Per Unit
Per Unit
Per Unit
T1 T2
G1 G2
Load
∆ ∆
Impedance Diagram:
The per phase impedance diagram of the circuit under balanced
condition is
XT 1 RTL XTL XT 2
Xs1 Xs2
RL
Y Y
Ra1 Ra1
2 2
XL
EG 1 + EG 2 +
− −
Reactance Diagram:
▶ Resistance is often neglected in fault calculations.
▶ Capacitance is also neglected in the fault analysis.
▶ Static loads are omitted as they do not contribute during a
fault.
▶ Synchronous motor loads are included in the analysis.
XT 1 XTL XT 2
Xs1 Xs2
EG 1 + + EG 2
− −
per unit
S, V , I , Z
Sb (MVA)
Ib = kA
Vb (kV)
Vb (kV)
Zb = Ω
Ib (kA)
Substituting Ib in Zb ,
Vb2 ( in kV)
Zb = Ω
Sb ( in MVA)
Zactual (Ω)
Zp.u. =
Zb (Ω)
Zactual (Ω) × Sb ( 1ϕ MVA)
∴ Zp.u. =
Vb2 ( L- N in kV)
For three phase.
Sb (MVA)
Ib = √ kA
3Vb (kV)
Vb (kV)
Zb = √ Ω
3 × Ib (kA)
Substituting Ib in Zb ,
Vb2 ( in kV)
Zb = Ω
Sb ( in MVA)
Zactual (Ω)
Zp.u. =
Zb (Ω)
Zactual (Ω) × Sb ( 3ϕ MVA)
∴ Zp.u. =
Vb2 (L-L in kV)
√
Sb3ϕ = 3Sb1ϕ ; VbL−L = 3VbL−N
3ϕ S 3ϕ 3 × S 1ϕ
Sp.u. = = = Sp.u.
Sb3ϕ 3 × Sb1ϕ
√
VL−L 3VL−N
Vp.u. = =√ = Vp.u.
VbL−L 3VbL−N
Sb
Zp.u. ∝
Vb2
Sb (new in MVA) V 2 (given in kV)
Zp.u. (new) = Zp.u. (given) × × b2
Sb (given in MVA) Vb (new in kV)
Advantages:
▶ The per unit values of impedance, voltage and current of a
transformer are the same regardless of whether they are
referred to the HV side or LV side. This is possible by
choosing base voltages on either side of the transformer using
the voltage ratio of the transformer.
√
▶ The factors 3 and 3 get eliminated in the per unit power
and voltage the equations.
Per unit Reactance Diagram:
▶ Choose Base MVA and Base kV.
▶ Find Base kV of other sections using transformation ratios.
▶ Find the per unit impedance.
1. If the impedance is given in Ω
1 2
G M
∆
▶ Base MVA is the same across the system.
▶ Base kV of the generator and motor sections have to be found.
33
Base kV of Generator = 220 × = 33 kV
220
11
Base kV of Motor = 220 × = 11 kV
220
100 252
XG = ȷ0.2 × × 2 = ȷ0.2870 p.u.
40 33
100 2202
XT 1 = ȷ0.15 × × = ȷ0.3750 p.u.
40 2202
100
XLine = ȷ50 × = ȷ0.1033 p.u.
2202
100 2202
XT 2 = ȷ0.15 × × = ȷ0.5 p.u.
30 2202
100 112
XM = ȷ0.3 × × 2 = ȷ0.6 p.u.
50 11
ȷ0.3750 ȷ0.1033 ȷ0.5
ȷ0.2870 ȷ0.6
EG + + EM
− −
Example 2 :
T1 T2
1 2
Line
G
Load
11
Base kV of Generator = 220 × = 11 kV
220
33
Base kV of Load = 220 × = 33 kV
220
100 112
XG = ȷ0.15 × × 2 = ȷ1.5 p.u.
10 11
100 2202
XT 1 = ȷ0.1 × × = ȷ0.2 p.u.
50 2202
100
XLine = 30 + ȷ100 × = 0.062 + ȷ0.2066 p.u.
2202
100 2202
XT 2 = ȷ0.1 × × = ȷ0.2 p.u.
50 2202
ȷ0.2 0.062 + ȷ0.2066 ȷ0.2
+
ȷ1.5
VL
EG +
− − IL
2 33
PL = = 0.02 p.u. VL = = 1 p.u.
100 33
PL 0.02
IL = = = 0.022 p.u.
VL × pf 1 × 0.9
VG = 1.0 0◦ + 0.022 −25.84◦ (ȷ0.2 + 0.062 + ȷ0.2066 + ȷ0.2)
VG = 1.0075∠0.65◦ p.u.
VG = 1.0075 × 11 = 11.08 kV