SM3300 DTS V202306
SM3300 DTS V202306
com
DC POWER SUPPLIES Zierikzee, the Netherlands Tel. +31 111 413656
Features Functionalities
• Designed for long life at full power • Operation on single and three phase input voltages
• Protected against all overload and short circuit conditions • Large user display, menu driven operations
• EMC surpasses CE requirements: • Durable digital encoders for voltage and current adjustment
low emission & high immunity
• Plug and play optional interfaces
• Low audible noise: fan is temperature controlled
Three phase
190 V : Pout max (W), Iin (A) 3300, 12.5 3300, 12.5 3300, 12.5 3300, 12.5 3300, 12.5
180 V : Pout max (W), Iin (A) 3100, 12.5 3100, 12.5 3100, 12.5 3100, 12.5 3100, 12.5
internal fuses 20 AT 20 AT 20 AT 20 AT 20 AT
standby input power (Vo=Io=0) 30 W 30 W 30 W 30 W 30 W
standby input power (Vo=Vmax) 60 W 50 W 50 W 50 W 60 W
Efficiency 89 % 90 % 90 % 91 % 92 %
400 V AC, 3 ph input, full load
Regulation
Load 0 - 100% CV 2.5 mV 5 mV 5 mV 5 mV 5 mV
Line 180 - 528 V AC CV 0.2 mV 1 mV 1 mV 3 mV 4 mV
(external voltage sense)
Load 0 - 100% CC 12 mA 6 mA 2 mA 1.2 mA 1.2 mA
Line 180 - 528 V AC CC 3 mA 1 mA 0.5 mA 0.2 mA 0.2 mA
(internal voltage sense,
after warm up)
33 / 66V 50 / 100 V 165 / 330 V 330 / 660 V
Ripple + noise
rms (BW=300 kHz) CV 3 mV 7 mV 7 mV 10 mV 15 mV
p-p (BW=20 MHz) CV 12 mV 18 mV 22 mV 50 mV 120 mV
Notes: 1. Measured at full load. 2. Signal latency depends on the interface used & data traffic. 3. See "Safety instructions" 4. With optional Interface.
Insulation
AC power terminals / DC power term. 3750 Vrms (1min.) 3750 Vrms (1min.) 3750 Vrms (1min.)
creepage / clearance 8 mm 8 mm 8 mm
AC power terminals / case 2500 Vrms 2500 Vrms 2500 Vrms
DC power terminals / case 1000 V DC 3 1330 V DC 3 1400 V DC 3
Safety cTUVus / EN 60950 / EN 61010
EMC Emission EN 61326-1, class B equipment (for use in domestic establishments)
Immunity EN 61326-1, equipment for use in industrial and domestic establishments
Operating Temperature at full load – 20 to + 50 °C
derate output to 75% at 60 °C
Humidity maximum 95% RH, non condensing, up to 40 °C
maximum 75% RH, non condensing, up to 50 °C
Storage temperature – 40 to + 85 °C
Thermal protection output shuts down in case of insufficient cooling
MTBF 500 000 hrs
Notes: 1. Measured at full load. 2. Signal latency depends on the interface used & data traffic. 3. See "Safety instructions" 4. With optional Interface. For
details see ‘Datasheet Interfaces SM3300 series’.
CV = Constant Voltage
CC = Constant Current
Specifications measured at
tamb = 25 ± 5 °C and Vin = 400 VAC,
50 Hz unless otherwise noted.
Notes:
1. Measured at full load.
2. Signal latency depends on the
interface used and data traffic.
3. See safety Instructions in the
operating manual.
4. With optional ‘plug and play’ interface. For
details see ‘Datasheet Interfaces SM3300
series’.
Typical Applications
• Solar inverter testing, PV-Simulation • Automotive battery simulations • Driving PWM-Controlled DC motors
Standard Features
Options