Getting Started IPC@CHIP Embedded Web Controller Family IEC 61850 Basics
Page 1 of 38
Documentation Control
Revision: Revision History: Revision Date: Document Status: 1.00 1.00 Initial release 28 April 2010 RELEASE
Page 2 of 38
TABLE OF CONTENTS
1 2 3 Introduction __________________________________________________________ 4 Abbreviations_________________________________________________________ 5 System Start-up_______________________________________________________ 6
3.1 3.2 What do we need to get started? __________________________________________ 6 Steps to run the IEC 61850 Software on the Development Kit ________________ 7
Set Up the Development Kit Hardware __________________________________________ 7 Copy the contents from the DK61 DemoCD to your PC: ___________________________ 7 Setting up the DK61 Device as Server __________________________________________ 8 Setting up the Client _________________________________________________________ 11 Building your own Server_____________________________________________________ 13
6 7
Appendix ____________________________________________________________ 28
7.1 Where to get further Information _________________________________________ 28
Getting Started _____________________________________________________________ 28 Updates, tools and examples _________________________________________________ 28 Support ____________________________________________________________________ 28 Order numbers _____________________________________________________________ 28 Tools related to IEC 61850 ___________________________________________________ 29 7.1.1 7.1.2 7.1.3 7.1.4 7.1.5
IEC 61850 Standards ____________________________________________________ 29 GetDataValues for DIPS_GGIO1.Ind3 _____________________________________ 31 Standardized Logical Nodes _____________________________________________ 32
Page 3 of 38
Introduction
Congratulations on purchasing your IPC@CHIP DK61 Development Kit. The Development Kit is a complete ready-to-use development system for building applications based on the Embedded Web Controllers IPC@CHIP SC123 and IPC@CHIP SC143. It runs with the @CHIP-RTOS operating system, which includes features like a real-time kernel that is capable of running common DOS applications concurrently, a full TCP/IP stack with a UDP/TCP socket interface, DHCP, FTP, PPP, Telnet, Web server, APIs for CAN and USB controllers, and IEC 61850. The Development Kit contains both hardware and software components required for a basic development. This document will introduce you to the basics of the standard IEC 61850 of the DK61. Chapter 3 gets you started with creating an IEC 61850 application with your DK61. Chapters 4 and 5 provide the basic concepts of IEC 61850 related to the DK61 with an example. This document is intended to provide the basic knowledge on IEC 61850 in order to run the introductory example. The example provides basic information, communication and system configuration information. The use of IEC 61850 requires the software loaded onto the DK61 board. After the DK61 board has been set up it will take only a few steps to run the first example to exchange the status values (on or off) of DIP Switches on board and to switch LEDs on and off. Basic knowledge of communication mechanisms is a prerequisite of the following description. Further information on IEC 61850 standards can be found in the Appendix.
Page 4 of 38
Abbreviations
IED GOOSE HMI ICD IEC IED INS IP LN SCL Intelligent Electronic Device Generic Object Oriented Substation Events Human Machine Interface IED Capability Description International Electro-technical Commission Intelligent Electronic Device Integer Status Internet Protocol Logical Node System Configuration Language
Page 5 of 38
3
3.1
System Start-up
What do we need to get started?
The Development Kit DK61 consisting of: o Development Board DK60 o Embedded Web Controller IPC@CHIP SC143 (on the DK60) o Serial null-modem cable o USB cable (A-to-Mini-B) o Ethernet patch cable(gray)TPFF FFPT o Ethernet crossover cable(red) o Secure digital memory card o Power supply unit o Paradigm C++ Beck IPC Edition CD (including IPC@CHIPTOOL, DEBUG@CHIP debugger,DK61 start-up documentation and drivers) Personal Computer: o Microsoft Windows NT/2000/XP Operating System o Ethernet network interface o Serial port o USB interface Software from the enclosed CD: o DemoCD.html o API User Manuals Contains IEC 61850 Protocol API User Manual.pdf and PIS10API/index.html online manual o DK61 Client Application o DK61 Server Application o IEC 61850 Documents PICS o IEC 61850 Library Contains all the license files for your DK61 serial number o Presentation Power Point Presentation: 61850 ICD Editor DK61 v3.pps Contains (movies) walk through slides creating ICD Designer files and using the DK61 o ICD Designer Demonstration Software
Be aware that the Embedded Controller SC143 and the Development Board DK60 are electrostatic sensitive components. Observe general precautions for handling
Page 6 of 38
3.2
3.2.1
3.2.2
Copy the contents from the DK61 DemoCD to your PC: Copy the contents of the CD_DRIVE:|\*.* to C:\DK61\*.* to make all the files, presentation, and source code examples available on your computer. Some files need to be customized and copied to the DK61 hardware for the example to work properly. Specifically, there is network address information on your PC and network to be edited. Also, there is a specific key that matches your specific DK61 hardware. The following pages describe setting this information up.
Page 7 of 38
3.2.3
1. Open CHIPTOOL. Note your specific information for your network and DK61:
The ICD Designer User Manual is in CD_DRIVE:\ICD Designer\ICDDesigner.pdf and also under Help.
2. Open DK61.ICD file (copied earlier under C:\DK61\DK61 Server Application) with the ICD Designer application. According to your specific information in CHIPTOOL: a. Select then change the IP b. Select then change the IP-SUBNET c. Select then chance the IP-GATEWAY
2010 Beck IPC GmbH Page 8 of 38
3. Using CHIPTOOL download the specific PIS10.key file matching your DK61 serial number. From CD_Drive:\IEC 61850 Library\BECK_SSSSS, where SSSSS is the Serial number of your specific DK61 (Example if Serial Number is 0583C) copy the PIS10.key to the DK61 4. Next, download DK61.ICD that you edited above with ICD Designer and also the SV61850.EXE to your DK61.
5. Again using CHIPTOOL, right-click on your DK61 and open a Telnet session into the DK61
Page 9 of 38
6. Start the server by typing SV61850 DK61.ICD at command prompt in Telnet. If there are any errors, please refer to API User Manual to resolve it.
7. Start IEDScout or any other Client test application to see if you can connect to the 61850 Server on DK61 8. On successful connection, autoexec.bat can be downloaded so that server starts automatically on reboot of DK61.
Page 10 of 38
3.2.4
1. On the PC that you will use as the client type at the Command Prompt: ipconfig /all
2. Note the information from ipconfig /all then enter that information into ICD Designer. NOTE: This shows the DK61 Client.ICD file. Do NOT confuse this with the Server DK61.ICD file
The ICD Designer User Manual is available on CD_DRIVE:\ICD Designer\ICDDesigner.pdf and also under Help. 3. Run the DK61Demo.exe IEC 61850 Client application:
C:\DK61\DK61 Client Application\DK61Demo.exe
4. Operate Dip switch and Led Output and notice the appropriate changes in the Client application
2010 Beck IPC GmbH Page 11 of 38
Page 12 of 38
3.2.5
1. Copy to PC iec61850.lib and IEC61850API.h From CD_Drive:\IEC 61850 Library\BECK_SSSSS; where SSSSS is the Serial number of your DK61 (Example : If the Serial number is A07899)
2. Open paradigm , Create New Project and than Select Add Node
Page 13 of 38
IPC@CHIP DK61 Getting Started IEC 618580 Basics V.1.00 3. Add nodes iec61850.lib and iec61850Api.h
4. Add your server application source code to the project (sample available at CD_Drive:\ DK61 Server Application\Sample Source Code) . 5. Build your custom Server executable. 6. Download your executable to the DK61.
Page 14 of 38
4
4.1
4.2
Page 15 of 38
4.3
4.4
Page 16 of 38
5
5.1
Introduction of Example
General remarks and basic definitions
The following example focuses on the signals to be described and exchanged with IEC 61850. IEC 61850 provides signal designations (names) for application information produced, exchanged and consumed by devices. The communication services provide the exchange of values in real-time (GOOSE and Sampled Values, based on Layer 2 Multicast) and in a client-server relation based on TCP/IP and higher layer protocols. The configuration language SCL describes all information of a system and the flow of the information between the devices of the system.
These basic features of IEC 61850 are depicted in the following figure:
Device E Device D Device C Device A Device B
Get
Operate Open TCP/IP based Report Open (event) Log Open Log Query Log
Layer 2 Multicast
listen to
Device B provides information (Status, 3-phase electrical Measurements, sensor information, Engineering and Configuration information, Nameplates, etc.) that can be retrieved (Get) by Device B. Device A may operate something in Device B (open a breaker, start a program, etc.) A change of the breaker position may cause a report of the new value to a specific Device; or the change may be logged and queried for retrieval later on. These services use a clientserver communication based on TCP/IP. IEC 61850 provides two special services for real-time communication based on Layer 2 multicast services (on publisher to many subscribers). GOOSE allows the exchange of any information in short reaction times (less 5 ms). Sample Measured Values (SMV) are intended to exchange values cyclically in a high frequency (typical sample rate: 4.000 messages per second for special functions).
2010 Beck IPC GmbH Page 17 of 38
IPC@CHIP DK61 Getting Started IEC 618580 Basics V.1.00 The System Configuration Language (SCL) describes the sources of the information, which services are to be used, who should listen to the information exchanged (information flow). Devices A, C, D and E are configured to listen to the red Multicast message sent by Device B. Devices could implement one or more of the following roles: Client, Server, Publisher, or Subscriber. The version of the IEC 61850 in the DK61 for this description is V1.0. This version provides the roles Server, Publisher (GOOSE) and Subscriber (GOOSE). The example introduces a Server that allows the access of information from DIP Switches and information for LEDs. The application between IEC 61850 and the Digital I/Os is implemented in C.
5.2
5.2.1
The DK61 Board, the Approach of IEC 61850 and the Example
Architecture The crucial aspects shown in the following figure (related to the example in this document) are: 1. The Ethernet connectivity on the top; the devices (the DK61 and two other documents shown to the left) are understood to be connected to one subnet. 2. The Digital Inputs and Outputs shown at the bottom. 3. The Inputs are implemented as 8 DIP Switches and the Output signals are implemented as 8 LEDs. The position of the DIP Switches can manually be changed. The positions (information) are intended to be communicated by IEC 61850 services. The LEDs will be used to demonstrate the control services. 4. The physical Inputs and Outputs are connected to an application. 5. For the purpose of communication it is required to designate (name) and format the information to be exchanged (in the first example position inputs and control outputs).
Ethernet
IEC 61850 Server/ Publisher Ethernet Ethernet GOOSE GOOSE Sampled Values Sampled Values Client/Server on TCP/IP Client/Server on TCP/IP Ethernet Sampled Values Client/Server on TCP/IP
GOOSE
Information Information Model Model Application Application HMI/Application HMI/Application IEC 61850 Client/ Subscriber
Digital Input/Output
Page 18 of 38
IPC@CHIP DK61 Getting Started IEC 618580 Basics V.1.00 5.2.2 The process interface The Digital Inputs and Outputs are shown in the following picture. The DIP Switches are shown on the left. The switches are identified as DIP Input 1 to DIP Input 8. The LEDs are LED Output 1 to LED Output 8. These names are defined and used in this description: the names in the corresponding C application are: /* Object Types */ enum { DIGITAL_INPUT = 1, DIGITAL_OUTPUT = 2, }eObjectTypes;
The access to the DIP Switches or LEDs from a client requires the access (path) information to identify (address) the right DIP Switch. The Application program may use any name for the DIP Switches. The programmer is free to choose any name. This name usually is not recommended to be used by a client because it may be changed by the programmer at any time.
DIP Input 1
DIP Input 8
5.2.3 The IEC 61850 information model for general I/Os IEC 61850 provides standardized designations for this kind of information. The so-called standardized Logical Node (LN) GGIO (Generic Process Input Output) is used to designate input and output signals. The following excerpt of the LN GGIO depicts three kinds of information (each having a Data Object (DO)): Measured Values (AnIn), Controls (SPCSO) and Status Information (Ind). Each has a Data Object has a suffix of 1 (e.g., Ind1) indicating that a LN GGIO may have four Data Objects (Ind1, Ind2, Ind4, and Ind4). These four Data Objects will represent the upper four of the eight DIP Switches in the example.
Page 19 of 38
GGIO class Measured Values AnIn1 instMag q t units Controls SPCSO1 ctlVal stVal q t Status information Ind1 stVal q t stVal q t
AnalogueValue Quality TimeStamp Unit BOOLEAN BOOLEAN Quality TimeStamp BOOLEAN Quality TimeStamp INT32 Quality TimeStamp
Analogue input
IntIn1
The eight LEDs are represented by eight Data Objects SPCSO1 SPCSO8. The signal designations (names) for both are shown in the next figure.
DIP Switches
General indication (binary input)
LED Output
Single Point Controllable Status Output
The blue parts of the names are defined in the standard. The Logical Node GGIO has been extended by a prefix to relate the Logical Node to the DIP Switches respectively to the LEDs. Each Logical Node has also an instance number (1 and 3) to differentiate several Logical Nodes that have the same class name.
Page 20 of 38
5.2.4
Browsing the information of an device A browser (IED Scout) depicts the information accordingly. The Logical Node DIPS_GGIO1 has Status Information (designated with the FC=ST). Besides common information Mod, Beh, Health, the Logical Node has a Data Object Ind1 with three Data Attributes: stVal, q, and t.
The browser has services to read the value of Ind1 one or cyclically (Polling). To read the value of the DIPS_GGIO1.ST.Ind1.stVal requires to send this name to the DK61 using the appropriate IEC 61850 service (GetDataObjectValues). 5.2.5 Communication services The next figure shows the communication for getting the value of the third DIP Switch.
HMI
The message received by the DK61 has to be interpreted by the IEC 61850 software to figure out which DIP Switch is addressed to return the right value. The arrows shown in the above figure are pointing to the hardware DIP Switches. These arrows need to be specified in a way that allows the software to address internally the right internal signal of the DIP Switch. The following figures show the relation between the physical I/Os, the internal memory and the name used in the communication. The following figure maps the physical I/Os to a list of inputs (1-8) and outputs (1-8). This list represents the memory location in which values may be stored.
Page 21 of 38
DIP Input 8
The communication stack of the IEC 61850 server (as shown in the following figure) is in principle accessing the memory location. These names Input 1 to Output 8 do not provide and specific meaning. To do so, there is a need of a mapping of the local information (e.g., value of DIP Switch position, time stamp of last change and quality of value (good or bad)) to the standardized designation.
Application Program Interface
Read
Value T/F
The Memory table with eight Inputs and eight Outputs is shown at the right side of the following picture. The relation between these locations and the access information of the standardized signal names need to be specified. The Data Object DIPS_GGIO1.ST.Ind1 of the corresponding Logical Node specifies three Data Attributes:
Ind1 stVal q t BOOLEAN Quality TimeStamp
Each of the three attributes will be communicated when a client reads the Data Object Ind1. The value stVal represents the status of a DIP Switch. The information, if it refers to the first, second, or the eights is specified by the name DIPS_GGIO1.ST.Ind1.stVal. The other two attributes q and t are also required to be specified and they need also be stored together with the status value.
2010 Beck IPC GmbH Page 22 of 38
IPC@CHIP DK61 Getting Started IEC 618580 Basics V.1.00 5.2.6 Binding of process values to standard information models The binding of the memory to the access specific information is shown in the following figure. When the communication stack receives a GetDataValues request for the Data Object DIPS_GGIO1.ST.Ind1, then needs to get the corresponding reference to the memory locations for the stVal, q and t. The API used for the first example uses a hierarchy of three fields: Field1 selects the position in the corresponding list between 1 and 8; Field2 (to identify if the value is related to the DIPs or to the LEDs; Field3 references to the values for stVal, q and t. This mapping is unique in order to refer to the correct memory location for any of the values.
The communication stack uses this hierarchical reference to get the value from the application. The following figure shows how the service <GetDataValues for DIPS_GGIO1.Ind3.stVal> is mapped the corresponding memory location (that is bound to the real DIP Switch 3). The stack uses the local Read (at the API between the communication software and the real application) with the three fields: Field1=3 (means third DIP Switch), Field2=1 (means DIP Switches), and Field3=1 (means Value). The returned value needs to be encoded according to the type of the Logical Node GGIO and Ind1.stVal. The type is a BOOLEAN. The Value TRUE or FALSE will be returned to the client that issued the GetDataValues request.
Page 23 of 38
The IEC 61850 communication stack is part of an entity between the messages on the communication link (TCP/IP, Ethernet, ) and the local Application. The concrete encoding of the request and response messages for the service <GetDataValues for DIPS_GGIO1.Ind3> is shown in the Appendix 7.3 - GetDataValues for DIPS_GGIO1.Ind3. The mapping table in this example is defined by the system designer of the API between the IEC 61850 communication stack and the real application. It is up to the system designer how to organize the internal communication between the stack and the application. From a communication point of view it is not visible during the exchange of messages with that particular server device. As shown in the next figure, the client just needs to know the name of the Data Object DIPS_GGIO1.Ind3.Ind3. The name is translated into an internal access mechanism using a table to map between the standard name and the memory location of the value.
Page 24 of 38
The communication stack may have its own memory that holds a copy of the real value from the application. The copy could be updated cyclically, on request by the communication stack, or by an event from the application. The service <GetDataValues for DIPS_GGIO1.Ind3> does not care about the implementation of the API. The difference between the three update mechanisms is not visible in the standard communication except that the delay is longer or shorter depending on the mechanism used. The timestamp and the quality information associated with the data value are provided the same way as the process value. 5.2.7 System Configuration Language (SCL) The configuration of the information model and the binding of the model to the real values are described by the System Configuration Language (SCL). The following figure shows the formal syntax of the binding based on the three Fields: Field1 (position), Field2 (DIP or LED), and Field3 (value, quality or timestamp).
Page 25 of 38
Communication services
Report GOOSE
Value T/F
alues Sampled V
Value T/F
Event
Event
Event
Page 26 of 38
6.1.1
Setting up the serial communication To set up serial communication to your Development Kit DK61 you need the enclosed nullmodem cable. 1. Connect the null-modem cable to a free serial port of your PC and with the COM1 interface of the DK61. 2. Choose Tools Terminal from the IPC@CHIPTOOL main menu 3. In the connection dialog that now opens choose the following settings: o Connection Type: Serial o Port: The serial port of your PC that you connected the null-modem cable to, e.g. COM1 o Baudrate: 19200
Page 27 of 38
7
7.1
7.1.1
Appendix
Where to get further Information
Getting Started All software referred to in this document can be downloaded from out Getting Started website at http://www.beck-ipc.com/gettingstarted.
7.1.2
Updates, tools and examples Regularly check out IPC@CHIP website at http://www.beck-ipc.com/ipc for: @CHIP RTOS updates New APIs Example programs that you may use as a base for your own applications Useful tools for your development Application notes
7.1.3
Support If you need support please 1. Check our support website at http://www.beck-ipc.com/ipc/support including a FAQ. 2. Visit our newsgroup at http://www.beck-ipc.com/ipc/support/forum. Here you will find a lot of answers to customer problems and you can also add your own ideas and questions. 3. Contact our support at support@beck-ipc.com. Of course you may also contact us by phone. But please use email if possible. This not only reduces the time you spend on the phone, it also allows us to easily manage the questions and identify problem areas. Important or frequent questions and the corresponding answers are becoming part of our FAQ that is published on the Internet.
7.1.4
Order numbers Most parts of the Development Kit DK61 can be ordered separately. Please visit our online shop. These are the order numbers. DK61 Development Kit DK60 Development Board ZK14 serial null-modem cable PSE10 power supply Paradigm C++ Beck Edition 542750 542751 195837 538934 541522
Page 28 of 38
7.1.5
Tools related to IEC 61850 The following tools may be used for the communication between an IEC 61850 server and client: IED Scout IEC 61850 Browser; Download demo version: http://www.omicron.at/en/products/pro/communication-protocols/iec-61850/iedscoutv210/ Wireshark IEC 61850 Network Analyser; Download open source version: http://sourceforge.net/projects/wireshark/ UNICA Network Analyser; Download of demo version: http://www.nettedautomation.com/solutions/uca/products/netana/index.html
7.2
IEC 61850-1 Introduction and Overview Introduction and overview of all of the parts of IEC 61850 IEC 61850-2 Glossary Terminology IEC 61850-3 General Requirements Quality requirements (reliability, maintainability, system availability, portability, IT security), operating conditions, auxiliary services and other engineering standards IEC 61850-4 System and Project Management Engineering services requirements (parameter classification, engineering tools, documentation), system Basics usage cycle (product versions, factory setup, support after factory setup), quality assurance (responsibilities, test systems, type tests, system tests, factory acceptance tests (FAT) and site acceptance tests (SAT) IEC 61850-5 Communications Requirements for Functions and Device Models The logical nodes principle, logical communications links, items of information for communications (PICOM), logical nodes and associated PICOMs, functions, performance requirements (response times, etc.), dynamic scenarios (information flow requirements under various operating conditions) IEC 61850-6 Configuration Description Language for Communication Communication in Electrical Substations Formal description of the single-line schemas, devices, system structure and how they fit into the single-line schema IEC 61850-7-1 Basic Communication Structure for Substation and Feeder Equipment Introduction to IEC 61850-7-x, communications principles and models IEC 61850-7-2
2010 Beck IPC GmbH Page 29 of 38
IPC@CHIP DK61 Getting Started IEC 618580 Basics V.1.00 Basic Communication Structure for Substation and Feeder Equipment Abstract Communication Service Interface (ACSI)Description of the Abstract Communication Service Interface (ACSI), specification of the Abstract Communication Service Interface, server database model IEC 61850-7-3 Basic Communication Structure for Substation and Feeder Equipment Common Data Classes Common data classes and attribute definitions IEC 61850-7-4 Basic Communication Structure for Substation and Feeder Equipment Definition von compatible logical node classes and data classes and their logical addressing. General and typical station abstract classes for logical nodes and data IEC 61850-7-410 Hydroelectric power plants - Communication for monitoring and control Extension of Information models for Hydro Power Plants. IEC 61850-7-420 Communications systems for distributed energy resources (DER) - Logical nodes Extension of Information models for decentralized Energy resources like PV, Fuel Cells, Solar, etc. IEC 61400-25-2 Communications for monitoring and control of wind power plants Extension of Information models for Wind Power Plants. IEC 61850-8-1 Specific Communication Service Mapping (SCSM) Mappings to MMS (ISO/IEC 9506- Part 1 and Part 2) and to ISO/IEC 8802-3 Communication mapping in the entire station (client-server communication for SCADA functions and GOOSE and GSSE data exchange for real time requirements, for example for tripping signals IEC 61850-9-2 Specific Communication Service Mapping (SCSM) Sample Values over ISO/IEC 8802-3 Mapping for bus-type, flexible communication of sample values from instrument transformers (with and without Merging Unit) IEC 61850-10 Conformance Testing Basic Conformance testing methods
Page 30 of 38
7.3
The following figures show the request and response messages of the service <GetDataValues for DIPS_GGIO1.Ind3>. This message comprises all layers from Data Link (Ethernet), over IP, TCP, upper layers including MMS. The IEC 61850-7-2 service <GetDataValues for DIPS_GGIO1.Ind3> is mapped to a MMS Read Request message. The Item Name at the bottom (ItemName) is DIPS_GGIO1$ST$nd3. The $ is used as the MMS-Separator (instead of a .). The ST is indicating the status information (stVal, q and t). The DomainName is used to carry the Logical Device Name of the IEC 61850. The Logical Device is (as for now) a container that contains Logical Nodes. Read Request:
The MMS response message contains a Structure of three components with the value and the corresponding Type. The first value is of type BOOLEAN (it represents the stVal). The second type is a Bitstring (that represents the quality information). The last component is the UTC time stamp note that the time of the clock was not synchronized during the test.
Page 31 of 38
7.4
LN Group
L System LNs
A Automatic Control
C Control
7-420 Ed1 IS 7-420 7-420 7-420 7-420 7-420 7-420 7-420 7-420 7-420 7-420 7-420 7-420 7-420 7-420 7-420 Ed1 Ed1 Ed1 Ed1 Ed1 Ed1 Ed1 Ed1 Ed1 Ed1 Ed1 Ed1 Ed1 Ed1 Ed1 IS IS IS IS IS IS IS IS IS IS IS IS IS IS IS
Page 32 of 38
IPC@CHIP DK61 Getting Started IEC 618580 Basics V.1.00 LN Group # 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 Clause 7.3.4 7.3.5 7.3.6 7.4.3 7.4.4 7.4.5 7.1.3 7.2.3 8.1.3 5.6.2 5.6.3 5.6.4 5.6.5 5.6.6 5.6.7 5.6.8 5.6.9 5.6.10 7.2.2 7.2.3 7.2.4 7.2.5 7.2.6 7.2.7 7.2.8 7.2.9 7.2.10 8.4.2 5.7.2 5.7.3 5.7.4 5.7.5 7.3.2 7.3.3. 7.3.4 7.3.5 7.3.6 7.3.7 7.3.8 7.3.9 7.3.10 7.3.11 7.3.12 7.3.13 7.3.14 7.3.15 7.3.16 7.3.17 7.3.18 7.3.19 Description Photovoltaics array characteristics Photovoltaics array controller Tracking controller CHP system controller Thermal storage Boiler Reciprocating Engine Fuel cell controller Fuel delivery system Counter Curve shape description Generic Filter Control function output limitation PID regulator Ramp function Set-point control function Action at over threshold Action at under threshold Counter Curve shape description Generic Filter Control function output limitation PID regulator Ramp function Set-point control function Action at over threshold Action at under threshold Sequencer Generic automatic process control Generic process I/O Generic log Generic security application Turbine - generator shaft bearing Combinator Hydropower dam Dam leakage supervision Gate position indicator Dam gate Intake gate Joint control Leakage supervision Water level indicator Mechanical brake Needle control Water net head data Dam over-topping protection Hydropower / water reservoir Hydropower unit sequencer Speed monitoring Hydropower unit Name DPVA DPVC DTRC DCHC DCTS DCHB DCIP DFCL DFLV FCNT FCSD FFIL FLIM FPID FRMP FSPT FXOT FXUT FCNT FCSD FFIL FLIM FPID FRMP FSPT FXOT FXUT FSEQ GAPC GGIO GLOG GSAL HBRG HCOM HDAM HDLS HGPI HGTE HITG HJCL HLKG HLVL HMBR HNDL HNHD HOTP HRES HSEQ HSPD HUNT Document 7-420 Ed1 IS 7-420 Ed1 IS 7-420 Ed1 IS 7-420 Ed1 IS 7-420 Ed1 IS 7-420 Ed1 IS 7-420 Ed1 IS 7-420 Ed1 IS 7-420 Ed1 IS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-410 Ed1 IS 7-410 Ed1 IS 7-410 Ed1 IS 7-410 Ed1 IS 7-410 Ed1 IS 7-410 Ed1 IS 7-410 Ed1 IS 7-410 Ed1 IS 7-410 Ed1 IS 7-420 Ed1 IS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-410 Ed1 IS 7-410 Ed1 IS 7-410 Ed1 IS 7-410 Ed1 IS 7-410 Ed1 IS 7-410 Ed1 IS 7-410 Ed1 IS 7-410 Ed1 IS 7-410 Ed1 IS 7-410 Ed1 IS 7-410 Ed1 IS 7-410 Ed1 IS 7-410 Ed1 IS 7-410 Ed1 IS 7-410 Ed1 IS 7-410 Ed1 IS 7-410 Ed1 IS 7-410 Ed1 IS
Page 33 of 38
F Functional Blocks
G Generic
H Hydro Power
IPC@CHIP DK61 Getting Started IEC 618580 Basics V.1.00 LN Group # 94 95 96 97 I 98 Interfacing 99 and Archiving 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 Clause 7.3.20 5.8.2 5.8.3 5.8.4 5.8.5 5.8.6 5.8.7 7.4.2 5.9.2 5.9.3 5.9.4 5.9.5 5.9.6 7.5.2 7.5.3 7.5.4 7.5.5 7.5.6 5.10.2 5.10.3 5.10.4 5.10.5 5.10.6 5.10.7 5.10.8 5.10.9 5.10.10 5.10.11 5.10.12 5.10.13 5.10.14 7.6.2 7.6.3 7.6.4 7.6.5 8.1.2 8.5.3 8.5.4 8.5.5 8.5.7 5.11.2 5.11.3 5.11.4 5.11.5 5.11.6 5.11.7 5.11.8 5.11.9 Description Water control Archiving Human machine interface Safety alarm function Telecontrol interface Telemonitoring interface Teleprotection communication interfaces Safety alarm function Fan Filter Pump Tank Valve control Fan Filter Pump Tank Valve control Environmental information Flicker Measurement Name Harmonics or interharmonics Non phase related harmonics or interharmonics Hydrological information DC measurement Meteorological information Metering Metering Non phase related Measurement Measurement Sequence and imbalance Metering Statistics Environmental information Hydrological information DC measurement Meteorological information Fuel characteristics Pressure measurements Heat measured values Flow measurements Emissions measurements Differential Direction comparison Distance Directional overpower Directional underpower Rate of change of frequency Harmonic restraint Ground detector Name HWCL IARC IHMI ISAF ITCI ITMI ITPC ISAF KFAN KFIL KPMP KTNK KVLV KFAN KFIL KPMP KTNK KVLV MENV MFLK MHAI MHAN MHYD MMDC MMET MMTN MMTR MMXN MMXU MSQI MSTA MENV MHYD MMDC MMET MFUL MPRS MHET MFLW MENV PDIF PDIR PDIS PDOP PDUP PFRC PHAR PHIZ Document 7-410 Ed1 IS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-410 Ed1 IS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-410 Ed1 IS 7-410 Ed1 IS 7-410 Ed1 IS 7-410 Ed1 IS 7-410 Ed1 IS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-410 Ed1 IS 7-410 Ed1 IS 7-410 Ed1 IS 7-410 Ed1 IS 7-420 Ed1 IS 7-420 Ed1 IS 7-420 Ed1 IS 7-420 Ed1 IS 7-420 Ed1 IS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS
Page 34 of 38
116 117 118 119 120 121 M Metering and 122 measurement 123 124 125 126 127 128 129 130 131 132 133 P 134 Protection 135 functions 136 137 138 139 140 141
2010 Beck IPC GmbH
IPC@CHIP DK61 Getting Started IEC 618580 Basics V.1.00 LN Group # 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 Q 168 Power quality 169 events 170 171 172 Clause 5.11.10 5.11.11 5.11.12 5.11.13 5.11.14 5.11.15 5.11.16 5.11.17 5.11.18 5.11.19 5.11.20 5.11.21 5.11.22 5.11.23 5.11.24 5.11.25 5.11.26 5.11.27 5.11.28 5.11.29 5.11.30 5.11.31 7.7.2 7.7.3 5.12.2 5.12.3 5.12.4 5.12.5 5.12.6 5.12.7 5.13.2 Description Instantaneous overcurrent Motor restart inhibition Motor starting time supervision Over power factor Phase angle measuring Rotor protection Protection scheme Sensitive directional earthfault Transient earth fault Tyristor protection Time overcurrent Overfrequency Overvoltage Protection trip conditioning Thermal overload Undercurrent Underfrequency Undervoltage Underpower factor Voltage controlled time overcurrent Volts per Hz Zero speed or underspeed Rotor protection Thyristor protection Frequency Variation Current Transient Current Unbalance Variation Voltage Transien Voltage Unbalance Variation Voltage Variation Disturbance recorder channel analogue Disturbance recorder channel binary Breaker failure Directional element Disturbance recorder function Disturbance record handling Fault locator Differential measurements Power swing detection/blocking Autoreclosing Synchronism-check synchronising or synchro-check device Monitoring and diagnostics for arcs Circuit breaker supervision Insulation medium supervision (gas) Insulation medium supervision Name PIOC PMRI PMSS POPF PPAM PRTR PSCH PSDE PTEF PTHF PTOC PTOF PTOV PTRC PTTR PTUC PTUF PTUV PUPF PVOC PVPH PZSU PRTR PTHF QFVR QITR QIUB QVTR QVUB QVVR RADR RBDR RBRF RDIR RDRE RDRS RFLO RMXU RPSB RREC RSYN RSYN SARC SCBR SIMG SIML Document 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-410 Ed1 IS 7-410 Ed1 IS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-410 Ed1 IS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS
Page 35 of 38
173 5.13.3 174 175 176 177 178 179 180 181 182 183 5.13.4 5.13.5 5.13.6 5.13.7 5.13.8 5.13.9 5.13.10 5.13.11 5.13.12 7.8.2
IPC@CHIP DK61 Getting Started IEC 618580 Basics V.1.00 LN Group # Clause Description (liquid) Tap changer Supervision Supervision of Operating Mechanism Monitoring and diagnostics for partial discharges Power Transformer Supervision Circuit Switch Supervision Temperature supervision Vibration supervision temperature supervision vibration supervision Vibration conditions Temperature measurements Angle Axial displacement Current transformer Distance Liquid flow Frequency Generic sensor Humidity LMedia level Magnetic field Movement senso Position indicator Pressure sensor Rotation transmitter Sound pressure sensor Temperature sensor Mechanical tension / stress Vibration sensor Voltage transformer Water acidity Angle sensor Axial displacement sensor Distance sensor Flow sensor Frequency sensor Humidity sensor Level sensor Magnetic field sensor Movement sensor Position indicator Pressure sensor Rotation transmitter Sound pressure sensor Temperature sensor Mechanical tension /stress sensor Vibration sensor Name SLTC SOPM SPDC SPTR SSWI STMP SVBR STMP SVBR SVBR STMP TANG TAXD TCTR TDST TFLW TFRQ TGSN THUM TLVL TMGF TMVM TPOS TPRS TRTN TSND TTMP TTNS TVBR TVTR TWPH TANG TAXD TDST TFLW TFRQ THUM TLEV TMGF TMVM TPOS TPRS TRTN TSND TTMP TTNS TVBR Document 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-410 Ed1 IS 7-410 Ed1 IS 7-420 Ed1 IS 7-420 Ed1 IS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-410 Ed1 IS 7-410 Ed1 IS 7-410 Ed1 IS 7-410 Ed1 IS 7-410 Ed1 IS 7-410 Ed1 IS 7-410 Ed1 IS 7-410 Ed1 IS 7-410 Ed1 IS 7-410 Ed1 IS 7-410 Ed1 IS 7-410 Ed1 IS 7-410 Ed1 IS 7-410 Ed1 IS 7-410 Ed1 IS 7-410 Ed1 IS
Page 36 of 38
188 5.14.6 189 5.14.7 190 5.14.8 191 192 193 194 195 196 197 198 T 199 Instrument 200 Ttransformers 201 and sensors 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232 233 234
2010 Beck IPC GmbH
5.14.9 5.14.10 5.14.11 5.14.12 7.9.2 7.9.3 8.5.6 8.5.2 5.15.2 5.15.3 5.15.4 5.15.5 5.15.6 5.15.7 5.15.8 5.15.9 5.15.10 5.15.11 5.15.12 5.15.13 5.15.14 5.15.15 5.15.16 5.15.17 5.15.18 5.15.19 5.15.20 5.15.21 7.10.2 7.10.3 7.10.4 7.10.5 7.10.6 7.10.7 7.10.8 7.10.9 7.10.10 7.10.11 7.10.12 7.10.13 7.10.14 7.10.15 7.10.16 7.10.17
IPC@CHIP DK61 Getting Started IEC 618580 Basics V.1.00 LN Group # Clause 235 7.10.18 236 Table 7 237 Table 8 238 Table 9 Description Water pH sensor Wind turbine general information Wind turbine rotor information Name TWPH WTUR WROT Document 7-410 Ed1 IS 61400-25-2 Ed1 IS 61400-25-2 Ed1 IS 61400-25-2 Ed1 IS 61400-25-2 Ed1 IS 61400-25-2 Ed1 IS 61400-25-2 Ed1 IS 61400-25-2 Ed1 IS 61400-25-2 Ed1 IS 61400-25-2 Ed1 IS 61400-25-2 Ed1 IS 61400-25-2 Ed1 IS 61400-25-2 Ed1 IS 61400-25-2 Ed1 IS 61400-25-2 Ed1 IS 61400-25-2 Ed1 IS 61400-25-2 Ed1 IS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-420 Ed1 IS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS
Wind turbine transmission WTRM information 239 Table 10 Wind turbine generator information WGEN 240 Table 11 Wind turbine converter information 241 Table 12 Wind turbine transformer information 242 Table 13 Wind turbine nacelle information 243 Table 14 Wind turbine yawing information W Wind Turbines 244 Table 15 Wind turbine tower information 245 Table 16 Wind power plant meteorological information 246 Table 17 Wind power plant alarm information 247 Table 18 Wind turbine state log information 248 Table 19 Wind turbine analogue log information 249 Table 20 Wind turbine report information 250 Table 21 Wind power plant active power control information 251 Table 22 Wind power plant reactive power control information 252 5.16.2 Circuit breaker 253 5.16.3 Circuit switch 254 8.3.2 Fuse 255 5.17.2 Earth fault neutralizer (Petersen coil) 256 5.17.3 Tap changer 257 5.17.4 Power shunt 258 5.17.5 Power transformer WCNV WTRF WNAC WYAW WTOW WMET WALM WSLG WALG WREP WAPC WRPC XCBR XSWI XFUS YEFN YLTC YPSH YPTR
Page 37 of 38
IPC@CHIP DK61 Getting Started IEC 618580 Basics V.1.00 LN Group # 259 260 261 262 263 264 265 266 267 268 269 270 Z 271 further power 272 system 273 equipment 274 275 Clause 5.18.2 5.18.3 5.18.4 5.18.5 5.18.6 5.18.7 5.18.8 5.18.9 5.18.10 5.18.11 5.18.12 5.18.13 5.18.14 5.18.15 5.18.16 5.18.17 5.18.18 Description Auxiliary network Battery Bushing Power cable Capacitor bank Converter Generator Gas insulated line Power overhead line Motor Reactor Resistor Rotating reactive component Surge arrestor Semi-conductor controlled rectifier Synchronous machine Thyristor controlled frequency converter Thyristor controlled reactive component Neutral resistor Semiconductor rectifier controller Synchronous machine Rectifier Inverter Battery systems Battery charger Name ZAXN ZBAT ZBSH ZCAB ZCAP ZCON ZGEN ZGIL ZLIN ZMOT ZREA ZRES ZRRC ZSAR ZSCR ZSMC ZTCF ZTCR ZRES ZSCR ZSMC ZRCT ZINV ZBAT ZBTC Document 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-4 Ed2 FDIS 7-410 7-410 7-410 7-420 7-420 7-420 7-420 Ed1 Ed1 Ed1 Ed1 Ed1 Ed1 Ed1 IS IS IS IS IS IS IS
276 5.18.19 277 278 279 280 281 282 283 7.11.2 7.11.3 7.11.4 6.4.2 6.4.3 8.2.2 8.2.3
* End of Document *