Fluke DSX 5000
Fluke DSX 5000
Fluke DSX 5000
Certificate of Calibration
Fluke Nederland B.V.
All measurements are traceable to national and/or international standards or have been derived by approved ratio
techniques. When possible standards used for this calibration are ISO/IEC 17025 accredited calibrated.
This calibration is performed by a DEKRA certified lab for ISO 9001. This certificate may not be reproduced other than in
full. Calibration certificates without signatures, either electronic or handwritten, are not valid.
Comments:
Brainport Industries Campus 1, 5657 BX, Eindhoven service.nl@fluke.com +31 40 267 5300 Page 1 of 5
Certificate of Calibration
Remarks
- The calibration status found in this certificate on the top of each results page must be interpreted as:
As Found : Data collected before the unit was adjusted and / or repaired
As Left : Data collected after the unit has been adjusted and / or repaired
Found / Left : Data collected without any adjustment and / or repair performed
- The calibration interval (due date) is the responsibility of the end user.
- According to the European norm 'Operation of electrical installations' NEN-EN 50110-1 release 2013 and the Dutch norm
NEN 3140 release 2015 paragraph 5.102.12 through 5.102.16, a safety test is not required. Therefore not performed.
- Temperature conversions (if applicable) are performed according to ISO/IEC 60584:2013 for thermocouples, and ISO/IEC
60751:2022 for resistance temperature devices.
en_US Page 2 of 5
DSX Cable Analyzer
Found-Left Report
Model DSX-5000 CAT 6A/CLASS Fa 1000MHz Copper Module
Serial Number 20300207 Test date 25-Nov-22
Page 1 of 3
NEXT
NEXT Artifact SN 3386461
4
3.5
3
2.5
(dB)
2
1.5
1
0.5
0
0 100 200 300 400 500 600 700 800 900 1000 1100
Frequency (MHz)
Pass Worst margin: 0.410 at 1 MHz in pair 36-12. Worst accuracy at each frequency shown.
CDNEXT
CDNEXT Artifact SN 3386449
4
3.5
3
2.5
(dB)
2
1.5
1
0.5
0
0 100 200 300 400 500 600 700 800 900 1000 1100
Frequency (MHz)
Pass Worst margin: 0.220 at 31.25 MHz in pair 45-78. Worst accuracy at each frequency shown.
CMRL
CMDMRL Artifact SN 3386324
3.5
3.0
2.5
2.0
(dB)
1.5
1.0
0.5
0.0
0 100 200 300 400 500 600 700 800 900
Frequency (MHz)
Pass Worst margin: 0.400 at 797 MHz in pair 45. Worst accuracy at each frequency shown.
Measured difference of DSX and reference laboratory equipment added to measurement accuracy of reference laboratory equipment.
Worst accuracy at each frequency shown.
Corresponding measurement accuracy requirement for nominally compliant Level IV or Level 2G/VI field tester.
DSX Cable Analyzer
Found-Left Report
Model DSX-5000 CAT 6A/CLASS Fa 1000MHz Copper Module
Serial Number 20300207 Test date 25-Nov-22
Page 2 of 3
RL
CMDMRL Artifact SN 3386324
3.5
3
2.5
2
(dB)
1.5
1
0.5
0
0 100 200 300 400 500 600 700 800 900 1000 1100
Frequency (MHz)
Pass Worst margin: 0.210 at 916 MHz in pair 45. Worst accuracy at each frequency shown.
TCL
TCL Artifact SN 3386457
3.0
2.5
2.0
(dB)
1.5
1.0
0.5
0.0
0 100 200 300 400 500 600 700 800 900 1000 1100
Frequency (MHz)
Pass Worst margin: 0.550 at 3.88 MHz in pair 45. Worst accuracy at each frequency shown.
IL
ILFEXT Artifact SN 3386158
3.5
3.0
2.5
2.0
(dB)
1.5
1.0
0.5
0.0
0 100 200 300 400 500 600 700 800 900 1000 1100
Frequency (MHz)
Pass Worst margin: 0.660 at 2 MHz in pair 36. Worst accuracy at each frequency shown.
Measured difference of DSX and reference laboratory equipment added to measurement accuracy of reference laboratory equipment.
Worst accuracy at each frequency shown.
Corresponding measurement accuracy requirement for nominally compliant Level IV or Level 2G/VI field tester.
DSX Cable Analyzer
Found-Left Report
Model DSX-5000 CAT 6A/CLASS Fa 1000MHz Copper Module
Serial Number 20300207 Test date 25-Nov-22
FEXT Page 3 of 3
ILFEXT Artifact SN 3386158
3.5
1.2
3.01
2.5
0.8
2.0
(dB)
0.6
1.5
0.4
1.0
0.2
0.5
0.00
0
898.8 100 200
899 300 400
899.2 500 899.4 600 700899.6 800 900
899.8 1000 1100
900
Frequency (MHz)
Pass Worst margin: 0.260 at 57.25 MHz in pair 12-36. Worst accuracy at each frequency shown.
Measured difference of DSX and reference laboratory equipment added to measurement accuracy of reference laboratory equipment.
Worst accuracy at each frequency shown.
Corresponding measurement accuracy requirement for nominally compliant Level IV or Level 2G/VI field tester.
DSX-8000 only: M_IL and M_FEXT measurements validate the ability of the DSX-8000 to make measurements with DSX-5000
adapters.
M IL Not applicable M_ILFEXT Artifact SN -
Certificate of Calibration
Fluke Nederland B.V.
All measurements are traceable to national and/or international standards or have been derived by approved ratio
techniques. When possible standards used for this calibration are ISO/IEC 17025 accredited calibrated.
This calibration is performed by a DEKRA certified lab for ISO 9001. This certificate may not be reproduced other than in
full. Calibration certificates without signatures, either electronic or handwritten, are not valid.
Comments:
Brainport Industries Campus 1, 5657 BX, Eindhoven service.nl@fluke.com +31 40 267 5300 Page 1 of 5
Certificate of Calibration
Remarks
- The calibration status found in this certificate on the top of each results page must be interpreted as:
As Found : Data collected before the unit was adjusted and / or repaired
As Left : Data collected after the unit has been adjusted and / or repaired
Found / Left : Data collected without any adjustment and / or repair performed
- The calibration interval (due date) is the responsibility of the end user.
- According to the European norm 'Operation of electrical installations' NEN-EN 50110-1 release 2013 and the Dutch norm
NEN 3140 release 2015 paragraph 5.102.12 through 5.102.16, a safety test is not required. Therefore not performed.
- Temperature conversions (if applicable) are performed according to ISO/IEC 60584:2013 for thermocouples, and ISO/IEC
60751:2022 for resistance temperature devices.
en_US Page 2 of 5
DSX Cable Analyzer
Found-Left Report
Model DSX-5000 CAT 6A/CLASS Fa 1000MHz Copper Module
Serial Number 20300207 Test date 25-Nov-22
Page 1 of 3
NEXT
NEXT Artifact SN 3386461
4
3.5
3
2.5
(dB)
2
1.5
1
0.5
0
0 100 200 300 400 500 600 700 800 900 1000 1100
Frequency (MHz)
Pass Worst margin: 0.410 at 1 MHz in pair 36-12. Worst accuracy at each frequency shown.
CDNEXT
CDNEXT Artifact SN 3386449
4
3.5
3
2.5
(dB)
2
1.5
1
0.5
0
0 100 200 300 400 500 600 700 800 900 1000 1100
Frequency (MHz)
Pass Worst margin: 0.220 at 31.25 MHz in pair 45-78. Worst accuracy at each frequency shown.
CMRL
CMDMRL Artifact SN 3386324
3.5
3.0
2.5
2.0
(dB)
1.5
1.0
0.5
0.0
0 100 200 300 400 500 600 700 800 900
Frequency (MHz)
Pass Worst margin: 0.400 at 797 MHz in pair 45. Worst accuracy at each frequency shown.
Measured difference of DSX and reference laboratory equipment added to measurement accuracy of reference laboratory equipment.
Worst accuracy at each frequency shown.
Corresponding measurement accuracy requirement for nominally compliant Level IV or Level 2G/VI field tester.
DSX Cable Analyzer
Found-Left Report
Model DSX-5000 CAT 6A/CLASS Fa 1000MHz Copper Module
Serial Number 20300207 Test date 25-Nov-22
Page 2 of 3
RL
CMDMRL Artifact SN 3386324
3.5
3
2.5
2
(dB)
1.5
1
0.5
0
0 100 200 300 400 500 600 700 800 900 1000 1100
Frequency (MHz)
Pass Worst margin: 0.210 at 916 MHz in pair 45. Worst accuracy at each frequency shown.
TCL
TCL Artifact SN 3386457
3.0
2.5
2.0
(dB)
1.5
1.0
0.5
0.0
0 100 200 300 400 500 600 700 800 900 1000 1100
Frequency (MHz)
Pass Worst margin: 0.550 at 3.88 MHz in pair 45. Worst accuracy at each frequency shown.
IL
ILFEXT Artifact SN 3386158
3.5
3.0
2.5
2.0
(dB)
1.5
1.0
0.5
0.0
0 100 200 300 400 500 600 700 800 900 1000 1100
Frequency (MHz)
Pass Worst margin: 0.660 at 2 MHz in pair 36. Worst accuracy at each frequency shown.
Measured difference of DSX and reference laboratory equipment added to measurement accuracy of reference laboratory equipment.
Worst accuracy at each frequency shown.
Corresponding measurement accuracy requirement for nominally compliant Level IV or Level 2G/VI field tester.
DSX Cable Analyzer
Found-Left Report
Model DSX-5000 CAT 6A/CLASS Fa 1000MHz Copper Module
Serial Number 20300207 Test date 25-Nov-22
FEXT Page 3 of 3
ILFEXT Artifact SN 3386158
3.5
1.2
3.01
2.5
0.8
2.0
(dB)
0.6
1.5
0.4
1.0
0.2
0.5
0.00
0
898.8 100 200
899 300 400
899.2 500 899.4 600 700899.6 800 900
899.8 1000 1100
900
Frequency (MHz)
Pass Worst margin: 0.260 at 57.25 MHz in pair 12-36. Worst accuracy at each frequency shown.
Measured difference of DSX and reference laboratory equipment added to measurement accuracy of reference laboratory equipment.
Worst accuracy at each frequency shown.
Corresponding measurement accuracy requirement for nominally compliant Level IV or Level 2G/VI field tester.
DSX-8000 only: M_IL and M_FEXT measurements validate the ability of the DSX-8000 to make measurements with DSX-5000
adapters.
M IL Not applicable M_ILFEXT Artifact SN -