Electrical Wiring Work – ELCB Detail

Earth Leakage Circuit Breaker also known as Residual Current Operated Circuit Breaker.

Detects leakage current


Save from leakage current accident

RCCB
Residual Current operated Circuit Breaker

© DAIKIN INDUSTRIES, LTD. TCDB005 Daikin Training


Page 152
Electrical Wiring Work – ELCB Detail

Fire accident

Electrical shock accident


100 mA

300 mA
30 mA

Life danger even at


Cardiac arrest occurs short duration contact Fire occurs

ELCB with a) Less than 30mA b) Less than 100mA b) Less than 300mA

leakage
current • Saves from direct • Saves from indirect • Saves from fire due to
contact electrical contact electrical leakage current spark
shocks shocks

© DAIKIN INDUSTRIES, LTD. TCDB005 Daikin Training


Page 153
Electrical Wiring Work – ELCB Detail
System Structure
Separate ELCB for each module Leakage current rating 300mA
Current Capacity As per ODU Installation In control panel or in
separate water proof box
a) Single System b) Multi System
(up to 20 HP) (Above 20 HP)

Main Distributor Main Distributor Panel


Panel

Bus-Bar MCB/ MCCB

MCB/ MCCB
Electrical
wiring to
ODU (as per
MCB/ MCCB MCB/ MCCB MCB/ MCCB
ODU MCA
rating)
ELCB/ RCCB
ELCB/ RCCB ELCB/ RCCB ELCB/ RCCB

VRV VRV System A VRV System B VRV System C


System

© DAIKIN INDUSTRIES, LTD. TCDB005 Daikin Training


Page 154