User Manual T Series 2.0

Download as pdf or txt
Download as pdf or txt
You are on page 1of 28

User Manual

T SERIES

This guide describes how to use the inverter. In order to prevent improper
operation before use, please read this manual carefully.
Table of Contents
1. Notes on This Manual................................................................................................................. 1
1.1 Scope of Validity................................................................................................................ 1
1.2 Target Group.......................................................................................................................1
1.3 Symbols Used.................................................................................................................... 1
1.4 Symbols Explanation........................................................................................................ 1
2. Safety.............................................................................................................................................2
2.1 Appropriate Usage.............................................................................................................2
2.2 PE Connection and Leakage Current............................................................................ 3
2.3 Surge Protection Devices (SPDs) for PV Installation..................................................4
3. Introduction................................................................................................................................... 4
3.1 Basic Features................................................................................................................... 4
3.2 Dimensions.........................................................................................................................4
3.3 Terminals of Inverter......................................................................................................... 5
4. Technical Data..............................................................................................................................5
4.1 PV Input / AC Output.........................................................................................................5
4.2 Efficiency, Safety and Protection.................................................................................... 7
4.3 General Data...................................................................................................................... 7
5. Installation..................................................................................................................................... 9
5.1 Check for Physical Damage............................................................................................ 9
5.2 Packing List........................................................................................................................ 9
5.3 Mounting............................................................................................................................. 9
6. Electrical Connection................................................................................................................ 12
6.1 Wiring Steps.....................................................................................................................12
6.2 Earth Connection.............................................................................................................15
6.3 Communication Device Installation (Optional)........................................................... 15
6.4 Inverter Start-Up.............................................................................................................. 17
6.5 Inverter Switch Off...........................................................................................................18
7. Operation.................................................................................................................................... 19
7.1 Control Panel................................................................................................................... 19
7.2 Function Tree................................................................................................................... 20
8. Firmware Upgrading................................................................................................................. 21
9. Maintenance............................................................................................................................... 21
9.1 Alarm List.......................................................................................................................... 22
9.2 Troubleshooting............................................................................................................... 23
9.3 Routine Maintenance......................................................................................................24
10. Decommissioning.................................................................................................................... 24
10.1 Dismantling the Inverter...............................................................................................24
10.2 Packaging.......................................................................................................................24
10.3 Storage and Transportation.........................................................................................24
1. Notes on This Manual
1.1 Scope of Validity
This manual describes assembly, installation, commissioning, maintenance and troubleshooting of the
following model(s) of Fox products:
T3, T4, T5, T6, T8, T8(Dual)
T10, T10(Dual), T12, T12(Dual)
T15, T15(Dual), T17, T20, T25
Note: Store this manual where it will be accessible at all times.

1.2 Target Group


This manual is for qualified electricians. The tasks described in this manual can be performed by qualified
individuals only.

1.3 Symbols Used


The following types of safety instructions and general information appear in this document as described
below:
Danger!
“Danger” indicates a hazardous situation which, if not avoided, will result in
death or serious injury.
Warning!
“Warning” indicates a hazardous situation which, if not avoided, could result in
death or serious injury.
Caution!
“Caution” indicates a hazardous situation which, if not avoided, could result in
minor or moderate injury.

Note!
“Note” provides important tips and guidance.

1.4 Symbols Explanation


This section explains the symbols shown on the inverter and on the type label:
Symbols Explanation

Symbol Explanation CE mark. The inverter complies with the requirements of the
applicable CE guidelines.

Beware of hot surface. The inverter can become hot during operation. Avoid
contact during operation.

Danger of high voltages.


Danger to life due to high voltages in the inverter!

1
Danger.
Risk of electric shock!

Danger to life due to high voltage.


There is residual voltage in the inverter which needs 5 min to discharge.
Wait 5 min before you open the upper lid.

Read the manual.

Product should not be disposed as household waste.

2. Safety
2.1 Appropriate Usage
This series inverter is designed and tested in accordance with international safety requirements.
However, certain safety precautions must be taken into account when installing and operating this
inverter. The installer must read and follow all instructions, cautions and warnings in this installation
manual.
- All operations including transport, installation, start-up and maintenance, must be carried out by
qualified, trained personnel.
- The electrical installation & maintenance of the inverter shall be conducted by a licensed electrician
and shall comply with local wiring rules and regulations.
- Before installation, check the unit to ensure it is free of any transport or handling damage, which
could affect insulation integrity or safety clearances. Choose the installation location carefully and
adhere to specified cooling requirements. Unauthorized removal of necessary protections, improper
use, incorrect installation and operation may lead to serious safety and shock hazards or equipment
damage.
- Before connecting the inverter to the power distribution grid, contact the local power distribution grid
company to get appropriate approvals. This connection must be made only by qualified technical
personnel.
- Do not install the equipment in adverse environmental conditions such as in close proximity to
flammable or explosive substances; in a corrosive environment; where there is exposure to extreme
high or low temperatures; or where humidity is high.
- Do not use the equipment when the safety devices do not work or are disabled.
- Use personal protective equipment, including gloves and eye protection during the installation.
- Inform the manufacturer about non-standard installation conditions.
- Do not use the equipment if any operating anomalies are found. Avoid temporary repairs.
- All repairs should be carried out using only approved spare parts, which must be installed in
accordance with their intended use and by a licensed contractor or authorized Fox service
representative.
- Liabilities arising from commercial components are delegated to their respective manufacturers.

2
- Any time the inverter has been disconnected from the public network, please be extremely cautious
as some components can retain charge sufficient to create a shock hazard. Prior to touching any
part of the inverter please ensure surfaces and equipment are under touch safe temperatures and
voltage potentials before proceeding.

2.2 PE Connection and Leakage Current


PV System Residual Current Factors
- In every PV installation, several elements contribute to the current leakage to protective earth (PE).
these elements can be divided into two main types.
- Capacitive discharge current - Discharge current is generated mainly by the parasitic capacitance of
the PV modules to PE. The module type, the environmental conditions (rain, humidity) and even the
distance of the modules from the roof can effect the discharge current. Other factors that may
contribute to the parasitic capacitance are the inverter’s internal capacitance to PE and external
protection elements such as lighting protection.
- During operation, the DC bus is connected to the alternating current grid via the inverter. Thus, a
portion of the alternating voltage amplitude arrives at the DC bus. The fluctuating voltage constantly
changes the charge state of the parasitic PV capacitor (i.e capacitance to PE). This is associated
with a displacement current, which is proportional to the capacitance and the applied voltage
amplitude.
- Residual current - if there is a fault, such as defective insulation, where an energized cable comes
into contact with a grounded person, an additional current flows, known as a residual current.
Residual Current Device (RCD)
- All Fox inverters incorporate a certified internal RCD (Residual Current Device) to protect against
possible electrocution in case of a malfunction of the PV array, cables or inverter (DC). The RCD in
the Fox inverter can detect leakage on the DC side. There are 2 trip thresholds for the RCD as
required by the DIN VDE 0126-1-1 standard. A low threshold is used to protect against rapid
changes in leakage typical of direct contact by people. A higher threshold is used for slowly rising
leakage currents, to limit the current in grounding conductors for the safety. The default value for
higher speed personal protection is 30mA, and 300mA per unit for lower speed fire safety.
Installation and Selection of an External RCD device
- An external RCD is required in some countries. The installer must check which type of RCD is
required by the specific local electric codes. Installation of an RCD must always be conducted in
accordance with local codes and standards. Fox recommends the use of a type-A RCD. Unless a
lower value is required by the specific local electric codes, Fox suggests an RCD value between
100mA and 300mA.

- In installations where the local electric code requires an RCD with a lower leakage setting, the
discharge current might result in nuisance tripping of the external RCD. The following steps are
recommended to avoid nuisance tripping of the external RCD:
1. Selecting the appropriate RCD is important for correct operation of the installation. An RCD with a
rating of 30mA may actually trip at a leakage as 15mA (according to IEC 61008). High quality RCDs will
typically trip at a value closer to their rating.
2. Configure the trip current of the inverter’ internal RCD to a lower value than the trip current of the
external RCD. The internal RCD will trip if the current is higher than the allowed current, but because the
internal inverter RCD automatically resets when the residual currents are low it saves the manual reset.

3
2.3 Surge Protection Devices (SPDs) for PV Installation
Lightning will cause damage either from a direct strike or from surges due to a nearby strike.
Induced surges are the most likely cause of lightning damage in majority or installations, especially
in rural areas where electricity is usually provided by long overhead lines. Surges may impact on
both the PV array conduction and the AC cables leading to the building. Specialists in lightning
protection should be consulted during the end use application. Using appropriate external lightning
protection, the effect of a direct lightning strike into a building can be mitigated in a controlled way,
and the lightning current can be discharged into the ground.
Thanks to the integrated SPD on DC and AC side, it is not necessary to install external lightning
protection system on both sides. The inside integrated SPD device is SPD type 2 protection, if the
voltage protection level (VP) of the surge arresters is greater than 1100V, an additional SPD type 3 is
required for surge protection for electrical devices.

3. Introduction
3.1 Basic Features
This three-phase high performance inverter covers 3kW to 25kW. The inverter is integrated with 2 MPP
trackers with high efficiency and reliability.
System advantages:
- Advanced DSP control technology.
- Utilizes the latest high-efficiency power components.
- Optimal MPPT technology.
- Two independent MPP trackers.
- Wide MPPT voltage range.
- Advanced anti-islanding solutions.
- IP65 protection level.
- Max. Efficiency up to 98.6%. EU efficiency up to 97.8%. THD<3%.
- Safety & Reliability: Transformerless design with software and hardware protection.
- External limitation (Meter/DRM0/ESTOP).
- Power factor regulation. Friendly HMI.
- LED status indications.
- LCD display technical data, human-machine interaction through touch key.
- Remote monitoring via PC or APP.
- Upgrade through USB interface.

3.2 Dimensions

4
3.3 Terminals of Inverter

Item Description Item Description


A DC Switch (Optional) E USB
B PV+ F COM
C PV- G Waterproof Lock Valve
D WiFi / GPRS H AC Connector

4. Technical Data
4.1 PV Input / AC Output
T8/ T10/ T12/ T15/
Model T3 T4 T5 T6 T17 T20 T25
T8(Dual) T10(Dual) T12(Dual) T15(Dual)

3000 4000 5000 6000 8000 10000 12000 15000 17000 20000 25000

PV INPUT

Max. DC Input
4500W 6000W 7500W 9000W 12000W 15000W 18000W 22500W 25500W 30000W 37500W
power

Max. DC voltage 1100V 1100V 1100V 1100V 1100V 1100V 1100V 1100V 1100V 1100V 1100V

Nominal DC
600V 600V 600V 600V 600V 600V 600V 600V 600V 600V 600V
operating voltage

Max. input 12.5/12.5 12.5/12.5 12.5/12.5 25/12.5

current (input 12.5/ 12.5/ 12.5/ 12.5/ (T8) (T10) (T12) (T15)
25/25 25/25 25/25
A/input B) (A) 12.5 12.5 12.5 12.5 25/25 25/25 25/25 25/25

(T8 Dual) (T10 Dual) (T12 Dual) (T15 Dual)

Max. short circuit 16.25/16. 16.25/16.2 16.25/16.2 32.5/16.25

current (input 16.25/ 16.25/ 16.25/ 16.25/ 25(T8) 5(T10) 5(T12) (T15)
32.5/32.5 32.5/32.5 32.5/32.5
A/input B) (A) 16.25 16.25 16.25 16.25 32.5/32.5 32.5/32.5 32.5/32.5 32.5/32.5

(T8 Dual) (T10 Dual) (T12 Dual) (T15 Dual)

5
MPPT voltage 160-850 160-850 160-850 160-850 160-850 160-850 160-850 160-850 160-850 160-850 160-850

range Vdc Vdc Vdc Vdc Vdc Vdc Vdc Vdc Vdc Vdc Vdc

330-850 410-850 490-850 410-850


MPPT voltage
(T8) (T10) (T12) (T15)
range (full load) 160-850 180-850 210-850 250-850 350-850 410-850 510-850
160-850 200-850 240-850 300-850
(Vdc)
(T8 Dual) (T10 Dual) (T12 Dual) (T15 Dual)

Start-up voltage 180V 180V 180V 180V 180V 180V 180V 180V 180V 180V 180V

No. of MPP
2 2 2 2 2 2 2 2 2 2 2
trackers

1+1(T8) 1+1(T10) 1+1(T12) 2+1(T15)


Strings per MPP
1+1 1+1 1+1 1+1 2+2 2+2 2+2 2+2 2+2 2+2 2+2
tracker
(T8 Dual) (T10 Dual) (T12 Dual) (T15 Dual)

Max. Inverter

backfeed current 0

to the array (mA)

AC OUTPUT

Nominal AC
3000W 4000W 5000W 6000W 8000W 10000W 12000W 15000W 17000W 20000W 25000W
power

Max. apparent
3300VA 4400VA 5500VA 6600VA 8800VA 11000VA 13200VA 16500VA 18700VA 22000VA 27500VA
AC power

Rated grid
voltage (AC 3/N/PE, 400V
voltage range)

Rated Grid
50/60Hz, ±5Hz
Frequency

Nominal AC
4.3A 5.8 A 7.2 A 8.7 A 11.6 A 14.5 A 17.4 A 21.7 A 24.6 A 29.0 A 36.2 A
current

Max. AC current 4.8A 6.4 A 8.0 A 9.6 A 12.8 A 15.9 A 19.1 A 23.9 A 27.1 A 31.9 A 39.9 A

14.5A@0.7ms (T8-T12)
19.3A@
Inrush current 9.6A@0.8ms 12.1A@0.6ms 12.1A@0.6ms
1.3ms
(T8(Dual)-T12(Dual))

Maximum output 58A@8us (T8-T12) 145A


30A@11us 93A@8us
fault current 93A@8us (T8(Dual)-T12(Dual)) @10us

Maximum output
overcurrent 10.1A 13.5A 16.9A 20.3A 27.1A 33.8A 40.6A 50.7A 57.5A 67.6A 84.5A
protection

Displacement
1 (Adjustable from 0.8 leading to 0.8 lagging)
power factor

Total harmonic
distortion (THDi, <3%
@rated output)

6
4.2 Efficiency, Safety and Protection
T8/ T10/ T12/ T15/
Model T3 T4 T5 T6 T17 T20 T25
T8(Dual) T10(Dual) T12(Dual) T15(Dual)

EFFICIENCY

Max. MPPT
99.00% 99.00% 99.00% 99.00% 99.00% 99.00% 99.00% 99.00% 99.00% 99.00% 99.00%
efficiency

Euro-efficiency 97.80% 97.80% 97.80% 97.80% 97.80% 97.80% 97.80% 97.80% 97.80% 97.80% 97.80%

Max. efficiency
98.60% 98.60% 98.60% 98.60% 98.60% 98.60% 98.60% 98.60% 98.60% 98.60% 98.60%
(@rated voltage)

PROTECTION

DC reverse-polarity
Yes
protection

Insulation
Yes
monitoring

Residual current
Yes
monitoring

AC short circuit
Yes
protection

AC output over
Yes
current protection

AC output over
Yes
voltage protection

Surge protection Yes

Temperature
Yes
protection

Anti-Islanding
Frequency shift
protection method

Integrated DC
Optional
switch

STANDARD

Safety IEC62109-1/2

EMC IEC 61000-6-1 / IEC 61000-6-2 / IEC 61000-6-3 / IEC61000-4-2/3/4/5/6/8

AS4777.2-2015 / VDE-AR-N 4105 /VDE0126-1-1 / G98 / G99 / EN50549-1 / CEI 0-21


Certification
IEC62116 / IEC61727 / IEC61683

4.3 General Data


T8/ T10/ T12/ T15/
Model T3 T4 T5 T6 T17 T20 T25
T8(Dual) T10(Dual) T12(Dual) T15(Dual)

GENERAL DATA

Dimensions (WxHxD) 384*475*186mm

7
20KG (T3-T12)
Net weight 24KG
24KG (T8(Dual)-T12(Dual))

Cooling concept Convection Forced convection

Ingress protection
IP65
(according to IEC60529)

Topology Non-isolated

Over voltage category III (AC side), II (PV side)

Noise emission (typical) <30dB <55dB

Max. operating altitude 3000m

Temperature range
-20…... +60°C (derating at +45°C)
(operating)

Temperature range
-40…... +70°C
(storage)

Humidity 0-100% (no condensation)

Self-consumption (night) <3W

Pollution degree II

Monitoring module
RS485, WiFi (optional)/ GPRS (optional)
(optional)

Communication Meter, DRM, E-stop, USB

Display LCD screen, touch key, APP, Web site

8
5. Installation
5.1 Check for Physical Damage
Make sure the inverter has not been damaged during transportation. If there is any visible damage, such
as cracks, please contact your dealer immediately.

5.2 Packing List


Open the package and take out the product, please check the accessories first. The packing list is as
shown as below.

A B C D

E F G H I J

K L M N

Object Quantity Description Object Quantity Description

A 1 Inverter H 1 Earth terminal

B 1 Bracket I 1 Communication connector


C 2/3/4 DC connector (F/M) J 1 Product manual
D 1 AC connector K 1 Quick installation guide
E 5 Expansion tube L 1 WiFi/GPRS (optional)
F 5 Expansion screw M 1 Screwdriver
DC pin contact
G 2/3/4 (1*positive, N 1 Unlock tool
1*negative)

5.3 Mounting
• Installation Precaution
Make sure the installation location complies with the following conditions:
- Not in direct sunlight.
- Not in areas where highly flammable materials are stored.
- Not in potentially explosive areas.
- Not in a direct flow of cool air.
- Not near a television antenna or antenna cable.
- Not higher than altitude of 3000m above sea level.

9
- Not in environment of precipitation or humidity (> 95%).
- Is well ventilated.
- The ambient temperature is in the range of -20°C to +60°C.
- The slope of the wall should be within ±5°.
- The wall where the inverter is mounted should comply with the following conditions:
1. Is solid brick/concrete or a mounting surface of equivalent strength;
2. The Inverter must be supported or strengthened if the wall's strength isn't adequate (such as a
stud wall or where the wall is covered by thick layer of decoration).
- Avoid direct sunlight, rain exposure or accumulations of snow during installation and operation.

• Space Requirement

Position Min Size


Left 30cm
Right 30cm
Top 30cm
Bottom 30cm
Front 30cm

• Mounting Steps
Tools required for installation.
- Manual wrench;
- Electric drill (drill bit set 8mm);
- Crimping pliers;
- Stripping pliers;
- Screwdriver.

10
Step 1: Fix the bracket on the wall
Choose the place you want to install the inverter. Place the bracket on the wall and mark the position of
the 5 holes from bracket.

Drill holes with electric drill, make sure the holes are at least 50mm deep, and then tighten the expansion
tubes.

Insert the expansion tubes into the holes and tighten them. Install the bracket with the expansion screws.

Step 2: Match the inverter with wall bracket


Hang the inverter over the bracket, slightly lower the inverter, and make sure the two mounting grooves
on the back are properly fixed with the two bracket bars.

11
6. Electrical Connection
6.1 Wiring Steps
Step 1: PV String Connection
This series inverters can be connected with 2 to 4 strings of PV modules depending on the inverter type.
Please select suitable PV modules with high reliability and quality. Open circuit voltage of the module
array connected should be less than 1100V, and operating voltage should be within the MPPT voltage
range.

Note!
Please choose a suitable external DC switch if the inverter does not have a built-in
DC switch.

Warning!
PV module voltage is very high and within a dangerous voltage range, please
comply with the electric safety rules when connecting.

Warning!

Please do not make PV positive or negative to ground!

Note!
PV modules – please ensure they are the same type, have the same output and
specifications, are aligned identically, and are tilted to the same angle. In order to
save cable and reduce DC loss, we recommend installing the inverter as near to
the PV modules as possible.

Step 2: DC Wiring
• Turn off the DC switch.
• Choose 12 AWG wire to connect the PV module.
• Trim 6mm of insulation from the wire end.

• Separate the DC connector as below.

• Insert striped cable into pin contact and ensure all conductor strands are captured in the pin contact.

12
• Crimp pin contact by using a crimping plier. Put the pin contact with striped cable into the
corresponding crimping pliers and crimp the contact.

• Insert pin contact through the cable nut to assemble into back of the male or female plug. When you
feel or hear a “click” the pin contact assembly is seated correctly.

• Unlock the DC connector


- Use the specified wrench tool.
- When separating the DC+ connector, push the tool down from the top.
- When separating the DC - connector, push the tool up from the bottom.
- Separate the connectors by hand.

• Grid Connection
This series inverters are designed for three-phase grid. Voltage range is 220/230/240V; frequency is
50/60Hz. Other technical requests should comply with the requirement of the local public grid.

Model (kW) 3.0 4.0 5.0 6.0 8.0 10.0 12.0 15.0 17.0 20.0 25.0
Cable 2.5~6mm² 4~6mm² 6~10mm² 10mm²

Micro-Breaker 16A 25A 40A 50A 60A

WARNING!
A micro-breaker for max output overcurrent protection device shall be installed between
inverter and grid, and the current of the protection device is referred to the table above,
any load SHOULD NOT be connected with the inverter directly.

Step 3: AC Wiring
• Check the grid voltage and compare with the permitted voltage range (refer to technical data).
• Disconnect the circuit-breaker from all the phases and secure against re-connection.
• Trim the wires:
- Trim all the wires to 52.5mm and the PE wire to 55mm.

13
- Use the crimping pliers to trim 12mm of insulation from all wire ends as below.

L1/L2/L3: Brown/Red/Green or Yellow Wire


N: Blue/Black Wire
PE: Yellow & Green Wire
Note: Please refer to local cable type and color for
actual installation.

• Separate the AC plug into three parts as below.

• Insert the sleeve assembly into the cable.

• Install the copper wire into the plug terminal and lock the screw.

• Lock the lock nut and the sleeve (3~5N·M), lock the sleeve and the plug (1.5~1.7N·M).

• Insert the plug assembly into the socket (inverter end) and lock each other by the coupling twist.

14
6.2 Earth Connection
Screw the ground screw with screwdriver as shown below:

6.3 Communication Device Installation (Optional)


This series inverter is available with multiple communication options such as WiFi, GPRS, RS485 and
Meter with an external device.
Operating information like output voltage, current, frequency, fault information, etc. can be monitored
locally or remotely via these interfaces.
• WiFi/GPRS (Optional)
The inverter has an interface for WiFi/GPRS devices that allow this device to collect information from
inverter; including inverter working status, performance etc., and update that information to monitoring
platform (the WiFi/GPRS device is available to purchase from your local supplier).
Connection steps:
1. For GPRS device: Please insert the SIM Card (please refer to the GPRS product manual for more
details).
2. Plug the WiFi/GPRS device into “WiFi/GPRS” port at the bottom of the inverter.
3. For WiFi device: Connect the WiFi with the local router and complete the WiFi configuration (please
refer to the WiFi product manual for more details).
4. Set-up the site account on the Fox monitoring platform (please refer to the monitoring user manual
for more details).

• RS485/Meter
- RS485
RS485 is a standard communication interface which can transmit the real time data from inverter
to a PC or other monitoring devices.

15
- Meter (optional)
The inverter has integrated export limitation functionality. To use this function, a power meter must be
installed. For Meter installation, please install it on the grid side.
Export limitation setting:
Short press the touch key to switch display or make the Value+1. Long press the touch key to confirm
your setting.

• DRM0/ESTOP
DRM0 setting
Short press the touch key to switch display or make the value+1. Long press the touch key to confirm
your setting.

The PIN definitions of RS485/DRM0/ESTOP interface are as below.

16
PIN 1 2 3 4 5 6 7 8
METER METER
Definition 485- 485+ GND DRM0 +12V ESTOP
485- 485+

Model Socket asserted by shorting pins Function


DRM0 5 6 Operate the disconnection device.
ESTOP 5 8 Emergency stop the inverter.

Note:
• Isolation Fault (Australia Market Only)
This inverter complies with IEC 62109-2 clause 13.9 for earth fault alarm monitoring. If an Earth Fault
Alarm occurs, the fault code Isolation fault will be displayed on the inverter screen and the RED LED
indicator will light up.
• Reactive Power Regulation for Voltage Variation (Volt-VAr Mode)
Details of how to enable this mode are contained in the “Advanced Configuration Guide”, which can be
accessed at our website at https://www.foxess.com.
• Power Derating for Voltage Variation (Volt-Watt Mode)
Details of how to enable this mode are contained in the “Advanced Configuration Guide”, which can be
accessed at our website at https://www.foxess.com.

6.4 Inverter Start-Up


Please refer to the following steps to start-up the inverter:
a) Check if device is fixed well on the wall;
b) Make sure all DC breakers and AC breakers are disconnected;
c) Ensure AC cable is connected to the grid correctly;
d) All PV panels are connected to inverter correctly; DC connectors that are not used should be sealed
by cover;
e) Turn on the external AC and DC connectors;
f) Turn the DC switch to the “ON” position (if equipped with DC switch on the inverter).
If the LED is not green, please check the below:
- All the connections are correct.
- All the external disconnect switches are closed.
- The DC switch of the inverter is in the “ON” position.
Note:
• When starting the inverter for the first time, the country code will be set by default to the local
settings. Please check if the country code is correct.
• Set the time on the inverter using the button or by using the APP.

Below are the three possible inverter states indicating that the inverter has started up successfully.

Waiting: Inverter is waiting to check whether or not the DC input voltage from panels is greater than
180V (lowest start-up voltage) and is waiting to check whether the voltage and frequency on AC side are
within the range; display will indicate the Waiting status and green LED will flash.

17
Checking: Inverter will check DC input environment automatically when DC input voltage from the PV
panels exceeds 180V and PV panels have enough energy to start inverter, display will indicate the
Checking status and green LED will flash.

Normal: Inverter begins to operate normally with green light on. Meanwhile feedback energy to grid, LCD
displays present output power.
Note: You can go to the setting interface on the display to follow the instructions if it is the first time to start
up.

 Complete inverter Start-up guide


After the initial start-up the inverter, display will go to the language settings page, short press to switch
language and long press to confirm selection. Once language set, display will guide to set the safety
regulation. Short press to switch safety regulation, and long press to confirm selection.

Note!
Please set-up the inverter if it is the first time to start-up. The above steps are for the
regular start-up of the inverter. If it is the first time to start up the inverter, you need to
carry-out the initial set-up of the inverter.
Warning!
Power to the unit must be turned on only after installation work has been completed.
All electrical connections must be carried out by qualified personnel in accordance
with legislation in force in the country of installation.

6.5 Inverter Switch Off


Please follow the below steps to switch off the inverter:
a) Switch off the inverter AC isolation switch.
b) Switch off the DC isolation switch and allow 5 minutes for the inverter to power down completely.

18
7. Operation
7.1 Control Panel

Object Name Function


A LCD Screen Display the information of the inverter.
B Green: The inverter is in normal state.
Indicator LED
C Red: The inverter is in fault mode.
The touch key is used to set the LCD to display different parameters.
Press time <1s (short press): Next;
D Touch Key
Press time >2s (long press): Enter.
Wait time 15s: Return to start.

19
7.2 Function Tree

20
8. Firmware Upgrading
User can upgrade inverter's firmware via a U-disk.
• Preparation
Please ensure the inverter is steadily powered on.
Inverter must remain powered through whole procedure of upgrading. Prepare a PC and make sure the
size of U-disk is under 32G, and the format is fat 16 or fat 32.
Note!
External U disk can only use USB2.0, using USB3.0 will cause the U disk to be
burned.

• Upgrading steps:
Step 1: Please contact our service support to get the update files, and extract it into your U-disk as
follows:
Master: “Update\master\xxxxx_Master_Vx.xx.hex”
Slave: “Update\slave\xxxxx_Slave_Vx.xx.hex”
Manager: “Update\manager\xxxxx_manager_Vx.xx.hex”
Note: Vx.xx is version number.
Warning: Make sure the directory structure is strictly in accordance with above! Do not modify the
program file name, or it may cause the inverter to cease working.
Step 2: Unscrew the waterproof lid and insert U-disk into the "USB" port at the bottom of the inverter.
Step 3: The LCD will show update information. Then shortly press touch key to select the firmware that
you want to upgrade and press touch key for 5 seconds to confirm the upgrade.
Step 4: Wait for few minutes until the upgrade is finished. The LCD will go back to the first page and show
“Upgrade Master”. Please pull out the U-disk and check if the firmware version is the correct one. Then
screw the waterproof lid.

9. Maintenance
This section contains information and procedures for solving possible problems with the Fox inverters

21
and provides you with troubleshooting tips to identify and solve most problems that can occur.

9.1 Alarm List


Fault Code Solution
- Turn off the PV and grid, reconnect them.
SPS fault
- Please seek for help from us if it does not go back to normal state.
- Disconnect PV (+), PV (-) using DC switch.
Bus volt fault - After the LCD switches off, reconnect and check again.
- Please seek for help from us if it does not go back to normal state.

- Wait for one minute after the inverter reconnects to grid.


- Disconnect PV (+), PV (-) using DC switch.
DCI over range
- After the LCD switches off, reconnect and check again.
- Please seek for help from us if it does not go back to normal state.

- Disconnect PV (+), PV (-) using DC switch.


EEprom fault - After the LCD switches off, reconnect and check again.
- Please seek for help from us if it does not go back to normal state.

-Disconnect DC and AC connector, check the surrounding equipment on the


AC side.
GFCI fault or GFCD
-Reconnect the input connector and check the state of inverter after
fault
troubleshooting.
-Please seek for help from us if it does not go back to normal state.
- System will reconnect if the grid is back to normal.
Grid10MinOVP
- Or seek for help from us if it does not go back to normal state.
- Wait for one minute, grid may go back to normal working state.
Grid freq fault - Make sure that grid voltage and frequency complies with standards.
- Or, please seek for help from us.
- Please check grid-connection, e.g., wires, interface etc.
Grid lost fault - Checking grid usability.
- Or seek for help from us.
- Disconnect PV (+), PV (-) using DC switch.
V grid transient - After the LCD switches off, reconnect and check again.
- Please seek for help from us if it does not go back to normal state.
- Wait for one minute, grid may go back to normal working state.
Grid volt fault - Make sure that grid voltage and frequency complies with standards.
- Or, please seek for help from us.
- Disconnect PV (+), PV (-) using DC switch.
Inconsistency - After the LCD switches off, reconnect and check again.
- Please seek for help from us if it cannot go back to normal state.
- Check the impedance among PV (+), PV (-) and ground. Impedance should
ISO fault be >100kohm.
- Please seek for help from us if the impedance is >100kohm.

22
- Check the voltage of neutral and PE.
- Check AC wiring.
Ground fault
- Disconnect PV (+), PV (-) using DC switch.
- After the LCD switches off, reconnect and check again.
- Turn off the PV and grid, reconnect them.
OCP fault
- Or seek for help from us if it does not go back to normal.
- Check the connection of ac grid
PLL fault - System will reconnect if the utility is back to normal.
- Or seek for help from us if it does not go back to normal state.
- Check the panel’s open-circuit voltage whether the value is similar or
Pv volt fault already >1000Vdc.
- Please seek help from us when voltage ≤1000Vdc.
- Disconnect PV (+), PV (-) using DC switch.
- Check the connection of ac grid
Relay fault
- After the LCD switches off, reconnect and check again.
- Please seek for help from us if it does not go back to normal state.
- Disconnect PV (+), PV (-) using DC switch.
Sample fault - After the LCD switches off, reconnect and check again.
- Please seek for help from us if it cannot go back to normal state.

SCI Comm fault or - Disconnect PV+, PV-, reconnect them.


SPI Comm fault - Or seek for help from us if it does not go back to normal state.

- Check if the environment temperature is over the limit.


Over temp fault
- Or seek for help from us.
- Check the inverter‘s setup items about meter.
- Disconnect DC and AC connector, check the connection of the meter.
Meter fault
- Reconnect the DC and AC connector.
- Please seek for help from us if it does not go back to normal state.
- Disconnect PV+, PV-, reconnect them.
Fan fault - Check whether the FAN is seized up by something or not.
- Or seek for help from us if it does not go back to normal state.

9.2 Troubleshooting
a. Please check the fault message on the System Control Panel or the fault code on the inverter
information panel. If a message is displayed, record it before doing anything further.
b. Attempt the solution indicated in table above.
c. If your inverter information panel is not displaying a fault light, check the following to make sure that
the current state of the installation allows for proper operation of the unit:
(1) Is the inverter located in a clean, dry, adequately ventilated place?
(2) Have the DC input breakers opened?
(3) Are the cables adequately sized?
(4) Are the input and output connections and wiring in good condition?
(5) Are the configurations settings correct for your particular installation?
(6) Are the display panel and the communications cable properly connected and

23
undamaged?

Contact Fox Customer Service for further assistance. Please be prepared to describe details of your
system installation and provide the model and serial number of the unit.

9.3 Routine Maintenance


• Safety check
A safety check should be performed at least every 12 months by a qualified technician who has adequate
training, knowledge and practical experience to perform these tests. The data should be recorded in an
equipment log. If the device is not functioning properly or fails any of the tests, the device has to be
repaired. For safety check details, refer to section 2 of this manual.

• Maintenance checking list


During the process of using the inverter, the responsible person shall examine and maintain the machine
regularly. The required actions are as follows.
- Check that if the cooling fins at the rear of the inverters are collecting dust/dirt, and the machine
should be cleaned when necessary. This work should be conducted periodically.
- Check that if the indicators of the inverter are in normal state, check if the display of the inverter is
normal. These checks should be performed at least every 6 months.
- Check if the input and output wires are damaged or aged. This check should be performed at least
every 6 months.
- Get the inverter panels cleaned and their security checked at least every 6 months.
Note: Only qualified individuals may perform these actions.

10. Decommissioning
10.1 Dismantling the Inverter
- Disconnect the inverter from DC Input and AC output. Wait for 5 minutes for the inverter to fully
de-energize.
- Disconnect communication and optional connection wirings. Remove the inverter from the bracket.
- Remove the bracket if necessary.

10.2 Packaging
If possible, please pack the inverter with the original packaging. If it is no longer available, you can also
use an equivalent box that meets the following requirements.
- Suitable for loads more than 30 kg.
- Contains a handle.
- Can be fully closed.

10.3 Storage and Transportation


Store the inverter in dry place where ambient temperatures are always between -40°C - + 70°C. Take
care of the inverter during the storage and transportation; keep less than 4 cartons in one stack. When
the inverter or other related components need to be disposed of, please ensure it is carried out according
to local waste handling regulations.

24
The copyright of this manual belongs to FOXESS CO., LTD WUXI BRANCH. Any corporation
or individual should not plagiarize, partially or fully copy (including software, etc.), and no
reproduction or distribution of it in any form or by any means is permitted. All rights reserved.
FOXESS CO., LTD WUXI BRANCH
Add: No.939, Jinhai Third Road, New Airport Industry Area, Longwan District, Wenzhou,
Zhejiang, China
Tel: 0510- 68092998
WWW.FOX-ESS.COM.

V4.2
10-203-00043-04