
Single Ratio CTs

Rated Short Time Withstand Current


Thermal Ith (kA) *
Dynamic (kApeak) 2.6xIth

Short Time Thermal Current duration


(sec.)

Rated primary short circuit current


IPSC (kA) *
Temperature Rise (°C) *
Core No. 1 /2 /3
Purpose (Relaying or Metering) / /
Type of Protection
(Back-up/differential/Distance/REF etc.) / /
Current Ratio at specified tap / /
Accuracy Class / /
Burden (VA)/Resistive Burden-Rb (ohms) / /
Secondary Winding Resistance at 20°C, Rct
(ohms) / /

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 45 OF 57


TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

7.0 DATA SCHEDULE

POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.22 (continued)
For class TPS CTs per IEC
Rated symmetrical short circuit current
factor -KSSC */ * /*
Dimensioning parameter -K */ * /*
Excitation limiting secondary voltage
-Ual (Volts)* */ * /*
Accuracy limiting secondary exciting
current – Ial (mA) */ * /*
Secondary excitation current-Imag
at half excitation limiting secondary
voltage (mA) */ * /*

For class C or K CTs per IEEE / Class P CT


per IEC
Magnetizing current -Imag (mA) */ * /*
Knee point voltage -Vk (Volts)/
/Secondary limiting e.m.f */ * /*

Low Voltage Bushing Current


Transformers

Manufacturer *
Type Designation *
No. of CTs per phase

Continuous Thermal Current Rating Factor


Metering CT
Protection CT
Multi Ratio CTs (MRCT)
Single Ratio CTs
Rated Short Time Withstand Current
Thermal Ith (kA) *
Dynamic (kApeak) 2.6xIth

Short Time Thermal Current duration


(sec.)

Rated primary short circuit current


IPSC (kA) *
Temperature Rise (°C) *
53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 46 OF 57
TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

7.0 DATA SCHEDULE

POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.22 (continued)

Core No. 1 /2 /3
Purpose (Relaying or Metering) / /
Type of Protection
(Back-up/differential/Distance/REF etc.) / /
Current Ratio at specified tap / /
Accuracy Class / /
Burden (VA)/Resistive Burden-Rb (ohms) / /
Secondary Winding Resistance at 20°C,
Rct (ohms) / /

For class TPS CTs per IEC


Rated symmetrical short circuit current
factor -KSSC */ * /*
Dimensioning parameter -K */ * /*
Excitation limiting secondary voltage
-Ual (Volts)* */ * /*
Accuracy limiting secondary exciting
current – Ial (mA) */ * /*
Secondary excitation current-Imag
at half excitation limiting secondary
voltage (mA) */ * /*

For class C or K CTs per IEEE / Class P CT


per IEC
Magnetizing current -Imag (mA) */ * /*
Knee point voltage -Vk (Volts)/
/Secondary limiting e.m.f */ * /*

High Voltage Neutral Bushing Current


Transformers

Manufacturer *
Type Designation *
No. of CTs

Continuous Thermal Current Rating Factor


Protection CT
Multi Ratio CTs (MRCT)

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 47 OF 57


TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

7.0 DATA SCHEDULE

POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.22 (continued)
Single Ratio CTs

Rated Short Time Withstand Current


Thermal Ith (kA) *
Dynamic (kApeak) 2.6xIth

Short Time Thermal Current duration


(sec.)

Rated primary short circuit current *


IPSC (kA)

Temperature Rise (°C) *

Core No. 1 / 2
Type of Protection
(differential/ REF etc.) /
Current Ratio at specified tap
/
Accuracy Class /
Burden (VA)/Resistive Burden-Rb (ohms) /
Secondary Winding Resistance at 20°C,
Rct (ohms) /

For class TPS CTs per IEC


Rated symmetrical short circuit current
factor -KSSC */*
Dimensioning parameter -K */*
Excitation limiting secondary voltage
-Ual (Volts)* */*
Accuracy limiting secondary exciting
current – Ial (mA) */*
Secondary excitation current-Imag
at half excitation limiting secondary
voltage (mA) */*

For class C or K CTs per IEEE / Class P CT


per IEC
Magnetizing current -Imag (mA) */*

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 48 OF 57


TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

7.0 DATA SCHEDULE

POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.22 (continued)
Knee point voltage -Vk (Volts)/
/Secondary limiting e.m.f */*

Low Voltage Neutral/Common


Neutral Bushing Current Transformers
for Auto Transformer

Manufacturer *
Type Designation *
No. of CTs

Continuous Thermal Current Rating Factor


Protection CT
Multi Ratio CTs (MRCT)
Single Ratio CTs

Rated Short Time Withstand Current


Thermal Ith (kA) *
Dynamic (kApeak) 2.6xIth

Short Time Thermal Current duration


(sec.)
Rated primary short circuit current
IPSC (kA) *
Temperature Rise (°C) *

Magnetizing curve enclosed * Yes/No

Core No. 1 / 2
Type of Protection
(differential/Distance/REF etc.) /
Current Ratio at specified tap /
Accuracy Class /
Burden (VA)/Resistive Burden-Rb (ohms) /
Secondary Winding Resistance at 20°C,
Rct (ohms) /
Temperature Rise (°C) *

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 49 OF 57


TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

7.0 DATA SCHEDULE

POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.22 (continued)

For class TPS CTs per IEC


Rated symmetrical short circuit current
factor -KSSC */*
Dimensioning parameter -K */*
Excitation limiting secondary voltage
-Ual (Volts)* */*
Accuracy limiting secondary exciting
current – Ial (mA) */*
Secondary excitation current-Imag
at half excitation limiting secondary
voltage (mA) */*
For class C or K CTs per IEEE / Class P CT
per IEC
Magnetizing current -Imag (mA) */*
Knee point voltage -Vk (Volts)/
/Secondary limiting e.m.f */*

Tertiary Bushing Current Transformer


Manufacturer *
Type Designation *
No. of CTs per phase
Continuous Thermal Current Rating Factor

Protection CT
Multi Ratio CTs (MRCT)
Single Ratio CTs

Rated Short Time Withstand Current


Thermal Ith (kA) *
Dynamic (kApeak) 2.6xIth

Short Time Thermal Current duration


(sec.)

Rated primary short circuit current


IPSC (kA) *

Temperature Rise (°C) *

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 50 OF 57


TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

7.0 DATA SCHEDULE

POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.22 (continued)
Core No. 1 / 2
Type of Protection
(differential/ REF etc.) /
Current Ratio at specified tap /
Accuracy Class /
Burden (VA)/Resistive Burden-Rb (ohms) /
Secondary Winding Resistance at 20°C,
Rct (ohms) /

For class TPS CTs per IEC


Rated symmetrical short circuit current
factor -KSSC /
Dimensioning parameter -K /
Excitation limiting secondary voltage
-Ual (Volts)* /
Accuracy limiting secondary exciting
current – Ial (mA) /
Secondary excitation current-Imag
at half excitation limiting secondary
voltage (mA) */*

For class C or K CTs per IEEE / Class P CT


per IEC
Magnetizing current -Imag (mA) */*
Knee point voltage -Vk (Volts)/
/Secondary limiting e.m.f */*

Bushing Current Transformers for W.T.I


Manufacturer *
Type Designation *
Ratio
HV *
LV *
TV *
Burden (VA) *
Accuracy Class *

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 51 OF 57


TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

7.0 DATA SCHEDULE

POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.23 Terminations

Termination for HV Winding

Open Bushings (oil/Air) Yes/No


Type of conductor
Conductor material
Conductor size (mm²)

Cable Box
Type of cable
Cable size (mm²)
Material
Number of phase
Method of termination
(Pothead, stress cone,heat shrinkable)
Number of terminations
Terminal enclosure required Yes/No
Type (Air, Oil)
Incoming cable take off method
(Vertical, horizontal, Angle to
horizontal)

GIS (Oil/ SF6)


(For details refer to 32-TMSS-02
Data Schedule and attach
relevant data) Yes/No

Bus Duct
(If bus duct is required, full
details will follow order
Placement) Yes/No

Termination for LV winding

Open Bushings (oil/Air) Yes/No

Type of conductor
Conductor material
Conductor size (mm²)

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 52 OF 57


TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

7.0 DATA SCHEDULE

POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.23 (continued)
Cable Box
Type of cable
Cable size (mm²)
Material
Number of phase
Method of termination
(Pothead, stress cone,
heat shrinkable)
Number of terminations
Terminal enclosure required Yes/No

Type (Air, Oil) Yes/No


Incoming cable take off method
(Vertical, horizontal, Angle to
horizontal)

GIS (Oil/ SF6)


(For details refer to 32-TMSS-02
Data Schedule and attach relevant data) Yes/No

Bus Duct
(If bus duct is required, full details will
follow order Placement) Yes/No

Termination for Tertiary Windings


Open Bushings Yes/No
Type of conductor
Conductor material
Conductor size (mm²)

Cable Box
Type of cable
Cable size (mm²)
Material
Number of phase
Method of termination
(Pothead, stress cone,heat shrinkable)

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 53 OF 57


TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

7.0 DATA SCHEDULE

POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.23 (continued)
Number of terminations
Terminal enclosure required Yes/No
Type (Air, Oil)
Incoming cable take off method
(Vertical, horizontal, Angle to
horizontal)
GIS (Oil/ SF6)
(For details refer to 32-TMSS-02
Data Schedule and attach relevant data) Yes/No

Bus Duct
(If bus duct is required, full details will
follow order Placement) Yes/No

4.24 Surge Arresters


Provision for Surge Arresters mounting
required
(If surge arresters are required
Data Schedule of 35-TMSS-03 shall
be completed and attached by the
specifying engineer) Yes/No

4.25 On line monitoring

On line gas analyzer Yes/No

On line moisture analyzer Yes/No

AUXILIARY SUPPLIES

Voltage for Motors and Controls (Vac/Vdc)

Number of phases

Number of wires

DC Voltage for Control and 125


Protection.(Vdc)

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 54 OF 57


TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

7.0 DATA SCHEDULE

POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'

5.0 WEIGHT AND DIMENSIONS


Weight of Core and Coil Assembly (kg) *
Weight of Core (kg) *
Weight of Copper (kg) *

Weight of Oil (kg *

Total Weight (kg)


with oil *
without oil *

Shipping Weight (kg) *

Volume of Oil - Main Tank (liters) *

Volume of Oil - Conservator (liters) *

Overall Dimensions of the Assembled


Transformer

Height (mm) *
Width (mm) *
Length (mm) *

Maximum Shipping Dimension


Transformer

Height (mm) *
Width (mm) *
Length (mm) *

Shipping

Maximum permissible acceleration


during shipment in, (g)

Lateral direction *

Longitudinal direction *

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 55 OF 57


TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

7.0 DATA SCHEDULE

POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
5.0 (continued)

Vertical direction *

Maximum Guaranteed Permanent


Deflection

Under Pressure test. (mm) *

Under Vacuum test (mm) *

6.3 Special Tests


Please list special tests that shall be required

TRANSPORTATION LIMITATIONS
(If yes, specify the maximum
overall dimensions of the transformer or
attach the route or profile) *

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 56 OF 57


TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0

7.0 DATA SCHEDULE

POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA

A. ADDITIONAL TECHNICAL INFORMATION OR FEATURES TO BE FURNISHED BY


SEC:

B. ADDITIONAL SUPPLEMENTARY DATA OR FEATURES PROPOSED BY


BIDDER/VENDOR/SUPPLIER/CONTRACTOR:

B. OTHER PARTICULARS TO BE FILLED UP BY BIDDER/VENDOR/SUPPLIER/


CONTRACTOR:

Actual Manufacturer Vendor/Supplier/


of Equipment/Material Contractor

Name of the Company


Location and address

Name and Signature of


authorized
representative
and date

Official Seal/Stamp
of the Company &
Date

53TMSS01R0/KSB Date of Approval: July 29, 2006 G PAGE NO. 57 OF 57

You might also like