Design of Steel Anchors For Rob: DOC. NO.: O22051-C-RP-FL-DC-2029
Design of Steel Anchors For Rob: DOC. NO.: O22051-C-RP-FL-DC-2029
Design of Steel Anchors For Rob: DOC. NO.: O22051-C-RP-FL-DC-2029
EPC CONTRACTOR:
STUP Consultants P.
Ltd
CLIENT: PROOF CONSULTANT:
EXECUTIVE ENGINEER,
RANCHI ROAD
CONSTRUCTION
DEPARTMENT (RCD) , IIT BOMBAY,
GOVERNMENT OF MUMBAI
JHARKHAND
This document is the property of L&T Construction, TI IC, and must not be
passed on to any third person or firm not authorized by us, nor be copied/made
use of in full or part by such person or firm without our prior permission in writing.
Date 09-Mar-23 Note No O22051-C-RP-FL-DC-
2029
1 .
STUP Consultants P. Ltd By MDE Sheet No
INDEX
1 Introduction 1
2 Design Data 2
3 Load Specification 3
8 Design of stifferes 24
13 STAAD INPUT 53
14 Annexure-I 74
________________________________________________________________________________
Date 09-Mar-23 Note No O22051-C-RP-FL-
DC-2029
2 .
STUP Consultants P. Ltd By MDE Sheet No
1 Introduction:-
This design presents the design steel anchor for main span of Cable Stay Bridge for
ROB at Ranchi.
The anchor is designed for maximum axial force and 2.5% lateral force is considered
for sagging or any eccentricity.
IRC:24-2010 is used for design.
Longitudinal Elevation
Plan
________________________________________________________________________________
Date 09-Mar-23 Note No O22051-C-RP-FL-
DC-2029
3 .
STUP Consultants P. Ltd By MDE Sheet No
2 Design Data:-
Span of the girder = 2.50 m
Density of steel = 78.5 kN/m3
Modulus of elasticity of steel = 200000 N/mm2
3 Load specification:-
________________________________________________________________________________
Date 09-Mar-23 Note No O22051-C-RP-FL-
DC-2029
4 .
STUP Consultants P. Ltd By MDE Sheet No
900 900
50 50
25
50 50
900 900
At Base At Opening location
________________________________________________________________________________
Date 09-Mar-23 Note No O22051-C-RP-FL-
DC-2029
5 .
STUP Consultants P. Ltd By MDE Sheet No
900
50
227.7
A1 505
0
A2 227.7 900
A3 444.6 495
25
50
900
A1 x y1 + A2 x y2 = 0.024210 m3
A3 x y3 = 0.023603 m3
\ Zp = 0.0478132 m3
Ze = 0.0427895 m3
________________________________________________________________________________
Date 09-Mar-23 Note No O22051-C-RP-FL-
DC-2029
6 .
STUP Consultants P. Ltd By MDE Sheet No
900
50
475
900
0 475
50
900
A1 x y1 = 0.021375 m3
A2 x y2 = 0.021375 m3
\ Zp = 0.04275 m3
Governing Case i)
hence, d/tw <= 345 x e2
________________________________________________________________________________
Date 09-Mar-23 Note No O22051-C-RP-FL-
DC-2029
8 .
STUP Consultants P. Ltd By MDE Sheet No
50 50
A1 225
450 0 450
225
A2
25
A3 900 900
450
A1 x y1 + A2 x y2 = 0.010125 m3
A3 x y3 = 0.010125 m3
\ Zp = 0.0203 m3
Ze = 1.35E-02 m3
Nd = 28364 kN
________________________________________________________________________________
Date 09-Mar-23 Note No O22051-C-RP-FL-
DC-2029
9 .
STUP Consultants P. Ltd By MDE Sheet No
Nd = 32727 kN
Where,
f bd = χLT f y / γmo
ϒmo= 1.10 = Partial safety factor
χLT = 1/(φLT + (φLT2 - λLT2)1/2 <1.0
φLT = 0.5*[1 + α LT(λLT - 0.2) + λLT2]
αLT = 0.49 Imperfection parameter for welded steel section
λLT = slenderness ratio = (βb Zp fy / Mcr)1/2 < (1.2 Ze fy / Mcr)1 / 2
Ze = 0.044 m3
Zp = 0.048 m3
βb = 0.914 (1 for plastic or compact section and Ze / Zp for Semi compact section)
2
2
Mcr = c1 π2*E*Iy K I + GIt(LLT)^2 + (c2-yg-c3yi) - (c2yg-c3yj) IRC 24-2010
LLT Kw Iw π2 *EIy AnnexureC1.2
E = 2.00E+05 MPa
a = 2500 mm
From Staad Model, δ for unit force applied
δ = 0.00001 mm < 6.43E-07 mm (a3/(40EIc))
LLT = 2500 mm eff. length for lateral torsion restraint
4
Iy = 6.08E+09 mm Moment of inertia @ weak axis
G = 77000 MPa Modulus of rigidity
3
It = Σbt (ti) /3 St. Venant's Torsion constant
4
= 8.0E+07 mm
4
Ifc = 3.038E+09 mm MI of Comp. flange @ minor axis
4
Ift = 3.038E+09 mm MI of Ten. flange @ minor axis
βf = Ifc / (Ifc + Ift )
________________________________________________________________________________
Date 09-Mar-23 Note No O22051-C-RP-FL-
DC-2029
10 .
STUP Consultants P. Ltd By MDE Sheet No
= 0.50
hy = 950 Dist. between shear center two flanges on c/s
2
Iw = (1 - βf) βf Iy hy Warping Constant
= 1E+15 mm^4
K = 1 The value of K depends on end restraints
K= 0.5,0.7,1 respectively for complete, partial & no restraint against rotation about weak axis
Kw = 1 (The value of Kw is generally taken as 1 unless special
arrangements have been made to restrain warping at end
supports of sections )
Moment check
Design Bending Moment
= 911 kN-m < 12709 kN-m
O.K.
Where,
f bd = χLT f y / γmo
ϒmo= 1.10 = Partial safety factor
χLT = 1/(φLT + (φLT2 - λLT2)1/2 <1.0
φLT = 0.5*[1 + α LT(λLT - 0.2) + λLT2]
αLT = 0.49 Imperfection parameter for welded steel section
λLT = slenderness ratio = (βb Zp fy / Mcr)1/2 < (1.2 Ze fy / Mcr)1 / 2
Ze = 0.014 m3
Zp = 0.020 m3
________________________________________________________________________________
Date 09-Mar-23 Note No O22051-C-RP-FL-
DC-2029
11 .
STUP Consultants P. Ltd By MDE Sheet No
βb = 1.000 (1 for plastic or compact section and Ze / Zp for Semi compact section)
2
2
Mcr = c1 π2*E*Iy K I + GIt(LLT)^2 + (c2-yg-c3yi) - (c2yg-c3yj) IRC 24-2010
LLT Kw Iw π2 *EIy AnnexureC1.2
E = 2.00E+05 MPa
a = 2500 mm
From Staad Model, δ for unit force applied
δ = 0.00001 mm < 6.43E-07 mm (a3/(40EIc))
LLT = 2500mm eff. length for lateral torsion restraint
4
Iy = 6.08E+09 mm Moment of inertia @ weak axis
G = 77000 MPa Modulus of rigidity
3
It = Σbt (ti) /3 St. Venant's Torsion constant
4
= mm
8.0E+07
4
Ifc = 3.038E+09 mm MI of Comp. flange @ minor axis
4
Ift = 3.038E+09 mm MI of Ten. flange @ minor axis
βf = Ifc / (Ifc + Ift )
= 0.50
hy = 0 Dist. between shear center two flanges on c/s
2
Iw = (1 - βf) βf Iy hy Warping Constant
= 0 mm^4
K = 1 The value of K depends on end restraints
K= 0.5,0.7,1 respectively for complete, partial & no restraint against rotation about weak axis
Kw = 1 (The value of Kw is generally taken as 1 unless special
arrangements have been made to restrain warping at end
supports of sections )
________________________________________________________________________________
Date 09-Mar-23 Note No O22051-C-RP-FL-
DC-2029
12 .
STUP Consultants P. Ltd By MDE Sheet No
Moment check
Design Bending Moment
= 911 kN-m < 5891 kN-m
O.K.
= 0.67 O.K.
________________________________________________________________________________