CHME325-Lab Manual Spring 2024
CHME325-Lab Manual Spring 2024
CHME325-Lab Manual Spring 2024
College of Engineering
Qatar University
CHME 325
Unit Operations Lab Laboratory Manual
Spring 2024
Contents
Preface .............................................................................................................................. iii
Objective .................................................................................................................. 16
Theory ...................................................................................................................... 16
Equipment Setup .................................................................................................... 17
Procedure ................................................................................................................ 19
Report requirement ................................................................................................ 20
U3. Distillation ............................................................................................................... 21
1. Objective .............................................................................................................. 21
2. Introduction and Theory .................................................................................... 21
3. Apparatus and procedure ................................................................................. 25
3.1 Apparatus ...................................................................................................... 25
3.2 Procedure ...................................................................................................... 27
4. Safety Aspects .................................................................................................... 29
5. References .......................................................................................................... 29
6. Appendix .............................................................................................................. 29
U4. Fixed and Fluidized Bed ...................................................................................... 31
Objective .................................................................................................................. 31
Introduction.............................................................................................................. 31
Theory ...................................................................................................................... 31
Equipment Setup .................................................................................................... 33
Procedure ................................................................................................................ 34
U5. Wetted Wall Gas Absorption ............................................................................... 35
Theory ...................................................................................................................... 35
i
Equipment Setup .................................................................................................... 38
Procedure ................................................................................................................ 39
Report requirement ................................................................................................ 40
U6. Gas Absorption ..................................................................................................... 41
Theory ...................................................................................................................... 41
Equipment Setup .................................................................................................... 42
Procedure ................................................................................................................ 43
U7. Molecular Diffusion in Gases .............................................................................. 45
1. Objectives: ........................................................................................................... 45
2. Introduction:......................................................................................................... 45
3. Apparatus ............................................................................................................ 47
4. Safety Aspects: ................................................................................................... 49
5. References .......................................................................................................... 49
ii
Preface
iii
General Safety in the Laboratory
General safety rules and regulations are explained during the LAB orientation
week. So it’s compulsory that students attend that positively to be aware of the
general safety procedures. Following point must be observed during laboratory
sessions:
iv
U1. Cooling Tower
Objectives
How a cooling tower works? A cooling tower in principle is a special type of packed
tower. The usual packing material is cypress wood, which is the most economical
tower filling that withstands the combined action of wind and water. The warm
water is admitted at the top of the tower and moves counter flow to the air. In the
tower, part of the water evaporates into the air, and sensible heat is transferred
from the warm water to the cooler air. Both processes reduce the temperature of
the water. Waste heat present in the warm water is rejected to the atmospheric
air through convection and evaporation heat transfer [Saravanan 2008]. Only
make-up water to replace that lost by evaporation is required to maintain the water
balance.
Types of Cooling Tower: Cooling towers falls into two main sub-divisions: natural
draft and mechanical draft. Natural draft designs use very large concrete chimneys
to introduce air through the media. Due to the tremendous size of these towers
(around 500 ft high and 400 ft in diameter at the base) they are generally used for
water flow rates above 200000 gal/min. Usually these types of towers are only
used by utility power stations. Mechanical draft cooling towers are much more
widely used. These towers utilize large fans to force air through circulated water.
The water falls downward over fill surfaces that help increase the contact time
between the water and the air. This helps to maximize heat transfer between the
two.
The driving force for evaporation is, very nearly, the difference between the vapor
pressure of the water and the vapor pressure it would have at the wet-bulb
temperature of the air. Obviously the water cannot be cooled to below the wet bulb
temperature. In practice the discharge temperature of the water will differ from the
wet bulb temperature. This difference in temperature is called the approach to wet
bulb.
If water from a cooling tower is to be used for process cooling, the design of the
cooling equipment must be based on the maximum expected temperature of the
cooling water. This in turn depends, not on the maximum dry bulb temperature of
the air, but on the maximum wet bulb temperature.
The traditional approach to determine the mass transfer coefficient is to describe
the column height as the product of a HTU (height of transfer unit) and NTU
(number of transfer units). The HTU can be thought of as describing the efficiency
of contacting and the NTU as the difficulty of separation.
Cooling Range:
This is the difference between the water temperature at entry to and exit from the
tower.
Cooling Load:
The rate at which heat is removed from the water. This may be expressed in kW,
Btu/h or kcal/h.
Make-up water:
It is the quantity of fresh water which must be supplied to the water circuit to make
up the losses due to evaporation
6
b) The water flow rate
c) The water temperature
d) The air temperature and humidity at inlet (particularly the wet bulb
temperature)
e) The type of packing used
f) The area and volume of packing
Theory:
Setting up Mass Balance:
Ideally, rate of evaporation observed from the volume of water decreased in the
tank is equal to the moisture content difference in the air leaving the tower and the
air entering the tower.
Mathematically,
m E = m SB − m SA
= m a (ω B − ω A )
E is the water evaporation rate, m SB is the moisture content in the outlet
Where, m
air, m SA is the moisture content in the inlet air, m a is the mass flow rate of dry air.
ω B and ω A are the moisture content or humidity ratio at the exit and inlet for air
(this is estimated using the psychrometric chart and using the inlet and exit air dry
bulb and wet bulb temperatures).
There are some non-idealities. So m E and m a (ω B − ω A ) are calculated separately,
and the error percentage has to be determined and possible sources of error
should be discussed.
In a cooling tower of infinite size and with adequate air flow, the water leaving the
tower will be at the wet bulb temperature of the incoming air. For this reason, the
difference between the temperature of the water leaving a cooling tower and the
local wet bulb temperature is an indication of the effectiveness of the cooling tower.
“Approach to wet bulb” = (t6 – t2)
We consider a packed water – cooling tower with air flowing upward and water countercurrently
downward in the tower. The total interfacial area between air and liquid phases is unknown since
the surface area of the packing is not equal to the interfacial area between the water droplets and
the air. Hence, we define a quatity a, defined as m2 of interfacial area per m3 volume of packed
section. This is combined with gas phase mass-transfer coefficient kG to give a volumetric
coefficient kG a. the process is carried out adiabatically and the various streams and conditions are
shown in the figure below:
7
L = water flow, kg water/s . m2
TL = temperature of water, ºC or K
G = dry air flow, kg/s . m2
TG = temperature of air, ºC or K
H = humidity of air, kg water/kg dry air
Hy = enthalpy of air-water vapor mixture, J/kg dry air
The heat capacity cL of the liquid is assumed constant at 4.187 x 103 J/kg.K. When a plot of Hy
versus TL is made, we obtain a straight line with a slope of LcL/G. Making an overall heat balance
over both ends of the tower,
G(Hy2 – Hy1) = LcL(TL2 – TL1) (2)
Again making a heat balance for the dz column height and neglecting sensible heat terms
compared to the latent heat,
LcL dTL = G dHy (3)
The total sensible heat transfer from the bulk liquid to the interface is:
LcL dTL = G dHy = hL a dz(TL - Ti) (4)
Where hLa is the liquid-phase volumetric heat transfer coefficient in W/m3.K and the Ti is the
interface temperature. For adiabatic mass transfer the rate of heat transfer due to the latent heat
in the water vapor being transferred can be obtained as:
qλ/A = MBkGaPλ0(Hi – HG)dz (5)
where qλ/A is in W/m2, MB is the molecular weight of air, kGa is the volumetric mass-transfer
coefficient in the gas in kg mol/s.M3.Pa, P is the atmospheric pressure in Pa, λ0 is the latent heat
of water in J/kg water, Hi is the humidity of the gas at the interface in kg water/kg dry air, and HG is
8
the humidity of the gas in the bulk gas phase in kg water/kg dry air. The rate of sensible heat
transfer in the gas is
qs/A = hG a (Ti – TG) dz (6)
where qs/A is in W/m2 and hG a is the volumetric heat transfer coefficient in the gas in W/m3.K.
From the figure equation 4 must be equal to the sum of equations 5 and 6.
G dHy = MBkGaPλ0(Hi – HG)dz + hG a (Ti – TG) dz (7)
From theory:
hG a
≅ cs (8)
M Bkya
hG a
≅ cs (9)
M B Pk G a
Substituting the above equation (9) into equation (7), and rearranging,
G dHy = MBkGaP dz [(cs Ti + λ0Hi) – (csTG + λ0HG)] (10)
The terms inside the braces are (Hyi – Hy), and hence the above equation becomes
G dHy = MBkGaP dz (Hyi – Hy) (12)
Integrating,
z H y2
G dH y
∫0 dz = z =
M B k G aP ∫
H y1
H yi − H y (13)
Often, only an overall mass-transfer coefficient KGa is available, and the above equation becomes
Hy2
G dH y
z=
M B K G aP ∫
H y1
H ∗y − H y (14)
First, H versus T plot for saturated air is drawn. The value of H*y is determined by going vertically
from the value of Hy at point P up to the equilibrium line.
9
Figure 2 Temperature enthalpy diagram and operating line for water-cooling tower
(In many cases the film coefficients kGa and hLa are not available. The few experimental data
available indicate that hLa is quite large and that the value of Hyi would approach that of H*y in
equation 3.)
Knowing the entering air conditions TG1 and H1, the enthalpy of this air Hy1 is
calculated. The point Hy1 and TL1 (leaving water temperature) is plotted in the figure
as a point on the operating line. The operating line is plotted with a slope of LcL/G
and ends at point TL2, which is the entering water temperature. This gives Hy2.
Point P represents Hy and TL on the operating line and point R represents H*y on
the equilibrium line. Hence, the vertical line RP or H*y – Hy represents the driving
force.
The driving force H*y – Hy is computed for various values of TL between TL1 and
TL2. Then by plotting 1/( H*y – Hy) versus Hy from Hy1 to Hy2, a graphical (or
numerical) integration is performed to obtain the value of the integral in equation
14. Then, experimental value of KGa can be obtained.
10
First, the equilibrium line is drawn using the enthalpies of saturated air.
T sat H (kJ/kg)
10 29.29303884
12 34.10376263
14 39.27608266
16 44.8512605
18 50.87488807
20 57.39736974
22 64.47447474
24 72.16797359
26 80.54637491
28 89.68578291
30 99.67090051
32 110.5962088
34 122.5673614
36 135.7028407
38 150.1359381
40 166.0171316
Next, the operating line is drawn using the information of temperatures of inlet (TL1)
and outlet water(TL2), and the enthalpies of the air entering the column (Hy1) and
leaving the column (Hy2).
Next, value of 1/(H*y - Hy) is calculated at selected values of Hy in between Hy1 and Hy2. We
find the integration value using MATLAB to find the area under the curve (trapz
function):
So the number of transfer units is obtained from the integration.
Next, the height of transfer unit (HOG) is calculated. This is given by: HOG = z/NOG,
where z is the tower height (0.48 m), and NOG is the number of transfer units just
calculated.
11
Note: The dimension for the packing cross section is 0.15 m × 0.15 m. the height
of the packing is 0.6 m.
2.1 Apparatus
The Basic Water Cooling Tower is used to introduce to the students the
characteristics and construction of a mechanical draft cooling tower. This operates
with moderate air and water flows with 0.5, 1.0 or 1.5 kW cooling loads.
12
The operation of a Basic Water Cooling Tower is as follows:
Water Circuit
The heated water from the tank is transferred to the top of the tower by a water
pump, with the cold water collected at the bottom of the tower and fed back into
the tank. A level gauge is present on the hot side of the tank, which indicates the
amount of water in the tank, as well as the maximum water level. To ensure a
constant level of water in the tank, a float valve is installed, with water slowly fed
into the tank to stabilize the water level and temperature. This facilitates accurate
results and provides a consistent environment for the temperature controller.
The unit is fitted with a centrifugal pump. The pump switch is located on the main
frame. The pump circulates water from the water tank through a needle valve to
regulate flow rate to the top of the column. The water is sprayed into the column,
it then passes by gravity down through the packing in the
column and back into the drip tray below. The water flow rate can be changed
using the needle valve.
Air circuit
A centrifugal fan is fitted on the right hand side of the unit. Air passes vertically
down a circular inlet duct to the fan. The fan accelerates the air, turns it 90
degrees and forces it into the right hand (dry) end of the water tank and up
through the tower. A calibrated orifice at the top of the fan inlet duct works with
an air pressure sensor to measure the air flow rate through the column. (VDAS®
calculates this automatically).
The EC1000V features in-built data acquisition hardware that facilitates direct
connection to a computer via a provided micro-USB cable. This connection is
located on the right-hand edge of the control panel, thus eliminating the need for
13
extra hardware. Our VDAS® software is optimally compatible with the EC1000V,
providing a range of essential features such as automatic logging and calculation
of data, enhanced productivity, increased accuracy, creation of charts and tables,
data export for further processing, and psychrometric chart generation.
2.2 Procedure
1. Check that the level of water in the water tank overflows the level switch.
2. Choose a temperature for the water in the tank and wait until it is reached.
3. Choose a flow for the airflow and wait some minutes until it is reached.
4. Choose a flow for the water flow and wait some minutes until it is reached.
5. Record the data.
3. Safety Aspects:
1. The COSHH (Control of Substances Hazardous to Health) regulations
(1988) - The equipment used for this experiment involves the use of water
14
which under certain conditions can create a health hazard due to infection
by harmful micro-organisms. For example, the microscopic bacterium called
Legionella pneumophila will feed on any scale, rust, algae or sludge in water
and will breed rapidly if the temperature of water is between 20 and 45°C.
Any water containing this bacterium which is sprayed or splashed creating
air-borne droplets can produce a form of pneumonia called Legionnaires
Disease which is potentially fatal. So the precaution for this is to change the
water regularly and not allowed to stagnate.
2. The equipment operates from a mains voltage electrical supply. The
regulations applying to the operation of electrical equipment must be
observed by the user. To give increased operator protection, and Earth
Leakage Circuit Breaker (ELCB, alternatively called a Residual Current
Circuit Breaker or RCCB) is provided as an integral part of the equipment.
If through misuse or accident the equipment becomes electrically
dangerous, and ELCB will switch off the electrical supply and reduce the
severity of any electric shock received by an operator to a level which, under
normal circumstances, will not cause injury to that person.
4. References
1. Lab Manual – Course handout, Chemical Engineering Department, Qatar
University.
2. Geankoplis, C.J., Transport processes and Unit Operations, 3rd Ed.,
Prentice Hall India.
3. Instruction Manual – Basic Water Cooling Tower (10), Dec. 1999.
15
U2. Tray Dryer
Objective
To produce a drying and a drying rate curve for a wet solid being dried with air of
fixed temperature and humidity.
Theory
Immediately after contact between the drying media (wet solid) and the drying
medium (hot air), the solid temperature adjusts until it reaches a steady state. If
the solid is initially very wet the surface is essentially covered in a thin film of
liquid which is considered to be unbound moisture. The solid temperature and
the rate of drying may increase or decrease to reach the steady state condition.
At steady state, the temperature of the wet solid surface is the wet bulb
temperature of the drying medium. Temperatures within the drying solid also tend
to equal the wet bulb temperature of the air. However, lag between the
movement of mass and heat result in some deviation. Once the media
temperatures reach the wet bulb temperature of the air, the temperatures of the
media and air become stable and the drying rate remains constant. This is the
“constant rate drying”. The moisture is transported to the surface of the media by
capillary forces and drying is limited only by the rate at which the heat is
supplied. This period ends when the solid reaches the critical moisture content.
The surface film of moisture over the solid has been reduced by evaporation to a
point where any further drying causes dry spots to appear on the solid
surface. Beyond the critical moisture content, the surface temperature of the
solid rises and the drying rate falls off rapidly. This is the “falling rate” period and
can last for a significantly longer time than the constant rate period. This holds
true even though the moisture removal may be less. The drying rate approaches
zero as the moisture content reaches equilibrium. This is the lowest moisture
content obtainable with the solid under the drying conditions used.
16
Figure 2: Typical Drying Rate Curve
Useful equations
Where:
Ss (kg) = Mass of dry solid
= Change in moisture content
(h) = Time period
A (m2) = Drying area
Equipment Setup
The equipment comprises a square section air duct fabricated from stainless
steel with variable speed fan, and removable trays for solids drying.
17
Figure 3: Tray Dryer (Armfield, UOP8 – MKII)
Air is drawn into the duct by an electronic motor driven axial fan impeller. The air
flow rate is determined using an air velocity transmitter.
The heated air passes over a combined humidity and temperature sensor before
passing over the three drying trays. Air temperature and relative humidity are
continuously measured at two points before and after the trays. The wet bulb
temperature can be calculated from Psychrometric Chart.
18
Specifications
• The dimensions for each tray are 254mm x 304.8mm x 9.5mm.
• The cross-sectional dimension of the central duct section (where the drying
trays are positioned) is (0.328 m x 0.177 m) = 0.051 m2.
Procedure
19
5. Place the loaded drying trays on to the tray holder and lock the side door
closed.
Note: Take care when placing the drying trays into the UOP8-MKII drier
as the internals may be hot and harmful to touch.
6. Record the total weight indicated (material and water).
7. Change the operation back to Automatic on the Heater PID menu.
8. Then select the icon to begin the data recording of the sensor readings
into the results table.
8. The end of drying occurs when there is no change in the total weight for 5
– 10 minutes.
11. When the end of drying has been confirmed from the graph, select the
icon to stop recording data.
C- Ending The Experiment:
1. Set the heater PID to “OFF” to begin cooling the equipment. When T2
reaches room temperature set the fan speed to 0%.
2. Switch the UOP8-MKII drier off using the main switch on the drier.
3. Remove the trays from the tray holders and return the dried material.
4. Return the trays back onto the tray holders and lock the side door closed.
Report requirement
(1) Calculate the total moisture content removed from the solid. Calculate the
free moisture content
(2) Plot the drying curve relating moisture content as a function of time. On
the secondary axis plot the temperature after the trays (T2). Find the
drying periods on this curve.
(3) Produce the drying rate vs. moisture content curve.
(4) Calculate the theoretical drying rate.
(5) Comment upon the results obtained and relate the curves to the
mechanism by which drying occurs.
a. What is the significance of the equilibrium moisture content?
b. If the results did not reflect that which the theory suggests, what
may have caused this discrepancy?
c. When the “critical moisture content” occurs, what happens to T2?
20
U3. Distillation
1. Objective
1) To observe the operation of the steady-state distillation of a binary mixture
under continuous operation.
2) Determine the theoretical number of stages
3) Determine the efficiency
2. Introduction and Theory
Distillation is one of the most important industrial processes for separating the
different components (having different volatilities or boiling points) of a liquid
mixture to obtain products of desired purity. Distillation usually forms part of a
larger chemical process, and is thus referred to as a unit operation. Design and
operation of a distillation tower depends on the feed and desired products.
Laboratory scale distillation columns are needed to provide adequate practical
training for students and plant operators in a safe environment. They may also be
used to acquire process separation data for use in full-scale plant design.
In distillation (fractionation) a feed mixture of two or more components of different
volatilities is separated into two or more products whose compositions differ from
that of the feed. Most often, the feed is liquid or vapor-liquid mixture. The bottoms
product is almost always a liquid, but the distillate maybe a liquid or a vapor or
both.
Separation by distillation requires the following: (1) a second phase be formed so
that both liquid and vapor phases are present and can contact each other on each
stage within the separation column, (2) the volatilities of the components are
different so that they will partition between the two phases to different extents, and
(3) the two phases can be separated by gravity or other mechanical means.
Distillation differs from absorption or stripping in that the second phase is usually
created by thermal means (vaporization or condensation) rather than by
introduction of a second phase that may contain an additional component or
components not present in the feed mixture.
Commercially, distillation has a number of uses. It is used to separate crude oil
into more fractions for specific uses such as transport, power generation and
heating. Water is distilled to remove impurities, such as salt from sea water. Air is
distilled to separate its components - notably oxygen, nitrogen and argon - for
industrial use. Distillation of fermented solutions has been used since ancient times
to produce distilled beverages with a higher alcohol content.
There are two main kinds of distillation: Simple Distillation & Fractional distillation.
Fractional distillation is essentially the same as simple distillation except that a
fractionating column is placed between the boiling flask and the condenser. The
fractionating column is usually filled with a packing. Fractional distillation gives
better separation between the liquids because the stages in the fractionating
column provide "theoretical plates" on which the refluxing liquid can condense, re-
evaporate, and condense again, essentially distilling the mixture over and over.
21
Figure 1 Simple Distillation Figure 2 Fractional Distillation
22
The mixture of 95.6% ethanol and 4.4% water (percentage by weight) is an
azeotrope with a boiling point of 78.2 ºC.
(For information only: The ethanol-water azeotrope can be broken by the addition
of a small quantity of entrainer – benzene or cyclohexane. Sometimes a molecular
sieve is used to selectively absorb the water from the 95.6% ethanol solution.
Synthetic zeolite can be used for this purpose. Membranes can also be used to
separate ethanol and water. Separation using membrane is not based on vapor-
liquid equilibria.)
23
xn is the liquid composition leaving the nth stage.
yn+1 is the mole fraction of A in Vn+1 (Vn+1 is molar flow rate of vapor
from tray n+1)
The enriching line equation is a straight line on a plot of vapor composition
versus liquid composition, and it relates the compositions of two streams passing
each other
• The stripping section line can be drawn between the points where the
enriching line intersects with the q-line and the point where xw meets the
diagonal line.
The equation stripping section operating line is
L Wx w
y m +1 = m x m −
Vm +1 Vm +1
• Draw the theoretical stages by starting at xD on the diagonal line, move
horizontal to the equilibrium line, and then vertically back to the enriching
operating line.
• Continue the process towards xw, switching to the stripping section line after
crossing the q-line till you meet xw. (The optimum feed plate is one which
crosses the q-line.)
• Count the number of theoretical stages, and then determine the overall
efficiency.
24
3. Apparatus and procedure
3.1 Apparatus
25
Figure 1 Apparatus – Armfield Distillation Column
26
Figure 2 Schematic diagram for continuous distillation
3.2 Procedure
27
obtained on the digital wattmeter. The contents of the reboiler will begin to
warm up and this can be observed on the temperature read-out meter.
(Vapor will begin to rise up the column and the progress of this can be
clearly observed by the increasing temperatures when switching the
temperature selector on T8, T7, T6, T5, T4, T3, T2 and T1. The vapor
formed as a result of temperature rise will enter the condenser and reappear
as droplets into the glass walled distillate receiver vessel. The distillate will
build up a small level in the receiver and eventually overflow to the reflux
regulator valve.)
28
4. Safety Aspects
1. Ethanol is a mild skin irritant, so nitrile or latex gloves must be worn when
the potential for contact exists.
2. There is also an inhalant and ingestion hazard linked with ethanol. Due to
the nature of the experiment vapors will escape although the air circulation
should prevent inhalation of a significant amount of vapors. However, if eye
irritation, headache, dizziness or nausea occurs, leave the lab immediately
and inhale fresh air.
3. When removing the liquid or vapor samples, a nitrile or latex glove may be
worn due to the high temperature of the samples.
4. It is also advisable to wear glasses or goggles at all times during the
experiment.
5. The cooling water should be turned on before any heating element is turned
on to ensure that any vapor created is condensed.
5. References
1. Lab Manual – Course handout, Chemical Engineering Department, Qatar
University.
2. Instruction Manual – Continuous Distillation Column (19) May 2004.
3. McCabe, W. L., J. C. Smith, P. Harriott, Unit Operations of Chemical
Engineeering, McGraw Hill International Editions, 4th Ed.
6. Appendix
The following attachment is the data logging sheet will be used by the students to
enter the data at the time of the experiment.
29
The following data should be used for getting calibration curve to get molar
composition of ethanol in the solution.
Molar % Refractive
ethanol Index
0 1.3314
12 1.3500
24 1.3595
36 1.3631
48 1.3646
60 1.3649
72 1.3645
82 1.3637
92 1.3626
100 1.3615
1.3700
1.3650
1.3600
1.3550
Refractive Index
1.3500
1.3450
1.3400
1.3350
1.3300
1.3250
0 10 20 30 40 50 60 70 80 90 100
Ethanol mol %
30
U4. Fixed and Fluidized Bed
Objective
Introduction
The upward flow of fluid through a bed of granular material is a situation
encountered both in nature and in industry. Natural occurrences include the
movement of ground water, the movement of crude petroleum or the movement
of natural gas through porous media. Industrial occurrences include operations
such as back-washing filters, ion-exchange processes, extraction of soluble
components from raw materials and certain types of chemical reactor.
It is well known that if the granules are loosely packed and the pressure drop due
to the flow through the bed is equivalent to the weight of the bed then the
phenomenon of fluidisation occurs. The fluidised state occurs naturally in so-
called 'quick sands' where an object on the surface of the sand will quickly sink
through the sand when an upward flow of water occurs through the sand The
high rate of solids mixing that accompanies fluidisation is utilised in various
industrial operations such as drying, coating, heat transfer and chemical reaction.
Theory
To predict the performance of a fluidised bed, it will be necessary to know the
Voidage of the granules used in the beds I.e. the ratio of the voids (spaces)
between the granules to the total volume.
The bed Voidage (porosity) ɛ can be determined using the following equation:
………(1)
The Voidage for glass beads is typically 0.4, Where the Particle density for the
glass beads (Ballotini) is 2500 kg/m3. In Particulate Fluidizing Bed, where the
fluid is liquid, The void fraction of the expanded bed.
𝑳𝑳(𝟏𝟏 − ɛ) = 𝑳𝑳𝒎𝒎 (𝟏𝟏 − 𝜺𝜺𝒎𝒎 ) ………(2)
31
𝑳𝑳𝑴𝑴 (𝟏𝟏−𝜺𝜺𝑴𝑴 )
𝜺𝜺 = 𝟏𝟏 − ………(3)
𝑳𝑳
Where (L) is the expanded bed height, (𝐿𝐿𝑚𝑚 ) is the minimum bed height (i.e. Fixed
Bed), (ɛ) is the porosity of the expanded bed, (𝜀𝜀𝑚𝑚 ) is the porosity of minimum
bed height.
−∆𝑷𝑷−𝑳𝑳𝑳𝑳𝑳𝑳 𝒅𝒅 𝟏𝟏 𝜺𝜺𝟑𝟑
𝒇𝒇𝑷𝑷𝑷𝑷 = ∗ ∗ 𝟐𝟐 ∗ (𝟏𝟏−𝜺𝜺) ………(5)
𝝆𝝆 𝑳𝑳 𝒗𝒗𝒔𝒔
Where, 𝑑𝑑 is the size of granules (m) = 0.625 x 10-3 m for the larger granular
material, and 0.250 x 10-3 m for the smaller granular material.
From equations (5) and (7) Pressure drop per unit length can be determined
theoretically, and Carman-Kozeny equation can be expressed in the form
32
𝒅𝒅𝟐𝟐 𝜺𝜺𝟑𝟑
𝐊𝐊 = � � ………(11)
𝟏𝟏𝟏𝟏𝟏𝟏(𝟏𝟏−𝜺𝜺)𝟐𝟐
At Incipient fluidization (onset of fluidisation) the force due to pressure drop must
be equal to the weight of the bed.
𝑩𝑩𝑩𝑩𝑩𝑩 𝒘𝒘𝒘𝒘𝒘𝒘𝒘𝒘𝒘𝒘𝒘𝒘
−∆𝑷𝑷 = 𝑨𝑨
= 𝝆𝝆𝒔𝒔 (𝟏𝟏 − 𝜺𝜺)𝒈𝒈𝒈𝒈 + 𝝆𝝆𝝆𝝆𝝆𝝆𝝆𝝆 ………(12)
𝟏𝟏𝟏𝟏𝟏𝟏𝟏𝟏𝟏𝟏𝒗𝒗𝒔𝒔 (𝟏𝟏−𝜺𝜺)𝟐𝟐
−∆𝑷𝑷 = = 𝒈𝒈𝒈𝒈[(𝝆𝝆𝒔𝒔 − 𝝆𝝆)(𝟏𝟏 − 𝜺𝜺)] ………(13)
𝒅𝒅𝟐𝟐 𝜺𝜺𝟑𝟑
Equipment Setup
The Armfield CEL-MKII is designed to facilitate the study of flow through fixed
and fluidised beds of solid granules. Low flow rates allow the characteristics of a
solid bed to be investigated. Increasing flow rates allow the onset of fluidisation
and the characteristics of a fluidised bed to be investigated.
33
Figure 1: Fixed and Fluidised Bed Apparatus (Armfield CEL-MKII)
The CEL-MKII has three test columns, one for use with water and two for use
with air. With granules of the same size in the water column and one air column,
the differences between ‘particulate’ and ‘aggregative’ (‘bubbling’) fluidised beds
can be demonstrated. The two air columns allow the effect of different granule
sizes to be demonstrated without having to remove, empty and re-pack a
column.
Electronic instrumentation is incorporated, allowing all relevant flow rates and
differential pressures to be displayed. A USB connector allows the measured
variables to be viewed and logged on a PC if required using the software
supplied with CEL-MKII.
Specifications
• The bed cross-sectional area (Bed diameter = 0.05 m).
• The size of the granules (m) = 0.625 x 10-3 m for the larger granular
material, and 0.250 x 10-3 m for the smaller granular material.
• Voidage for glass beads is typically 0.4
• The particle density for the glass beads (Ballotini) is 2500 kg/m3.
Procedure
1) Set the flow regulator in front of the column to minimum flow (fully
anticlockwise).
2) Switch on the air compressor or water pump via the switch on the console.
3) Adjust the flow rate in increments of small quantities l/min by slowly
turning the flow regulator clockwise and observing the flow reading on
display.
4) Continue increasing the flow until the bed is fully fluidised and the
pressure drop across the bed remains constant for several readings.
5) At each setting allow the conditions to stabilize, then record the flow rate
and the differential pressure reading from the display.
6) Also record the height of the bed, measured using the scale on the
column, and observe and record the state of bed i.e. any movement of the
granules.
Report requirements.
Discuss the effect of particle size and fluid type on the pressure drop, friction
factor and minimum required velocity.
34
U5. Wetted Wall Gas Absorption
Objective
1. To estimate the liquid film mass transfer coefficient.
2. To determine the power-law relationship between the liquid film mass
transfer coefficient and the mass flow rate of water and to compare the
results with theoretical predictions.
3. Discuss the effect of both liquid phase and gas phase flow rates on the
mass transfere coeffificent.
Theory
The process of absorption of gases in liquid in absorption towers is widely used
in industry. The process facilitates the removal of one or more components from
a mixture of gases. This is achieved by diffusion into a suitable liquid.
In view of the complexity of mass transfer in actual mass transfer devices such
as packed towers, sieve trays and bubble cap columns, fundamental equations
for mass transfer are rarely available. This problem has been approached using
experimental devices in which area of contact between the phases is known and
where boundary layer separation does not take place. Wetted wall column is one
such device [McCabe Smith].
Wetted wall gas absorption tower is a vertical column in which liquid flows down
while the gas flows upward in counter current motion. The liquid comes in contact
with the flowing gas by means of convective mass transfer to dissolve one or
more of the gas components. The wetted wall gas absorption column provides a
means of determining this coefficient and has been widely used in the
development of correlations for packed towers. Mass transfer in wetted wall
column involves well defined interfacial area between the phases. The surface
area is assumed to be that of the inner tube surface area provided the liquid
flows in a smooth, thin and laminar layer.
The absorption of oxygen in water is an example in which most of the resistance
to mass transfer lies in the liquid phase. Many measurements of the mass
transfer coefficient have been developed for comparison between the mass
transfer coefficient and the mass flow rate of the liquid stream.
There are two mass transfer coefficients that are of interest to us in finding them
for applying mass transfer applications, which are called the overall mass
transfer coefficients for gas and liquid phases ‘KG’/’KL’ for linear equilibrium
curves, and can be calculated using these formulas:
1 1 𝑚𝑚 1 1 1
= + = +
𝐾𝐾𝐺𝐺 𝑘𝑘𝐺𝐺 𝑘𝑘𝐿𝐿 𝐾𝐾𝐿𝐿 𝑚𝑚𝑘𝑘𝐺𝐺 𝑘𝑘𝐿𝐿
Where,
35
‘𝐾𝐾𝐺𝐺 ’ is the overall mass transfer coefficient for gas phase.
‘𝐾𝐾𝐿𝐿 ’ is the overall mass transfer coefficient for the liquid phase.
‘𝑘𝑘𝐺𝐺 ’ is the gas film mass transfer coefficient.
‘𝑚𝑚’ is the proportionality constant for the linear equilibrium curves.
1 1 1 1 KLz
= + ≈ ⬄ ( Sh) L =
KL m𝑘𝑘𝐺𝐺 𝑘𝑘𝐿𝐿 𝑘𝑘𝐿𝐿 DL
1 1 𝑚𝑚 𝑚𝑚 mK G z
= + ≈ ⬄ ( Sh) L =
KG 𝑘𝑘𝐺𝐺 𝑘𝑘𝐿𝐿 𝑘𝑘𝐿𝐿 DL
1 1 1 1
= + ≈
KL m𝑘𝑘𝐺𝐺 𝑘𝑘𝐿𝐿 m𝑘𝑘𝐺𝐺
1 1 𝑚𝑚 1
= + ≈
KG 𝑘𝑘𝐺𝐺 𝑘𝑘𝐿𝐿 𝑘𝑘𝐺𝐺
36
(kinematic viscosity) (ν=μ/𝜌𝜌)
to the Mass diffusivity.
• Is used to characterize fluid
flows in which there are
simultaneous momentum
and mass diffusion
convection processes.
• Describes the ratio of the
Gravity forces to viscous
forces.
Galileo Number • Is used in viscous flow and 𝜌𝜌2 𝑔𝑔𝑧𝑧 3
𝐺𝐺𝐺𝐺 =
(Ga) thermal expansion 𝜇𝜇 2
calculations, for example to
describe fluid film flow over
the walls.
Where
4A
Dh = hydraulic diameter, Dh = P
kL = liquid film mass transfer coefficient, ms-1
z = height of column, m
DL = diffusivity of oxygen in water, m2/s
µL = viscosity of water Ns/m2
ρL = density of water kg/m3
Γ = mass flow rate of water per meter of wetted perimeter kg/s-m
ScL and GaL are constants if the properties of fluid are not changing
(Temperature is assumed constant). It is therefore possible to determine the
power-law relationship between (Sh)L and (Re)L by experiment and compare it
with the above correlation.
Where
• 𝐾𝐾𝑂𝑂𝑂𝑂 :Overall Mass Transfere Coeifficent based on the Liquid phase
• 𝑄𝑄 is the volumentric flow rate (m3/s).
• 𝑨𝑨 is the area of mass transfer
37
• �𝐶𝐶𝑂𝑂2,𝑂𝑂𝑂𝑂𝑂𝑂 − 𝐶𝐶𝑂𝑂2 ,𝑖𝑖𝑖𝑖 �Is the is the change in the oxygen concentration in the
water passing the column (mol/ m3).
• 𝛥𝛥𝐶𝐶𝐿𝐿𝐿𝐿 is the log mean concentration difference
• (𝐶𝐶𝑂𝑂𝐿𝐿2 ) is liquid phase oxygen concentration.
• 𝐶𝐶𝑂𝑂∗2 is the theoretical equilibrium oxygen concentration.
Equipment Setup
The Wetted wall gas absorption is a vertical column in which liquid flows down
while the gas flows upward in countercurrent motion. The liquid comes in contact
with flowing gas by means of Convective Mass Transfer to dissolve one or more
of the gas components. First, Water is sparged with nitrogen gas in order to
remove its oxygen content before entering the top of the wetted wall column.
Then, the Air is pumped by an air compressor into the base of the absorption
column. Air passes up the column, giving up the oxygen to the deoxygenated
water. The amount of dissolved oxygen at the inlet and outlet of the wetted wall
column can be measured using a DO calibrated electrode.
38
.
Figure 2: Schematic diagram of Wetted Wall Column (Pignat, France).
Procedure
C. Preparation of the Experiment:
(1) Open the valve of nitrogen gas (1 bar) and allow it to flow through the
WWC to remove any traces of 𝑂𝑂2.
(2) Open V7 (to allow the 𝑁𝑁2 flow into the system).
(3) Open V9 (to allow the 𝑁𝑁2 flow into the WWC).
(4) Close V8 (to prevent the 𝑁𝑁2 flow through DeOC).
(5) Close V11 (to prevent the 𝑁𝑁2 flow through Air compressor hoses ).
(6) Monitor the OX2 that measure the 𝑂𝑂2 (mg/L) of the outlet WWC until
reaches ≈1 mg/L. Now the WWC is almost free of Oxygen, so we can
close it and allow the N2 to pass through the DeOC.
(7) Close V9 (to stop the N2 flow into the WWC).
(8) Open V8 (to allow the N2 flow through DeOC).
(9) Switch on Pump 1 and adjust the water flowmeter at 20 L/h (to allow
the water to be de-oxygenated in the DeOC and been derived to the
WWC.
39
(10) Ensure that all wetted wall of the column is wetted with water (if not,
you can pour some water at the top of the WWC to make the column
totally wetted by water..
(11) Monitor O2 concentration that connected to OX2 until reaches around
0.4 mg/L. Now, the system is ready to start the experiment.
Report requirement
(1) Calculate the overall mass transfer coefficient 𝐾𝐾𝑂𝑂𝑂𝑂 experimentally.
(2) Determine Sherwood Number from the calculated mass transfer
coefficient.
(3) Determine Sherwood Number empirically.
(4) From empirical Sherwood, number calculate theoretical liquid film mass
transfer coefficient.
(5) Find and discuss the difference between experimental and empirical
findings.
(6) Plot a relation between log Sh vs log Re, and check the validity of the
empirical Sherwood Number.
(7) Discuss the effect of both liquid phase and gas phase flow rates on the
mass transfer coefficient.
40
U6. Gas Absorption
Objective
1. To estimate the Loading and flooding points in the wet column.
2. To compare between the pressure drop trend betwwen dry column and
wet column.
Theory
Absorption is a basic operation of mass transfer that consists on the separation
of some components of a gaseous miscture by contact with an adequate solvent.
The packed tower, in which two liquids flowing in opposite directions enable a
chemical component to be transferred from one fluid phase to the other, occurs
in almost all chemical plants. This process of chemical component transfer can
be gas absorption, distillation, solvent extraction etc. As a Chemical engineer
(design engineer) we should have the knowledge of the characteristics of fluid
flow and of mass transfer in such towers. The Armfield Gas Absorption column is
designed to allow both these studies to be made.
Packed towers are vertical columns filled with suitable packing and normally
operate countercurrently. Liquid enters the top of the column and is distributed
over the top of the column packing via nozzles or distributor plates. Liquid flows
downward while contacting with the vapor phase. Internal packing provides a
large surface area for two-phase contact and facilitates transfer of materials
between phases.
For a dry tower the differential pressure drop (P) is related to the gas flowrate (Q)
(or velocity) (V) by an equation of the form:
P Qn
P Vn
The pressure drop depends significantly on the nature of the packing. Different
packings have different free cross-sectional areas. The free cross-sectional area
is related to the voidage ().
The introduction of liquid into the tower increases the frictional resistance and
viscous drag affecting gas flow and so the pressure drop is greater in the wet
tower than in the dry tower. If the gas flow rate remains constant, the pressure
drop will increase with an increase in the liquid flow rate. This occurs because as
the liquid fills the voids in the column, the cross-sectional area available for gas
flow is reduced. Up to the loading point, the pressure drop graphs (P vs V) at
constant liquid rate show slopes that are fairly linear and approximately equal to
that of the dry run.
Above the loading point, an increase in slope occurs, indicating a more rapidly
increasing pressure drop with increasing gas velocity. This continues until gas
can no longer pass freely up the column, nor the liquid pass freely down it. The
frictional drag becomes so great that the downward flow of liquid is substantially
impeded and the column is to flood. At the flooding point, the slope becomes
41
exponential and the drag force of the gas bubbling through the downcoming
liquid is the predominate cause of the pressure drop (Pflood ) across the column
Equipment Setup
42
.
Figure 2: Schematic diagram of Gas Absorption Column (Edibon M7,
Spain).
Procedure
E. Preparation of the Experiment:
(12) The column must be dried by passing the maximum air flow until all
evidence of moisture in the packing has disappeared.
(13) Connect the column top and bottom to the water manometer.
43
3. Take manometer readings of pressure differential across the
column for a range of air flow rates.
b. Wet Column Experiment:
i. Switch on the water pump.
ii. Switch on the air compressor.
iii. Adjut the water flowrate at certain flow rate.
iv. Take manometer readings of pressure differential across the
column for a range of air flow rates.
v. Repeat the previous steps for a range of water flow rates.
44
U7. Molecular Diffusion in Gases
1. Objectives:
1) To come up with experimental procedure to determine the diffusion
coefficient of a gas by evaporation from a liquid surface for acetone-air
system.
2) To compare the experimental value of the diffusion coefficient obtained with
theoretical predictions.
2. Introduction:
Fick’s law of proportionality, DAB, is known as the diffusion coefficient. Diffusivity is
one of the important properties of fluids. Fluid flow and mass transfer operations
depend partially on this property and such data is always needed in plant design.
The diffusion coefficient depends on the pressure, the temperature and the
composition of the system. Specifically, the gas-phase diffusion coefficient is
• an inverse function of total system pressure
DAB α 1/P
• a 3/2 power-law function of the absolute temperature
DAB α T 3/2
For gaseous diffusion taking place, diffusion coefficients DAB and DBA are equal.
(This is not the case for liquid diffusion) [“Pseudo-Steady-State Diffusion” in
[Chapter 26] Welty textbook, page 409]
45
Figure 1 Image of the gaseous diffusion apparatus
Modern versions of the kinetic theory have been attempted to account for forces
of attraction and repulsion between the molecules. Hirschfelder et al. (1949)
using Lennard-Jones potential to evaluate the influence of the molecular forces,
46
presented an equation for the diffusion coefficient for gas pairs of nonpolar, no
reacting molecules:
1/ 2
1 1
0.001858 T 3/ 2
+
D AB ,theo = MA MB
1
Pσ AB Ω D
2
= A B 2
k k k
σ AB = 1 / 2(σ A + σ B ) 3
3. Apparatus
The equipment consists of acrylic assembly which is subdivided into two
compartments. One compartment (4) is constructed from clear acrylic and is used
as a constant temperature water bath. The other compartment (15) incorporates
an air pump and the necessary electrical controls for the equipment. The assembly
is mounted on adjustable feet (6). Water in the bath is heated by a cartridge
element (7) which is controlled by an adjustable on/off temperature controller (11)
connected to a PTC temperature sensor (3) mounted in the wall of the bath.
Temperature in the bath is also indicated on a glass thermometer (1) mounted in
a gland on top of the bath. Air is supplied to the capillary tube via a flexible tube
(17) connected to the air pump. The air pump is switched on by operating the right
hand mains switch (14). The height of the liquid in the capillary tube is monitored
using a travelling microscope (10) mounted on a removable support stand (9)
which incorporates a vernier height gauge (8). The water bath is fitted with a lever
operated cock (5) to facilitate drainage using a piece of flexible tubing.
The equipment is connected to the electrical supply using the integral cable (13).
An Earth Leakage Circuit Breaker (RCCB) is installed at the right-hand end of the
equipment to protect the user in the event of an electrical fault. The electrical
components are protected by a mains fuse mounted at the rear of the equipment.
47
Note: The water bath will be damaged if the water temperature exceeds 80°C.
Ensure that the temperature controller is not set above 60°C in use.
48
The equipment is designed for bench-mounting on a firm level surface. It is a self
contained unit and needs only a temporary supply hose to the water bath, for initial
filling.
4. Safety Aspects:
This equipment is designed for safe operation. However there can be potential
hazards arising from the following:
1. Injury through misuse
2. Injury from electric shock
3. Burns from components at high temperature
4. Risk of infection through lack of cleanliness
Accidents can be avoided if the equipment is regularly maintained and staff and
students are made aware of potential hazards. Students must be supervised by a
competent member of staff at all times when in the laboratory. No one should
operate the equipment alone, do not leave the equipment unattended.
However, to give increased operator protection, Armfield Ltd have incorporated an
Earth Leakage Circuit Breaker (ELCB, alternatively called a Residual Current
Circuit Breaker or RCCB) as an integral part of this equipment. If through misuse
or accident the equipment becomes electrically dangerous, an ELCB will switch off
the electrical supply and reduce the severity of any electric shock received by an
operator to a level which, under normal circumstances, will not cause injury to that
person.
5. References
1. Lab Manual – Course handout, Chemical Engineering Department, Qatar
University.
2. Welty, J. R., C. E. Wicks, R. E. Wilson, G. L. Rorrer, Fundamentals of
Momentum, Heat, and Mass Transfer, Chapters 24 and 26, 5th Edition, John
Wiley & Sons, Inc.
49
50