Gree

Download as pdf or txt
Download as pdf or txt
You are on page 1of 119

P Contents

PRODUCT ......................................................................................................................... 1
1 Product List ........................................................................................................................... 2
2 Nomenclature ........................................................................................................................ 2
3 Specifications ....................................................................................................................... 3
CONTROL ......................................................................................................................... 5
1 Wired Controller.................................................................................................................... 6
2 Remote Controller YAP1F ................................................................................................... 9
3 Introduction to IDU Functions .......................................................................................... 10
4 Monitoring Software ........................................................................................................... 20
INSTALLATION .............................................................................................................. 63
1 Engineering Installation Preparation and Notice .......................................................... 64
2 Installation Materials Selection ........................................................................................ 65
3 Installation of Indoor Unit.................................................................................................. 67
4 Installation of outdoor unit ............................................................................................... 71
5 Installation of drain pipe.................................................................................................... 73
6 Electrical Installation ......................................................................................................... 76
DEBUGGING & MAINTENANCE.................................................................................. 78
1 Debugging of Unit .............................................................................................................. 79
2 Malfunction List .................................................................................................................. 83
3 Troubleshooting.................................................................................................................. 85
4 After-sales Emergency Masures .................................................................................... 104
5 Wiring Diagram ................................................................................................................. 105
6 Disassembly And Assembly Procedure Of Main Parts .............................................. 107
7 Exploded Views And Part List ........................................................................................ 109
Duct type split Air conditioner Inverter Series

PRODUCT

1
Duct type split Air conditioner Inverter Series

1 Product List
Cooling Heating
Capacity Capacity Appearance
Power
Model Refrigerant
Supply
kW kW Outdoor Indoor

FGR20Pd/DNa-X 20 22

FGR25Pd/DNa-X 25 27.5

3N/380-41
FGR30Pd/DNa-X 30 33
5V/50Hz/ R410a
60Hz

FGR40Pd/D(2)Na-X 40 43

2 Nomenclature

2
Duct type split Air conditioner Inverter Series

NO. Description Options


1 Ducted Type Air Conditioner -
Cooling only type-omitted
2 Unit type Heat pump
Auxiliary hot water plate and pipe type-W
3 Cooling capacity Nominal cooling capacity (kW)
Fixed frequency-omitted
4 Frequency conversion system
Frequency conversion-Pd
5 Design No. Arranged based on A, B, C, D,and so on
R22-omitted
R407-N
6 Refrigerant
R410a-Na
Others to be applied for when they are used
380-415V 3Ph~,50/60Hz-X
7 Power type
(The unit to be exported must be expressed)
Outdoor unit-(O)
8 Indoor and outdoor unit code Indoor unit-(I)
The entire unit is not expressed.

3 Specifications
Model Heat pump FGR20Pd/DNa-X FGR25Pd/DNa-X
Cooling kW 20 25
Capacity
Heating kW 22 27.5
EER/COP W/W 2.55/3.25 2.65/3.10
Power supply Ph/V/Hz 3N/380-415/(50/60) 3N/380-415/(50/60)
Cooling kW 7.8 9.4
Power input
Heating kW 6.8 8.9
Cooling A 16.5 18.9
Current input
Heating A 14.4 17.2
Refrigerant charge volume kg 6.4 8.0
CFM 2178 2472
Airflow volume
m3/h 3700 4200
Rated Pa 120 120
ESP
Range Pa 0-250 0-250
Indoor unit
Sound pressure level dB(A) 52 53

Dimension Outline mm 1460×790×365 1690×870×440


(W×D×H) Package mm 1575×880×385 1785×985×450
Net Weight/Gross weight kg 82/104 99/134
Sound pressure level dB(A) 62 63

Dimension Outline mm 940×320×1430 940×460×1615


Outdoor unit
(W×D×H) Package mm 1020×420×1460 1020×560×1645
Net Weight/Gross weight kg 120/130 146/162
Outer Liquid Inch(mm) Φ3/8 Φ3/8
diameter Gas Inch(mm) Φ3/4 Φ7/8
Connection
pipe Height mm 30 30
Max. distance
Length mm 50 50
Loading
20'GP/40'GP/40'HQ set 12/24/24 10/20/22
quantity

3
Duct type split Air conditioner Inverter Series

Model Heat pump FGR30Pd/DNa-X FGR40Pd/D(2)Na-X

Cooling kW 30 40
Capacity
Heating kW 33 43
EER/COP W/W 2.65/3.20 2.60/3.10
Power supply Ph/V/Hz 3N/380-415/(50/60) 3N/380-415/(50/60)
Cooling kW 11.3 15.4
Power input
Heating kW 10.3 13.9
Cooling A 22.7 27.8
Current input
Heating A 20.7 26.4
Refrigerant charge volume kg 9.5 6.4×2
CFM 3060 4120
Airflow volume 3
m /h 5200 7000
Rated Pa 120 120
ESP
Range Pa 0-250 0-250
Indoor unit
Sound pressure level dB(A) 55 56

Dimension Outline mm 1690×870×440 1680X900X650


(W×D×H) Package mm 1785×985×450 1800X1020X670
Net Weight/Gross weight kg 105/145 165/210
Sound pressure level dB(A) 65 66

Dimension Outline mm 940×460×1615 940×320×1430


Outdoor unit
(W×D×H) Package mm 1020×560×1645 1020×420×1460
Net Weight/Gross weight kg 175/190 (120/130) X2

Liquid Inch(mm) Φ1/2 Φ3/8


Outer
diameter
Connection Gas Inch(mm) Φ1 Φ3/4
pipe
Max. Height mm 30 30
distance Length mm 50 50
Loading
20'GP/40'GP/40'HQ set 10/20/22 7/18/18
quantity

Note:
◆Specifications may be changed due to product improvement. Please refer to nameplates of the units.

◆Noise data are collected from a semi-anechoic room. Decibels may be slightly higher in actual operation due to

environmental change.

◆Above parameters are tested under the condition:high fan speed

◆Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB/24°C WB;

◆Heating : Indoor air temperature 20°C DB/15°C WB, Outdoor air temperature 7°C DB/6°C WB.

4
Duct type split Air conditioner Inverter Series

CONTROL

5
Duct type split Air conditioner Inverter Series

1 Wired Controller
1.1 Control panel

Fig1.1 Appearance of wired controller

Fig1.2 LED graphics of wired controller


Table 1.1 LED display instruction
No. Symbols Instructions

1 Up and down swing function

2 * Left and right swing function

It's valid under Save mode and displays during setting process.
Temperature lower limit for Cooling: Limit the minimum temperature value
under Cooling or Dry mode.
3
Temperature upper limit for Heating: Limit the maximum temperature value
under Heating, Space Heating or 3D Heating
mode.
Auto mode (Under Auto mode, the indoor units will automatically select their
4 * operating mode as per the temperature
change so as to make the ambient comfortable.)
It shows the setting temperature value(In case the wired controller is controlling
5 a Fresh Air Indoor Unit, then the
temperature zone will display FAP)

6 Cooling mode

7 Dry mode

8 Fan mode

6
Duct type split Air conditioner Inverter Series

No. Symbols Instructions

9 Heating mode

10 When inquiring or setting project number of indoor unit, it displays "NO." icon
Floor Heating mode (When Heating and Floor Heating simultaneously shows
11 *
up, it indicates 3D Heating is activated.)

12 Display "SET" icon under parameter setting interface

13 - * Space Heating mode

14 Display "CHECK" icon under parameter view interface


Outdoor unit operates under Save mode/upper limit of system capacitor less
15
100%/remote Save status

16 Sleep status

Current set fan speed (including auto, low speed, medium-low speed, medium
17 speed, medium-high speed, high speed
and turbo seven status)

18 * Air status, Indoor unit optional function

19 Remind to clean the filter

20 Quiet status (including Quiet and Auto Quiet two status)

21 * Allow auxiliary electric heating On icon

22 Light On/Off function

23 X-fan function

24 * Health function, Indoor unit optional function

25 * Reserved function

26 Out function

27 Outdoor unit defrosting status

28 Gate-control function

29 Shielding status

30 Child Lock status

31 One wired controller controls multiple indoor units

32 Save status of indoor unit

It indicates the current wired controller is the slave wired controller (address of
33
wired controller is 02)
Memory status (The indoor unit resumes the original setting state after power
34
failure and then power recovery)

35 Invalid operation

36 Current wired controller connects master indoor unit

37 Timer zone:Display system clock and timer status

Note: When wired controller is connected with different indoor units, some functions will be different

1.2 Installation and removal


1.2.1 Installation dimensions

7
Duct type split Air conditioner Inverter Series

Fig1.3 Installation dimensions


1.2.2 Installation method

Fig1.4 Installation of Wired Controller

Above is a simple installation method of wired controller. Please pay attention to the following:
◆Before installation, disconnect power of the indoor unit. Do not operate when power is connected.
◆Pull out the 2-core twisted pair cable from the installation hole on the wall and lead it through the hole
on the back plate of wired controller.
◆Place the wired controller on wall and secure its back plate on wall with screw M4X25.
◆Connect the 2-core twisted pair cable to terminal H1 and terminal H2. Tighten up the screws.
◆Stick the cable in the slot that is left of the terminals and buckle the wired controller’s panel with its
back plate.
Note:
If caliber of the communication cord is too large, which causes difficulty in leading or sticking the cord
according to above point 2 and point 5, strip some of the sheath of the communication cable to meet the
installation requirement.
1.2.3 Removal method
8
Duct type split Air conditioner Inverter Series

Fig1.5 Removal of Wired Controller


1.2.4 Connection of communication cord

Fig1.6 One wired controller controls one indoor unit

2 Remote Controller YAP1F

9
Duct type split Air conditioner Inverter Series

Button name and function introduction

No. Button name Function


1 ON/OFF Turn on or turn off the unit
2 TURBO Set turbo function
3 MODE Set operation mode

4 Set up&down swing status

5 I FEEL Set I FEEL function


6 TEMP Switch temperature displaying type on the unit’s display

7 Set health function and air function

8 LIGHT Set light function


9 X-FAN Set X-FAN function
10 SLEEP Set sleep function
11 CLOCK Set clock of the system
12 TOFF Set timer off function
13 TON Set timer on function

14 Set left&right swing status

15 FAN Set fan speed

3 Introduction to IDU Functions


Indoor unit functions cover user operation functions and engineering application functions. For user
operation functions, refer to wired controller and remote controller.
Engineering application functions include:

SN Function Name
1 User parameter query

10
Duct type split Air conditioner Inverter Series

2 User parameter settings


3 Engineering parameter query
4 Engineering parameter settings
Engineering application functions can be operated through the IDU wired controller(XK46).
3.1 User Parameter Query
User parameters can be queried in power-on or power-off status.
(1) Press and hold the “FUNCTION” button for five seconds to enter the user parameter query interface.
The temperature area displays “C00” and “View” is on.
(2) Select a parameter code by pressing “ ” or “ ”.
(3) Press the “ENTER/CANCEL” button to return to the upper-level menu till quitting parameter query.
The user parameter query list is as follows:
Parameter Parameter
Parameter Name View Method
Code Range
Display mode:
 Timer area: displays the project number of the
Parameter current IDU.
C00 -
setting ingress Note: If the current HBS network consists of multiple
IDUs, only the IDU that has the minimum project
number is displayed.
Operation method:
In “C06” status, press the “MODE” button to enter the
00: common preferential operation query interface. Press “ ” or “ ” to
operation switch the IDU SN.
Preferential
C06 01: Display mode:
operation query
preferential Temperature area: displays the project number of the
operation current IDU.
Timer area: displays the preferential operation setting
value of the current IDU.
Operation method:
In “C07” status, press the “MODE” button to enter the
indoor environment temperature query interface. Press "
Indoor
" or " " to switch the IDU SN.
environment
C07 -9 to 99 Display mode:
temperature
Temperature area: displays the project number of the
query
current IDU.
Timer area: displays the temperature value of the indoor
environment temperature sensor after replenishment.
Prompt time
C08 query for air filter 4-416: days Timer area: displays the prompt time for air filter cleaning.
cleaning
Wired controller Timer area: displays the adress of the current wired
C09 01, 02
adress query controller.
Outdoor
environment Timer area: displays the temperature value of the
C12 -9 to 99
temperature environment temperature sensor of the master ODU.
query
Operation method:
In “C17” status, press the “MODE” button to enter the
indoor relative humidity query interface. Press “▲” or “▼”
to switch the IDU SN.
Display mode:
Indoor relative
C17 20-90 Temperature area: displays the relative humidity value.
humidity query
Timer area: displays the project number of IDU (project
numberes are arranged from small to large).
If the HBS network consists of only one IDU, the timer
area directly displays the IDU relative humidity value in
the “C17” interface.

11
Duct type split Air conditioner Inverter Series

Note:

In parameter query status, "FAN", “TIMER”, "SLEEP", and "SWING" are invalid. By pressing the
“ON/OFF” button, users can return to the main interface but not power on/off the unit.
3.2 User Parameter Settings
User parameters can be set in power-on or power-off status.

(1) Press and hold the “FUNCTION” button for five seconds. The temperature area displays “C00”.
Press and hold the “FUNCTION” button for another five seconds to enter the wired controller
parameter setting interface. The temperature area displays “P00”.

(2) Select a parameter code by pressing “ ” or “ ”. Press the “MODE” button to switch to parameter
value settings. The parameter value blinks. Adjust the parameter value by pressing “ ” or “ ” and
then press the “ENTER/CANCEL” button to complete settings.

(3) Press the “ENTER/CANCEL” button to return to the upper-level menu till quitting parameter
settings.
(4) The user parameter setting list is as follows:
Parameter Parameter Default
Parameter Range Remark
Code Name Value
00: does not change the
After the IDU connected
master/slave status of the
Master IDU with the current wired controller is
P10 current IDU 00
settings successfully set to master IDU, "MASTER"
01: sets the current IDU on the wired controller is on.
to master IDU
This setting can only be enabled through the
master wired controller.
Infrared
connection 00: disabled When the infrared remote receiving function
P11 01 of the wired controller is disabled, neither the
settings of 01: enabled
wired controller master nor slave wired controller can receive
remote signals. The wired controllers can
only be operated by pressing.
When two wired controllers simultaneously
control one IDU, the two wired controllers
Wired controller 01: master wired
should use different addresses. The slave
P13 address controller 01
wired controller (address: 02) does not have
settings 02: slave wired controller
the unit parameter setting function except its
own address settings.
After identifying the IDU type, the wired
controller only displays the available
static pressure levels.
1) The static pressure levels fall into five
levels and nine levels for VRF IDUs. The
wired controller only displays the static
pressure levels matched with the
identified IDU type.
Type 1: 03.04.05.06.07 2) When the HBS network consists of IDUs
Static pressure
P30 settings for Type 2: 05 with both five and nine static pressure
indoor fan 01.02.03.04.05.06.07.08. levels, the wired controller displays nine
09 adjustable static pressure levels
according to the maximum control
principle. If the static pressure levels
received by the IDU from the wired
controller, remote controller, or remote
monitoring system exceed the setting
range, the limit value prevails.
3)During power-on and synchronization, the
setting value of static pressure levels is

12
Duct type split Air conditioner Inverter Series

Parameter Parameter Default


Parameter Range Remark
Code Name Value
determined by settings of the IDU.
00: standard-ceiling
High-ceiling installation height
P31 00
installation 01: high-ceiling
installation height
Timer function 00: common timing
P33 00
settings 01: time-point timing
Repeating
validity for 00: single timing This setting is valid only when the timer
P34 00
time-point 01: repeated everyday function is set to time-point timing.
timing
Cooling setting
P37 temperature in 17°C -30°C 25 Cooling setting temperature – heating setting
automatic mode temperature ≥ 1.
Heating setting Note: The two settings are still valid in
P38 temperature in 16°C -29°C 20 remote shielding status.
automatic mode
When power supply is insufficient, users are
Preferential 00: common operation allowed to power on/off the IDU set with
P43 operation 00 preferential operation and other IDUs are
settings 01: preferential operation forcibly powered off. A fault code is displayed
on the IDU that is forcibly powered off.
Accumulated
time clearing for 00: not cleared
P46 00
air filter 01: cleared
cleaning

Note:
In parameter setting status, "FAN", “TIMER”, "SLEEP", and "SWING" are invalid. By pressing the
“ON/OFF” button, users can return to the main interface but not power on/off the unit.
3.3 Engineering Parameter Query
Engineering parameters can be queried in power-on or power-off status.
Press and hold the “FUNCTION” button for five seconds to enter the engineering parameter query
interface. The temperature area displays “C00” and “View” is on.
(1) Within five seconds after “C00” is displayed, continuously press the “MODE” button for three times in
an interval less than one second to enter engineering parameter query.
(2) Select a parameter code by pressing “ ” or “ ”.
(3) Press the “ENTER/CANCEL” button to return to the upper-level menu till quitting parameter query.
In the engineering parameter query interface, users can also query user parameters listed in Table 3.1.
The engineering parameter query list is as follows:
Parameter Parameter
Parameter Name View Method
Code Range
Display mode:
Parameter setting Timer area: displays the project number of the current IDU.
C00 -
ingress (default) Note: If the current HBS network consists of multiple IDUs, only
the IDU that has the minimum project number is displayed.
Operation method:
Indoor unit In “C02” status, press the “MODE” button to enter the preferential
C02 -
capacity query operation query interface. Press " " or " " to switch the project
number of IDU.

13
Duct type split Air conditioner Inverter Series

Parameter Parameter
Parameter Name View Method
Code Range
Display mode:
Temperature area: displays the project number of the current IDU.
Timer area: displays the current IDU capacity/IDU capacity after
adjustment.
Operation method:
1. In “C05” status, press the “MODE” button to enter the historical
fault query interface. Press " " or " " to switch the project
Historical fault number of IDU. Press the “MODE” button to enter fault code query
Five historical of the current IDU. Press “ ” or “ ” to switch the fault SN. Press
C05 query ingress of
faults the “ENTER/CANCEL” button to return to the upper-level menu.
IDU
Display mode:
Temperature area: displays the fault SN and fault code.
Timer area: displays the project number of IDU.
Operation method:
In “C10” status, press the “MODE” button to enter static pressure
00: 0 Pa
Static pressure setting query of ODU. Press " " or " " to switch the ODU
20: 20 Pa
C10 setting query of address.
50: 50 Pa
ODU Display mode:
82: 82 Pa
Temperature area: displays the address of the current ODU.
Timer area: displays the static pressure setting value.
Outdoor unit
C13 network number 1-255 Timer area: displays the network number of the current ODU.
query
Operation method:
In “C14” status, press the “MODE” button to enter inlet-tube
temperature sensor query of IDU. Press " " or " " to switch the
IDU SN.
Display mode:
Temperature Temperature area: displays the project number of the current IDU.
query for Timer area: displays the temperature value.
C14 inlet-tube -9 to 99 If the HBS network consists of only one IDU, the timer area
temperature directly displays the temperature value in the “C14” interface.
sensor of IDU
No matter Fahrenheit or Centigrade remote signals are received,
the temperature is displayed in Centigrade.
When the wired controller displays the inlet-tube temperature after
receiving signals from the remote controller, the inlet-tube
temperature of the IDU that has the minimum project number in the
HBS network is displayed by default.

14
Duct type split Air conditioner Inverter Series

Parameter Parameter
Parameter Name View Method
Code Range
Operation method:
In “C15” status, press the “MODE” button to enter outlet
temperature sensor query of IDU. Press " " or " " to switch the
IDU SN.
Display mode:
Temperature area: displays the project number of the current IDU.
Temperature
Timer area: displays the temperature value.
query for outlet
C15 -9 to 99 If the HBS network consists of only one IDU, the timer area
temperature
sensor of IDU directly displays the temperature value in the "C14" interface.
No matter Fahrenheit or Centigrade remote signals are received,
the temperature is displayed in Centigrade.
When the wired controller displays the inlet-tube temperature after
receiving signals from the remote controller, the inlet-tube
temperature of the IDU that has the minimum project number in the
HBS network is displayed by default.
Operation method:
In “C16” status, press the “MODE” button to enter electronic
expansion valve opening degree query of IDU. Press " " or " "
to switch the IDU SN.
Display mode:
Temperature area: displays the project number of the current IDU.
Opening degrees
query of electronic Timer area: displays the opening degree value.
C16 0-20 If the HBS network consists of only one IDU, the timer area
expansion valve
of IDU directly displays the opening degree value of electronic expansion
valve in the “C16” interface.
When the wired controller displays the opening degree of
electronic expansion valve after receiving signals from the remote
controller, the opening degree of electronic expansion valve of the
IDU that has the minimum project number in the HBS network is
displayed by default.
Capacity
Temperature area: displays the parameter code.
configuration ratio 35: 135%
n2 Timer area: displays the setting value of capacity configuration
upper-limit of 50: 150%
ratio of the current outdoor/IDU.
outdoor/IDU

Operation method:
In “n6” status, press the “MODE” button to enter fault code query
of ODU (when a wired controller controls multiple IDUs, only the
faults memorized by the IDU that has the minimum project number
Historical fault can be queried). Press “ ” or “ ” to switch the fault SN. Press
Five historical
n6 query ingress of the “ENTER/CANCEL” button to return to the upper-level menu.
faults
ODU
Display mode:
Temperature area: displays the fault SN and fault code from left to
right (1-5, faults are arranged from the earliest to the latest).
Timer area: displays the project number of the ODU.

Operation method (n7 query is not supported for the slave wired
controller):
In “n7” status, the timer area is not displayed. Press the “MODE”
Parameter query 01-13 button to enter parameter query of ODU. The first bit in the
n7 temperature area (display bit of the ODU module ID) blinks. Press
ingress of ODU 25-29 “▲” or “▼” to switch the ODU module ID. Press the “MODE”
button to select an ODU module. In this case, the first bit in the
temperature area stops blinking, and the second and third bits in
the temperature area display the parameter code. The timer area

15
Duct type split Air conditioner Inverter Series

Parameter Parameter
Parameter Name View Method
Code Range
displays a corresponding parameter value. Press “▲” or “▼” to
switch the parameter code and press the “ENTER/CANCEL”
button to return to the upper-level menu.
Display mode:
Temperature area: displays the ODU module ID and parameter
code from left to right.
Timer area: displays a corresponding parameter value to the right.
Parameter
Parameter Name Unit
Code
Outdoor environment
01 °C
temperature
Operation frequency of
02 Hz
compressor 1
Operation frequency of
03 Hz
compressor 2
Operation frequency of outdoor
04 Hz
fan
05 Module high-pressure °C
06 Module low-pressure °C
Discharge temperature of
07 °C
compressor 1
Discharge temperature of
08 °C
compressor 2
Discharge temperature of
09 °C
compressor 3
Discharge temperature of
10 °C
compressor 4
Discharge temperature of
11 °C
compressor 5
Discharge temperature of
12 °C
compressor 6
Operation frequency of
13 Hz
compressor 3
Outdoor unit heating EXV1
25 (Actual value = Displayed value * PLS
10)
Outdoor unit heating EXV2
26 (Actual value = Displayed value * PLS
10)
Subcooler EXV
27 (Actual value = Displayed value * PLS
10)
28 Defrosting temperature °C
Liquid-extracting temperature of
29 °C
subcooler
Outlet temperature of
30 °C
accumulator
31 Oil return temperature °C
Inlet-tube temperature of
32 °C
condenser
33 Outlet temperature of condenser °C
nA:
cooling/heating
Unit nC: Temperature area: displays the parameter code.
A6 cooling/heating single-cooling Timer area: displays the cooling/heating function setting value of
function nH: the current unit.
single-heating
nF: air supply
Operation method (nb query is not supported for the slave wired
controller):
Bar code query of
nb 0-9, A-Z, a-z, - In “nb” status, the timer area is not displayed. Press the “MODE”
IDU
button to enter bar code query. The temperature area displays
“nb” and the project number in the timer area blinks. Press “▲” or

16
Duct type split Air conditioner Inverter Series

Parameter Parameter
Parameter Name View Method
Code Range
“▼” to switch the project number of IDU.
Press the “MODE” button to select an IDU. The temperature area
displays “Un” and the timer area displays “-n”. Press “▲” or “▼” to
display the entire-unit bar code and controller bar code of IDU.
Press the “ENTER/CANCEL” button to return to the upper-level
menu. The temperature area displays “nb” and the timer area
displays the project number of the queried IDU. Press the
“ENTER/CANCEL” button again to return to the upper-level menu.
Display mode:
Temperature area: displays nb/Un/Pc/bar code.
Timer area: displays -n/project number/bar code.
The following is an example:
Temperature Timer
Example Remark 1 Remark 2
Area Area
It indicates
that the
-n
Un (to the following is
(in the
right) the entire-unit
middle)
bar code of
IDU.
Entire-init bar
It indicates
code of IDU
the former
N1r0128150066 N1r 0128
seven bits of
the bar code.
It indicates
the latter six Press “▼” to
150 066
bits of the bar display
code. downward and
It indicates press “▲” to
that the display
following is upward.
Pc -n
the controller
bar code of
IDU.
Controller bar
It indicates
code of IDU
the former
N1r0128150067 N1r 0128
seven bits of
the bar code.
It indicates
the latter six
150 067
bits of the bar
code.

Note:
1. Un indicates the entire-unit bar code of IDU and Pc indicates
the controller bar code of IDU.
2. When there is only one IDU, press the “MODE” button in “nb”
status to enter bar code query without selecting the project
number of IDU.
3. The system quits the query status if no operations are
performed in 60 seconds.
4. The bar code query starts from the entire-unit bar code of IDU
and ends at the controller bar code of IDU without circulation. That
is, the query does not start again even if users press “▼”.

Note:
In parameter query status, "FAN", “TIMER”, "SLEEP", and "SWING" are invalid. By pressing the
“ON/OFF” button, users can return to the main interface but not power on/off the unit.
3.4 Engineering Parameter Settings
Engineering parameters can be set in power-on or power-off status.

17
Duct type split Air conditioner Inverter Series

(1) Press and hold the “FUNCTION” button for five seconds. The temperature area displays “C00”.
Continuously press the “MODE” button for three times, and then press and hold the
“FUNCTION” button for five seconds to enter the engineering parameter setting interface. The
temperature area displays “P00”.
(2) Select a parameter code by pressing “ ” or “ ”. Press the “MODE” button to switch to parameter
value settings. The parameter value blinks. Adjust the parameter value by pressing “ ” or “ ” and
then press the “ENTER/CANCEL” button to complete settings.
(3) Press the “ENTER/CANCEL” button to return to the upper-level menu till quitting parameter
settings.
In the engineering parameter setting interface, users can also set user parameters. The engineering
parameter setting list is as follows:
Parameter
Parameter Name Parameter Range Default Value Remark
Code
00: standby after
power-down recovery
Power-down
P15 01: restoring the original 00 --
memory mode
status after power-down
recovery
Historical faults of all IDUs controlled
Historical fault 00: not cleared
P17 00 by the current wired controller are
clearing for IDU 01: cleared
cleared.
01: temperature sensor
When there are master and slave
of air return vent
wired controllers and the
02: temperature sensor temperature sensor of wired
of wired controller controller is used, only the
03: temperature sensor temperature sensor of the master
of air return vent for wired controller is used by default.
cooling, dehumidifying, Note:
Environment and air supply;
temperature 1) In automatic mode, the
P20 temperature sensor of 03
sensor settings environment temperature sensor
wired controller for
for IDU settings are invalid for a common
heating
IDU but the setting value is
04: temperature sensor memorized.
of wired controller for
2)The environment temperature
cooling, dehumidifying,
sensor settings are invalid for a
and air supply;
fresh-air IDU. The temperature
temperature sensor of
sensor of air return vent is used by
air return vent for
default.
heating
Corrected value
of environment Temperature
temperature sensor of unit:
Press “ ” or “ ” to add or reduce
P21 sensor of IDU (for -15 to +15 0°C; temperature
by 1°C.
cooling, sensor of wired
dehumidifying, controller: 0°C
and air supply)
Press ” ” or ” ” to add or reduce
by 1°C.
Corrected value
Temperature The temperature sensor of unit and
of environment
sensor of unit: the temperature sensor of wired
temperature
-2°C; controller share the same corrected
P22 sensor of IDU (for -15 to +15
temperature value.
heating, fast
sensor of wired In heating mode, corrected value of
heating, and air
controller: 0°C temperature sensor of unit =
warming)
corrected value of temperature
sensor of wired controller - 2°C.
P32 Capacity -40% to +40% 00 Press " " or " " to add or reduce

18
Duct type split Air conditioner Inverter Series

Parameter
Parameter Name Parameter Range Default Value Remark
Code
adjustment by 10%.
function of IDU
Select "01" and then press and hold
Factory setting 00: invalid the “ENTER/CANCEL” button to
P35 recovery for user 00 restore the factory settings for user
functions 01: valid functions (factory setting recovery
fails if remote shielding is valid).
Select "01" and then press and hold
Factory setting the “ENTER/CANCEL” button to
recovery for 00: invalid restore the factory status for
P36 00
engineering 01: valid engineering settings (factory setting
settings recovery fails if remote shielding is
valid).
00: disabled
10: 10 seconds
20: 20 seconds It indicates the number of seconds
Prevention for
P40 30: 30 seconds 00 for enabling the low-level fan every
heat collection
40: 40 seconds 15 minutes.
50: 50 seconds
60: 60 seconds
In P52, timer area show the actual
rotate speed of AHRI indoor fan
motor. Quick press “MODE”, enter
into setting interface, timer area
show the rotate speed of indoor fan
motor and twinkle, press “▲”
and”▼” to select the rotate speed,
Press “Mode” and hold for
0~5s, the rotate speed of indoor fan
motor will increase or decrease by
Setting of indoor
single digits; Press “MODE” and
rotate speed in
P52 100~1800 hold for 5~10s, the rotate speed of
efficiency testing
indoor fan motor will increase or
mode
decrease by ten digits, within its
maximum and minimum value
(100~1800). Quick press
“Confirm/Cancel” to confirm and
return to last status,

Present Way:
Temperature area: P52
Timer arer: Indoor fan motor rotate
speed.
Select the way of 00: manually
P67 adjusting static 00 -
pressure 01:automatically

00: comfortability
System preferred
n0 conservation 00
operation settings 01: conservation
preferred
40: 40 minutes
Defrosting period
n1 50: 50 minutes 50
settings
60: 60 minutes
Forcible 00: common After settings, it automatically
n3 -
defrosting 01: forcible defrosting restores to "00".
Enter query in “n4” status. The
Highest capacity 08: 80% temperature area displays the
n4 output limitation 09: 90% 10 function code and the timer area
settings for ODU 10: 100% displays the corresponding function
setting value.

Silent function of 00: no silent function Enter query in “A7" status. The
A7 00 temperature area displays the
ODU 01-09: intelligent function code and the timer area

19
Duct type split Air conditioner Inverter Series

Parameter
Parameter Name Parameter Range Default Value Remark
Code
nighttime silent mode displays the corresponding function
10-12: forcible silent setting value.
mode

Note:
In parameter setting status, "FAN", “TIMER”, "SLEEP", and "SWING" are invalid. By pressing the
“ON/OFF” button, users can return to the main interface but not power on/off the unit.
3.5 Failure Display
When a fault occurs during the system operation, the temperature area of wired controller displays
the fault code. When multiple faults occur, fault codes are circularly displayed.
 When a fault occurs, power off the unit and ask for professional maintenance personnel for help.
The following figure shows the power-on high-pressure protection fault interface.

Power-on High-pressure Protection Fault Interface

4 Monitoring Software
4.1 Function introduction
Integrating with telecommunication technology and computing software, Gree Commissioning Tool
Kits can realize the comprehensive monitor, control and commissioning on central air conditioners. It is
an efficient solution for the management of central air conditioners that are separated in different parts of
a building. Administrator doesn’t need to control every unit on site, but rather controls the units by just
sitting in front of a computer. This will not only improve the productivity, but also reduce cost on human
resources, property and management.
Gree Commissioning Tool Kits can monitor and control the duct type split air conditioner inverter
series. User can monitor and control units by monitoring the computer. This software is an efficient tool
for the intelligent air conditioning management as well as installation and after-sales service and
commissioning. It can debug units and control units’ operation status quickly and conveniently. It will not
only improve the productivity but also reduce the difficulty and cost of commissioning and maintenance,
providing better and faster service to customers.

20
Duct type split Air conditioner Inverter Series

4.2 Connection of computer and units

It can be connected with single-system network or multi-system network. In the single-system


network, indoor units or outdoor units are connectable, while in the multi-system network, only the
master outdoor unit can be connected.
Seen from the diagram, Gree commissioing network is made up of 3 parts:
The 1st part is the monitoring computer, including Gree debugger and Gree USB converter driver
that are installed in the computer.
The 2nd part is Gree USB converter, which is to convert the air conditioning communication into
computing communication. This part is made up of Gree USB data converter and USB data wire.
The 3rd part is air conditioners, including outdoor units, indoor units and the connection wires. If
connection wire is not long enough, it’s OK to connect via the patching board of the commissioning tool
kits. In a single-system network, both indoor units and outdoor units can be connected, while in a
multi-system network, only the master outdoor unit can be connected.
4.3 Parts introduction
4.3.1 List of parts
Name Model Material no. Remark
Convert the air conditioning communication
Gree USB data converter MC40-00/B 30118027
into computing communication
Include Gree debugger, monitoring software,
Gree Commissioning Tool Kits
DG40-33/A(C) 36400000003 USB driver and USB converter configuring
(CD-ROM)
software.
Wire connecting computer’s USB interface
USB wire \ 40020082
and converter
This board can be used when units are far
Communicaiton board \ 30118015
from the computer.
Board connection wire (1m) \ 4001023229 4-core wire connecting units and converter
Board connection wire (5.5m) \ 4001023214 4-core wire connecting units and converter
Instruction manual \ 66174100018 Instruction manual
4.3.2 Gree USB data converter
4.3.2.1 Functions introduction
Gree USB data converter will convert the RS485, HBS and CAN commucation within the air
conditioners into the communication that is recognizable by computer’s USB interface.

4.3.2.2 Appearance

21
Duct type split Air conditioner Inverter Series

4.3.2.3 Operation instruction


 Power LED: a red light. If the red light is on, it indicates normal power supply. If the red light is off,
it indicates the power supply of converter is not normal.
 Communication LEDs: yellow lights. When converter is working and the computer is transmitting
data, the TX data transmitting light will be flickering. When units are uploading data to the

22
Duct type split Air conditioner Inverter Series

computer, the RX data receiving light will be flickering.


 When converter is under RS485 data transferring mode, the function LED of RS485 to USB will
be on.
 When converter is under CAN data transferring mode, the function LED of CAN to USB will be
on.
 When converter is under HBS data transferring mode, the function LED of HBS to USB will be
on.
 USB interface: connect USB data wire.
 CAN interface: When converter is under CAN communication mode, connect air conditioner’s
CAN data interface. CAN interface exhibits no polarity (A and B are equal).
 HBS interface: When HBS converter is under HBS communication mode, connect air
conditioner’s HBS data interface. HBS interface exhibits no polarity (This interface is not yet
available for Gree debugger and the monitoring software).
 RS485 interface: When RS485 converter is under RS485 communication mode, connect air
conditioner’s RS485 data interface. RS485 interface exhibits polarity and terminal A and B are
different.

4.3.2.4 Installation notice


 Install indoors. To avoid collision, it is suggested to place it in the monitoring room together with
the computer.
 No need of power supply. Power is supplied through computer’s USB interface.
4.3.3 Communication board
Communication board is mainly used for transferring data. It functions similar with a patching board.
Provided that units are far away from the monitoring computer, communication board can be used for
connection.
4.3.4 Communication cord
4.3.4.1 USB wire
 Connect USB wire with computer’s USB interface at one end and with the USB interface of USB
data converter at the other end, as indicated below:

USB Wire

4.3.4.2 Board Connection Wire


 There are 2 board connection wires supplied for the commissioning tool kits. One is 1 meter’s
long and the other is 5.5 meters’ long. They are only different in length. One end of the wire shall

23
Duct type split Air conditioner Inverter Series

connect with air conditioner’s communication interface and the other end shall connect with CAN
interface of Gree USB converter. As shown below, the wire can be connected to the
communication interface of outdoor unit or the communication interface of indoor unit:

Board Connection Wire

4.4 Software introduction


(1)One-button commissioning
Personnel responsible for the commissioning of air conditioners can start commissioning by
pressing one button according to the commissioning logic of software, which will give the
commissioning order to units. Then commissioning will be started up automatically step by step.
During the commissioning, the corresponding process will be ticked in green on the software
interface. If any commissioning process is not normal, it will be displayed in red.
(2)Comprehensive monitoring
The software can monitor every part of the air conditioning system, including functions, equipment
and components operating status. The monitoring results will be displayed in text or curve so that
user can acquire the operating status of the entire system conveniently and straightforwardly.
(3)Real-time control
Air conditioner’s operating time and requirements may be different based on areas and functions.
User can set units’ parameters on computer according to actual needs, such as the on/off,
temperature, fan speed, mode, etc. Meanwhile, the software can also set or view the function
parameters of outdoor units, gateway and other equipment. In this way, the mangement of central
air conditioners is realized.
(4)Replay history
Software can replay and save the historical monitoring information in the data base. The replay
speed can be selected and the information will be shown in text or curve. This function has greatly
saved the time to track problem cause and resolved the difficulty of problem reproduction.
(5)Applicable to multiple series, models and users
Gree Commissioning Tool Kits is applicable to air conditioning system that comsists of multiple
series and models. Later, it will be developed to cover all series of Gree central air conditioners,
such as multi VRF, centrifugal chiller, screw type chiller, ground source heat pump units, modular

24
Duct type split Air conditioner Inverter Series

units, fan coiled units, close control units, etc. It can be used by system and controller designers to
develop and monitor units, or used for maintenance and commissioning.
(6)Other functions
For the convenience of users, the software has added functions like connection guide, printing
screen, opening database folder, rebuilding database, changing database saving path, etc.
4.4.1 Software installation
4.4.1.1 Installation requirements
(1)Computer Configuration
1 GB at least
Memory
2 GB or above is preferred
Hard Disc 10 GB available
Core 2 or higher
CPU 1 GHz at least
2 GHz or above is preferred
Windows Server 2003 SP3 or higher
Windows XP SP3 or higher
Operation System
Windows Vista
Windows 7

(2) CD Playing
Make sure you have administrator access to the computer and there is a CD-ROM in the computer.
Put the CD into the CD-ROM. If it’s automically running, then the following display will be shown. Or
double-click the file “Launcher.exe”.

For the first time to use Gree Commissioning Tool Kits, install these programmes: .Net Framework
4.0, USB Data Converter, Access Driver (necessary for versions below OFFICE 2007), Gree Debugger.

25
Duct type split Air conditioner Inverter Series

4.4.1.1 Installation flowchart

Button Graphics

This flowchart describes basically the software installation process. See below for details.

4.4.1.2 Installation process

(1) Install .Net Framework 4.0


 If your computer has installed .Net Framework 4.0 or versions above, there’s no need to install
again. Otherwise, click “Install .Net Framework 4.0”.

26
Duct type split Air conditioner Inverter Series

 Extracting files

 Click and select “I have read and accept the license terms”. Then click “Install”.

27
Duct type split Air conditioner Inverter Series

 Installation is in progress.

 Click “Finish” to complete the installation.

28
Duct type split Air conditioner Inverter Series

(2) Install Access Driver


 Before operating Gree commissioning software, please first install Access Driver (necessary for
versions below OFFICE 2007). Click “Install Access Driver”.

 Click ”Next”.

29
Duct type split Air conditioner Inverter Series

 Tick “I accept the terms in the License Agreement” and then click “Next”

 Click “Browse” to change the default folder to the expected one, or click “Install” to continue the
installation.

30
Duct type split Air conditioner Inverter Series

 Installation is in progress.

 Click “Ok” to complete the installation.

(3) Install Gree Debugger


 Before installing Gree debugger, make sure that your computer is installed with .Net Framework
4.0 or versions above. Then click “Install Gree Debugger”.

31
Duct type split Air conditioner Inverter Series

 Click “Next”.

 Click “Browse” to select installation folder. If no change is needed for the folder, click “Next” to
continue the installation.

32
Duct type split Air conditioner Inverter Series

 Click “Next”.

 Installation is in progress.

33
Duct type split Air conditioner Inverter Series

 Click “Close” to complete the installation.

(4) Install USB Converter Driver


 If USB converter driver is already installed in your computer, this part can be skipped. Otherwise,
click “Install USB Converter Driver”.

34
Duct type split Air conditioner Inverter Series

 Then the following installation window will be shown.

 This window will exit after installation is finished.

35
Duct type split Air conditioner Inverter Series

(5) Install Gree USB Data Converter


 If converter baud rate is needed to be set, then converter configuring software must be installed.
Click “Install Gree USB Data Converter”.

 Then select the setup language. You can choose Chinese ”simplified”, Chinese “traditional” or
English. Then click “OK”.

 Click “Next”.

36
Duct type split Air conditioner Inverter Series

 Tick “I accept the agreement”. Then click “Next” to continue installation.

 Click “Browse” to select your expected installation folder. Click “Next” to continue.

37
Duct type split Air conditioner Inverter Series

 Click “Browse” to change folder. Click “Next” to continue.

 If you want to create s desktop shortcut, tick “Creat a desktop icon”. Then click “Next” to continue.

38
Duct type split Air conditioner Inverter Series

 Destiniation location, folder and additional task will be shown in the next step. If you need to change
any of it, please click “Back”. If not, click “Install” to start installation.

 Installaiton is in progress.

39
Duct type split Air conditioner Inverter Series

 Click “Finish” to complete the installation.

4.4.2 Data monitoring


 Start up Gree Debugger.

 On the original interface, user can select language and units system. Click “OK” to confirm the
defaulted language and units system and start up the software.

40
Duct type split Air conditioner Inverter Series

 Select language.

 Select system of units.

41
Duct type split Air conditioner Inverter Series

 If units you want to monitor are already connected, and able to communicate normally, with correct
COM and protocal, then you may click “Connect” to enter the interface of numbers. Otherwise,
connect in accordance with the connection diagram shown below.

 COM selection: the serial port in your computer can be detected automatically. You just need to
select your desired serial port.

42
Duct type split Air conditioner Inverter Series

 Protocal selection: This is to select the communication method of your units. Currently, CAN is
applicable to the units.

 After the selection, click “Connnect”. If units can communicate normally with computer, then the
interface of numbers will be shown soon. Otherwise, “Connecting” will be shown.

43
Duct type split Air conditioner Inverter Series

 There are several display zones on this interface. You can hide devices information and system
information by clicking devices information icon and system icon . Display zones of indoor
unit information and errors can be dragged up and down at the dividing lines. As to the display zone
of outdoor modules information, it can show information of only one module and hide information of
others (two modules are defaulted to be shown). Menu bar can be hidden by clicking icon .
Status bar shows the current time and period for data collection.

Menu bar
Title bar

Error display

System info

Outdoor modules info

Devices info

IDU info

Status bar

44
Duct type split Air conditioner Inverter Series

 On the display zone of devices information, you may click to select and view units that need
monitoring.

4.4.3 Project debugging


 Click icon of “Debug” on the menu bar and the interface will be switched to project debugging,
where auto debugging will be started from up to down and from left to right. Note: Debugging
function is only applicable to a single-system network.

45
Duct type split Air conditioner Inverter Series

 Click “Start” to enable the debugging function. Then debugging will be started up automatically.
indicates that debugging is in progress while indicates debugging is completed.

 If “OK” button is displayed, it means user needs to judge whether to continue debugging or not.
Click icon and relevant information will be shown for your reference. Click “Close” to close the
pop-up (For No.3 Confirm ODU Basic Module NO. and No.4 Confirm IDU NO., the current number
of units under debugging will be displayed. See the following marked with circle. For No.8 Compr.
Preheat Confirmation, the preheat time will be displayed. See the following marked with circle).

46
Duct type split Air conditioner Inverter Series

 Icon indicates that there is problem found during debugging. Debugging will not be completed
unless problem is solved (after problem is solved, step without “OK” button will switch to the next
step automatically, otherwise user needs to click “OK” to continue). Click icon and relevant
information detected in this step will be displayed for your reference in order to solve problems.
Click “Close” to close the pop-up.

 During debugging, a click on “Break” can stop debugging. Click “Start” to resume debugging and
then debugging will be finished step by step. For No.10 ODU Valves Check Before Startup, there
are “Back” and “Skip” buttons. If there is error in this step, you can back to step No.9 and click “OK”
to restart debugging on step No.10. If the error in step No.10 is U6 error (valve error alarm), you can
click “Skip”. In other cases, “Skip” button is null.
 Step 11, 13 and 14 are reserved steps. And step 13, 14, 15 and 16 are steps in parallel (only one of
the four will be selected according to actual needs).

47
Duct type split Air conditioner Inverter Series

4.4.4 Control units


 Click icon of “Setting” on menu bar and select parameter settings, which include “Gateway Settings”,
“IDU Settings”, “System Settings”, “Project Number Conflict (In case there is project number conflict
in indoor units, other functions will be shielded. Then this parameter needs to be set in order to
eliminate the conflict)” and “System Historical Info”. Click the corresponding set and adjust the
parameters.

 Take indoor unit as an example. Click “IDU Settings” and a dialog box will pop up.

48
Duct type split Air conditioner Inverter Series

 Tick the indoor units that need setting in the IDU selection zone or you may click “Select All” to
select all of them or “Select Inverted” to select none of them. After selection, the current values of
the corresponding parameters will be displayed in the zone of settings. Click “Set” and then click
in the pop-up dialog box to select values. Click “Set” and then the corresponding order will be
sent to units. If setting is successful, it will be displayed at the current values.

49
Duct type split Air conditioner Inverter Series

4.4.5 Other functions


Capture screen
 Click icon of “Capture Screen” to print the interface. If you want to open the interface, click “Open”.

50
Duct type split Air conditioner Inverter Series

Search for database folder


 Click icon of “Open Data Folder” on the menu bar to open database folder.

51
Duct type split Air conditioner Inverter Series

Conversion of pressure value


 Click icon of “Others” on the menu bar and then click “Display Settings” to select “High Low
Pressure Value” and “Refrigerant Type”. Select “Temperature” and the pressure parameter
displayed on the interface will be temperature. Select “Pressure” and the pressure parameter
displayed on the pressure interface will be pressure. Refrigerant type will affect the pressure
parameter displayed on the interface.

52
Duct type split Air conditioner Inverter Series

Database saving of multiple systems


 Click icon of “Others” on the menu bar and click “Database Save Settings” to select which system
that needs to save database. Because there is a large quantity of data in a network that contains
multiple systems, data of only one system can be saved.

53
Duct type split Air conditioner Inverter Series

Change database saving path and rebuild database


 Change of database saving path and rebuilding of database should be set before the software
starts monitoring (see below interface). Click “Change database saving path” and click “Browse” to
change the saving path. Click “Rebuild Database” to rebuild the database folder. You can also stop
monitoring and turn back to the connection interface to change saving path or rebuild database
during monitoring.

54
Duct type split Air conditioner Inverter Series

4.4.6 Usage of USB Converter


Usage of converter
 Gree commissioning software should be connected with CAN interface when converter is used. For
air conditioners with a single system, connect D1 and D2 interfaces of the wiring board. For air
conditioners with multiple systems, connect G1 and G2 interfaces of the wiring board.

 Gree monitoring software should be connected with RS485 interface when converter is used.
Connect outdoor or indoor units or the mainboard of wired controller according to actual needs.

 HBS, CAN and RS485 of the converter can be switched by buttons. Press the button “SET” on the
converter to realize the conversion among HBS, CAN and RS485 interfaces. You can check the
setting through the function LEDs.
Notice: If it’s the first time your PC uses Gree USB data converter, in order to prevent Gree USB
data converter from being mistaken by your computer as other devices and make sure your mouse
can work well, it is necessary to turn off the Serail Enumerator of computer after Gree USB data
converter is connected. Below are the steps:
Step 1: Right-click ”My Computer” on the desktop and click ”Manage”.

Step 2: In the pop-up window, select “Device Manager” in the left column and then find “Port
(COM and LPT)” in the right column. Click its .

55
Duct type split Air conditioner Inverter Series

56
Duct type split Air conditioner Inverter Series

Step 4: Right-click ”USB Serial Port (COM6) and then click ”Properties”. The dialog box of properties will
then pop up.

Step 5: Then click ”Port Settings” in the dialog box.

57
Duct type split Air conditioner Inverter Series

Step 6: Click ”Advanced” and then a new dialog box will pop up. Find the ”Serial Enumerator” in
the miscellaneous options and cancel the tick. Click ”OK” to exit.

58
Duct type split Air conditioner Inverter Series

Usage of converter configuring software:


 When the converter is working, hold the button ”SET” for 5 sec. Function LED will be flickering,
indicating that the converter has enter the baud rate setting mode. Then you can use the converter
configuring software to set the baud rate of converter. Baud rate supported by the converter (baud
rate of air conditioner’s communication interface matches with the baud rate of USB interface
automatically):
Ex-factory defaulted baud rate: (unit: bps)

AC is connected with Baud rate of air conditioner interface Baud rate of USB interface
CAN 20000/50000 self-adaptive 115200
HBS 57600 38400
RS485 9600 9600
Baud rate look-up table for RS485 interface (unit: bps)

RS485 interface 4800 9600 19200 38400 57600 115200


USB interface 4800 9600 19200 38400 57600 115200

Baud rate look-up table for HBS interface (unit: bps)

HBS interface 9600 19200 38400 57600


USB interface 4800 9600 19200 38400
Baud rate look-up table of CAN interface (unit: bps)

CAN interface 20000 50000 100000 125000


USB interface 115200 115200 256000 256000

 Double-click the desktop shortcut.

59
Duct type split Air conditioner Inverter Series

 Select the needed communication serial port and language in the “System Settings”.

 Select the function that is to be set and the corresponding baud rate (refer to the look-up table) in
the “Converter Setup”.Then click “Set”.

60
Duct type split Air conditioner Inverter Series

 If you want to restore ex-factory settings, click “Default” to restore the default settings.

 Click “Get” to get the current setting details of converter.

61
Duct type split Air conditioner Inverter Series

 Switchover of Software Languages

62
Duct type split Air conditioner Inverter Series

INSTALLATION

63
Duct type split Air conditioner Inverter Series

1 Engineering Installation Preparation and


Notice
1.1 Installation notice
Personnel and property safety are highly concerned during the entire installation process.
Installation implementation must abide by relevant national safety regulations to ensure personnel and
property safety.
All personnel involved in the installation must attend safety education courses and pass
corresponding safety examinations before installation. Only qualified personnel can attend the
installation. Relevant personnel must be held responsible for any violation of the regulation.
1.2 Installation key points and importance
The system use refrigerant, instead of other agent, to directly evaporate to carry out the system heat.
High level of pipe cleanness and dryness is required in the system. Since various pipes need to be
prepared and laid out onsite, carelessness or maloperation during installation may leave impurities,
water, or dust inside refrigerant pipes. If the design fails to meet the requirement, various problems may
occur in the system or even lead to system breakdown.
Problems that usually occur during installation are as follows:
No. Installation Problem Possible Consequence
Pipes are more likely to be blocked; air conditioning performance is reduced;
Dust or impurities enter into the
1 compressor wear is increased or even hinder the normal operation of the system
refrigeration system.
and burn the compressor.
Nitrogen is not filled into the Pipes are more likely to be blocked; air conditioning performance is reduced;
2 refrigerant pipe or insufficient compressor wear is increased or even hinder the normal operation of the system
Nitrogen is filled before welding. and burn the compressor.
The refrigeration performance is reduced. The system fails to keep normal
The vacuum degree in the
3 operation due to frequent protection measures. When the problem getting serious,
refrigerant pipe is insufficient.
compressor and other major components can be damaged.
Copper plating may appear on the compressor and reduce the compressor
Water enters into
4 efficiency with abnormal noise generated; failures may occur in the system due to
the refrigeration
ice plug.
system.
The refrigerant pipe Smaller configuration specifications can increase the system pipe resistance and
5 specifications do not meet the affect the cooling performance; larger configuration specifications are waste of
configuration requirements. materials and can also reduce the cooling performance.
The cooling performance is reduced; in certain cases, it may cause long-term
compressor operating under overheat conditions; the lubricating effect can be
6 Refrigerant pipe is blocked.
affected and the compressor may be burnt if impurities were mixed with the
lubricating oil.
Refrigerant pipe exceeds the The loss in pipe is considerable and the unit energy efficiency decreases, which
7 limit. are harmful for long-term running of the system.
The system cannot correctly control the flow allocation; the compressor may be
Incorrect amount of refrigerant is
8 operating under over-heating environment or running when the refrigerant flows
filled.
back to the compressor.
Insufficient refrigerant circulating in the system decreases the cooling performance
9 The refrigerant pipe leaks. of the air conditioner. Long-term operation under such circumstance may cause an
overheating compressor or even damage the compressor.
Water drainage from the
Residual water in IDUs can affect the normal operation of the system. The
10 condensate water pipe is not
possible water leakage can damage the IDU's decoration.
smooth.
The ratio of slop for condensate
water pipe is insufficient or the Reverse slop or inconsistent connection of condensate water pipe can hinder the
11 condensate water pipe is smooth drainage and cause leakage of the IDU.
incorrectly connected.
The air channel is improperly
12 The air channel will deform; vibration and noise occur during unit operating.
fixed.
The guide vane of air channel is Uneven air quantity allocation reduces the overall performance of the air
13 not reasonably manufactured. conditioner.

64
Duct type split Air conditioner Inverter Series

No. Installation Problem Possible Consequence


The refrigerant pipe or
Water can easily condensate and drip to damage the indoor decoration, or even
14 condensate water pipe does not
trigger the protection mode of system due to overheating operation.
meet the insulation requirement.
The installation space for IDU is Since there is a lack of space for maintenance and checking, indoor decoration
15 insufficient. might need to be damaged during such operation.
The IDU or the location of the air
The air outlet or return air inlet may be short-circuited, thus affecting the air
16 outlet or return air inlet is not
conditioning performance.
designed reasonably.
The ODU is difficult to be maintained; unit exhaust is not smooth, which reduces
the heat exchanging performance or even prevent the system from normal
17 The ODU is improperly installed. operation; in addition, the cold and hot air for heat exchange and the noise may
annoy people in surrounding areas.
Power cables are incorrectly
18 Unit components may be damaged and potential safety hazard may occur.
provided.
Control communication cables
The normal communication in the system fails or the control over IDUs and ODUs
19 are incorrectly provided or
turn in a mess.
improperly connected.
Control communication cables The communication cables are short-circuited or disconnected, and the unit
20 are not properly protected. cannot be started up due to communication failure.

Understand the special requirement (if any) for unit installation before implementation to ensure
installation quality. Relevant installers must have corresponding engineering construction qualifications.
Special type operators involved in the engineering implementation, such as welders, electricians,
and refrigeration mechanics must have relevant operating licenses and are accredited with vocational
qualification certification.

2 Installation Materials Selection


The materials, equipment and instruments used during air conditioning engineering construction
must have certifications and test reports. Products with fireproof requirements must be provided with
fireproof inspection certificates and must meet national and relevant compulsory standards. If
environmentally-friendly materials are to be used as required by customers, all such materials must
meet national environmental protection requirement and be provided with relevant certificates.
2.1 Refrigerant piping
a. Material requirement: Dephosphorization drawing copper pipe for air conditioners;
b. Appearance requirement: The inner and outer surface of pipe should be smooth without pinhole,
crack, peeling, blister, inclusion, copper powder, carbon deposition, rust, dirt or severe oxide film, and
without obvious scratch, pit, spot and other defects.
c. Test report: Certifications and quality test reports must be provided.
d. The tensile strength must be at least 240 kgf/mm².
e. Specifications requirement

R410A Refrigerant System

OD (mm/inch) Wall Thickness (mm) Model

Ф6.35(1/4) ≥0.8 0

Ф9.52(3/8) ≥0.8 0

65
Duct type split Air conditioner Inverter Series

Ф12.70(1/2) ≥0.8 0

Ф15.9(5/8) ≥1.0 0

Ф19.05(3/4) ≥1.0 0

Ф22.20(7/8) ≥1.2 0

Ф25.40(8/8) ≥1.2 0
f. After the inner part of the copper pipe is cleaned and dried, the inlet and outlet must be sealed
tightly by using pipe caps, plugs or adhesive tapes.
2.2 Condensate water pipe
a. Pipes that can be used for air conditioner drainage include: water supplying UPVC pipe, PP-R
pipe, PP-C pipe, and HDG steel pipe;
b. All relevant certificates and quality test reports are provided.
c. Requirements for specifications and wall thickness
Water supplying UPVC pipe: Φ32mm×2mm,Φ40mm×2mm,Φ50mm×2.5mm;
HDG steel pipe: Φ25mm×3.25mm,Φ32mm×3.25mm,Φ40mm×3.5mm,Φ50mm×3.5mm.
2.3 Insulation material
a. Rubber foam insulation material;
b. Flame retardancy level: B1 or higher;
c. Refractoriness: at least 120℃;
d. The insulation thickness of condensate water pipe: at least 10 mm;
e. When the diameter of copper pipe is equal to or greater than Φ15.9 mm, the thickness of
insulation material should be at least 20 mm; when the diameter of copper pipe is less than 15.9 mm, the
thickness of insulation material should be at least 15 mm.
2.4 Communication cable and control cable
Note: For air conditioning units installed in places with strong electromagnetic interference, shielded
wire must be used as the communication cables of the IDU and wired controller, and shielded twisted
pairs must be used as the communication cables between the IDU and ODU.
Communication cable selection for ODU and IDUs:
Total Length L
(m/feet) of
Communication
Wire size Material
Material Type Cable between 2 Remarks
(mm /AWG) Standard
Indoor Unit and
Indoor (Outdoor)
Unit
1. If the wire diameter is enlarged to 2×1
mm2 (2×AWG16), the total
Light/Ordinary
communication line length can reach
polyvinyl
1500 m (4921-1/4feet).
chloride L≤1000m ≥2×0.75 IEC
2. The cord shall be Circular cord (the
sheathed cord. (L≤3280-5/6feet) (≥2×AWG18) 60227-5:2007
cores shall be twisted together).
(60227 IEC 52
3. If unit is installed in places with intense
/60227 IEC 53)
magnetic field or strong interference, it
is necessary to use shielded wire.
Communication cable selection for IDU and wired controller:

66
Duct type split Air conditioner Inverter Series

Total length of
communication
line between 2 Material
Material type Wire size (mm /AWG) Remarks
indoor unit and Standard
wired controller
L (m/feet)
1.Total length of communication
line can't exceed 250m
Light/Ordinary
(820-1/5feet).
polyvinyl
2.The cord shall be Circular cord
chloride
L≤250m 2×0.75~2×1.25 IEC (the cores shall be twisted
sheathed
(L≤820-1/5feet) (2×AWG18~2×AWG16) 60227-5:2007 together).
cord. (60227
3.If unit is installed in places with
IEC 52
intense magnetic field or strong
/60227 IEC 53)
interference, it is necessary to
use shielded wire.
2.5 Power cable
Only copper conductors can be used as power cables. The copper conductors must meet relevant
national standard and satisfy the carrying capacity of unit.
2.6 Hanger rod and support
a. Hanger rod: M8 or M10;
b. U-steel: 14# or above;
c. Angle steel: 30mm×30mm×3mm or above;
d. Round steel: Φ10mm or above

3 Installation of Indoor Unit


3.1 Outline and installation dimension

67
Duct type split Air conditioner Inverter Series

b. 40kW
Below are dimensions of A, B, C, etc. for different models:

Unit: mm
Model a b c d e f

FGR20Pd/DNa-X(I) 1334 632 990 1150 192 363

FGR25Pd/DNa-X(I) 1541 705 980 1350 270 420

FGR30Pd/DNa-X(I) 1541 705 980 1350 270 420

FGR40Pd/D(2)Na-X(I) 1730 760 1054 1450 360 560

3.2 Installation space

3.3 External static pressure setting and reading


3.3.1 External static pressure setting
You can enter P67 select the way of adjusting static pressure for the blast pipe manually or
automatically.The default value is 00,which means adjusting manually.
(1) If you choose 00,you can select the suitable level for any blast pipes. It can reach to 250Pa

68
Duct type split Air conditioner Inverter Series

.You can enter P30 to set the value.

① Long press FUNCTION button for 5s and the temperature zone displays “C00”; long press
FUNCTION button for another 5s to enter the interface of setting wired controller parameters. “P00” is
displayed in temperature zone.

② Press “▲” or “▼” button to select parameter code. Press MOD E button to enter parameter setting.
At that time, parameter value is blinking. Press “▲” or “▼” button to adjust the parameter value and
press ENTER/CANCEL button to finish setting.
③ Press ENTER/CANCEL button to return to last step until exists setting parameters.
The parameter setting list is as following
Parameter Default
Parameter name Parameter range Note
code value

There are 9 static


Set static pressure of indoor 01-09: static pressure level of pressure level:
P30 05
fan motor indoor fan motor 01, 02, 03, 04, 05, 06,
07, 08, 09

Note:
① Under parameter setting status, FAN, TIMER, SLEEP and SWING button are invalid. Press
ON/OFF button to go back to home page, but not turning on/off the unit.
② If the power cord is more than 15 m (49-1/4 ft.) long, please increase properly the sectional area of
power cord to avoid overload, which may cause accident.

External Static Pressure static pressure level of indoor fan motor


0 inWG(0 Pa) 01
0.12 inWG(30 Pa) 02
0.24 inWG(60 Pa) 03
0.36 inWG(90 Pa) 04
0.48 inWG(120 Pa) 05
0.60 inWG(150 Pa) 06
0.72 inWG(180 Pa) 07
0.84 inWG(210 Pa) 08
1.00 inWG(250 Pa) 09

Note:
Keep in mind that a shortage of airflow quantity or water leakage will result because the air conditioner
will be operated outside the rated range of airflow quantity if the external static pressure is wrongly set.
(2) If you choose 01,the indoor motor will adjust static pressure of the blast pipe automatically
when start-up every time.So how to enter P67?
① Long press FUNCTION button for 5s and the temperature zone displays “C00”; press MODE button
for three times in 3s;long press FUNCTION button for another 5s to enter the interface of setting wired
controller parameters. “P00” is displayed in temperature zone.
② Press “▲” or “▼” button to select parameter code. Press MOD E button to enter parameter setting. At

69
Duct type split Air conditioner Inverter Series

that time, parameter value is blinking. Press “▲” or “▼” button to adjust the parameter value and press
ENTER/CANCEL button to finish setting.
(3) Press ENTER/CANCEL button to return to last step until exists setting parameters.
The parameter setting list is as following

Parameter code Parameter name Parameter range Default value

00: manually
P67 Select the way of adjusting static pressure 00
01:automatically

3.3.3 External static pressure reading


If you want to know the exact external static pressure,you can set P67 to 01,restart the
machine,after about 2 minutes,enter C24 to read the exact ESP.
① Long press FUNCTION button for 5s and the temperature zone displays “C00”; press MODE button
for three times in 3s.
② Press “▲” or “▼” button to C24,there you can read the exact ESP.
3.4 Installation notice
◆The unit shall be installed by the professional personnel according to this installation instruction
to
ensure proper use.
◆ Please contact the local Gree appointed service center before installation. Any
malfunctioncaused by the unit that is not installed by the Gree appointed service center would probably
not be dealt with on time because of the inconvenience of the business contact.
◆It should be guided under the professional personnel when the air conditioner unit is moved to
other place.
◆Installation of the unit must be in accordance with National Electric Codes and local regulations.
◆Improper installation will affect unit’s performance, so do not install the unit by yourself. Please
contact local dealer to arrange professional technicians for the installation.
◆Do not connect power until all installation work is finished.
◆If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a
similarly qualified person in order to avoid a hazard.
3.5 Selection of air switch and power cord
Circuit (mm2)Number of (mm2)Number of
breaker
Model Power supply ground wire * Min power cord * Min
capacity
sectional area sectional area
(A) (mm2) (mm2)
FGR20Pd/DNa-X(I) 220V~50/60HZ 10 1×1.5 2×1.5

70
Duct type split Air conditioner Inverter Series

FGR25Pd/DNa-X(I) 220V~50/60HZ 10 1×1.5 2×1.5


FGR30Pd/DNa-X(I) 220V~50/60HZ 10 1×1.5 2×1.5
FGR40Pd/D(2)Na-X(I) 3N~ 380V 50/60HZ 10 1×1.5 4×1.5

4 Installation of outdoor unit


4.1 Check before installation
a. Before installation, please check the power cord if it complies with the power supply requirement
on the nameplate. Make sure the power supply is safe.
b. This air conditioner must be properly grounded through the receptacle to avoid electric shock.
The ground wire shouldn’t be connected with gas pipe, water pipe, lightning arrester or telephone line.
c. Maintain good air circulation to avoid lacking oxygen.
d. Read this manual carefully before installation.
4.2 Selection of installation site
a. Select a location which is strong enough to hold unit’s weight so that unit can stand still and erect.
b. Make sure the unit is not exposed to sun and rain. And the location can resist dust, typhoon and
earthquake.
c. Please keep the unit away from inflammable, explosive and corrosive gas or waste gas.
d. Make sure the location has space for heat exchange and maintenance so that unit can operate
reliably with good ventilation.
e. ODU and IDU should stay as close as possible to shorten the length of refrigerant pipe and
reduce bend angles.
f. Select a location which is out of children’s reach. Keep the unit away from children.
4.3 Carrying and installing outdoor unit
When carrying the outdoor unit, hang the unit in four directions with two sufficient ropes. In order to
avoid excursion from the center, the angel of ropes must be smaller than 40º during hanging and
moving.
4.4 Installation notices
In order to ensure proper operation, the selection of installation site must conform to the following
principle:
●The discharged air of outdoor unit will not flow back and there is sufficient space around the unit
for maintenance;
●The installation site must be well ventilated to ensure sufficient air intake and discharge. Make
sure there is no obstacle at the air inlet and air outlet. If there is any obstacle, please remove it;
●The installation site shall be able to withstand the weight of outdoor unit and capable for
soundproof and vibration. The air outlet and noise of unit will not affect neighbors;
●The hanging of outdoor unit must use appointed hanging hole. Pay attention to protect the unit
during hanging and installation. Prohibit hitting the sheet metal to avoid rust in the future.
●Avoid direct sunlight;

71
Duct type split Air conditioner Inverter Series

●The rain and condensation water can be drained out smoothly;


●The outdoor unit will not be embedded by the snow and not affected by garbage and oil smog;
●The installation of outdoor unit shall adopt rubber damping pad or spring damper to reduce noise
and vibration;
●The installation dimension shall accord with the installation requirement of this manual and the
outdoor unit must be fixed at the installation site;
●The installation shall be done by professional technicians.

4.5 Fixing and damping of unit


The outdoor unit shall be fixed with 4 M12 bolts and closely contacted with the foundation.
Otherwise, big vibration and noise will be caused.
The outdoor unit shall be fixed firmly. The rubber board with thickness over 20mm or corrugated
rubber damping pad shall be applied between the unit and foundation.
4.6 Outline dimension and position of installation hole
When carrying the outdoor unit, hang the unit in four directions with two sufficient ropes. In order to
avoid excursion from the center, the angel of ropes must be smaller than 40º during hanging and
moving.

Unit: mm
Model A B C D E
FGR20Pd/DNa-X(O) 940 320 1430 632 350
FGR25Pd/DNa-X(O) 940 460 1615 610 486

72
Duct type split Air conditioner Inverter Series

FGR30Pd/DNa-X(O) 940 460 1615 610 486

4.7 Installation space requirement


If all sides of the ODU (including the top) are surrounded by walls, process according to the
following requirements for installation space:

5 Installation of drain pipe


5.1 Precautions When Doing the Piping Work
◆ Keep piping as short as possible and slope it downwards at a gradient of at least 1/100 so that
air may not remain trapped inside the pipe.
For example:

◆Keep pipe size equal to or greater than that of the connecting pipe.
◆Install the drain piping as shown and take measures against condensation. Improperly rigged
piping could lead to leaks and eventually wet furniture and belongings.

◆When directly connecting a hard vinyl chloride pipe joint to the drain hose connected to the indoor
unit, use a commercially available hard vinyl chloride pipe joint (nominal diameter 13mm).

73
Duct type split Air conditioner Inverter Series

◆ Drain hose connectedto the indoor unitCommercially availablehard vinyl chloride pipejoint
(nominal diameter 13mm)Commercially availablehard vinyl chloride pipe(nominal diameter 13mm)
◆Do not connect the drain piping directly to sewage pipes that smell of ammonia. The ammonia in
the sewage might enter the indoor unit through the drain pipes and corrode the heat exchanger.
5.2 Installing the Drain Pipes
◆ Insert the drain hose into the drain outlet, and tighten the clamp securely with tape.
◆Tighten the clamp until the screw head is less then 4 mm from the hose.

◆Insulate the pipe clamp and the drain hose using heat insulation sponge.

◆If the air flow of indoor unit is high, this might cause negative pressure and result in return suction
of outdoor air. Therefore, U-type water trap shall be designed on the drainage side of each indoor unit.

◆ Install water trap as shown below


◆ Install one water trap for each unit
◆Installation of water trap shall consider easy cleaning in the future.

◆Connection of drainage branch pipe to the standpipe or horizontal pipe of drainage main pipe
◆The horizontal pipe cannot be connected to the vertical pipe at a same height. It can be
connected in a manner as shown below:
N01:3-way connection of drainage pipe joint

74
Duct type split Air conditioner Inverter Series

NO2: Connection of drain elbow

NO3: Connection of horizontal pipe

◆ When unifying multiple drain pipes, install the pipes as shown below. Select converging drain
pipes whose gauge is suitable for the operating capacity of the unit.(take the cassette type unit for
example)

5.3 Precautions when doing riser piping work


◆Make sure that heat insulation work is executed on the following 2 spots to prevent any possible

75
Duct type split Air conditioner Inverter Series

water leakage due to dew condensation.


a) Connect the drain hose to the drain raiser pipe, and insulate them.
b) Connect the drain hose to the drain outlet on the indoor unit, and tighten it with the clamp.

◆Stand the raiser piping horizontally, and make sure it is not further than 300 mm from the base of
the drain outlet.
◆Secure a downward gradient of 1/100 or more for the drain pipe. To accomplish this, mount
supporting brackets at an interval of 1 - 1.5 m.(take the cassette type unit for example)

◆ The incline of attached drain hose should be 75 mm or less so that the drain outlet does not have
to withstand additional force.(take the cassette type unit for example)

5.4 Testing of Drain Piping


◆After piping work is finished, check if drainage flows smoothly.
◆Shown in the figure, Add approximately 1liter of water slowly into the drain pan and check
drainage flow during COOL running.

6 Electrical Installation

76
Duct type split Air conditioner Inverter Series

◆The wiring must be in accordance with the local rules.


◆Rated supply voltage and special circuit for air conditioner must be used.
◆Do not pull the power cord forcefully.
◆All the electric installations must be carried out by specialist technicians in accordance with the
local laws, rules and these instructions.
◆The diameter of flexible wire should be wide enough. Replace the damaged power cord and
connecting wire with special flexible wire.
◆The earthing shall be reliable and connected to the special earthing device on the construction.
The installation must be done by specialist technicians. The leak protection switch and air switch with
enough capacity must be installed. The air switch shall have both the magnetic tripping and thermal
tripping functions to ensure protection against the short circuit and overload.
● Earthed Requirements
◆The air conditioner belongs to I type electric appliances. The reliable earthed action is a must.
◆The yellow and green wire inside the air conditioner is the earthed wire. Do not use it for other
purpose or even cut off it. Do not fix it with tapping screw,. Otherwise, it may cause electric shock.
◆The earthed resistance must meet the requirements of national standard GB17790.
◆There should be reliable earthed terminal for the power supply. Never connect the earth lead to
the following articles:
①water pipe; ②gas pipe; ③drain pipe; ④unreliable place considered by professionals.

77
Duct type split Air conditioner Inverter Series

DEBUGGING & MAINTENANCE

78
Duct type split Air conditioner Inverter Series

1 Debugging of Unit
Caution:
1. After the initial installation is finished and the main board of outdoor unit is replaced, it must perform
debugging. Otherwise, the unit can’t operate.

2. The debugging must be performed by professional person or under the the guide of professional
person.
1.1 Preparation for debugging
(1) Do not disconnect the power before the installation is finished,

(2) All wires for controller and electric wires must be connected correctly and reliably.

(3) Check the the fixing ring of the foot of compressor for transportaion is removed.

(4) Remove all sundries from the unit, such as metal chips, joint, forceps holder, and so on.

(5) Check whether the appearance and pipeline system are damaged during carry or transportation
process.

(6) Calculate the required added refrigerant-charging volume according to the length of pipe of system
and pre-charge the refrigerant. If refrigerant can’t be added any more when the required
refrigerant-charging volume hasn’t been reached, record to refrigerant volume which still needs to
be added and continue to add refrigerant during run test operation process. Please refer to below
run test for the refrigerant-adding stage during run test process.

(7) After adding refrigerant, please make sure the valve for outdoor is opened completely.

(8) For the convenient of troubleshooting, the unit can’t be connected to the PC which installed with
related debugging software and make sure that the the datas in real time of this unit can be
inspected by this computer. Please refer to Service Manual for the installation and connection of the
bebugging software.

(9) Before turn test, please do make sure that the preheat time for compressor is 8h above and touch
the compressor to see whether preheat is normal. You can perform run test only after normal
preheat. Otherwise, it may damage the compressor.
1.2 Debugging of unit
1.2.1 flow-process diagram of debugging

79
Duct type split Air conditioner Inverter Series

1.2.2 Test Operation and Debugging


Once the unit is energized and turned on for the first time, the display tube of outdoor unit displays
“A0”, which indicates debugging standby status. At this time, hold SW3 button successively for 5s on the
main module to enter into the automatic debugging, and then the engineering debugging will perform
according to the set procedures. Step 4(conformation of outdoor unit’ quantity) and step 4(conformation
of indoor unit’ quantity) should be confirmed manually by pressing “SW3”, while other procedures will be
performed automatically. Once the debugging for each step is finished, “oC” will be displayed; once all
engineering debugging are finished, “oF” will be displayed, which indicates the unit is under standby

80
Duct type split Air conditioner Inverter Series

status.
Functions of debugging buttons:
Key No. SW1 SW2 SW3 SW4
Function Up Down OK Back

Buttons and digital display tube on the motherboard location:

Debugging procedure for test run, display instruction for indicator on main board of outdoor unit and
operation method are as below:
Description of each stage of debugging progress
—— Debugging Code
LED Instruction for Code and Operating Method
Progress Display
Display Code
Code
There is no master unit in the system. The system cannot
Display
01/CC continue to conduct debugging, and all the buttons are invalid
repeatedly
that must be reset by cutting the power.
01_ Set master There are two or more master units in the system. The system
Display
unit 01/CF cannot continue to conduct debugging, and all the buttons are
repeatedly
invalid that must be reset by cutting the power.
Display There is only one master unit in the system. The unit will
01/OF
repeatedly automatically enter into the next step after display for once.
The system is allocating addresses. It will display asbelow after
02 Flicker
10 seconds:
There is no master unit. The display will last for 1 minute, within
this 1 minute, the master IDU can be set by debugging software.
Display
02_ Allocate 02/L7 If the master IDU has not been set within this 1 minute, the
repeatedly
addresses system will automatically set the IDU with the minimum IP
address as the master IDU.
The system has finished allocating the addresses, there is
Display
02/OC master IDU.It will automatically enter into the next step’s
repeatedly
operation after displaying for once.
Confirmation of quantity of modules in the system. If the actual
Display quantity of ODU is inconformity with the displayed quantity,
03/QTY of module
repeatedly please check the dial code and wire connection and then
conduct debugging for confirmation.
03_ Confirm the
If the actual quantity of ODU is in conformity with the displayed
quantity of ODU
quantity, press SW3 button to confirm. After confirmation, all the
Display
03/OC module nixie tubes will repeatedly display “03” and “0C”, after
repeatedly
displaying for once, the system will automatically enter into the
next operation.

81
Duct type split Air conditioner Inverter Series

Description of each stage of debugging progress


—— Debugging Code
LED Instruction for Code and Operating Method
Progress Display
Display Code
Code
Display It is not allowed to connect more than one indoor unit in the
04/Cb
04_ Confirm the repeatedly system. Please check and debug again to confirm.
quantity of IDU Display The quantity of IDU in the system has been confirmed.It will
04/oC
repeatedly enter into the next step.
Communication between master control and driving of ODU.
Please check if the communication wire between
Display mainboard and driving board of ODU is correctly
05/C2
05_ Detect ODU’s repeatedly connected, if it is, enter into the next step. If the ODU should be
internal powered off for the debugging, after re-energizing the unit,
communication please conduct debugging from the above 01 step.
The communication between master control and driving of ODU
Display
05/oC are normal. After displaying for once, it will automatically enter
repeatedly
into the next step.
Error of components of ODU. Except “06”, others will flickeringly
display corresponding error code. After eliminating all the
06/corresponding Display
06_ Detect errors, it will automatically enter into the next step. If the ODU
error code repeatedly
outdoor should be powered off for the debugging, after re-energizing the
components unit, please conduct debugging from the above 01 step.
Display No component of ODU is found in the system, it will enter into
06/oC
repeatedly the next step 10 seconds later.
Error of components of IDU are detected. For example, the IDU
displays d5 and d6 simultaneously, the nixie tube will repeatedly
07/ corresponding Display display “07”, “d5”, “d6”. After eliminating all the errors, it will
07_ Detect indoor error code repeatedly automatically enter into the next step. If the ODU should be
components powered off for the debugging, after re-energizing the unit,
please conduct debugging from the above 01 step.
Display No component of IDU is found in the system, it will automatically
07/oC
repeatedly enter into the next step 5 seconds later.
Insufficiency preheating of compressor. The nixie tube will
display as the left until the preheating time for compressor has
reached 8 hours, then press SW3 can skip over the waiting
Display
08/U0 time, and automatically enter into the next step 2 seconds later.
repeatedly
(Note: if the preheating time for the compressor is less than 8
08_ Confirm
hours, there may be a risk for damage of compressor, please
preheated
conduct with care)
compressor
If the ODU is continuously energized for ≥8h, or the continous
8-hour energizing time in the last time till now is less than 2
Display
08/oC hours (it requires clock chip), it means the preheating is
repeatedly
completed, the system will automatically enter into the next step
2 seconds later.
The system shuts down due to malfunction. The error module
nixie tube repeatedly display “09” and “U6”, other module nixie
tubes repeatedly display “09” and “J0”. If erroe occurs, please
09_Confirm status Display check if the valve is opened, and at the same time check if the
09/U4
of valve of ODU repeatedly connecting pipes between different modules are correctly
connected.
If all the modules shut down, then all the module nixie tube will
display “09” and “oC” for once.
10_Debugging The whole unit has gone through the debugging, the system is in
OFF On
completed status stand-by status.

1.3 Parameters reference value for the normal operation of unit


No. Debug item Parameter name Unit Reference
1 Outdoor temperature ℃ ——
●When compressor starts, discharge temp in
cooling mode is within 70~105℃ and at least
System ODU Compressor 10℃ higher than the high pressure saturation
2 parameters parameters discharge ℃ temp;
temperature ●As for temp in heating mode, it is within 65~90℃
and at least 10℃ higher than the high pressure
saturation temp.

82
Duct type split Air conditioner Inverter Series

●In cooling mode, defrosting temp is 4~10 ℃


Defrosting lower than system’s high pressure value;
3 ℃
temperature ●In heating mode, defrosting temp is about 2℃
different from system’s low pressure value.
●In cooling mode, the normal high pressure value
is within 20℃~55℃. According to the change of
ambient temp and system’s operating capacity,
the high pressure value will be 10℃~30℃ higher
than ambient temp. The higher ambient temp is,
System high the smaller temp difference is. If ambient temp is
4 ℃
pressure 25~35℃ in cooling mode, system’s high pressure
value will be within 44~53℃.
●In heating mode, if ambient temp is above -5℃,
system’s high pressure value is within 40~52℃. If
ambient temp is low and many IDUs are turned
on, the high pressure will be lower.
●When ambient temp in cooling mode is 25~35℃,
the low pressure value is 0~8℃.
5 System low pressure ℃
●When ambient temp in heating mode is above
-5℃, the low pressure value is -15~8℃.
●In cooling mode, the thermal electronic
Opening angle of expansion valve remains 480PLS.
6 PLS
thermal EXV ●In heating mode, the adjustable opening angle of
EXV is 60~480PLS.
Compressor working When compressor works normally, the current is
7 A
current no more than 23.0A.
When ambient temperature is below 35℃, IPM
Compressor’s IPM
8 ℃ temperature is lower than 70℃. Maximum
temp
temperature is 80℃.
9 IDU ambient temp ℃ ——
Indoor heat ●According to ambient temp, for a same IDU in
10 exchanger’s inlet ℃ cooling mode, the inlet temp will be 1 ℃ ~7 ℃
temp lower than the outlet temp, and 4~9℃ higher than
IDU Indoor heat the low pressure value.
11 parameters exchanger’s inlet ℃ ●For a same IDU in heating mode, the inlet temp
temp will be 10℃~20℃ lower than the outlet temp.
●In cooling mode, the opening angle of indoor
Opening angle of EXV varies within 40~480PLS.
12 PLS
indoor EXV ●In heating mode, the opening angle of indoor
EXV varies within 70~480PLS.
Communication Number of IDUs detected by software is the same
13 Communication data —
parameters with the actual number. No communication error.
Indoor unit can drain water out completely and
smoothly. Condensate pipe has no backward
14 Drainage system —— — slope of water; Water of outdoor unit can be
drained completely through drain pipe. No water
drop from unit base.
Compressor and indoor/outdoor fan motor do not
15 Others —— —
have strange noise. Unit can operate normally.

2 Malfunction List
2.1 Malfunction list for the IDU
Display Display Display
Content Content Content
code code code
Wrong number of indoor
Malfunction of Malfunction of water
L0 L9 unit for one-to-more indoor d8
indoor unit temperature sensor
unit
Indoor fan Wrong series for
L1 LA d9 Malfunction of jumper cap
protection one-to-more indoor unit
Alarming due to bad air Abnormal address for
L2 E-heater protection LH dA
quality indoor unit
The indoor unit model can’t
Water overflow Abnormal PCB for wired
L3 LC match with outdoor unit dH
protection controller
model

83
Duct type split Air conditioner Inverter Series

Power supply
Abnormal code-dialing
L4 of wired controller d1 Poor indoor PCB dC
setting of capacity
is faulted
Freeze prevention Malfunction of ambient Malfunction of air exhause
L5 d3 dL
protection temperature sensor temperature sensor
Malfunction of entry tube Malfunction of indoor C02
L6 Mode shock d4 dE
temperature sensor sensor
Malfunction of exit tube Communication
L7 No main indoor unit d6 C0
temperature sensor malfunction
Insufficient power Malfunction of humidity
L8 d7 AJ Clean alarming for filter
supply sensor
db Special code: engineering debugging code

2.2 Status display table for indicators on main board of ODU


Display Display Display
Content Content Content
code code code
Malfunction of Low-temperature
E0 E1 High pressure protection E2
outdoor unit protection for dicharge
Loose protection for
Low pressure Discharge high temperature
E3 E4 EC discharge temperature
protection protection for compressor
sensor for compressor 1
Poor main board of Malfunction of high pressure Malfunction of low
F0 F1 F3
outdoor unit sensor pressure sensor
Malfunction of
discharge Overcurrent protection for
F5 J0 Other module protection J1
temperature sensor compressor 1
for compressor 1
Air-mixing protection High pressure ration Low pressure ratio
J7 J8 J9
for 4-way valve protection of system protection of system
High pressure is too Malfunction for outdoor Maflunction of defrosting
JL b1 b2
low ambient temperature sensor temperature sensor 1
Maflunction of Malfunction of liquid Malfunction of gas
b3 defrosting b4 temperature sensor for b5 temperature sensor for
temperature sensor 2 subcooler subcooler
Malfunction for
Malfunction for temperature Malfunction of gas exit
temperature sensor of
b6 b7 sensor of exit tube of gas and b9 temperature sensor for
inlet tube of gas and
liquid separator liquid separator (exit tube A) heat exchanger
Driven board of
Abnormal clock of Malfunction driven board for
bH P0 P1 compressor works
system compressor
abnormally
Power voltage
protection for the Reset protection for the driven Driven PFC protection of
P2 P3 P4
driven board of module of compressor compressor
compressor

Overcurent protection Malfunction of driven


Driven IPM module protection
P5 for inverter P6 P7 temperature sensor for
for compressor
compressor compressor

Overheating High voltage protection


Desynchronizing protection for
P8 protection for driven P9 PH for driven DC bus bar of
inverter compressor
IPM of compressor compressor
Circuit malfunction of
Low voltage protection for
driven current Phase-losing of inverter
PC PL driven DC bus bar of PE
detection for compressor
compressor compressor
Malfunction of driven
Failure start up for inverter AC current protection for
PF charging loop for PJ PP
compressor inverter compressor
compressor
Preheat time is not Capacity code of outdoor
Insufficient refrigerant
U0 enough for U2 unit/wrong setting of jumper U4
protection
compressor cap
Wrong address for
Malfunction of pipeline for
U5 the driven board of U6 Alarm due to abnormal valve U8
indoor unit
compressor
Malfunction of Wrong code-dialing
Setting for indoor unit and
U9 pipeline for outdoor UC UL during emergency
oudoor unit is succeeded
unit operation

84
Duct type split Air conditioner Inverter Series

Display Display Display


Content Content Content
code code code
Communication malfunction Driven communication
Refrigerant-charging for indoor unit, outdoor unit malfunction between
UE C0 C2
is invalid and wired controller of indoor main board and inverter
unit compressor
Driven
Alarming due to
communication
Malfunction of indoor engineering series
C3 malfunction between C4 C5
unit-lacking number shock of indoor
main board and
unit
inverter compressor
Alarming due to
Emergency status of
C6 wrong quanity of C8 C9 Emergency status of fan
compressor
outdoor unit
Energycy status of No malfunction of main
CA CH High rated capacity CC
module control unit
Malfunction of main control
CL Low rated capacity CF CJ Address shock of syste
unit
Communication
malfunction between Distribution overflow of Ip
CU Cb A0 Debugging for unit
indoor unit receiving address
lamp board
Operational
A1 parameter inquiry of A2 Refrigerant recovery A3 Defrosting
compressor
Heat pump function
A4 Oil return A5 On-line test A6
setting
Vacuum pump
A7 Quit mode setting A8 A9 IPLV test
mode
EU AA class energy Charge refrigerant
AA AH Heating AL
efficiency test mode automatically
Charge refrigerant by
AE AF Fan blow AJ Cleaning alarm for filter
hand
Startup debugging Long-distance emergency
AP AU Ab Emergency stop
confirmation of unit stop
Defrosting period K 1
Ad Limit opereation n0 SE setting for the operation n1
setting
Upper limit setting for
the collocation Engineering series
Limit setting for the maximum
n2 matching ratio for n4 n6 number inqury for indoor
ouput capacity
indoor unit and unit
outdoor unit
n7 Malfunction inquiry n8 Parameters inquiry nA Heat pump unit
nH Heating only model nC Cooling only model nE Negative code
nF Fan model

3 Troubleshooting
3.1 Exception Analyzing and Troubleshooting(IDU)
3.1.1 “d1” Indoor circuit board error

Error display: IDU wired controller and IDU receive light board will display
Error judgment condition and method:

Check if the reading of address chip and memory chip of IDU mainboard is normal. If the data of
address chip and memory chip cannot be read, it is abnormal
Possible reason:

■Address chip is abnormal


■Memory chip is abnormal. Replace main control board directly
Troubleshooting:

85
Duct type split Air conditioner Inverter Series

Replace main control board directly


3.1.2 “d3” Ambient temperature sensor error

Error display: IDU wired controller and IDU receive light board will display

Error judgment condition and method:


Sample the AD value of temperature sensor through temperature sensor detecting circuit and judge
the range of AD value, If the sampling AD value exceeds upper limit and lower limit in 5 seconds
continuously, report the error
Possible reason:

■Poor contact between ambient temperature sensor and terminal in mainboard interface
■Ambient temperature sensor is abnormal
■Detecting circuit is abnormal
Troubleshooting:

3.1.3 “d4” Inlet pipe temperature sensor error

Error display: IDU wired controller and IDU receive light board will display
Error judgment condition and method:

Sample the AD value of temperature sensor through temperature sensor detecting circuit and judge
the range of AD value. If the sampling AD value exceeds upper limit and lower limit in 5 seconds
continuously, report the error
Possible reason:

■Poor contact between inlet pipe temperature sensor and terminal in mainboard interface
■Inlet pipe temperature sensor is abnormal
■Detecting circuit is abnormal
Troubleshooting:

86
Duct type split Air conditioner Inverter Series

3.1.4 “d6” Outlet pipe temperature sensor error

Error display: IDU wired controller and IDU receive light board will display
Error judgment condition and method:

Sample the AD value of temperature sensor through temperature sensor detecting circuit and judge
the range of AD value. If the sampling AD value exceeds upper limit and lower limit in 5 seconds
continuously, report the error
Possible reason:

■Poor contact between outlet pipe temperature sensor and terminal in mainboard interface
■Outlet pipe temperature sensor is abnormal
■Detecting circuit is abnormal

87
Duct type split Air conditioner Inverter Series

3.1.5 “d9” Jumper cap error

Error display: IDU wired controller and IDU receive light board will display
Error judgment condition and method:
Possible reason:

If jumper cap model doesn’t match with mainboard, report the error
■Jumper cap is not installed
■Jumper cap model is wrong
■Detecting circuit is abnormal
Troubleshooting:

88
Duct type split Air conditioner Inverter Series

3.1.6 “dH” wired controller circuit board error

Error display: IDU wired controller and IDU receive light board will display
Error judgment condition and method:

Wired controller IIC communication is abnormal


Possible reason:

■Communication of wired controller touch button board and display board IIC is abnormal;
■Read and write of wired controller memory chip IIC is abnormal (when memory chip is existed);
Troubleshooting:

3.1.7 “dC” Capacity DIP switch setting error

Error display: IDU wired controller and IDU receive light board will display
Error judgment condition and method:
If capacity DIP switch is set to the wrong position, report the error.
Possible reason:
■Capacity DIP switch is set to the wrong position
■Detecting circuit is abnormal
Troubleshooting:

89
Duct type split Air conditioner Inverter Series

3.1.8 “db” Project debugging


Error display: ODU mainboard, IDU wired controller and IDU receive light board will display

Error judgment condition and method:

This is a status code of project debugging, not a error code. When IDU or ODU displays this code, it
means the unit is under debugging status and the IDU cannot be operated.
Troubleshooting: ——
Possible reason:——

3.1.9 “L1” Indoor fan protection

Error display: IDU wired controller and IDU receive light board will display
Error judgment condition and method:

Check if the rotation speed of IDU is too slow, or it stops rotation, or protection signal of outdoor fan
is transferred. If yes, it is judged that indoor fan protection occurs.
Possible reason:

■Motor stops operation or it is blocked


■IDU mainboard is abnormal
Troubleshooting:

90
Duct type split Air conditioner Inverter Series

3.1.10 “L4” Power supply overcurrent protection

Error display: IDU wired controller and IDU receive light board will display
Error judgment condition and method:

Check if the power supply current from IDU to wired controller is normal. If power supply current is
too big, it is judged that the current is abnormal.

91
Duct type split Air conditioner Inverter Series

Possible reason:

■Power supply conducting wire of wired controller is short circuited


■IDU mainboard is abnormal
■Mainboard of wired controller is abnormal
Troubleshooting:

3.1.11 “L5” Freeze protection

Error display: IDU wired controller and IDU receive light board will display
Error judgment condition and method:

Check IDU pipe temperature. When pipe temperature is too low, freeze protection will be activated
to prevent freezing damage of evaporator.
Possible reason:

■IDU filter and evaporator are dirty


■IDU motor is blocked
■Refrigerant amount is insufficient
■Ambient temperature of IDU and ODU is too low
Troubleshooting:

92
Duct type split Air conditioner Inverter Series

3.1.12 “LC” Mismatch of IDU and ODU models

Error display: IDU wired controller and IDU receive light board will display
Error judgment condition and method:

When some IDUs or devices which cannot be identified by some ODUs are installed in the system,
mismatch error of IDU and ODU models will occur.
Possible reason:

■Mismatch of IDU and ODU


Troubleshooting:
When some IDUs or devices which cannot be identified by some ODUs are installed in the system (E.g.
floor heating device is installed in modular DC inverter multiple VRF system), the error will occur. Please
remove the relevant IDU devices or replace the ODU with suitable model.

3.2 Exception Analyzing and Troubleshooting(ODU)


3.2.1 Communication malfunction

93
Duct type split Air conditioner Inverter Series

94
Duct type split Air conditioner Inverter Series

3.2.2 High pressure protection

3.2.3 Low-pressure protection

95
Duct type split Air conditioner Inverter Series

Low pressure
protection

NO Measure YES Replace main


Measure whether the low pressure whether the
is too low with manometer board of outdoor
pressure switch
unit
is normal

NO
Replace
yes pressure switch

YES
Charge refrigerant according to the volume
Check whether the refrigerant-
charging volume is insufficient on nameplate; check whether there is
leakage for the system

NO
NO
Check whether gas valve and liquid Open the valve
valve are open completely
completely

YES

NO Cover the panel


Check whether the panel of
outdoor unit is covered and sealed of outdoor unit
well
well

YES

NO
Check whether the air can blow Eliminate obstacles and
smoothly at the heat exchanger of
indoor unit and outdoor unit sundries

YES

NO
Measure the
Check whether the indoor fan
and outdoor fan can operate circumstances of fan
motor and signal input

YES

NO
Measure the
Check whether the indoor swing
blade is open completely circumstances of swing
motor and signal input

YES

NO
Check whether the electronic
expansive value for indoor unit and
Engage valve and
outdoor unit can operate normally coil

YES
NO
Mainly check the air inlet and air outlet
connecting indoor unit and main pipe, and the
Blockage for
expansive valve for indoor unit and outdoor unit.
system pipeline
Replace electronic expansion valve, dry
strainer,ect.

96
Duct type split Air conditioner Inverter Series

3.2.4 Discharge temperature protection

3.2.5 Mafunction of temperature sensor


97
Duct type split Air conditioner Inverter Series

3.2.6 Malfunction of sensor

3.2.7 Unit and main board can’t be energized


Unit and main board can’t
be energized

NO Check whether it’s


Measure whether voltage between pole L the malfunction of
and pole N of wiring board is 220V power supply for
wiring board

YES

NO
Check whether there’s power Replace filter
supply for filter board board

YES

Replace main board


of outdoor unit

98
Duct type split Air conditioner Inverter Series

3.2.8 Failure start-up

3.2.9 Reset protection for drive module of compressor, drive PFC


protection for compressor, malfunction of drive temperature sensor for
compressor, circuit malfunction of drive current detection for
compressor

3.2.10 Drive IPM overtemperature protection for compressor

99
Duct type split Air conditioner Inverter Series

Wired
controller
displays P0

LED3 dual-8
nixie tube
displays P8

yes no
Whether two IPM
module is tightened?

Replace main Tighten


board module

Work normally

100
Duct type split Air conditioner Inverter Series

3.2.11 Desynchronizing protection for inverter compressor

3.2.12 Failure startup for inverter compressor

101
Duct type split Air conditioner Inverter Series

3.2.13 Loop malfunction of driven charging for compressor

3.2.14 Malfunction of memory chip for inverter compressor

102
Duct type split Air conditioner Inverter Series

3.2.15 Overcurrent protection for inverter compressor, IPM module


protection, phase-lacking of inverter compressor

3.2.16 High pressure protection for driven DC bus bar of compressor,


low pressure protection for driven DC bus bar of compressor

103
Duct type split Air conditioner Inverter Series

3.2.17 AC current protection for inverter compressor

3.2.18 Communication malfunction between main contoller and driver of


inverter compressor

4 After-sales Emergency Masures


When some unrecoverable fault occurs to one module which is connected with several others in
parallel, the following emergency measures are recommended to guarantee the heating or cooling

104
Duct type split Air conditioner Inverter Series

capacity of the indoor units and the service life of modules except the faulted one are not affected.
Step 1: set all indoor units under “Off” mode and cut off the power supply to the indoor and outdoor
units.
Step 2:.shut off all cutoff valves of the faulted outdoor unit, including the cutoff valves of the
liquid/gas pipe as well as the oil balancing valve.
Step 3: cut off the air switch of the module.
Step 4: remove the communication line between the faulted module and other modules which are
still kept connected through the communication line.
Step 5: readjust the address and quantity settings on the main board of the modules except the
faulted one.
Step 6: power and restart the unit.

5 Wiring Diagram
Advertence: These diagrams only for reference ,the actually diagram please reference the
diagram on actually unit.
FGR20Pd/DNa-X(I)/FGR25Pd/DNa-X(I)/FGR30Pd/DNa-X(I):

FGR40Pd/D(2)Na-X(I):

105
Duct type split Air conditioner Inverter Series

FGR20Pd/DNa-X(O):

FGR25Pd/DNa-X(O):

106
Duct type split Air conditioner Inverter Series

FGR30Pd/DNa-X(O):

6 Disassembly And Assembly Procedure Of


Main Parts
107
Duct type split Air conditioner Inverter Series

Introduction to Main Parts


Disassembly and Assembly of Compressor
Remark: Make sure that there isn’t any refrigerant in pipe system and the power supply is cut off before removal of the
compressor
Step Illustration Handling Instruction

①Unscrew the retaining screw of


Earmark the
colour of power cord with screwdriver.
wire ②Unplug the power cord.
correspondi
1.Disconnect the power cord ng to the Note:Earmark the colour of wire
terminal corresponding to the terminal when
Removing the wire , and the
mixture can be avoided when
recovering the wire connection.

2. Cut off the connection between Don’t leave the welding slag inside
compressor and pipes pipes

① Unscrew retaining nuts of the


footing of compressor
3.Remove the compressor from
the chassis ② Remove the compressor from
the chassis
Hold it tightly to avoid accident.

①Place the new compressor on


4.Fix the new compressor on chassis
chassis ②Fix retaining nuts of comprssor
footing.

5. Connect the compressor with


Don’t block it by welding.
system pipes

Note:Earmark the colour of wire


6.Connect the power cord of corresponding to the terminal when
compressor connecting the wire , and the
mixture can be avoided

7.Recover the electric heating tape


Enwind the bottom of compressor
of compressor and discharge
with electric heating tape and fix it.
temperature sensor,etc.

Check if the wiring is correct with


8.Check if the compressor
reference to circuit diagram and
rotates in reverse and if lubricant
check if there is any leakage after
have leaked
welding.

Disassembly and Assembly of 4-way valve

108
Duct type split Air conditioner Inverter Series

Remark: Make sure that there isn’t any refrigerant in pipe system and the power supply is cut off before removal of
4-way valve.
Step Illustration Handling Instruction
Place electric coils far away from
Remove electric coils of 4- way the 4-way valve to prevent the
valve connecting line of 4-way valve from
burning when succeeding welding.

Disconnect the pipe (site D in


Don’t leave welding slag inside
illustration) of 4-way valve and
pipes.
discharge pipe

Disconnect the pipe (site E in


Don’t leave welding slag inside
illustration) of 4-way valve and
pipes.
connecting pipe

Disconnect the pipe (site C in


Don’t leave welding slag inside
illustration) of 4-valve and
pipes.
connecting pipe

Disconnect the pipe (site S in


Don’t leave welding slag inside
illustration) of 4-way valve and
pipes.
connecting pipe

Remove 4-way valve after it is


Remove the 4-way valve
cooled.

Install new 4-way valve in reversed order and wrap it with wet cloth before welding.

7 Exploded Views And Part List


7.1 Indoor Unit
1、Model: FGR20Pd/DNa-X(I)、FGR25Pd/DNa-X(I)、FGR30Pd/DNa-X(I)
Exploded View:

109
Duct type split Air conditioner Inverter Series

Model FGR20Pd/DNa-X(I) FGR25Pd/DNa-X(I) FGR30Pd/DNa-X(I)


NO Product Code CF010N0730 CF010N0740 CF010N0750 Qty
Part Name Part Code Part Code Part Code
1 Filter Sub-Assy 11725211 11724102 11724102 2
2 Water Tray Assy 01284620 01284306 01284306 1
3 Display Board 300001000097 300001000097 300001000097 1
4 Sensor Sub-assy 390002000058 390002000058 390002000058 1
5 Choke Plug of Water Pipe 76712454 76712454 76712454 2
6 Top Cover Board Sub-assy 01265359 01264100090 017011000037 1
7 Hook 02112466 02112466 02112466 4
8 Electric Box Assy 100002002010 100002002010 100002002010 1
9 Radiator 49018000068 49018000068 49018000068 1
10 Reactor 43130189 43130189 43130189 1
11 Teminal Board 4201800002601 4201800002601 4201800002601 1
12 Main Board 300002000383 300002000383 300002000383 1
13 Teminal Board 42010259 42010259 42010259 1
14 Main Board 300002000357 300002000357 300002000357 1
15 Electronic Expansion Valve 43044100190 43044100190 43044100190 1
16 Eletric Expand Valve Fitting 4304413205 4304413205 4304413205 1
17 Strainer 0741410000601 0741410000601 0741410000601 2

110
Duct type split Air conditioner Inverter Series

Model FGR20Pd/DNa-X(I) FGR25Pd/DNa-X(I) FGR30Pd/DNa-X(I)


NO Product Code CF010N0730 CF010N0740 CF010N0750 Qty
Part Name Part Code Part Code Part Code
18 Evaporator Assy 011001000372 011001000371 011001000271 1
19 Motor for Centrifugal Fan(Right Type) 15705307 1570411801 10300400004701 1
20 Brushless DC Motor 15704100009 15704100009 15704100009 1
21 Motor for Centrifugal Fan(Left Type) 15705306 15704118 103004000047 1
2、Model: FGR40Pd/D(2)Na-X(I)
Exploded View:

Model FGR40Pd/D(2)Na-X(I)
NO Product Code CF010N0760 Qty
Part Name Part Code
1 Air Outlet Panel Sub-assy 000040000029 1
103004000048/
2 Motor for Centrifugal Fan 1/1
10300400004801

111
Duct type split Air conditioner Inverter Series

3 Left Side Plate Assy 000080000020 1


4 Hange frame assy 000249000001 1
5 Brushless DC Motor 150104000015 1
6 Top Cover Board Sub-assy 017011000039 1
7 Water Collecting Tray Assy 007070000002 1
8 Strainer 07210037 1
9 Main Board 300002000357 1
10 Terminal Board 420001000004 1
11 Terminal Board 4201800002601 1
12 Main Board 300002000380 1
13 Radiator 49018000013 1
14 Reactor 43130189 1
15 Electric Expand Valve Fitting 4304413205 2
16 Electric Box Assy 100002001945 1
17 Strainer 0741410000601 2
18 Electronic Expansion Valve 43044100190 2
19 Strainer 07415210 2
20 Evaporator Assy 011001000429 1
21 Access panel sub-assy 000170000001 1
22 Filter Sub-Assy 07210029 1
23 Temperature Sensor 3900028024G 1
24 Temperature Sensor 3900028022G 1
25 Ambient Temperature Sensor 39000198G 1

7.2 Outdoor Unit


1、Model:FGR20Pd/DNa-X(O)、FGR25Pd/DNa-X(O)
Exploded View:

112
Duct type split Air conditioner Inverter Series

Model FGR20Pd/DNa-X(O) FGR25Pd/DNa-X(O)


NO Product Code CF010W0730 CF010W0740 Qty
Part Name Part Code Part Code
1 Front Grill 01572800003 01572800003 2
2 Diversion Circle 10474100003 10474100003 2
3 Cabinet Assy 01514100015 01514100023 1
4 Left Side Plate 01314100084P 01314100090P 1
5 Handle \ 26235253 1
6 Front Side Plate 01314100082P 01314100091P 1
7 Axial Flow Fan 10434100006 10434100008 2
8 Compressor and Fittings 00204100013 00204100033 1
1570280000401\ 15704100010/
9 Brushless DC Motor 1/1
1570280000402 1570410001001
10 Motor Support Assy 000046000007 000046000057 1
11 Electrical Heater(Compressor) 7651521212 7651521212 1
12 Oil Separator 07424105 07424100050 1
13 Cut off Valve 07334100011 07334100011 1
14 Cut off valve 07334100054 07334100012 1
15 Pressure Protect Switch 4602000902 4602000902 1
16 Pressure Protect Switch 46020007 46020007 1
17 One Way Valve 07334100075 07335210 1
18 Strainer 07212402 07414100026 1
19 4-way Valve 43000338 43000339 1
20 Strainer 07212403 07415200002 1
21 Bidirection Strainer / 07220016 1

113
Duct type split Air conditioner Inverter Series

Model FGR20Pd/DNa-X(O) FGR25Pd/DNa-X(O)


NO Product Code CF010W0730 CF010W0740 Qty
Part Name Part Code Part Code
22 One Way Valve 07133618 04324001 1
23 Electronic Expansion Valve 43044100173 43044100173 1
24 Electric Expand Valve Fitting 4304413219 4304413205 1
25 Gas-liquid Separator 07424140 07424141 1
26 Rear Side Plate 01314100083P 01314100092P 1
27 Rear Grill 01574100011 01574100014 1
28 Strainer 07212403 07212121 1
29 Condenser Assy 000100000042 000100000059 1
30 Electric Box Assy 100002001182 100002001106 1
31 Radiator 430034000028 49018000080 1
32 Radiator 430034000027 49018000088 1
33 Terminal board 420001000019 420001000019 1
34 Terminal board 42011221 42011221 1
35 Main Board 300027000340 300027000392 1
36 Main Board 300027000244 300027000244 1
37 Filter Board 30223000118 30228000015 1
38 Reactor 4313017401 4313017401 1
39 Coping 01264100047P 01264100052P 1
40 Drainage Joint 26113009 26113009 1
41 Sensor Sub-assy 390002000046 390002000046 1
42 Magnet Coil 4300040032 4300040032 1

2、Model: FGR30Pd/DNa-X(O)
Exploded View:

114
Duct type split Air conditioner Inverter Series

Model FGR30Pd/DNa-X(O)
NO Product Code CF010W0750 Qty
Part Name Part Code
1 Front Grill 01572800003 2
2 Diversion Circle 10474100003 2
3 Cabinet 01514100016P 1
4 Front Side Plate 01314100091P 1
5 Handle 26235253 2
6 Axial Flow Fan 10434100008 2
7 Brushless DC Motor 15704100010 1
8 Brushless DC Motor 1570410001001 1
9 Chassis Assy 209058000011 1
10 Oil Separator 07424100050 1
11 Cut off Valve 07130208 1
12 Cut off Valve 07334100013 1
13 Strainer 07415200002 1
14 Compressor and Fitting 00204100015 1
15 Cut off Valve 07334100014 1
16 Strainer 07414100024 1
17 Pressure Protect Switch 4602000902 1
18 Pressure Protect Switch 46020007 1
19 4-way Valve 43000339 1
20 Gas-liquid Separator 07424100048 1

115
Duct type split Air conditioner Inverter Series

Model FGR30Pd/DNa-X(O)
NO Product Code CF010W0750 Qty
Part Name Part Code
21 One way Valve 04324001 1
22 Electronic Expansion Valve 43044100190 1
23 Reactor 4313017401 1
24 Terminal board 42011221 1
25 Terminal board 420001000019 1
26 Main Board 30223000039 1
27 Electric Box Assy 100002001274 1
28 Radiator 49018000080 1
29 Radiator 49018000088 1
30 Filter Board 30228000015 1
31 Main Board 300027000244 1
32 Rear Grill 01574100014 2
33 Filter 0341010701 1
34 Condenser Assy 000100000050 1
35 Drainage Joint 26113009 1
36 Drainage hole Cap 76715005 3
37 Electric Expand Valve Fitting 4304413205 1
38 Electric Heater(Compressor) 7651540714 1
39 Magnet Coil 4300040032 1
40 Sensor Sub-assy 390002000027 1
41 Coping 01264100052P 1

116