13 DX Power Station
13 DX Power Station
13 DX Power Station
Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
038 POWER STATION
038 POWER STATION 1 23.2 Aug 1600 2130 23.9 630.5 3.38
No data is available for this report. Space by space ventilation calculations were not performed for this air system because it uses the 'user-defined' sizing option. With this option
the system outdoor ventilation air flow is specified directly by the user. Therefore, space-by-space calculations are not performed.
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 0.788 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 3463.3 BTU/(hr-CFM)
Site Altitude = 8466.0 ft
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 0.788 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 3463.3 BTU/(hr-CFM)
Site Altitude = 8466.0 ft