GM420 DW
GM420 DW
GM420 DW
XM420-W-variant_D00234_00_D_XXEN/04.2015
The XM420-DW series to meet
EXTREME environmental requirements
Description
The measuring and monitoring relays of the XM420-DW series are increasingly used where
extreme climatic and mechanical environmental conditions prevail. The XM420-DW se-
ries is characterised by its robustness under harsh ambient conditions. In particular, it is
extremely weather resistant, interference resistant as well as vibration resistant.
The measuring and monitoring relays of this series are designed as standard with two alarm
relays with one changeover contact each. In addition, the devices are also available with the
following standardised analogue interfaces:
Option M
Analogue output with galvanic separation, output signal selectable in the menu:
DC 0…400 µA Current output, e.g. for Bender measuring instruments of series 96…
DC 0…10 V Standard voltage signal
DC 0/4…20 mA Standard current output
XM420 series Option M1C
Analogue output 0/4…20 mA (without galvanic separation), one changeover contact as
Device characteristics freely configurable alarm message.
• Model according to flammability class
UL 94V-0
Interface options
• F or use at system components that
generate vibrations/shocks
• For use in places with highly fluctuating
temperatures
• Flexible interface options for devices of
the XM420-DW series
• E asy transfer of measured values for
measurement and control technology
• G
alvanic separation prevents inaccurate
measurement results (option M)
• Start-up delay, response delay and delay
on release can be set
• Digital measured value indication on
LC display
• LEDs for operation, alarm 1, alarm 2
• Test/reset button internal/external
• Two separate alarm relays
with 1 changeover contact each
• N/O or N/C operation and fault memory
are selectable
• Permanent self monitoring
• Multifunctional LC display (until -25 °C)
• Password protection for device settings
• Sealable transparent cover
• Push-wire terminal
(two terminals per connection)
• 2-module enclosure (36 mm)
Approvals
2 XM420-W-variant_D00234_00_D_XXEN/04.2015
XM420 series variant "W"
XM420-D W
EXTREMLY EXTREMELY
resistant according to DIN EN 50155 vibration-resistant according
to DIN EN 50155
DIN EN 60068-2-6
DIN EN 60068-2-27
– from -40 °C to +70 °C (+85 °C) – vibration resistance up to 4 g
– in case of condensation and formation of ice – shock resistance up to 30 g
) VM
E(D E(D
CM )
Current monitoring Voltage and
(single-phase and frequency monitoring
three-phase) (single-phase and three-phase)
XM420-W-variant_D00234_00_D_XXEN/04.2015 3
Overview Technical data
XM420-W-variant_D00234_00_D_XXEN / 04.2015 / pdf / © Bender GmbH & Co. KG, Germany – subject to change! The specified standards take into account the version that was valid at the time of printing.
You can find additional information about the listed device series Min. load 1 kΩ
in our product range on www.bender.de. Current output DC 0/4…20 mA
Max. load 500 Ω
Current output DC 0…400 µA
Max. load 12.5 kΩ
( )* Factory setting