Dixell xr20c
Dixell xr20c
Dixell xr20c
,QVWDOOLQJDQG2SHUDWLQJ,QVWUXFWLRQV
Digital controller with off cycle defrost
SET: To display target set point; in programming mode it selects a parameter or confirm an operation.
XR20C
CONTENTS 1. GENERAL WARNING___________________________________________ 2. GENERAL DESCRIPTION _______________________________________ 3. CONTROLLING LOADS _________________________________________ 4. FRONT PANEL COMMANDS_____________________________________ 5. TEMPERATURE ALARM AND ITS DURATION RECORDING (HACCP) ___ 6. MAIN FUNCTIONS _____________________________________________ 7. PARAMETERS ________________________________________________ 8. DIGITAL INPUT________________________________________________ 9. INSTALLATION AND MOUNTING _________________________________ 10. ELECTRICAL CONNECTIONS ___________________________________ 11. HOW TO USE THE HOT KEY ____________________________________ 12. ALARM SIGNALS ______________________________________________ 13. TECHNICAL DATA _____________________________________________ 14. CONNECTIONS _______________________________________________ 15. DEFAULT SETTING VALUES ____________________________________ 1 1 1 1 1 1 2 2 3 3 3 3 3 3 4
' (UP): To see the last temperature alarm happened; in programming mode it browses the parameter codes or increases the displayed value. & (DOWN) To see the last temperature alarm happened; in programming mode it
browses the parameter codes or decreases the displayed value. To lock & unlock the keyboard. To enter in programming mode. To return to the room temperature display. KEY COMBINATIONS:
1. GENERAL WARNING
1.1 PLEASE READ BEFORE USING THIS MANUAL
This manual is part of the product and should be kept near the instrument for easy and quick reference. The instrument shall not be used for purposes different from those described hereunder. It cannot be used as a safety device. Check the application limits before proceeding.
Flashing -Programming Phase (flashing with - Anti-short cycle delay enabled ON Defrost enabled Flashing - Programming Phase (flashing with ON An temperature alarm happened
1.2
SAFETY PRECAUTIONS
Check the supply voltage is correct before connecting the instrument. Do not expose to water or moisture: use the controller only within the operating limits avoiding sudden temperature changes with high atmospheric humidity to prevent formation of condensation Warning: disconnect all electrical connections before any kind of maintenance. Fit the probe where it is not accessible by the End User. The instrument must not be opened. In case of failure or faulty operation send the instrument back to the distributor or to Dixell s.r.l. (see address) with a detailed description of the fault. Consider the maximum current which can be applied to each relay (see Technical Data). Ensure that the wires for probes, loads and the power supply are separated and far enough from each other, without crossing or intertwining. In case of applications in industrial environments, the use of mains filters (our mod. FT1) in parallel with inductive loads could be useful.
Alarm duration
Tim e
5.1 HOW TO SEE THE ALARM DURATION AND MAX (MIN) TEMPERATURE
If the alarm LED is on, an alarm has taken place. To see the kind of alarm, the max (min) reached temperature and alarm duration do as follows: 1. Push the Up or Down key. 2. On the display the following message is shown:: HAL for high temperature alarm (LAL fot the minimum allarm), followed by the Maximum (minimum) temperature. Then the tiM (tiMe) message is displayed, followed by the Duration in h.mm. 3. Then the instrument displays the temperature once again. NOTE1: if an alarm is still occurring the tim shows the partial duration. NOTE2: the alarm is recorded when the temperature come back to normal values
2. GENERAL DESCRIPTION
Model XR20C, format 32 x 74 mm, is a digital termostat with off cycle defrost designed for refrigeration applications at normal temperature. It provides a relay output to drive the compressor and a PTC or NTC probe input. A internal timer manages the off cycle defrost. The instrument is fully configurable through special parameters that can be easily programmed through the keyboard.
3. CONTROLLING LOADS
3.1 COMPRESSOR
The regulation is performed according to the temperature measured by the thermostat probe with a positive differential from the set point: if the temperature increases and reaches set point plus differential the compressor is started and then turned off when the temperature reaches the set point value again.
6. MAIN FUNCTIONS
6.1 HOW TO SEE THE SETPOINT
In case of fault in the thermostat probe the start and stop of the compressor are timed through parameters COn and COF. 1. Push and immediately release the SET key: the display will show the Set point value;
3.2 DEFROST
Defrost is performed through a simple stop of the compressor. Parameter IdF controls the interval between defrost cycles, while its length is controlled by parameter MdF.
2.
Push and immediately release the SET key or wait for 5 seconds to display the probe value again.
' &
;5&
1/4
,QVWDOOLQJDQG2SHUDWLQJ,QVWUXFWLRQV
&
&
' &
'
6.5.2 HOW TO MOVE A PARAMETER FROM THE HIDDEN MENU TO THE FIRST LEVEL AND VICEVERSA. Each parameter present in the HIDDEN MENU can be removed or put into THE FIRST LEVEL (user level) by pressing SET + . In HIDDEN MENU when a parameter is present in First Level the decimal point is on.
&
1. 2. 3.
Keep pressed for more than 3 s the and keys. The POF message will be displayed and the keyboard will be locked. At this point it will be possible only to see the set point or the MAX o Min temperature stored If a key is pressed more than 3s the POF message will be displayed.
'
&
'
The compressor operates in continuous mode for the time set through the CCt parameter. The cycle can be terminated before the end of the set time using the same activation key for 3 seconds.
DISPLAY CF Temperature measurement unit: C=Celsius; F=Fahrenheit. WARNING: When the measurement unit is changed the SET point and the values of the parameters Hy, LS, US, Ot, ALU and ALL have to be checked and modified if necessary). rES Resolution (for C): (in = 1C; dE = 0.1 C) allows decimal point display. DEFROST IdF Interval between defrost cycles: (0120h) Determines the time interval between the beginning of two defrost cycles. MdF (Maximum) length for defrost: (0255min) When P2P = n, (not evaporator probe: timed defrost) it sets the defrost duration, when P2P = y (defrost end based on temperature) it sets the maximum length for defrost. dFd Temperature displayed during defrost: (rt = real temperature; it = temperature at defrost start; SEt = set point; dEF = dEF label) dAd MAX display delay after defrost: (0255min). Sets the maximum time between the end of defrost and the restarting of the real room temperature display. ALARMS ALC Temperature alarms configuration: (Ab; rE) Ab= absolute temperature: alarm temperature is given by the ALL or ALU values. rE = temperature alarms are referred to the set point. Temperature alarm is enabled when the temperature exceeds the SET+ALU or SET-ALL values. ALU MAXIMUM temperature alarm: (SET110C; SET230F) when this temperature is reached the alarm is enabled, after the ALd delay time. ALL Minimum temperature alarm: (-50.0 SETC; -58230F when this temperature is reached the alarm is enabled, after the ALd delay time. ALd Temperature alarm delay: (0255 min) time interval between the detection of an alarm condition and alarm signalling. dAO Exclusion of temperature alarm at startup: (from 0.0 min to 23.5h) time interval between the detection of the temperature alarm condition after instrument power on and alarm signalling. DIGITAL INPUT i1P Digital input polarity: oP: the digital input is activated by opening the contact; CL: the digital input is activated by closing the contact. i1F Digital input configuration: EAL = external alarm: EA message is displayed; bAL = serious alarm CA message is displayed. PAL = pressure switch alarm, CA message is displayed; dor = door switch function; dEF = activation of a defrost cycle; LHt =not enabled; Htr = kind of action inversion (cooling heating). did: (0255 min) with i1F= EAL or i1F = bAL digital input alarm delay: delay between the detection of the external alarm condition and its signalling. with i1F= dor: door open signalling delay with i1F = PAL: time for pressure switch function: time interval to calculate the number of the pressure switch activation. nPS Pressure switch number: (0 15) Number of activation of the pressure switch, during the did interval, before signalling the alarm event (I2F= PAL). If the nPS activation in the did time is reached, switch off and on the instrument to restart normal regulation. odc Compressor status when open door: no, Fan = normal; CPr, F_C = Compressor OFF OTHER PbC Type of probe: it allows to set the kind of probe used by the instrument: PbC = PBC probe, ntC = NTC probe. rEL Software release for internal use. Ptb Parameter table code: readable only.
'
8. DIGITAL INPUT
The free contact digital input is programmable in five different configurations by the i1F parameter.
7. PARAMETERS
NOTE: the parameters preceded by dots are in the Hidden Menu. REGULATION Hy Differential: (0,1 25,5C / 1255 F) Intervention differential for set point. Compressor Cut IN is Set Point Plus Differential (Hy). Compressor Cut OUT is when the temperature reaches the set point. LS Minimum set point: (- 50CSET/-58FSET): Sets the minimum acceptable value for the set point. US Maximum set point: (SET110C/ SET230F). Set the maximum acceptable value for set point. Ot Thermostat probe calibration: (-12.012.0C; -120120F) allows to adjust possible offset of the thermostat probe. OdS Outputs activation delay at start up: (0255min) This function is enabled at the initial start up of the instrument and inhibits any output activation for the period of time set in the parameter. AC Anti-short cycle delay: (050 min) minimum interval between the compressor stop and the following restart. CCt Compressor ON time during continuous cycle: (0.024.0h; res. 10min) Allows to set the length of the continuous cycle: compressor stays on without interruption for the CCt time. Can be used, for instance, when the room is filled with new products. COn Compressor ON time with faulty probe: (0255 min) time during which the compressor is active in case of faulty thermostat probe. With COn=0 compressor is always OFF. COF Compressor OFF time with faulty probe: (0255 min) time during which the compressor is OFF in case of faulty thermostat probe. With COF=0 compressor is always active. CH Type of action: CL = cooling; Ht = heating. 1592007210 XR20C GB r1.0 15.05.2003.doc
;5&
2/4
,QVWDOOLQJDQG2SHUDWLQJ,QVWUXFWLRQV
12. ALARM SIGNALS
Message Cause P1 Room probe failure HA LA dA EA CA CA Maximum temperature alarm Minimum temperature alarm Door open External alarm Serious external alarm (i1F=bAL) Pressure switch alarm (i1F=PAL)
Outputs Compressor output according to par. Con and COF Outputs unchanged. Outputs unchanged. Regulation restarts Output unchanged. All outputs OFF. All outputs OFF
If the nPS activation in the did time is reached, switch off and on the instrument to restart normal regulation.
The temperature range allowed for correct operation is 060 C. Avoid places subject to strong vibrations, corrosive gases, excessive dirt or humidity. The same recommendations apply to probes. Let air circulate by the cooling holes.
14. CONNECTIONS
14.1 XR20C: 8A COMPRESSOR
Room
8(3)A250V
Comp
Line N.C .
Hot Key
'
12Vac/dc supply: connect to the terminals 7 and 8. 24Vac/dc supply: connect to the terminals 7 and 8. 120Vac supply: connect to the terminals 7 and 8.
NOTE: the Err message is displayed for failed programming. In this case push again key if you want to restart the upload again or remove the Hot key to abort the operation.
'
Hot Key Comp
4. 5.
NOTE the message Err is displayed for failed programming. In this case turn the unit off and then on if you want to restart the download again or remove the Hot key to abort the operation.
12Vac/dc supply: connect to the terminals 7 and 8. 24Vac/dc supply: connect to the terminals 7 and 8. 120Vac supply: connect to the terminals 7 and 8.
;5&
3/4
,QVWDOOLQJDQG2SHUDWLQJ,QVWUXFWLRQV
0 255 min
rE= related to set; Ab = absolute Set110.0C; Set230F -50.0CSet/ -58FSet
MAXIMUM temperature alarm Minimum temperature alarm Temperature alarm delay Delay of temperature alarm at start up i1P Digital input polarity i1F Digital input configuration
did Digital input alarm delay Nps Number of activation of pressure switch odc Compressor status with open door: PbC Kind of probe rEL Software release Ptb Map code Hidden parameters
0255min
0 15 no, Fan = normal; CPr; F_C = Compr. OFF; Ptc; ntc
5 15 no ntc/Ptc 4.0 -
---