Digital controller with off cycle defrost



SET: To display target set point; in programming mode it selects a parameter or confirm an operation.

XR20C
CONTENTS 1. GENERAL WARNING___________________________________________ 2. GENERAL DESCRIPTION _______________________________________ 3. CONTROLLING LOADS _________________________________________ 4. FRONT PANEL COMMANDS_____________________________________ 5. TEMPERATURE ALARM AND ITS DURATION RECORDING (HACCP) ___ 6. MAIN FUNCTIONS _____________________________________________ 7. PARAMETERS ________________________________________________ 8. DIGITAL INPUT________________________________________________ 9. INSTALLATION AND MOUNTING _________________________________ 10. ELECTRICAL CONNECTIONS ___________________________________ 11. HOW TO USE THE HOT KEY ____________________________________ 12. ALARM SIGNALS ______________________________________________ 13. TECHNICAL DATA _____________________________________________ 14. CONNECTIONS _______________________________________________ 15. DEFAULT SETTING VALUES ____________________________________ 1 1 1 1 1 1 2 2 3 3 3 3 3 3 4

' (UP): To see the last temperature alarm happened; in programming mode it browses the parameter codes or increases the displayed value. & (DOWN) To see the last temperature alarm happened; in programming mode it
browses the parameter codes or decreases the displayed value. To lock & unlock the keyboard. To enter in programming mode. To return to the room temperature display. KEY COMBINATIONS:

(DEF) To start a manual defrost

' +& SET + & SET + '

4.1 USE OF LEDS


Each LED function is described in the following table. LED MODE ON Compressor enabled FUNCTION )

1. GENERAL WARNING
1.1 PLEASE READ BEFORE USING THIS MANUAL
This manual is part of the product and should be kept near the instrument for easy and quick reference. The instrument shall not be used for purposes different from those described hereunder. It cannot be used as a safety device. Check the application limits before proceeding.

Flashing -Programming Phase (flashing with - Anti-short cycle delay enabled ON Defrost enabled Flashing - Programming Phase (flashing with ON An temperature alarm happened

5. TEMPERATURE ALARM AND ITS DURATION RECORDING (HACCP)


XR20C signals and records temperature alarms, together with their duration and max value reached. See drawing: Ex. High temperature alarm
Tem pera ture M ax Tem p erature A Lu H igh te mp. alarm S et A LL Low te mp . alarm
; ; ;

1.2

SAFETY PRECAUTIONS
Check the supply voltage is correct before connecting the instrument. Do not expose to water or moisture: use the controller only within the operating limits avoiding sudden temperature changes with high atmospheric humidity to prevent formation of condensation Warning: disconnect all electrical connections before any kind of maintenance. Fit the probe where it is not accessible by the End User. The instrument must not be opened. In case of failure or faulty operation send the instrument back to the distributor or to Dixell s.r.l. (see address) with a detailed description of the fault. Consider the maximum current which can be applied to each relay (see Technical Data). Ensure that the wires for probes, loads and the power supply are separated and far enough from each other, without crossing or intertwining. In case of applications in industrial environments, the use of mains filters (our mod. FT1) in parallel with inductive loads could be useful.

Safe food zone

Alarm duration

Tim e

5.1 HOW TO SEE THE ALARM DURATION AND MAX (MIN) TEMPERATURE
If the alarm LED is on, an alarm has taken place. To see the kind of alarm, the max (min) reached temperature and alarm duration do as follows: 1. Push the Up or Down key. 2. On the display the following message is shown:: HAL for high temperature alarm (LAL fot the minimum allarm), followed by the Maximum (minimum) temperature. Then the tiM (tiMe) message is displayed, followed by the Duration in h.mm. 3. Then the instrument displays the temperature once again. NOTE1: if an alarm is still occurring the tim shows the partial duration. NOTE2: the alarm is recorded when the temperature come back to normal values

2. GENERAL DESCRIPTION
Model XR20C, format 32 x 74 mm, is a digital termostat with off cycle defrost designed for refrigeration applications at normal temperature. It provides a relay output to drive the compressor and a PTC or NTC probe input. A internal timer manages the off cycle defrost. The instrument is fully configurable through special parameters that can be easily programmed through the keyboard.

3. CONTROLLING LOADS
3.1 COMPRESSOR
The regulation is performed according to the temperature measured by the thermostat probe with a positive differential from the set point: if the temperature increases and reaches set point plus differential the compressor is started and then turned off when the temperature reaches the set point value again.

5.2 HOW TO RESET A RECORDED ALARM OR ONE THAT IS STILL OCCURRING


1. 2. Hold the SET key pressed for more than 3s, while the recorded alarm is displayed. (the rSt message will be displayed) To confirm the operation, the rSt message starts blinking and the normal temperature will be displayed.

6. MAIN FUNCTIONS
6.1 HOW TO SEE THE SETPOINT
In case of fault in the thermostat probe the start and stop of the compressor are timed through parameters COn and COF. 1. Push and immediately release the SET key: the display will show the Set point value;

3.2 DEFROST
Defrost is performed through a simple stop of the compressor. Parameter IdF controls the interval between defrost cycles, while its length is controlled by parameter MdF.

2.

Push and immediately release the SET key or wait for 5 seconds to display the probe value again.

6.2 HOW TO CHANGE THE SETPOINT


1. 2. 3. 4. Push the SET key for more than 2 seconds to change the Set point value; LED starts blinking; The value of the set point will be displayed and the arrows within 10s. or To change the Set value push the To memorise the new set point value push the SET key again or wait 10s.

4. FRONT PANEL COMMANDS

' &

6.3 HOW TO START A MANUAL DEFROST


Push the DEF key for more than 2 seconds and a manual defrost will start.

1592007210 XR20C GB r1.0 15.05.2003.doc

;5&

1/4

 

,QVWDOOLQJDQG2SHUDWLQJ,QVWUXFWLRQV



6.4 HOW TO CHANGE A PARAMETER VALUE


To change the parameters value operate as follows: 1. Enter the Programming mode by pressing the Set and DOWN key for 3s ( and start blinking). 2. Select the required parameter. 3. Press the SET key to display its value (now only the LED is blinking). 4. Use UP or DOWN to change its value. 5. Press SET to store the new value and move to the following parameter. To exit: Press SET + UP or wait 15s without pressing a key. NOTE: the set value is stored even when the procedure is exited by waiting the time-out to expire.

6.5 THE HIDDEN MENU


The hidden menu Includes all the parameters of the instrument. HOW TO ENTER THE HIDDEN MENU 1. Enter the Programming mode by pressing the Set + key for 3s (LED 1 and start blinking). 2. When a parameter is displayed keep pressed the Set+ for more than 7s. The Pr2 label will be displayed immediately followed from the HY parameter. NOW YOU ARE IN THE HIDDEN MENU. 3. Select the required parameter. 4. Press the SET key to display its value (Now only the LED is blinking). 5. Use or to change its value. 6. Press SET to store the new value and move to the following parameter. or wait 15s without pressing a key. To exit: Press SET + NOTE: the set value is stored even when the procedure is exited by waiting the time-out to expire. 6.5.1

&

&

' &

'

6.5.2 HOW TO MOVE A PARAMETER FROM THE HIDDEN MENU TO THE FIRST LEVEL AND VICEVERSA. Each parameter present in the HIDDEN MENU can be removed or put into THE FIRST LEVEL (user level) by pressing SET + . In HIDDEN MENU when a parameter is present in First Level the decimal point is on.

&

6.6 HOW TO LOCK THE KEYBOARD

1. 2. 3.

Keep pressed for more than 3 s the and keys. The POF message will be displayed and the keyboard will be locked. At this point it will be possible only to see the set point or the MAX o Min temperature stored If a key is pressed more than 3s the POF message will be displayed.

'

&

6.7 TO UNLOCK THE KEYBOARD


Keep pressed together for more than 3s the will be displayed.

' and & keys, till the Pon message

6.8 THE CONTINUOUS CYCLE


When defrost is not in progress, it can be activated by holding the key pressed for about 3 seconds.

'

The compressor operates in continuous mode for the time set through the CCt parameter. The cycle can be terminated before the end of the set time using the same activation key for 3 seconds.

DISPLAY CF Temperature measurement unit: C=Celsius; F=Fahrenheit. WARNING: When the measurement unit is changed the SET point and the values of the parameters Hy, LS, US, Ot, ALU and ALL have to be checked and modified if necessary). rES Resolution (for C): (in = 1C; dE = 0.1 C) allows decimal point display. DEFROST IdF Interval between defrost cycles: (0120h) Determines the time interval between the beginning of two defrost cycles. MdF (Maximum) length for defrost: (0255min) When P2P = n, (not evaporator probe: timed defrost) it sets the defrost duration, when P2P = y (defrost end based on temperature) it sets the maximum length for defrost. dFd Temperature displayed during defrost: (rt = real temperature; it = temperature at defrost start; SEt = set point; dEF = dEF label) dAd MAX display delay after defrost: (0255min). Sets the maximum time between the end of defrost and the restarting of the real room temperature display. ALARMS ALC Temperature alarms configuration: (Ab; rE) Ab= absolute temperature: alarm temperature is given by the ALL or ALU values. rE = temperature alarms are referred to the set point. Temperature alarm is enabled when the temperature exceeds the SET+ALU or SET-ALL values. ALU MAXIMUM temperature alarm: (SET110C; SET230F) when this temperature is reached the alarm is enabled, after the ALd delay time. ALL Minimum temperature alarm: (-50.0 SETC; -58230F when this temperature is reached the alarm is enabled, after the ALd delay time. ALd Temperature alarm delay: (0255 min) time interval between the detection of an alarm condition and alarm signalling. dAO Exclusion of temperature alarm at startup: (from 0.0 min to 23.5h) time interval between the detection of the temperature alarm condition after instrument power on and alarm signalling. DIGITAL INPUT i1P Digital input polarity: oP: the digital input is activated by opening the contact; CL: the digital input is activated by closing the contact. i1F Digital input configuration: EAL = external alarm: EA message is displayed; bAL = serious alarm CA message is displayed. PAL = pressure switch alarm, CA message is displayed; dor = door switch function; dEF = activation of a defrost cycle; LHt =not enabled; Htr = kind of action inversion (cooling heating). did: (0255 min) with i1F= EAL or i1F = bAL digital input alarm delay: delay between the detection of the external alarm condition and its signalling. with i1F= dor: door open signalling delay with i1F = PAL: time for pressure switch function: time interval to calculate the number of the pressure switch activation. nPS Pressure switch number: (0 15) Number of activation of the pressure switch, during the did interval, before signalling the alarm event (I2F= PAL). If the nPS activation in the did time is reached, switch off and on the instrument to restart normal regulation. odc Compressor status when open door: no, Fan = normal; CPr, F_C = Compressor OFF OTHER PbC Type of probe: it allows to set the kind of probe used by the instrument: PbC = PBC probe, ntC = NTC probe. rEL Software release for internal use. Ptb Parameter table code: readable only.

'

8. DIGITAL INPUT
The free contact digital input is programmable in five different configurations by the i1F parameter.

7. PARAMETERS
NOTE: the parameters preceded by dots are in the Hidden Menu. REGULATION Hy Differential: (0,1 25,5C / 1255 F) Intervention differential for set point. Compressor Cut IN is Set Point Plus Differential (Hy). Compressor Cut OUT is when the temperature reaches the set point. LS Minimum set point: (- 50CSET/-58FSET): Sets the minimum acceptable value for the set point. US Maximum set point: (SET110C/ SET230F). Set the maximum acceptable value for set point. Ot Thermostat probe calibration: (-12.012.0C; -120120F) allows to adjust possible offset of the thermostat probe. OdS Outputs activation delay at start up: (0255min) This function is enabled at the initial start up of the instrument and inhibits any output activation for the period of time set in the parameter. AC Anti-short cycle delay: (050 min) minimum interval between the compressor stop and the following restart. CCt Compressor ON time during continuous cycle: (0.024.0h; res. 10min) Allows to set the length of the continuous cycle: compressor stays on without interruption for the CCt time. Can be used, for instance, when the room is filled with new products. COn Compressor ON time with faulty probe: (0255 min) time during which the compressor is active in case of faulty thermostat probe. With COn=0 compressor is always OFF. COF Compressor OFF time with faulty probe: (0255 min) time during which the compressor is OFF in case of faulty thermostat probe. With COF=0 compressor is always active. CH Type of action: CL = cooling; Ht = heating. 1592007210 XR20C GB r1.0 15.05.2003.doc

8.1 DOOR SWITCH INPUT (i1F = dor)


It signals the door status and the corresponding relay output status through the odc parameter: no, Fan = normal (any change); CPr, F_C = Compressor OFF; Since the door is opened, after the delay time set through parameter did, the door alarm is enabled, the display shows the message dA and the regulation restarts. The alarm stops as soon as the external digital input is disabled again. With the door open, the high and low temperature alarms are disabled.

8.2 GENERIC ALARM (i1F = EAL)


As soon as the digital input is activated the unit will wait for did time delay before signalling the EAL alarm message. The outputs status dont change. The alarm stops just after the digital input is de-activated.

8.3 SERIOUS ALARM MODE (i1F = bAL)


When the digital input is activated, the unit will wait for did delay before signalling the CA alarm message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-activated.

8.4 PRESSURE SWITCH (i1F = PAL)


If during the interval time set by did parameter, the pressure switch has reached the number of activation of the nPS parameter, the CA pressure alarm message will be displayed. The compressor and the regulation are stopped. When the digital input is ON the compressor is always OFF.

;5&

2/4

 

,QVWDOOLQJDQG2SHUDWLQJ,QVWUXFWLRQV
12. ALARM SIGNALS
Message Cause P1 Room probe failure HA LA dA EA CA CA Maximum temperature alarm Minimum temperature alarm Door open External alarm Serious external alarm (i1F=bAL) Pressure switch alarm (i1F=PAL)


Outputs Compressor output according to par. Con and COF Outputs unchanged. Outputs unchanged. Regulation restarts Output unchanged. All outputs OFF. All outputs OFF

If the nPS activation in the did time is reached, switch off and on the instrument to restart normal regulation.

8.5 START DEFROST (i1F = dFr)


It starts a defrost if there are the right conditions. After the defrost is finished, the normal regulation will restart only if the digital input is disabled otherwise the instrument will wait until the MdF safety time is expired.

8.6 INVERSION OF THE KIND OF ACTION: HEATINGCOOLING (i1F = Htr)


This function allows to invert the regulation of the controller: from cooling to heating and viceversa.

12.1 ALARM RECOVERY


Probe alarm P1 starts some seconds after the fault in the related probe; it automatically stops some seconds after the probe restarts normal operation. Check connections before replacing the probe. Temperature alarms HA and LA automatically stop as soon as the thermostat temperature returns to normal values and when defrost starts. Alarms EA and CA (with i1F=bAL) recover as soon as the digital input is disabled. Alarm CA (with i1F=PAL) recovers only by switching off and on the instrument.

8.7 DIGITAL INPUTS POLARITY


The digital input polarity depends on the i1P parameter. i1P=CL: the input is activated by closing the contact. i1P=OP: the input is activated by opening the contact

9. INSTALLATION AND MOUNTING


Instrument XR20C shall be mounted on vertical panel, in a 29x71 mm hole, and fixed using the special bracket supplied. To obtain an IP65 protection grade use the front panel rubber gasket (mod. RG-C) as shown in figure.

13. TECHNICAL DATA


Housing: self extinguishing ABS. Case: XR20C frontal 32x74 mm; depth 60mm; Mounting: XR20C panel mounting in a 71x29mm panel cut-out Protection: IP20. Frontal protection: IP65 with frontal gasket RG-C (optional). 2 Connections: Screw terminal block 2,5 mm wiring. Power supply: according to the model: 12Vac/dc, 10%; 24Vac/dc, 10%; 230Vac 10%, 50/60Hz, 110Vac 10%, 50/60Hz Power absorption: 3VA max Display: 3 digits, red LED, 14,2 mm high. Inputs: 1 NTC or PTC probe. Digital input: free contact Relay outputs compressor: SPDT relay 8(3) A, 250Vac or SPST relay 20(8)A; 250Vac Data storing: on the non-volatile memory (EEPROM). Kind of action: 1B; Pollution grade: normal; Software class: A. Operating temperature: 060 C. Storage temperature: -3085 C. Relative humidity: 2085% (no condensing) Measuring and regulation range: NTC probe: -40110C (-40230F) PTC probe: -50150C (-58302F) Resolution: 0,1 C or 1C or 1 F (selectable). Accuracy (ambient temp. 25C): 0,7 C 1 digit

The temperature range allowed for correct operation is 060 C. Avoid places subject to strong vibrations, corrosive gases, excessive dirt or humidity. The same recommendations apply to probes. Let air circulate by the cooling holes.

10. ELECTRICAL CONNECTIONS


The instrument is provided with screw terminal block to connect cables with a cross section up to 2,5 mm2. Before connecting cables make sure the power supply complies with the instruments requirements. Separate the probe cables from the power supply cables, from the outputs and the power connections. Do not exceed the maximum current allowed on each relay, in case of heavier loads use a suitable external relay.

14. CONNECTIONS
14.1 XR20C: 8A COMPRESSOR
Room

10.1 PROBE CONNECTION


The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid infiltration. It is recommended to place the thermostat probe away from air streams to correctly measure the average room temperature. Place the defrost termination probe among the evaporator fins in the coldest place, where most ice is formed, far from heaters or from the warmest place during defrost, to prevent premature defrost termination.

   
8(3)A250V

11. HOW TO USE THE HOT KEY


11.1 HOW TO PROGRAM A HOT KEY FROM THE INSTRUMENT (UPLOAD)
1. 2. 3. 4. Program one controller with the front keypad. When the controller is ON, insert the Hot key and push key; the "uPL" message appears followed a by flashing End Push SET key and the End will stop flashing. Turn OFF the instrument remove the Hot Key, then turn it ON again.

  
Comp
Line N.C .

  
Hot Key

'

12Vac/dc supply: connect to the terminals 7 and 8. 24Vac/dc supply: connect to the terminals 7 and 8. 120Vac supply: connect to the terminals 7 and 8.

NOTE: the Err message is displayed for failed programming. In this case push again key if you want to restart the upload again or remove the Hot key to abort the operation.

'

14.2 XR20C: 20A COMPRESSOR


Room

11.2 HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY (DOWNLOAD)


1. 2. 3. Turn OFF the instrument. Insert a programmed Hot Key into the 5 PIN receptacle and then turn the Controller ON. Automatically the parameter list of the Hot Key is downloaded into the Controller memory, the doL message is blinking followed a by flashing End. After 10 seconds the instrument will restart working with the new parameters. Remove the Hot Key..
Line
20(8)A250V

        
Hot Key Comp

4. 5.

NOTE the message Err is displayed for failed programming. In this case turn the unit off and then on if you want to restart the download again or remove the Hot key to abort the operation.

12Vac/dc supply: connect to the terminals 7 and 8. 24Vac/dc supply: connect to the terminals 7 and 8. 120Vac supply: connect to the terminals 7 and 8.

1592007210 XR20C GB r1.0 15.05.2003.doc

;5&

3/4

 

,QVWDOOLQJDQG2SHUDWLQJ,QVWUXFWLRQV



15. DEFAULT SETTING VALUES


Label Set Hy LS US Ot OdS AC CCt COn COF CH CF rES IdF MdF dFd dAd ALc ALU ALL ALd dAO Name Set point Differential Minimum set point Maximum set point Thermostat probe calibration Outputs delay at start up Anti-short cycle delay Continuos cycle duration Compressor ON time with faulty probe Compressor OFF time with faulty probe Kind of action Temperature measurement unit Resolution Interval between defrost cycles (Maximum) length for defrost Displaying during defrost MAX display delay after defrost Temperat. alarms configuration Range LSUS 0,125.5C/ 1 255F -50CSET/-58FSET SET110C/ SET 230F -1212C /-120120F 0255 min 0 50 min 0.024.0h 0 255 min 0 255 min CL=cooling; Ht= heating C F
in=integer; dE= dec.point
1 120 ore 0 255 min rt, it, SEt, DEF

C/F 3.0/37 2.0/4 -40,0/-40 110/230 0.0 0 1


0.0

15 30 CL C/F dE/8 20 it 30 Ab 110/230 -50/-58 15 1.3 cL EAL

0 255 min
rE= related to set; Ab = absolute Set110.0C; Set230F -50.0CSet/ -58FSet

MAXIMUM temperature alarm Minimum temperature alarm Temperature alarm delay Delay of temperature alarm at start up i1P Digital input polarity i1F Digital input configuration

0 255 min 0 23h e 50 oP=opening;CL=closing


EAL=extern. alarm; bAL=lock regulation; PAL=press. switch; dor=door switch; dEF=defrost; LHt=disabled; Htr= cooling heating

did Digital input alarm delay Nps Number of activation of pressure switch odc Compressor status with open door: PbC Kind of probe rEL Software release Ptb Map code Hidden parameters

0255min
0 15 no, Fan = normal; CPr; F_C = Compr. OFF; Ptc; ntc

5 15 no ntc/Ptc 4.0 -

---