Link Box-1
Link Box-1
Link Box-1
MECHANCIAL
Enclosures IP65 minimum. Materials Fabrication of box from 316 alloy stainless steel. Conductors Extruded copper in hard drawn high conductivity 300mm2 minimum. Mounting Arrangements Pit mounted, Structure mounted & Pillar Mounted. Plating, all conductors plated with 8m of tin. Stress cones in polyurethane elastomer. Insulators in high tension porcelain with all stainless steel hardware. Mechanical Details 1. P design in walls in 4mm sheet, lid in 8mm plate. 2. S design in 3mm sheet, lid in 6mm plate Seals Hermetically sealed. Elastomer specification to requirements standard manufacture is: Pit/indoor mounted: Nitrile Outdoor: EPDM or shrouded nitrile For use with oil or ddb insulated HV cables: Viton.
AK Power Solutions Pty Ltd Quality Endorsed Company AS/NZS ISO 9001.2000 HV Cable Sheath Earthing Link Boxes www.akpowersolutions.com Phone: +612 9676 3500 Fax: +612 9676 3511 AKP|HVCSELB.B P1
Tests: Type tests are carried out under water, under vacuum and with halogen leak tests at 100kPa. Routine leak tests are made using halogen leak tests at 100 kPa as <10W (10-4 bar.mLS-1).
ELECTRICAL
Through current withstand. Link boxes are generally tested to 50KArms but alternative withstand can be provided. Voltage Withstand Cross Bonding Link Boxes Insulation is 60kVimpulse phase to phase and 40kVimpulse phaseto-earth. For link boxes fitted with SVL arresters refer to technical data sheet for more information. Solid Earthing Link Boxes These boxes are 25kVdc phase-tophase and phase-to-earth. Routine Test: 25kVdc between-phases and phase-to-earth for 5 minutes. Contact Resistance. The link box terminal to the link and to the cable termination are 5 W.
Price and delivery is by quotation and depends on the construction requested and modifications or special features. When requesting a quotation please include: Maximum value and duration of system fault current. Whether pit/vault or structure mounted. Cable size of bonding and earth cables. If cross bonding or SVL earthing boxes, the maximum power frequency voltage that will occur at the point of installation during a system fault. Any special requirements modifications required.
Ordering Information
Select the part number from the selection table. For modification or non-standard requirements, contact AK Power Solutions.
AK Power Solutions Pty Ltd Quality Endorsed Company AS/NZS ISO 9001.2000 HV Cable Sheath Earthing Link Boxes www.akpowersolutions.com Phone: +612 9676 3500 Fax: +612 9676 3511 AKP|HVCSELB.B P2
Note: 1. Dashed lines (viz:) represent outer conductor of concentric bonding leads.
AK Power Solutions Pty Ltd Quality Endorsed Company AS/NZS ISO 9001.2000 HV Cable Sheath Earthing Link Boxes www.akpowersolutions.com Phone: +612 9676 3500 Fax: +612 9676 3511 AKP|HVCSELB.B P3