MGC100 en
MGC100 en
MGC100 en
USER MANUAL
CONTENT
1 OVERVIEW ......................................................................................................................................................5
2 PERFORMANCE AND CHARACTERS ............................................................................................................5
3 SPECIFICATION ..............................................................................................................................................6
4 OPERATION ....................................................................................................................................................7
4.1 PUSHBUTTONS .......................................................................................................................................7
4.2 CONTROLLER PANEL AND ICON DESCRIPTION ..................................................................................7
4.2.1 CONTROLLER PANEL .......................................................................................................................7
4.2.2 ALARM ICON INDICATION ...............................................................................................................8
4.2.3 PANEL INDICATOR ...........................................................................................................................8
4.3 OPERATION .............................................................................................................................................8
4.3.1 REMOTE START SEQUENCE............................................................................................................8
4.3.2 REMOTE STOP SEQUENCE ..............................................................................................................8
4.3.3 MANUAL START/STOP ....................................................................................................................9
5 PROTECTION ..................................................................................................................................................9
6 CONNECTION .............................................................................................................................................. 10
7 DEFINITION AND RANGE OF PARAMETERS ............................................................................................. 11
8 PARAMETERS SETTING ............................................................................................................................. 14
8.1 PARAMETERS REGULATION ............................................................................................................... 14
8.2 RESTORE FACTORY SETTINGS ........................................................................................................... 14
8.3 ELIMINATE ACCUMULATED TIME ...................................................................................................... 14
9 CASE DIMENSIONS ..................................................................................................................................... 15
10 TYPICAL APPLICATION ............................................................................................................................ 16
11 FAULT FINDING ......................................................................................................................................... 16
All rights reserved. No part of this publication may be reproduced in any material form (including
photocopying or storing in any medium by electronic means or other) without the written permission of
the copyright holder.
SmartGen reserves the right to change the contents of this document without prior notice.
Sign Instruction
MGC100 Petrol Genset Controller is designed for start and protection of single genset. It allows
manual and remote start/stop, data measurement, alarm indication, shutdown protection functions.
The controller fit with LED display, button-press operation, and it achieves precise measurement of
various parameters, protection and control of genset. All of parameters can be configured from front
panel. The controller which can be widely used in data display and fault protection of a number of small
diesel and petrol genset with easy operation, reliable work, compact structure and simple connections.
Item Contents
DC9.0V to 18.0V, continuous power supply (suitable for DC12V
Working Voltage
system)
Overall Consumption Regular working:<1W (Standby mode:<0.4W)
AC Volt Input:
3-phase 4-wire AC 30V – AC 360V (ph-N)
3-phase 3-wire AC 50V – AC 620V (ph-ph)
2-phase 3-wire AC 30V – AC 360V (ph-N)
Single phase 2-wire AC 30V – AC 360V (ph-N)
AC Frequency 50Hz/60Hz
Speed Sensor Voltage 1.0V to 24V(effective value)
Speed Sensor Frequency 10000Hz (Max)
Start Relay 7A DC12V power supply
Fuel Relay 7A DC12V power supply
Flexible Transistor 1A DC12V connect to (B+)
Overall Dimensions 105.8mm x 61mm x 36.6mm
Panel Cutout 92mm x 44mm
Working Temperature (-25~+70)°C
Working Humidity (20~93)%RH
Storage Temperature (-25~+70)°C
Protection Level IP55 Gasket
Apply AC2.2kV voltage between high voltage terminal and low
Insulation voltage terminal; The leakage current is not more than 3mA within
1min.
Weight 94g
4.1 PUSHBUTTONS
Working status indicator: in start delay duration, start indicator will blink; in other working duration,
the indicator will always light; in stop status, the indicator will extinguish.
Stop status indicator: in stop process, stop indicator will blink; in stop duration, the indicator will
always light; in start status, the indicator will extinguish.
4.3 OPERATION
a) After remote start, when remote start signal is invalid, “Stop Delay” timer is initiated;
b) Once this “stop delay” has expired, the “Cooling Delay” is then initiated;
c) During “Stop Idle” Delay (if configured), idle relay is energized;
d) “ETS Solenoid Hold” begins, ETS relay is energized while fuel relay is de-energized;
e) “Fail to Stop Delay” begins, complete stop is detected automatically;
f) Genset is placed into standby mode after its “After Stop Time”.
a) Press to start genset. It will detect complete start and accelerate to high-speed running
automatically. With high temperature, low oil pressure, over speed and volt abnormal during
genset running, controller can protect it to stop quickly (Please refer to Start Sequence b-g).
b) Press to stop the running genset (Please refer to Stop Sequence b-f).
NOTE:
a) The genset can be stopped manually in remote start status; at this time, remote input is inhibited and it will be
active when remote input is closed again.
b) After start conditions are satisfied, accumulative running timer will be initiated; at the same time, the last
blinking decimal of nixie tube indicates that genset works normally.
5 PROTECTION
1) Low Oil Pressure: detect after Safety On, Alarm Stop when Low Oil Pressure input is active and
lasts for 2s.
2) High Temperature: detect when start, Alarm Stop when High Temperature is active and lasts
for 2s.
3) Over Speed: detect when start, Alarm Stop after duration exceeds Over Speed Stop Delay.
4) Gen Over Volt: Alarm Stop when the controller detects genset voltage exceeds overvoltage
value and delay exceeds abnormal delay.
5) Gen Under Volt: Alarm Stop when the controller detects genset voltage less than under voltage
value and delay less than abnormal delay.
6) Emergency Stop: ETS output immediately when Emergency Stop is active, in the meanwhile
fuel, preheat and start signal are cut off and Emergency Shutdown Alarm Signal is sent.
7) Fail to Start: Alarm Stop when start failed in preset start times.
8) Gen Under Frequency: When genset is normal running, controller detects gen frequency falls
below under frequency value and the “under frequency” delay has expired, under frequency
shutdown alarm will be sent.
9) Gen Over Frequency: Detection when start genset, if gen frequency exceeds over frequency
value and the “over frequency” delay has expired, over frequency shutdown alarm will be sent.
No. Content
0 Magnetic Sensor
1 Generator
2 Magnetic Sensor + Generator
NOTE:
1) Magnetic sensor is magnetic device which detects numbers of flywheel teeth installed in generator.
2) If magnetic sensor is selected, please insure numbers of flywheel teeth is same with set value, otherwise,
“Over Speed Shutdown” may be caused.
3) If genset without magnetic sensor, please don’t select corresponding items, otherwise, “Start Failure” may be
caused.
4) If generate isn’t selected, the controller won’t detect over/under voltage; if magnetic sensor isn’t selected,
speed of genset is converted via generate signal.
When the controller is running, press for 3s, it will enter into parameter number menu and LED
will display :
2) After parameter number is selected, press to enter into parameter setting menu; press
In emergency stop input status, press and for 5s at the same time, it can restore to
default and “reset” will be displayed on LED.
Press and for 5s at the same time, accumulated running time will be reset an “hclr” will
be displayed on LED.
NOTE:
NOTE: MGC100 controller can suit for widely range of battery voltage DC(9~18)V. Negative of battery must be
connected with the engine shell soundly. The diameter of wire which from power supply to battery must be over 1.0mm2.
If floating charge configured, please firstly connect output wires of charger to battery’s positive and negative directly,
then, connect wires from battery’s positive and negative to controller’s corresponding input ports in order to prevent
charge disturbing the controller’s normal working.
NOTE: Speed sensor is magnetic equipment which is installed on engine body for testing flywheel teeth number. 2
core shielding wire is used for the connection of the sensor and controller. The wire is supposed to be connected to 11
terminal of controller with one end and the other end hanging in the air. The other two signal lines connect separately to
11, 12 terminal. Speed sensor output voltage is supposed to be at AC (1-24)V (virtual value) when it is in full speed range,
and AC12V (when in rated rotate speed) is recommened. When install the speed sensor, screw it to contact the flywheel
firstly, inverse it with 1/3 circle, and then tighten the nut finally.
CAUTION: When controller has been installed in control panel, if the high voltage test is needed, please disconnect
controller’s all terminals in order to prevent high voltage into controller and damage it.
NOTE: When it controls petrol genset, terminal 4 connects with ignition control; when it controls diesel genset,
terminal 5 needs to short connect with B+, terminal 4 needs to connect with fuel output.
11 FAULT FINDING