Certificate of Calibration
Fluke Nederland B.V.

Certificate Number: SA01115965 Date of Calibration: 25 Nov 2022


Receive Condition: IN TOLERANCE Date of Recalibration: 25 Nov 2023
Return Condition: IN TOLERANCE Place of Calibration: Eindhoven
Manufacturer: FLUKE NETWORKS Temperature within: (23.0 ± 3) °C
Model: DSX-5000 INTL Humidity within: (45 ± 20) %rh
Serial Number: 20300207
Description: 1 GHZ DSX CABLE ANALYZER
Procedure: Manual Procedure

Customer: A-LAN TECHNOLOGIE SP. Z O.O. SP. K


KRAKÓW
Customer Asset ID: -
RMA Number: 606296598

All measurements are traceable to national and/or international standards or have been derived by approved ratio
techniques. When possible standards used for this calibration are ISO/IEC 17025 accredited calibrated.

This calibration is performed by a DEKRA certified lab for ISO 9001. This certificate may not be reproduced other than in
full. Calibration certificates without signatures, either electronic or handwritten, are not valid.

Comments:

Issue Date: 25 Nov 2022


F8BBB8F025A1ADD4ACCE40F8BBB8F
E2AAA2E038E8703165BC60E2AAA2E
AAC1AEAFE53DDF1B6A90FFD334A36 Electronically signed
F40D07A0E2F0A1BFA5E9BEE03F0BE
A10675A061343431450066C01D4BE
B222A2B07517AD450682F8A8F3467 Authorized By
F0EEE0F0BB42A43E2083B98EF249A
88888880880080080808880800088 K. Jeevanandam

Fluke Nederland B.V. E-mail Telephone Rev 221123

Brainport Industries Campus 1, 5657 BX, Eindhoven service.nl@fluke.com +31 40 267 5300 Page 1 of 5
Certificate of Calibration

Certificate Number: SA01115965

Remarks

- The calibration status found in this certificate on the top of each results page must be interpreted as:

As Found : Data collected before the unit was adjusted and / or repaired
As Left : Data collected after the unit has been adjusted and / or repaired
Found / Left : Data collected without any adjustment and / or repair performed

- The calibration interval (due date) is the responsibility of the end user.

- According to the European norm 'Operation of electrical installations' NEN-EN 50110-1 release 2013 and the Dutch norm
NEN 3140 release 2015 paragraph 5.102.12 through 5.102.16, a safety test is not required. Therefore not performed.

- Temperature conversions (if applicable) are performed according to ISO/IEC 60584:2013 for thermocouples, and ISO/IEC
60751:2022 for resistance temperature devices.

Standards and test-equipment used

Inventory No Model Serial No

WP2467 DSX-CALVERST E000069

en_US Page 2 of 5
DSX Cable Analyzer
Found-Left Report
Model DSX-5000 CAT 6A/CLASS Fa 1000MHz Copper Module
Serial Number 20300207 Test date 25-Nov-22
Page 1 of 3
NEXT
NEXT Artifact SN 3386461
4
3.5
3
2.5
(dB)

2
1.5
1
0.5
0
0 100 200 300 400 500 600 700 800 900 1000 1100
Frequency (MHz)

Pass Worst margin: 0.410 at 1 MHz in pair 36-12. Worst accuracy at each frequency shown.

CDNEXT
CDNEXT Artifact SN 3386449
4
3.5
3
2.5
(dB)

2
1.5
1
0.5
0
0 100 200 300 400 500 600 700 800 900 1000 1100
Frequency (MHz)

Pass Worst margin: 0.220 at 31.25 MHz in pair 45-78. Worst accuracy at each frequency shown.

CMRL
CMDMRL Artifact SN 3386324
3.5
3.0
2.5
2.0
(dB)

1.5
1.0
0.5
0.0
0 100 200 300 400 500 600 700 800 900
Frequency (MHz)

Pass Worst margin: 0.400 at 797 MHz in pair 45. Worst accuracy at each frequency shown.
Measured difference of DSX and reference laboratory equipment added to measurement accuracy of reference laboratory equipment.
Worst accuracy at each frequency shown.
Corresponding measurement accuracy requirement for nominally compliant Level IV or Level 2G/VI field tester.
DSX Cable Analyzer
Found-Left Report
Model DSX-5000 CAT 6A/CLASS Fa 1000MHz Copper Module
Serial Number 20300207 Test date 25-Nov-22
Page 2 of 3
RL
CMDMRL Artifact SN 3386324
3.5
3
2.5
2
(dB)

1.5
1
0.5
0
0 100 200 300 400 500 600 700 800 900 1000 1100
Frequency (MHz)

Pass Worst margin: 0.210 at 916 MHz in pair 45. Worst accuracy at each frequency shown.

TCL
TCL Artifact SN 3386457
3.0
2.5
2.0
(dB)

1.5
1.0
0.5
0.0
0 100 200 300 400 500 600 700 800 900 1000 1100
Frequency (MHz)

Pass Worst margin: 0.550 at 3.88 MHz in pair 45. Worst accuracy at each frequency shown.

IL
ILFEXT Artifact SN 3386158
3.5
3.0
2.5
2.0
(dB)

1.5
1.0
0.5
0.0
0 100 200 300 400 500 600 700 800 900 1000 1100
Frequency (MHz)

Pass Worst margin: 0.660 at 2 MHz in pair 36. Worst accuracy at each frequency shown.

Measured difference of DSX and reference laboratory equipment added to measurement accuracy of reference laboratory equipment.
Worst accuracy at each frequency shown.
Corresponding measurement accuracy requirement for nominally compliant Level IV or Level 2G/VI field tester.
DSX Cable Analyzer
Found-Left Report
Model DSX-5000 CAT 6A/CLASS Fa 1000MHz Copper Module
Serial Number 20300207 Test date 25-Nov-22

FEXT Page 3 of 3
ILFEXT Artifact SN 3386158
3.5
1.2
3.01
2.5
0.8
2.0
(dB)

0.6
1.5
0.4
1.0
0.2
0.5
0.00
0
898.8 100 200
899 300 400
899.2 500 899.4 600 700899.6 800 900
899.8 1000 1100
900
Frequency (MHz)

Pass Worst margin: 0.260 at 57.25 MHz in pair 12-36. Worst accuracy at each frequency shown.

Measured difference of DSX and reference laboratory equipment added to measurement accuracy of reference laboratory equipment.
Worst accuracy at each frequency shown.
Corresponding measurement accuracy requirement for nominally compliant Level IV or Level 2G/VI field tester.

Loop Resistance Loop Resistance Artifact SN 3386276


Measured Expected Limit
Resistance on pair 12 0.12 0.00 0.80 Pass
Resistance on pair 36 49.95 49.80 0.60 Pass
Resistance on pair 45 99.99 99.80 1.60 Pass
Resistance on pair 78 453.12 453.00 4.00 Pass

Resistance imbalance Resistance Unbalance Artifact SN 3386085


Measured Expected Limit
Resistance on pair 12 0.19 0.00 0.80 Pass
Resistance on pair 36 25.07 24.90 0.90 Pass
Resistance on pair 45 12.25 12.13 0.90 Pass
Resistance on pair 78 24.21 24.05 0.90 Pass
Resistance imbalance on pair 12 0.00 0.00 0.05 Pass
Resistance imbalance on pair 36 0.01 0.00 0.13 Pass
Resistance imbalance on pair 45 0.32 0.32 0.06 Pass
Resistance imbalance on pair 78 0.85 0.85 0.12 Pass

DSX-8000 only: M_IL and M_FEXT measurements validate the ability of the DSX-8000 to make measurements with DSX-5000
adapters.
M IL Not applicable M_ILFEXT Artifact SN -

M FEXT Not applicable M_ILFEXT Artifact SN -

Test Program TFSTest v2.5.7025


DSX Report Form v3.05 18-May-2017
CallSheetUID:1C49EB68-44C7-40DE-A0ED-F50EC4EC9E91

Certificate of Calibration
Fluke Nederland B.V.

Certificate Number: SA01115965 Date of Calibration: 25 Nov 2022


Receive Condition: IN TOLERANCE Date of Recalibration: 25 Nov 2023
Return Condition: IN TOLERANCE Place of Calibration: Eindhoven
Manufacturer: FLUKE NETWORKS Temperature within: (23.0 ± 3) °C
Model: DSX-5000 INTL Humidity within: (45 ± 20) %rh
Serial Number: 20300207
Description: 1 GHZ DSX CABLE ANALYZER
Procedure: Manual Procedure

Customer: A-LAN TECHNOLOGIE SP. Z O.O. SP. K


KRAKÓW
Customer Asset ID: -
RMA Number: 606296598

All measurements are traceable to national and/or international standards or have been derived by approved ratio
techniques. When possible standards used for this calibration are ISO/IEC 17025 accredited calibrated.

This calibration is performed by a DEKRA certified lab for ISO 9001. This certificate may not be reproduced other than in
full. Calibration certificates without signatures, either electronic or handwritten, are not valid.

Comments:

Issue Date: 25 Nov 2022


F8BBB8F025A1ADD4ACCE40F8BBB8F
E2AAA2E038E8703165BC60E2AAA2E
AAC1AEAFE53DDF1B6A90FFD334A36 Electronically signed
F40D07A0E2F0A1BFA5E9BEE03F0BE
A10675A061343431450066C01D4BE
B222A2B07517AD450682F8A8F3467 Authorized By
F0EEE0F0BB42A43E2083B98EF249A
88888880880080080808880800088 K. Jeevanandam

Fluke Nederland B.V. E-mail Telephone Rev 221123

Brainport Industries Campus 1, 5657 BX, Eindhoven service.nl@fluke.com +31 40 267 5300 Page 1 of 5
Certificate of Calibration

Certificate Number: SA01115965

Remarks

- The calibration status found in this certificate on the top of each results page must be interpreted as:

As Found : Data collected before the unit was adjusted and / or repaired
As Left : Data collected after the unit has been adjusted and / or repaired
Found / Left : Data collected without any adjustment and / or repair performed

- The calibration interval (due date) is the responsibility of the end user.

- According to the European norm 'Operation of electrical installations' NEN-EN 50110-1 release 2013 and the Dutch norm
NEN 3140 release 2015 paragraph 5.102.12 through 5.102.16, a safety test is not required. Therefore not performed.

- Temperature conversions (if applicable) are performed according to ISO/IEC 60584:2013 for thermocouples, and ISO/IEC
60751:2022 for resistance temperature devices.

Standards and test-equipment used

Inventory No Model Serial No

WP2467 DSX-CALVERST E000069

en_US Page 2 of 5
DSX Cable Analyzer
Found-Left Report
Model DSX-5000 CAT 6A/CLASS Fa 1000MHz Copper Module
Serial Number 20300207 Test date 25-Nov-22
Page 1 of 3
NEXT
NEXT Artifact SN 3386461
4
3.5
3
2.5
(dB)

2
1.5
1
0.5
0
0 100 200 300 400 500 600 700 800 900 1000 1100
Frequency (MHz)

Pass Worst margin: 0.410 at 1 MHz in pair 36-12. Worst accuracy at each frequency shown.

CDNEXT
CDNEXT Artifact SN 3386449
4
3.5
3
2.5
(dB)

2
1.5
1
0.5
0
0 100 200 300 400 500 600 700 800 900 1000 1100
Frequency (MHz)

Pass Worst margin: 0.220 at 31.25 MHz in pair 45-78. Worst accuracy at each frequency shown.

CMRL
CMDMRL Artifact SN 3386324
3.5
3.0
2.5
2.0
(dB)

1.5
1.0
0.5
0.0
0 100 200 300 400 500 600 700 800 900
Frequency (MHz)

Pass Worst margin: 0.400 at 797 MHz in pair 45. Worst accuracy at each frequency shown.
Measured difference of DSX and reference laboratory equipment added to measurement accuracy of reference laboratory equipment.
Worst accuracy at each frequency shown.
Corresponding measurement accuracy requirement for nominally compliant Level IV or Level 2G/VI field tester.
DSX Cable Analyzer
Found-Left Report
Model DSX-5000 CAT 6A/CLASS Fa 1000MHz Copper Module
Serial Number 20300207 Test date 25-Nov-22
Page 2 of 3
RL
CMDMRL Artifact SN 3386324
3.5
3
2.5
2
(dB)

1.5
1
0.5
0
0 100 200 300 400 500 600 700 800 900 1000 1100
Frequency (MHz)

Pass Worst margin: 0.210 at 916 MHz in pair 45. Worst accuracy at each frequency shown.

TCL
TCL Artifact SN 3386457
3.0
2.5
2.0
(dB)

1.5
1.0
0.5
0.0
0 100 200 300 400 500 600 700 800 900 1000 1100
Frequency (MHz)

Pass Worst margin: 0.550 at 3.88 MHz in pair 45. Worst accuracy at each frequency shown.

IL
ILFEXT Artifact SN 3386158
3.5
3.0
2.5
2.0
(dB)

1.5
1.0
0.5
0.0
0 100 200 300 400 500 600 700 800 900 1000 1100
Frequency (MHz)

Pass Worst margin: 0.660 at 2 MHz in pair 36. Worst accuracy at each frequency shown.

Measured difference of DSX and reference laboratory equipment added to measurement accuracy of reference laboratory equipment.
Worst accuracy at each frequency shown.
Corresponding measurement accuracy requirement for nominally compliant Level IV or Level 2G/VI field tester.
DSX Cable Analyzer
Found-Left Report
Model DSX-5000 CAT 6A/CLASS Fa 1000MHz Copper Module
Serial Number 20300207 Test date 25-Nov-22

FEXT Page 3 of 3
ILFEXT Artifact SN 3386158
3.5
1.2
3.01
2.5
0.8
2.0
(dB)

0.6
1.5
0.4
1.0
0.2
0.5
0.00
0
898.8 100 200
899 300 400
899.2 500 899.4 600 700899.6 800 900
899.8 1000 1100
900
Frequency (MHz)

Pass Worst margin: 0.260 at 57.25 MHz in pair 12-36. Worst accuracy at each frequency shown.

Measured difference of DSX and reference laboratory equipment added to measurement accuracy of reference laboratory equipment.
Worst accuracy at each frequency shown.
Corresponding measurement accuracy requirement for nominally compliant Level IV or Level 2G/VI field tester.

Loop Resistance Loop Resistance Artifact SN 3386276


Measured Expected Limit
Resistance on pair 12 0.12 0.00 0.80 Pass
Resistance on pair 36 49.95 49.80 0.60 Pass
Resistance on pair 45 99.99 99.80 1.60 Pass
Resistance on pair 78 453.12 453.00 4.00 Pass

Resistance imbalance Resistance Unbalance Artifact SN 3386085


Measured Expected Limit
Resistance on pair 12 0.19 0.00 0.80 Pass
Resistance on pair 36 25.07 24.90 0.90 Pass
Resistance on pair 45 12.25 12.13 0.90 Pass
Resistance on pair 78 24.21 24.05 0.90 Pass
Resistance imbalance on pair 12 0.00 0.00 0.05 Pass
Resistance imbalance on pair 36 0.01 0.00 0.13 Pass
Resistance imbalance on pair 45 0.32 0.32 0.06 Pass
Resistance imbalance on pair 78 0.85 0.85 0.12 Pass

DSX-8000 only: M_IL and M_FEXT measurements validate the ability of the DSX-8000 to make measurements with DSX-5000
adapters.
M IL Not applicable M_ILFEXT Artifact SN -

M FEXT Not applicable M_ILFEXT Artifact SN -

Test Program TFSTest v2.5.7025