30 Auxiliary Relays (P2 Series)
30 Auxiliary Relays (P2 Series)
30 Auxiliary Relays (P2 Series)
Series P2
C
Benefits
of the new
system
Colour coded lock lever
according to coil voltage
DC Blue
AC Red
AC / DC Grey
Industrial size
combination Large wire inlets (Upto 4sq mm )
screws ( M3 ) for easy wiring
S2D is a Two Pole Touch protected Interface Socket with Input / Output configuration
Coil Terminals ( A1 & A2 ) on one side and Contact Terminals ( NO, NC, CO ) on the opposite side.
1
C
Benefits
of the new
system
Colour coded lock lever
according to coil voltage
DC Blue
AC Red
AC / DC Grey
Industrial size
combination
screws ( M3 )
Standard 35mm
m
Mountable Socket
S2LD is a Two Pole Touch protected Socket with Input / Output configuration
Coil Terminals ( A1 & A2 ) on one side and Contact Terminals ( NO, NC, CO ) on the opposite side.
1
P2
Two Poles, Change-Over Contact
6A 250V AC1 0.5A 110V DC1
6A 30V DC1 0.2A 220V DC1
NC NO NC NO
Contacts
3 1 9 7 4
12 14 22 24 A1 + Materials: Standard, AgNi
Optional, code 1 AgNi + 0.2µ Au
COIL Optional, code 2 AgNi + 5.0µ Au
Max. switching current 6A
11 21 A2 - Max. Peak inrush current (20 ms.) 30 A
2 8 5 Max. Switching voltage 250 V
COM COM Max. AC load (Graph 1)* 1.5 KVA
Max. DC load See Graph 2*
Specifications
Operate Time + Bounce Time 10 ms.
Vdc Release Time + Bounce Time 8 ms.
Ambient Temperature -40ºC (no ice)…. +70ºC
Mechanical life ops. 10 Million AC, 20 Million DC relays
Electrical life at nominal load > 100,000 ops.
Operating frequency at nominal load 1,200 / hour
Protection degree IP40 / RT1
Weight Approx. 21 gms.
29 Max
36
9 3
P = LED P2-FP …. VDC
W = Free Wheeling Diode P2-FPW .... VDC
20
20
Specifications
Vdc
Operate Time + Bounce Time 10 ms.
Release Time + Bounce Time 8 ms.
Ambient Temperature -40ºC (no ice)…. +70ºC
Mechanical life ops. 10 Million AC, 20 Million DC relays
Electrical life at nominal load > 100,000 ops.
Operating frequency at nominal load 1,200 / hour
Protection degree IP40 / RT1
Weight Approx. 21 gms.
13 Max.
DC : 12, 24, 48, 110
7.5 F = Mechanical Flag Indicator
W = Free-Wheeling Diodes P2-FW …. VDC
7 1
5
8 2
5
29 Max
36
9 3
20
20
A1 A2
4 5 Suitable Sockets : S2D, S2LD, S2P
9
0.5
2.5 Approvals
C US
P2-A
Two Pole, Normally Open Contact
6A 250V AC1 0.8A 110V DC1
6A 30V DC1 0.4A 220V DC1
NO NO
Contacts
1 7 4
14 24 A1 + Materials: Standard, AgNi
Optional, code 1 AgNi + 0.2µ Au
COIL Optional, code 2 AgNi + 5.0µ Au
Max. switching current 6A
11 21 A2 - Max. Peak inrush current (20 ms.) 15 A
2 8 5 Max. Switching voltage 250 V
COM COM Max. AC load (Table 1) 1.5 KVA
Max. DC load See Table 3
6
Graph 1 Electrical life, ops x 10 Coils (Ohms ± 10% @ 20ºC)
Pull-in voltage < 0.8 x Un
Drop-out voltage < 0.1 x Un
Nominal coil power 1.1 VA (AC) / 0.7 W (DC)
VAC Ω mA VDC Ω mA
24 290 45.0 12 224 53.0
48 1.200 23.0 24 742 32.0
115 7.300 9.5 48 3.500 13.7
230 28.800 4.7 110 19.900 5.5
500 1000 1500
Specifications
Operate Time + Bounce Time 10 ms.
Vdc Release Time + Bounce Time 8 ms.
Ambient Temperature -40ºC (no ice)…. +70ºC
Mechanical life ops. 10 Million AC, 20 Million DC relays
Electrical life at nominal load > 100,000 ops.
Operating frequency at nominal load 1,200 / hour
Protection degree IP40 / RT1
Weight Approx. 21 gms.
Contacts
Materials: Standard AgNi
A1 +
Max. switching current 6A
Max. Peak inrush current (20 ms.) 30 A
Max. Switching voltage 250 V
A2 - Max. AC load (Graph 1)* 1.5 KVA
Max. DC load See Graph 4*
6
Graph 1 Electrical life, ops x 10 Coils (Ohms ± 10% @ 20ºC)
Pull-in voltage < 0.8 x Un
Drop-out voltage < 0.1 x Un
Nominal coil power 1.1 VA (AC) / 0.7 W (DC)
VAC Ω mA VDC Ω mA
24 290 45.0 12 224 53.0
48 1.200 23.0 24 742 32.0
115 7.300 9.5 48 3.500 13.7
230 28.800 4.7 110 19.900 5.5
500 1000 1500
Specifications
Operate Time + Bounce Time 10 ms.
Vdc
Release Time + Bounce Time 8 ms.
Ambient Temperature -40ºC (no ice)…. +70ºC
Mechanical life ops. 10 Million AC, 20 Million DC relays
Electrical life at nominal load > 100,000 ops.
Operating frequency at nominal load 1,200 / hour
Protection grade IP40 / RT1
Weight Approx. 21 gms.
A1 A2
4 5 Suitable Sockets : S2D, S2LD, S2P
9
0.5
2.5 Approvals
C US
P2-A....M
MAGNETIC BLOW OUT
Two Pole, Normally Open Contact
6A 250V AC1 4A 220V DC1
6A 30V DC1 1A 220V DC13
Contacts
A1 + Materials: Standard AgNi
Optional, code 1 AgNi + Au 0.2µ
Optional, code 2 AgNi + Au 5.0µ
Max. switching current 6A
A2 - Max. Peak inrush current (20 ms.) 15 A
Max. Switching voltage 250 V
Max. AC load (Graph 1)* 1.5 KVA
Max. DC load See Graph 5*
6
Graph 1 Electrical life, ops x 10 Coils (Ohms ± 10% @ 20ºC)
Pull-in voltage < 0.8 x Un
Drop-out voltage < 0.1 x Un
Nominal coil power 1.1 VA (AC) / 0.7 W (DC)
VAC Ω mA VDC Ω mA
24 290 45.0 12 224 53.0
48 1.200 23.0 24 742 32.0
115 7.300 9.5 48 3.500 13.7
230 28.800 4.7 110 19.900 5.5
500 1000 1500
Graph 5 Insulation
Dielectric strength (1 minute):
Open Contacts 1 KV
Between Adjacent Poles 3 KV
DC1 Between Contacts & Coil 5 KV
DC13 Insolation resistance at 500VDC >3GΩ
Isolation, IEC 61810-5: 4 KV / 3
Specifications
Operate Time + Bounce Time 10 ms.
Vdc
Release Time + Bounce Time 8 ms.
Ambient Temperature -40ºC (no ice)…. +70ºC
Mechanical life ops. 10 Million AC, 20 Million DC relays
Electrical life at nominal load > 100,000 ops.
Operating frequency at nominal load 1,200 / hour
Protection grade IP40 / RT1
Weight Approx. 21 gms.
A1 A2
4 5 Suitable Sockets : S2D-A, S2LD-A, S2P
9
2.5
Approvals
0.5
C US
P2-A-FW-M(5 KV)
MAGNETIC BLOW OUT
Two Pole, Normally Open Contact
6A 250V AC1 5A 220V DC13
( L/R ratio:7msecs )
Contacts
A1 + Materials: Standard AgNi
Optional, code 1 AgNi + Au 0.2µ
Optional, code 2 AgNi + Au 5.0µ
Max. switching current 6A
A2 - Max. Peak inrush current (20 ms.) 15 A
Max. Switching voltage 250 V
Max. AC load (Graph 1)* 1.5 KVA
Max. DC load See Graph 5*
Graph 5 Insulation
Dielectric strength (1 minute):
Open Contacts 2 KV
Between Adjacent Poles 5 KV
DC1 Between Contacts & Coil 5 KV
DC13 Insolation resistance at 500VDC >3GΩ
Isolation, IEC 61810-5: 4 KV / 3
Specifications
Operate Time + Bounce Time 10 ms.
Vdc
Release Time + Bounce Time 8 ms.
Ambient Temperature -40ºC (no ice)…. +70ºC
Mechanical life ops. 10 Million AC, 20 Million DC relays
Electrical life at nominal load > 100,000 ops.
Operating frequency at nominal load 1,200 / hour
Protection grade IP40 / RT1
Weight Approx. 21 gms.
29 Max
36
20
20
A1 A2
4 5 Suitable Sockets : S2D-A, S2LD-A, S2P
8.9
2.5
Approvals
0.5
C US
P2....H
HEAVY RATING RELAY
Two Pole, Change-Over Contact
8A 250V AC1 0.5A 110V DC1
8A 30V DC1 0.2A 220V DC1
Contacts
Materials: Standard AgNi
A1 + AgNi + Au 0.2µ
Optional, code 1
Optional, code 2 AgNi + Au 5.0µ
Max. Switching current 8A
Max. Peak inrush current (20 ms.) 30 A
A2 -
Max. Switching voltage 250 V
Max. AC load ( Graph 6) * 2.0 KVA
Max. DC load See Graph 7*
6
Graph 6 Electrical life, ops x 10 Coils (Ohms ± 10% @ 20ºC)
Pull-in voltage < 0.8 x Un
Drop-out voltage < 0.1 x Un
Nominal coil power 1.1 VA (AC) / 0.7 W (DC)
VAC Ω mA VDC Ω mA
24 290 45.0 12 224 53.0
48 1.200 23.0 24 742 32.0
115 7.300 9.5 48 3.500 13.7
230 28.800 4.7 110 19.900 5.5
500 1000 1500 2000
Specifications
Operate Time + Bounce Time 10 ms.
Vdc
Release Time + Bounce Time 8 ms.
Ambient Temperature -40ºC (no ice)…. +70ºC
Mechanical life ops. 10 Million AC, 20 Million DC relays
Electrical life at nominal load > 100,000 ops.
Operating frequency at nominal load 1,200 / hour
Protection grade IP40 / RT1
Weight Approx. 21 gms.
Contacts
Materials: Standard AgNi
A1 + Optional, code 1 AgNi + Au 0.2µ
Optional, code 2 AgNi + Au 5.0µ
Max. Switching current 8A
A2 - Max. Peak inrush current (20 ms.) 30 A
Max. Switching voltage 250 V
Max. AC load ( Graph 6) * 2.0 KVA
Max. DC load See Graph 8*
6
Graph 6 Electrical life, ops x 10 Coils (Ohms ± 10% @ 20ºC)
Pull-in voltage < 0.8 x Un
Drop-out voltage < 0.1 x Un
Nominal coil power 1.1 VA (AC) / 0.7 W (DC)
VAC Ω mA VDC Ω mA
24 290 45.0 12 224 53.0
48 1.200 23.0 24 742 32.0
115 7.300 9.5 48 3.500 13.7
230 28.800 4.7 110 19.900 5.5
500 1000 1500 2000
Specifications
Operate Time + Bounce Time 10 ms.
Vdc Release Time + Bounce Time 8 ms.
Ambient Temperature -40ºC (no ice)…. +70ºC
Mechanical life ops. 10 Million AC, 20 Million DC relays
Electrical life at nominal load > 100,000 ops.
Operating frequency at nominal load 1,200 / hour
Protection grade IP40 / RT1
Weight Approx. 21 gms.
Weight Approx.
DIN Rail / Panel Mountable
48
84 Max.
Accessories
Bridge Bar S2D-B1 & S2D-B4 for Coil Terminal (A2 / 5 )
Dimensions in mm.
Approvals
C US
S2D-A
Input / Output Socket (6A / 8A)
for P2 NO Relays
DIN Rail or Panel Mountable
Weight Approx.
DIN Rail / Panel Mountable
48
84 Max.
Accessories
Bridge Bar S2D-B1 & S2D-B4 for Coil Terminal (A2 / 5 )
Dimensions in mm.
Approvals
C US
S2LD 16mm
Input / Output Socket (6A / 8A)
for P2 CO Relays
DIN Rail or Panel Mountable
Weight Approx.
49
1
12
14
2
3
4
16 Max.
S2-LD
A2
21
22
24
9
78 Max.
Accessories Accessories
S2LD-B1 - 1 Way Bridge
S2LD-B1 C Terminal
Dimensions in mm.
6.4 (± 0.20)
22.10 7.5 3.7(-0 /+0.2)
4
2
6.5
21 ( ±1.0)
10 ( ± 0.50 )
8
5.3
Ø 1.7 (±0.20)
Ø 4.0 (±0.30)
Weight Approx.
13
52
40.5
1
14
2
4
S2-LD
A2
21
24
8
78
Accessories Accessories
S2LD-B1 - 1 Way Bridge
S2LD-B1 C Terminal
Dimensions in mm.
6.4 (± 0.20)
22.10 7.5 3.7(-0 /+0.2)
4
2
6.5
21 ( ±1.0)
10 ( ± 0.50 )
8
5.3
Ø 1.7 (±0.20)
Ø 4.0 (±0.30)
15 Specifications
Nominal load 6A / BA @250V
Dielectric strength 1 min.
Coil terminals to contacts 5 KV
Hard brass tin-plated terminals 0.3 x 1mm
Integrated Relay hold down clip
Weight Approx. 6 gms.
Ordering Information
P2
1 2 3 4 5 6
1 : Relay Type 4 : Features 5 : Contact Material
Blank : General Purpose / Blank : No features / Standard Blank : AgNi
Standard F : Mechanical Operation Indicator 1 : AgNi + Au 0.3µ
2 : Contact Form P : LED Indicator 2 : AgNi + Au 5.0µ
Blank : DPDT (2 C/O) Z : Free Wheeling + Polarity Diode
A : DPST-NO(2 N/O) I : Lockable + Manual Push Button 6 : Rated Coil Voltage
3 : Contact Type B : Bridge rectifier
6 / 12 / 24 / 48 / 110 - VDC
R : R/C (Snubber Circuit)
Blank : Single 6 / 12 / 24 / 115 / 230 - VAC
M : Magnetic Blow Out
H : Heavy Duty Relay
W: Free Wheeling Diode
Example : P2-FPZI-1-24VDC means Standard, DPDT (2 C/O Contact), with Mechanical Operation Indicator,
with LED Indicator, with Free Wheeling and Polarity Diode, with Lockable and
Manual Push Button, with AgNi Contacts and 0.2µ Gold Flash with 24 VDC Coil
S2D is the World’s most compact (15mm width) DIN Rail Mountable Socket for the relays
with the below Pitch & Pin configuration
Ø6
73
15 Max.
68
48
84 Max.
28
2.15 Ø3.5
Ø2.5 35
40
15mm width of the S2D DIN Rail Mountable Socket allows to mount 64 Sockets on a Standard 35 mm Din Rail with
a length of 1 meter / 1000 mm length (with a provision for 5 Nos. of End stoppers each with a width of 8 mm).
Generally the PLC (Programmable Logic Controller) / DCS (Distributed Control System) output is 64 Bit output which
requires 64 Relays to drive the load.
All the 64 Relays driven by a particular PLC / DCS can be mounted on a single 35 mm standard 1 Mt / 1000 mm
Din Rail.
The provision to mount 64 Relays on a single 35 mm DIN Rail with 1 mt / 1000 length makes the wiring, identification
of the relays from a particular PLC / DCS & maintenance very easy and convenient.
7
Schematic diagram showing typical mounting of 64 Relays & Sockets on a standard 35 mm Din Rail with 1 meter (1000 mm) length
15mm ( per socket ) x 16 nos = 240mm 15mm ( per socket ) x 16 nos = 240mm 15mm ( per socket ) x 16 nos = 240mm 15mm ( per socket ) x 16 nos = 240mm
Socket 1 Socket 2 .... Socket 16 Socket 17 Socket 18 .... Socket 32 Socket 33 Socket 34 .... Socket 48 Socket 49 Socket 50 .... Socket 64
15 mm max. 15 mm max. 15mm max. 15 mm max. 15 mm max. 15 mm max. 15 mm max. 15 mm max. 15 mm max. 15 mm max. 15 mm max. 15 mm max.
22 12 22 12 22 12 22 12 22 12 22 12 22 12 22 12 22 12 22 12 22 12 22 12
9 3 9 3
.... 9 3 9 3 9 3
.... 9 3 9 3 9 3
.... 9 3 9 3 9 3
.... 9 3
21 11 21 11 21 11 21 11 21 11 21 11 21 11 21 11 21 11 21 11 21 11 21 11
8 2 8 2 8 2 8 2 8 2 8 2 8 2 8 2 8 2 8 2 8 2 8 2
24 14 24 14 24 14 24 14 24 14 24 14 24 14 24 14 24 14 24 14 24 14 24 14
7 1 7 1 7 1 7 1 7 1 7 1 7 1 7 1 7 1 7 1 7 1 7 1
P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2
Relay Relay Relay Relay Relay Relay Relay Relay Relay Relay Relay Relay
DIN Rail
5 nos.
5 4 5 4 White Label 5 4 5 4 5 4 5 4 5 4 5 4 5 4 5 4 5 4 5 4
End Stopper
A2 A1 A2 A1 A2 A1 A2 A1 A2 A1 A2 A1 A2 A1 A2 A1 A2 A1 A2 A1 A2 A1 A2 A1 (max. Width 8mm)
S2 D sockets can be interconnected through bridge bars in the coil line at the points A2 by using S2D-B1 and S2D-B4 Coil Bridges
Paramount Industries
#70, 5th Cross, SSI Area, Rajajinagar,
Bangalore - 560 010, India.
Tel : +91-80-22970010, 23157313, 23150828
Fax : +91-80-23302574, 28520623
Email : info@paramount.net.in
Website : www.paramount.net.in
Specification may change in the view of product improvement without prior intimation.