TRANSMISSION MATERIALS STANDARD SPECIFICATION 53-TMSS-01, Rev. 0
TABLE OF CONTENTS
1.0 SCOPE
4.1 General
4.2 Performance Characteristics and Ratings
4.3. Construction
4.4. Tap Changer
4.5 Temperature Control Devices
4.6 Outdoor Control Cabinet
4.7 Buchholz Relay
4.8 Pressure Relief Device
4.9 Outdoor Bushings (Oil/Air)
4.10 Radiator
4.11 Fans
4.12 Oil Pumps
4.13 Oil Preservation System
4.14 Breather
4.15 Drain, Filter and Sampling Valves
4.16 Inspection Facilities
4.17 Lifting, Moving and Jacking Facilities
4.18 Ladder
4.19 Grounding
4.20 External Terminal Markings and Location
4.21 Transformer Oil
4.22 Bushing Current Transformers
4.23 Terminations
4.24 Surge Arresters
4.25 On line monitoring
4.26 Nameplate
5.0 SHIPPING
5.1 Packing
5.2 Impact Recorder
6.0 TESTS
1.0 SCOPE
This SEC Transmission Material Standard Specification (TMSS) specifies the minimum
technical requirements for design, engineering, manufacture, inspection, testing and
performance of outdoor, three phase, mineral oil immersed power transformers, rated 2
MVA up to 100 MVA intended to be used in the system of the Saudi Electricity Company,
Saudi Arabia.
This TMSS does not cover Generator Transformers and associated auxiliary transformers.
This Material Standard Specification shall always be read in conjunction with SEC General
Specification No. 01-TMSS-01, titled "General Requirements for All Equipment/Materials",
which shall be considered as an integral part of this TMSS.
This TMSS shall also be read in conjunction with SEC Purchase Order or Contract
Schedules for project, as applicable.
The latest revision/amendments of the following Codes and Standards shall be applicable for
the equipment/material covered in this TMSS. In case of conflict, the vendor/manufacturer
may propose equipment/material conforming to one group of Industry Codes and Standards
quoted hereunder without jeopardizing the requirements of this TMSS.
3.4 IEC 60137 Insulated Bushings for Alternating Voltages above 1000V
3.5 IEC 60214-1 Tap Changers Part 1: Performance Requirements and Test
Methods On-Load Tap Changers
3.9 IEC 60616 Terminal and Tapping Markings for Power Transformers
3.10 IEC 60354 Loading Guide for Oil Immersed Power Transformers
3.11 ANSI C57.12.10 Requirements for Transformers, 230kV and below, 833/958
through 8333/10417 kVA, Single Phase; and 750/862 through
60 000/80 000/100 000 kVA, 3-Phase without Load Tap
Changing: and 3750/4687 through 60 000/80 000/100 000
kVA with Load Tap Changing – Safety Requirement
3.12 ANSI C57.12.70 Terminal Markings and Connections for Distribution and
Power Transformers
3.13 ANSI C57.12.90 Test Code for Liquid Immersed Distribution, Power and
Regulating Transformers and Guide for Short Circuit Testing
of Distribution and Power Transformers
3.16 ANSI C57.19.00 General Requirements and Test Procedures for Outdoor
Apparatus Bushings
3.17 IEEE C57.19.00 General Requirements and Test Procedure for Outdoor Power
Apparatus Bushings
4.1 General
4.2.1 Rating
4.2.3 Paralleling
4.2.4 Losses
The manufacturer shall state the guaranteed transformer losses as part of the
proposal for natural cooling with tolerance per IEC or IEEE standards. The
guaranteed total losses shall not exceed 0.5% (Max.) of ONAN rating. The
factory measured total loss values shall not exceed guaranteed values.
Otherwise penalty shall be imposed per contract schedules for loss values up
to 5% above guaranteed value including tolerance. If the actual losses exceed
5% above guaranteed value, SEC shall have the right to reject the
transformer.
b. The tertiary winding shall be connected internally and all ends of the
windings shall be brought outside through three fully rated bushings
for connection to external circuit. The insulation level of the bushings
shall match with that of the winding. Series current limiting reactor
shall not be used in the tertiary winding.
4.2.8 Cooling
c. The start and stop impulses for fans shall be from winding
temperature indicator. Sufficient temperature difference between start
and stop signals shall be kept and frequent start/stop operation for
small temperature differences shall be avoided.
d. Control shall be suitable for both manual and automatic operation for
each group of fans and changeover from automatic to manual control
shall be possible.
b. The design and clamping of the core and windings shall be such that
excessive vibrations shall not be transmitted from the magnetic
circuits to the tank and accessories. The maximum limit of vibration
shall be 100µm.
Inrush harmonic contents and the duration of inrush currents for worst
energization criteria shall be provided on current versus time curve. All
relevant factors such as source impedance, remanence, damping, switching
instant, existence of already energized parallel transformer shall be
considered.
4.3 Construction
4.3.1 Tank
2. Full vacuum
d. If the tap changer diverter switch enclosure is inside the main tank, it
shall be so designed that, in the event of full vacuum being applied in
the main tank, no oil can leak from diverter switch enclosure.
h. Core and coil assembly shall not be an integral part of the main cover.
j. Provision for equalizing the main tank and OLTC shall be provided
by an equalizer pipe with valve. The equalizer pipe shall be tapped
from the pipe of main tank just before Buchholz relay or on the top
cover and connected to OLTC chamber.
4.3.2 Core
e. The core earthing shall be brought out of the tank through insulated
bushing and shall have disconnecting link with protective cover. As a
second point of earth, yoke channel shall be grounded with similar
construction.
4.3.3 Windings
4.4.1 General
c. The step voltage for on-load tap changer shall be 1.25% unless
otherwise specified in data schedule. Total number of taps and the
number of positive steps and negative steps shall be as specified in
data schedule.
e. The OLTC diverter switch shall be housed in its own oil-tight vacuum
proof compartment supplied with oil from a separate section of the
main conservator tank, or from a separate conservator tank.
h. The OLTC Diverter Switch Oil compartment shall be fitted with two
filtration valves together with the facility for sampling the oil from
ground level.
4.4.4 Enclosure
The control equipment and the drive mechanism shall be housed in corrosion
proof cabinet made of 2mm sheet steel with hinged door with provision for
b. The O.T.I. shall have a dark face dial with light markings, a light
colored indicating pointer and a hand resettable maximum indicating
pointer. The dial marking shall be 20 to 160°C with ± 0.5% accuracy.
e. O.T.I shall be mounted in outdoor control cabinet, so that its dial shall
be easily readable through a window by a person standing at the
ground level.
c. The W.T.I. shall have a dark face dial with light markings, a light
colored indicating pointer and a hand reset maximum indicating
pointer. The dial marking shall be 20 to 160°C with ± 0.5% accuracy.
e. The automatic control of fans (in one or two stages) and pumps shall
be accomplished by winding temperature indicator.
4.6.1 Control cabinet shall be tank mounted using anti-vibration mountings and
accessible from finsihed ground level.
4.6.2 The cabinet shall be of the outdoor type. It shall be made from 2mm sheet
steel or 4mm thick anodized Aluminum and shall offer degree of protection
per 01-TMSS-01. It shall have a hinged door with provision for padlocking
and door switch operated interior lights. A thermostatically controlled anti-
condensation heater with overriding manual control shall be provided within
the cabinet. The cabinet shall be designed for bottom entry of the external
control and protection cables.
4.6.4 All relays, switches, terminal blocks and lamps shall be identified by
permanent nameplates. Plates shall be laminated, bolted type. Adhesive
labels are not acceptable.
4.6.5 The door of the outdoor cabinet shall be provided with a suitable glass
window through which the temperature indicators can be easily observed.
f. All cable glands used for the attachment of cables shall be metallic
and not plastic.
i. Rigid pocket for storing the concerned circuit diagram inside the
cabinet shall be provided.
DC circuits : Grey
Alarm Circuits : Blue
CT Circuits : Yellow
Grounding : Green or Green with Yellow stripes
3-phase, 4-core AC power circuits: red, yellow, blue and black
(neutral).
2-phase, 3-core AC power circuits: red, white or yellow,
black(neutral).
1-phase, 2-core AC power circuits: red, black (neutral).
4.7.1 General
A two stage Buchholz relay shall be provided for the main tank and located
in the pipe (with a slope of pipe not less than 1 in 12) between the
transformer and to the conservator. It shall be equipped with two contacts,
one for alarm and the other for tripping with 0.5amps, 125Vdc rating.
The gas release connection from the Buchholz relay shall be brought down to
a gas sampling device, which shall be accessible at ground level. Gas
sampling valve at the top shall be with an outlet approximately 3mm
diameter and shall be suitable to take rubber tube connection. The outlet shall
have a captive screwed cap A test connection from the Buchholz relay shall
be brought to the gas sampling device or may be terminated beside it.
Isolating valve shall be provided in the gas sampling and test connection
accessible at ground level.
4.7.3. The Buchholz relay shall be provided with reed switches (not mercury
switches) only. The relay shall be insensitive to vibrations and shocks with
accelerations up to 0.5g.
4.7.4. The pipes connecting the Buchholz relay shall have slide valves on the
conservator side to enable dismantling of the Buchholz relay without oil
leakage.
Self resetting type pressure relief device shall be provided for rapid release of over
pressure within the transformer, with oil collecting guard in order to direct or
disperse the oil only to ground level for personnel/equipment safety. The device
shall operate at a pressure less than the designed withstand pressure of the tank. The
pressure relief device shall be provided with two sets of alarm/trip contacts, rated 0.5
amps, 125 Vdc.
4.9.1 General
All outdoor bushings shall withstand a washing pressure of 3500 kPa without
permitting water ingress into the bushing turret and secondary terminal box
of the bushing CT's.
Table - I
Nominal System Minimum Phase To Ground
voltage Clearance In Air
(kV rms) (mm)
13.8 200
33 400
34.5 400
69 720
110 1365
115 1365
132 1575
230 2260
380 3600
4.9.3 All phase bushings for system voltages 69kV and above shall have a test tap
brought out to a separate terminal. Power frequency withstand voltage of the
tap shall be minimum 2 kVac.
4.9.4 The dimensions of 69kV and 115kV bushings shall be per Figure 1.
4.10 Radiators
4.10.1 The tank shall have detachable radiators with flanged shut off valves at each
end.
4.10.2 The radiator fins shall be welded with stiffening rods (horizontally and
diagonally). In addition suitable ironwork shall be fitted to the radiator
groups to prevent vibration during operation of the transformers.
4.10.3 The design of the radiators shall be such that dust and sand cannot
accumulate and block or restrict circulation of the air.
4.10.4 Each radiator shall be provided with an air release vent and drain plug.
4.10.5 The radiators shall withstand the pressure and vacuum conditions specified
for the tank.
4.10.6 Radiator interior shall be with corrosion proof painting and outer surface
shall be either hot-dip galvanized or painted per 01-TMSS-01.
4.10.7 For shipping purposes, the radiator valves shall be furnished with a gasketted
blanking plate.
4.11 Fans
4.11.1 The fan blades shall be provided with galvanized wire mesh guards at top and
bottom with a degree of protection IP20 per IEC 60529 or equivalent. All
moving shafts and couplings shall be guarded. It shall be possible to remove
a fan unit without dismantling the radiators or the supporting structures.
4.11.2 Fans shall not over hang from coolers/radiator fins. They shall be mounted on
suitable structure members using anti-vibration mounts or mounted
independently.
4.11.3 The cooling fans and fan blades shall be made of noncorrosive material.
4.11.4 All motors shall have degree of protection per 01-TMSS-01. Fan motors shall
be mounted sufficiently above ground level for air in-take and space for
maintenance. Airflow shall be vertically upward and the direction shall be
marked on the fans.
4.12.1 Oil pumps shall be of submerged type. The design of the pumps shall be
such that the natural oil circulation through radiators is not impaired when the
oil pumps are not operating.
4.12.2 Each oil pump shall be so located and fitted with a shut off valve and bypass
arrangement such that it can be readily removed for repairs or replacement
without taking the transformer out of service.
4.12.3 A direct acting mechanical oil flow indicator shall be provided on each pump
indicating whether or not the oil is being pumped. Insufficient oil flow shall
initiate automatic change over to the standby pump along with an alarm.
4.12.4 Controls
The control equipment shall be mounted in the outdoor control cabinet and
all wiring between the outdoor control cabinet and the transformer shall be
mechanically protected.
c. Shut-off valves in the pipes leading to the conservator from the main
tank and OLTC diverter switch compartment.
4.13.3 The main tank oil conservator shall be fitted with bellows or other suitable
expansion devices. The material used for these devices shall be Nitryle
Rubber or better material and shall have the same service life as of the
transformer. The failure of the membrane (puncture etc.) shall initiate an
alarm.
4.13.4 One end of the conservator shall be removable for cleaning purposes and the
drain valve shall be so situated that the conservator can be emptied
completely without dismantling.
4.14 Breather
4.15.2 The drain/filter valve shall be located such that the tank can be drained
completely. The size of the valve shall be 50mm diameter.
4.15.3 The filter valve shall be of 50mm diameter, and located at the top of the tank
diagonally opposite to the drain/filter valve.
4.15.4 Each oil drain and filter valve, shall be provided with the following SEC
standard connection fittings:
a. Coupler brass 1-1/2" N.P.T., Female plug connection rated 300 Psi
b. Dust plug for coupler with retention chain, 1-1/2" N.P.T., Brass plug
connection rated 300 Psi.
4.15.5 The sampling valves shall have 20mm diameter each and shall be located at
the bottom and top of the tank. The lower sampling valve may be integrated
with the drain/filter valve. The valves shall be of petcock type complete with
dust cover. The valves shall be readily accessible with the transformer in
service.
4.15.6 All valves shall be made of bronze or stainless steel materials. Means shall
be provided for locking valves. Each valve shall be provided with an
indicator clearly showing its position.
4.16.1 Adequate space shall be provided for inspection, testing and carrying out
minor repairs in the interior of the transformer.
b. Adequate lifting lugs shall be provided for untanking the core and coil
assembly. Lifting eyes shall be provided for lifting the cover.
Jacking pads shall be provided at each of the four corners near the extreme
ends of the main tank and approximately 400mm above the lowest part of the
tank. These pads shall be designed to take the complete weight of transformer
with oil. Each pad shall be designed to take 50% of the total weight.
Ultimate stress of lifting and moving facilities shall be designed for a safety
factor of 5.
4.18 Ladder
4.19 Grounding
4.19.1 The transformer shall be provided with grounding provisions near the base on
two diagonally opposite sides.
4.19.2 Porcelain insulators for supporting the external grounding lead(s) to the
neutral bushing shall be mounted on suitable brackets on the transformer
tank.
4.19.3 One corner of the tertiary delta winding shall be grounded externally per
Appendix B, IEC 60076-3.
Unless otherwise specified in data schedule terminal markings and location shall be
as follows:
4.20.1 The primary (HV) bushings shall be marked H1, H2, H3. The secondary
(L.V) bushings shall be designated X1, X2, X3 and if tertiary winding is
provided, the corresponding bushing arrangement shall bear markings Y1,
Y2, Y3.
4.20.2 The neutral bushing of primary winding, if applicable, shall be marked H0,
whereas the neutral bushing of secondary winding shall be marked X0. The
neutral bushing of auto-transformer, which is common to both the primary
and secondary windings, shall be designated by the Letter 'N'.
4.20.3 The terminal markings shall be so applied, that the phase sequence of primary
winding shall be H1, H2, H3. The phase sequence of the secondary winding
shall be X1, X2, X3 and the phase sequence of the tertiary winding, if
applicable shall be Y1, Y2, Y3 respectively.
4.20.4 The H1 bushing shall be located on the right hand side of the case when
facing the primary (H.V) side. The H1, H2 and H3 terminals shall be arranged
in numerical order, reading from right to left. H0/N terminal, if applicable,
shall be located on the right of H1 terminal.
The X1 terminal shall be located on the left hand side of the case when facing
the secondary (L.V) side. The X1, X2, X3 terminals shall be arranged in
numerical order, reading from left to right. The X0 terminal shall be located
on the left of X1 terminal.
The transformer shall be filled with mineral insulating oil, which shall conform to
the latest revision of 54-TMSS-01.
4.22.1 Power Transformer shall be provided with Bushing type current transformers
(BCTs). The short circuit withstand capability of BCT shall be equal to that
of power transformer.
4.22.2 Secondary leads of all BCTs shall be wired to terminal blocks with manual
shorting facility in the control cabinet. The blocks shall be marked clearly to
designate the BCT phase and tap number in use.
4.23 Terminations
4.23.1 The terminations may be of the following types, as applicable per Data
Schedule :
a. The cable entry shall be designed for bottom entry. Suitable metallic
cable glands with shrouds shall be provided for sealing all cable
entries at the enclosures.
b. Dry type cable enclosure shall be provided for rated voltage 34.5kV
and below, suitable for termination of single core, copper/aluminum
XLPE cable as specified in data schedule. Above 34.5kV, cable
termination shall be of oil filled type.
If surge arresters are to be mounted on the transformer then the transformers shall be
provided with mounting brackets before and adjacent to the HV outdoor air bushing
connections.
On line fault gas and moisture analyzer with alarm contacts shall be provided if
specified in data schedule
4.26 Nameplate
4.26.1 The transformer shall bear a nameplate permanently and legibly marked by
acid or laser etched in English per IEC 60076-1 or ANSI C57.12.00 along
with the following additional information:
b. 53-TMSS-01
4.26.2 The nameplate material shall be stainless steel and shall be firmly affixed to
the tank by stainless steel screws or rivets.
4.26.3 Individual identification labels shall be provided for each equipment housed
inside the OLTC enclosure.
4.26.4 Stainless steel chart plate indicating oil level versus oil temperature for main
tank and OLTC shall be provided.
5.0 SHIPPING
5.1 Packing
Packing and shipping shall meet the requirements laid down in 01-TMSS-01.
5.2.1 The transformer with ONAN rating of 30MVA and above shall be provided
with two number three dimensional Impact Recorders (one mechanical and
one electronic type) and transformer below 30MVA ONAN rating shall be
provided with one number three dimensional “Mechanical Impact Recorder”
during shipment which shall remain charged until the transformer is delivered
to site.
5.2.2 The recorder shall be fixed on the top of transformer cover, shielded to
prevent damage.
5.2.3 The recorder shall have a minimum time scale of 60 days. Duration of shock
impulses recording shall be longer than 50 milli seconds.
The manufacturer shall state the safe limits of shock impact(s) with time
duration, which the transformer shall sustain without requiring any inspection
against damage and furnish necessary instructions for interpretation of
recorded data. In the event that the transformer is found to have been
subjected to excessive shock in transit, such examination as is necessary shall
be made in the presence of SEC.
5.2.4 In case Impact Recorder(s) are not installed on the transformer and/or not
been functional up to the delivery to the site, or excessive acceleration above
the manufacturer’s guaranteed value, SEC shall have the right to reject the
transformer and SEC decision is final.
6.0 TESTS
All test results shall be provided for review and approval by SEC.
6.1.1 All type tests prescribed in the relevant IEC or equivalent ANSI standard
shall be performed on the representative unit or on the first unit of every new
design or rating to be supplied to SEC.
6.1.2 Temperature rise test shall be performed at each stage of cooling. Test at
forced cooling rating(s) shall be carried out with 25% redundant cooling
equipment not operating.
6.1.3 In lieu of actual type tests, certified test reports of type tests performed on an
identical unit may be submitted to SEC for review and approval during
bidding stage.
6.1.4 Low leakage flux tests shall be performed per IEC 60044-6 at all taps for
class TPS CTs when the value of factor of construction Fc ≤ 1.1.
All routine tests prescribed in the relevant IEC or equivalent ANSI standard shall be
performed on all transformers.
Lightning impulse test shall be carried out on all windings as a routine test on
all transformers. For orders of identical type transformers with voltage rating
lower than 230kV, this test shall be performed on at least one unit.
Switching impulse test shall be carried out on all transformers with a rated
voltage of 300kV and above.
Transformer tank and accessories shall with stand operating pressure due to
oil preservation system i.e. oil in tank and conservator, plus an additional
pressure of 35kPa for 24 hours. Oil leakage shall not be observed during this
period. Operating pressure (kPa) due to oil preservation system shall be
stated in the test report.
Transformer tank and accessories shall withstand 25% higher than the
maximum operating pressure due to the oil preservation system i.e. oil in tank
and conservator, for 30 minutes. The permanent deflection after releasing
pressure shall not exceed 0.3%.
Completely assembled tank with its coolers, cable box, conservator and other
accessories shall be subjected to full vacuum for 30 minutes. The permanent
deflection, after releasing the vacuum, shall not exceed 0.3%.
DGA test shall be carried out before and after dielectric and heat run test.
6.3.1 The following special tests shall be carried out on all power transformers:
c. Chopped impulse test shall be carried out on one of the 380kV SF6/Oil
bushings if specified in data schedule.
6.3.2 Special tests required per IEC/ANSI shall be carried out on one
representative transformer, if specified in Data Schedule:
All routine and type tests on on-load tap changer and drive mechanism shall be
carried out in accordance with IEC 60214.
6.5 Bushings
All routine and type tests on bushings shall be carried out in accordance with IEC
60137 or ANSI/IEEE standards.
6.6.1 All routine tests prescribed in the relevant IEC or equivalent ANSI
standards shall be performed.
6.6.2 The following additional tests shall be performed in accordance with IEC
60044-1/IEC60044-6 or equivalent at each tap for all CTs:
6.6.3 The following additional test shall be performed for CTs manufactured per
IEEE/IEC:
POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
Number of Windings
Type of Cooling
POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
Winding °C *
Oil °C *
Winding maximum (hot spot)
*
Temperature (°C)
HV *
LV *
TV *
POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.2.1 (continued)
3. At Extreme Minus Tap
HV - LV *
HV-TV (if applicable) *
LV-TV (if applicable) *
Zero-sequence impedance on natural
cooling power base and reference temp. of
75°C (%)(Manufacturer shall indicate the
value with applicable tolerance)
1. At Principal Tap
HV - LV *
HV-TV (if applicable) *
LV-TV (if applicable) *
POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.2.1 (continued)
110% voltage *
No-load current harmonics
at 100% rated voltage (%)
3rd Harmonics *
5th Harmonics *
7th Harmonics *
at 110% rated voltage (%)
3rd Harmonics *
5th Harmonics *
7th Harmonics *
HV winding (kVrms) *
LV winding (kVrms) *
HV neutral end (kVrms) *
LV neutral end (kVrms) *
Common neutral for auto
transformer winding (kVrms) *
Tertiary Winding (kVrms) *
POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.2.1 (continued)
Tertiary neutral end (kVrms) *
(if applicable)
- HV to LV *
- LV to TV at TV rated power *
- HV to TV at TV rated power *
POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.2.4 (continued)
Duration (seconds) *
HV winding (kA) *
LV winding (kA) *
TV winding (kA) *
HV winding (kApeak) *
LV winding (kApeak) *
TV winding (kApeak) *
POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.3 Construction
POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.4 (continued)
Dynamic short circuit current (kApeak) *
Location (In-tank type fitted inside
transformer main tank/outside transformer
main tank or External mounted type) *
POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.4 (continued)
Pressure Relief Device (OLTC)
Manufacturer *
Type Designation *
Number of Pressure Relief Device(s) *
Resealing Pressure (kPa) *
Number of alarm/trip contacts 2
Alarm Contact Current Rating
at 125 Vdc (A) *
Manufacturer *
Type Designation *
Type of Liquid Sensing Element *
Provision of maximum indicator Yes/No
Adjustment Range of Alarm and
Trip contacts (From to °C) 20-160ºC
Adjustment Range of Forced
cooling contacts (From to °C) 20-160ºC
Contact Current Rating at
125 Vdc (A) *
Number of contacts 4
POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.9 Bushings
High Voltage Bushings
Manufacturer *
Type designation *
Material *
Location (top, side, others)
Terminal take off angle
(vertical, horizontal, angle)
Number
Rated Voltage (kV)
Rated Maximum Voltage (kV)
Rated current (A) *
BIL (kVpeak) *
Switching Impulse Withstand Voltage,
if applicable (kVpeak) *
Power Frequency Dry/Wet *
Withstand Voltage (kVrms)
Creepage distance (mm) *
Cantilever strength (kN) *
POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.9 (continued)
Mounting details
Hole circle diameter of the
flange (mm) *
Number of bolts *
Hole diameter (mm) *
Terminal *
Type *
Size *
No. of holes, if applicable *
POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.9 (continued)
HV Neutral Bushing
Manufacturer *
Type designation *
Material *
Location (top, side, others)
Terminal take off angle
(vertical, horizontal, angle)
Rated Voltage (kV) *
Rated Maximum Voltage (kV) *
Rated current (A) *
BIL (kVpeak) *
Power Frequency Dry/Wet *
Withstand Voltage (kVrms)
Creepage distance (mm) *
Cantilever strength (kN) *
Mounting details
Hole circle diameter of the *
flange (mm)
Number of bolts *
Hole circle diameter (mm) *
Terminal
Type *
Size *
No. of holes, if applicable *
Manufacturer *
Type designation *
Material *
Location (top, side, others)
Terminal take off angle
(vertical, horizontal, angle)
Rated Voltage (kV) *
POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.9 (continued)
Rated Maximum Voltage (kV) *
Rated current (A) *
BIL (kVpeak) *
Power Frequency Dry/Wet
Withstand Voltage (kVrms) *
Creepage distance (mm) *
Cantilever strength (kN) *
Mounting details
Hole circle diameter of the
flange (mm) *
Number of bolts *
Hole circle diameter (mm) *
Terminal
Type *
Size *
No. of holes, if applicable *
Tertiary Bushing
Manufacturer *
Type designation *
Material *
Location (top, side, others)
Terminal take off angle
(vertical, horizontal, angle)
Rated Voltage (kV)
Rated Maximum Voltage (kV) *
Rated current (A) *
BIL (kVpeak) *
Power Frequency Dry/Wet *
Withstand Voltage (kVrms)
Creepage distance (mm) *
Cantilever strength (kN) *
Mounting details
Hole circle diameter of the *
flange (mm)
Number of bolts *
Hole circle diameter (mm) *
POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.9 (continued)
Terminal
Type *
Size *
No. of holes, if applicable *
Fans
Number of cooling fans (main/spare) *
Number of cooling fan groups *
Power rating of each fan *
Supply Voltage (Vac) *
Number of phases *
Number of wires *
Total fan consumption at full load (kW) *
Degree of protection for fan blades *
Pumps
Number of oil pumps *
Type designation *
Motor rating (kW/HP) *
Supply Voltage (Vac) *
Number of phases *
Number of wires *
Degree of protection for motor pumps *
Total Power Consumption at
full load (kW) *
4.13 Conservator
4.13.2 Oil Level Indicator for the Main Tank
Manufacturer *
Type Designation *
Alarm Contact Current Rating at
125 Vdc (A) *
POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.13.2 (continued)
Manufacturer *
Type Designation *
Alarm Contact Current rating at
125 Vdc (A) *
POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
Manufacturer *
Type Designation *
No. of CTs per phase
Continuous Thermal Current Rating Factor
Metering CT
Protection CT
Multi Ratio CTs (MRCT)
Single Ratio CTs
POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.22 (continued)
For class TPS CTs per IEC
Rated symmetrical short circuit current
factor -KSSC */ * /*
Dimensioning parameter -K */ * /*
Excitation limiting secondary voltage
-Ual (Volts)* */ * /*
Accuracy limiting secondary exciting
current – Ial (mA) */ * /*
Secondary excitation current-Imag
at half excitation limiting secondary
voltage (mA) */ * /*
Manufacturer *
Type Designation *
No. of CTs per phase
POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.22 (continued)
Core No. 1 /2 /3
Purpose (Relaying or Metering) / /
Type of Protection
(Back-up/differential/Distance/REF etc.) / /
Current Ratio at specified tap / /
Accuracy Class / /
Burden (VA)/Resistive Burden-Rb (ohms) / /
Secondary Winding Resistance at 20°C,
Rct (ohms) / /
Manufacturer *
Type Designation *
No. of CTs
POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.22 (continued)
Single Ratio CTs
Core No. 1 / 2
Type of Protection
(differential/ REF etc.) /
Current Ratio at specified tap
/
Accuracy Class /
Burden (VA)/Resistive Burden-Rb (ohms) /
Secondary Winding Resistance at 20°C,
Rct (ohms) /
POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.22 (continued)
Knee point voltage -Vk (Volts)/
/Secondary limiting e.m.f */*
Manufacturer *
Type Designation *
No. of CTs
Core No. 1 / 2
Type of Protection
(differential/Distance/REF etc.) /
Current Ratio at specified tap /
Accuracy Class /
Burden (VA)/Resistive Burden-Rb (ohms) /
Secondary Winding Resistance at 20°C,
Rct (ohms) /
Temperature Rise (°C) *
POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.22 (continued)
Protection CT
Multi Ratio CTs (MRCT)
Single Ratio CTs
POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.22 (continued)
Core No. 1 / 2
Type of Protection
(differential/ REF etc.) /
Current Ratio at specified tap /
Accuracy Class /
Burden (VA)/Resistive Burden-Rb (ohms) /
Secondary Winding Resistance at 20°C,
Rct (ohms) /
POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.23 Terminations
Cable Box
Type of cable
Cable size (mm²)
Material
Number of phase
Method of termination
(Pothead, stress cone,heat shrinkable)
Number of terminations
Terminal enclosure required Yes/No
Type (Air, Oil)
Incoming cable take off method
(Vertical, horizontal, Angle to
horizontal)
Bus Duct
(If bus duct is required, full
details will follow order
Placement) Yes/No
Type of conductor
Conductor material
Conductor size (mm²)
POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.23 (continued)
Cable Box
Type of cable
Cable size (mm²)
Material
Number of phase
Method of termination
(Pothead, stress cone,
heat shrinkable)
Number of terminations
Terminal enclosure required Yes/No
Bus Duct
(If bus duct is required, full details will
follow order Placement) Yes/No
Cable Box
Type of cable
Cable size (mm²)
Material
Number of phase
Method of termination
(Pothead, stress cone,heat shrinkable)
POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
4.23 (continued)
Number of terminations
Terminal enclosure required Yes/No
Type (Air, Oil)
Incoming cable take off method
(Vertical, horizontal, Angle to
horizontal)
GIS (Oil/ SF6)
(For details refer to 32-TMSS-02
Data Schedule and attach relevant data) Yes/No
Bus Duct
(If bus duct is required, full details will
follow order Placement) Yes/No
AUXILIARY SUPPLIES
Number of phases
Number of wires
POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
Height (mm) *
Width (mm) *
Length (mm) *
Height (mm) *
Width (mm) *
Length (mm) *
Shipping
Lateral direction *
Longitudinal direction *
POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
5.0 (continued)
Vertical direction *
TRANSPORTATION LIMITATIONS
(If yes, specify the maximum
overall dimensions of the transformer or
attach the route or profile) *
POWER TRANSFORMERS,
RATED 2 MVA UP TO 100 MVA
Official Seal/Stamp
of the Company &
Date