Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

GM420 DW

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

The XM420-D W series to meet

EXTREME environmental requirements

Preliminary data sheet

XM420-W-variant_D00234_00_D_XXEN/04.2015
The XM420-DW series to meet
EXTREME environmental requirements

Description
The measuring and monitoring relays of the XM420-DW series are increasingly used where
extreme climatic and mechanical environmental conditions prevail. The XM420-DW se-
ries is characterised by its robustness under harsh ambient conditions. In particular, it is
extremely weather resistant, interference resistant as well as vibration resistant.
The measuring and monitoring relays of this series are designed as standard with two alarm
relays with one changeover contact each. In addition, the devices are also available with the
following standardised analogue interfaces:
Option M
Analogue output with galvanic separation, output signal selectable in the menu:
DC 0…400 µA Current output, e.g. for Bender measuring instruments of series 96…
DC 0…10 V Standard voltage signal
DC 0/4…20 mA Standard current output
XM420 series Option M1C
Analogue output 0/4…20 mA (without galvanic separation), one changeover contact as
Device characteristics freely configurable alarm message.
• Model according to flammability class
UL 94V-0
Interface options
• F or use at system components that
generate vibrations/shocks
• For use in places with highly fluctuating
temperatures
• Flexible interface options for devices of
the XM420-DW series
• E asy transfer of measured values for
measurement and control technology
• G
 alvanic separation prevents inaccurate
measurement results (option M)
• Start-up delay, response delay and delay
on release can be set
• Digital measured value indication on
LC display
• LEDs for operation, alarm 1, alarm 2
• Test/reset button internal/external
• Two separate alarm relays
with 1 changeover contact each
• N/O or N/C operation and fault memory
are selectable
• Permanent self monitoring
• Multifunctional LC display (until -25 °C)
• Password protection for device settings
• Sealable transparent cover
• Push-wire terminal
(two terminals per connection)
• 2-module enclosure (36 mm)

Approvals

2 XM420-W-variant_D00234_00_D_XXEN/04.2015
XM420 series variant "W"

XM420-D W

EXTREMLY EXTREMELY
resistant according to DIN EN 50155 vibration-resistant according
to DIN EN 50155

DIN EN 60068-2-6
DIN EN 60068-2-27
– from -40 °C to +70 °C (+85 °C) – vibration resistance up to 4 g
– in case of condensation and formation of ice – shock resistance up to 30 g

Overview of the extreme weather resistant product series

XM420-DW Residual current monitoring


Loop monitoring GM RCM(A)
(pulsed and AC/DC sensitive)

) VM
E(D E(D
CM )
Current monitoring Voltage and
(single-phase and frequency monitoring
three-phase) (single-phase and three-phase)

Ideal for critical applications such as:


• high shock impact
• high vibration impact
• extreme humidity/formation of ice
• severe pollution
• strong temperature variations (large temperature ranges)

XM420-W-variant_D00234_00_D_XXEN/04.2015 3
Overview Technical data

2 changeover Switching elements


Series Option M Option M1C
contacts Default amount 2 x 1 changeover contacts
Electrical endurance in rated operating conditions  10,000 cycles
RCM420
Contact data according to IEC 60947-5-1
RCMA423 Utilisation category AC-13 AC-14 DC-12 DC-12 DC-12
VME42… Rated operational voltage 230 V 230 V 24 V 110 V 220 V
VMD42… Rated operational current 5A 3A 1 A 0.2 A 0.
CME42… Minimum contact rating  1 mA at AC/DC ≥ 10 V
CMD42… Interfaces
GM42… Max. no-load voltage (open terminals) DC 20 V
Max. short-circuit current 30 mA short-circuit-proof
Additional information:
Voltage output DC 0…10 V

XM420-W-variant_D00234_00_D_XXEN / 04.2015 / pdf / © Bender GmbH & Co. KG, Germany – subject to change! The specified standards take into account the version that was valid at the time of printing.
You can find additional information about the listed device series Min. load 1 kΩ
in our product range on www.bender.de. Current output DC 0/4…20 mA
Max. load 500 Ω
Current output DC 0…400 µA
Max. load 12.5 kΩ
( )* Factory setting

Bender GmbH & Co. KG


P.O. Box 1161 • 35301 Gruenberg • Germany
Londorfer Straße 65 • 35305 Gruenberg • Germany
Tel.: +49 6401 807-0 • Fax: +49 6401 807-259
Email: info@bender.de • www.bender.de

BENDER Group

You might also like