Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Final Drawing

Download as pdf or txt
Download as pdf or txt
You are on page 1of 112

Final

Rubrik
drawing

Including: Shipyard :
- Tank Level Gauging System HYUNDAI MIPO DOCKYARD
Drawings
- Type approval cert. CO.,LTD.
- Operating manual
- Installation manual Hull no.: H2377/78/79/80
Vessel type:
51K PRODUCT / CHEMICAL TANKER
Class.: DNV

Scanjet Macron Co., Ltd.


Tel : + 82 51 711 3500
Fax : +82 51 711 3505
Web: www.scanjet.kr
E-Mail : info@scanjet.kr
1 2 3

4 5 6

7 8 9

0
<0>

DET NORSKE VERITAS


TYPE APPROVAL CERTIFICATE

CERTIFICATE NO. A-12913

This is to certify that the


Level Indicating System

with type designation(s)


SML 1000 A/D

Manufactured by
Scanjet Macron Co., Ltd.
Pusan Korea, Republic of Korea

is found to comply with


Det Norske Veritas' Rules for Classification of Ships, High Speed & Light Craft and Det Norske Veritas' Offshore Standards

Application
Location classes:

Temperature B
Humidity B
Vibration A
EMC A
Enclosure A

Høvik, 2012-09-20 This Certificate is valid until


for Det Norske Veritas AS 2014-06-30

Odd Magne Nesvåg DNV local office: Geir Bjørn Alnes


Head of Section Pusan Surveyor

This Certificate is subject to terms and conditions overleaf. Any significant change in design or construction may render this Certificate invalid.
The validity date relates to the Type Approval Certificate and not to the approval of equipment/systems installed.
If any person suffers loss or damage which is proved to have been caused by any negligent act or omission of Det Norske Veritas, then Det Norske Veritas shall pay compensation to such
person for his proved direct loss or damage. However, the compensation shall not exceed an amount equal to ten times the fee charged for the service in question, provided that the maximum
compensation shall never exceed USD 2 million. In this provision "Det Norske Veritas" shall mean the Foundation Det Norske Veritas as well as all its subsidiaries, directors, officers,
employees, agents and any other acting on behalf of Det Norske Veritas.

DET NORSKE VERITAS AS, Veritasveien 1, NO-1322 Høvik, Norway, Tel.: +47 67 57 99 00, Fax: +47 67 57 99 11, Org.No. NO 945 748 931 MVA www.dnv.com
Form No.: TA 1411a Issue: October 2009 Page 1 of 3
Certificate No.: A-12913
File No.: 863.30
Job Id.: 262.1-008468-2

Product description
SML 1000 A Analogue Electro-pneumatic tank level and draft gauging system.
Cabinet TLG30 comprising the following components:
- ACU 16, Analogue Control Unit
- CP SNT70, Power Supply Unit
- GSBxx, Gauge Pressure Sensor
- MNRxx, Modulator without rubber membrane
- MWRxx, Modulator with rubber membrane as option

SML 1000 D Digital Electro-pneumatic tank level and draft gauging system.
Cabinet TLG30 comprising the following components:
- MCU 302, Main Control Processor PCB
- SDU 30C, Service and Display unit
- DAU 16, Digital Analogue Converter Unit
- CP SNT70, Power Supply Unit
- GSBxx, Gauge Pressure Sensor
- ASBxx, Absolute Pressure Transmitter
- TBxx, Terminal Board
- SW30, Pressure Switch
- MNRxx, Modulator without rubber membrane
- MWRxx, Modulator with rubber membrane as option

Application/Limitation
The following documentation of the actual application is to be submitted for approval in each case:
- Reference to this Type Approval Certificate
- System block diagram
- Power supply arrangement (may be part of the System block diagram)

The Type Approval covers hardware and software listed under Product description.

As long as the units are covered by the Type Approval, a product certificate according to Pt.4 Ch.9 Sec.1 A 202 will not be
required. Correct configuration and set up for each delivery to be tested during commissioning after installation.

Type Approval documentation


Tests carried out
Applicable tests according to Standard for Certification No. 2.4, April 2006.

DET NORSKE VERITAS AS, Veritasveien 1, NO-1322 Høvik, Norway, Tel.: +47 67 57 99 00, Fax: +47 67 57 99 11, Org.No. NO 945 748 931 MVA www.dnv.com
Form No.: TA 1411a Issue: October 2009 Page 2 of 3
Certificate No.: A-12913
File No.: 863.30
Job Id.: 262.1-008468-2

Certificate Retention Survey


The scope of the retention/renewal survey is to verify that the conditions stipulated for the type are complied with, and that no
alterations are made to the product design or choice of systems, software versions, components and/or materials.
The main elements of the survey are:
• Ensure that type approved documentation is available
• Inspection of factory samples, selected at random from the production line (where practicable)
• Review of production and inspection routines, including test records from product sample tests and control routines
• Ensuring that systems, software versions, components and/or materials used comply with type approved documents and/or
referenced system, software, component and material specifications
• Review of possible changes in design of systems, software versions, components, materials and/or performance, and make
sure that such changes do not affect the type approval given
• Ensuring traceability between manufacturer’s product type marking and the type approval certificate
Retention survey is to be performed at least every second year and at renewal of this certificate.

END OF CERTIFICATE

DET NORSKE VERITAS AS, Veritasveien 1, NO-1322 Høvik, Norway, Tel.: +47 67 57 99 00, Fax: +47 67 57 99 11, Org.No. NO 945 748 931 MVA www.dnv.com
Form No.: TA 1411a Issue: October 2009 Page 3 of 3
SML 1000D Operation Manual 1.0

ELECTRO-PNEUMATIC TANK LEVEL GAUGING


AND DRAFT MEASURING SYSTEM

OPERATING MANUAL
MODEL: SML 1000D
March 2010
Scanjet Macron International Ltd.
Kornetintie 10, 3rd floor, FI-00380 Helsinki, Finland
Tel: +358 20 711 8210 Fax: +358 20 711 8219
email: info@scanjet.fi www.scanjetmacron.com

PROPRIETARY RIGHTS NOTICE


The information contained in this manual is the property of Scanjet Macron Co Ltd
And must not be used/copied/transmitted to third party without the express written authority of Scanjet Macron Co.,Ltd.
Revision date 31.3.2010
SML 1000D Operation Manual 1.0

1. INTRODUCTION ........................................................................................................................................... 4
1.1 General Description of SML 1000D ...................................................................................................... 4
2. OPERATING SML1000D .............................................................................................................................. 4
2.1 Principle of Pneumatic Tank Level Measurements ............................................................................ 4
2.2 Supply Air and Piping ............................................................................................................................ 4
2.3 Non-return Valves and Shut-off Valves ................................................................................................ 6
2.4 Tank Level Calculations ........................................................................................................................ 9
2.4.1 Level Calculations for Unpressurized Tanks - Gauge Sensors .................................................. 9
2.4.2 Tank Level Calculations for Unpressurized Tanks - Absolute Sensors................................... 10
2.4.3 Approximate Tank Level Calculations using Pressure Instrument ........................................... 11
2.5 Tank Level Calculations for Pressurized Tanks ................................................................................ 12
2.6 Air Flow Controller – Pneumatic Units .............................................................................................. 13
2.6.1 Constant Air Flow Controller and Purging Valve ....................................................................... 13
2.6.2 Adjusting Constant Air Flow ........................................................................................................ 15
2.6.3 Air Purging Procedure .................................................................................................................. 17
2.6.4 Manifold .......................................................................................................................................... 19
2.7 Air Dryer Unit ........................................................................................................................................ 20
2.7.1 Air Filter and Optional Oil Mist Filter ........................................................................................... 21
2.7.2 Air Fiber Dryer ............................................................................................................................... 22
2.7.3 Air Flow Pressure Regulator ........................................................................................................ 23
2.8 Pneumatic 1:1 Converter..................................................................................................................... 23
2.9 Sensors ................................................................................................................................................. 24
2.9.1 Gauge Pressure Sensors.............................................................................................................. 25
2.9.2 Absolute Pressure Sensors ......................................................................................................... 27
3 ELECTRONIC UNITS................................................................................................................................... 30
3.1 MCU302 (Main Control Processor Unit) ......................................................................................... 32
3.2 SDU30c (Service Display Unit) ........................................................................................................ 34
3.3 Terminal Board for Sensor Connection ......................................................................................... 35
3.4 Digital to Analog Converter (DAU16) – Optional ........................................................................... 37
3.4.1 Supply Air Pressure Switch ......................................................................................................... 39
3.4.2 Power Supply Unit (SNT 30) ......................................................................................................... 40
4. USER MANUAL FOR SERVICE DISPLAY UNIT OPERATION ................................................................. 41
4.1 Starting up the Service Display Unit SDU30c ................................................................................... 42
4.1.1 Single Cabinet in a System .......................................................................................................... 42
4.1.2 Number of Cabinets in a SML 1000D System ............................................................................. 44
4.2 Display Mode ........................................................................................................................................ 45
4.2.1 Display Menu, Sheet 1 .................................................................................................................. 46
4.2.2 Fluid Level Height on Display Menu - Sheet 2............................................................................ 47
4.2.3 Density on Display Menu - Sheet 3 .............................................................................................. 48
4.2.4 Offset on Display Menu - Sheet 4 ................................................................................................ 49
4.2.5 Sensor Status on Display Menu - Sheet 5 .................................................................................. 50

2
SML 1000D Operation Manual 1.0

4.2.6 Pressure reading on Display Menu - Sheet 6 ............................................................................. 51


4.2.7 Pipe Flow Resistance on Display Menu, Sheet 7 ....................................................................... 52
4.3 Service Mode ........................................................................................................................................ 53
4.3.1 Service Menu - Sheet 1 ................................................................................................................. 54
4.3.2 Calibration of Pressure Sensor- Service Menu Sheet 2 ............................................................ 55
4.3.3 Calibration Analog Output Rescaling- Service Menu Sheet 3 --
Optional Function ................................................................................................................................. 56
4.3.4 Setting of Tank Offset & Density - Service Menu Sheet 4 ......................................................... 57
4.3.5 Analog Output Simulation - Service Menu, Sheet 5 --
Optional Function ................................................................................................................................. 58
4.3.6 Flow Resistance - Service Menu Sheet 6 .................................................................................... 59

3
SML 1000D Operation Manual 1.0

1. Introduction
1.1 General Description of SML 1000D
The Scanjet Macron SML 1000D is a microprocessor-controlled electro-pneumatic system for remote
continuous online measurements of liquid levels in ship tanks, as well as for measuring ship drafts.
The system can also be used for detection and monitoring of water and other fluid ingress in dry
compartments, voids and empty tanks.
The electro-pneumatic tank level measuring system consists of measuring piping and one or more
cabinets with pressure sensors, flow controllers and necessary electronics for processing and displaying
the measured tank pressures as tank levels.
There are no sensors or moving parts inside the tanks requiring tank entry.
Three different cabinet sizes available for the Scanjet Macron SML 1000D electro-pneumatic tank level
gauging system –with max. 10, 20 or 30 gauge sensors in one cabinet for measuring pressures tanks,
water ingress and drafts.
The different cabinet sizes allow for optimization and efficient distribution of the TLG system cabinets in
larger systems, resulting in significant savings as fewer cabinets can be used (saved electronics etc.),
and less piping material and work.
All cabinets should be located in easily accessible and safe area for service and check purposes. The
cabinets have been designed to be user and maintenance friendly.

2. Operating SML1000D
2.1 Principle of Pneumatic Tank Level Measurements
All Scanjet Macron SML 1000D sensors are inside the system cabinets and mounted in racks. The
maximum number of tank level gauging, water ingress detection and draft measuring sensors is 10, 20
or 30 depending on cabinet size. The sensors are gauge (breathing) type requiring normally no
atmospheric compensation
In addition, there may be two atmospheric reference absolute pressure sensors depending on the
location of the cabinet. If there are significant pressure differences between outdoor pressure and
pressure at cabinet location, then this air pressure difference must be considered when calculating the
actual tank levels using the gauge sensors.
There is at least one measuring air pipe from the cabinet to inside every tank measured.
In case there is no manual sounding possibility for a tank, then two independent measuring pipes are
required by the Authorities, or alternatively one other type of system, in the same tank.

2.2 Supply Air and Piping


SML 1000D utilizes dry and clean compressed air (instrument air). Based on our experience, we always
deliver an air dryer with filter and air pressure regulator to secure the dryness and cleanness of the
supply air.

4
SML 1000D Operation Manual 1.0

General System Overview

5
SML 1000D Operation Manual 1.0

The supply air inlet pressure is approximately 7 bar. The air pressure is reduced with the air pressure
regulator to 4.5-5 bar. This eliminates any random pressure fluctuations caused by other consumers
connecting and disconnecting to the supply air pipe.

The constant flow controller maintains the airflow constant in the measuring pipe to the tank irrespective
of the counter pressure –with increasing tank pressure the air consumption increases as the flow
remains constant.

The airflow may be set and adjusted with the screw in front of the airflow controller when necessary. In
normal operation, the set value 0.5 Nl/min is recommended for empty tank condition.

The measuring air pipe from the cabinet to the tank side or top has OD 10mm, inside the tank the
diameter is increased to OD 20mm (3/4”). The increase in diameter inside the tank is based on our
experience showing that this eliminates fluctuations in the measured tank pressures (and thus
calculated tank levels) during pumping and discharging operations.

The hydrostatic pressure changes when the fluid level increases or decreases, and sensors record
changing tank levels and filling/discharging rates.

By measuring the hydrostatic counter pressure, accurate tank pressures and levels in water ballast
tanks, heavy fuel oil, marine diesel oil and various other tanks can be obtained. The same applies to
water and fluid ingress detection and monitoring.

The low end of the measuring pipe inside the tank should be as close as possible to the bottom for
accurate tank level readings with low tank filling, because it is not possible to create hydrostatic counter
pressure with air bubbling below the lower pip end. Consequently, there may be some fluid in the tanks,
even if the remote tank level gauging system shows that the tank is empty.

Typically, this distance (offset) is 50-100 mm. The lower end of the pipe should also be sniped at 30O
angle for consistent measuring air escape at tank bottom.

For fresh water and some special fluid tanks (wine, edible oils etc.) it is not accepted to use air
in the tank because of health reasons (bacteria etc.), or because of chemical reactions caused by
oxygen. For these tanks, a pneumatic 1:1 pressure converter is used for measuring the hydrostatic
pressure inside. The pneumatic 1:1 pressure converter should be located as close to the bottom as
possible.

The Scanjet Macron SML 1000D is self-cleaning because the instrument air is always flowing through
the pipes, even when the tanks are empty. As a result, the air pipes stay clean of any sediments even if
their low ends are close to the tank bottom.

Every flow controller has a built in by pass feature allowing purging of blocked pipe with full line pressure.
By turning the knob on the flow counter clockwise, the purge is opened for the tank and closed by
turning clockwise.

2.3 Non-return Valves and Shut-off Valves


The Scanjet Macron SML 1000D has three different non-return valve arrangements for the protection
against accidental fluid backflow through measuring lines from tanks, void spaces and drafts.

For every measuring line, there is a built-in non-return valve in the constant flow controller module
hindering any backflow of fluid into the cabinet in case supply air pressure is lost.

There is also an air pressure control switch in every cabinet, which closes should the supply air pressure
drop below 0.3 MPa, keeping air pressure in the cabinet and the pipes hindering backflow. The switch is
automatically opened when the supply air pressure exceeds 0.35 MPa.

Depending on type and location of the tank, non-return valves are fitted at the tank side or the tank top
to prevent backflow from tanks in case the air pressure is lost.

6
SML 1000D Operation Manual 1.0

In case the Scanjet Macron SML 1000D cabinet is installed below main deck and tank air vent pipe
heads, we recommend that also that high located water ballast tanks such as fore peak and top wing
tanks are fitted with non-return valves hindering any backflow of ballast water.

The non-return valves at tank side and top are gravity loaded and the housing with float must be
installed in vertical position in order for the float to function properly.

For fuel tanks, side penetrations must be fitted shut-off valve according to safety regulations. We
recommend installing non-return valves for these tanks as a safety precaution against accidental spray
of fuel oil on hot surfaces, or oil spill in the engine room in case the measuring air pipes are accidentally
damaged.

Every draft measuring point is fitted with non-return valve after the globe shut-off valve in order to hinder
seawater from entering to the ship through draft measuring openings should the draft measuring pipe be
accidentally ruptured or broken.

Constant air flow Counter pressure


Purge valve
Flow control valve

Dried & Clean air(5bar)  P E TB 30


Air Dryer Unit

7 BAR
MCU302
TO CABINET TO CABINET
DAU16_1

DAU16_2

Optional SDU 30c


Level Height

ELECTRONIC PARTS
Height

IN CABINET FOR SML 1000D

UNPRESSURIZED TANK PRESSURIZED TANK


General system overview for pneumatic principle

7
SML 1000D Operation Manual 1.0

STRUCTURE OF NRV - FS , NRV -FE , NRV-NF

HEAD

PLUG
MALE
CONNECTOR O-RING

FLOAT
BODY

A. How Air Flow in NRV B. How Water Flow in NRV

air flow     air flow    









 



Liquid

In Tank In Tank

All NRVs are constructed in the same way, except for the tank connection, which can be a
flange connection or threaded. Also 90O bended NRV construction is available.

 Maximum working pressure: 0.5MPa


 Connection size for yard copper tube: OD10mm or OD8mm
 Method: plastic floater with O-ring
NRV-FS: Non return valve straight type with flange
NRV-FE: Non return valve elbow type with flange
NRV-NS: Non return valve inner threads type without flange

The head of NRV can be disconnected from the body for replacing O-ring by turning counterclockwise
direction.

The float moves upwards with the tank level, closes the air supply line, and prevents any back flow of
fluid.

Leakage can possibly occur from male connector, plug, head connection or tank connection.

8
SML 1000D Operation Manual 1.0

2.4 Tank Level Calculations


The electro-pneumatic tank level and draft measuring system measures continuously online the
hydrostatic counter-pressure in tanks and voids spaces and the hydrostatic sea pressure for drafts.

All sensors are located in the cabinet(s) in safe area. The tank levels are calculated in the main control
unit from the measured pressures considering the pipe resistance, the distance from tank measuring
pipe to inside the bottom and the fluid densities.

The atmospheric pressure compensation depends on the type of sensor and the measured difference
between weather deck atmospheric pressure and local cabinet pressure.

2.4.1 Level Calculations for Unpressurized Tanks - Gauge Sensors


Water ballast, fuel oil, lubrication oil, and fresh water tanks are unpressurized tanks that have open-air
vent pipes, and should hence not in general contain any gases such as nitrogen or inert gas.

In some double hull oil tankers, inert gas is used in ballast tanks. This type of tanks are pressurized and
have pressure release valves– see 2.5 for tank level calculation in pressurized tanks.

The actual hydrostatic counter pressure from fluid in unpressurized tanks is measured using gauge type
pressure sensors (self-breathing). The tank levels displayed on the service display unit (SDU30c) are
calculated in the SML 1000D by using below formulae:

Hydrostatic pressure PT = Pmg - (ᇞPD - Pr)


To be added ᇞPD in case PA < Pa , PT = Pmg + (ᇞPD - Pr)
To be subtracted ᇞPD in case PA > Pa , PT = Pmg - (ᇞPD - Pr)
Height h = PT (mbar) * conversion factor ( 0.010197162)
Level Height LH = (h / D) + To

Below formulae can be used for same results


Hydrostatic pressure PT = Pmg - (ᇞPD - Pr)
Level Height LH = (PT / D * G) + To
The symbols used in above formulae are given in Table 1.

Table.1. Definition of symbols


Tank offset – distance of measuring pipe end from tank bottom m To
Density of liquid in tank kg/m3 D
Air flow resistance in measuring pipe mbar Pr
Tank level height m LH
Tank height without density D, and offset To m h
mbar PT
Hydrostatic counter pressure in tank
Measured pressure acting on gauge sensor mbar Pmg
Measured pressure acting on absolute sensor mbar Pma
Saved cabinet ATM reference pressure value at zero calibration mbar PA
Pressure reading in real time for inside cabinet mbar Pa
Difference pressure ᇞPD = PA- Pa mbar ᇞPD
Saved weather deck ATM reference pressure at zero calibration mbar PAO
Saved tank measurement pressure as absolute sensor at zero mbar Pao
calibration
This symbol only is used in calculation when tank measuring
sensor is absolute sensor type

Difference pressure ; ᇞPd = PAO - Pao mbar ᇞPd


Gravity acceleration (9.80665 m/s2) m/s2 G

9
SML 1000D Operation Manual 1.0

on deck in room


Gauge Sensor for
tank measuring

Flow resistance

Absolute Sensor
for ATM measuring

Hydrostactic Pressure

Absolute Sensor
for ATM measuring
TANK BOTTOM
TANK OFFSET

Calculations for unpressurized tank


Density Gravity measuring by gauge sensor

Note! In general, the atmospheric pressure outside on the weather deck, and inside the ship near the
SML 1000D cabinet that are almost the same, and no atmospheric compensation is hence needed for
the gauge tank level sensors (ᇞPD = 0).

2.4.2 Tank Level Calculations for Unpressurized Tanks - Absolute Sensors


The formulae below is applied for absolute sensors
Hydrostatic pressure PT = Pma - (ᇞPd - Pr)
To be added ᇞPD in case PAO > Pao , PT = Pmg + ᇞPd - Pr
To be subtracted ᇞPD in case PAO < Pao , PT = Pmg - (ᇞPd - Pr)
Height h = PT (mbar) * conversion factor ( 0.010197162)
Level Height LH = (h / D) + To

Below formula also can be used as same results


Hydrostatic pressure PT = Pma - (ᇞPd - Pr)
Level Height LH = (PT / D * G) + To

10
SML 1000D Operation Manual 1.0

on deck in room


Absolute Sensor
for tank measuring

Flow resistance

Absolute Sensor
for ATM measuring

Hydrostactic Pressure

TANK BOTTOM TANK OFFSET

Calculations for unpressurized tank


Density Gravity measuring by absolute sensor

2.4.3 Approximate Tank Level Calculations using Pressure Instrument


The SML 1000D measures continuously the actual tank pressures online.
In case the air supply is lost, there will still be pressure in the measuring pipes, because the air pressure
switch inside the cabinet and the non-return valves inside the flow controllers will close when supply air
pressure drops.

The tank levels are then calculated as described in 2.4.1 and 2.4.2 respectively until the air supply is
restored.

In case the power supply is lost because of ship general electrical blackout or other similar reason, then
the tank levels are not calculated and shown in the SML 1000D (unless the tank level gauging system
has been supplied with an emergency generator and compressor unit for supply air).
However, the tank pressures can still be measured with a pressure instrument for every tank measuring
line from the tank level gauging system cabinet as described below.

Following factors provide approximate values for tank pressure conversion into level height.

To bar mbar kPa


mH2O 10.197162 0.010197162 0.10197162

For example:
1. The pressure instrument reading is 1068 mbar
2. To convert: 1068 mbar * 0.010197162 = 10,890 mH2O
3. If the tank offset, the fluid density, and the flow resistance are known, these
can be applied to obtain a more accurate tank level.
Tank offset: 0.1m, Density: 1.025 kg/m3 and Flow resistance: 3 mbar
Level Height = (((1068 mbar – 3 mbar) * 0.010197162 ) / 1.025 ) + 0.1 m
= 10.695 mH2O
Note! ATM reference pressure is disregarded in above calculation

11
SML 1000D Operation Manual 1.0

2.5 Tank Level Calculations for Pressurized Tanks


Most pressurized cargo tanks should have nitrogen or inert gas for protection against explosion.

The actual hydrostatic counter pressure from fluid in pressurized tanks is measured using absolute type
pressure sensors (vacuum).

The tank levels displayed on the service display unit (SDU30c) are calculated in the SML 1000D by
using below formulae:

Measured pressure Pma = PT + Pt + Pr


Measured pressure Pmo = Pt + Pro
Tank Top pressure Pt = Pmo - (ᇞPd - Pro)
Hydrostactic pressure PT = Pma – (Pt - ᇞPd - Pr)
Level Height LH = (PT / D * G) + To

Table 2. Definition of Symbols


Tank offset – distance of measuring pipe end from tank bottom m To
Density of liquid in tank kg/m3 D
Air flow resistance for measuring pipe in liquid mbar Pr
Air flow resistance for measuring pipe in tank ullage space mbar Pro
Tank level height m LH
Tank height without density D, and offset To m h
Hydrostatic counter pressure in tank mbar PT
Tank ullage pressure – in air above the liquid surface mbar Pt
Measured pressure for tank liquid mbar Pma
Measured pressure for tank ullage pressure mbar Pmo
Saved cabinet ATM reference pressure value at zero calibration mbar PA
Actual ATM pressure at the time of measurement for inside mbar Pa
cabinet
Difference pressure ᇞPD = PA- Pa mbar ᇞPD
Saved weather deck ATM reference pressure at zero calibration mbar PAO
Saved tank measurement pressure as absolute sensor at zero mbar Pao
calibration
Difference pressure ; ᇞPd = PAO - Pao mbar ᇞPd
Gravity acceleration (9.80665 m/s2) m/s2 G

12
SML 1000D Operation Manual 1.0

on deck in room


Absolute Sensor for tank
liquid measuring

Flow resistance 


Absolute Sensor for tank top
pressure measuring
Flow resistance

Hydrostactic Pressure

Absolute Sensor
for ATM measuring

TANK BOTTOM
TANK OFFSET

Density Gravity Calculations for pressurized tank


measuring by absolute sensor

2.6 Air Flow Controller – Pneumatic Units


For every measuring line there is a flow controller unit inside the SML 1000D cabinet.
The air flow controller unit consists of following components:
(1) Purge Valve, (2) Flow Control Valve, (3) Air flow indicator, (4) Air filter , (5) Fiber dry,
(6) Air Regulator, (7) Upper part of modulator (Air flow controller), and (8) Lower part of modulator
(Manifold), see figure on the next page.

2.6.1 Constant Air Flow Controller and Purging Valve


The constant air flow controller includes a check valve in the manifold and a purge valve, a constant flow
control valve, flow indicator, and two barb fittings in the upper part.

The instrument air will flow through the check valve. A spring will push the valve to close when the inlet
working pressure is less than 0.3 MPa.

The flow adjustment screw in front of the controller is used to set the constant air flow to the tank for
optimum measuring conditions.

13
SML 1000D Operation Manual 1.0

8
7

The air flow screw on the front of the air flow controller will regulate the air flow rate in the pneumatic
measuring line. The set air flow rate is adjusted to increase/decrease by turning the screw
counterclockwise/clockwise.

The air flow indicator shows the actual air flow in the measuring pipe.

It is recommended that all air flow adjustments are carried out to show same air flow rate of
approximately 0.5L/ min on the air flow indicator. The air flow can be adjusted from 0.2L ~ 1.0L / min.

Air purging is used for testing and cleaning tank and draft measuring pipes. The purge valve is opened
turning the knob counterclockwise and closed clockwise.

During purging, the airflow controller is bypassed by opening purge valve knob, and high pressure
supply air enters the measuring line to tank directly.

The purge valve must always be kept closed when tank levels and drafts are measured.

In case the valve is partly open or has a leakage, the tank level shown on the LCD will be higher than
the real tank level. The leakage will result in pressure drop in the measuring line, and the air flow must
increase in the tank measuring pipe to match the hydrostatic counter pressure. Consequently the
pressure acting on the sensor will be higher and the level shown will be higher.

When purging, the tank level will show more than the real tank level because the 5 bar purge pressure is
directly acting on the sensor.

In case the measuring line is clogged, this can be opened in most cases by purging at high/full supply
air pressure 5 or 7 bar.

14
SML 1000D Operation Manual 1.0

TO PRESSURE SENSOR
TO PRESSURE SENSOR

TO TANK TO TANK

2
OPERATING AIR 5bar OPERATING AIR 5bar
3
INSTRUMENT AIR 7bar INSTRUMENT AIR 7bar

6 4

(A) (B)

Air purging flow in air flow controller (A)

Prior to commissioning, the measuring lines should be blown free of any dirt and moisture by opening
purge valve knob (1) counterclockwise.

The compressed air will go through the purge valve to the connected pressure sensor and to the tank
bottom when the purge valve is opened.

During purging, the tank level will indicate full range or more because the compressed pressure air is
acting directly on the pressure sensor.

When finished purging, the purge valve must be closed completely by turning the valve knob clockwise.
After a few seconds, the present actual level measuring result will show on the LCD.

Air flow during tank level and draft measuring (B)

The constant air flow is controlled by the air flow control valve (2), which is mounted on the front side of
the air flow controller unit.

The constant air flow rate can be different in each tank depending on the length of the measuring pipe.

The air flow rate adjustment must be done when there is no counter pressure in the tank so that the
correct measuring pipe flow resistance is obtained.

2.6.2 Adjusting Constant Air Flow


It is important to ensure that the following conditions have been checked before adjusting the constant
air flow rate.

Make sure that:


 the stop valve (6) is open
 the pressure gauge (7) on air dryer unit shows 5 bar after it has been regulated
 the purge valve (2) on the unit is closed completely.
 if the flow control valve (4) is completely closed, the black ball is at the bottom
 the tank is empty. If not, the measuring line must be disconnected from the non-return
valve to measure correct flow resistance.
 in case there is a counter-pressure in the line, the value of flow resistance is much
higher than expected. It means that the level calculation will be wrong.

15
SML 1000D Operation Manual 1.0

When everything above is checked and done, the constant air flow can be adjusted and then air flow
resistance also measured by shown on the display unit SDU 30c at the same time.

It is recommended to set the ball position at 0.5 L/min using the flow control valve when the above
conditions are met.

If tank liquid filling/unloading rate is low, the airflow rate can be decreased manually from B condition.
Then the normal air flow setting will be below 0.5L/min line on the air flow indicator.

If the tank filling and unloading rate is higher than the measuring result update rate (e.g. updating speed
for tank level on LCD), then the airflow can be increased to be above the 0.5L/min as in figure C.

Warning!
If the flow rate for one of the tanks is adjusted upwards or downwards after commissioning, the
measuring pipe flow resistance must be measured again in empty tank for correct compensation of the
measured tank level, because the measuring pipe resistance is dependent on the actual flow rate. If not
the pipe resistance is measured again for new air flow value, then the tank levels calculated will be
wrong!

16
SML 1000D Operation Manual 1.0

2.6.3 Air Purging Procedure


The SML 1000D is an electro-pneumatic tank level and draft measuring system operating at an air
pressure of 4.5-5 bar. Because the system is continuously blowing air at a constant flow rate of 0.5L/min
also into empty tanks, the system is self-cleaning even when the low end of the measuring pipe is close
to the tank bottom, where sediments are found in ballast water tanks.

In case the tank level gauging system is completely shut down, like during dry-docking, there might be
some sediments at, or even inside the lower end of the measuring pipe. If the measuring pipe from the
cabinet to the tank is disconnected either from the non-return valve or at the cabinet, sediments may
enter in the measuring pipe because there will be no air pressure in the measuring pipe after
disconnecting.

17
SML 1000D Operation Manual 1.0

These sediments may be removed by opening the purge screw on the air flow controller for the
measuring pipe in question. Usually this 5 bar pressure sufficient to open the clogged measuring pipe. In
case the pipe remains clogged after purging at 5 bar, then full 7 bar may be used by increasing the air
flow to full at the air pressure regulator.

How a clogged measuring line is detected?

The clogging is easily observed, because the tank level increases/or decreases even when no pumping
is carried out.
 The tank level increases slowly to full height.
 The flow indicator ball moves gradually towards bottom from original setting.
 The same results are obtained if the measuring pipe is pressed together or bent severely
somewhere between the cabinet and the tank. The condition of the measuring pipe should be
checked to find possible damage.
 If none of the above applies, then there may be a problem with the purge valve.

How to purge a measuring pipe?


1. Open the purge valve (2 in the figure below) by turning the knob on the air flow controller
counterclockwise to purge the measuring line at 5 bar pressure.
2. Let the purge valve be open for 1-2 minutes.
3. Close the purge valve by turning it clockwise until it is closed.
4. The flow rate indicator ball should now show 0.5 L/min.
5. If the ball is not at 0.5 L/min, repeat the procedures 1-3 above 1-2 times.
6. In case the ball after the above is not at 0.5 L/min, proceed as below
7. Increase the pressure from 5 bar to 7 bar by turning air pressure regulator (8)
8. Check that pressure gauge (3) shows 7 bar
9. Open the purge valve (2) on the air flow controller
10. After purging, reduce the air pressure back to the normal working pressure 5 bar

18
SML 1000D Operation Manual 1.0

What if purging does not open the measuring pipe in the tank?

This is a very rare situation, which we have not observed during our 20 years of experience from electro-
pneumatic tank level gauging on some 3500 ships.

For such a problem, we propose to remove the non-return valve at the tank top or the tank side and to
insert into the measuring pipe a steel wire long enough to reach the bottom. Pulling and pushing this
steel wire up and down should remove any dried mud or similar in the measuring pipe.

After this manual wire cleaning, connect the non-return valve and check that the air flow indicator ball is
at 0,5L/min. Additional purging may be needed to remove remaining loose sediments in the measuring
pipe.

2.6.4 Manifold
As standard, 10 air flow controllers can be connected to one manifold. It is also possible to install fewer
air flow controllers to the manifold. Then a block plate should be mounted to cover the unused flow
controller positions.

19
SML 1000D Operation Manual 1.0

1. Hole of position pin


2. Threads for tighten upper and lower part each other
3. Penetration hole for constant air flow, which is connected to a flow control valve and is
sealed by O-ring
4. Penetration hole for air purging line and seal between two parts by O-ring
5. Air flow controller
6. Manifold block

2.7 Air Dryer Unit


The instrument air from the air receiver should be dry and clean. However, experience shows that this is
not always the case onboard, especially not for older ships where the compressors may leak oil into the
instrument air.

Consequently, Scanjet Macron always includes an air dryer unit in the standard SML 1000D system
scope of supply.

The air dryer unit is always mounted outside the cabinet(s).The air dryer unit consists of a shut-off valve,
an air filter, a fiber dryer, and an air pressure regulator as standard supply. An oil mist filter can be added
(option), which is installed between the air filter and the fiber dryer as shown below.

The air pressure regulator reduces the supply instrument air pressure from about 7 bars down to 5 bars
for steady air flow.

The drainage from air filter is not automatic. Section 2.7.1 shows how to drain the filter manually.

How often manual draining should be done depends on the air quality from air receiver, and must be
considered based on experience gained onboard.

20
SML 1000D Operation Manual 1.0

Air Dryer Unit Complete ( An oil mist is an optional )

Ball Valve Filter Oil Mist Fiber Dryer Regulator


Filter

2.7.1 Air Filter and Optional Oil Mist Filter

2 5 9
PUSH PUSH

3
6 8
4
7
10

Cleaning and Replacing Instructions

The bowl (4) should be removed for cleaning and replacing the filter element according to following
procedure:

1. Close the supply air with the shut-off valve in order to eliminate the existing pressure in the bowl
2. Make sure that the mark “▲” (2) on the lever of locker and the mark “▼” (1) on the body.
3. Turn the bowl (4) while pushing the locker lever (3) in arrow (5) direction (counterclockwise) until a
mark (2) sets to another mark (1)
4. Pull the bowl (4) downward in (6) direction
5. If the bowl needs cleaning, please use a neutral detergent. No alcohol or thinner should be used!
6. The filter element needs to be cleaned or replaced if the supply instrument air pressure drop is
equal to or more than 0.07 MPa.
7. After cleaning or replacing the filter element, the bowl (4) must be assembled by reversing the
above procedure.

There are three different types of filters, which can be used depending on the supply air quality.

21
SML 1000D Operation Manual 1.0

Pressure drop
Name Filtration capacity Scope of supply
≥ 0.07 MPa
Re-usable after
Air filter 5 µm As standard
cleaning
Mist filter 0.3 µm To be replaced Optional
Micro-mist filter 0.01 µm To be replaced Optional

Draining
Push the cock (7) in the bottom of the filter manually towards left and filter is drained as shown in (10).
After draining is finished, the cock (7) must be pushed towards right (original position).
Please refer to the commissioning and service manual for how to replace the filter element.

2.7.2 Air Fiber Dryer

The compressed humid air enters the air fiber dryer, and flows into the hollow tube in the casing of the
fiber air dryer.

Operating Instructions
1. On the top of the unit, there is an adjusting dial (1) for adjusting the purging air rate, which be set
from 1 (low) to 3 (max).
2. The flow rate capacity is 80 L/min with dial set at 1. This means that one fiber dryer unit is enough
for 60 measuring points at the same tank.

22
SML 1000D Operation Manual 1.0

2.7.3 Air Flow Pressure Regulator

Operating Regulator

4 3

5
1

The air flow pressure regulator set to 0.5 MPa when the SML 1000D system is delivered and
commissioned.

Adjusting the Supply Air Pressure

There is no need to adjust the supply air pressure except in case of purging with 5 bar is not enough to
clean the clogged measuring pipe.

To use full 7 bar supply air pressure for purging do following:


1. The pressure gauge (2) shows the present air pressure and this pressure can be changed by
turning the adjusting knob (1).
2. Unlock the knob by pulling up (3) before turning.
3. The pressure increases by turning the knob clockwise, and drops when turning
counterclockwise.
4. After adjusting, lock the knob by pushing it down again.

2.8 Pneumatic 1:1 Converter


To measure the hydrostatic pressure in tanks where air bubbling is prohibited, such as fresh water tanks
and potable water tanks, the pneumatic 1:1 pressure converter can be used.

The pneumatic 1:1 pressure converter is installed outside the tank as low as possible to tank bottom. It
is connected to the cabinet with one measuring pipe and with a pipe to free air.

Before installation of the pneumatic 1:1 pressure converter, the measuring pipe must be blown clean by
using compressed air to remove any dust/dirt inside of pipe before connecting the line to the converter.

If there is dust/dirt on the membrane surface in the converter, it will not show accurate measuring results.

The pressure converter must be stored indoors well protected from dust and moisture before installing
onboard the ship.

23
SML 1000D Operation Manual 1.0

Note! There are three connections (A, B, and C) in front of the converter as shown in the figure above.

The air pipe from the SML 1000D cabinet is connected to A. Connection B (air vent) breathes freely into
the atmospheric air. The connection “C” should be plugged if there is no local pneumatic level indicator.

2.9 Sensors
The tank fluid creates a hydrostatic counter pressure against the air flowing out from the measuring pipe
end inside the tank. The draft sensors measure the hydrostatic counter pressure measured from the sea
level down to the location of the draft measuring point.

The hydrostatic pressure acts on the silicon pressure sensor, which has an overload capacity of 3 times
full scale. Every gauge sensor has ion implanted piezoresistive strain gauges in a Wheatstone bridge
configuration using micromachining techniques.

The piezoresistive sensor registers the hydrostatic pressure as a resistance change, which is then
converted into a voltage from 0-100mV corresponding to the actual hydrostatic pressure. This voltage is
amplified by the sensor card to an output signal of 0.4V to 3.6V (or 4-20 mA for analog version) and is
compensated for offset, sensitivity, temperature drift and nonlinearity.

The piezoresistive sensor is more accurate and less susceptible to zero setting drift etc. than a
piezoelectric sensor. The piezoresistive sensor in SML 1000D is also temperature compensated for 0O C
to + 60OC contributing to improved performance.

24
SML 1000D Operation Manual 1.0

Piezoresistive pressure sensor with signal amplification

Selecting the sensor measuring range

The SML 1000D has two measuring ranges for the tank and draft sensors. The sensor range is selected
based on the actual height of each tank and the ship’s draft as obtained from the tank tables.

NOTE! Please make sure you select correct sensor range for each tank and draft measuring
sensor if you need to replace a defect sensor!

Selecting a sensor with big measuring range for a low tank will result in less accurate measurement of
the hydrostatic pressure inside the tank, and consequently the calculated tank level displayed will not be
as accurate when compared with a sensor with small range.

Selecting a sensor with small measuring range for a deep tank will result in wrong measurement for
pressures at higher tank levels, i.e. for levels above the sensor range.

Different sensor types and maximum sensor measuring ranges for SML 1000D

Name Pressure Range Applicable tanks


GSB 30 0 – 21.092 mH2O, gauge Except pressurized tank
GSB 50 0 – 35.153 mH2O, gauge Except pressurized tank
ASB 30 0 – 21.092 mH2O, absolute All of tanks
ASB 50 0 – 35.153 mH2O, absolute All of tanks

2.9.1 Gauge Pressure Sensors


The gauge pressure sensor measures relative pressure, i.e. the actual hydrostatic pressure in the
unpressurized tank directly, because the gauge sensor is self-breathing.

Self-breathing means that the atmospheric air pressure at the location of the cabinet acts on the other
side of the membrane, and the tank pressure, which consists of the hydrostatic pressure and the
atmospheric air pressure on the weather deck on the other.

25
SML 1000D Operation Manual 1.0

As the local air pressure in the cabinet and the air pressure on the weather deck are in most cases
almost the same, the measured tank pressure is equal to the hydrostatic pressure.

In case the cabinet is located in an area with strong local air pressure variations, such as on car decks
with heavy fans starting and stopping resulting in air pressure variations, also the air pressure
differences must be considered, when calculating the tank levels.

The gauge sensor is mounted on a PCB card with adjusters for zero setting and span.

There are two connections on the sensor card; - one is the electric cable connection on the sensor card
and another is pneumatic urethane color tube connection, which is directly connected to the gauge
sensor itself as well as to the air flow controller.

1
Gnd Sig +24V Gnd Sig +24V

2
Zero Zero

3
Span Span
4
5
6
7
8 9

Gauge sensor card components

Item no Description
1 Terminal Block (Single level and Clamping yoke connection)
2 Zero adjuster
3 Span adjuster
4 Piezoresistive sensor
5 Tube for connection, the pneumatic tube will be connected to this
6 Reference for gauge sensor
If sensor is absolute type, there is no reference hole. It just blind
7 Printed circuit board
8 The PCB supporter will be mounted on the hole to install acrylic plate
9 Black acrylic plate cover.

Two pressure sensors cards are mounted on one UM profile, which is mounted on a DIN rail at the back
of the flow controller manifold rack, making access after turning the flow controller rack 90O or more
forward.

Each flow rack contains up to 5 UM profiles with a total of 10 sensors, and a maximum of three racks fits
in a cabinet.

Using a UM profile with two sensors means that not everything needs to be opened and disconnected
for replacing a defect or malfunctioning sensor, but only that UM profile containing the sensor that needs
to be replaced. This is user friendly and saves time.

The tank level and draft sensor cards can be replaced one by one, and are fully interchangeable without
any need for calibration or other adjustments, provided that the measuring range of the sensor is the
same.

The two sensors on the UM profile are protected by an acrylic plate on top of the sensor card.

26
SML 1000D Operation Manual 1.0

The pressure sensors zero setting & span can be adjusted without removing the acrylic plate cover.

Calculating Tank Levels from Sensor Voltage

All sensor cables are connected to the TB 30 (Terminal Board). The electric signals are transferred to
MCU302 (main Control Processor Unit) with 0.4V to 3.6V that will be in proportion to the hydrostatic
pressure in the tanks and for the drafts.

For sensor cable wiring connection between terminal block (item 1), and terminal board (TB30), please
see section 2.9.2.

The voltage output range after amplification is from 0.4V to 3.6V, and values can be measured on the
terminal board for each channel by digital multi-meter.

The obtained voltage value can be converted to tank level as an approximately value.

Example: It is simple to convert voltage to level mH2O as shown below.


0.4V = 0 mH2O for zero setting
3.6V = 21.092 mH2O (2068.4 mbar) for maximum if GSB 30/ASB 30 sensor is connected
Tank offset = 0.1m
Density = 1025 kg/m3
If the value given is 2.56 VDC
In this example, “X” denotes the converted level from voltage
X = ((2.56 – 0.4) / 3.2) * 21.092 mH2O = ((14.237 mH2O / 1025))*1000 + 0.1 m = 13.99 m
(air flow pipe resistance value is not considered)
When GSB 50/ASB 50 sensor is connected with the same parameters, the results is
X = ((2.56 – 0.4) / 3.2) * 35.153 mH2O = ((23.728 mH2O / 1025))*1000 + 0.1 m =23.25 m
If we use mbar instead of mH2O, we should use conversion factor to change from mbar to mH2O.
(Density = 1025 kg/m3 is equal to 1.025 t/m3)

2.9.2 Absolute Pressure Sensors


The absolute pressure sensor measures pressure, i.e. the actual hydrostatic pressure in the tank
including the atmospheric air pressure acting in the tank.

The absolute pressure sensor is not self-breathing but has a vacuum on the other side of the pressure
sensor membrane.

If absolute pressure sensors are used the system for unpressurized tank level gauging instead of gauge
pressure sensors, then it is necessary to install one absolute pressure sensor on weather deck for
atmospheric reference air pressure measuring.

This means that the atmospheric air pressure on the weather deck acting in the tank must be subtracted
from the measured tank pressure in order to obtain the correct tank level values.

In Scanjet Macron SML 1000D, absolute pressure sensors are used for:
a) atmospheric reference air pressure measurements
b) electro-pneumatic tank level measurements for pressurized tanks

A. Atmospheric air pressure reference measuring

For SML 1000D, which has gauge sensors for measuring levels in unpressurized tanks and drafts, two
absolute sensors may be included inside the cabinet in order to compensate for atmospheric air
pressure variations in case the cabinet(s) is installed in an area with possibly strong local air pressure
variations, such as on car deck(s) or in engine room.

For atmospheric air pressure compensation, one absolute sensor is installed for measuring the on
weather deck air pressure, and the other for measuring the local atmospheric air pressure inside the
cabinet (because the gauge sensors use this local atmospheric air pressure as reference for the gauge
sensor relative pressure.

27
SML 1000D Operation Manual 1.0

If the cabinet is located in an area with no pressure variations, then ATM reference pressure
compensation is not necessary, and the absolute pressure sensors need not be installed.

Note! Atmospheric reference pressure measuring pipe on deck and inside cabinet

Particular care should be given the installation of the atmospheric reference measuring pipe on deck.
Our experience shows that moisture can accumulate in this pipe if there are any bends, and this will
result in erroneous random tank levels as the measured reference pressure will not be correct.

The atmospheric air pipe end of the on deck should be bent downwards to avoid any ingress of water.
An absolute pressure sensor inside the cabinet does not require any tube connection, because it
measures the air pressure inside the cabinet.

B. Electro-pneumatic tank level measuring for pressurized tanks

Measuring the tank level in pressurized tanks is only possible by using two absolute pressure sensors
for the same tank.

One of the absolute sensors measure the hydrostatic pressure of the actual fluid level by blowing air into
the tank through a measuring pipe extending down as far as possible inside the tank, with the pipe
distance from the bottom to be used as offset. Basically, in the same way as for unpressurized tanks, but
with absolute sensor instead.

The other absolute sensor measures the ullage (space in tank above the fluid) air pressure. The
measuring air pipe can be quite short so that also the ullage pressure at high filling level is measured.

The hydrostatic pressure and ullage pressure act on the absolute pressure sensor located in the cabinet.
The ullage pressure is measured with the other absolute pressure sensor, and the pressure difference
between the two sensors in the same tank give the actual hydrostatic pressure and hence the tank level
can be calculated.

The absolute tank pressure sensors are located inside the SML 1000D cabinet in same manner as the
gauge pressure sensors.

There are no limitations in combining gauge and absolute sensor measurements in the same cabinet
and system. It is only the sensor that is different, the tank pressure signals are processed in same way.

Except of course, if atmospheric air pressure variation requires that the gauge pressure sensors are
compensated. As explained above, pressurized tanks do not need any atmospheric pressure
compensation.

The Scanjet Macron TLG system should be protected from ullage inert gas and other harmful gases by
quick close valve or similar.

The absolute pressure sensor cards are similar to the gauge pressure cards. The only difference is that
the absolute pressure sensor does not have a breathing hole, because it has vacuum on the other side
of the membrane.

28
SML 1000D Operation Manual 1.0

Pressurized cargo tank for measuring line connection example drawing

One or two absolute pressure sensor cards are mounted in a UM profile on a DIN rail.

All absolute pressure sensor cables are connected to a TB 30 (Terminal board), and the electric signals
are transferred to the MCU 302 (Main control processor unit) for ATM reference pressure compensation

The two absolute sensors for atmospheric pressure measuring should not be connected to other
channels.

If there are only 10 measuring points in the cabinet, then a smaller terminal board TB 16 can be supplied
to which up to 14 sensors can be connected and with 2 channels available for ATM pressure sensor as
Ch15 and Ch16.

29
SML 1000D Operation Manual 1.0

3 Electronic Units
Below is an overview of all major electronic components, which are located on the inside of the tank
level gauging cabinet door.

The pressure sensors and pressure switch are not mounted on the door, but to the right in the cabinet.
See number explanation in the table on next page.

1 2 3 3 2
4 5 6 -

7 8 9 

0   

12 21
13
11 14
10
9

5 22
16 15
17 20

DC24V Analog output 4~20mA


16chnnels in 1 unit
8 7 19
18 3.TB30 (Terminal Board)
Main powersupply
AC 100~240V

Flow controllers
and sensors

30
SML 1000D Operation Manual 1.0

This section contains brief functional description of the main electronic components of the SML1000D
cabinet.

The system consists of the following electronic PCB:


 Main control processor unit (MCU302)
 Digital analog convert unit (DAU16) as option
 Service display unit (SDU30c) for SML 1000D fully digital model
 Gauge pressure sensor card (GSB30 for 0.2MPa range, GSB50 for 0.35MPa range)
 Absolute pressure sensor card (ASB30 for 0.2MPa range, ASB50 for 0.35MPa range)

The system can give 4~20mA analog signal to connected analog pointer instruments with re-scalable
function by DAU16 card, which can be supplied as option.

List of the electronic components

Item Description
no
1 Character- LCD, 4 lines x 20 characters
2 LEDs for Power supply, Alarm Status and Communication Status
3 Keys for service display unit operation
4 Ribbon cable with 2x20 - pin connector
5 Ribbon cable with 2x25 - pin connector
6 Ribbon cable with 2x10 - pin connector
7 Absolute Sensor, 2 sensors are connected to TB30 for 1 cabinet
8 Gauge Sensor for tank measurement, Up to 30 sensors
9 Terminal Block (Triple level and Clamping yoke connection), 32 sets
10 Socket, 2x25 – pin on TB30
11 Socket, 2x25 – pin on MCU302
12 Socket, 2x20 – pin on MCU302
13 Socket, 2x10 – pin on MCU302 for DAU16 unit_2 connection
14 Socket, 2x10 – pin on MCU302 for DAU16 unit_1 connection
15 Terminal Block (Single level and Clamping yoke connection)
Power supply connection
16 Terminal Block (Single level and Clamping yoke connection)
2-Communication connection
17 Terminal Block (Single level and Clamping yoke connection)
3- Relay output to external PC and 1- Relay input from pressure switch
18 Pressure switch for low pressure alarm, Activate less than 3 bar
19 Power Supply Unit (Input: VAC 100~240 and output: VDC 24, 3A)
20 Terminal Block (Single level and Clamping yoke connection)
The connected yard cables should be transferred current signals to analog pointer
instruments or any possible current I/O module
21 Socket, 2x10 – pin on DAU16
22 Re scale card, 2 channels in 1 card
8 cards could be connected with 1 DAU16 unit for 16 analog output

31
SML 1000D Operation Manual 1.0

3.1 MCU302 (Main Control Processor Unit)


The main control processor unit can be mounted either on the inside of the cabinet door, or flush
mounted on outside the door.
The MCU302 unit provides following output signals to the system and to external systems like ship
automation and loading computer.
 2 x RS-485 Communication Port, Modbus RTU for communication with loading computer and
ship automation system
 3 x Alarm relay output for external alarm activation
 1 x Relay input for pressure switch from air supply low pressure alarm (0,3 MPa)
 1 x Digital input for low pressure inlet alarm as NC, activated at 0,3 MPa pressure
 1 x Address setting DIP switch(SW1), it can be set up to 15
 Up to 15 cabinets can be connected in parallel with same RS-485, a total of 450 measuring
points can be operated in one system. If one system has 15 cabinets with 30 sensors in each,
then updating time for new level is approximately 60 seconds
 LED lamp power is +5V and +24V
The MCU302 unit has 4 terminal sockets for ribbon cable communication with components, terminal
board, service display unit, and DAU 16 units.
 2 x Terminal sockets (J103-1 & J103-2) with 20 pins for DAU16 connection
 1 x Terminal socket (J102) with 40 pins for SDU30c connection
 1 x Terminal socket (J101) with 50 pins for TB 30, Purpose: sensor cable connection
The MCU302 unit has 20 terminal blocks at the bottom of board
 Terminal block number, X100, DC24V power supply connection
 Terminal block number, X120, 2- Serial Communication Port for external system
 Terminal block number, X140, 3 relay-output for external alarm and Low Pressure alarm
indication on the SDU30c
The electrical connection drawing is provided separately in the TLG system working drawings.

32
SML 1000D Operation Manual 1.0

The below abbreviations are indicated on the PCB of MCU302 and describe what functions/meanings
are having.

Abbreviation:

LD 1; Green Color LED, It will activate when DC24V power is connected


LD 2; Green Color LED, It will activate when converted from DC24V to safe power DC5V
J3; 6 pin connector for program downloads. This is only used by service engineers.
SW 1; Cabinet address setting switch
SW 2; Reset key, This key can be used for re-loading data such as the latest setting values
 If key SW 2 is pressed, the system has to be restarted by switching main power off/on
RY1; Relay for Common alarm as normally close contact
RY2; Relay for Power Fail alarm as normally close contact
RY3; Relay for System Failure (=Sensor Failure) alarm as normally close contact

When more than 2 cabinets are connected, the SW 1 of each cabinet must have different settings and
should be the same as the cabinet number, which is shown on the name plate on the door.

The program will display the cabinet number on the LCD when the display starts up. More information is
provided later in this manual.

The switch SW 1 is located on the top of the MCU302 main board. The switch has four selectors as
shown below.

Up to 15 cabinets can be parallel connected to same RS485, with a total 450 measuring points
SW1
Cabinet
address 1(20=1) 2(21=2) 3(22=4) 4(23=8)
1 ON OFF OFF OFF
2 OFF ON OFF OFF
3 ON ON OFF OFF
4 OFF OFF ON OFF
5 ON OFF ON OFF
6 OFF ON ON OFF
7 ON ON ON OFF
8 OFF OFF OFF ON
9 ON OFF OFF ON
10 OFF ON OFF ON
11 ON ON OFF ON
12 OFF OFF ON ON
13 ON OFF ON ON
14 OFF ON ON ON
15 ON ON ON ON

33
SML 1000D Operation Manual 1.0

3.2 SDU30c (Service Display Unit)


The MCU302 incorporates a liquid crystal display (LCD) as service display unit.
The SDU30c consists of a Liquid Crystal Display (LCD), 19 key press buttons, several LED lamps such
as for Rx/Tx communication, Fault Alarm and Power On.
 To access the menu on the LCD, the user must press the ESC key.
This provides visual access to all the data required to operate the system and displays the tank
measuring data and other input setting values.

The screen will not show any characters if no key is pressed for 20 minutes.

LED’s in front of the display unit


 Power On MCU302 power supply +24V; Green and +5V; Green
 Alarm Alarms are activated. System Fail; Red Low Pressure; Red
 RS485A Communicating status with external PC 1,
Rx: Received (Green), Tx: Transmitted (Yellow)
 RS485B Communicating status with external PC 2,
Rx: Received (Green), Tx: Transmitted (Yellow)

A. FRONT PANEL WITH LCD OF SDU 30C

1 2 3

4 5 6 -

7 8 9 

0   

34
SML 1000D Operation Manual 1.0

B. PRINTED CIRCUIT BOARD FOR SDU 30C

The SDU30c PCB terminal name and component abbreviations:


 J102; Terminal Socket with 40-pins. Should be connected to MCU302 J102 by ribbon cable
 J203; Terminal Socket for LCD power supply and data transmission
 J204; LCD back light On/Off signal
 J201; 6-pins connector for LCD program download. It is only used by service engineer with
programming kit
 LD1; Power on green LED for DC 24V supply
 LD2; Power on green LED for DC 5V supply
 LD3; Alarm indication red LED for system failure or sensor failure
 LD4; Alarm indication red LED for low pressure supply, less than 3.0 bar
 LD5; Received signal green LED for communication port 1, RS485 A
 LD6; Transmitted signal yellow LED for communication port 1, RS485 A
 LD7; Received signal green LED for communication port 2, RS485 B
 LD8; Transmitted signal yellow LED for communication port 2, RS485 B
 R17; Adjustable screw for brightness of LCD

3.3 Terminal Board for Sensor Connection


The 3-wire sensor cables are connected to the terminal board (TB30), and a ribbon cable with 50 pins
male connector is connected with a socket (J101).

The selectable switch each of channels as on/off that is located at the middle of the terminal board and
thus it must be used when the sensor is replaced.

There are DIP switches for connecting/disconnecting power to the sensor in order to protect the sensors
from electric shock when replacing a defect sensor.

If a sensor is to be replaced, the DIP switch has to be in OFF position without switching off the main
power supply.

There are four DIP switches mounted on the SW1 board, and one DIP switch has 8 channels

35
SML 1000D Operation Manual 1.0

SW 1: Channel 1 ~ 8
SW 2: Channel 9 ~ 18
SW 3: Channel 19 ~ 24
SW 4: Channel 25 ~ 30 and including ATM sensor as 31 and 32 channel

The cable wire connection on between sensor card terminal and terminal board TB30 is shown below.

36
SML 1000D Operation Manual 1.0

In case TB16 (Terminal Board 16) is mounted in cabinet, the DIP switch is available with 14 measuring
points and 2 switches are used for ATM pressure sensor .

SW 1: Channel 1 ~ 8
SW 2: Channel 9 ~14 and including ATM sensor as 15 and 16 channel

Note! UM Profile
Individual adaptation of the UM profile to PCB dimensions means that electronics circuits can be made
rail mountable.
Generally, the UM profile in SML 1000D has 2 pressure sensor cards and a black acrylic protection plate.
The cables between sensor card and TB30 are pair twisted 6 shielded different sheath color wires.

3.4 Digital to Analog Converter (DAU16) – Optional


The digital to analog converter card DAU16 can be supplied with the SML 1000D in case local analog
pointer instruments are installed to show tank levels and/or volumes.

The SML 1000D system cabinet can contain 2 x DAU16 for max. 30 analog outputs. Only one DAU16
can be installed if no more than 15 analog outputs are needed.

Eight RSC21 re-scaling cards can be installed in a DAU16 unit and each card has 2 channels with
individually adjustable zero and span as shown below.

37
SML 1000D Operation Manual 1.0

X340

RSC21

J103
LD1 LD2

The connector (2) on RSC21 card is connected with DAU 16 main board, and the terminal socket J103
can be connected to either J103-1 or J103-2 on the MCU302 board.

In case 2 x DAU16 units are included in the system, then one of the two is connected to J103-1 and will
be taken care of the analog outputs from channel 01 to 16, and the other DAU16 unit connected to
J103-2 terminal socket on the MCU302 that will work for channels (17 to 30).

There are two green LEDs for DC 24V and DC 5V power supply respectively on the left bottom corner of
DAU16 main board. These are marked as LD1 and LD2.

Following example shows connection between Channel 1 of X340 terminal block on DAU 16 board, and
analog pointer instrument as loop powered connection.

See Commissioning and Service Manual for detailed description on how to adjust zero and span if
necessary.

On the drawing example shown below, terminal block X340 is located on the DAU16 main board and all
of yard cables should be connected directly to X340 terminal block according to electric cable
connection drawing.

38
SML 1000D Operation Manual 1.0

X340
C1 N

On local display console

loop powered connection

0V

(+) DC24V

Analog pointer instrument

The DAU16 can be used with external display as loop powered connection.

Note! The cables to the analog pointer instrument should not be installed close to high current cables or
other disturbing equipment.

The DAU 16 unit can be connected to both analog pointer instruments and digital display units.

In general, the minimum tank level or height for pointer instrument scale is 4 mA, and the maximum as
20mA.

Please see the Commissioning and Service manual, section 3 for menu program for scaling measures.

3.4.1 Supply Air Pressure Switch


A supply air pressure switch is installed in the cabinet, and closes the supply air pipe in case the supply
air pressure drops below appr. 0,3 MPa. An alarm is given to the automation system low supply air
pressure. The alarm is also shown in the LCD.

When air pressure is restored to 0,3 MPa, the switch opens automatically and the alarm is deactivated.
The contact switch is normally closed.

The alarm point can be adjusted with the alarm push-lock knob.

The pressure switch cable for low pressure alarm activation can be directly connected to either the main
board (MCU302), or to an external I/O module.

If the cable is connected to an external system directly, an alarm will not be shown in the SML 1000D
system.

39
SML 1000D Operation Manual 1.0

NC Black Adjusting Knob


Common Brown
NO Blue

Pressure Switch

"a"

Adapter

Pressure Calibrator

The relay on the MCU302 will activate as normally closed contact (Brown – Black) and as shown above,
the pressure calibrator should be connected to pressure switch air inlet instead of original pneumatic line
when adjusting the switch.

In order to get a new alarm point, a digital multi-meter and pressure calibrator should be connected to
pressure switch, and make sure that air stop valve on air dryer unit is closed before doing connection.

When turn adjusting knob clockwise direction, a new set alarm point will higher than before, and when
turning the other way (counterclockwise), it will be lower.

The adjusting knob should be locked by pushing it down after the new setting is completed and all
disconnected parts should be reconnected.

3.4.2 Power Supply Unit (SNT 30)


A compact single-phase switched-mode power supply module is mounted inside the cabinet. This power
supply module complies with all mandatory national and international standards and approvals.

The power supply unit consists of a transformer for alternating voltage into different direct voltage of any
value. A rectifier circuit is used to convert a secondary alternating voltage into a pulsating direct voltage,
which is then smoothed by means of a filter circuit.
A detailed technical description is given in the Functional & Technical Description Manual.

40
SML 1000D Operation Manual 1.0

C
NC NO
Power Supply Unit
Input: 100-240VAC 50/60Hz 2.0-1.0A
121114 +V +V-V -V
Output: 24VDC 3.0A
Model: CP SNT 70W 24V 3A

Adjustable Screw from DC24V to DC28V

L N PE

Front view of the unit Top view of the unit

Note! The ground cable should be grounded to the ship’s hull and the terminal (12, 11 and 14) can be
used for relay output.

There is screw on the center of power unit top for adjusting the power DC output, varying from DC24V to
DC28V.

4. User Manual for Service Display Unit Operation


This section shows how to operate and use “DISPLAY” and “SERVICE” menu on the SDU 30c unit.

Key definitions

Enter After selecting a tank by using Left & Right arrow keys, press “Enter” to
show values

ESC To cancel the present display

For Next tank selection

For Previous tank selection

41
SML 1000D Operation Manual 1.0

4.1 Starting up the Service Display Unit SDU30c


Every time the service display unit is started, the following window is shown for initializing the system.

A
Initializing the SDU30c
SML 1000 D
The screen will automatically change
----- from A to B after initializing for 5 seconds
2009.12.05
Scanjet Macron

B
Cabinet Number
01
Enter: Go
Select NO: 1, 2

Text explanation for A & B screens

On the “A” screen


 SML 1000 D: Model name of system
 ----- : Initializing the system for 5 seconds
 2009.12.05: Delivery date from factory
 Scanjet Macron: Company name

On the “B” screen


 01 : Cabinet address is showing automatically, depends on SW1 setting
on MCU302 board
 Enter: Go : If press “Enter” key, the display will show only cabinet 1
 Select NO: 1, 2 : The figures 1 & 2 means that two cabinets were delivered

If there are three cabinets in the system, the figures 1,2 and 3 will be shown.

If there is just one cabinet, it will also show “Select cabinet number 1”.

4.1.1 Single Cabinet in a System


When the system is delivered with only one cabinet, it is not allowed to select another cabinet.

This section shows the windows to select either display mode or service mode after initializing for 5
seconds

The display mode has 6 different menus showing the measuring results (pressures and calculated levels)
and the tank data (offset and pipe flow resistance) saved for each sensor in the memory.

The service mode has 3 menus to calibrate the sensor and to give a new value for tank data such as
density, tank offset and analog output scaling.

42
SML 1000D Operation Manual 1.0

SML 1000 D
----- 5 Sec
2009.12.05 Cabinet Number
Scanjet Macron 01
Enter: Go

ESC Enter
Display
Select

Display or Service
Service
ESC: Back
ESC

Display Menu Service Menu


1. Level H 2. Density Password
3. Offset 4. Sensor
5. Pressure 6. Pr Enter:Go ESC:Back

Password xxxx,

Enter

ESC
Refer to section 4.2.1 for next display Service Menu
1. Calibration
2. Setting
3. Pr

Refer to section 4.3.1 for next display

43
SML 1000D Operation Manual 1.0

4.1.2 Number of Cabinets in a SML 1000D System


When the system is delivered with two cabinets or more, the operator can select the cabinet number(s)
and the measuring results for all cabinets.
In case the cabinet number “02” is selected from cabinet “01”, the service menu is not available but the
display menu will be shown for cabinet number “02”.

5 Sec
SML 1000 D
-----
2009.12.05
Scanjet Macron

Cabinet Number Cabinet Number


2
02 01
Enter: Go Enter: Go
Select NO: 1, 2 Select NO: 1, 2

Enter ESC Enter ESC

Display Menu Select


1. Level H 2. Density
3. Offset 4. Sensor Display or Service
5. Pressure 6. Pr ESC: Back

Refer to section 4.2.1 for next display Select either Display or Service

Up to 15 cabinets can be connected in parallel to same RS-485 by MODBUS RTU mode protocol. A
total of 450 measuring points can be viewed and operated in one system.

44
SML 1000D Operation Manual 1.0

4.2 Display Mode


If it is necessary to calibrate sensors and to change density and tank offset, the user must switch to the
“Service mode”, and enter service password (Default is 1234).

After initializing and pressing “Display” key, the display will show the tank level height results and saved
data such as density, pipe end offset, and pipe flow resistance values for every connected sensor and
measuring pipe.

There are 6 options in the main display menu, and the following description shows the features of each
menu.

1. Level Height (Refer to section 2.4 and 2.5 Calculations)


The display shows the calculated tank level height, corrected for tank offset, pipe resistance and
density.

2. Density
The display shows the density of liquid as the latest input. Changing density can be done in the
Service menu. The density can also be changed in the loading computer and in the automation
system. This density overruns then density set in the cabinet. The density can also be changed in
the Service menu.

3. Offset : Tank Pipe Offset


The display shows the pipe offset in the tank. The offset can be changed in the Service menu.
The pipe offset is the distance measured from bottom of tank to upper end of the sniped measuring
pipe in the tank. The offset is recorded and saved for every tank during installation / commissioning.

4. Sensor
The display shows the sensor status either OK or E
“OK” means everything is good condition
“E” means ERROR. If sensor has “E” on the status of sensor, the sensor cannot measure the
pressure and all of measuring results are not displayed.
What to do when Sensor shows status “E”?
 Check first the condition of sensor
 Then decide to replace the sensor or not

5. Pressure
The display shows the pressure value in mbar if sensor is OK.
If the sensor is not working properly, it will display only “E

6. Pr: Pipe Flow Resistance


The display shows the pipe flow resistance which has been measured when the tank was empty.

45
SML 1000D Operation Manual 1.0

4.2.1 Display Menu, Sheet 1


Press the key “Display” on the panel

Display Menu Level Height


1. Level H 2. Density 1 Channel: 01 Status: OK See Sheet 2
3. Offset 4. Sensor << Prev Next >> A
5. Pressure 6. Pr Enter:Go ESC

2 Density Value kg/m3


Channel: 01 Status: OK See Sheet 3
<< Prev Next >>
Enter:Go ESC
B

3 Tank Offset (m)


Channel: 01 Status: OK See Sheet 4
<< Prev Next >> C
Enter:Go ESC

Sensor Status
4
Channel: 01 Status: OK See Sheet 5
<< Prev Next >>
Enter:Go ESC
D

5 Pressure (mbar)
Channel: 01 Status: OK See Sheet 6
<< Prev Next >> E
Enter:Go ESC

6 Pipe Flow Resistance


Channel: 01 Status: OK See Sheet 7
<< Prev Next >> F
Enter:Go ESC

The user can select the number from 1 to 6 on the Display menu
The LCD will show measuring point selection display and status of current measuring point as any of
keys are pressed.

46
SML 1000D Operation Manual 1.0

4.2.2 Fluid Level Height on Display Menu - Sheet 2


A

From Sheet 1 Level Height


Channel: 01 Status: OK
<< Prev Next >>
Enter:Go ESC

ESC

Display Menu Level Height


1. Level H 2. Density Channel: 02 Status: OK
3. Offset 4. Sensor << Prev Next >>
5. Pressure 6. Pr Enter:Go ESC

ESC

Select Level Height


Channel: 03 Status: OK
Display or Service << Prev Next >>
ESC: Back Enter:Go ESC

Enter
Display
Service
Level Height
Ch 03: 12.34 m
<< Prev Next >>
Enter:Go ESC

Display Menu
1. Level H 2. Density
3. Offset Service Menu
4. Sensor
Password
ESC Level Height
5. Pressure 6. Pipe R
xxxx Ch 30: 11.22 m
Enter:Go ESC:Back << Prev Next >>
Enter:Go ESC

The sensor measuring results can be read in this window if the sensor status is OK.
In case sensor status is “E” on the display, the measuring result also will be “E”.

By using (<<) left key or (>>) right key on the panel, the channels of measuring points can be displayed.

It is not possible to change channel number directly by entering numbers instead of using arrow keys to
select channels.

The level height is displayed in meters.

47
SML 1000D Operation Manual 1.0

4.2.3 Density on Display Menu - Sheet 3


B

From Sheet 1 Density Value kg/m3


Channel: 01 Status: OK
<< Prev Next >>
Enter:Go ESC

ESC

Display Menu Density Value kg/m3


1. Level H 2. Density Channel: 02 Status: OK
3. Offset 4. Sensor << Prev Next >>
5. Pressure 6. Pr Enter:Go ESC

ESC

Select Density Value kg/m3


Channel: 03 Status: OK
Display or Service << Prev Next >>
ESC: Back Enter:Go ESC

Enter
Display
Service
Density Value kg/m3
Ch 03: 1025 kg/ m3
<< Prev Next >>
Enter:Go ESC

Display Menu
1. Level H 2. Density
3. Offset Service Menu
4. Sensor
Password
ESC Density Value kg/m3
5. Pressure 6. Pipe R
xxxx Ch 01: 0980 kg/m3
Enter:Go ESC:Back << Prev Next >>
Enter:Go ESC

The latest saved density value is shown and the current status of sensor is displayed before pressing
“Enter” key.

In order to change density value from 0980 kg/m3 of channel 01, the service menu must be opened as
above. The density can also be changed in the loading computer and in the automation system. This
density overruns then density set in the cabinet.

48
SML 1000D Operation Manual 1.0

4.2.4 Offset on Display Menu - Sheet 4


C

From Sheet 1 Tank Offset (m)


Channel: 01 Status: OK
<< Prev Next >>
Enter:Go ESC

ESC

Display Menu Tank Offset (m)


1. Level H 2. Density Channel: 02 Status: OK
3. Offset 4. Sensor << Prev Next >>
5. Pressure 6. Pr Enter:Go ESC

ESC

Select Tank Offset (m)


Channel: 03 Status: OK
Display or Service
<< Prev Next >>
ESC: Back
Enter:Go ESC

Enter
Display
Service
Tank Offset (m)
Ch 03: 0.105 m
<< Prev Next >>
Enter:Go ESC

Display Menu
1. Level H 2. Density
3. Offset Service Menu
4. Sensor
Password
ESC Tank Offset (m)
5. Pressure 6. Pipe R
xxxx Ch 01: 0.155 m
Enter:Go ESC:Back << Prev Next >>
Enter:Go ESC

The latest saved tank offset value is shown and the current status of sensor is displayed before pressing
“Enter” key.

In order to change tank offset value from 0.105m of channel 03, the service menu must be opened as
above.

49
SML 1000D Operation Manual 1.0

4.2.5 Sensor Status on Display Menu - Sheet 5


D

From Sheet 1 Sensor Status


Channel: 01 Status: OK
<< Prev Next >>
Enter:Go ESC

ESC

Display Menu Sensor Status


1. Level H 2. Density Channel: 02 Status: OK
3. Offset 4. Sensor << Prev Next >>
5. Pressure 6. Pr Enter:Go ESC

ESC

Select Sensor Status


Channel: 03 Status: OK
Display or Service << Prev Next >>
ESC: Back Enter:Go ESC

Enter
Display
Service
03: OK 04: OK
05: OK 06: OK
07: E 08: E
<< Prev Next >>

Display Menu
1. Level H 2. Density
3. Offset Service Menu
4. Sensor
Password
09: OK 10: OK
5. Pressure 6. Pipe R
xxxx 11: OK 12: OK
Enter:Go ESC:Back 13: E 15: E
<< Prev Next >>

ESC

ESC Sensor Status


Channel: 15 Status: OK
<< Prev Next >>
Enter:Go ESC

The display shows the sensor status either “OK” or “E” for five tanks at the same time.

When press an arrow key, the display will show another new five sensors status with “OK” or “E”.

50
SML 1000D Operation Manual 1.0

4.2.6 Pressure reading on Display Menu - Sheet 6


E

From Sheet 1 Pressure (mbar)


Channel: 01 Status: OK
<< Prev Next >>
Enter:Go ESC

ESC

Display Menu Pressure (mbar)


1. Level H 2. Density Channel: 02 Status: OK
3. Offset 4. Sensor << Prev Next >>
5. Pressure 6. Pr Enter:Go ESC

ESC

Select Pressure (mbar)


Display or Service Channel: 03 Status: OK
ESC: Back
<< Prev Next >>
Enter:Go ESC

Enter
Display
Service
Pressure (mbar)
Ch 03: 100
<< Prev Next >>
Enter:Go ESC

Display Menu
1. Level H 2. Density
3. Offset Service Menu
4. Sensor
Password
Pressure (mbar)
5. Pressure 6. Pipe R
xxxx Ch 04: 200
Enter:Go ESC:Back << Prev Next >>
Enter:Go ESC

ESC

ESC Pressure (mbar)


Channel: 04 Status: OK
<< Prev Next >>
Enter:Go ESC

The pressure is displayed in mbar and another unit is not available

The indicated pressure considers flow resistance (Pr) and thus it can be used for converting the
hydrostatic pressure to level height based on 2.4.3 section conversion table.

51
SML 1000D Operation Manual 1.0

4.2.7 Pipe Flow Resistance on Display Menu, Sheet 7


Unit: mbar

Flow resistance means the air pressure loss at constant air flow in the measuring pipe. This air pressure
loss is measured in an empty tank, or equivalent condition.

During commissioning on board the vessel, it should be checked that the pipe resistance has been
recorded and stored.

Checked and measured flow resistance values can be displayed for 6 channels at the same time on the
display

F
From Sheet 1 Pipe Flow Resistance
Channel: 01 Status: OK
<< Prev Next >>
Enter:Go ESC

ESC

Display Menu Pipe Flow Resistance


1. Level H 2. Density Channel: 02 Status: OK
3. Offset 4. Sensor << Prev Next >>
5. Pressure 6. Pr Enter:Go ESC

ESC

Select Pipe Flow Resistance


Channel: 03 Status: OK
Display or Service
<< Prev Next >>
ESC: Back
Enter:Go ESC

Enter
Display
Service
03: 1.0 04: 1.2
05: 1.4 06: 2.0
07: 1.3 08: 1.5
<< Prev Next >>

Display Menu
1. Level H 2. Density
3. Offset Service Menu
4. Sensor
Password
09: 1.1 10: 1.0
5. Pressure 6. Pipe R
xxxx 11: 1.1 12: 1.0
Enter:Go ESC:Back 13: 1.1 15: 1.0
<< Prev Next >>

ESC

ESC Pipe Flow Resistance


Channel: 15 Status: OK
<< Prev Next >>
Enter:Go ESC
52
SML 1000D Operation Manual 1.0

4.3 Service Mode


The service mode is used to set and change the basic measuring settings for each sensor and
measuring pipe during commissioning.
There are 3 numbers in main service menu, and the following description shows the features of each
menu.

1. Calibration
There are two sub-menus for calibration of gauge and absolute pressure sensors. One is pressure
sensor zero point settings and the other is analog output re-scaling.
A. Pressure sensor
The zero points for pressure sensors can be adjusted if the crew has a pressure calibrator.
Before zero point calibrating, ensure that the air supply is stopped and there is no pressure in the
measuring line. The sensor should be kept to atmospheric pressure for zero calibration.
B. AO Rescaling ( Scaling for analog outputs 4-20mA )
As an option, the program can be given to analog pointer instrument as 4-20mA. These scaling
values are set depend on the device measuring range which is printed on scale plate of the device.

2. Setting
There are 3 sub-menus for this setting as below and it can be edited corresponding to specified
information
A. Tank Pipe Offset
The distance from the upper end of sniped measuring pipe to the lowest bottom of tank.
The indicating offset is displayed in meters, and the user should give a new value without decimal
when the value is entered.

B. Density
Unit is kg/m3 (SI standard) and the user should give a new value without decimal when the value is
entered.
To change density from 1000 kg/m3 to 0850 kg/m3.
There is no decimal key on the SDU30c. So, User only press key 0850.
After that 0850 kg/m3 will display on the LCD.

C. AO Simulation
This menu is used to generate current for testing analog pointer instrument if connected as option.
Then the user can verify both the analog device and giving signal

3. Pr
The flow resistance value has to be measured during commissioning and it must be done when the tank
is empty or in similar condition. This is a set value and not automatically changed.
If there is very high flow resistance in some line even if no liquid in tank, then the measuring line is most
likely clogged or bent.

53
SML 1000D Operation Manual 1.0

4.3.1 Service Menu - Sheet 1


Password is set to 1234 as default

Service Menu
Password Password

Enter:Go ESC:Back

Service Menu
1. Calibration
2. Setting
3. Pr

1 2 3

Calibration Setting Pipe Flow Resistance


Ch 01: 0.0 mbar
1. Pressure Sensor 1. Tank Offset << Prev Next >>
2. AO ReScaling 2.Density 3. AO Simul Enter:Go ESC

See Sheet 6
Pressure Sensor Cal.
F
1. Zero
ESC
1 Offset Value on See Sheet 4
Ch 01: 0.000 m
<< Prev Next >> C
Enter:Go ESC
See Sheet 2
A
2 Density Value on
See Sheet 4
Ch 01: 1025 kg/m3
<< Prev Next >> C
Enter:Go ESC

AO ReScaling
Ch 01 4-20 mA
3 AO Simulation
<< Prev Next >> See Sheet 5
Ch 01 4-20 mA
Enter:Go ESC D
<< Prev Next >>
Enter:Go ESC

See Sheet 3
B

54
SML 1000D Operation Manual 1.0

4.3.2 Calibration of Pressure Sensor- Service Menu Sheet 2


A
Pressure Sensor Cal.
From Sheet 1
1. Zero
ESC
ESC
ESC 1

Calibration Zero Calibration.

1. Pressure Sensor 1. Selected Sensor


2. AO ReScaling ESC

1 ESC
Right arrow
Zero Calibration Zero Calibration
Channel: 03 Status: OK Channel: 01 Status: OK
<< Prev Next >> << Prev Next >>
Enter:Go ESC Enter:Go ESC

Enter

Press left arrow once for Ch 02


Zero Calibration.
Zero Calibration
Calibrating….
Channel: 02 Status: OK
<< Prev Next >>
Enter:Go ESC
After 5 second

Zero Calibration.
Press left arrow 4 times for Ch 06
Done

Zero Calibration
Channel: 06 Status: OK Zero Calibration
<< Prev Next >> Channel: 02 Status: OK
Enter:Go ESC << Prev Next >>
Enter:Go ESC
Enter
Enter
Same procedure Ch 01
Same procedure Ch01

Note! When zero point is calibrated, the measuring pipe pressure should be equal to atmospheric air
pressure.

55
SML 1000D Operation Manual 1.0

4.3.3 Calibration Analog Output Rescaling- Service Menu Sheet 3


-- Optional Function
This AO Rescaling is only available when DAU16 unit is included in the system
If there are no analog pointer instruments, the AO Rescaling function will not be shown on Service
Display Unit

B
From Sheet 1 AO ReScaling
Channel: 01 4-20 mA
<< Prev Next >>
Enter:Go ESC

AO ReScaling AO ReScaling
Channel:02 4-20 mA Channel:02 4-20 mA
<< Prev Next >> << Prev Next >>
Enter:Go ESC Enter:Go ESC

ESC

AO ReScaling
Calibration Mode Channel:03 4-20 mA
1. Pressure Sensor << Prev Next >>
2. AO ReScaling Enter:Go ESC
ESC

ESC

AO ReScaling
Service Menu Channel:02 4-20 mA
1. Calibration << Prev Next >>
2. Setting Enter:Go ESC
3. Pr

Enter
ESC

Select Ch:02 AO ReScaling


Display or Service 4 mA out: xx.xxx m
20 mA out: xx.xxx m
ESC: Back Enter:Go ESC

Display Service Enter the numbers


according to scale plate

Enter Ch:02 AO ReScaling


Display Menu
1. Level H 2. Density 4 mA out: 0.1 m
3. Offset Service Menu
4. Sensor 20 mA out: 15.10 m
5. Pressure Password
6. Pipe R Enter:Go ESC
xxxx
Enter:Go ESC:Back

56
SML 1000D Operation Manual 1.0

4.3.4 Setting of Tank Offset & Density - Service Menu Sheet 4


After inserted a new value and then press ”Enter” key, the LCD will show next channel as below. So, use
left arrow key to confirm the value which is correctly inserted.

C
From Sheet 1 Setting Mode

1. Tank Offset
2. Density 3. AO Simul
1

Density value on 2 Offset value on


Ch 01: 1025 kg/m3
Ch 01: 0.000 m
<< Prev Next >>
<< Prev Next >>
Enter:Go ESC
Enter:Go ESC

Enter

Ch01 Set Density to


Default: 1025 kg/m3 Offset value on
Next: 1000 kg/m3 Ch 02: 0.000 m
Enter:Go ESC << Prev Next >>
Enter:Go ESC

1
Enter

Density value on
Ch 02: 1025 kg/m3 Ch02 Set offset to
<< Prev Next >> Default: 0.000 m
Enter:Go ESC Next: xx.xxx m
Enter:Go ESC

0 0 1
Enter

Density value on
Offset value on
Ch 01: .000 kg/m3
Ch 03: 0.000 m
<< Prev Next >>
<< Prev Next >>
Enter:Go ESC
Enter:Go ESC

ESC ESC Offset value on


Ch 02: 0.100 m
<< Prev Next >>
Enter:Go ESC

57
SML 1000D Operation Manual 1.0

4.3.5 Analog Output Simulation - Service Menu, Sheet 5 --


Optional Function
This AO simulation is only available when DAU16 unit is included in the system.
If there are no analog pointer instruments, the AO simulation function will not be shown on Service
Display Unit.

D
From Sheet 1 Setting Mode

1. Tank Offset
2. Density 3. AO Simul
3

ESC
AO Simulation
Ch 01 4-20 mA
<< Prev Next >>
Enter:Go ESC

Service Menu
1. Calibration Enter
2. Setting
3. Pr AO Simulation
Ch 01: xx.xx mA
ESC
Enter:Go ESC

Select
1 2 5 0
Enter
Display or Service
ESC: Back
AO Simulation
Ch 01: 12.50 mA
Generating
Display Service ESC

Display Menu ESC


1. Level H 2. Density
3. Offset 4. Sensor
5. Pressure 6. Pr AO Simulation
Ch 01 4-20 mA
<< Prev Next >>
Service Menu Enter:Go ESC
Password
xxxx
Enter:Go ESC:Back

ESC
AO Simulation
Ch 30 4-20 mA
<< Prev Next >>
Enter:Go ESC

58
SML 1000D Operation Manual 1.0

4.3.6 Flow Resistance - Service Menu Sheet 6


Unit: mbar

There should be no liquid in the tank when measuring Pr value.

Alternatively disconnect the measuring pipe at the non-return valve, and measure pipe resistance from
the cabinet to the tank top or tank side at the pipe end.
If measured result is very higher than others, it should be checked and corrected

F
From Sheet 1 Service Menu
1. Calibration
2. Setting
3. Pr
3

Pipe Flow Resistance

Ch 01: 0.0 mbar


ESC << Prev Next >>
Enter:Go ESC

Enter

Pipe Flow Resistance


Measuring

Enter:Go ESC
Select

Display or Service
ESC: Back
Pipe Flow Resistance
Done

Display Service Enter:Go ESC

Display Menu
1. Level H 2. Density After measured
3. Offset 4. Sensor
5. Pressure 6. Pr Pipe Flow Resistance
Ch 01: 1.3mbar
<< Prev Next >>
Service Menu Enter:Go ESC
Password

Enter:Go ESC:Back

ESC Pipe Flow Resistance


Ch 30: 0.0 mbar
<< Prev Next >>
Enter:Go ESC

59
SML 1000D Installation Manual 1.2

ELECTRO-PNEUMATIC TANK LEVEL GAUGING


AND DRAFT MEASURING SYSTEM

INSTALLATION MANUAL
MODEL: SML 1000D
March 2010
Scanjet Macron International Ltd.
Kornetintie 10, 3rd floor, FI-00380 Helsinki, Finland
Tel: +358 20 711 8210 Fax: +358 20 711 8219
email: info@scanjet.fi www.scanjetmacron.com

PROPRIETARY RIGHTS NOTICE


The information contained in this manual is the property of Scanjet Macron Intl. Ltd
and must not be used/copied/transmitted to third party without the express written acceptance by Scanjet Macron Intl. Ltd.
Revision date 18.3.2010
SML 1000D Installation Manual 1.2

1 INTRODUCTION ........................................................................................................................................ 3
1.1 General Description of SML 1000D.................................................................................................... 3
1.2 TLG 1000D Cabinets.......................................................................................................................... 5
1.3 Cabinet Specification.......................................................................................................................... 5
2 BEFORE EQUIPMENT DELIVERY FROM FACTORY .............................................................................. 6
3 INSTALLATION .......................................................................................................................................... 6
3.1 Preventive Actions before Installation ................................................................................................ 6
3.2 Installation Work Process ................................................................................................................... 6
3.3 Cabinet Installation ............................................................................................................................. 7
3.4 Supply Air ........................................................................................................................................... 8
3.5 Piping Installation ............................................................................................................................. 10
3.5.1 Measuring Pipe inside Tanks ....................................................................................................... 10
3.5.2 Water Ingress Detection Pipe in Void Spaces and Compartments ............................................. 14
3.5.3 Measuring Line from bottom of Cabinets to Deck/Side Penetration............................................ 14
3.5.4 Draft measuring lines ................................................................................................................... 16
3.5.5 Non-Return Valves ....................................................................................................................... 20
3.5.6 Pneumatic 1:1 Pressure Converter ............................................................................................. 21
3.5.7 Shut-off Valves and Globe Valves ............................................................................................... 22
3.6 Electrical Installation and Connection .............................................................................................. 24
3.6.1 Cable Wiring ................................................................................................................................ 24
4 SYSTEM CHECKS PRIOR TO COMMISSIONING AFTER INSTALLATION .............................................. 26
4.1 Leakage Testing ............................................................................................................................... 26
4.2 Measuring Line Address –Channel Verification ............................................................................... 28
4.3 Cable wiring check on terminal block ............................................................................................... 28
5 DRAWING LIST ........................................................................................................................................ 28

2
SML 1000D Installation Manual 1.2

1 Introduction
1.1 General Description of SML 1000D

The standard scope of supply of Scanjet Macron SML 1000D tank level gauging water ingress monitoring,
and draft measuring system consists of following main components:

1. TLG cabinet(s) with


a. Main Control Processor PCB Unit (MCU302)
b. Service Display Unit (SDU30c)
c. Pneumatic unit with flow-controllers and sensors for pressure measuring

2. Air dryer unit including air pressure regulator and particle filter (FDR100)

3. Non-return valve (NRV straight or NRV 90O bend) for fuel tanks, ballast water tanks etc.

4. Hydrostatic pressure 1:1 converter for fresh water tanks, potable water tanks, edible oil tanks,
etc.

Following items can be supplied as options on request

 Digital Analog Converter Unit (DAU16) for re-scalable analog output for local
instruments
 Digital display units or Analog pointer instruments
 Oil mist removal filter combined with standard type air drier unit (FMDR100)

NOTE! Piping and pipe connectors are not included in the scope of supply.

3
1 2 3

4 5 6

7 8 9 
C:\D
C:\DS
C:
C:
\ \DS
C:\DS DS
S Do
Doc
Doccu
Do um
ume
cuume
men
en
nt\My
mennt\My
t\My
t\ My Pi
t\My Pi
Pic ctu
tures
u
t res
cctu reres\s
tures s\s
\sc
\sca
ca
\scca
an
nje
an nje
e t_ma
jjet_ _ ma
ttt_ma
_ maccron
cron_
ro n_RGB.
macron
cron__RGB
_RGB
R .jp
j.jpg
RGB.j
GB.jppg
gg
0   

General system configuration layout


SML 1000D Installation Manual 1.2

4
SML 1000D Installation Manual 1.2

1.2 TLG 1000D Cabinets

There are three different cabinet sizes available for max.10, 20 and 30 measuring points.

The system is designed considering the number of measuring points and the size and location of
cabinets, so that the total number of cabinets and the piping length is minimized.

This way the system and installation costs are reduced. The service friendliness is improved because
the system function and operation can be checked from fewer locations. One cabinet can be addressed
as master and other cabinets are slaves, facilitating reading all measuring point information from master
cabinet.

The cabinet protection class is IP44 (water spray proof) and allowed operation temperature range is 0 to
60℃. For special cabinet locations, such as on ferry ship car decks, higher IP class can be provided, e.g.
IP 56.

1.3 Cabinet Specification


The cabinet contains two parts, the electrical part and the pneumatic sensor part. The electrical part is
located either above the pneumatic unit in the cabinet, or on the inner side of the door. The pneumatic
sensor part consists of one, two or three manifolds with max.10 independent pressure sensors and flow-
controllers. For every measuring point there is one dedicated sensor and flow-controller with built in non-
return valve.

Compartments Components Remarks


Electrical Main control processor unit Maximum 30 measuring points
MCU and 2 atm reference pressure sensors
can be connected
Service & display unit LCD: 4 line 20 character
Key pad: Calibration and data input
All set values can be changed and
viewed
Pressure switch Switch set pressure: at 0.3 MPa
Normally close contact in operation
Sensor board Gauge sensor: tanks, voids and drafts
Absolute sensor: atm pressure ref.
Digital analog converter unit 1 board with max. 16 channels analog
output 4-20mA (as option only)
Pneumatic Modulator with air manifold 10 units are mounted on each
manifold
Flow controllers & Normal set flow rate: 0.4~0.6 l/min
indicators
Purge valve For cleaning the pneumatic line
Air dry unit Max. flow rate: 300 Nl/min
Air filter + Dryer + Regulator
Optional: Oil mist filter
Dimensions 750 x 600 x 300 (hxbxd)mm max.30 measuring points
650 x 600 x 300 max.20 measuring points
400 x 600 x 300 max.10 measuring points
Color Munsell No. 2.5G 7/2 Other colors at request
Weight About 60 kg fully equipped Full 30 measuring point cabinet
Material SS400 Stainless Steel
Free space for Approx. 700mm Opening the door requires approx.
maintenance 700mm free space in front of cabinet
IP Grade IP44 Water spray proof

5
SML 1000D Installation Manual 1.2

2 Before Equipment Delivery from Factory


All the system components are checked for compliance with approval and other drawings and
specifications before starting assembly. The test certificates for all sensors are checked for compliance
with accuracy requirements and verified with identification/serial number.
All assembled cabinets are checked for compliance with scope of supply and system approval drawings.
All connections, couplings and glands are checked for tightness and leakages. Cable connections are
numbered according to the wiring diagram. All air pipes inside the cabinet are numbered and checked.
Measuring pipe connections from tanks, voids and drafts to cabinet(s) are checked against sensor air
pipe numbering inside cabinet(s).
The system is completely calibrated and tested at the factory after all internal wiring and pneumatic
tubing is finished.

Cabinet and system functionality is tested at the factory. Every measuring sensor is checked from zero
to max. measuring range and back to zero in order to verify compliance with system accuracy
requirement of 0.25 % of full scale.
For traceability management, we always provide the system test data sheets with the delivery. The test
report is generated automatically and will be enclosed inside the cabinet with final documentation.

3 Installation

3.1 Preventive Actions before Installation

Following actions will ensure reliable operation of the SML 1000D system with minimum anticipated
need of service and spares.

a) In case the system has been stored at shipyard for a long time before installation,
please check for possible dirt inside the cabinet(s) and remove it by cleaning air.

b) Do not install or connect/disconnect electrical parts with power on in order to avoid


electrical shocks.

c) Do not open any protection covers/enclosures exposing the internal electrical and
electronic components to water/moisture or dirt.

d) Never connect supply air pipe to system cabinet(s) before cleaning and drying the air
supply lines by blowing air freely! The air pipe may contain water, oil, moisture, and
particles that may influence the proper function of the TLG system.

e) Compressed instrument air is used for measuring tank levels and drafts. It must always
be routed via the air dryer unit in order to avoid condensation, oil, and dirt/particles
inside the air flow controller etc.

f) The supply air pressure is reduced to 4.5-5 bar for steady air flow to tanks thus avoiding
random supply air pressure fluctuation caused by other possible consumers hooking on
or disconnecting from the instrument air supply piping.

3.2 Installation Work Process


It is necessary to follow the installation work process described below in order to avoid any late changes
in the installation and the commissioning, which can directly affect the ship’s construction time schedule
and consequently delay the delivery of the ship.

When Scanjet Macron receives an order from the shipyard or the shipowner, the following installation

6
SML 1000D Installation Manual 1.2

work flow process will be initiated and applied.

The Scanjet Macron information form is submitted to the shipyard or the


1 shipowner, see Appendix 1

The information form has to be returned to Scanjet Macron with all


2 required information completely filled in for production purposes

The system is delivered to the shipyard according to the scope of supply


3 and approved drawings

The shipyard completes installation of measuring lines, cabinets, and


4 electrical installation with all supplied components and connections.
Installation to be verified according to Scanjet Macron working drawings

Final inspection of installation including leakage testing must be done by


5 shipyard and possible leaks must be repaired before calling Scanjet
Macron commissioning engineer

3.3 Cabinet Installation

The cabinets have been designed to comply with the requirements of IP44 (spray proof) protection class.
The TLG cabinets should not be installed in hazardous (Eex-classified) area without using ex-barriers.
For special installations and locations, please check with Authorities and Class for relevant rule
requirements and possible restrictions.
Several cabinets can be located in same area, or be distributed for instance by fire zones along ship´s
length. There are three different cabinet sizes for max 10, 20 or 30 measuring points facilitating cost
optimization of number of cabinets and supply air piping. The general objective is to reduce the number
of cabinets and the piping length and work.
Sufficient free space must be around the cabinet to allow easy fitting of glands, bulkhead/floor
penetrations and sealings, routing of the cables, and easy installation/connection of pipes to the cabinet.
In front of the cabinet a minimum free space of approx. 700 mm must be provided for the door to be
opened.

7
SML 1000D Installation Manual 1.2

Cabinet dimensions Free space required for maintenance

3.4 Supply Air

SML 1000D tank level gauging, water ingress monitoring, and draft measuring system is based on
electro-pneumatic principle. This means that the hydrostatic pressure in tanks is measured by blowing
clean and dry instrument air into the tank through special measuring pipes. The pressure is converted
electronically to tank levels. Same principle is used for measuring the drafts.

The instrument air must be dry and clean in order to avoid any condensation or dirt in the measuring
system. Therefore, the supply air is always routed through the air dryer with drainer installed outside
every cabinet. A particle filter is installed close to the air filter for removing dirt from supply air.

NOTE! Before connecting supply air pipe to the tank level gauging system, the supply air
pipeline must be blown clear from any moisture and particles that may be present.

NOTE! If same supply air pipes are used for other systems where water is present, then the other
system MUST be fitted with non-return valves in order to avoid flooding the tank level gauging
system.
The air dryer unit is mounted close to the cabinet(s) and consists of an air filter, a fiber dryer and an air
regulator as standard supply. An oil mist filter can be provided in addition for removing possible oil in the
supply air. The regulator reduces the supply air pressure from about 7 bars down to 5 bars for steady air
flow.

8
SML 1000D Installation Manual 1.2

Ball Valve Filter Fiber Dry Regulator

3
1
0

AIR OUT PIPE (¥ 1


Õ0)

Ball Valve Filter Oil Mist Fiber Dry Regulator


Filter

2
3
1

AIR OUT PIPE (¥ 1


Õ0)

9
SML 1000D Installation Manual 1.2

3.5 Piping Installation

In general, piping is not included in the Scanjet Macron scope of supply. Consequently the shipyard or
their subcontractors have the full responsibility for all piping, penetrations, and leakage testing.
The tank level gauging and draft measuring piping consists of following:

 Measuring pipes inside tanks and void spaces/compartments


 Measuring pipes from cabinets to tank side/top and void spaces/compartments
 Measuring pipes from cabinets to draft measuring points
 Supply instrument air pipes to cabinets
 Atmospheric pressure compensation pipes to cabinets
 Globe, shut-off and non-return valve installations
 Bulkhead and deck penetrations, sockets

Leakage testing is to be carried out by the shipyard for all measuring air pipes. Any detected leakages
should be repaired before the commissioning is started.

3.5.1 Measuring Pipe inside Tanks


We strongly recommend using seamless, stainless steel 316, or galvanized steel, with the diameter of
20 mm (3/4”) inside tanks. Other pipe materials must be considered for liquid chemical suitability,
strength, corrosion, and leakage properties before considering installation inside the tanks.
The measuring pipe can be installed from the tank top or from the tank side with welded penetrations
and with appropriate connections such as 5k-25A or DN20 flanges. The pipe should be fastened to the
tank wall by proper support against vibration.
The measuring pipe should be located as close as possible to the manual sounding pipe (if manual
sounding pipe exists). The reason is that the tank levels measured by remote electro pneumatic
measuring technology will then be fairly close to the levels measured by manual sounding tape.
In case the measuring pipe is not located close to the mid of the tank, then the measured tank levels
must be compensated for trim and list in order to show actual level correctly.
Please note that the electro pneumatic system provides very accurate tank levels as opposed to
manual sounding where the pipes can be bent and the levels can be different from the correct
ones.
The lower end of the pipe inside the tank should be at the distance of 50mm ~ 100mm from the tank
bottom.
This distance is called offset and should be measured and stored as a set value for every tank
and void space.
Consequently, there may be some liquid in the tanks even if the system shows that it is empty.
The lower end of the pipe should also be sniped (30o) in order for the air bubbles always to leave from
the higher side of the pipe (=constant offset).
The low end of measuring pipe should never be located close to turbulent areas such as bilge wells,
because the pressure variations during pumping will result in unreliable pressure readings and tank
levels.

For trim and list corrections of tank levels, the location of the measuring
pipe lower end in every tank must be recorded, e.g. the distance from
nearest bulkhead or frame in longitudinal direction (x), in transverse
direction (y) and height from bottom plating (vertical direction, z)

10
SML 1000D Installation Manual 1.2

11
SML 1000D Installation Manual 1.2

12
SML 1000D Installation Manual 1.2

13
SML 1000D Installation Manual 1.2

3.5.2 Water Ingress Detection Pipe in Void Spaces and Compartments

In void spaces and compartments, the water ingress detection pipe material and dimension (8 or 10mm)
is usually the same as for the measuring line from the cabinet to the tanks, see 3.5.3 below.

The water ingress detection pipes should preferably be located in the forward or aft end of the
compartments because of ship trim.

In case of forward damage, the ship will most likely trim on the bow and the water will then first show in
the forward end of the compartment. For aft damage, the opposite is valid.

For large compartments separate water ingress detection pipes for both port and starboard side should
be considered because of list effects due to flooding caused by side damage.

The location of the measuring pipe lower end in every void space and
compartment must be recorded, e.g. the distance from the nearest
bulkhead or frame in longitudinal direction (x), in transverse direction (y)
and height from bottom plating (vertical direction, z)

3.5.3 Measuring Line from bottom of Cabinets to Deck/Side Penetration

Copper or stainless steel pipe with 8mm or 10mm outer diameter is recommended. Other equivalent
materials must be considered for liquid chemical suitability, strength, corrosion, and leakage properties.

There is no limitation to the total length of the measuring line from the cabinet to the tank. However, if
the total measuring line is longer than 200 meters, the pipe outer diameter should be 10mm because of
higher pipe resistance.

For ships with a length 250+ meters, installing one or more system cabinets in the bow should be
considered because of high pipe resistance.

Multi-core pipe can be used for measuring lines.

We recommend that measuring pipes on deck are protected in order to avoid any accidental mechanical
damage.

The following must be considered when installing the piping:

 The piping material must be selected considering possible risks for corrosion and damage. In
waste handling rooms possible high nitrogen concentration may result in corrosion of the copper
pipes unless these are properly protected.
 All pipe connectors used must be of premium material applicable for marine use.
 Threaded connections must be sealed with pneumatic pipe sealing compound, PTFE tape or
any other suitable and reliable method to avoid air leakage because of vibrations etc.
 Galvanic couples must be avoided for fitting materials when connecting with pipes and
for pipe extensions.

14
SML 1000D Installation Manual 1.2

15
SML 1000D Installation Manual 1.2

3.5.4 Draft measuring lines

In general, ship drafts are measured at forward, midship port and starboard, and aft locations.

The draft measuring is very accurate using the electro pneumatic measuring system. The drafts are
used to check the ship’s loading condition, i.e. that the ship is not loaded too deep, jeopardizing the
safety of the ship, crew and cargo.

The drafts are also used to calculate the ship’s trim and list in port during loading and unloading.

For forward and aft draft measurements, the draft measuring point should be located as close as
possible to the center line and the hull draft marks. The measuring drafts must be corrected to hull
marks considering the distance from the draft measuring point to the corresponding hull marks.

This way the displayed readings for fore and aft drafts will be the same as those observed visually at the
ship’s bow and stern hull draft marks. Consequently trim and list is considered in the actual draft
readings.

For midship drafts port and starboard, the measuring point should be located on each side of the bottom
and as close as possible to midship hull draft marks.

Note! The draft measuring points should not be installed in areas with cavitation such as close
to sea water intakes or in way of bow/aft thrusters or propellers because pressure variations will
result in unreliable draft readings.

According to safety regulations, all draft measuring lines must be fitted with globe valves close
to the hull penetrations to prevent any sea water ingress.

The globe valves for drafts measuring pipes at ship hull penetrations are generally supplied by the
shipyard and have to be approved by the classification society. Also the hull penetration welding for
drafts are to be approved by the classification society.

In addition, all draft measuring lines must also be fitted with non-return lines for safety to
prevent sea water ingress in case the measuring line is accidentally broken.

The draft measuring pipes from cabinets to draft measuring points are typically 10 mm stainless steel or
copper pipes.

The location of the measuring pipe at sea side must be recorded, e.g. the
distance from nearest bulkhead or frame in longitudinal direction (x), in
transverse direction (y) and height from bottom plating (vertical direction,
z)

16
SML 1000D Installation Manual 1.2

17
SML 1000D Installation Manual 1.2

18
SML 1000D Installation Manual 1.2

19
SML 1000D Installation Manual 1.2

3.5.5 Non-Return Valves

There are four different non-return valve arrangements for the protection of any accidental fluid back-
flow through measuring lines from tanks and void spaces and drafts.
1. Air flow controller non-return valve
Every air flow controller unit has a built-in spring loaded non-return valve, which closes
when the air pressure is lost making the measuring line hermetically sealed thus
hindering any back flow from tanks, voids, and drafts.

2. Pressure switch non-return valve


Every cabinet has one pressure switch which automatically closes when the air
pressure drops below 3 bar making all measuring lines hermetically sealed. The
pressure switch is automatically reactivated when the air pressure exceeds 3 bar again.

3. Non-return valves at tank side and top


Depending on type and location of the tank, a non-return valve is fitted at the tank side
or the tank top to prevent back flow from tanks in case the air pressure is lost.

This non-return valve also prevents any leakage in case the measuring pipe outside the
tank is broken. This provides protection against any accidental spray of oil on hot
surfaces and reducing the risk of engine room fires and oil spills in engine room, to the
sea etc.

The non-return valves at tank top and tank side are gravity loaded and must be installed
with housing in vertical position in order to function properly. For side mounting the non-
return valve is 90O bent.

For fuel tanks, side penetrations must also be fitted with a shut-off valve according to
safety regulations.

Note! If a measuring cabinet is located lower than the height of tank measured, the tank should
always be fitted with a non-return valve for safety against fluid back-flow from the tank.

4. Non-return valves for draft measuring points


Every draft measuring point is fitted with non-return valve after the globe shut-off valve
in order to prevent seawater ingress through draft measuring openings.

The specification and application of non-return valves are shown below:

 Maximum working pressure: 0.5MPa


 Connection size for yard copper/stainless steel tube: OD10mm or OD8mm
 Method: gravity based plastic floater with O-ring
 Tank penetration connection size for flange type and location are:

No Location Type of NRV(flange) Tank penetration


1 Water Ballast 5K 25A Tank top
2 Forward Draft 16K 40A Tank/Void space bottom
3 Midship Drafts 16K 40A Tank/Void space bottom
4 Aft Draft 16K 40A In E/R
5 HFO/DO bunker 10K 25A Tank top or side
6 HFO/DO service 5K 25A Tank top or side

DIN type connection can be supplied as well at request.

Note! Make sure that the gasket is installed when non return valve is mounted on tank
penetration flange.

20
SML 1000D Installation Manual 1.2

3.5.6 Pneumatic 1:1 Pressure Converter

Pneumatic pressure 1:1 converters are used for measuring the hydrostatic pressure in tanks where air
bubbling cannot be used for direct measuring, such as fresh water tanks, drinking/potable water tanks,
and edible oil tanks.
Before installation of the pneumatic pressure 1:1 converters, the measuring pipe must be blown clean
by compressed air to remove any dust inside of pipe before connecting the measurement air pipe to the
converter.
There are three connections (A, B, and C) in front of the converter as shown in the figure below.
The pneumatic 1:1 converter should be installed outside the tank as low as possible. Only one
measuring line (A) is connected to the pressure sensor inside the cabinet. The air vent line (B) is not
connected and breathes freely into the air.
Generally, a globe valve is installed between the pneumatic pressure 1:1 converter and the tank so that
the pneumatic pressure 1:1 converter can be dismounted for maintenance.
It is also possible to install the pneumatic pressure 1:1 converter inside of tank with special membrane
only in exceptional cases. Then the air vent line (B) must be connected to outside of the tank.

A pneumatic pointer instrument can be attached to (C). A cover is to be applied at (A) if pneumatic point
instrument are disengaged.

Operation principle:
Clean and dry instrument air from the cabinet is blown through the constant flow controller to the
pneumatic 1:1 pressure converter. The air flow is increased with the fluid hydrostatic pressure until the
air passes through the air vent pipe. This air pressure is measured by the pressure sensor in the cabinet
in the same way as for other tanks.

21
SML 1000D Installation Manual 1.2

The test connection (4) must be closed during normal use.

Storage instructions:
The pneumatic 1:1 pressure converter must be stored indoors well protected from dust and moisture.
The pneumatic pressure 1:1 converter is delivered with plastic protection covers. The covers shall be
removed during installation, not before.
If the covers have been removed before installation, then the internal parts must be inspected carefully,
and any dirt must be removed before installation using pressure air.
If there is dust and dirt on the converter membrane surface, the pneumatic 1:1 pressure converter
cannot show accurate tank pressures.

3.5.7 Shut-off Valves and Globe Valves

Shut-off valves are to be installed as required by rules and regulations for fuel, fresh water, and other
tanks. This is normally shipyard supply.
Shut-off valves can be installed close to the measuring cabinets for tanks not fitted with non-return valve
to prevent possible back-flow when the measuring air pipe is disconnected inside the cabinet.
A globe valve is required close to the hull opening for draft measuring pipes as safety against flooding
caused by sea water ingress. This is normally shipyard supply.

22
SML 1000D Installation Manual 1.2

23
SML 1000D Installation Manual 1.2

3.6 Electrical Installation and Connection


The electrical installation is shown in the system documentation (Connection drawing).
The communication between TLG cabinets, the automation system, and the loading computer is by
standard RS 485 MODBUS RTU (Remote Terminal Unit) mode serial lines.
For more information regarding the Modbus communication, please see the separate Modbus
specification document.

3.6.1 Cable Wiring

Shielded cable type should be used. These cables are completely insensitive to external electrical
disturbances.
It is recommended that the cables are installed away from any equipment which may be causing strong
magnetic field disturbance.
All electrical wiring must have suitable insulation for reliable signal and system accuracy.
Ensure that all electrical connections are properly tightened and that none of them are partial or floating.
Only standard electrical precautions are required.
No special tools or instruments are needed during installation/electrical connection.
Note! Earth wire must be connected to the earth stud on the side of the control box.

 Power Cable
The power cable is EP rubber insulated, PVC sheathed & steel wire braided cable or
with protective covering

 Communication cables
PVC insulated, PVC sheathed & steel wire braided telephone cable with common shield
or with protective covering

 Analog output cables


Multi-core, EP rubber, PVC sheathed, steel wire braided & protective covered cable
with common shield.
In case the system cabinet is fitted with an analog output board, either DAU16 or
ACU16, the cable gland size at the bottom of the cabinet depends on the numbers of
analog outputs.
Other cable glands size will depend on shipyard cable selection.

24
SML 1000D Installation Manual 1.2

Recommended Cable Types

Connection Cable type


Power Supply 2 x 1.5mm2 x earth, 220V AC x 60Hz x 1ø
Communication 2 x 1.0mm2 twisted pair + screen
For serial interface 1 port RS485
Analog Channel Nos. x 1.0mm2 x twisted pair + screen
Output(DAU16) For displays (Optional)
Analog Channel Nos. x 1.0mm2 x twisted pair + screen
Output(ACU16) For displays
Alarm Relay 1 2 x 1.0 x twisted pair + screen
For common alarm, NC
Alarm Relay 2 2 x 1.0 x twisted pair + screen
For system failure, NC
Low Pressure Will be connected to MCU302 TB X140 by Maker
Alarm
Earth Cable Conductor area 4.0mm2

Refer to the yard electrical cable connection drawing

25
SML 1000D Installation Manual 1.2

4 System Checks prior to Commissioning after Installation


Remove any dirt or any loose items in the cabinet before starting system checks. Check all connections
for tightness and tighten them if necessary.
Never connect supply air pipe to system cabinet(s) before cleaning and drying the air supply lines by
blowing air freely! The air pipe may contain water, oil, moisture, and particles that may influence the
proper function of the TLG system.

4.1 Leakage Testing

The leakage testing should be carried out by the shipyard after the system installation has been
completed. This is very important for accurate system performance and reliable operation.
The following actions should be carried out and the testing must be verified before commissioning:

1. The pipe ends of tank inside should be plugged and then the lines should be pressurized

2. Dry and clean instrument air for this leakage testing must be used

3. If any leakage is detected in any pipe connections, the pressure in the line will drop

4. The pipe and flange connections (see the drawing below) should be checked very carefully
with soap water, or similar

5. If any pipe or flange leakage is detected, this must be repaired by the shipyard before
commissioning.

26
SML 1000D Installation Manual 1.2

27
SML 1000D Installation Manual 1.2

4.2 Measuring Line Address –Channel Verification

In order for the measuring system to function properly, all measuring lines have to be addressed
correctly according to working drawing.
Following checks are to be carried out after installation for verifying the correctness of the measuring
line addresses:

1. Disconnect male/female connector on non-return valve for tank to be checked


2. Open “purge valve” on flow controller allowing air to flow into the line at full measuring pressure
3. Verify that air flowing at the end of pipe in the tank with same channel specification

4.3 Cable wiring check on terminal block


Check the following cables and cable connections on the terminal block

1. Power cable
2. Earth wire should be connected to the hull
3. Communication cable wiring
4. External output relay
5. Analog output cables are to be connected according to channel specification in
enclosed drawing in the each cabinet if delivered
6. Cable glands are tighten properly after connecting yard cables

5 Drawing List
The completed system is delivered to shipyard or customer based on requested information form which
is enclosed in the cabinet and approval drawing as well.

No. DWG No. Description


1 SMDW10-0001 Measuring line pipe in tank from tank top with NRV-FS
2 SMDW10-0002 Measuring line pipe in tank from tank side with NRV-FS
3 SMDW10-0003 Non-return valve side mounting type NRV-F90
4 SMDW10-0004 Measuring line installation examples
5 SMDW10-0005 Non-return valve top mounting type for fore and aft draft A
6 SMDW10-0006 Non-return valve top mounting type for midship draft B
7 SMDW10-0007 Non-return valve top mounting type for midship draft C
8 SMDW10-0008 Measuring line leakage testing

28

You might also like