Schneider Isolator Module

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

Esmi Short

Circuit Isolator UL
Instruction Sheet
R10180GB
1 Esmi Short Circuit Isolator UL

Schneider Electric Fire & Security Oy

Sokerilinnantie 11 C
FI-02600 Espoo, Finland
Tel: +358 10 446 511
Website: www.se.com
Document number: R10180GB0
Published: 03.06.2020

© 2020 – Schneider Electric. All Rights Reserved. This information is only to be used as guidance. Subject to changes and errors.

2 R10180GB
2 Esmi Short Circuit Isolator UL

1 Esmi Short Circuit Isolator UL

Class A Configuration Wiring:

The Esmi Short Circuit Isolator UL (FFSULH2008) should be located between any
devices on the S-SC line. In the event of a short on the S-SC line, the two adjacent
isolators (closest isolators to the left and right of the shorted section) will activate and
their respective LED indicators will be turned on.

All devices between the active short circuit isolators will be dead. This will prevent entire
loop failure. Upon removal of the short condition, the Esmi Short Circuit Isolator‘s will
automatically restore the entire loop to the normal operating state.

Class B Configuration Wiring:

The Esmi Short Circuit Isolator UL (FFSULH2008) should be located between any de-
vices on the S-SC line. In the event of a short on the S-SC line, an isolator closest to the
shorted section will activate and the LED will be turned on.

All the devices beyond the shorted section will be disabled. Upon removal of the short
condition the Esmi Short Circuit Isolator UL will automatically restore the entire loop to the
normal operating state.

For the best performance of Esmi Short Circuit Isolator UL, use class A configuration.

1.1 Standard Features

• Can be placed at any location on S-SC line

• Checks the line for short circuit at power ON. If a line is normal, the relay will be
turned on. If a line short is detected, the relay remains open

• Indication of short circuit by a yellow LED

• Ordering Code FFSULH2008.

2 Engineering Specifications

The contractor shall furnish and install where indicated on the plans, the Esmi Short
Circuit Isolator UL. The module shall be UL listed compatible with the Schneider Electric
Digital Communications Protocol (DCP) supporting control panel loops. The isolator mod-
ule must be suitable for mounting in a standard 4" (106mm) square electrical box or dou-
ble gang. The isolator module must provide a yellow LED for indication of status.

R10180GB 3
1 Esmi Short Circuit Isolator UL

3 Typical Wiring Diagrams

WIRING:

Note: All wiring must conform to local codes, ordinances and regulations.

1. Install module wiring in accordance with job drawings and appropriate wiring diagram.
2. Secure the module to an approved electrical box (supplied by installer).

MOUNTING REQUIREMENTS: 4" (106mm) square electrical box or double gang.

4 R10180GB
2 Esmi Short Circuit Isolator UL

4 Product Listings

SIGNALLING California State Fire Marshal


S36311 7300-0410:150

R10180GB 5