The Power Factor

Controller BR 6000
User-friendly and Intelligent Controller with
Multi-functional Display

Product Profile 2002

http://www.epcos.com
EPCOS BR 6000
PFC Controller
Innovative and intelligent Control

concept ■ Menu-driven handling
Power Factor
■ Mega user-friendly
handling procedures
(plain language) Correction Controller
■ Multilingual display (menu)
■ Easy to install and
maintain
■ Self-optimizing control BR 6000
capability
■ Reasonable price level ■ Recall-function of recorded
(cost /performance) values
■ 4 Quadrant operation
Display (e.g. stand-by generator)
■ Large and multifunctional ■ Large measuring voltage
LCD (2 x 16 characters) range (50 ... 525 V, phase
■ Graphic and alphanumeric to phase)
■ LCD illumination ■ Powerful alarm output

Optional
■ RS 232 Interface
■ Harmonics display
■ Real-time power factor
correction (RTPFC)

U
I

2 EPCOS AG
EPCOS AG
BR 6000 in Operation

■ Display of large numbers of


system parameters
– System voltage (VAC)
– Reactive power (kvar)
– Active power (kW)
– Apparent power (kVA)
– Apparent current (A)
– Temperature (°C)
– Real time cos ϕ
– Target cos ϕ ■ Recall recorded values ■ RTPFC support (transistor output)
– kvar value to target cos ϕ – Number of contactor switching – Contactor switching
operations – Thyristor switching
■ Alarm output – Maximum voltage, U (Vmax)
– Insufficient compensation – Maximum reactive power, Control panel
– Over-compensation Q (kvar)
– Under-current Operation (selection button)
– Maximum active power, P (kW)
– Over-current – Maximum apparent power, Input end (enter, confirmation)
– Over-temperature S (kVA)
– Harmonics exceeded – Maximum temperature (°C) Changing of parameter (up)

Changing of parameter (down)

Phase shift

ϕ
Reactive power Reactive power Reactive power
U I

U
I

0° Time
360°

90° Supplied to the network,


if uncompensated

EPCOS AG 3
Power Factor Controller BR 6000

Putting the Power factor regulator BR6000-R12


B44066-R6012-E230

PFC Controller Meas. voltage: 30-300VAC 50/60 Hz


Supply voltage: 230 V L-N 50/60 Hz

BR 6000 Supply Meas. Meas.


Ser. No.: 0001/2002

voltage Us voltage U m current Ι m

into operation L1 (R)


k
(5 A / 1 A)
l
1. Capacitor
branch

L2 (S)
L3 (T)
N
Easy and simple handling PE

6,3 A
2A

2A
procedure indicated by

T
Only BR6000-12
N L N L k l RS 232*
K1
the written instruction Us Um Ιm P1 P2
Power factor
controller BR6000 * Option
sequence shown on the
display panel. a b 1 2 3 4 5 6 7 8 9 10 11 12
Alarm
relay 2. Relay* Target
Capacitor Capacitor COS Phi2*
contactors 1-6 contactors 7-12 KLK1710-Z-E

Circuit diagram on the rear side of the controller

EPCOS AG 4
BR 6000 PFC Controller

Technical data
Weight: 1 kg
Casing: Panel-mounted instrument, 144 x 144 x 60 mm
Ambient conditions
Over-voltage class: III
Pollution degree: 2
Operating temperature: –10 °C ... + 60 °C
Storage temperature: –20 °C ... + 65 °C
Sensitivity to disturb. (industrial areas): EN55082-2:1995
Spurious radiation (residential areas): EN55011 10.1997
Safety guidelines: EN61010-1 03.1994 + A2 05.1996 / IEC1010-1 1990 + A1 1992
Mounting position: any
Operating height: 0 ... 3000 m over NN
Humidity class: 15 % to 95 % without dew
Protection class:
Front plate: IP54 according to IEC529 / DIN 40050
Rear side: IP20 according to IEC529 / DIN 40050
Operation
Supply voltage: 230 VAC, other voltages available upon request
Mains frequency: 50 and 60 Hz power lines
Power consumption: 5 VA
Target cosϕ: 0.8 ind. – 0.8 cap.
Switching time range: 1 – 1200 seconds
Discharge time range: 1 – 1200 seconds
Number of control series: 20 series preset + control series editor for free programming
Control modes: Series switching (LIFO), circular switching (FIFO),
self-optimized intelligent control mode
4 Quadrant operation: yes (e.g. for stand-by generator)
Measurement
Measurement voltage range: 30 ... 300 VAC phase to neutral (i.e. 50 ... 525 V phase to phase)
Fundamental frequency: 50 and 60 Hz
Measurement current (CT): x/1 and x/5 Ampere possible
Minimum operating current: 40 mA
Maximum current: 5.3 A (sinusoidal)
Zero voltage release: < 15 ms
Switching outputs
Relay outputs
Number of relays: 6 and 12 steps available
Switching voltage: max. 250 VAC
Switching power: max. 1000 W
Max. switching frequency: 0.25 Hz
Expected mechanical life: > 30 x 106 switching operations
Expected electrical life: > 5 x 106 switching operations (load = 200 VA, cosphi = 0.4)
Transistor outputs
Switching voltage : 15 ... 30 Vdc
Switching current : max. 50 mA
Max. switching frequency : 10 Hz
Alarm relay potential-free contact (6 parameters)

BR 6000 ordering codes


Type (230 V) Features Ordering code
BR 6000-R6 6 relay outputs, 1 alarm contact B44066R6006E230
BR 6000-T6 6 transistor outputs, 1 alarm contact B44066R6106E230
BR 6000-R12 12 relay outputs, 1 alarm contact B44066R6012E230
BR 6000-T12 12 transistor output, 1 alarm contact B44066R6112E230
BR 6000-R12/O 2 relay (alarm or temperature control) B44066R6212E230
– Harmonics display, temperature control
– Input target cosϕ 1, change over to target cosϕ 2
BR 6000-R12/OS RS232 interface, others identical to option O B44066R6312E230

EPCOS AG 5
Herausgegeben von EPCOS AG

(
Unternehmenskommunikation, Postfach 80 17 09, 81617 München, DEUTSCHLAND
++49 89 636 09, FAX (0 89) 636-2 26 89
 EPCOS AG 2002. Vervielfältigung, Veröffentlichung, Verbreitung und Verwertung dieser Broschüre und ihres Inhalts ohne aus-
drückliche Genehmigung der EPCOS AG nicht gestattet.
Bestellungen unterliegen den vom ZVEI empfohlenen Allgemeinen Lieferbedingungen für Erzeugnisse und Leistungen der Elek-
troindustrie, soweit nichts anderes vereinbart wird.
Diese Broschüre ersetzt die vorige Ausgabe.
Fragen über Technik, Preise und Liefermöglichkeiten richten Sie bitte an den Ihnen nächstgelegenen Vertrieb der EPCOS AG
oder an unsere Vertriebsgesellschaften im Ausland. Bauelemente können aufgrund technischer Erfordernisse Gefahrstoffe ent-
halten. Auskünfte darüber bitten wir unter Angabe des betreffenden Typs ebenfalls über die zuständige Vertriebsgesellschaft ein-
zuholen.

Published by EPCOS AG

(
Corporate Communications, P.O. Box 80 17 09, 81617 Munich, GERMANY
++49 89 636 09, FAX (0 89) 636-2 26 89
 EPCOS AG 2002. Reproduction, publication and dissemination of this brochure and the information contained therein without
EPCOS’ prior express consent is prohibited.
Purchase orders are subject to the General Conditions for the Supply of Products and Services of the Electrical and Electronics
Industry recommended by the ZVEI (German Electrical and Electronic Manufacturers’ Association), unless otherwise agreed.
This brochure replaces the previous edition.
For questions on technology, prices and delivery please contact the Sales Offices of EPCOS AG or the international Representa-
tives.
Due to technical requirements components may contain dangerous substances. For information on the type in question please
also contact one of our Sales Offices.