Gas Insulated

Up to 145kV
Switchgear
GIS
Characteristics
Gas Insulated Switchgear
Up to 145kV
LS’s GIS satisfying your various needs
LS offers the range of GIS(gas-insulated switchgear) from 25.8kV to 420kV for many types
of power plants and substations to satisfy customers various needs.
LS's GIS meets the electric systems requirements of increasing capacity according
to expansion of consumers and large plants.
By opening and closing the circuit breaker under normal and fault condition,
customer can prevent & protect the implemented facilities over the whole system.
LS’s compact size GIS is comparable with other manufactures within the
same rating while
the design and constitution of our GIS offers high reliability, safety and convenience.
We also provide economical & feasible solutions for limited space.
Our products are designed and tested according to the latest international standards
to give our customers the highest quality product.
LS also adopts procedures for production, delivery and technical service
which are fully environment-friendly under control of ISO 14001
for our future generation, which include minimizing the use of SF6 gas.

2
Gas Insulated Switchgear 145kV

Contents 4 Line-up
6 Modular design
8 Circuit breaker module
10 3 position switch & HSES
12 Termination
13 PDPS
14 Layout
17 Technical data
18 Research & development
19 Quality assurance

High reliability and safety

Easy installation and


maintenance convenience

Compact design

Environmental-friendliness
and minimal maintenance cost

3
GIS
Line-up

Leading the future with world class products

Rated voltage (kV) 25.8/36 72.5 145

Rated current (A) ~3150 2000 ~3150

Rated breaking current (kA) ~40 20/31.5 40

Power frequency withstand voltage (kV) 70 140 275

Lightning impulse withstand voltage (kV) ~170 325 650

4
Gas Insulated Switchgear 145kV

170 245 362 420

1250~4000 ~3150 4000~6300 4000

50 40/50 50/63 50

325 460 520 650

750 1050 1175 1425

5
GIS
Modular design

Economical efficiency Environmental-friendliness High appliance


Compact design can reduce space Modules are designed to fit in Modular system can satisfy
requirement and operating costs. optimal space for installation, customers` various needs and
Modular system cuts construction while protecting the environment layout requests.
time and saves costs. thanks to minimal use of SF6 gas.

Convenience Reliability
Modular system makes Maximize system security
our GIS easier to operate. with a minimum
of maintenance.

All typical configuration can be realized


with only a few modules

6
Gas Insulated Switchgear 145kV

72.5kV & 145kV GIS construction

72.5kV GIS

Circuit breaker
Bus disconnector
with maintenance earthing switch
Current transformer
Line DS/ES
High speed earthing switch (HSES)
Cable head
Operating mechanismfor CB
Potential transformer

145kV GIS

Circuit breaker
Bus disconnector
withmaintenance earthingswitch
Current transformer
Line DS/ES
High speed earthingswitch (HSES)
Cable head
Operating mechanismfor CB
Potential transformer

7
GIS
Circuit breaker module

CB & CT module
The 3-phase common circuit breaker (CB),
a core equipment of the GIS, is composed
with current transformer (CT) in one module,
the 3-phase interrupter is simultaneously run
by a motor operation or hydraulic operation.
The motor mechanism is disposed at the
bottom part of the interrupter. The CT can be
installed to incoming or outgoing side, and
also can be composed of several units by
number of CTs.

Operating mechanism for CB


The operating mechanism for circuit breaker
is spring stored-energy type that is installed at
the bottom of the circuit breaker in parallel,
for manual operation and easy to check close-
open status for convenient maintenance.
The circuit breaker mechanism is composed
of separate module which make it a simple
design, highly reliable apparatus made from
the latest technology.
The circuit breaker has a mechanical
endurance capability over 10,000 operations
with minimal use of each part. Closing spring
Also, the circuit breaker mechanism minimizes Trip spring
the influence of temperature. Fly wheel
Trip latch
Closing latch
Closing chain
Motor

8
Gas Insulated Switchgear 145kV

The interrupter unit is applied thermal expansion double flow puffer (self-expansion) type,
Interrupter unit the most effective arc quenching method. This ensures high reliability to terminate accidental
electric current, and minimal mechanical movement from at low operation energy to
minimize stress delivered to the enclosure.
Also, the 3-phase common enclosure is used to minimize the width of bay through interrupt
principle and electric field analysis.

Arc quenching principle

Closed position Contact separation

The current flows continuously The arc is started between the


through the main contacts. arcing contacts.
The gas flows to the arcing
contact from the compression
Upper arcing contact
chamber through the expansion
Nozzle
chamber.
Upper main contact
Lower main contact
Lower arcing contact
Expansion chamber
Compression chamber

Arc quenching Open position

The arc is developed and elongated Current does not flow any more,
between contacts. and recovers the dielectric
Pressure rise in expansion chamber strength between main contacts.
due to the arc.
The expanded and compressed gas
blast into the open gap of arcing
contacts when the current reach to
zero and then extinguish arc.

9
GIS
3 position switch & HSES

The 3 position switch is combination of disconnector and earthing switch put


3 position switch together, and is composed of finger and tulip type contact design.
This eliminates the need for an additional mechanical interlock between the
disconnector and earthing switch, and also electric interlock.
The 3 position switch is installed inside the 3-phase common type enclosure which
operates simultaneously by motor operation, and can be manually operated in case
of emergency.

Line DS/ES & HSES module

Enclosure
Gas barrier
Conductor
Moving Contact
Fixed contact (DS)
Fixed contact (ES)
Earthing Terminal
High Speed earthing switch
Operating mechanism for HSES

10
Gas Insulated Switchgear 145kV

High speed earthing switch has finger type construction.


High speed It is operated by motor spring mechanism and its moving part is inserted
earthing switch in the finger type contact parts with high speed when it is operated.
(HSES)

The 3 position switch operates with conductor rotating twice.


Operating principle The conductor operates clockwise and closes DS when DS and ES is in open, neutral state.
In order to close the ES, the conductor rotates counter-clockwise in first stage and in
second stage the DS is open to a neutral state and closes the ES.

Neutral position Disconnector closed Earthing switch closed

HSES closed HSES open

11
GIS
Termination

The termination units of the GIS connect to the following equipment :


• Overhead line
• Underground cable
• Transformer

Gas to air bushing unit


SF6 gas- to-air bushing is a method that is
generally used to connect overhead line with
GIS or GIS and transformer connection. The
bushing can be made of porcelain or composite
material to satisfy customer requirement.

Cable connection unit


The 3-phase encapsulated type cable
termination is used to connect high voltage
cable to GIS. This connecting method is applied
with conventional type cable sealing end and
plug-in type, and with no special request given
by the user the IEC regulation is applied.

TR termination
This method is used when connecting directly
to the GIS and transformer.
The 3 phase segregated unit of the GIS is used
to connect to gas-to-oil bushing of the
transformer, and expansion joint is provided to
absorb vibration and temperature change
caused by transformer.

12
Gas Insulated Switchgear 145kV
PDPS (Power Equipment Diagnosis & Preventive System)

Through regular monitoring of major power equipment, accidents can be prevented.


Also database management system supports efficient management of events and history for each unit.

[Work station]

GIS /TR/ switchgear diagnosis HMI

1GBps fiber switched ethernet

(DNP3.0 over TCP/IP)

PD DAU RT DAU

System r ack

Lighting Dissolve Gas Oil- Oil-level


UHF PD Gas-Density CB Conditio Others
Arrester Analysis Temperatur Gauge

GIS diagnosis Transformer diagnosis


•Partial discharge (UHF PD) •Oil contained gas concentration
•SF6 gas density monitoring •Insulated oil / winding temperature
•Analysis of circuit breaker operating & condition •FAN driving current / time
•Cumulative breaking current •PUMP driving current / time
•Cable PD monitoring •OLTC operating current / time
•Lightening arrester leakage current

13
GIS
Layout

72.5kV typical bay arrangements

Double bus system (Cable connection) Double bus system (Gas to air bushing)
2,900

3,300
2,150

2,150

5,000 5,170

Single bus system (Cable connection) Bus coupler


2,900

2,150

5,000 4,200

14
Gas Insulated Switchgear 145kV

145kV typical bay arrangements

Double bus system (Cable connection) Double bus system (Gas to air bushing)

3,800
2,650
3,000
2.650

3,850 6,100

Single bus system (Cable connection) Bus coupler


2,650
3,000

4,650 5,100

15
GIS
Layout

Mobile type
• Service for mobility and flexibility
• Standby or temporary power supply
• Service for over-load area
• Replacement in case of equipment failure
• Power supply for isolated areas
• Reduced works and maintenance costs
• Connectivity with the renewable energy

GIS AIS Power transformer Switchgear


Voltage level, Capacity Up to 245kV Up to 145kV 31.5MVA Up to 36kV

HV trailer MV/LV trailer

Single line diagram

Cable

16
Gas Insulated Switchgear 145kV
Technical data

72.5kV 145kV

Rated voltage (kV, rms) 72.5 145

Rated frequency (Hz) 50 / 60 50 / 60

Rated normal current (A, rms) 2000 Up to 3,150

Rated short-duration power-frequency


withstand voltage
- Common (kV, peak) 140 275
- Across the isolating distance (kV, peak) 160 315

Rated lightning impulse withstand voltage


- Common (kV, rms) 325 650
- Across the isolating distance (kV, rms) 375 750

Rated short-circuit breaking current (kA, rms) 31.5 40

Rated break time (Cycle) 3 3

Rated short-time withstand current (kA, rms) 31.5 40

Rated peak withstand current (kA, peak) 79 100

Rated duration of short-circuit (sec) 3 3

Phase arrangements 3 phase common encapsulated

Applicable standards IEC 62271-203, IEC 62271-100, IEC 62271-102

17
GIS
Research & development

LS obtained certification about major research and development tasks in some leading countries
and continues to invest in developing the best GIS product for our customers worldwide.
To produce highest quality GIS, optimized design is conducted through 3D electric field analysis,
arc diagnosis and structure & temperature analysis.

Electro technology R&D center Power testing & technology institute

Multi-physics technology PT&T is a KOLAS-qualified (Korea Laboratory Accreditation


Scheme) accredited testing laboratory and provides worldwide
testing service with its 1,600MVA-capacity high power laboratory,
high voltage laboratory and reliability testing laboratory.

DS/ES unit temperature prediction using electro-


Magnetic field and temperature flow analysis.

Optimized electric Interruption


field control performance analysis

3D electric field analysis Arc movement prediction


is used for effective space to evaluated breaker
design and optimization capability High Voltage Test | Impulse Test

18
Gas Insulated Switchgear 145kV
Quality assurance

Providing high quality products and services to lead customer satisfaction is the motto of LS,
and it is what motivates the company to perfecting zero-defect product.
The quality assurance program by LS provides strict quality control from promotion,
manufacture and delivery in compliance to ISO 9001.
LS’s GIS fully comply with the latest international standards, and acquired type test certificates
for efficient design and excellent quality.
It is our goal to provide world-best product to our customers,
only to be done by maintaining the latest quality system and service.

Certificates

ISO 9001 ISO 14001 OHSAS 18001

KERI CESI KEMA

19
Safety Instructions

For your safety, please read user's manual thoroughly before operating.
Contact the nearest authorized service facility for examination, repair, or adjustment.
Please contact qualified service technician when you need maintenance.
Do not disassemble or repair by yourself!
Any maintenance and inspection shall be performed by the personnel having expertise
concerned.

According to The WEEE Directive, please do not discard the device with your
household waste.

www.ls-electric.com
Headquarter Overseas Branches
LS-ro 127(Hogye-dong) Dongan-gu, Anyang-si, Gyeonggi-Do, 14119, Korea •L
Seoul Office Tel: 81-3-6268-8241 E-Mail: tokyo ls-electric.com
LS Yongsan Tower, 92, Hangang-daero, Yongsan-gu, Seoul, 04386, Korea •LS ELECTRIC Beijing Office (China)
Tel: 82-2-2034-4916, 4684, 4429 Tel: 86-10-5095-1631 E-Mail: china lselectric.com.cn
•LS ELECTRIC Shanghai Office (China)
Overseas Subsidiaries Tel: 86-21-5237-9977 E-Mail: china lselectric.com.cn
•LS ELECTRIC Japan Co., Ltd. (Tokyo, Japan) •LS ELECTRIC Guangzhou Office (China)
Tel: 81-3-6268-8241 E-Mail: japan ls-electric.com Tel: 86-20-3818-2883 E-Mail: china lselectric.com.cn
•LS ELECTRIC (Dalian) Co., Ltd. (Dalian, China) •LS ELECTRIC Chengdu Office (China)
Tel: 86-411-8730-5872 E-Mail: china.dalian lselectric.com.cn Tel: 86-28-8670-3201 E-Mail: china lselectric.com.cn
•LS ELECTRIC (Wuxi) Co., Ltd. (Wuxi, China) •LS ELECTRIC Qingdao Office (China)
Tel: 86-510-6851-6666 E-Mail: china.wuxi lselectric.com.cn Tel: 86-532-8501-2065 E-Mail: china lselectric.com.cn

•LS ELECTRIC Vietnam Co., Ltd. (Hanoi, Vietnam) •LS ELECTRIC Nanjing Office (China)
Tel: 84-93-631-4099 E-Mail: vietnam ls-electric.com Tel: 86-25-8467-0005 E-Mail: china lselectric.com.cn
•LS ELECTRIC Bangkok Office (Thailand)
•LS ELECTRIC Middle East FZE (Dubai, U.A.E.)
Tel: 66-90-950-9683 E-Mail: thailand ls-electric.com
Tel: 971-4-886-5360 E-Mail: middleeast ls-electric.com
•LS ELECTRIC Jakarta Office (Indonesia)
•LS ELECTRIC Europe B.V. (Hoofddorp, Netherlands)
Tel: 62-21-2933-7614 E-Mail: indonesia ls-electric.com
Tel: 31-20-654-1424 E-Mail: europartner ls-electric.com
•LS ELECTRIC Moscow Office (Russia)
•LS ELECTRIC America Inc. (Chicago, USA) Tel: 7-499-682-6130 E-Mail: info lselectric-ru.com
Tel: 1-800-891-2941 E-Mail: sales.us lselectricamerica.com
•LS ELECTRIC America Western Office (Irvine, USA)
•LS ENERGY Solutions LLC (Charlotte, USA) Tel: 1-949-333-3140 E-Mail: america ls-electric.com
Tel: 1-704-587-4051 E-Mail: cmfeldman ls-es.com
•LS ELECTRIC India Office (India)
•LS ELECTRIC Turkey Co., Ltd. (Istanbul, Turkey) Tel: 91-80-6142-9108 E-Mail: Info_india ls-electric.com
Tel: 90-212-806-1252 E-Mail: turkey ls-electric.com
•LS ELECTRIC Singapore Office (Singapore)
Tel: 65-6958-8162 E-Mail: singapore ls-electric.com
•LS ELECTRIC Italy office (Italy)
Tel: 39-030-8081-833 E-Mail: italia ls-electric.com

2020. 04 2017. 12 LS ELECTRIC Co.,Ltd. All rights reserved. / (02) 2020. 04 Human Power

You might also like