Alarma Hikvision
Alarma Hikvision
Alarma Hikvision
User Manual
AX HYBRID PRO User Manual
Legal Information
© 2022 Hangzhou Hikvision Digital Technology Co., Ltd. All rights reserved.
About this Manual
The Manual includes instructions for using and managing the Product. Pictures, charts, images and
all other information hereinafter are for description and explanation only. The information
contained in the Manual is subject to change, without notice, due to firmware updates or other
reasons. Please find the latest version of this Manual at the Hikvision website
(https://www.hikvision.com/).
Please use this Manual with the guidance and assistance of professionals trained in supporting the
Product.
Trademarks
and other Hikvision's trademarks and logos are the properties of
Hikvision in various jurisdictions.
Other trademarks and logos mentioned are the properties of their respective owners.
Disclaimer
TO THE MAXIMUM EXTENT PERMITTED BY APPLICABLE LAW, THIS MANUAL AND THE PRODUCT
DESCRIBED, WITH ITS HARDWARE, SOFTWARE AND FIRMWARE, ARE PROVIDED “AS IS” AND
“WITH ALL FAULTS AND ERRORS”. HIKVISION MAKES NO WARRANTIES, EXPRESS OR IMPLIED,
INCLUDING WITHOUT LIMITATION, MERCHANTABILITY, SATISFACTORY QUALITY, OR FITNESS FOR
A PARTICULAR PURPOSE. THE USE OF THE PRODUCT BY YOU IS AT YOUR OWN RISK. IN NO EVENT
WILL HIKVISION BE LIABLE TO YOU FOR ANY SPECIAL, CONSEQUENTIAL, INCIDENTAL, OR INDIRECT
DAMAGES, INCLUDING, AMONG OTHERS, DAMAGES FOR LOSS OF BUSINESS PROFITS, BUSINESS
INTERRUPTION, OR LOSS OF DATA, CORRUPTION OF SYSTEMS, OR LOSS OF DOCUMENTATION,
WHETHER BASED ON BREACH OF CONTRACT, TORT (INCLUDING NEGLIGENCE), PRODUCT
LIABILITY, OR OTHERWISE, IN CONNECTION WITH THE USE OF THE PRODUCT, EVEN IF HIKVISION
HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES OR LOSS.
YOU ACKNOWLEDGE THAT THE NATURE OF INTERNET PROVIDES FOR INHERENT SECURITY RISKS,
AND HIKVISION SHALL NOT TAKE ANY RESPONSIBILITIES FOR ABNORMAL OPERATION, PRIVACY
LEAKAGE OR OTHER DAMAGES RESULTING FROM CYBER-ATTACK, HACKER ATTACK, VIRUS
INSPECTION, OR OTHER INTERNET SECURITY RISKS; HOWEVER, HIKVISION WILL PROVIDE TIMELY
TECHNICAL SUPPORT IF REQUIRED.
YOU AGREE TO USE THIS PRODUCT IN COMPLIANCE WITH ALL APPLICABLE LAWS, AND YOU ARE
SOLELY RESPONSIBLE FOR ENSURING THAT YOUR USE CONFORMS TO THE APPLICABLE LAW.
ESPECIALLY, YOU ARE RESPONSIBLE, FOR USING THIS PRODUCT IN A MANNER THAT DOES NOT
INFRINGE ON THE RIGHTS OF THIRD PARTIES, INCLUDING WITHOUT LIMITATION, RIGHTS OF
PUBLICITY, INTELLECTUAL PROPERTY RIGHTS, OR DATA PROTECTION AND OTHER PRIVACY RIGHTS.
YOU SHALL NOT USE THIS PRODUCT FOR ANY PROHIBITED END-USES, INCLUDING THE
DEVELOPMENT OR PRODUCTION OF WEAPONS OF MASS DESTRUCTION, THE DEVELOPMENT OR
i
AX HYBRID PRO User Manual
ii
AX HYBRID PRO User Manual
Symbol Conventions
The symbols that may be found in this document are defined as follows.
Symbol Description
Indicates a hazardous situation which, if not avoided, will or could
Danger
result in death or serious injury.
Indicates a potentially hazardous situation which, if not avoided,
Caution could result in equipment damage, data loss, performance
degradation, or unexpected results.
Provides additional information to emphasize or supplement
Note
important points of the main text.
Note
Please update firmware to the latest version.
For installers, it is recommended to install and maintain devices via Hik-ProConnect.
iii
AX HYBRID PRO User Manual
Regulatory Information
EN 50131-3:2009
EN 50131-10:2014
EN 50136-2:2013 Security Grade (SG): 2
EN 50136-1:2012+A1:2018 Environmental Class (EC) : II
EN 50131-6:2017 SP4
EN 50131-1:2006+A1:2009+A2:2017+A3:2020
EN 50130-4:2011+A1:2014
EN 50130-5:2011
iv
AX HYBRID PRO User Manual
Contents
Chapter 1 Introduction ............................................................................................................... 1
System Description ...................................................................................................................... 1
Chapter 2 Start Up...................................................................................................................... 3
2.1 Activate the Device with WEB .............................................................................................. 3
2.2 Activation with Wi-Fi ............................................................................................................. 3
Chapter 3 Configuration ........................................................................................................... 10
3.1 Set-up with the Web Client ................................................................................................. 10
3.1.1 System Settings ........................................................................................................ 11
3.1.2 Device Management ................................................................................................ 21
3.1.3 Video Management .................................................................................................. 31
3.1.4 Area Settings ............................................................................................................ 33
3.1.5 Communication Settings .......................................................................................... 34
3.1.7 Maintenance............................................................................................................. 48
3.1.8 Check Status ............................................................................................................. 53
3.2 Set-up with Hik-Proconnect ................................................................................................ 53
3.3 Set-up with Hik-Connect ..................................................................................................... 75
3.4 Report to ARC (Alarm Receiver Center) ............................................................................. 98
Setup ATS in Transceiver of Receiving Center .................................................................. 98
Setup ATS in Transceiver of the Panel .............................................................................. 99
Signaling Test ................................................................................................................... 101
Chapter 4 General Operations ................................................................................................ 102
4.1 Access Entries .................................................................................................................... 102
4.2 Arming ............................................................................................................................... 102
4.3 Disarming ........................................................................................................................... 104
4.4 SMS Control ....................................................................................................................... 104
A. Trouble Shooting................................................................................................................ 105
A.1 Communication Fault ........................................................................................................ 105
A.1.1 IP Conflict ............................................................................................................... 105
A.1.2 Web Page is Not Accessible ................................................................................... 105
v
AX HYBRID PRO User Manual
vi
Chapter 1 Introduction
System Description
AX HYBRID PRO control panel is a wired intrusion control panel with wireless detectors &
peripherals access capability. It is the first control panel that supports high-speed Speed-X Bus,
which is a creative technology and is used to transmit verification video/picture from PIR-CAM.
Besides, this hybrid control panel supports customized voice library, which is designed for users to
upload customized voice files. These voice files will be played via alarm phone call when alarm
triggered. As for basic functions, it supports Wi-Fi, PSTN, TCP/IP and GPRS/3G/4G communication
methods. It also supports Hik-ProConnect, Hik-Connect, Hik IP Receiver, Hik IP Receiver Pro and
Hik-Central, which is applicable to the scenarios of market, hotel, supermarket, warehouse, office,
house (especially with cables pre-installed), etc.
1
Note
ISUP5.0: a privacy internet protocol that is used for accessing the third-party platform, which
supports alarm report uploading, AX HYBRID PRO management, and short video uploading.
The prioritization of the message and indications are the same. The AXPRO uploads messages and
gives indications synchronously.
Note
Standard DC-09 Protocol:
ADM-CID: The data presenting method of DC-09 is CID, which is not encrypted and only for
uploading alarm report.
*ADC-CID: The data presenting method of DC-09 is CID, which is encrypted and only for
uploading alarm report.
SIA-DCS: The data presenting method of DC-09 is DCS (also called SIA protocol), which is not
encrypted and only for uploading alarm report.
*SIA-DCS: The data presenting method of DC-09 is DCS (also called SIA protocol), which is
encrypted and only for uploading alarm report.
2
Chapter 2 Start Up
Note
If you connect the device with the PC directly, you need to change the IP address of your PC
to the same subnet as the device. The default IP address of the device is 192.0.0.64.
2. Create and confirm the admin password. (The default user name of admin account is admin.)
Caution
STRONG PASSWORD RECOMMENDED-We highly recommend you create a strong password
of your own choosing (using a minimum of 8 characters, including upper case letters, lower
case letters, numbers, and special characters) in order to increase the security of your
product. And we recommend you reset your password regularly, especially in the high
security system, resetting the password monthly or weekly can better protect your product.
3. Click OK to complete activation.
Note
• The default user name of admin account is admin.
• You should login the admin account first to enable the installer.
• The default password of the installer is installer12345.
3
Step1 Create a site (Only for HPC)
Download the Hik-ProConnect and login with the installer account.
A site is the place where the alarm system deployed. Create a site where the device can be added
to with it’s site name and address. The owner of the site would be an end user, usually regarded as
administrator.
4. Connect your phone to your home Wi-Fi. Make sure that this Wi-Fi can access the Internet
normally and the signal is stable.
5. Open the HC or HPC, tap +, and select Scan QR Code. Scan the QR code of the AX HYBRID and
wait for the result.
Or you can tap Manual Adding and enter the serial No.
4
6. Tap Next.
8. The APP will automatically fill in the home Wi-Fi currently used by the mobile phone into the
page, as shown in the figure below. After confirming the Wi-Fi password, tap Next.
5
9. Tap Connect to a Network.
10. Enter the device verification code and tap OK. (The verification code is on the device label.)
11. The APP will search the device Wi-Fi automatically. Check whether the connected Wi-Fi is
belonged to the target device and tap Connect. As shown in the figure below, the Wi-Fi connected
6
to the mobile phone should with name “HAP_serial number” (AX HYBRID PRO serial number)
12. Follow the prompts: turn the Wi-Fi mode switch to WLAN.
7
13. Wait for the device to join the home Wi-Fi and log in the Cloud.
(1) When the home Wi-Fi signal is good, the control panel will successfully log in to cloud and
complete the binding before the countdown ends.
(2) When the home Wi-Fi signal is unstable, the control panel may not be connected to the cloud
before the countdown ends, and the following page will appear:
8
If you make sure that the home Wi-Fi password is correct and quality is good, tap Refresh
Network, the control panel will enter a new countdown. You can wait for the connection.
If you want to change the home Wi-Fi, you should change the home Wi-Fi connected to the mobile
phone first, then press the RESET button of the control panel (marked in the figure below) for 10
seconds. Tap Retry. The interface will jump back step 8, you can configure the network again.
9
Chapter 3 Configuration
Note
Only the admin and the installer can login to the web client.
You can view the user, device, and area status on the overview page.
10
3.1.1 System Settings
Time Settings
You can set the device time zone, synchronize device time, and set the DST time. The device
supports time synchronization via Hik-Connect server.
Time Management
Click System → System Settings → Time Management to enter the Time Management page.
Note
While you synchronize the time manually or with the computer time, the system records the log
“SDK Synchronization”.
DST Management
Click System → System Settings → DST Management to enter the Time Management page.
You can enable the DST and set the DST bias, DST start time, and DST end time.
11
Authority Management
Set the authority options.
Click System → System Options → System Management to enter the page.
Note
You should disable the Arm With Faults in the Arm Options page. Or the Forced Auto
Arm/Forced Arming function cannot be valid.
Forced Arming
After enabled, when manual arming starts, if there are active faults in a zone, the zone will be
automatically bypass.
You can use keyfobs, tags, and keypads to arm zones, or manually arm zones on APP. Single,
multiple or all areas can be selected for arming.
Note
You should disable the Arm With Faults in the Arm Options page. Or the Forced Auto
Arm/Forced Arming function cannot be valid.
12
Audible Tamper Alarm
While enabled, the system will alert with buzzer for the tamper alarm. Regardless of whether it
is enabled or not, the tamper alarm will be normally pushed to Cloud (for APP) and ARC.
Panel Lockup Button
All functions of AX HYBRID PRO will be frozen after it is enabled. This function can only be
enabled by users with installer permission.
Bypass on Re-Arm
While enabled, after the detector is bypassed, if its faults are restored and the linked area is
armed, the detector will automatically arm.
Polling Loss Times
Set the maximum number of times for polling loss of peripherals and detectors. The system will
report fault if the time is over the limit. The status of these peripherals and detectors will be
shown as offline.
Motion Detector Restore
Motion detectors include all PIR detectors.
-Disable: No automatic restore.
-Immediate After Alarm: Motion detectors automatically restores immediately after the alarm
and reports to Cloud (for APP) and ARC.
-After Disarm: Motion detectors automatically restores after disarming and reports to Cloud
(for APP) and ARC
Jamming Sensitivity Settings
The device will detect RF interference and push messages when the RF interference interferes
with communication. You can adjust the detection sensitivity.
Enable PD6662
Enable PD6662 standard. Functions that do not meet the standard will not take effect.
Keypad Logout
After the keypad enters the programming page, if there is no key operation, it will exit the
programming page after reaching this time.
13
2. Select an area.
3. Set the following parameters according to actual needs.
Enable Auto Arm
Enable the function and set the arming start time. The zone will be armed according to the
configured time.
Note
● The auto arming time and the auto disarming time cannot be the same.
● The buzzer beeps slowly 2 minutes before the auto arming starts, and beeps rapidly 1
minute before the auto arming starts.
● You can select to enable forced arming on the System Options page. While the function is
enabled, the system will be armed regardless of the fault.
Note
● The auto arming time and the auto disarming time cannot be the same.
Late to Disarm
Enable the function and set the time. If the alarm is triggered after the configured time, the
person will be considered as late.
14
Note
You should enable the Panel Management Notification function in Communication
Parameters → Event Communication before enabling the Late to Disarm function.
Weekend Exception
Enable the function and the zone will not be armed in the weekend.
Holiday Exception
Enable the function and the zone will not be armed/disarmed in the holiday. You should set
the holiday schedule after enabling.
Note
Up to 6 holiday groups can be set.
Note
The available time duration range is from 10 s to 900 s.
5. Click Save.
Fault Check
The fault check here is only for the control panel in the normal status.
The system determines whether to check the faults listed on the page. The system will only check
the fault that is selected.
Click System → System Options → System Fault Check to enter the page.
15
Detect Network Camera Disconnection
If the option is enabled, when the linked network camera is disconnected, an alarm will be
triggered.
Panel Battery Fault Check
If the option is enabled, when battery is disconnected or in low battery status, the device will
upload events.
LAN Lost
If the option is enabled, when the wired network is disconnected or with other faults, the alarm
will be triggered.
Wi-Fi Lost
If the option is enabled, when the Wi-Fi is disconnected or with other faults, the alarm will be
triggered.
Cellular Lost
If the option is enabled, when the cellular data network is disconnected or with other faults, the
alarm will be triggered.
Panel Main Power Lost
If the option is enabled, an alarm will be triggered when the control panel main supply is
disconnected.
Panel Main Power Loss Delay
The system checks the fault after the configured time duration after AC power down.
To compliant the EN 50131-3, the check time duration should be 10 s.
Arm Options
This function is for the whole alarm system, to inform the user of the current system status before
arming. If it is enabled, there will be a fault prompt and confirmation process for keypads, keyfobs,
and APP. If it is not enabled, there will be no fault detection before arming.
Click System → System Options →Arm Options to enter the page.
16
You can set the following parameters:
Arm with Fault
Check the faults in the Arm with Fault list, and the device will not stop the arming process when
faults occurred.
Fault Checklist
The system will check if the device has the faults in the checklist during the arming process.
Early Alarm
A delay zone is triggered first, and the area is in the "Entry Delay" stage. During the delay time
period, an instant zone is triggered. At this time, the area enters the early alarm stage. There
are control panel voice alarm and local sounder alarm, but no alarm message is pushed. If the
zone is disarmed or silence before both the early alarm and entry delay end, the alarm message
will not be reported. Otherwise, both the delayed zone and the instant zone will alarm.
17
Entry Delay
Disarm/Silence No Alarm
OR
Entry Delay
Disarm/Silence No Alarm
Security Settings
SSH Settings
Enable or disable SSH (Secure Shell) according to your actual needs.
Click System → System Security → SSH Settings to enter the SSH Settings page and you can
enable or disable the SSH function.
18
Locking User Settings
The device will be locked 90 s after 3 failed credential attempts (can be set in Retry Time before
Auto-Lock) in a minute.
You can view the locked user or unlock a user and set the user locked duration.
Note
To compliant the EN requirement, the system will only record the same log 3 times continuously.
Steps
1. Click System → System Security → User Lockout Attempts to enter the Locking User Settings
page.
19
Note
The administrator has two more attempts than the configured value.
Auto-lock Time
Set the locking duration when the account is locked.
Note
The available locking duration is 5s to 1800s.
3. Click to unlock the account or click Unlock All to unlock all locked users in the list.
4. Click Save.
20
4. Click OK.
5. Optional: Click the Lock icon to unlock the locked module.
Zone
You can set the zone parameters on the zone page.
Steps
1. Click Device → Zone to enter the Zone page.
21
Note
Only enabled areas will be listed.
The newly added peripheral is linked to area 1 by default.
-Entry Delay: Entry Delay provides you time to enter the zone to disarm the system without
alarm.
After triggering, if the zone is not disarmed or silenced before the entry delay time ends, the
zone will alarm.
-Stay Arm Delay Time: Stay arming uses Stay Arm Delay Time to count down.
The system gives Entry/Exit delay time when it is armed or reentered. It is usually used in
entrance/exit route (e.g. front door/main entrance), which is a key route to arm/disarm via
operating keypad for users.
Note
You can set 2 different time durations in System Options → Schedule & Timer.
Ensure that timer is no longer than 45 seconds in order to comply with EN50131-1.
You can set Stay Arm Delay Time for the delay zone.
Panic Zone
24-hour active zone, whether armed or not. Report panic alarm after triggering. It is usually
used in the sites equipped with panic button, smoke detector and glass-break detector.
Medical Alarm
24-hour active zone, whether armed or not. Report medical alarm after triggering.
Fire Zone
24-hour active zone, whether armed or not. Report fire alarm after triggering.
Gas Zone
22
24-hour active zone, whether armed or not. Report gas alarm after triggering.
Follow Zone
The zone acts as delayed zone when it detects triggering event during system Entry Delay,
while it acts as instant zone otherwise.
Keyswitch Zone
-By Trigger Time: Change the arming and disarming status after each trigger. For example, in
the disarmed status, if the zone is triggered, the linked area will be armed. Trigger the zone
again and the area will be disarmed.
-By Zone Status: You need to choose to arm or disarm the linked area after the zone is
triggered.
In the case of the tampering alarm, the arming and disarming operation will not be triggered.
Disabled Zone
Zone disabled ignoring any alarm event. It is usually used to disable faulty detectors.
24-hour Zone
The zone activates all the time with sound/light output when alarm occurs, whether it is
armed or not. It is usually used in fire hazardous areas equipped with smoke detectors and
temperature sensors.
Timeout Zone
The zone activates all the time. When this zone has been triggered or restored and exceeds
the set time, an alarm will be generated.
It can be used in places equipped with magnetic contacts that require access but for only a
short period (e.g., fire hydrant box's door or another external security box door).
-Not-Triggered Zone Alarm: If the zone is not triggered for the set time, it will alarm.
-Alarm on Zone Activated: If the zone is triggered for the set time, it will alarm.
-Retry Time Period: Set the timeout period.
7. Enable other functions according to your detector types and actual needs.
Note
The configurable functions vary in different detectors and zones. Refer to the actual zone to set
the function.
Arm Mode
If the zone is a public zone (the zone is belongs to more than one areas), you can set arm
mode.
And: When all linked areas are armed, the zone will arm. When any of linked areas is
disarmed, the zone will disarm.
Or: When any of the linked areas is armed, the zone will arm. When all linked areas are
disarmed, the zone will disarm. When the zone is in alarm, the disarmed areas linked with the
zone cannot be armed.
23
Stay Arm Bypass
The zone will be automatically bypassed in stay arming.
Cross Zone
PD6662 is not enabled: You need to set the combined time interval.
When the first zone is triggered, the system will start timing after the zone is restored. If the
second zone is triggered within the set time, both zones will give alarms. Otherwise, no alarm
will be triggered.
If the first zone is not be restored, both zones will give alarms when the second zone is
triggered, regardless of whether the set time has elapsed.
PD6662 is enabled: You need to set the combined time interval.
The first zone will give an alarm when triggered. If the first zone is not restored and the
second zone is triggered, the system will report the alarm confirmation.
If the first zone is restored, the system will start timing. If the second zone is triggered within
the set time, the system will report the alarm confirmation.
If the first zone is restored, the system will start timing. If the second zone is not triggered
within the set time, no information will be reported.
Forbid Bypass on Arming
After enabled, you cannot bypass zones when arming.
Chime
Enable the doorbell. Usually used for door magnetic detectors.
Silent Alarm
After enabled, when an alarm is triggered, only the report will be uploaded and no sound is
emitted.
Double knock
After enabled, the time interval can be set. If the same detector is triggered twice or
continuously in a period of time, the alarm will be triggered.
Sounder Delay Time
The sounder will be triggered immediately (0s) or after the set time.
Final Door Exit
Only magnetic contacts have this option.
After enabling, when the user use keypads or tags to arm:
-Arm With Faults is enabled: During the arming countdown, if the magnetic contact is
triggered and then restored, the arming process will be terminated immediately after
restoring, and the arming is completed.
- Arm With Faults is disabled: If the magnetic contact is triggered and then restored, the
linked area immediately arms the delayed zone.
Dual Zone
After enabled, when multi transmitter detects that the entire zone circuit of the local zone
and the extended zone is open circuit, both zones trigger lid opened alarms.
24
Timer With Restart
During the Exit Delay process, the exit delay time will be re-timed at the time when the
second delay zone was triggered.
7. If required, link a PIRCAM or a camera for the zone.
8. Click OK.
Note
After setting the zone, you can enter Maintenance → Device Status → Zone Status to view the
zone status.
Sounder
Set sounder parameters.
Steps
1. Click Device → Sounder to enter the Sounder page.
2. Click to enter the Sounder Settings page.
Note
Only enabled areas will be listed.
The newly added peripheral is linked to area 1 by default.
25
7. Click OK.
Note
After the sounder is configured, you can click Maintenance → Device Status → Sounder Status
to view the sounder status.
Keypad
You can set the parameters of the keypad that is enrolled to the AX HYBRID PRO .
Steps
1. Click Device → Keypad to enter the page.
2. Click to enter the Keypad Settings page.
26
When someone enters the delay zone, the screen and backlight of the keypad will be on.
This function can indicate the keypad position for those who enter the delay zone at night.
Keypad Arming Light
Enable the arming indicator of the keypad.
Note
Only enabled areas will be listed.
The newly added peripheral is linked to area 1 by default.
For detailed information, refers to the keypad user manual.
7. Click OK.
Note
● After the keypad is configured, you can click Maintenance → Device Status → Keypad Status
to view the keypad status.
● You can set the keypad password on the page of User → User Management→ Operation.
Keyfob
You can set the parameters of the keyfob.
Steps
1. Click Device → Keyfob to enter the page.
2. Click Enroll to add a keyfob.
3. Click to edit the keyfob parameters.
27
6. Configure the functions of the buttons according to your actual needs.
7. Click OK.
Tag
You can set the parameters of tags.
Steps
1. Click Device → Tag to enter the page.
2. Click Enroll, enter the serial No. to add a tag, or click to edit the tag parameters.
Automation
You can set the parameters of the relay outputs that is enrolled.
Steps
1. Click Device → Automation to enter the page.
2. Click Enroll, enter the serial No. and select the main device type, main device name, channel to
add a relay output device.
3. Click to edit the relay information.
28
4. Set the relay name.
5. Select the linked area.
Note
Only enabled areas will be listed.
The newly added peripheral is linked to area 1 by default.
The function varies according to different relay types
29
7. Click OK.
Network Camera
You can add network cameras in the system.
Steps
1. Click Device → Network Camera to enter the network camera management page.
2. Click Enroll, and enter the basic information of the camera, such as IP address and port No., and
select the protocol type.
3. Enter the user name and password of the camera.
SADP Scanning
Scan all network cameras in the same LAN. A list will pop up after scanning. You can directly
check to add cameras in the list.
4. Click OK.
5. Optional: Click Edit or Delete to edit or delete the selected camera.
Module
Set module parameters.
Steps
1. Click Device → Module to enter the page.
2. Click edit the parameters.
3. Select linked areas.
4. Optional: Enable AUX according to your needs. It will enable the auxiliary power output of the
module. (Only for input expanders and output expanders.)
5. Click OK.
30
Scan Adding
Scan peripherals on the bus, and display the scanned peripherals that are not enroll as a list.
Steps
1. Click Device → Scan Adding to enter the page.
2. Click Scan Updating to see if there are devices can be added.
Note
The scan takes 3 to 5 minutes.
Steps
1. Click Device → Network Camera to enter the network camera management page.
31
2. Click Enroll, and enter the basic information of the camera, such as IP address and port No., and
select the protocol type.
3. Enter the user name and password of the camera.
SADP Scanning
Scan all network cameras in the same LAN. A list will pop up after scanning. You can directly
check to add cameras in the list.
4. Click OK.
5. Optional: Click Edit or Delete to edit or delete the selected camera.
Steps
1. Click Device → Zone to enter the configuration page.
2. Select a zone that you wish to include video monitoring, and click .
3. Select the Link Camera.
4. Click OK.
Note
Only if the zone is linked with a network camera, the alarm email will be attached with alarm
video.
Steps
1. Click Device → Network Camera → Video Parameters to enter the page.
32
2. Select a camera and set the video parameters.
Stream Type
Main Stream: Being used in recording and HD preview, it has a high resolution, code rate and
picture quality.
Sub-Stream: It is used to transmit network and preview pictures as a video streaming with
features of lower resolution, bit rate and picture quality.
Bitrate Type
Select the Bitrate type as constant or variable.
Resolution
Select the resolution of the video output.
Video Bitrate
The higher value corresponds to the higher video quality, but the better bandwidth is
required.
Post-record/Pre-record
Set the recording video time before and after the alarm.
Basic Settings
You can link zones to the selected area.
Steps
1. Click Area → Basic Settings to enter the page.
2. Select an area.
33
3. Check Enable.
4. Check the check box to select zones for the area.
5. Click Save.
Wired Network
You can set the device IP address and other network parameters.
Steps
Note
Functions varied depending on the model of the device.
34
Wi-Fi
You can set the Wi-Fi parameters if there are secure and credible Wi-Fi networks nearby.
Steps
1. Click Communication → Wi-Fi to enter the Wi-Fi page.
2. Connect to a Wi-Fi.
– Manually Connect: Enter the SSID Wi-Fi and Wi-Fi Password, select Encryption Mode and click
Save.
– Select from Network List: Select a target Wi-Fi from the Network list. Click Connect and enter
Wi-Fi password and click Connect.
3. Click WLAN to enter the WLAN page.
35
4. Set IP Address, Subnet Mask, Gateway Address, and DNS Server Address.
Note
If enable DHCP, the device will gain the Wi-Fi parameters automatically.
5. Click Save.
Cellular Network
Set the cellular network parameters if you insert a SIM card inside the device. By using the cellular
network, the device can upload alarm notifications to the alarm center.
Before You Start
Insert a SIM card into the device SIM card slot.
Steps
1. Click Communication → Cellular Data Network to enter the Cellular Data Network Settings
page.
36
2. Enable the function.
3. Set the cellular data network parameters.
Access Number
Input the operator dialing number.
Note
Only the private network SIM card user needs to enter the access number.
User Name
Ask the network carrier and input the user name.
Access Password
Ask the network carrier and input the password.
APN
Ask the network carrier to get the APN information and enter the APN information.
Data Usage Limit
You can enable the function and set the data threshold every month. If data usage is more
than the configured threshold, an alarm will be triggered and uploaded to the alarm center
and mobile client.
Data Used This Month
The used data will be accumulated and displayed in this text box.
4. Click Save.
37
Alarm Center
You can set the alarm center’s parameters and all alarms will be sent to the configured alarm
center.
Steps
1. Click Communication → Alarm Receiving Center to enter the Alarm Receiving Center page.
2. Select the ARC1 or ARC3 for configuration, and slide the slider to enable the selected alarm
receiver center.
Note
Only if the alarm receiver center 1/3 is enabled, you can set the alarm receiver center 2/4 as the
backup channel and edit the channel parameters.
3. Select the Protocol Type as ADM-CID, ISUP, SIA-DCS, *SIA-DCS, *ADM-CID, or CSV-IP to set
uploading mode.
38
Note
Standard DC-09 Protocol
ADM-CID: The data presenting method of DC-09 is CID, which is not encrypted and only for
uploading alarm report.
*ADM-CID: The data presenting method of DC-09 is CID, which is encrypted and only for
uploading alarm report.
SIA-DCS: The data presenting method of DC-09 is DCS (also called SIA protocol), which is not
encrypted and only for uploading alarm report.
*SIA-DCS: The data presenting method of DC-09 is DCS (also called SIA protocol), which is
encrypted and only for uploading alarm report.
ADM-CID or SIA-DCS: You should select the Address Type as IP or Domain name, and enter the
Server address, port number, account code, impulse counting time, attempts, polling rate, etc.
Note
Set the polling rate with the range from 10 to 3888000 seconds.
ISUP, CSV-IP: You do not need to set the protocol parameters.
*SIA-DCS or *ADM-CID You should select the Address Type as IP or Domain name, and enter
the IP address, port number, account code, impulse counting time, attempts, polling rate,
encryption arithmetic, password length, etc.
Note
Set the polling rate with the range from 10 to 3888000 seconds.
1. Click Save.
39
(6) Configure SMTP or FTP parameters.
Configure SMTP parameters:
Click Communication → Notification by Email.
Enable Video Verification Events and set corresponding parameters. For details, see
Notification by Email. Click Save.
40
2. Upload Videos
In this condition, when the PIRCAM is set to catch more than two pictures, videos will be
uploaded.
(1) Click Communication → Alarm Receiving Center to enter the Alarm Receiving Center
page.
(2) Slide the slider to enable the selected alarm receiver center.
(3) Select the Protocol Type as SIA-DCS.
(4) Click Save.
(5) Configure SMTP or FTP parameters as same as Upload Photos.
Notification Push
When an alarm is triggered, if you want to send the alarm notification to the client, alarm center,
cloud or mobile phone, you can set the notification push parameters.
Steps
1. Click Communication → Event Types Notification.
41
2. Enable the target notification.
Zone Alarm/Lid Opened
The device will push notifications when the zone alarm (on web client, software client or mobile
client) is triggered or the zone peripherals alarm is triggered or restored.
Peripherals Lid Opened
The device will push notifications when lid opened alarm of any peripheral is triggered or
restored.
Panel Lid Opened
The device will push notifications when lid opened alarm of the control panel is triggered or
restored.
Panic Alarm
The device will push notifications when panic alarm on keypads or keyfobs is triggered or
restored.
Medical Alarm
The device will push notifications when medical alarm on keypads is triggered.
Fire Alarm
The device will push notifications when fire alarm on keypads is triggered or a user presses the
fire alarm key on the keypad.
42
Gas Alarm
The device will push notifications when gas alarm on keypads is triggered.
Panel Status
The device will push notifications when the control panel system status is changed.
Zone Status
The device will push notifications when any zone status is changed.
Peripherals Status
The device will push notifications when any peripheral status is changed.
Panel Operation
The device will push notifications when the user operate the control panel.
Smart Alarm Event
The device will push notifications when alarm is triggered in network cameras.
3. Optional: For Alarm Receiving Center, you need to select center number before settings.
4. Optional: If you want to send the alarm notifications to the mobile client, you should set Phone
Call and SMS parameters.
(1) Set the Mobile Phone Index and Mobile Phone Number.
43
(2) Check Voice Call on Telephone page.
(3) Select time of Filtering Interval Time and Number of Calls.
(4) Check SMS on Message page.
(5) Select areas that have arming, disarming or alarm clearing permission.
General Hint
You can import Common Voice. When the alarm is triggered, your customized voice will be
added at the beginning of the content of the phone dialed by the system.
Note
Only WAV format is supported, up to 512 KB and 15 s.
You can enter Common Message. When the alarm is triggered, your customized content will be
added at the beginning of the message sent by the system.
5. Click Save.
Note
For mobile phone notification:
You need to press * to finish the call.
It is required to add control code when entering the mobile phone number.
Cloud Service
If you want to register the device to the mobile client for remote configuration, you should set the
mobile client registration parameters.
Before You Start
● Connect the device to the network via wired connection, dial-up connection, or Wi-Fi
connection.
● Set the device IP address, subnet mask, gateway and DNS server in the LAN.
Steps
1. Click Communication → Cloud Service to enter the Hik-Connect Registration Settings page.
44
2. Check Register to Hik-Connect.
Note
By default, the device Hik-Connect service is enabled.
You can view the device status in the Hik-Connect server (www.hik-connect.com).
3. Enable Custom Server Address.
The server address is already displayed in the Server Address text box.
4. Select a communication mode from the drop-down list according to the actual device
communication method.
Wired Network & Wi-Fi Priority
The connection priority order from high to low is: wired network, Wi-Fi, cellular data
network.
Wired &Wi-Fi
The system will select wired network first. If no wired network detected, it will select Wi-Fi
network.
Cellular Data Network
The system will select cellular data network only.
5. Optional: Change the verification code.
Note
● By default, the verification code is displayed in the text box.
● The verification code should contain 6 to 12 letters or digits. For security reasons, an 8-
character password is suggested, which containing two or more of the following character
types: uppercases, lowercases, and digits.
45
6. Enable Periodic Test. Enter the periodic test interval.
7. Click Save.
Notification by Email
You can send the alarm video or event to the configured email.
Steps
1. Click Communication → Notification by Email to enter the page.
2. Enable Video Verification Events and Server Authentication.
3. Enter the sender’s information.
Note
It is recommended to use Gmail and Hotmail for sending mails.
Only if the zone is linked with a network camera, the alarm email will be attached with alarm
video.
NAT
Universal Plug and Play (UPnP™) is a networking architecture that provides compatibility among
networking equipment, software and other hardware devices. The UPnP protocol allows devices
to connect seamlessly and to simplify the implementation of networks in the home and corporate
environments.
Enable the UPnP function, and you don’t need to configure the port mapping for each port, and
the device is connected to the Wide Area Network via the router.
Steps
1. Click Communication → NAT to enter the page.
46
2. Drag the slider to enable UPnP.
3. Optional: Select the mapping type as Manual and set the HTTP port and the service port.
4. Click Save to complete the settings
FTP
You can configure the FTP server to save alarm video.
Steps
1. Click Communication → FTP to enter the page.
2. Configure the FTP parameters
FTP Type
Set the FTP type as preferred or alternated.
FTP Protocol
FTP and SFTP are selectable. The files uploading is encrypted by using SFTP protocol.
Server and Port
The FTP server address and corresponding port.
User Name and Password
The FTP user should have the permission to upload pictures. If the FTP server supports
picture uploading by anonymous users, you can check Anonymous to hide your device
information during uploading.
Directory Structure
The saving path of snapshots in the FTP server.
47
3.1.7 Maintenance
Device Upgrade
Only installer can upgrade the device on web client.
Steps:
1. Click Maintenance→ Device Information to enter the page.
Note
Both of the users and configuration information will be retained after upgrade finished.
View Licenses
You can view device name and other information.
48
Select a major type and a minor type from the drop-down list, set the log start time and end time
and click Filter. All filtered log information will be displayed in the list.
You can also click Reset to reset all search conditions.
Test
The AX HYBRID PRO supports walk test function.
Steps
1. Enter Maintenance → Device Maintenance → Test to enable the function.
49
Note
Only when all the detectors are without fault, you can enter the mode TEST mode.
System Maintenance
You can reboot the device, restore default settings, import/export configuration file.
Select the device and click in the client software, or enter the device IP address in the address
bar of the web browser. Click Maintenance→ Device Maintenance→ Maintenance to enter the
page.
50
Reboot
Click Reboot to reboot the device.
Restore Default Settings
Click Partly Restore to restore all parameters except for admin user information, wired
network, Wi-Fi network, detector information, and peripheral information to default ones.
Click Restore All to restore all parameters to the factory settings.
Import Configuration File
Click View to select configuration file from the PC and click Import Configuration File to import
configuration parameters to the device. Importing configuration file requires entering the
password set at the time of exporting.
Export Configuration File
Click Export Configuration File to export the device configuration parameters to the PC.
Exporting configuration file requires a password to be used for file encryption.
Tamper Alarm on HPC Login
After this function is enabled, the device lid opened alarm (tamper alarm) takes effect when
installer login. (By default, the lid opened alarm (tamper alarm) does not take effect when the
installer login.)
Export File
You can export debugging file to the PC.
Steps
1. Click Maintenance → Device Maintenance → Export File to enter the page.
51
2. Check the check box to enable the function.
3. Click Export to save the debugging file in the PC.
Note
Formats include ca.crt、ca-chan.crt、private.txt are allowed.
5. Click Install.
6. Click Save.
52
3.1.8 Check Status
After setting the zone, repeater, and other parameters, you can view their status.
Click Maintenance → Device Status. You can view the status of zone, sounder, automation,
keypad, keyfob and module.
Note
● For details, see User Manual of Hik-ProConnect Mobile Client.
● You need an invitation code for registration. Please ask technical supports.
53
3.2.2 Add AX HYBRID PRO to the Mobile Client
Add AX HYBRID PRO to the mobile client before other operations.
Steps
1. Power on the AX HYBRID PRO.
2. Create or search a site.
– Tap +, set site name, time zone, address, city, state/province/region and tap OK to create a
site.
– Enter site name in the search area and tap Search Icon to search a site.
3. Tap Add Device.
– Tap Scan QR Code to enter the Scan QR code page. Scan the QR code on the AX HYBRID PRO.
Note
Normally, the QR code is printed on the label stuck on the back cover of the AX HYBRID PRO.
Tap Manual Adding to enter the Add Device page. Enter the device serial No. and verification code
to add the device.
4. Activate the Device.
54
Enable Alarm
Tap to select Audible Panic Alarm or Silent Panic Alarm.
View Faults
Tap to view faults.
Area Management
Tap + to add an area.
Tap Area to enter the area management page. Refers to 3.2.15 Set Arming/Disarming
Schedule for details.
55
● Away Arming: Tap to away arm a single area. When all the people in the detection area
leave, turn on the Away mode to arm all zones in the area after the defined dwell time.
● Stay Arming: Tap to stay arm a single area. When all the people stays inside the detection
area, turn on the Stay mode to arm all the perimeter burglary detection set in all the zones of all
areas.
● Select Areas: Tap to select areas you want to operate. If you do not select areas, following
operations will take effect for all areas.
● Away Arming: Tap to away arm selected areas. When all the people in the detection area
leave, turn on the Away mode to arm all zones in all areas after the defined dwell time.
● Stay Arming: Tap to stay arm all areas. When the people stays inside the detection area,
turn on the Stay mode to arm all the perimeter burglary detection (such as perimeter detector,
magnetic contacts, curtain detector in the balcony) set in all the zones of all areas. At the
meantime, the detectors inside the detection area are bypassed (such as PIR detectors). People
can move inside the area and alarm will not be triggered.
● Disarming: Tap to disarm all areas. In Disarm mode, all the zones of all areas will not
trigger alarm, no matter alarm events happen or not.
● Silent Alarm: Tap to silent alarms for all areas.
56
2. Tap + to add a new zone.
3. Tap a zone to enter the management page. You can view device status (e.g. temperature,
battery status, single strength, etc.).
4. Tap on the upper right corner to enter the zone settings page.
5. Select a zone type.
Instant Zone
This Zone type will immediately trigger an alarm event when armed.
Delay Zone
-Exit Delay: Exit Delay provides you time to leave through the zone without alarm.
Arm with faults is enabled: You should confirm faults first, and then the zone is in arming
process. If the delay zone is triggered within the exit delay time but it restores before the
time ends, the alarm will not be triggered and the zone will be armed.
Arm with faults is disabled: Immediately armed. If the delay zone is triggered within the exit
delay time but it restores before the time ends, the alarm will not be triggered.
-Entry Delay: Entry Delay provides you time to enter the zone to disarm the system without
alarm.
After triggering, if the zone is not disarmed or silenced before the entry delay time ends, the
zone will alarm.
-Stay Arm Delay Time: Stay arming uses Stay Arm Delay Time to count down.
The system gives Entry/Exit delay time when it is armed or reentered. It is usually used in
entrance/exit route (e.g. front door/main entrance), which is a key route to arm/disarm via
operating keypad for users.
57
Note
You can set 2 different time durations in System Options → Schedule & Timer.
Ensure that timer is no longer than 45 seconds in order to comply with EN50131-1.
You can set Stay Arm Delay Time for the delay zone.
Panic Zone
24-hour active zone, whether armed or not. Report panic alarm after triggering. It is usually
used in the sites equipped with panic button, smoke detector and glass-break detector.
Medical Alarm
24-hour active zone, whether armed or not. Report medical alarm after triggering.
Fire Zone
24-hour active zone, whether armed or not. Report fire alarm after triggering.
Gas Zone
24-hour active zone, whether armed or not. Report gas alarm after triggering.
Follow Zone
The zone acts as delayed zone when it detects triggering event during system Entry Delay,
while it acts as instant zone otherwise.
Keyswitch Zone
-By Trigger Time: Change the arming and disarming status after each trigger. For example, in
the disarmed status, if the zone is triggered, the linked area will be armed. Trigger the zone
again and the area will be disarmed.
-By Zone Status: You need to choose to arm or disarm the linked area after the zone is
triggered.
In the case of the tampering alarm, the arming and disarming operation will not be triggered.
Disabled Zone
Zone disabled ignoring any alarm event. It is usually used to disable faulty detectors.
24-hour Zone
The zone activates all the time with sound/light output when alarm occurs, whether it is
armed or not. It is usually used in fire hazardous areas equipped with smoke detectors and
temperature sensors.
Timeout Zone
The zone activates all the time. When this zone has been triggered or restored and exceeds
the set time, an alarm will be generated.
It can be used in places equipped with magnetic contacts that require access but for only a
short period (e.g., fire hydrant box's door or another external security box door).
-Not-Triggered Zone Alarm: If the zone is not triggered for the set time, it will alarm.
-Alarm on Zone Activated: If the zone is triggered for the set time, it will alarm.
58
-Retry Time Period: Set the timeout period.
7. Enable other functions according to your detector types and actual needs.
Note
The configurable functions vary in different detectors and zones. Refer to the actual zone to set
the function.
Arm Mode
If the zone is a public zone (the zone is belongs to more than one areas), you can set arm
mode.
And: When all linked areas are armed, the zone will arm. When any of linked areas is
disarmed, the zone will disarm.
Or: When any of the linked areas is armed, the zone will arm. When all linked areas are
disarmed, the zone will disarm. When the zone is in alarm, the disarmed areas linked with the
zone cannot be armed.
Stay Arm Bypass
The zone will be automatically bypassed in stay arming.
Cross Zone
PD6662 is not enabled: You need to set the combined time interval.
When the first zone is triggered, the system will start timing after the zone is restored. If the
second zone is triggered within the set time, both zones will give alarms. Otherwise, no alarm
will be triggered.
If the first zone is not be restored, both zones will give alarms when the second zone is
triggered, regardless of whether the set time has elapsed.
PD6662 is enabled: You need to set the combined time interval.
The first zone will give an alarm when triggered. If the first zone is not restored and the
second zone is triggered, the system will report the alarm confirmation.
If the first zone is restored, the system will start timing. If the second zone is triggered within
the set time, the system will report the alarm confirmation.
If the first zone is restored, the system will start timing. If the second zone is not triggered
within the set time, no information will be reported.
Forbid Bypass on Arming
After enabled, you cannot bypass zones when arming.
Chime
Enable the doorbell. Usually used for door magnetic detectors.
Silent Alarm
After enabled, when an alarm is triggered, only the report will be uploaded and no sound is
emitted.
59
Double knock
After enabled, the time interval can be set. If the same detector is triggered twice or
continuously in a period of time, the alarm will be triggered.
Sounder Delay Time
The sounder will be triggered immediately (0s) or after the set time.
Final Door Exit
Only magnetic contacts have this option.
After enabling, when the user use keypads or tags to arm:
-Arm With Faults is enabled: During the arming countdown, if the magnetic contact is
triggered and then restored, the arming process will be terminated immediately after
restoring, and the arming is completed.
- Arm With Faults is disabled: If the magnetic contact is triggered and then restored, the
linked area immediately arms the delayed zone.
Dual Zone
After enabled, when multi transmitter detects that the entire zone circuit of the local zone
and the extended zone is open circuit, both zones trigger lid opened alarms.
Timer With Restart
During the Exit Delay process, the exit delay time will be re-timed at the time when the
second delay zone was triggered.
Note
There are four types of users for the AX HYBRID PRO, including administrator (or owner),
operator, and installer (or setter). Different types of users have different permissions for
accessing the functionality of the AX HYBRID PRO.
1. Enter the site, tap the AX HYBRID PRO and then log in to the device (if required) to enter the AX
HYBRID PRO page.
2. Tap Next to invite the user.
Note
The recipient need to accept the invitation.
60
5. Optional: Perform the following operations if required.
User Permission You can tap the target user on the user list and then tap Edit Icon to
set the permissions authorized to the target user.
Note
Only the administrator can do such an operation.
Set Linked Areas If the target user is an operator, tap the target user on the user list
and then tap Linked Areas to set the area linked to the target user.
Note
Only the administrator can do such an operation.
Change Duress If the target user is an administrator or an operator, you can tap the
Password target user on the user list and then tap Change Duress Password to
set the duress password to the target user.
Note
If under duress, you can enter the duress code on the keyboard to
arm and disarm area(s) and upload a duress alarm.
Note
● Configuration items and user permission will vary according to the user type.
● You can view linked cards/tags and keyfobs of the user but you do not have permission to
configure them.
61
disarm all the detectors added to specific area(s) of the AX HYBRID PRO, and silence alarms.
Note
The tag ID/PIN is a 32 bit long integer, and the variant could be 42949672956.
Steps
1. Enter the site, tap the AX HYBRID PRO and then log in to the device (if required) to enter the
page.
2. Tap → User Management → Card/Tag to enter the Card/Tag page.
3. Tap + to add a tag.
4. When hearing the voice prompt "Swipe Tag", you should present the tag on the AX HYBRID PRO
tag presenting area.
● When hearing a beep sound, the tag is recognized.
● The tag will be displayed on the tag page.
5. Optional: Tap a Tag to enter the Setting Page.
6. Tap Edit Icon to edit the Tag name.
Note
● If you log in as an installer, skip this step. Editing tag name is only available to administrator.
● The name should contain 1 to 32 characters.
Note
Different linked users have different tag permissions.
Operation Tag
You can swipe the tag to arm or disarm.
Patrol Tag
When you swipe the tag, the system will upload a record.
10. Optional: Tap Delete to delete the tag.
62
3. Select device language and time zone.
Steps
1. On the device list page, tap the AX HYBRID PRO and then log in to the device (if required) to
enter the page.
2. Tap → System → System Options → System Management to enter the page.
Forced Auto Arm
After enabled, when the timed automatic arming starts, if there are active faults in a zone, the
zone will be automatically bypass.
You can go to System → System Options → Schedule & Time to set the auto arming/disarming
schedule and linked areas.
Note
You should disable the Arm With Faults in the Arm Options page. Or the Forced Auto
Arm/Forced Arming function cannot be valid.
Forced Arming
After enabled, when manual arming starts, if there are active faults in a zone, the zone will be
automatically bypass.
You can use keyfobs, tags, and keypads to arm zones, or manually arm zones on APP. Single,
multiple or all areas can be selected for arming.
Note
You should disable the Arm With Faults in the Arm Options page. Or the Forced Auto
Arm/Forced Arming function cannot be valid.
63
While enabled, the system will alert with buzzer for the tamper alarm. Regardless of whether it
is enabled or not, the tamper alarm will be normally pushed to Cloud (for APP) and ARC.
Panel Lockup Button
All functions of AX HYBRID PRO will be frozen after it is enabled. This function can only be
enabled by users with installer permission.
Alarm Duration
Set linked alarm voice prompt lasting time.
Wireless Supervision Loss
Detectors and peripherals whose heartbeat loss times exceed the set value will be shown as
offline.
Bypass on Re-Arm
While enabled, after the detector is bypassed, if its faults are restored and the linked area is
armed, the detector will automatically arm.
Motion Detector Restore
Motion detectors include all PIR detectors.
-Disable: No automatic restore.
-Immediate After Alarm: Motion detectors automatically restores immediately after the alarm
and reports to Cloud (for APP) and ARC.
-After Disarm: Motion detectors automatically restores after disarming and reports to Cloud (for
APP) and ARC
Jamming Sensitivity Settings
The device will detect RF interference and push messages when the RF interference interferes
with communication. You can adjust the detection sensitivity.
Enable PD6662
Enable PD6662 standard. Functions that do not meet the standard will not take effect.
Keypad Logout
After the keypad enters the programming page, if there is no key operation, it will exit the
programming page after reaching this time.
64
2. Tap → System → System Options → System Fault Check to enter the page.
Detect Network Camera Disconnection
If the option is enabled, when the linked network camera is disconnected, an alarm will be
triggered. The delay time of network camera disconnection detection is the same as that of
LAN.
Panel Battery Fault Check
If the option is enabled, when panel battery is disconnected or in low battery status, the device
will upload events.
LAN Lost
If the option is enabled, when the wired network is disconnected or with other faults, the alarm
will be triggered.
WiFi Lost
If the option is enabled, when the Wi-Fi is disconnected or with other faults, the alarm will be
triggered.
Cellular Lost
If the option is enabled, when the cellular data network is disconnected or with other faults, the
alarm will be triggered.
Panel Mains Power Lost
If the option is enabled, an alarm will be triggered when the control panel main supply is
disconnected.
Panel Mains Power Loss Delay
The system checks the fault after the configured time duration after AC power down.
To compliant the EN 50131-3, the check time duration should be 10 s.
65
Early Alarm
A delay zone is triggered first, and the area is in the "Entry Delay" stage. During the delay time
period, an instant zone is triggered (only for the first triggered instant zone). At this time, the
area enters the early alarm stage. There are control panel voice alarm and local sounder alarm,
but no alarm message is pushed. If the zone is disarmed or silence before both the early alarm
and entry delay end, the alarm message will not be reported. Otherwise, both the delayed zone
and the instant zone will alarm.
Entry Delay
Disarm/Silence No Alarm
OR
Entry Delay
Disarm/Silence No Alarm
3. Tap Save.
Steps
1. On the device list page, tap the AX HYBRID PRO and then log in to the device (if required) to
enter the page.
2. Tap → System → System Options → Enrollment Mode to enter the page.
3. Tap Enter the Enrollment Mode. You can enroll the peripheral by triggering it.
66
4. Enter IP address, port, the user name and password of the camera.
5. Tap Save Icon.
6. Optional: tap Edit or Delete to edit or delete the selected camera.
Steps
1. In the site, tap the AX HYBRID PRO and then log in to the device (if required).
2. Tap → Network Camera → Event Video Settings to enter the page.
3. Select a camera and set the video parameters.
Stream Type
Main Stream: Being used in recording and HD preview, it has a high resolution, code rate and
picture quality.
Sub-Stream: It is used to transmit network and preview pictures as a video streaming with
features of lower resolution, bit rate and picture quality.
Bitrate Type
Select the Bitrate type as constant or variable.
Resolution
Select the resolution of the video output.
Bitrate
The higher value corresponds to the higher video quality, but the better bandwidth is
required.
Before Alarm
The recording time length before the alarm.
After Alarm
The recording time length after the alarm.
Steps
1. On the device list page, tap the AX HYBRID PRO and then log in to the device (if required) to
enter the page.
2. Tap → Area to enter the page.
3. Tap an area in the list, enable the area and select linked devices.
4. Set parameters:
Auto Arm
Enable the area to automatically arm itself in a specific time point.
Auto Arm Time
67
Set the schedule for the area to automatically arm itself.
Auto Disarm
Enable the area to automatically disarm itself in a specific time point.
Auto Disarm Time
Set the schedule for the area to automatically disarm itself.
Auto Arming Sound Prompt
After disabled, the buzzer will not beep before auto arming.
Late to Disarm
Enable the device to push a notification to the phone or tablet to remind the user to disarm the
area when the area is still armed after a specific time point.
Note
You should enable the Panel Management Notification function on the Web Client of
Communication Parameters → Event Communication before enabling the Late to Disarm
function.
Note
Up to 6 holiday groups can be set.
3.2.16 Communication
Wired Network
Steps
1. In the site, tap the AX HYBRID PRO and then log in to the device (if required).
2. Tap → Communication Parameters→ Wired Network to enter the page.
3. Set the parameters.
– Automatic Settings: Enable DHCP and set the HTTP port.
– Manual Settings: Disabled DHCP and set IP Address, Subnet Mask, Gateway Address, DNS
Server Address.
68
4. Optional: Set correct DNS server address if the device needs to visit Hik-Connect server via a
domain name.
5. Click Save.
Wi-Fi Configuration
Steps
1. In the site, tap the AX HYBRID PRO and then log in to the device (if required).
2. Tap → Communication Parameters→ Wi-Fi Configuration to enter the page.
3. Tap a Wi-Fi to connect in the list.
Cellular Data Network
Steps
1. In the site, tap the AX HYBRID PRO and then log in to the device (if required).
2. Tap → Communication Parameters→ Cellular Data Network Settings to enter the page.
3. Enable Cellular Data Network.
4. Tap to select a SIM card. Tap Parameter Configuration → Edit Icon and set parameters
including the user name, access password, APN, MTU and PIN code.
5. Tap Save Icon.
6. Enable Data Usage Limit.
7. Edit Data Used This Month and Data Limited per Month.
Access Number
Input the operator dialing number.
Note
Only the private network SIM card user needs to enter the access number.
User Name
Ask the network carrier and input the user name.
Access Password
Ask the network carrier and input the password.
APN
Ask the network carrier to get the APN information and input the APN information.
Data Limited per Month
You can enable the function and set the data threshold every month. If data usage is more
than the configured threshold, an alarm will be triggered and uploaded to the alarm center
and mobile client.
Data Used This Month
The used data will be accumulated and displayed in this text box.
69
Push Notifications
When an alarm is triggered, if you want to send the alarm notification to the mobile phone, you
can set the notification push parameters.
Steps
1. In the site, tap the AX HYBRID PRO and then log in to the device (if required).
2. Tap → Communication Parameters→ Push Notification(s) to enter the page.
3. Enable the target notification.
Zone Alarm/Lid Opened
The device will push notifications when the zone alarm is triggered or the zone lid opened is
triggered or restored.
Note
You need to set event filtering interval time for phone calling.
70
Smart Alarm Event
The device will push notifications when the alarm is triggered in thermal cameras.
4. Tap Phone Call and SMS.
5. Tap + Add Phone Number to enter the phone number.
6. Tap the added phone number to enable Phone Call and SMS according to your need.
(For Phone Call) Set Numbers of Calling.
(For SMS) Set Arming Permission, Disarming Permission and Alarm Clearing Permission for
areas.
Common Message
You can enter message content. When the alarm is triggered, your customized content will be
added at the beginning of the message sent by the system.
Common Voice
You can import a new audio. When the alarm is triggered, your customized voice will be added
at the beginning of the content of the phone dialed by the system. You can also tap Clear to
delete audios
Note
Only WAV format is supported, up to 512 KB and 15 s.
7. Check notifications.
71
Transmission Mode
Select the Transmission Mode as TCP or UDP. UDP is recommended by the SIA DC-09
standard.
Impulse Counting Time
After the selected time, the system will retry to transmit.
Attempts
Set the number of retry attempts.
Polling Option
Set the polling rate with the range from 10 to 3888000 seconds. The system will report fault if
the time is over the limit. The status of device will be shown as offline.
Periodic Test
After enabling, you can set the time interval, setting how often to send a test event to the
ARC to ensure the connection.
Companies
Select the support company as None, Hungary-Multi Alarm Receiving Company or French
Alarm Receiving Company.
72
4. Enable Periodic Test. Enter the periodic test interval.
Periodic Test
After enabling, you can set the time interval, setting how often to send a test event to the
ARC to ensure the connection.
5. Tap Save.
Notification by Email
Steps
1. In the site, tap the AX HYBRID PRO and then log in to the device (if required).
2. Tap → Communication Parameters→ Notification by Emails to enter the page.
3. Enable Email 1.
4. Enter the sender name, sender email address, SMTP server address, SMTP port, user name and
password.
Note
It is recommended to use Gmail and Hotmail for sending mails.
Only if the zone is linked with a network camera, the alarm email will be attached with alarm
video.
73
User Name & Password/Anonymity
The FTP user should have the permission to upload pictures. If the FTP server supports
picture uploading by anonymous users, you can enable Anonymous to hide your device
information during uploading.
Directory Structure
The saving path of snapshots in the FTP server.
4. Tap Save.
NAT
Universal Plug and Play (UPnP™) is a networking architecture that provides compatibility among
networking equipment, software and other hardware devices. The UPnP protocol allows devices
to connect seamlessly and to simplify the implementation of networks in the home and corporate
environments.
Enable the UPnP function, and you don’t need to configure the port mapping for each port, and
the device is connected to the Wide Area Network via the router.
Steps
1. In the site, tap the AX HYBRID PRO and then log in to the device (if required).
2. Tap → Communication Parameters→ NAT to enter the page.
3. Drag the slider to enable UPnP.
4. Optional: Select the mapping type as Manual to set the HTTP port and the service port.
5. Click Save to complete the settings.
Walk Test
Steps
1. In the site, tap the AX HYBRID PRO and then log in to the device (if required).
2. Tap →Maintenance → Device Maintenance to enter the maintenance page.
3. Tap Test, and tap Start Walk Test to test the whether the device works properly or not.
Maintenance
1. In the site, tap the AX HYBRID PRO and then log in to the device (if required).
2. Tap →Maintenance →Maintenance.
Tamper Alarm on HPC Login
If enabled, an alarm will be triggered when the device is tampered after you log in to HPC.
Reboot Device
The AX HYBRID PRO will reboot.
Log
74
View device logs.
Device Upgrade
Steps
1. In the site, tap the AX HYBRID PRO and then log in to the device (if required).
2. Tap →Maintenance → Device Upgrade to upgrade the control panel, or tap
→Maintenance → Detector & Peripheral Upgrade to upgrade detectors and peripherals.
Remote Log Collection
Steps
1. In the site, tap the AX HYBRID PRO and then log in to the device (if required).
2. Tap →Maintenance → Remote Log Collection to enable the function.
Remote Log Collection is for getting logs relating to the device. When this is enabled, our technical
support will be able to collect logs relating to the device remotely and upload then to our server
for troubleshooting. You can set the validity period according to actual needs. This function will be
disabled after the set validity period.
Note
For details, see User Manual of Hik-Connect Mobile Client.
75
Tap + → Scan QR Code to enter the Scan QR code page. Scan the QR code on the AX HYBRID PRO.
Note
Normally, the QR code is printed on the label stuck on the back cover of the AX HYBRID PRO.
Tap + → Manual Adding to enter the Add Device page. Enter the device serial No. with the Hik-
Connect Domain adding type.
3. Tap to search the device.
4. Tap Add on the Results page.
5. Enter the verification code and tap OK.
6. After adding completed, enter the device alias and tap Save.
7. Optional: Tap → Delete Device to delete the device.
8. Optional: Tap → to edit the device name.
76
Enable Alarm
Tap to select Audible Panic Alarm or Silent Panic Alarm.
View Faults
Tap to view faults.
Area Management
Tap + to add an area.
Tap Area to enter the area management page. Refers to 3.2.15 Set Arming/Disarming
Schedule for details.
77
● Away Arming: Tap to away arm a single area. When all the people in the detection area
leave, turn on the Away mode to arm all zones in the area after the defined dwell time.
● Stay Arming: Tap to stay arm a single area. When all the people stays inside the detection
area, turn on the Stay mode to arm all the perimeter burglary detection set in all the zones of all
areas.
● Select Areas: Tap to select areas you want to operate. If you do not select areas, following
operations will take effect for all areas.
● Away Arming: Tap to away arm selected areas. When all the people in the detection area
leave, turn on the Away mode to arm all zones in all areas after the defined dwell time.
● Stay Arming: Tap to stay arm all areas. When the people stays inside the detection area,
turn on the Stay mode to arm all the perimeter burglary detection (such as perimeter detector,
magnetic contacts, curtain detector in the balcony) set in all the zones of all areas. At the
meantime, the detectors inside the detection area are bypassed (such as PIR detectors). People
can move inside the area and alarm will not be triggered.
● Disarming: Tap to disarm all areas. In Disarm mode, all the zones of all areas will not
trigger alarm, no matter alarm events happen or not.
● Silent Alarm: Tap to silent alarms for all areas.
78
2. Tap + to add a new zone.
3. Tap a zone to enter the management page. You can view device status (e.g. temperature,
battery status, single strength, etc.).
4. Tap on the upper right corner to enter the zone settings page.
5. Select a zone type.
Instant Zone
This Zone type will immediately trigger an alarm event when armed.
Delay Zone
-Exit Delay: Exit Delay provides you time to leave through the zone without alarm.
Arm with faults is enabled: You should confirm faults first, and then the zone is in arming
process. If the delay zone is triggered within the exit delay time but it restores before the
time ends, the alarm will not be triggered and the zone will be armed.
Arm with faults is disabled: Immediately armed. If the delay zone is triggered within the exit
delay time but it restores before the time ends, the alarm will not be triggered.
-Entry Delay: Entry Delay provides you time to enter the zone to disarm the system without
alarm.
After triggering, if the zone is not disarmed or silenced before the entry delay time ends, the
zone will alarm.
-Stay Arm Delay Time: Stay arming uses Stay Arm Delay Time to count down.
The system gives Entry/Exit delay time when it is armed or reentered. It is usually used in
entrance/exit route (e.g. front door/main entrance), which is a key route to arm/disarm via
operating keypad for users.
79
Note
You can set 2 different time durations in System Options → Schedule & Timer.
Ensure that timer is no longer than 45 seconds in order to comply with EN50131-1.
You can set Stay Arm Delay Time for the delay zone.
Panic Zone
24-hour active zone, whether armed or not. Report panic alarm after triggering. It is usually
used in the sites equipped with panic button, smoke detector and glass-break detector.
Medical Alarm
24-hour active zone, whether armed or not. Report medical alarm after triggering.
Fire Zone
24-hour active zone, whether armed or not. Report fire alarm after triggering.
Gas Zone
24-hour active zone, whether armed or not. Report gas alarm after triggering.
Follow Zone
The zone acts as delayed zone when it detects triggering event during system Entry Delay,
while it acts as instant zone otherwise.
Keyswitch Zone
-By Trigger Time: Change the arming and disarming status after each trigger. For example, in
the disarmed status, if the zone is triggered, the linked area will be armed. Trigger the zone
again and the area will be disarmed.
-By Zone Status: You need to choose to arm or disarm the linked area after the zone is
triggered.
In the case of the tampering alarm, the arming and disarming operation will not be triggered.
Disabled Zone
Zone disabled ignoring any alarm event. It is usually used to disable faulty detectors.
24-hour Zone
The zone activates all the time with sound/light output when alarm occurs, whether it is
armed or not. It is usually used in fire hazardous areas equipped with smoke detectors and
temperature sensors.
Timeout Zone
The zone activates all the time. When this zone has been triggered or restored and exceeds
the set time, an alarm will be generated.
It can be used in places equipped with magnetic contacts that require access but for only a
short period (e.g., fire hydrant box's door or another external security box door).
-Not-Triggered Zone Alarm: If the zone is not triggered for the set time, it will alarm.
-Alarm on Zone Activated: If the zone is triggered for the set time, it will alarm.
80
-Retry Time Period: Set the timeout period.
7. Enable other functions according to your detector types and actual needs.
Note
The configurable functions vary in different detectors and zones. Refer to the actual zone to set
the function.
Arm Mode
If the zone is a public zone (the zone is belongs to more than one areas), you can set arm
mode.
And: When all linked areas are armed, the zone will arm. When any of linked areas is
disarmed, the zone will disarm.
Or: When any of the linked areas is armed, the zone will arm. When all linked areas are
disarmed, the zone will disarm. When the zone is in alarm, the disarmed areas linked with the
zone cannot be armed.
Stay Arm Bypass
The zone will be automatically bypassed in stay arming.
Cross Zone
PD6662 is not enabled: You need to set the combined time interval.
When the first zone is triggered, the system will start timing after the zone is restored. If the
second zone is triggered within the set time, both zones will give alarms. Otherwise, no alarm
will be triggered.
If the first zone is not be restored, both zones will give alarms when the second zone is
triggered, regardless of whether the set time has elapsed.
PD6662 is enabled: You need to set the combined time interval.
The first zone will give an alarm when triggered. If the first zone is not restored and the
second zone is triggered, the system will report the alarm confirmation.
If the first zone is restored, the system will start timing. If the second zone is triggered within
the set time, the system will report the alarm confirmation.
If the first zone is restored, the system will start timing. If the second zone is not triggered
within the set time, no information will be reported.
Forbid Bypass on Arming
After enabled, you cannot bypass zones when arming.
Chime
Enable the doorbell. Usually used for door magnetic detectors.
Silent Alarm
After enabled, when an alarm is triggered, only the report will be uploaded and no sound is
emitted.
81
Double knock
After enabled, the time interval can be set. If the same detector is triggered twice or
continuously in a period of time, the alarm will be triggered.
Sounder Delay Time
The sounder will be triggered immediately (0s) or after the set time.
Final Door Exit
Only magnetic contacts have this option.
After enabling, when the user use keypads or tags to arm:
-Arm With Faults is enabled: During the arming countdown, if the magnetic contact is
triggered and then restored, the arming process will be terminated immediately after
restoring, and the arming is completed.
- Arm With Faults is disabled: If the magnetic contact is triggered and then restored, the
linked area immediately arms the delayed zone.
Dual Zone
After enabled, when multi transmitter detects that the entire zone circuit of the local zone
and the extended zone is open circuit, both zones trigger lid opened alarms.
Timer With Restart
During the Exit Delay process, the exit delay time will be re-timed at the time when the
second delay zone was triggered.
Note
There are four types of users for the AX HYBRID PRO, including administrator (or owner),
operator, and installer (or setter). Different types of users have different permissions for
accessing the functionality of the AX HYBRID PRO.
1. Enter the site, tap the AX HYBRID PRO and then log in to the device (if required) to enter the AX
HYBRID PRO page.
2. Tap Next to invite the user.
Note
The recipient need to accept the invitation.
82
5. Optional: Perform the following operations if required.
User Permission You can tap the target user on the user list and then tap Edit Icon to
set the permissions authorized to the target user.
Note
Only the administrator can do such an operation.
Set Linked Areas If the target user is an operator, tap the target user on the user list
and then tap Linked Areas to set the area linked to the target user.
Note
Only the administrator can do such an operation.
Change Duress If the target user is an administrator or an operator, you can tap the
Password target user on the user list and then tap Change Duress Password to
set the duress password to the target user.
Note
If under duress, you can enter the duress code on the keyboard to
arm and disarm area(s) and upload a duress alarm.
Note
● Configuration items and user permission will vary according to the user type.
● You can view linked cards/tags and keyfobs of the user but you do not have permission to
configure them.
83
disarm all the detectors added to specific area(s) of the AX HYBRID PRO, and silence alarms.
Note
The tag ID/PIN is a 32 bit long integer, and the variant could be 42949672956.
Steps
1. Enter the site, tap the AX HYBRID PRO and then log in to the device (if required) to enter the
page.
2. Tap → User Management → Card/Tag to enter the Card/Tag page.
3. Tap + to add a tag.
4. When hearing the voice prompt "Swipe Tag", you should present the tag on the AX HYBRID PRO
tag presenting area.
● When hearing a beep sound, the tag is recognized.
● The tag will be displayed on the tag page.
5. Optional: Tap a Tag to enter the Setting Page.
6. Tap Edit Icon to edit the Tag name.
Note
● If you log in as an installer, skip this step. Editing tag name is only available to administrator.
● The name should contain 1 to 32 characters.
Note
Different linked users have different tag permissions.
Operation Tag
You can swipe the tag to arm or disarm.
Patrol Tag
When you swipe the tag, the system will upload a record.
10. Optional: Tap Delete to delete the tag.
84
3. Select device language and time zone.
Steps
1. On the device list page, tap the AX HYBRID PRO and then log in to the device (if required) to
enter the page.
2. Tap → System → System Options → System Management to enter the page.
Forced Auto Arm
After enabled, when the timed automatic arming starts, if there are active faults in a zone, the
zone will be automatically bypass.
You can go to System → System Options → Schedule & Time to set the auto arming/disarming
schedule and linked areas.
Note
You should disable the Arm With Faults in the Arm Options page. Or the Forced Auto
Arm/Forced Arming function cannot be valid.
Forced Arming
After enabled, when manual arming starts, if there are active faults in a zone, the zone will be
automatically bypass.
You can use keyfobs, tags, and keypads to arm zones, or manually arm zones on APP. Single,
multiple or all areas can be selected for arming.
Note
You should disable the Arm With Faults in the Arm Options page. Or the Forced Auto
Arm/Forced Arming function cannot be valid.
85
While enabled, the system will alert with buzzer for the tamper alarm. Regardless of whether it
is enabled or not, the tamper alarm will be normally pushed to Cloud (for APP) and ARC.
Panel Lockup Button
All functions of AX HYBRID PRO will be frozen after it is enabled. This function can only be
enabled by users with installer permission.
Alarm Duration
Set linked alarm voice prompt lasting time.
Wireless Supervision Loss
Detectors and peripherals whose heartbeat loss times exceed the set value will be shown as
offline.
Bypass on Re-Arm
While enabled, after the detector is bypassed, if its faults are restored and the linked area is
armed, the detector will automatically arm.
Motion Detector Restore
Motion detectors include all PIR detectors.
-Disable: No automatic restore.
-Immediate After Alarm: Motion detectors automatically restores immediately after the alarm
and reports to Cloud (for APP) and ARC.
-After Disarm: Motion detectors automatically restores after disarming and reports to Cloud (for
APP) and ARC
Jamming Sensitivity Settings
The device will detect RF interference and push messages when the RF interference interferes
with communication. You can adjust the detection sensitivity.
Enable PD6662
Enable PD6662 standard. Functions that do not meet the standard will not take effect.
Keypad Logout
After the keypad enters the programming page, if there is no key operation, it will exit the
programming page after reaching this time.
86
2. Tap → System → System Options → System Fault Check to enter the page.
Detect Network Camera Disconnection
If the option is enabled, when the linked network camera is disconnected, an alarm will be
triggered. The delay time of network camera disconnection detection is the same as that of
LAN.
Panel Battery Fault Check
If the option is enabled, when panel battery is disconnected or in low battery status, the device
will upload events.
LAN Lost
If the option is enabled, when the wired network is disconnected or with other faults, the alarm
will be triggered.
WiFi Lost
If the option is enabled, when the Wi-Fi is disconnected or with other faults, the alarm will be
triggered.
Cellular Lost
If the option is enabled, when the cellular data network is disconnected or with other faults, the
alarm will be triggered.
Panel Mains Power Lost
If the option is enabled, an alarm will be triggered when the control panel main supply is
disconnected.
Panel Mains Power Loss Delay
The system checks the fault after the configured time duration after AC power down.
To compliant the EN 50131-3, the check time duration should be 10 s.
87
Early Alarm
A delay zone is triggered first, and the area is in the "Entry Delay" stage. During the delay time
period, an instant zone is triggered (only for the first triggered instant zone). At this time, the
area enters the early alarm stage. There are control panel voice alarm and local sounder alarm,
but no alarm message is pushed. If the zone is disarmed or silence before both the early alarm
and entry delay end, the alarm message will not be reported. Otherwise, both the delayed zone
and the instant zone will alarm.
Entry Delay
Disarm/Silence No Alarm
OR
Entry Delay
Disarm/Silence No Alarm
3. Tap Save.
Steps
1. On the device list page, tap the AX HYBRID PRO and then log in to the device (if required) to
enter the page.
2. Tap → System → System Options → Enrollment Mode to enter the page.
3. Tap Enter the Enrollment Mode. You can enroll the peripheral by triggering it.
88
4. Enter IP address, port, the user name and password of the camera.
5. Tap Save Icon.
6. Optional: tap Edit or Delete to edit or delete the selected camera.
Steps
1. In the site, tap the AX HYBRID PRO and then log in to the device (if required).
2. Tap → Network Camera → Event Video Settings to enter the page.
3. Select a camera and set the video parameters.
Stream Type
Main Stream: Being used in recording and HD preview, it has a high resolution, code rate and
picture quality.
Sub-Stream: It is used to transmit network and preview pictures as a video streaming with
features of lower resolution, bit rate and picture quality.
Bitrate Type
Select the Bitrate type as constant or variable.
Resolution
Select the resolution of the video output.
Bitrate
The higher value corresponds to the higher video quality, but the better bandwidth is
required.
Before Alarm
The recording time length before the alarm.
After Alarm
The recording time length after the alarm.
Steps
1. On the device list page, tap the AX HYBRID PRO and then log in to the device (if required) to
enter the page.
2. Tap → Area to enter the page.
3. Tap an area in the list, enable the area and select linked devices.
4. Set parameters:
Auto Arm
Enable the area to automatically arm itself in a specific time point.
Auto Arm Time
89
Set the schedule for the area to automatically arm itself.
Auto Disarm
Enable the area to automatically disarm itself in a specific time point.
Auto Disarm Time
Set the schedule for the area to automatically disarm itself.
Auto Arming Sound Prompt
After disabled, the buzzer will not beep before auto arming.
Late to Disarm
Enable the device to push a notification to the phone or tablet to remind the user to disarm the
area when the area is still armed after a specific time point.
Note
You should enable the Panel Management Notification function on the Web Client of
Communication Parameters → Event Communication before enabling the Late to Disarm
function.
Note
Up to 6 holiday groups can be set.
3.3.16 Communication
Wired Network
Steps
1. In the site, tap the AX HYBRID PRO and then log in to the device (if required).
2. Tap → Communication Parameters→ Wired Network to enter the page.
3. Set the parameters.
– Automatic Settings: Enable DHCP and set the HTTP port.
– Manual Settings: Disabled DHCP and set IP Address, Subnet Mask, Gateway Address, DNS
Server Address.
90
4. Optional: Set correct DNS server address if the device needs to visit Hik-Connect server via a
domain name.
5. Click Save.
Wi-Fi Configuration
Steps
1. In the site, tap the AX HYBRID PRO and then log in to the device (if required).
2. Tap → Communication Parameters→ Wi-Fi Configuration to enter the page.
3. Tap a Wi-Fi to connect in the list.
Cellular Data Network
Steps
1. In the site, tap the AX HYBRID PRO and then log in to the device (if required).
2. Tap → Communication Parameters→ Cellular Data Network Settings to enter the page.
3. Enable Cellular Data Network.
4. Tap to select a SIM card. Tap Parameter Configuration → Edit Icon and set parameters
including the user name, access password, APN, MTU and PIN code.
5. Tap Save Icon.
6. Enable Data Usage Limit.
7. Edit Data Used This Month and Data Limited per Month.
Access Number
Input the operator dialing number.
Note
Only the private network SIM card user needs to enter the access number.
User Name
Ask the network carrier and input the user name.
Access Password
Ask the network carrier and input the password.
APN
Ask the network carrier to get the APN information and input the APN information.
Data Limited per Month
You can enable the function and set the data threshold every month. If data usage is more
than the configured threshold, an alarm will be triggered and uploaded to the alarm center
and mobile client.
Data Used This Month
The used data will be accumulated and displayed in this text box.
91
Push Notifications
When an alarm is triggered, if you want to send the alarm notification to the mobile phone, you
can set the notification push parameters.
Steps
1. In the site, tap the AX HYBRID PRO and then log in to the device (if required).
2. Tap → Communication Parameters→ Push Notification(s) to enter the page.
3. Enable the target notification.
Zone Alarm/Lid Opened
The device will push notifications when the zone alarm is triggered or the zone lid opened is
triggered or restored.
Note
You need to set event filtering interval time for phone calling.
92
Smart Alarm Event
The device will push notifications when the alarm is triggered in thermal cameras.
4. Tap Phone Call and SMS.
5. Tap + Add Phone Number to enter the phone number.
6. Tap the added phone number to enable Phone Call and SMS according to your need.
(For Phone Call) Set Numbers of Calling.
(For SMS) Set Arming Permission, Disarming Permission and Alarm Clearing Permission for
areas.
Common Message
You can enter message content. When the alarm is triggered, your customized content will be
added at the beginning of the message sent by the system.
Common Voice
You can import a new audio. When the alarm is triggered, your customized voice will be added
at the beginning of the content of the phone dialed by the system. You can also tap Clear to
delete audios
Note
Only WAV format is supported, up to 512 KB and 15 s.
7. Check notifications.
93
Transmission Mode
Select the Transmission Mode as TCP or UDP. UDP is recommended by the SIA DC-09
standard.
Impulse Counting Time
After the selected time, the system will retry to transmit.
Attempts
Set the number of retry attempts.
Polling Option
Set the polling rate with the range from 10 to 3888000 seconds. The system will report fault if
the time is over the limit. The status of device will be shown as offline.
Periodic Test
After enabling, you can set the time interval, setting how often to send a test event to the
ARC to ensure the connection.
Companies
Select the support company as None, Hungary-Multi Alarm Receiving Company or French
Alarm Receiving Company.
94
4. Enable Periodic Test. Enter the periodic test interval.
Periodic Test
After enabling, you can set the time interval, setting how often to send a test event to the
ARC to ensure the connection.
5. Tap Save.
Notification by Email
Steps
1. In the site, tap the AX HYBRID PRO and then log in to the device (if required).
2. Tap → Communication Parameters→ Notification by Emails to enter the page.
3. Enable Email 1.
4. Enter the sender name, sender email address, SMTP server address, SMTP port, user name and
password.
Note
It is recommended to use Gmail and Hotmail for sending mails.
Only if the zone is linked with a network camera, the alarm email will be attached with alarm
video.
95
User Name & Password/Anonymity
The FTP user should have the permission to upload pictures. If the FTP server supports
picture uploading by anonymous users, you can enable Anonymous to hide your device
information during uploading.
Directory Structure
The saving path of snapshots in the FTP server.
4. Tap Save.
NAT
Universal Plug and Play (UPnP™) is a networking architecture that provides compatibility among
networking equipment, software and other hardware devices. The UPnP protocol allows devices
to connect seamlessly and to simplify the implementation of networks in the home and corporate
environments.
Enable the UPnP function, and you don’t need to configure the port mapping for each port, and
the device is connected to the Wide Area Network via the router.
Steps
1. In the site, tap the AX HYBRID PRO and then log in to the device (if required).
2. Tap → Communication Parameters→ NAT to enter the page.
3. Drag the slider to enable UPnP.
4. Optional: Select the mapping type as Manual to set the HTTP port and the service port.
5. Click Save to complete the settings.
96
3.3.18 Wi-Fi Connection
You can make the AX HYBRID PRO connect to Wi-Fi through APP.
Steps
1. On the device list page, tap the AX HYBRID PRO and then log in to the device (if required) to
enter the page.
2. Tap → Configure Wi-Fi Network.
3. Follow the instructions on the page and change the AX HYBRID PRO to the AP mode. Tap Next.
4. Select a stable Wi-Fi for the device to connect.
5. Back to configuration page to enter the Wi-Fi password and tap Next.
6. Tap Connect to a network and wait for connection.
After the connection is completed, the AX HYBRID PRO will prompt to exit AP mode and
automatically switch to STA mode.
97
3. Optional: If the zone has linked a camera, you can view the playback when the alarm is
triggered.
4. Optional: Tap to search events by dates or devices.
98
3. Click Alarms and Accounts→ Accounts Management, and assign an account for the panel as
show below.
99
= Protocol Setting =
Protocol Type
— ADM-CID
— SIA-DCS
— *ADM-CID
— *SIA-DCS
Select token supported by the receiver in the ARC. Choose the token with “*” mark to
improve the communication security.
= Server Setting =
Address Type
— IP
— Domain Name
Server Address / Domain Name
Port No.
Input IP address or domain name by which the transceiver of receiving center could be
reached. Input port number of the server provided by the ARC
= Account Setting =
Account Code
Input the assigned account provided by the ARC.
100
standard.
Connection Setting
○ Impulse Counting Time / Retry Timeout Period
Setup the timeout period waiting for receiver to respond. Re-transmission will be
arranged if the transceiver of receiving center is timeout.
○ Attempts
Setup the maximum number that re-transmission will be tried.
○ Polling Rate
Setup the interval between 2 live polling if enable is checked.
Encryption Setting
○ Encryption Arithmetic
— AES
○ Password Length
— 128
— 192
— 256
○ Secret Key
Setup the encryption key length and input the key provided by the ARC.
Signaling Test
Activate a panic alarm from the control panel.
Login to Receiver. Click Traffic to review all the messages received.
101
Chapter 4 General Operations
4.2 Arming
You can use keypad, keyfob, tag, client software, mobile client to arm your system.
After the arming command is sending to AX HYBRID PRO, the system will check the detector
status. If the detector is in fault, you will need to choose whether to arm the system with fault.
While the system is armed, the AX HYBRID PRO will prompt the result in 5s, and upload the arming
report.
102
Access level of Arming
The user in level 2 or 3 has the permission to arm or partly arm the system.
Arming Indication
The arming/disarming indicator keeps solid blue for 5s.
Reason of Arming Failure
● Intrusion detector triggered (excepts the detector on the exit route).
● Panic alarm device triggered.
● Lid opened (tamper) alarm occurred.
● Communication exception
● Main power supply exception
● Backup battery exception
● Alarm receiving fault
● Sounder fault
● Low battery of the keyfob
● Others
Arming with Fault
While the arming is stopped with fault, user in level 2 has the permission to arm the system with
fault (forced arming).
Forced arming only takes effect on the current arming operation.
The forced arming operation will be record in the event log.
103
4.3 Disarming
You can disarm the system with keypad, keyfob, Tag, client software, or mobile client.
Disarming Indication
The arming/disarming indicator flashes 30s while the user successfully disarm the system through
the entry/exit route.
The system will report the disarming result after the operation completed.
Entry Delay Duration
Ensure that timer is no longer than 45 seconds in order to comply with EN50131-1.
Early Alarm
If either the intrusion or tampering alarm occurs on the enter/exit route when the AX HYBRID PRO
is in the status of entry delay, the AX HYBRID PRO then enters the early alarm mode.
The early alarm duration can be set (> 30s).
The AX HYBRID PRO will reports the alarm only if the alarm event lasts over the duration of early
alarm with the addition of entry delay.
104
A. Trouble Shooting
A.1.1 IP Conflict
Fault Description:
IP that the panel automatically acquired or set is same as other devices, resulting in IP conflicts.
Solution:
Search the current available IP through ping. Change the IP address and log in again.
105
Check the web page: whether the Hik-Connect is offline.
106
View status of zones which displays triggered/fault.
Solution:
Reset the detector.
A.5.2 The Alarm Clearing Operation on the Panel Does Not Produce the
Alarm Clearing Report
Fault Description:
The alarm clearing operation on the panel does not produce the alarm clearing report.
Solution:
In the absence of alarm, no report will be uploaded for arm clearing.
107
Solution:
Wrong configuration of mailbox parameters. Please edit the mailbox configuration information, as
shown in table 1/1.
108
A.6.6 Mail Configuration
Table A-1 Mail Configuration
Mail Type Mail Server SMTP Port Protocols Supported
Gmail smtp.gmail.com 587 TLS/STARTTLS (TLS)
Outlook smtp.office365.com 587 STARTTLS (TLS)
Hotmail smtp.office365.com 587 STARTTLS (TLS)
QQ smtp.qq.com 587 STARTTLS (TLSv1.2)
Yahoo smtp.mail.yahoo.com 587 STARTTLS (TLSv1.2)
126 smtp.126.com 465 SSL/TLS
SSL/TLS/STARTTLS
Sina smtp.sina.com 25/465/587
(SSL/TLS)
Note
About mail configuration:
● SMTP portDefault to use port 25 without encryption, or using port 465 if SSL/TLS is used.
Port 587 is mainly used for STARTTLS protocol mode.
The STARTTLS protocol mode that is usually used by default when selecting TLS.
● User nameUser name of Outlook and Hotmail require full names, and other email require a
prefix before @.
109
B. Input Types
110
Input Types Operations
Audible Response: Trigger the system sound and sounder.
Voice Prompt: Zone X fire alarm.
The zone activates all the time with sound/sounder output
when alarm occurs.
Gas Zone
Audible Response: Trigger the system sound and sounder.
Voice Prompt: Zone X gas alarm.
The zone activates all the time with beep confirmation when
alarm occurs.
Medical Zone
Audible Response: Trigger the system sound and sounder.
Voice Prompt: Zone X medical alarm.
The zone activates all the time. The zone type is used to
monitor and report the "ACTIVE" status of a zone, but it will
Timeout Zone
only report and alarm this status after the programmed time
has expired (1 to 599) seconds.
Alarms will not be activated when the zone is triggered or
tampered.
Disabled Zone
Audible Response: No system sound (voice prompt or
sounder).
The system will immediately alarm when it detects triggering
event after system armed.
Virtual Zone (Keypad/Keyfob)
Audible Response: Trigger the system sound and sounder.
Voice Prompt: Buzzer beeps.
The system will immediately alarm when it detects triggering
event after system armed.
Tamper Alarm (Lid Opened
Alarm) Audible Response: Trigger the system sound and sounder.
Voice Prompt: Zone X tampered.
Trigger the linked device when event occurs.
Link e.g. The output expander linked relays will be enabled when
the AX HYBRID PRO is armed.
When armed: Voice prompt for fault. You can handle the fault
according to the voice prompt.
Arm ● System sound for arming with Tag or keyfob.
● Voice prompt for fault. You can handle the fault according to
the voice prompt.
111
Input Types Operations
Fault event displays on client. You can handle the fault via
client software or mobile client.
● Voice Prompt: Armed/Arming failed.
112
C. Output Types
113
D. Event Types
114
E. Access Levels
Level Description
1 Access by any person; for example the general public.
User access by an operator and administrator; for example customers
2
(systems users).
3 User access by an installer; for example an alarm company professional.
Note
a By the condition of being accredited by user in level 2.
bBy the condition of being accredited by user in level 2 and level 3.
dUsers can only edit their own user code.
● The user level 2 can assign the login permission of the controller to the user level 3 in the
settings page.
● The user level 2 should assign permissions to the user level 3 if the user level 3 wants to login
the controller remotely.
● When the controller is bypassed, the user level 3 can login the controller without the permission
assignment of the user level 2.
115
● When the controller is bypassed, the user level 3 can login the controller without the permission
assignment of the user level 2.
● The user level 4 can login the controller only when the user level 2 or level 3 has assigned
permissions to the user level 4.
116
F. Signalling
Detection of ATP/ATS Faults
ATP (Alarm Transmission Path) faults will be detected when network interface of the control
panel disconnected or the transmission path to the transceiver of receiving center located in ARC
blocked somewhere in between. An ATS (Alarm Transmission System) fault will be reported when
ATP faults are detected on both transmission paths.
ATP restore will be detected as soon as network interface connected and the transmission path to
the transceiver of receiving center restored. ATS restore will be reported when ATP restore of any
transmission path is detected.
The timing performance of detecting ATP faults and restores shows in the table below.
TN Maximum timing of detection
Primary ATP failure/restore LAN/WiFi 10 min
GPRS 60 min
Secondary ATP failure/restore
3G/4G LTE 20 min (when primary ATP failed )
Signalling will be always transmitted from primary ATP when it is operational. Otherwise it will be
automatically switched to secondary transmission path that is operational at the moment. Both primary
and secondary ATP fault and restore events will be reported to ARC when there is an ATP left to work. They
will also be recorded to mandatory log memory with capacity of 1000 records allocated in non-volatile flash
memory storage, as well as the ATS fault record. The detail of reports and log records are listed in the table
below.
Event code when
Event log description
signalling
Primary ATP failure/restore E351/R351 LAN Path Failed/LAN Path Recovery
E352/R352 Mobile Net Path Failed/Mobile Net Path
Secondary ATP failure/restore
Recovery
ATS failure/restore N/A ATS Failed
Primary network interface failure/restore E351/R351 LAN Path Failed/LAN Path Recovery
E352/R352 Mobile Net Path Failed/Mobile Net Path
Secondary network interface failure/restore
Recovery
ATS Category
The ATS category of AXPRO is DP2. While the alarm receiving center is enabled. The control panel will upload alarm
report to the receiver center via the main path (LAN or Wi-Fi) or the back-up path (3G/4G). If the control panel is
properly connected to the LAN or Wi-Fi, the main path is selected as the transmission path. If the main path
connection is failed, the path will be switched to 3G/4G. And if the main path connection is restored, the path will be
switched back to LAN or Wi-Fi. The control panel checks the connection status continuously, and generates logs
transmission fault for any of the path. While both of the paths are invalid, the control panel determines ATS fault.
117
G. SIA and CID Code
Note
The code below is for transmitting from the security control panel to ARC via DC09 protocol.
118
SIA code CID code Description
TR 3137 Lid Restored
BV 1139 Confirmed Alarm
BW 3139 Confirmed Alarm Restore
BUS Open-circuit Alarm
BUS Open-circuit Restored
AF 1142 BUS Short-circuit Alarm
CN 3142 BUS Short-circuit Restored
TA 1144 External Probe Disconnected
TR 3144 External Probe Connected
AG 1148 Device Motion Alarm
CO 3148 Device Motion Alarm Restored
1149 Masking Alarm
3149 Masking Alarm Restored
GA 1162 Gas Leakage Alarm
GH 3162 Gas Leakage Alarm Restored
AH 1207 Zone Early-Warning
CP 3207 Zone Early-Warning Dismissed
AT 1301 Mains Power Lost
AR 3301 Mains Power Restored
YT 1302 Battery Low
YR 3302 Battery Voltage Restored
ZY 1305 Reset to defaults
YM 1311
Transmitter battery missing Transmitter battery missing Battery Disconnected
ID range: 301~ ID range: 301~
YR 3311
Transmitter battery missing Transmitter battery missing Battery Reconnected
ID range: 301~ ID range: 301~
YI 1312 Overcurrent Protection Triggered
YJ 3312 Overcurrent Protection Restored
YP 1319 Overvoltage Protection Triggered
YQ 3319 Overvoltage Protection Restored
AI 1333 Expander Exception
CQ 3333 Expander Restored
AJ 1336 Printer Disconnected
CR 3336 Printer Connected
XT 1384 Battery Low
XR 3384 Battery Voltage Restored
Expander Low Voltage
Normal Expander Voltage
AT 1342 Mains Power Lost
AR 3342 Mains Power Restored
YM 1311 Battery Disconnected
119
SIA code CID code Description
YR 3311 Battery Reconnected
TA (The serial number of 1144 (The serial number of
output module starts from 1, output module starts from 1,
Lid Opened
of keypad starts from 101, of of keypad starts from 101, of
tag reader starts from 201) tag reader starts from 201)
TR (The serial number of 3144 (The serial number of
output module starts from 1, output module starts from 1,
Lid Restored
of keypad starts from 101, of of keypad starts from 101, of
tag reader starts from 201) tag reader starts from 201)
YP 1301
Transmitter AC power Loss Transmitter AC power Loss
ID range: 301~ ID range: 301~ Expander AC Power Loss
Sounder AC power Loss Sounder AC power Loss
ID range: 202~ ID range: 202~
YQ 3301
Transmitter AC power Loss Transmitter AC power Loss
ID range: 301~ ID range: 301~ Expander AC Power Loss Restored
Sounder AC power Loss Sounder AC power Loss
ID range: 202~ ID range: 202~
TA 1144 Lid Opened
TR 3144 Lid Restored
TA 1144 Lid Opened
TR 3144 Lid Restored
XL 1381 Device Offline
XC 3381 Device Restored
TA (The serial number of 1144 (The serial number of
output module starts from 1, output module starts from 1,
of keypad starts from 101, of of keypad starts from 101, of Lid Opened
tag reader starts from 201, of tag reader starts from 201, of
transmitter starts from 301) transmitter starts from 301)
TR (The serial number of 3144 (The serial number of
output module starts from 1, output module starts from 1,
of keypad starts from 101, of of keypad starts from 101, of Lid Restored
tag reader starts from 201, of tag reader starts from 201, of
transmitter starts from 301) transmitter starts from 301)
XT (The serial number of 1384 (The serial number of
output module starts from 1, output module starts from 1,
of keypad starts from 101, of of keypad starts from 101, of Battery Low
tag reader starts from 201, of tag reader starts from 201, of
transmitter starts from 301) transmitter starts from 301)
XR (The serial number of 3384 (The serial number of
output module starts from 1, output module starts from 1,
of keypad starts from 101, of of keypad starts from 101, of Battery Voltage Restored
tag reader starts from 201, of tag reader starts from 201, of
transmitter starts from 301) transmitter starts from 301)
120
SIA code CID code Description
XL (The serial number of 1381 (The serial number of
output module starts from 1, output module starts from 1,
of keypad starts from 101, of of keypad starts from 101, of Device Offline
tag reader starts from 201, of tag reader starts from 201, of
transmitter starts from 301) transmitter starts from 301)
XC (The serial number of 3381 (The serial number of
output module starts from 1, output module starts from 1,
of keypad starts from 101, of of keypad starts from 101, of Device Restored
tag reader starts from 201, of tag reader starts from 201, of
transmitter starts from 301) transmitter starts from 301)
LT 1351 Main Signalling Path Fault
LR 3351 Main Signalling Path Restored
LT 1352 Backup Signalling Path Fault
LR 3352 Backup Signalling Path Restored
AM 1354 Telephone Line Disconnected
CU 3354 Telephone Line Connected
AN 1382 BUS Supervision Fault
CV 3382 BUS Supervision Restored
1380
3380
TA 1144 Lid Opened
TR 3144 Lid Restored
Zone Open-circuit Alarm
Zone Short-circuit Alarm
OP 1401 Disarmed
CL 3401 Armed
OA 1403 Auto Disarmed
CA 3403 Auto Armed
BC 1406 Alarm Silenced
CW 3408 Instant Arming
CS 1409 Keyswitch Zone Disarming
OS 3409 Keyswitch Zone Arming
NL 3441 Armed in home mode
CX 3442 Forced Arming
Turn On Output by Schedule
Turn Off Output by Schedule
CT 1452 Late to Disarm
CD 1455 Auto Arming Failed
Turning On Output Failed
Turning Off Output Failed
Auto Disarming Failed
1556 Network Change
QB 1570 Bypassed
121
SIA code CID code Description
QU 3570 Bypass Restored
AU 1574 Group Bypass
CZ 3574 Group Bypass Restored
AV 1601 Manual Report Test
RP 1602 Periodic Report Test
TS 1607 Walk Test Enabled
TE 3607 Walk Test Disabled
AW 1617 Telephone Connection Test
LB 1627 Programming mode
LX 1628 Exit Programming
BA 1131 Intrusion Detection
BH 3131 Intrusion Detection Restored
BA 1131 Cross-Zone Alarm
BH 3131 Cross-Zone Alarm Restored
PIR Alarm
PIR Alarm Restored
Sudden Increase of Sound Intensity
AY 1775
Alarm
Sudden Increase of Sound Intensity
DE 3775
Alarm Restored
Sudden Decrease of Sound Intensity
AZ 1776
Alarm
Sudden Decrease of Sound Intensity
DF 3776
Alarm Restored
Audio Input Fault
Audio Input Restored
BA 1131 Line Crossing Alarm
BH 3131 Line Crossing Alarm Restored
BA 1134 Region Entrance Detection
EA 1134
FA 1112 Fire Source Alarm
FH 3112 Fire Source Alarm Restored
KS 1158 High Temperature Pre-Alarm
KR 3158 High Temperature Pre-Alarm Restored
ZS 1159 Low Temperature Pre-Alarm
ZR 3159 Low Temperature Pre-Alarm Restored
KA 1158 High Temperature Alarm
KH 3158 High Temperature Alarm Restored
ZA 1159 Low Temperature Alarm
ZH 3159 Low Temperature Alarm Restored
EA 1134 Region Exiting Detection
PA (The user No. of keyfob 1120 (The user No. of keyfob
Audible Panic Alarm
starts from 901) starts from 901)
122
SIA code CID code Description
Audible Panic Alarm
Audible Panic Alarm
Audible Panic Alarm
FA 1110 Keypad/Keyfob Fire Alarm
Keypad/Keyfob Burglary Alarm
CI 1454 Arming Failed
MA
(Contains user information in
1100 Keypad/Keyfob Medical Alarm
the text message if triggered
by keyfobs.)
DK 1501 Keypad Locked
DO 3501 Keypad Unlocked
Absence Alarm
Keypad Disconnected
Keypad Connected
KBUS Relay Disconnected
KBUS Relay Connected
KBUS GP/K Disconnected
KBUS GP/K Connected
KBUS MN/K Disconnected
KBUS MN/K Connected
DK 1501 Tag Reader Locked
DO 3501 Tag Reader Unlocked
BD 1865 Unregistered Tag
XL 1381 Device Offline
XC 3381 Device Restored
XT 1384 Battery Low
XR 3384 Battery Voltage Restored
XL (The serial number of 1381 (The serial number of
output module starts from 1, output module starts from 1,
Device Offline
of keypad starts from 101, of of keypad starts from 101, of
tag reader starts from 201) tag reader starts from 201)
XC (The serial number of 3381 (The serial number of
output module starts from 1, output module starts from 1,
Device Restored
of keypad starts from 101, of of keypad starts from 101, of
tag reader starts from 201) tag reader starts from 201)
XL 1381 Device Offline
XC 3381 Device Restored
BI 1918 Radar Transmitter Fault
DL 3918 Radar Transmitter Restored
XT 1384 Battery Low
XR 3384 Battery Voltage Restored
NT 1350 Cellular Fault
123
SIA code CID code Description
NR 3350 Cellular Restored
NT 1350 SIM Card Exception
NR 3350 SIM Card Restored
NT 1350 Network Fault
NR 3350 Network Restored
XQ 1344 Jamming Detected
XH 3344 Jamming Restored
NT 1350 Data limitation Reached
XT 1384 Battery Low
XR 3384 Battery Voltage Restored
NT 1350 IP Address Already Used
NR 3350 Normal IP address
NT 1350 Network Fault
NR 3350 Network Restored
BA 1131 Motion Detection Alarm Started
BH 3131 Motion Detection Alarm Stopped
BJ 1941 Device Blocked
DM 3941 Device Blocking Alarm Restored
Video Signal Loss
Video Signal Restored
Input/Output Format Unmatched
Input/Output Format Restored
Video Input Exception
Video Input Restored
Full HDD
Free HDD
HDD Exception
HDD Restored
Upload Picture Failed
BQ 1948 Email Sending Failed
BR 1949 Network Camera Disconnected
DS 3949 Network Camera Connected
Duty Checking
Post Response
BU 1962 Fire Alarm Consulting
DT 3962 Fire Alarm Consulting Over
BV 1963 Duress Alarm Consulting
DU 3963 Duress Alarm Consulting Over
BW 1964 Emergency Medical Alarm Consulting
Emergency Medical Alarm Consulting
DV 3964
Over
DW 3250 Patrol Signing
124
SIA code CID code Description
BX 1970 BUS Query
BY 1971 BUS Registration
BZ 1973 Single-Zone Disarming
DX 3973 Single-Zone Arming
CA 1974 Single-Zone Alarm Cleared
CB 1306 Device Deleted
DY 3306 Device Enrolled
CC 1976 Business Consulting
DZ 3976 Business Consulting Over
CD 1306 Device Deleted
EA 3306 Device Enrolled
CE 1306 Device Deleted
EB 3306 Device Enrolled
CF 1306 Device Deleted
3306 Device Enrolled
1306 (The serial number of
output module starts from 1,
CG of keypad starts from 101, of Device Deleted
tag reader starts from 201, of
transmitter starts from 301)
3306 (The serial number of
output module starts from 1,
ED of keypad starts from 101, of Device Enrolled
tag reader starts from 201, of
transmitter starts from 301)
JA 1461 Incorrect Password
NT 1350 Device Offline
YM 1311 Power Depletion
125
H. Communication Matrix and Operation Command
Please scan the OR code for communication matrix and operation command
126
127