Lvped208006en (Web)
Lvped208006en (Web)
Lvped208006en (Web)
Compact NSX
Masterpact NW
DC - DC PV
Power circuit breakers and switch-disconnectors
direct current from 16 to 4000 A
A complete DC offer
from 16 to 4000 A
Compact NSX and Masterpact NW direct current (DC) circuit breakers are used to
protect and control low-voltage distribution systems.
0
V X63 )
0 NS 550 A
/ 75 V X40
0 (
36
kA 750 NS 400A)
k A/ V
500
0
100
F 5 (
/ V X2 )
4P S 36
kA 500 0V
NS 250 A
3P/ 5 kA
/
/ 50
0
X16 )
(
F 8 A NS 160 A
M 0k 0V
10 / 25
0 (
2P V X10 )
S 6k
A 250 NS 100 A
3 k A/ 0V (
F 50 / 25
N 5 kA
8
1P M
The Compact NSX range is designed for DC voltages from 24 to 750 V and offers:
b a wide selection of models suited to many applications:
v 1, 2, 3 and 4 poles up to 160 A
v 3 and 4 poles from 250 to 630 A
b high breaking capacities, with four performance levels F, N, M and S:
vF
- 36 kA in a 1 pole version, for systems y 250 V
- 36 kA in a 2 poles version, for systems y 500 V
- 36 kA in a 3 or 4 poles version, for systems y 750 V
vN
- 50 kA in a 1 pole version, for systems y 250 V
vM
- 85 kA in a 1 pole version, for systems y 250 V
- 85 kA in a 2 poles version, for systems y 500 V
vS
- 100 kA in a 2 poles version, for systems y 500 V
- 100 kA in a 3 or 4 poles version, for systems y 750 V
b fewer frame sizes: just two poles pitches (35 and 45 mm) for easy integration in
installation systems (enclosures, machines, etc.)
b accessories for insulation and series or parallel connection of poles, suited to the
particularities of DC applications
b fixed and withdrawable versions (3 and 4 poles, DC type).
Breaking capacity Icu for 250 V per pole and L/R = 15 ms (1)
(1P: 250 V, 2P: 500 V, 3P: 750 V)
(1) L/R = time constant of the distribution system (see page A-7).
II
40 A)
V NW 4000
0 (
/ 90
0
2 A)
kA 0V NW 2000
35 A / 75 0V 0 (
0k
1 A )
H 5 / 50 NW 1000
5k
A 0V
/ 50
H (
8 A
H 3 5k
N
The Masterpact NW range is designed for DC voltages from 24 to 900 V and offers:
b 2 versions : C/D (3 poles)
E (4 poles)
b three current ratings: 1000, 2000 and 4000 A
b two high breaking-capacity levels N and H.
Breaking capacity Icu for L/R = 15 ms (1) for 500, 750 or 900 V system voltages:
vN
- 35 kA for systems y 500 V
vH
- 85 kA for systems y 500 V
- 50 kA for systems y 750 V
- 35 kA for systems y 900 V
b two models:
v circuit breaker for the protection of power circuits and loads
v switch-disconnector for circuit control and disconnection
b fixed and drawout versions for the entire range.
(1) L/R = time constant of the distribution system (see page A-7).
III
VI
@
Firewall
bus
Mod
Modbus
Modbus IFM
interface
VII
Schneider Electric’s Masterpact NW HADCD-PV switch-disconnectors are used for circuit control and disconnection.
VIII
Presentation 2
Functions
A-1
and characteristics
Installation
B-1
recommendations
Dimensions and
C-1
connection
Additional
E-1
characteristics
Catalogue numbers
F-1
and order form
DB416526.eps
The Compact NSX and Masterpact NW DC - DC PV ranges are designed for use
under 1000 V for photovoltaic application.
standards: France NF, Germany VDE, UK BS, Australia AS, Italy CEI
Compact b the specifications of the marine classification companies (Veritas, Lloyd’s Register
of Shipping, Det Norske Veritas, etc.)
NSX1250 NA DC PV b French standard NF C 79-130 and the recommendations issued by the CNOMO
organisation for the protection of machine tools. For United States UL, Canadian
Ui 1000 V Uimp 8 kV CSA, Mexican NOM and Japanese JIS standards, please consult us.
Ue (max) 1000V Compact NSX and Masterpact NW DC - DC PV switches and auxiliaries comply with
Icw 20kA/1s the following:
b the main international standards and in particular IEC 60947-2 (circuit breaker),
Icm 20kA
IEC 60947-3 (switch-disconnectors)
Ie 40°C 1250A
bb European (EN 60947-1, EN 60947-2 and EN 60947-3) and the corresponding
DC22B national standards: France NF, Germany VDE, United Kingdom BS, Australia AS,
Italy CEI.
Open communication
Compact NSX and Masterpact NW DC devices can be equipped with
communication options for integration in a supervision system via Modbus/JBus bus.
IEC / EN 60947-3 Pollution degree
Compact NSX and Masterpact NW DC circuit breakers are certified for operation
NSX1250 NA DC PV rating plate.
under pollution conditions in industrial environments, as per standard IEC 60947,
corresponding to:
b pollution degree 3 (Compact NSX)
b pollution degree 4 (Masterpact NW).
Tropicalisation
DB104462.eps
DB416572.eps
Masterpact
NW20 HADCD-PV
Compact NSX and Masterpact NW DC circuit breakers have successfully passed
Ui 1000V Uimp 12kV the tests prescribed by the following standards for extreme atmospheric conditions:
Ue 1000 V c 3P in series
Icw 85kA/1s b IEC 60068-2-1 - dry cold (-40 °C)
Icm 85kA b IEC 60068-2-1 - dry heat (+85 °C)
b IEC 60068-2-30 - damp heat (95 % relative humidity at +55 °C)
b IEC 68-2-52 (level 2) - salt mist.
IEC 60947-3
Environmental protection
Ith 2000A 55°C
Schneider Electric circuit breaker ranges benefit from Eco-design:
Ue (V) Ie (A) b use of materials not representing a danger to the environment
DC22A 1000 2000 b non-polluting production units complying with ISO 14001 standards
b filtered breaking for high current ratings to avoid pollution in the switchboard
b low dissipated energy per pole, making energy losses insignificant
NW20 HDC-D rating plate. NW20 HADCD-PV rating
b marking of products in view of sorting recyclable materials at the end of the service
plate.
life.
connection of poles
Series connection - controlled temperature rise and
guaranteed performance
Schneider Electric DC circuit breakers comply with product standards
IEC 60947-1 and 2.
To that end, series connection of poles meets:
b temperature-rise conditions. Connections specifically designed to dissipate heat
mean the thermal model is equivalent to that for AC applications. The devices
dissipate the temperature rise produced by relatively short series connections
b optimum safety conditions. Connections are designed for extreme operating
conditions (insulation and safety clearances, ultimate breaking capacity, high
Compact NSX DC - safety and flexibility. pollution levels, etc.).
DB403286.eps
DB402976.eps
DB403287.eps
DB402977.eps
DB104468.eps
DB402606.eps
DB403289.eps
DB402978.eps
Four-pole devices
DB403290.eps
DB402979.eps
DB403291.eps
DB402980.eps
b All connections are possible for the fixed and Great flexibility for connections
withdrawable versions.
DB104475.eps
DB402981.eps
All connections are possible for the fixed and Indifferent connection of polarities.
withdrawable versions.
DB402982.eps
DB402606.eps
DB402988.eps
DB402252_55.eps
connections of the Masterpact NW DC
circuit breakers have to be respected in order to
ensure the magnetic threshold tolerances.
DB402264_55.eps
DB402989.eps
Front view: three-pole case - three poles in Rear view with connections.
series.
Version E
DB402990.eps
DB402276_55.eps
Front view: four-pole case - four poles in Rear view with connections.
series.
DB403292.eps
DB402984.eps
technique virtually doubles, triples or quadruples
the current rating depending on the type of
circuit breaker and thus reduces the cost of
solutions.
DB104485.eps
heat sinks.
DB402985.eps
Customer connections are made directly
to the connection plates after removing the heat
sinks.
DB104486.eps
DB402986.eps
DB402987.eps
Note: creation of the additional connection (1) is the responsibility of the panel builder or the
installer.
DB416273.eps
with heatsinks
2 Series connections
(dissipators)
with heatsinks
(dissipators)
4 interphase
barriers or
terminal shields
2 terminal shields
F1-
F1+
F1-
F2-
Photovoltaic panels
F1+
F2+
F2-
F3- Photovoltaic panels
F2+
F3+
F3-
F3+
Ecodial
Presentation 2
Selection guide for DC circuit breakers
Types of DC distribution systems A-2
Solutions depending on the distribution system and the voltage A-3
Examples of circuit breaker selection A-5
Calculation of DC distribution-system characteristics
Short-circuit currents L/R time constant A-7
General characteristics of Compact NSX DC and DC PV
Operating conditions A-8
Compact NSX DC and DC PV A-9
Circuit breaker characteristics
Compact NSX100 DC to NSX630 DC A-10
Trip-unit characteristics
Types of trip units - Trip units for Compact NSX DC A-12
Accessories and auxiliaries
Overview of Compact NSX100 to 630 DC fixed version A-14
Overview of Compact NSX100 to 630 DC plug-in and withdrawable versions A-16
Electrical and mechanical accessories
Compact NSX100 to 630 DC A-18
Connection of fixed devices A-20
Connection of electrical auxiliaries A-22
Selection of auxiliaries for Compact NSX100/160/250 DC A-24
Selection of auxiliaries for Compact NSX400/630 DC A-26
Indication contacts for Compact NSX DC A-27
Rotary handles A-28
Motor mechanism A-30
Remote tripping A-31
Locks A-32
Sealing accessories A-33
Escutcheons and protection collars A-34
Circuit breaker characteristics
Compact NSX80 TM DC PV to NSX500 TM DC PV A-36
Switch-disconnectors characteristics
Compact NSX100 NA DC PV to NSX500 NA DC PV A-38
Compact NSX630b NA DC PV to NSX1600 NA DC PV A-40
Accessories and auxiliaries
Overview of Compact NSX80 TM to NSX500 TM DC PV circuit breakers A-42
Overview of Compact NSX100 NA to NSX500 NA DC PV switch-disconnectors A-43
Overview of Compact NSX630b NA to NSX1600 NA DC PV
switch-disconnectors A-44
General characteristics of Masterpact NW DC - DC PV
Operating conditions A-46
Masterpact NW DC and DC PV A-47
Masterpact NW10 to NW40 DC A-48
Trip-unit characteristics
Trip units for Masterpact NW DC A-50
Switch-disconnectors for PV application
Masterpact NW HADCD-PV A-52
Connections and safety clearances A-53
Communication
COM option in Masterpact NW DC A-54
Overview of functions A-55
Masterpact NW communication
Networks and sofware A-56
RCU utilities A-58
Supervision software A-59
Panorama of electrical and mechanical accessories
Masterpact NW10 to NW40 DC A-60
Installation recommendations B-1 Connection
Dimensions and connection C-1
Overview of solutions A-62
Electrical diagrams D-1
Additional characteristics E-1 Electrical and mechanical accessories
Catalogue numbers and order form F-1 Masterpact NW10 to NW40 DC A-64
A-1
There are three types of DC distribution systems (see Selection of a circuit breaker depends essentially on the distribution-system
the table). parameters presented below which are used to determine the corresponding
The operational voltage in conjunction with one of the characteristics:
three systems determines the number of poles taking b type of system - determines the type of product and the number of poles
part in current interruption. connected in series for each polarity
b rated voltage - determines the number of series poles taking part in current
interruption
b nominal current - determines the rated current of the circuit-breaker
b maximum short-circuit current at the point of installation - determines the breaking
capacity.
Types of systems
Earthed systems Isolated systems
The source has one earthed polarity (1) The source has an earthed mid-point
Diagrams and different faults
DB116982.eps
DB116983.eps
DB116984.eps
Fault analysis (neglecting resistance of earth electrodes)
Fault A b maximum Isc at U b maximum Isc at U/2 b no consequences
b only protected polarity concerned b only positive polarity concerned b the fault must be indicated by an IMD
b all poles of protected polarity must have b all poles of positive polarity must have (insulation-monitoring device) and cleared
breaking capacity u Isc max. at U breaking capacity u Isc max. at U/2 (standard IEC/EN 60364)
Fault B b maximum Isc at U b maximum Isc at U b maximum Isc at U
b if only one polarity (the positive here) is b both polarities are concerned b both polarities are concerned
protected, all poles of protected polarity must b all poles of the two polarities must have b all poles of the two polarities must have
have breaking capacity u Isc max. at U breaking capacity u Isc max. at U breaking capacity u Isc max. at U
b if both polarities are protected, to enable
disconnection, all poles of the two polarities
must have breaking capacity u Isc max. at U
Fault C No consequences b same as fault A b same as fault A with the same obligations
b all poles of the
negative polarity must have breaking capacity
u Isc max. at U/2
Double fault Double fault not possible, Double fault not possible, b maximum Isc at U
A and D or C and system trips on first fault system trips on first fault b only positive polarity (cases A and D) or
E negative (C and E) concerned
b all poles of each polarity must have breaking
capacity u Isc max. at U
Most unfavourable cases
Fault A and fault B (if only one polarity is Fault B Double fault A and D or C and E
protected)
Conclusion: selection of number of poles and breaking capacity
Layout of protection poles
b on only one polarity (1) b identical for each polarity b identical for each polarity
Number of series poles
Per polarity b all on same polarity b equal b equal
Total b 1, 2 or 3 without disconnection b 2 or 4 (2) b 2 or 4 (2)
b 2, 3 or 4 with disconnection
Breaking capacity
b all poles of the protected polarity u Isc max. b all poles of both polarities u Isc max. at U b all poles of each polarity u Isc max. at U
at U b all poles of each polarity u Isc max. at U/2
Disconnection of both polarities (3)
Possible by adding a pole to the non-protected b ensured b ensured
polarity
Implementation
See the selection table opposite
(1) Positive or negative, depending on the polarity connected to the exposed conductive parts.
(2) A 3P circuit breaker can be used if a 2P version does not exist. In this case, the central pole is not connected.
(3) Disconnection made possible by multi-pole breaking.
A-2
DB116985.eps
DB116986.eps
DB116987.eps
DB116988.eps
(and types of faults)
DB115851.eps
DB115851.eps
DB115850.eps
DB115851.eps
Single-pole. Two-pole (1). Two-pole (1). Two-pole (1).
250 V < Un y 500 V
DB115852.eps
DB115853.eps
DB115851.eps
DB115854.eps
Two-pole (1). Three-pole. Two-pole (1). Four-pole.
500 V < Un y 750 V
DB115855.eps
DB115854.eps
DB115856.eps
DB115857.eps
DB115857.eps
DB115857.eps
DB115859.eps
DB115859.eps
DB115859.eps
DB115859.eps
DB115859.eps
A-3
DB116985.eps
DB116986.eps
DB116987.eps
DB116988.eps
(and types of faults)
DB115861.eps
DB115861.eps
DB115861.eps
DB115861.eps
Parallel connection of poles divides the current per Parallel connection of poles, on the contrary, imposes the system voltage on
pole and optimises the rated current for systems that each pole, but is the means to:
do not exceed the withstand voltage of each pole. b divide the current flowing through each pole by the number of poles
The maximum useable rating and the value of the b increase the rated current.
magnetic setting are indicated (see page B-7). For example, the same Compact NSX630 DC 3P circuit breaker with three poles in
parallel provides:
b a maximum voltage of 250 V (250 V per pole)
b a rated current of 1500 A (see table page B-7)
b a breaking capacity of 100 kA / 250 V.
Consequently, a 630 A device used in a 250 V system can handle 1500 A.
A-4
DB115868.eps
b all poles of the two polarities must have breaking capacity u Isc max. at Un,
i.e. 60 kA/500 V in this case
b all poles of the each polarity must have breaking capacity u Isc max. at Un/2,
i.e. 60 kA/250 V in this case.
Selection possibilities - (see pages A-3 and A-4)
The tables indicate for 250 V < Un y 500 V and for this system:
b poles connected in series: two-pole 2P in series V selection 1
b poles connected in parallel: four-pole 2 x 2P parallel connected in series
V selection 2.
Circuit breaker selection - (see pages A-10 and B-7)
b selection 1: the 250 A rated current does not exist in 2P. It is possible to use a
Selection 1. Selection 2: Compact NSX160 DC 4P 250 A 3P DC type circuit breaker with the central pole not connected V selection 3
2 x 2P parallel mounted in series. b selection 2: the 160 A rated current (DC version) is suitable with a 2 x 2P
assembly connected in parallel because (see table page B-7):
v the rated current of the 2 x 2P assembly connected in parallel is In = 288 A > 250 A
DB115869.eps
Example 2
b Type of system - one polarity earthed
DB115870.eps
DB115872.eps
A-5
Selection of a Masterpact NW DC
Example 1
b
DB115870.eps
Example 2
b
DB115870.eps
A-6
Short-circuit currents
Calculation of the short-circuit current across the terminals of
DB403117.eps
a battery
During a short-circuit, the battery discharges a current equal to :
Vb
Isc =
Ri
b Vb = maximum discharge voltage (battery 100 % charged)
b Ri = internal resistance equivalent to all cells (a function of the capacity in
ampere-hours).
Example
b Consider a set of four 500 Ah batteries connected in parallel.
b Discharge voltage of one battery: 240 V (110 cells 2.2 V each).
b Discharge current of one battery: 300 A with a run-time of 30 minutes.
b Discharge current of all four batteries: 1200 A with a run-time of 30 minutes.
b Internal resistance 0.5 mW per cell, i.e. for one battery:
Ri = 110 x 0.5 x 10-3 = 55 x 10-3 W.
b Short-circuit current of one battery: Isc = 240 V / 55 x 10-3 W = 4.37 kA.
b Neglecting the resistance of the connections, for all four batteries discharging the
short-circuit current in parallel, the total short-circuit current is four times that of one
battery, i.e. Isc = 4 x 4.37 kA = 17.5 kA.
Note: if the internal resistance is not known, it is possible to use the following rough
approximation: Isc = kc where c is the capacity of the battery in ampere-hours and k is a
coefficient close to 10 and always less than 20.
from the load current (y In) to the short-circuit current Isc over a period of time that
depends on the value of the resistance R and inductance L of the short-circuited
loop.
The equation determining the current in the loop is:
U = Ri + L Di/Dt
The curve of I versus time is defined (neglecting In) by the equation:
I= Isc (1 - exp(t/t))
where t = L/R is the time constant for the rise to Isc.
DB403119.eps
To express breaking capacity, the interrupted short-circuit current with the following
time constants is used:
b L/R = 5 ms, fast short-circuit
b L/R = 15 ms, standardised value used in standard IEC 60947-2
b L/R = 30 ms, slow short-circuit.
In general, the value of the system time constant is calculated under worst-case
conditions, across the terminals of the generator.
A-7
(m)
Altitude
DB111389.eps
2000
Compact NSX circuit breakers are designed to operate at their rated values at
altitudes under 2000 metres.
Above 2000 metres, the changes in the characteristics of the ambient air (electrical
resistance, cooling capacity) result in a reduction of the characteristics below.
Altitude (m) 2000 3000 4000 5000
Compact NSX DC
Impulse withstand voltage Uimp (kV) 8 7.1 6.4 5.6
Rated insulation voltage (Ui) 750 710 635 560
Maximum rated NSX DC y 250 V 250 220 200 175
operationnal NSX DC 250 V to 500 V 500 440 400 350
DC voltage NSX DC 500 V to 750 V 750 660 600 525
Rated current (A) 1 x In 0.96 x In 0.93 x In 0.9 x In
Compact NSX DC PV
Impulse withstand voltage Uimp (kV) 8 7.1 6.4 5.6
Rated insulation voltage (Ui) 1000 900 800 700
Maximum rated operationnal DC voltage 1000 900 800 700
Rated current (A) 1 x In 0.96 x In 0.93 x In 0.9 x In
Vibrations
Compact NSX circuit breakers are guaranteed against electromagnetic or
mechanical vibrations.
DB111390.eps
Tests are carried out in compliance with standard IEC 68-2-6 for the levels required
by merchant-marine inspection organisations (Veritas, Lloyd’s, etc.):
b 2 to 13.2 Hz: amplitude ±1 mm
b 13.2 to 100 Hz: constant acceleration 0.7 g.
Excessive vibration may cause tripping, breaks in connections or damage to
mechanical parts.
Electromagnetic compatibility
Compact NSX circuit breakers are protected against:
DB111391.eps
Ambient temperature
Operating-temperature range
b Compact NSX circuit breakers and switches may be used between
-25 °C and +70 °C.
bb For temperatures higher than 40 °C (65 °C for circuit breakers used to protect
motor feeders), devices must be derated as indicated in the documentation.
b Circuit breakers and switches should be put into service under the normal,
ambient operating temperatures indicated above. Exceptionally, they may be put
into service when the ambient temperature is between -35 °C and -25 °C.
Derating
Above 40 °C, it is necessary to take into account the derating values.
Storage-temperature range
b Compact NSX circuit breakers and switches may be stored in their original
packing between -50 °C and +85 °C.
A-8
Degree of protection
Compact NSX DC circuit breakers offer the following protection characteristics
depending on the installation conditions:
b IP: degree of protection (standard IEC 60529)
b IK: protection against external mechanical impacts (standard EN 50102).
Compact NSX DC
Bare circuit breaker with terminal shields
With toggle IP3X IK07
DB402607.eps
standard or VDE
standard or VDE
CCM IP43 IK07
CNOMO IP54 IK07
Ø5...8
DB403582.eps
For Compact NSX DC, installation of a rotary handle or a motor mechanism does
not alter the reliability of the position-indication system.
A-9
Number of poles
Electrical characteristics as per IEC 60947-1/ 60947-2 and EN 60947-1 / 60947-2
Rated current at 40 °C In (A)
Rated insulation voltage Ui (V)
Rated impulse withstand voltage Uimp (kV peak)
Rated operational voltage Ue (V DC)
Type of circuit breaker
Ultimate breaking capacity Icu (kA rms) V DC 48-125 V (1P) (1)
(L/R = 5 ms and L/R = 15 ms) 250 V (1P) (1)
500 V (2P) (1)
750 V (3P) (1)
Service breaking capacity Ics % Icu
PB108202.eps
Electrical 250 V In
250 V In/2
500 V In
500 V In/2
750 V In
750 V In/2
Indication and control auxiliaries
Auxiliary contacts
Voltage release MX shunt release
MN undervoltage release
Installation and connections
Fixed Front connection
Rear connection
PB105035_31r.eps
A-10
b b b b b b - b b b b b b - - b b
- - - - - - b - - - - - - b b - -
b b b b b b b b b b b b b b - - -
b b b b b b b b b b b b b b b b b
10000 5000
5000 1000
10000 2000
5000 1000
10000 2000
5000 1000
10000 2000
b
b
b
b
b
- - - - - - b - - - - - - b b b b
- - - - - - b - - - - - - b b b b
- - - - - - b - - - - - - b b b b
- - - - - - b - - - - - - b b b b
b
b
b
161 x 35 x 86 - - 161 x 35 x 86 - - -
- 161 x 70 x 86 - - 161 x 70 x 86 - -
- - 161 x 105 x 86 - - 161 x 105 x 86 255 x 140 x 110
- - 161 x 140 x 86 - - 161 x 140 x 86 225 x 185 x 110
0.7 - - 0.7 - - -
- 1.2 - - 1.2 - -
- - 1.6 to 1.9 - - 1.6 to 1.9 6.0
- - 2.1 to 2.3 - - 2.1 to 2.3 7.8
A-11
Depending on the version, Compact NSX DC circuit breakers are equipped with:
pb107518_13_r.eps
260 260 400 400 700 700 700 800 1000 1200 1250
Depending on the version, Compact NSX DC circuit breakers are equipped with:
b 3P/4P:
v up to 250 A, TM-D, TM-DC or TM-G interchangeable thermal-magnetic trip units
v for 400 and 630 A, MP1, MP2, MP3 built-in magnetic trip units.
Trip units for Compact NSX100 DC - NSX160 DC - NSX250 DC
Three-pole 3P-3d and four-pole 4P-4d (interchangeable trip units)
Type of trip unit TM-D TM-DC
Rating (A) In (A) at 40 °C 16 25 32 40 50 63 80 100 125 160 200 250
Compact NSX100 DC b b b b b b b b - - - -
circuit NSX160 DC b b b b b b b b b b - -
breaker b b b b b b
NSX250 DC - - - - - -
Overload protection (thermal)
Tripping Ir (at 40 °C) Adjustable
PB107547_32.eps
DB416264.eps
DC DC
1 overload protection threshold. Up to 250 A for Compact NSX DC, protection is provided by thermal-magnetic trip
2 short-circuit protection pick-up.
units.
For 1 or 2 poles, trip units are built in
b TM-D up to 160 A: fixed thermal threshold and magnetic pick-up
For 3 or 4 poles, trip units are interchangeable
b TM-D up to 63 A: adjustable thermal threshold and fixed magnetic pick-up
b TM-DC from 80 to 250 A: fixed or adjustable (for 200 and 250 A) magnetic pick-up
and adjustable thermal threshold
b TM-G, up to 250 A: adjustable thermal threshold and fixed low magnetic pick-up to
protect long cables.
MP magnetic trip unit for 400 and 630 A
DB402615.eps
Above 250 A, the protection of Compact NSX400 DC and 630 DC circuit breaker is
ensured by built-in magnetic trip unit, offering one of three protection levels MP1,
MP2 or MP3.
A-13
Insulation accessories
DB416262.eps
Interphase barriers
Sealable terminal
shields
Indication contact
A-14
One-piece spreader
Cable connectors
Rear connectors
Cable connectors
Communication
(1) (1)
Terminal
extensions
BSCM module
NSX cord
(1)
Modbus interface
Motor mechanism
A-15
Insulation accessories
DB414015.eps
Interphase barriers
Heat sink
A-16
Lugs
Rear connectors
Adapter
Cable connectors
Circuit breaker
Terminal extensions
Plug-in base
Power connection
accessories
Power connections
A-17
DB112200.eps
DB112201.eps
DB112202.eps
For the last two, components must be added (base,
chassis) to the fixed version.
Many connection components are shared by the three
versions.
(with adapter).
DB112203.eps
DB112204.eps
L3
L2
L1
8 Nm
L2
8 Nm
L3
8 Nm
DB112208.eps
L3
L2
L1
DB112205.eps
DB112207.eps
A-18
sides plates mounted on the circuit breaker. Similar to the plug-in version, a safety
trip causes automatic tripping if the device is ON, before engaging or withdrawing it,
and enables device operation in the disconnected position.
Accessories
Accessories are the same as for the base, with in addition:
bb auxiliary contacts for installation on the fixed part, indicating the “connected” and
“disconnected” positions
bb locking by 1 to 3 padlocks (shackle diameter 5 to 8 mm), to:
vv prevent insertion for connection
vv lock the circuit breaker in connected or disconnected position
bb toggle collar for circuit breakers with a toggle mounted through a front panel,
intended to maintain the degree of protection whatever the position of the circuit
breaker (supplied with a toggle extension)
bb telescopic shaft for extended rotary handles. The door can then be closed with the
Withdrawable Compact NSX250 DC. device in the connected and disconnected positions.
DB112209.eps
DB111369.eps
DB112219.eps
Installation positions.
Protection collar for toggle and toggle Telescopic shaft.
extension to provide IP4 in the connected and
DB112210.eps
disconnected positions.
DB112221.eps
DB112312.eps
A-19
Fixed circuit breakers are designed for standard front Front connection
connection using bars or cables with lugs.
Cable connectors are available for bare cables. Rear Bars or cables with lugs
connection is also possible. Standard terminals
Compact NSX100 to 630 DC come with terminals comprising snap-in nuts with
screws:
bb Compact NSX100/160/250 DC: M8 nuts and screws
bb Compact NSX400/630 DC: M10 nuts and screws.
These terminals may be used for:
DB112169.eps
DB112168.eps
mandatory.
Maximum size of bars
Compact NSX DC circuit breaker 100 to 250 400 to 630
Without spreaders pitch (mm) 35 45
maximum bar size (mm) 20 x 2 32 x 6
With spreaders pitch (mm) 45 52.5
Small lug for copper cables. maximum bar size (mm) 32 x 2 40 x 6
Crimp lugs
DB112171.eps
DB112173.eps
DB112174.eps
DB112176.eps
DB112177.eps
Connection of large cables may require an increase in the distance between the
device terminals.
The one-piece spreader is the means to:
bb increase the 35 mm pitch of the NSX100 to 250 DC circuit breaker terminals to the
45 mm pitch of a NSX400/630 DC device
bb use all the connection and insulation accessories available for the next largest
frame size (lugs, connectors, spreaders, right-angle and edgewise terminal
extensions, terminal shields and interphase barriers).
DB112179.eps
DB112180.eps
A-20
DB112314.eps
Bare cables
For bare cables (without lugs), the prefabricated bare-cable connectors may be used
for both copper and aluminium cables.
Cable connectors for Compact NSX100 to 250 DC
The connectors snap directly on to the device terminals or are secured by clips to
right-angle and straight terminal extensions as well as spreaders.
Bare cable.
Cable connectors for Compact NSX400 to 630 DC
The connectors are screwed directly to the device terminals.
Cable connectors for Compact NSX100 to 250 and 400/630 DC
The connectors are screwed to device terminals or right-angle terminal extensions.
Distribution connectors for Compact NSX100 to 250 DC
These connectors are screwed directly to device terminals. Interphase barriers are
supplied with distribution connectors, but may be replaced by long terminal shields.
Each connector can receive six cables with cross-sectional areas ranging from 1.5 to
35 mm² each.
DB112316.eps
DB112317.eps
DB111326.eps
Rear connection
DB111327.eps
DB111330.eps
For the connection of bare cables, the 1-cable connectors for Compact NSX100
to 250 DC may be secured to the rear connections using clips.
DB104730.eps
A-21
Auxiliary circuits exit the device through a knock-out in the front cover.
Plug-in/withdrawable
Compact NSX DC.
DB403557.eps
DB403556.eps
Connector 1
Connector 1
Connector 2
Connector 2
Connector 3
DB111376.EPS
Compact
NSX100/160/250 DC.
A-22
DB403583.eps
Connector 2
DB115611.eps
A-23
MN undervoltage release
This release trips the circuit breaker when the control voltage drops below a tripping
threshold:
b tripping threshold between 0.35 and 0.7 times the rated voltage
b circuit breaker closing is possible if the voltage exceeds 0.85 times the rated
voltage. For a lower value, circuit breaker closing cannot be guaranteed.
Circuit breaker tripping by an MN release meets the requirements of standard
IEC 60947-2.
MX shunt release
Trips the circuit breaker when the control voltage rises above 0.7 x Un.
Control signals can be of the impulse type (u 20 ms) or maintained.
Operation
When the circuit breaker has been tripped by an MN or MX release, it must be reset
locally.
MN or MX tripping takes priority over manual closing.
In the presence of a standing trip order, closing of the contacts, even temporary,
is not possible.
Mechanical characteristics
b Endurance is equal to 50 % of the mechanical endurance of the circuit breaker.
b The releases clip in behind the front cover.
b Connection using wires up to 1.5 mm2, to integrated terminal blocks.
Electrical characteristics
b Consumption:
v pick-up (MX): < 30 VA
v seal-in (MN and MNR): < 5 VA.
b Response time: < 50 ms.
DB403012.eps
Motor mechanism /
rotary handle / toggle handle
SD SDE
OF1 OF2 OF2
SD SDE OF1
MN /
MX MN /
MX
A-24
TMD, TMG
Communication of status indications (1)
Rotary handle / Communicating
DB403584.eps
DB403585.eps
toggle handle motor mechanism
BSCM BSCM
NSX cord
or
NSX cord
A-25
DB403586.eps
OF1,
OF2, SD
OF1 SD OF3
SDE
OF2
OF3 SDE
MN / MN /
MX MX
A-26
One contact model provides circuit breaker status These common-point changeover contacts provide remote circuit breaker status
indications (OF - SD - SDE). information.
An early-make or early-break contact, in conjunction They can be used for indications, electrical locking, relaying, etc.
with a rotary handle, can be used to anticipate device They comply with the IEC 60947-5 international recommendation.
opening or closing.
A CE / CD contact indicates that the chassis is Functions
connected / disconnected. Breaker-status indications, during normal operation or after a fault
A single type of contact provides all the different indication functions:
bb OF (ON/OFF) indicates the position of the circuit breaker contacts
bb SD (trip indication) indicates that the circuit breaker has tripped due to:
vv an overload
vv a short-circuit
DB125549.eps
rotary handle.
They are used in particular for advanced opening of safety trip devices (early break)
or to energise a control device prior to circuit breaker closing (early make).
Chassis-position contacts
bb CE/CD (connected/disconnected) contacts are microswitch-type carriage
switches for withdrawable circuit breakers.
CE/CD carriage switches.
Installation
bb OF, SD, SDE functions: a single type of contact provides all these different
indication functions, depending on where it is inserted in the device. The contacts
clip into slots behind the front cover of the circuit breaker.
The SDE function on a Compact NSX100 - 250 DC equipped with a thermal-
magnetic trip unit requires the SDE actuator.
bb CAM function: the contact fits into the rotary-handle unit (direct or extended).
bb CE/CD function: the contacts clip into the fixed part of the chassis.
A-27
Device locking
The rotary handle facilitates circuit breaker locking.
bb Padlocking:
vv standard situation, in the OFF position, using 1 to 3 padlocks, shackle diameter 5
to 8 mm, not supplied
vv with a simple modification, in the ON and OFF positions. Locking in the ON
position does not prevent free circuit breaker tripping if a fault occurs. In this case,
the handle remains the ON position after the circuit breaker tripping. Unlocking is
required to go to the tripped then the OFF position.
bb Keylock (and padlock)
It is possible to install a Ronis or Profalux keylock (optional) on the base of the
handle to obtain the same functions as with a padlock.
Early-make or early-break contacts (optional)
Compact NSX DC with a rotary handle. Early-make and/or early-break contacts may be used with the rotary handle. It is thus
possible to:
PB103607-50.eps
A-28
reversible.
When a number of extended rotary handles are installed on a door, this disabling
function is the means to ensure door locking by a single device.
Device and door padlocking
Padlocking locks the circuit breaker handle and disables door opening:
bb standard situation, in the OFF position, using 1 to 3 padlocks, shackle diameter 5
to 8 mm, not supplied
bb with a simple modification, in the ON and OFF positions. Locking in the ON
position does not prevent free circuit breaker tripping if a fault occurs.
In this case, the handle remains in the ON position after the circuit breaker tripping.
Unlocking is required to go to the tripped then the OFF position.
If the door controls were modified to voluntarily disable door locking, padlocking
does not lock the door, but does disable handle operation of the device.
Device locking using a keylock inside the switchboard
It is possible to install a Ronis or Profalux keylock (optional) on the base of the rotary
handle to lock the device in the OFF position or in either the ON or OFF positions.
Accessory for device operation with the door open
When the device is equipped with an extended rotary handle, a control accessory
mounted on the shaft makes it possible to operate the device with the door open.
bb The device can be padlocked in the OFF position.
bb The accessory complies with UL508.
Early-make or early-break contacts (optional)
The extended rotary handle offers the same possibilities with early-make and/or
early-break contacts as the standard rotary handle.
Parts of the extended rotary handles
bb A unit that replaces the front cover of the circuit breaker (secured by screws).
bb An assembly (handle and front plate) on the door that is always secured in the
same position, whether the circuit breaker is installed vertically or horizontally.
bb An extension shaft that must be adjusted to the distance. The min/max distance
between the back of circuit breaker and door is:
vv 185…600 mm for Compact NSX100 to 250 DC
vv 209…600 mm for Compact NSX400/630 DC.
For withdrawable devices, the extended rotary handle is also available with a
telescopic shaft to compensate for device disconnection. In this case, the min/max
distances are:
vv 248…600 mm for Compact NSX100 to 250 DC
vv 272...600 mm for Compact NSX400/630 DC.
A-29
breakers feature very high mechanical endurance as well as easy and sure
operation:
bb all circuit breaker indications and information remain visible and accessible,
including trip-unit settings and indications
bb suitability for isolation is maintained and padlocking remains possible
bb double insulation of the front face.
A specific motor mechanism is required for operation via the communication
function (1). This communicating motor mechanism must be connected to the
BSCM module to receive the opening and closing orders. Operation is identical to
that of a standard motor mechanism.
Compact NSX250 DC with motor mechanism.
Applications
bb Local motor-driven operation, centralised operation, automatic distribution control.
bb Normal/standby source changeover or switching to a replacement source to
ensure availability or optimise energy costs.
bb Load shedding and reconnection.
bb Synchrocoupling.
Operation
The type of operation is selected using the manual/auto mode selection switch (7).
A transparent, lead-seal cover controls access to the switch.
Automatic
When the switch is in the "auto" position, the ON/OFF (I/O) buttons and the charging
lever on the mechanism are locked.
bb Circuit breaker ON and OFF controlled by two impulse-type or maintained signals.
1 2 3
DB416307.eps
8 7 6 5 Optional accessories
bb Keylock for locking in OFF position.
1 Position indicator bb Operations counter for the Compact NSX400/630 DC, indicating the number
(positive contact indication) of ON/OFF cycles. Must be installed on the front of the motor mechanism module.
2 Spring status indicator (charged, discharged)
3 Manual spring-charging lever Characteristics
4 Keylock device (optional)
Locking device (OFF position), using 1 to 3 padlocks, Motor mechanism MT100 to MT630
shackle diameter 5 to 8 mm, not supplied Response time (ms) opening < 600
5 I (ON) pushbutton closing < 80
6 O (OFF) pushbutton Operating frequency cycles/minute max. 4
7 Manual/auto mode selection switch. The position of this Control voltage (V) DC 24/30 - 48/60 - 110/130 - 250
switch can be indicated remotely. AC 50/60 Hz 48 (50 Hz) - 110/130 -
8 Operation counter (Compact NSX400/630 DC). 220/240 - 380/440
Consumption (1) DC (W) opening y 500
closing y 500
AC (VA) opening y 500
closing y 500
(1) For NSX100 to 250 DC, the inrush current is 2 In for 10 ms.
Electrical endurance
Circuit breaker + motor
DB403870.eps
50 mechanism module, in
40 thousands of operations
30 NSX100 DC (IEC 60947 2), at 440 V.
20 NSX160 DC
15
10 NSX250 DC
6 NSX400 DC
4 NSX630 DC
A-30
MX or MN voltage releases are used to trip the circuit breaker. They serve primarily
044313_20_SE.eps
MN undervoltage release
The MN release opens the circuit breaker when its supply voltage drops to a value
below 35 % of its rated voltage Un.
Undervoltage tripping, combined with an emergency-off button, provides fail-safe
MX or MN voltage release. tripping. The MN release is continuously supplied, i.e. if supply is interrupted:
bb either voluntarily, by the emergency-off button,
Failsafe opening Possible opening bb or accidentally, through loss of power or faulty wiring,
DB115605.eps
Delayed A time delay unit for the MN release eliminates the risk of nuisance tripping due to a
trip order transient voltage dip lasting y 200 ms. For shorter micro-outages, a system of
capacitors provides temporary supply to the MN at U > 0.7 to ensure non tripping.
DB115631.eps
D1 MX shunt release
The MX release opens the circuit breaker via an impulse-type (u 20 ms) or
MN release with a time-delay Wiring diagram for maintained order.
unit. emergency-off function with Opening conditions
MN + time-delay unit. When the MX release is supplied, it automatically opens the circuit breaker. Opening
is ensured for a voltage U u 0.7 x Un.
Possible opening Failsafe opening Characteristics
DB115608.eps
A-31
DB111365.eps
systems can receive up to three padlocks with shackle diameters ranging from 5 to
8 mm (padlocks not supplied). Certain locking systems require an additional
accessory.
DB111359.eps
DB111360.eps
Ø5...8
u auto u auto
man man
DB111361.eps
A-32
Outgoing-circuit identification
DB115224.eps
Compact NSX100 to 630 DC can be equipped with label holders supplied in sets of
ten (cat. no. LV429226).
They are compatible with escutcheons.
A bag contains:
bb 6 sealing accessories
bb 6 lead seals
bb 0.5 m of wire
bb 2 screws.
Sealing accessories.
DB112301.eps
DB112303.eps
Toggle control
DB112302.eps
DB112306.eps
DB403120.eps
Rotary handle
DB112304.eps
DB112305.eps
DB112307.eps
Motor mechanism
DB125896.eps
Ø5...8
Ø5...8
u auto
man
u auto
man
auto
Ø5...8
uto
Types of seals Front-cover fixing screw Trip-unit transparent Motor mechanism Terminal-shield fixing
cover transparent cover screw
Protected operations bb front removal bb access to manual/auto bb access to power
bb access to auxiliaries bb modification of settings mode selection switch: connections (protection
bb trip-unit removal. bb access to test connector. depending on its position, against direct contact).
manual (1) or automatic
operation is not possible.
(1) In this case, local
operation is not possible.
A-33
IP40
PB104942.eps
The four types, with a gasket, are screwed to the door cut-out:
bb three escutcheons identical to the previous, but IP40
bb a wide model for Vigi and ammeter modules that can be combined with the above.
DB112290.eps
DB402617.eps
IP30 escutcheon.
PB104938.eps
Escutcheon for toggle without and with access to the trip unit.
A-34
DB112294.eps
DB112295.eps
DB112296.eps
Ø5...8
Ø5
Ø5...8
...8
Toggle cover.
PB103820_35.eps
Toggle cover.
A-35
Number of poles
Electrical characteristics as per IEC 60947-2 and EN 60947-2
Rated current (A) In 40 °C heatsink standard-IP4X
(free air + no venting)
Altitude m 2000
Rated insulation voltage (V) Ui
Rated impulse withstand Uimp
voltage (kV)
Rated operational voltage (V) Ue DC
Type of circuit breaker
Ultimate breaking capacity Icu (kA rms) DC 1000 V (4P series)
Compact NSX200 TM DC PV. (L/R 2 ms)
Service breaking capacity Ics % Icu
PB110846.eps
A-36
b b b b b b b b
1000 1000 1000 1000 1000 1000 1000 1000
8 8 8 8 8 8 8 8
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
- - - - - - - -
- - - - - - - -
- - - - - - - -
- - - - - - - -
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b - - - -
140 x 161 x 86 140 x 161 x 86 140 x 161 x 86 140 x 161 x 86 225 x 185 x 110 225 x 185 x 110 225 x 185 x 110 225 x 185 x 110
2.8 2.8 2.8 2.8 8.1 8.1 8.1 8.1
A-37
Number of poles
Electrical characteristics as per IEC 60947-3
Rated current (A) In 40 °C
(free air + no venting)
Altitude m 2000
Rated insulation voltage (V) Ui
Rated impulse withstand Uimp
voltage (kV)
Rated operational voltage (V) Ue DC
Type of circuit breaker
Rated short circuit withstand Icw/Icm t=1s
current (kA rms),
Rated conditionnal short-circuit Iq kA
current with back-up fuse A gPV
Compact NSX200 NA DC PV. Rated conditionnal short-circuit Iq with circuit breaker kA with MCCB
current
Utilization category
PB110847.eps
A-38
10 10 10 10 10
100 160 200 400 500
10 10 10 - -
NSX125 TM DC PV NSX160-200 TM DC PV NSX200 TM DC PV
DC22-A DC22-A DC22-A DC22-A DC22-A
b b b b b
3 3 3 3 3
b b b b b
b b b b b
b b b b b
b b b b b
b b b b b
- - - - -
- - - - -
- - - - -
- - - - -
b b b b b
b b b b b
b b b b b
b b b b b
b b b b b
b b b b b
b b b b b
b b b - -
140 x 161 x 86 140 x 161 x 86 140 x 161 x 86 185 x 255 x 110 185 x 255 x 110
2.8 2.8 2.8 8.1 8.1
A-39
Number of poles
Electrical characteristics as per IEC 60947-3
Rated current (A) In 40 °C
(free air + no venting)
Altitude m 2000
Rated insulation voltage (V) Ui
Rated impulse withstand Uimp
voltage (kV)
Rated operational voltage (V) Ue DC
Type of circuit breaker
Compact NSX1600 NA DC PV. Rated short circuit withstand Icw/Icm t=1s
current (kA rms)
Rated conditionnal short-circuit Iq kA
current with back-up fuse A gPV
Rated conditionnal short-circuit Iq with circuit breaker
current
Utilization category
Suitability for isolation
Pollution degree
Durability
Endurance (C-O cycles) mechanical
electrical (In) 1000 V
rear connection
A-40
20 20 20 20 20
10 10 10 10 10
N/A N/A N/A N/A N/A
10 10 10 10 10
b b b b b
b b b b b
b b b b b
b b b b b
b b b b b
b b b b b
b b b b b
b b b b b
b b b b b
280 x 327 x 182 280 x 327 x 182 280 x 327x 182 280 x 327 x 182 280 x 327 x 182
18 18 18 18 18
A-41
Terminal shields
Communication
(1)
(1)
Modbus interface
Cable connectors
Terminal
Terminal shields Rear connectors
extensions
A-42
Terminal shields
(1)
Heatsink
I I
n m
Modbus interface
A-43
Phase
barriers
Sealable terminal
shield
Heatsink
Auxiliary contact
Escutcheon
I ON
OOFF
pus h
pus h
Voltage release
ed
harg
disc
O OFF
53
012
Phase barriers
Phase
barriers
Sealable terminal
shield
A-44
Ambient temperature
DB402051.eps
Masterpact devices have successfully passed the tests defined by the following
standards for extreme atmospheric conditions:
bb IEC 60068-2-1: dry cold at -40 °C
bb IEC 60068-2-2: dry heat at +85 °C
bb IEC 60068-2-30: damp heat (temperature +55 °C, relative humidity 95 %)
bb IEC 60068-2-52 level 2: salt mist.
Masterpact devices can operate in the industrial environments defined by standard
IEC 60947 (pollution degree up to 4).
It is nonetheless advised to check that the devices are installed in suitably cooled
switchboards without excessive dust.
Vibrations
DB128163.eps
A-46
Altitude
DB128162.eps
(m)
2000 At altitudes higher than 2000 metres, the modifications in the ambient air (electrical
resistance, cooling capacity) lower the following characteristics as follows:
Altitude (m) 2000 3000 4000 5000
NW DC
Impulse withstand voltage Uimp (kV) 12 10.6 9.5 8.4
Rated insulation voltage (Ui) 1000 900 800 700
Maximum rated operationnal NW DC y500 V 500 450 390 350
voltage 50/60 Hz Ue (V) NW DC 500-900 V 900 800 700 630
Rated current (A) at 40 °C 1 x In 0.98 x In 0.96 x In 0.94 x In
NW DC PV
Impulse withstand voltage Uimp (kV) 12 10.6 9.5 8.4
Rated insulation voltage (Ui) 1000 1000 950 850
Maximum rated operationnal DC voltage 1000 1000 950 850
Rated current (A) at 40 °C 1 x In 0.98 x In 0.96 x In 0.94 x In
Intermediate values may be obtained by interpolation.
Electromagnetic disturbances
DB128164.eps
Degree of protection
Masterpact NW DC circuit breakers offer the following protection characteristics
depending on the installation conditions:
b IP: degree of protection (standard IEC 60529)
b IK: protection against external mechanical impacts (standard EN 50102).
Masterpact NW DC
Circuit breaker installed in a switchboard
Bare circuit breaker IP30
DB104534.eps
A-47
A-48
b b b b b b
- - - - - -
b b b b b b
20000
10000
8500 5000 2000
- 2000 - 2000 - 1000
b b b b b b
b b b b b b
b b b b b b
HA HA HA
- 85 - 85 - 85
- 85 - 85 - 85
b b b b - -
b b b b b b
b b b b - -
b b b b b b
A-49
All Masterpact NW DC devices Protection using the Micrologic 1.0 DC control unit
are equipped with a Micrologic 1.0 DC control unit.
Masterpact NW DC circuit breakers use Micrologic 1.0 DC control units. These
interchangeable units with instantaneous thresholds, operating with electromagnetic
sensors, can be adjusted on site.
The circuit breakers can be used with the three versions of sensors,
defined by their setting range.
PB101139-32R.eps
Adjustments
Settings for Masterpact NW DC circuit breakers may be accessed from the front,
with the switchboard door open.
b Settings are made for the input (+ pole) and the output (- pole).
b The setting range comprises eleven positions, plus five preferential settings
marked A, B, C, D and E.
b The setting values for the two corresponding sensors must be identical.
DB403050.eps
DB402618.eps
A-50
Minimum Maximum
Sensor versions Settings Settings Settings Settings Settings
A1 and A2 B1 and B2 C1 and C2 D1 and D2 E1 and E2
1250/2500 1250 A 1500 A 1600 A 2000 A 2500 A
2500/5400 2500 A 3300 A 4000 A 5000 A 5400 A
5000/11000 5000 A 8000 A 10000 A 11000 A 11000 A
DB403114.eps
Intermediate settings
It is possible to set eleven other (unmarked) intermediate values.
DB403115.eps
A-51
Masterpact under 1000 V DC with all the 3 poles in series and this is a mandatory condition whatever the type of fault. This comes to say that
NW40 HADCD-PV the PV systems using these switch-disconnectors must be isolated systems from the earth and that the double fault situation (A
Ui 1000V Uimp 12kV and D or C and E on the diagram below) must be absolutely avoided : insulation monitoring devices shall detect the first fault and
Ue 1000 V c 3P in series the staff shall look for this first fault and clear it with no delay. These switch-disconnectors cannot be used in grounded systems as
Icw 85kA/1s in this situation they may be expected to break the current under the full voltage (1000 V DC) with only 1 pole or 2 poles in series.
Icm 85kA These devices are not designed for that purpose and could sustain irremediable damage if used to break in these conditions.
DB116984.eps
IEC 60947-3
A-52
DB402268_55.eps
Safety clearances Insulated Metal parts Energised
parts parts
DB416461.eps
DB416462.eps
A 0 0 100
B 0 0 60
F : Datum.
A(*) An overhead clearance of 110 mm is required to remove the arc chutes.
An overhead clearance of 20 mm is required to remove the terminal block.
DB402311_55.eps
DB416464.eps
A 0 0 0
B 0 0 60
F : Datum.
A-53
The COM option is required for integration of the circuit For fixed devices, the COM option is made up of:
breraker or switch disconnector in a supervision bb a Modbus BCM ULP “device” communication module, installed behind the
system. Micrologic control unit and supplied with its set of sensors (OF, SDE ,PF and CH
Masterpact uses the Modbus communications protocol micro switches) its kit for connection to XF and MX1 communicating voltage releases
for full compatibility with the ION enterprise. An external and its COM terminal block (inputs E1 to E6).
gateway is available for communication on other For drawout devices, the COM option is made up of:
networks: bb a Modbus BCM ULP “device” communication module, installed behind the
b Profibus Micrologic control unit and supplied with its set of sensors (OF, SDE, PF and CH
b Ethernet. micro switches) its kit for connection to XF and MX1 communicating voltage releases
and its COM terminal block (inputs E1 to E6).
bb a “chassis” communication module supplied separately with its set of sensors (CE,
CD and CT contacts) Modbus CCM.
Status indication by the COM option is independent of the device indication contacts.
These contacts remain available for conventional uses.
Modbus BCM ULP “Device” communication module
This module is independent of the control unit. It receives and transmits information
on the communication network. An infra-red link transmits data between the control
unit and the communication module.
Consumption: 30 mA, 24 V.
PB106674-20.eps
CCM
A-54
Communication functions
Switch-disconnector
and circuit breaker
with communication
Modbus
Device identification
Address b
Rating -
Type of device -
Type of control unit -
Status indications
ON/OFF (OF) b
Spring charged (CH) b
Ready to close (PF) see page D-10
Fault-trip (SDE) b
Connected/disconnected/test position (CE/CD/CT) b
Controls
ON/OFF (MX/XF) b
Spring charging -
Reset of the mechanical indicator -
Communication Modbus
The Modbus RS 485 (RTU protocol) system is an open bus on which communicating
Modbus devices (Compact NSX DC with Modbus COM, Power Meter PM700,
PM800, Sepam, Vigilohm, etc.) are installed. All types of PLCs and microcomputers
may be connected to the bus.
Addresses
The Modbus communication parameters (address, baud rate, parity) are entered
using the RSU (Remote Setting Utility) Micrologic utility.
Modbus addresses
@xx Circuit breaker manager (1 to 47)
@xx + 50 Chassis manager (51 to 97)
The manager addresses are automatically derived from the circuit breaker address
@xx entered via the Micrologic control unit (the default address is 47).
Number of devices
The maximum number of devices that may be connected to the Modbus bus
depends on the type of device (Compact with Modbus COM, PM700, PM800,
Sepam, Vigilohm, Compact NSX DC, etc.), the baud rate (19200 is recommended),
the volume of data exchanged and the desired response time. The RS 485 physical
layer offers up to 32 connection points on the bus (1 master, 31 slaves).
A fixed device requires only one connection point (communication module on the
device). A drawout device uses two connection points (communication modules on
the device and on the chassis).
The number must never exceed 31 fixed devices or 15 drawout devices.
Length of bus
The maximum recommended length for the Modbus bus is 1200 meters.
Bus power source
A 24 V DC power supply is required (less than 20 % ripple, insulation class II).
A-55
Automatic
DB404305.eps
Firewall notification
Nomad
Internet
mode
Site Intranet
Ethernet (TCP/IP/Modbus)
Consultation Consultation
EGX300 RCU RCU
Modbus
CCM FDM121
FDM121
Ethernet (TCP/IP/Modbus)
Modbus
ULP
A-56
RCU
Gateway
The gateway has two functions:
bb access to the company intranet (Ethernet) by converting Modbus frames to the
TCP/IP/Modbus protocol
bb optional web-page server for the information from the devices.
Examples include EGX100 and EGX300.
PE86181r-251.eps
EGX 300.
A-57
PB108204.eps
A-58
Types of software
Masterpact and Compact NSX DC communication functions are designed
to interface with software dedicated to electrical installations:
bb switchboard supervision
bb electrical installation supervision
bb process control
bb SCADA (Supervisory Control & Data Acquisition), EMS (Enterprise Management
System) or BMS (Building Management System) type software.
Other software
Masterpact, Compact NSX DC devices can forward their operating information to
special software integrating the electrical installation and other technical facilities:
bb SCADA process control software: Vijeo CITECT
bb BMS Building Management System software: Vista.
ION-E.
A-59
PB104736.eps
exist in circuit-breaker (equipped with Micrologic DC
1.0 control unit) and switch-disconnector versions. All
auxiliaries are common from 1000 to 4000 A.
1 OFF pushbutton.
2 ON pushbutton.
3 Closing mechanism charging handle.
4 Operation counter.
5 Operating mechanism charged and “ready to close”
indication:
b spring charged
DB104522.eps
b spring discharged.
b OFF.
Connections
b Rear vertical connection in standard.
b Possibility of conversion to horizontal connection by turning the connectors
on the site by the customer (except for the NW40).
b Prefabricated series connections.
b Safety shutters, shutter locking blocks.
b Optional accessories:
v interphase barriers
v shutter position indication and locking.
A-60
PB104367A32.eps
PB104366A32.eps
PB100780-32R_SE.eps
b Pushbutton locking by padlockable transparent
cover.
b OFF-position locking by padlock or keylock.
b Chassis locking:
v in disconnected position by keylock
v in connected, disconnected and test positions.
b Door interlock (inhibits door opening with breaker in
connected position).
b Racking interlock (inhibits racking with door open).
b Racking interlock between crank and OFF
pushbutton.
b Automatic spring discharge before breaker removal.
b Mismatch protection. Locking in disconnected position by keylock or padlock. Door interlock (inhibits door
opening with breaker in
connected position).
Indication contacts
PB100806-19R.eps
PB100807-12R.eps
PB100820-19R.eps
PB100816-19R.eps
b Standard or low-level contacts:
v ON/OFF indication (OF)
v “fault-trip” indication (SDE)
v carriage switches for connected (CE), disconnected
(CD) and test (CT) positions.
Remote operation
PB104349A55.eps
PB100808-22R.eps
PB100809-11R.eps
PB100818-11R.eps
b Remote ON/OFF:
v gear motor
v XF closing or MX opening voltage releases
v PF ready-to-close contact
v options:
- RAR automatic or Res electrical remote reset
- BPFE electrical closing pushbutton.
b Remote tripping function:
v MN voltage release:
- standard
- adjustable or non-adjustable delay
v or 2nd MX voltage release.
Accessories
DB104524.eps
b Escutcheon.
b Transparent cover for escutcheon.
PB104382-27R.eps
A-61
Two types of connection are available: vertical Rear connection fixed device
connection is standard however the connectors can be
Masterpact NW DC
rotated for on-site conversion to horizontal connection
(except for NW40). Vertical rear connection
PB105026.eps
A-62
DB402303_59.eps
DB402323_59.eps
A-63
DB125380.eps
reset button.
2 OFF position locking.
3 Electrical closing
pushbutton.
4 ON pushbutton.
5 OFF pushbuton.
6 Operating mechanism
charged and “ready to
close” indication.
7 Pushbutton locking.
8 Main contact position
indication.
9 Operation counter.
The transparent cover blocks access to the pushbuttons used to open and close the
device.
It is possible to independently lock the opening button and the closing button.
The locking device is often combined with a remote operating mechanism.
The pushbuttons may be locked using either:
b three padlocks (not supplied)
b lead seal
Access to pushbuttons protected by transparent cover. b two screws.
Accessory-compatibility
3 padlocks and/or 2 keylocks.
A-64
DB125388.eps
2 “Connected/test/
disconnected” position
indication.
3 Racking interlock.
4 Racking-handle storage.
5 Reset pushbutton.
6 Padlock locking.
7 Keylock locking.
8 Chassis front plate
(accessible with cubicle
door closed).
9 “Disconnected” position
door interlock.
10 Mismatch protection.
A-65
is reached.
OF
Supplied as standard 4
Maximum number 12
Breaking capacity (A) Standard minimum load: 100 mA/24 V
p.f.: 0.3 V AC 240/380 10/6 (1)
AC12/DC12 480 10/6 (1)
690 6
V DC 24/48 10/6 (1)
125 10/6 (1)
250 3
Low-level minimum load: 2 mA/15 V
V AC 24/48 6
240 6
380 3
V DC 24/48 6
125 6
250 3
(1) Standard contacts: 10 A; optional contacts: 6 A.
690 3
V DC 24/48 3
125 0.3
250 0.15
Low-level minimum load: 2 mA/15 V
V AC 24/48 3
240 3
380 3
V DC 24/48 3
125 0.3
250 0.15
A-66
switches
Three series of optional auxiliary contacts are available for the chassis:
b changeover contacts to indicate the “connected” position CE
b changeover contacts to indicate the “disconnected” position CD. This position is
indicated when the required clearance for isolation of the power and auxiliary circuits
is reached.
b changeover contacts to indicate the “test” position CT. In this position, the power
circuits are disconnected and the auxiliary circuits are connected.
Additional actuators
A set of additional actuators may be installed on the chassis to change the functions
of the carriage switches.
CE, CD and CT “connected/disconnected/test” position
carriage switches. Contacts CE CD CT
Maximum number Standard with additional 3 3 3
actuators 9 0 0
6 3 0
6 0 3
3 6 0
Breaking capacity (A) Standard minimum load: 100 mA/24 V
p.f.: 0.3 V AC 240 8
AC12/DC12
380 8
480 8
690 6
V DC 24/48 2.5
125 0.8
250 0.3
Low-level minimum load: 2 mA/15 V
V AC 24/48 5
240 5
380 5
V DC 24/48 2.5
125 0.8
250 0.3
A-67
Two solutions are available for remote operation of Remote operation: remote ON / OFF
Masterpact devices:
The remote ON / OFF function is used to remotely open and close the circuit breaker.
b a point-to-point solution
It is made up of:
b a bus solution with the COM communication option. b an electric motor MCH equipped with a “springs charged” limit switch contact CH
b two voltage releases:
v a closing release XF
v an opening release MX.
Optionally, other functions may be added:
PB104349A-68R.eps
COM
A-68
The electric motor automatically charges and recharges the spring mechanism when
the circuit breaker is closed. Instantaneous reclosing of the breaker is thus possible
following opening. The spring-mechanism charging handle is used only as a backup
if auxiliary power is absent.
The electric motor (MCH) is equipped as standard with a limit switch contact (CH)
that signals the “charged” position of the mechanism (springs charged).
Characteristics
Power supply V AC 50/60 Hz 48/60 - 100/130 - 200/240 - 277 - 380/415 - 400/440 - 480
V DC 24/30 - 48/60 - 100/125 - 200/250
Operating threshold 0.85 to 1.1 Un
Consumption (VA or W) 180
Motor overcurrent 2 to 3 In for 0.1 s
Charging time maximum 4 seconds
Operating frequency maximum 3 cycles per minute
CH contact 10 A at 240 V
Opening release MX
The MX release instantaneously opens the circuit breaker when energised. It locks
the circuit breaker in OFF position if the order is maintained (except for MX
“communicating” releases).
Note: whether the operating order is maintained or automatically disconnected (pulse-type), XF
or MX “communicating” releases (“bus” solution with “COM” communication option) always have
an impulse-type action.
Characteristics XF MX
Power supply V AC 50/60 Hz 24 - 48 - 100/130 - 200/250 - 277 - 380/480
V DC 12 - 24/30 - 48/60 - 100/130 - 200/250
Operating threshold 0.85 to 1.1 Un 0.7 to 1.1 Un
Consumption (VA or W) pick-up: 200 (during 200 ms) pick-up: 200 (during 200 ms)
PB100809-16R.eps
Characteristics
Supplied as standard -
Maximum number 1
Breaking capacity Standard minimum load: 100 mA/24 V
p.f.: 0.3 V AC 240/380 5
AC12/DC12
480 5
690 3
V DC 24/48 3
125 0.3
“Ready to close” contacts PF.
250 0.15
Low-level minimum load: 2 mA/15 V
V AC 24/48 3
240 3
380 3
V DC 24/48 3
125 0.3
250 0.15
A-69
DB402622.eps
A-70
DB402625.eps
DB402626.eps
DB402624.eps
When energised, the MX voltage release instantaneously opens the circuit breaker.
A continuous supply of power to the second MX locks the circuit breaker in the OFF
position.
Characteristics
Power supply V AC 50/60 Hz 24 - 48 - 100/130 - 200/250 - 277 - 380/480
V DC 24/30 - 48/60 - 100/130 - 200/250
Operating threshold 0.7 to 1.1 Un
Permanent locking function 0.85 to 1.1 Un
Consumption (VA or W) pick-up: 200 (during 80 ms) hold: 4.5
MX or MN voltage release. Circuit-breaker response time at Un 50 ms ±10
Characteristics
Power supply V AC 50/60 Hz 24 - 48 - 100/130 - 200/250 - 380/480
V DC 12 - 24/30 - 48/60 - 100/130 - 200/250
Operating threshold opening 0.35 to 0.7 Un
closing 0.85 Un
Consumption (VA or W) pick-up: 200 (during 200 ms) hold: 4.5
MN consumption with delay unit pick-up: 200 (during 200 ms) hold: 4.5
Circuit-breaker response time at Un 90 ms ±5
MN delay units
To eliminate circuit-breaker nuisance tripping during short voltage dips, operation of
the MN release can be delayed. This function is achieved by adding an external
delay unit in the MN voltage-release circuit. Two versions are available, adjustable
and non-adjustable.
Characteristics
Power supply non-adjustable 100/130 - 200/250
VAC 50-60 Hz/DC adjustable 48/60 - 100/130 - 200/250 - 380/480
Operating threshold opening 0.35 to 0.7 Un
closing 0.85 Un
Consumption of delay unit alone (VA or W) pick-up: 200 (during 200 ms) hold: 4.5
Circuit-breaker response non-adjustable 0.25 s
time at Un adjustable 0.5 s - 0.9 s - 1.5 s - 3 s
A-71
Optional equipment mounted on the chassis, the shield prevents access to the
terminal block of the electrical auxiliaries.
The operation counter sums the number of operating cycles and is visible on the front
panel. It is compatible with manual and electrical control functions.
Escutcheon CDP
DB101173.eps
Optional equipment mounted on the door of the cubicle, the escutcheon increases
the degree of protection to IP 40 (circuit breaker installed free standing: IP30) .
It is available in fixed and drawout versions.
This option allows the grounding of the breaker mechanism while the front cover is
removed. The grounding is made via the chassis for the drawout version and via the
fixation side plate for the fixed version.
A-72
Presentation 2
Functions and characteristics A-1
Compact NSX DC PV
Safety clearances and minimum distances B-8
Temperature derating B-10
Power dissipation / Resistance B-11
B-1
DB413249.eps
DB413250.eps
Fig. C Fig. D
DB413251.eps
DB413252.eps
Fig. E
DB413253.eps
Possible supports
For fixed or withdrawable circuit breakers
On a plain mounting plate On a slotted mounting plate
DB413249.eps
DB413254.eps
On rails
DB413255.eps
B-2
The circuit breakers can be connected with copper, tinned copper or tinned
aluminum conductors (rigid or flexible bars, cables).
In the event of a short-circuit, electrodynamic forces will be exerted on the
conductors.
They must therefore be correctly sized and maintained in place using supports.
Electrical connection points on all types of devices (contactors, circuit breakers, etc.)
should not be used for mechanical support.
Weights
Type Circuit Plug-in Chassis Motor
breaker base mechanism
NSX100N/H DC 1P/1D 0.5 - - -
2P/2D 1.45 - - -
NSX100 DC 3P/3D 1.79 0.8 2.2 1.2
4P/4D 2.57 1.05 2.2 1.2
NSX160N/H DC 1P/1D 0.5 - - -
2P/2D 1.45 - - -
NSX160N DC 3P/3D 1.85 0.8 2.2 1.2
4P/4D 2.58 1.05 2.2 1.2
NSX250 DC 3P/3D 2.2 0.8 2.2 1.2
4P/4D 2.78 1.05 2.2 1.2
NSX400/630 DC 3P/3D 6.19 2.4 2.2 2.8
4P/4D 8.13 2.8 2.2 2.8
B-3
NSX100/160/250 DC NSX400/630 DC
Bars L (mm) y 25 y 32
DB115656.eps
I (mm) d + 10 d + 15
d (mm) y 10 y 15
Ø
400 e (mm) y6 3 y e y 10
d Ø (mm) 8.5 10.5
I
L Lugs L (mm) y 25 y 32
L
Ø (mm) 8.5 10.5
e Tightening torque (Nm) (1) 15 50
Tightening torque (Nm) (2) 5 20
(1) Tightening torque for lugs or bars on the circuit breaker.
(2) Tightening torque for rear connections or terminal extensions on plug-in base.
DB115660.eps
NSX100 to 250 DC
DB111327.eps
DB112315.eps
(1)
S (mm²) Cu/Al 1.5... 95 10... 16 25... 35 50...185
150 max. flexible
Tightening 12 15 20 26
torque (Nm)
6-cable distribution connector (copper or aluminium)
L (mm) 15 or 30
S (mm²) Cu/Al 1.5... 6 (1) 8... 35
Tightening 4 6
torque (Nm)
(1) For flexible cables from 1.5 to 4 mm2, connection with crimped or self-crimping ferrule.
NSX400 to 630 DC
DB111326.eps
DB112316.eps
B-4
DB402630.eps
DB402628.eps
A1
A2
Minimal distance between the circuit breaker and top, bottom or side panels
DB402629.eps
DB413245.eps
DB413246.eps
D1
D1
NSX100-250 DC U y 250 V 0 30 30 5 35 35 0 10 0
U y 500 V 0 30 30 10 (1) 35 35 0 20 0
U y 750 V 0 30 (4) 30 (4) 20 (1) 35 (4) 35 (4) 0 40 (4) 0
NSX400-630 DC U y 250 V 0 30 30 5 60 60 0 10 0
U y 500 V 0 30 30 10 (1) 60 60 0 20 0
U y 750 V 0 30 (4) 30 (4) 20 (1) 100 (4) 100 (4) 0 40 (4) 0
(1) Distance must be doubled with interphase barriers.
(2) For Compact NSX DC with long or short terminal shields.
(3) For Compact NSX DC without terminal shields.
(4) For voltage > 500 V, terminal shields are mandatory. The length of terminal shields (long or short terminal shields) should be considered.
The mandatory distances when installing Compact NSX DC circuit breakers are calculated from the device case, not taking into account the terminal shields or the
interphase barriers.
B-5
These values are valid for fixed and withdrawable When the ambient temperature is greater than 40 °C, overload-protection
circuit breakers with or without terminal shields. characteristics are slightly modified.
To determine tripping times using time/current curves, use the values of the current
indicated in the table below, corrected to take into account the ambient temperature.
Example: Compact NSX100 DC equipped with a TM80DC trip unit has a rating of:
b 84 A at 40 °C
b 78 A at 55 °C.
B-6
DB413830.eps
DB415722.eps
D1
D3
C1
0.8 min.
DB416421.eps
D1
Fiber
insulating
plate
Fiber
insulating
plate
D2
Dimensions (mm) C1 C2 D1 D2
NSX80 to 200 DC PV 13 13 13 13
NSX250 to 500 DC PV 25.4 25.4 25.4 25.4
Note: the thermal behaviour of switchgear and enclosures warrants careful monitoring. PV generator boxes and array boxes are usually installed outdoors
and exposed to the elements. In the event of high ambient temperatures, high IP levels could reduce air flow and thermal power dissipation.
In addition, the way switchgear devices achieve high voltage operation - i.e. through the use of poles in series - increases their temperature. Special attention
should therefore be paid to the temperature of switchgear inside outdoor enclosures on the DC side.
Schneider Electric recommend to check the installation as per IEC 61439 or any other equivalent standard.
B-8
DB413832.eps
DB413833.eps
DB413834.eps
panel
D1/D2
Compact NSX200 NA DC PV
with short heatsinks and
interphase barriers.
D3 Insulating
C1 screen is
PB110839_69.eps
mandatory (1)
(1) Dimensions of the insulating screen are identical as for the circuit breaker (see page B-8).
Compact NSX200 NA DC PV
with long heatsinks and
interphase barriers.
Note: the thermal behaviour of switchgear and enclosures warrants careful monitoring. PV generator boxes and array boxes are usually installed outdoors
and exposed to the elements. In the event of high ambient temperatures, high IP levels could reduce air flow and thermal power dissipation.
In addition, the way switchgear devices achieve high voltage operation - i.e. through the use of poles in series - increases their temperature. Special attention
should therefore be paid to the temperature of switchgear inside outdoor enclosures on the DC side.
Schneider Electric recommend to check the installation as per IEC 61439 or any other equivalent standard.
B-9
DC PV overcurrent protection
Compact NSX TM DC PV
Maximum current (A): Ith Cooper
For Compact NSX the overload protection is calibrated 20 °C 25 °C 30 °C 35 °C 40 °C 45 °C 50 °C 55 °C 60 °C 65 °C 70 °C
cable
section (1)
at 40 °C and for C60 DC PV at 20 °C. This means that
when the ambient temperature is less or greater than NSX80 TM DC PV
these temperatures, the Ir protection pickup is slightly 88 86 84 82 80 77 75 72 69 66 63 Cu 25 mm2
modified. NSX125 TM DC PV
b Temperature rise for Compact range have been 137.5 135 131 128 125 121 116 112 108 103 98 Cu 50 mm2
checked with terminal shields (mandatory) heatsink on NSX160 TM DC PV
top, four cables on bottom connections with section 176 172 168 164 160 153 147 142 136 130 124 Cu 70 mm2
and length according to IEC60947-1 Table 9. NSX200 TM DC PV
b Values in the tables are provided for vertical 194 189 183 178 172 167 161 155 149 142 136 Cu 95 mm2
mounting only. In case of horizontal mounting consult NSX250 TM DC PV
us. To obtain the tripping time for a given temperature: 302 295 288 280 250 143 235 228 220 210 197 Cu 120 mm2
v see the tripping curves for 20 or 40 °C NSX320 TM DC PV
v determine tripping times corresponding to the Ir 371 362 352 342 320 309 297 286 273 261 248 Cu 185 mm2
value (thermal setting on the device), corrected for the NSX400 TM DC PV
breaker ambient temperature as indicated in the tables 455 444 433 421 400 386 372 358 343 327 311 Cu 240 mm2
below. NSX500 TM DC PV
557 542 526 511 495 478 461 444 426 405 384 Cu 2x150 mm2
(1) Temperature rise have been checked with four cables on bottom connections with section and length according to IEC60947-1 Table 9
a. When used in array boxes, with short connection to string protections the cross section of the bars or cables shall have a higher cross section.
b. When cables have a cross section lower than the value indicated an additional 0.9 derating coefficient shall be applied.
Values in the tables are provided for vertical mounting only.
B-10
Power dissipation / Resistance
B-11
Possible positions
DB402631.eps
DB402632.eps
DB402633.eps
Power supply
The plus and minus polarities (LINE + and LINE -) of the power supply must be
connected as indicated in the “Dimensions and connection” chapter.
DB402634.eps
DB402636.eps
Mounting on rails.
DB402637.eps
B-12
Mounted on the right or left-hand side of the craddle, Door interlock catch VPEC
this device inhibits opening of the cubicle door when
the circuit breaker is in “connected” or “test” position. Y
DB402638.eps
It the breaker is put in the “connected” position with the
door open, the door may be closed without having to
disconnect the circuit breaker.
Dimensions (mm)
Type DC (1) (2)
NW10-40 DC (versions C-D) 215 215
NW10-40 DC (version E) 330 215
Type DC PV (1) (2)
NW10-40 DC PV (version D) 215 215
Note:
The door interlock can either be mounted on the right side or
the left side of the breaker.
F : Datum.
B-13
DB402737.eps
DB402738.eps
DB402739.eps
B-14
Cable connections
DB402740.eps
DB402741.eps
If cables are used for the power connections, make
sure that they do not apply excessive mechanical
forces to the circuit breaker terminals.
For this, make the connections as follows:
bb extend the circuit breaker terminals using short bars
designed and installed according to the
recommendations for bar-type power connections:
vv for a single cable, use solution B opposite
vv for multiple cables, use solution C opposite.
bb in all cases, follow the general rules for connections
to busbars:
vv position the cable lugs before inserting the bolts
v the cables should firmly secured to the framework of
the switchboard E.
DB402742.eps
Busbar connections
DB402743.eps
DB402744.eps
Electrodynamic stresses
The first busbar support or spacer shall be situated within a maximum distance from
the connection point of the breaker (see table below). This distance must be
respected so that the connection can withstand the electrodynamic stresses between
phases in the event of a short circuit.
Maximum distance A between busbar to circuit breaker connection and the first busbar
support or spacer with respect to the value of the prospective short-circuit current.
Isc (kA) 30 50 65 80 100
distance A (mm) 350 300 250 150 150
B-15
Clamping
DB402746.eps
DB402747.eps
DB402748.eps
DB402749.eps
1 Terminal screw factory-tightened to 16 Nm.
2 Breaker terminal. Tightening torques
3 Busbar. Ø Ø Tightening torque (Nm) Tightening torque
4 Bolt. with flat washers or (Nm) with contact
Nominal (mm) Drilling (mm)
5 Washer. split lockwashers or serrated washers
6 Nut.
10 11 37.5 50
Busbar drilling
Examples
DB402750.eps
DB402751.eps
DB402752.eps
Isolation distance
DB402753.eps
Dimensions (mm)
Ui X mini
500 V DC 8 mm
900 V DC 14 mm
Busbar bending
When bending busbars maintain the radius indicated below
(a smaller radius would cause cracks).
DB402754.eps
Dimensions (mm)
e Radius of curvature r
Min. Recommended
5 5 7.5
10 15 18 to 20
B-16
DB402756.eps
DB402757.eps
DB402758.eps
DB402759.eps
DB402760.eps
DB402762.eps
DB402763.eps
DB402764.eps
DB402765.eps
B-17
Basis of tables
b maximum permissible busbar temperature: 100 °C
b Ti: temperature around the circuit breaker and its connections
b busbar material is unpainted copper.
Example
Conditions:
b drawout version
b horizontal busbars
b Ti: 50 °C
b service current: 2000 A.
Solution
For Ti = 50 °C, use an NW20 DC - DC PV which can be connected
with three 100 x 5 mm bars or two 80 x 10 mm bars.
Basis of tables
b maximum permissible busbar temperature: 100 °C
b Ti: temperature around the circuit breaker and its connections
b busbar material is unpainted copper.
Example
Conditions:
b fixed version
b vertical busbars
b Ti: 40 °C
b service current: 1000 A.
Solution
For Ti = 40 °C, use an NW10 DC - DC PV which can be connected
with two 50 x 5 mm bars or one 50 x 10 mm bar.
B-18
B-19
schneider-electric.com
Presentation 2
Functions and characteristics A-1
Installation recommendations B-1
Front-panel accessories
Compact NSX100 to 630 DC C-14
Power connections
Compact NSX100 to 630 DC fixed version C-16
Connection of insulated bars or cables with lugs
to Compact NSX100 to 630 DC C-20
Connection of bare cables to Compact NSX100 to 630 DC C-21
Dimensions
1 pole 2 poles
DB402532.eps
DB402533.eps
DB402534.eps
X X X
Y Y
Mounting
On backplate
1 pole 2 poles
DB416364.eps
DB416365.eps
X X
Y Y
(c) For rear connection only.
On rails
1 pole 2 poles
DB402537.eps
DB402538.eps
X X
Y Y
C-2
DB416366.eps
DB416367.eps
DB416368.eps
X X X X
Y Y
Y
With escutcheon
DB416369.eps
DB402543.eps
X X
Dimensions (mm)
Type C C1 C2 C3 C6 C7 G G1 G4 G5 H
NSX100/160 DC 29 76 54 108 43 104 62.5 125 70 140 80.5
Type H1 H2 H3 H4 H6 H7 K K1 L3 L4 L5
NSX100/160 DC 161 94 188 160.5 178.5 357 17.5 35 17.5 70 35
Type P1 P2 P4 P5 P6 R R1 R2 R4 R5 R6
NSX100/160 DC 81 86 111 83 88 14.5 29 19 38 73 29
Type R7 ØT ØT4 U
NSX100/160 DC 58 6 22 y 32
C-3
Dimensions 3P 4P
DB112061.eps
DB112062.eps
DB112063.eps
DB112064.eps
A4
A3
A A2
A1
X X X
A A2
A3
A4
C1 B B
C2 B1 B2
C3
Z Y Y
Interphase barriers. Long terminal shields (also available for NSX400/630 DC spreaders with 52.5 mm pitch:
Short terminal shields. B1 = 157.5 mm, B2 = 210 mm).
F1 F1 F1 F1 F1 F1 F1
DB112065.eps
DB111411.eps
DB112067.eps
DB112066.eps
F2 F2 F2
F1 F1 F3
E4
X X X
E2
E1 E3
2 Ø6 Y ØT(1) Y 4 Ø6 Y 4 Ø6
On rails 3P 3P 4P
F1 F1 F3
DB112068.eps
DB111412.eps
DB112069.eps
DB112070.eps
F2 F2 F2
X X X
E2
E1
2 Ø6 Y Y 4 Ø6 Y 4 Ø6
C-4
DB112072.eps
G5
G3 X
G2
G1
Dimensions (mm)
Type A A1 A2 A3 A4 B B1 B2 C1 C2 C3
NSX100/160/250 DC 80.5 161 94 145 178.5 52.5 105 140 81 86 126
NSX400/630 DC 127.5 255 142.5 200 237 70 140 185 95.5 110 168
Type E1 E2 F1 F2 F3 G1 G2 G3 G4 G5
NSX100/160/250 DC 62.5 125 35 17.5 70 95 75 13.5 23 17.5
NSX400/630 DC 100 200 45 22.5 90 - - - - -
C-5
Dimensions 3P 4P
M
DB112640.eps
DB112641.eps
DB112642.eps
DB112643.eps
N
A11
M A10
A A2
N A1
X X X
A A2
A10
A11
B B
27 B1 B2
45
D1 C3
Z Y Y
Interphase barriers for base. Long terminal shields (also available for NSX400/630 DC spreaders with 52.5 mm pitch:
Short terminal shields on circuit breaker. B1 = 157.5 mm, B2 = 210 mm)
Adapter for base, required to mount long terminal shields or interphase barriers.
Mounting
Through front panel (N) 3P 3P 4P
NSX100 to 250 DC NSX400/630 DC NSX100 to 630 DC
F1 F1 F3
DB112648.eps
DB112649.eps
DB115637.eps
DB112650.eps
N F2 F2 F2
E10 E12 X X Y
X
E9 E11
F4 F4 F4 4 Ø6
2 Ø6 4 Ø6
F5 F5 F6
Y Y Y
C-6
F1 F3
DB112654.eps
DB112655.eps
DB112656.eps
F2 F2
E14 X X
E13
2 Ø6 4 Ø6
Y Y
F1 F1 F1 F1 F1
DB112657.eps
DB112658.eps
DB112659.eps
F1 F2
F2 F3
E14 E16 X X
E13 E15
2 Ø6 ØT1(1) 4 Ø6
Y Y
(1) The ØT1 holes are required for rear connection only.
F1 F1
DB112660.eps
DB112661.eps
DB112662.eps
F1 F1 F1
F1 F2
F2 F3
E14
E18 X
X
E13 E17
2 Ø6 ØT1(1) 4 Ø6
Y Y
(1) The ØT1 holes are required for rear connection only.
On rails 3P 4P
F7 F8
DB112663.eps
DB112664.eps
DB112665.eps
F9 F9
U
X X
E20
E19
2 Ø6 4 Ø6
Y Y
C-7
Dimensions 3P 4P
M
DB112644.eps
DB112645.eps
DB112646.eps
DB112647.eps
N
A10
M A12 A11
N
X X X
A13 A11
A10
B3 B3
27 B4 B6
45 B5 B7
D1 C3 Y Y
Z
M
DB112681.eps
C3 32
Z
Interphase barriers for base. Long terminal shields.
Short terminal shields on circuit breaker. Adapter for base, required to mount long terminal shields or interphase barriers.
Mounting
Through front panel (N) 3P 3P 4P
NSX100 to 250 DC NSX400/630 DC NSX100 to 630 DC
F1 F1 F3
DB112651.eps
DB112652.eps
DB115638.eps
DB112653.eps
N
F2 F2 F2
3 E10 E12 X X X
E9 E11
C-8
F1
DB112682.eps
DB112655.eps
DB112656.eps
F3
F2 F2
E14 X X
E13
2 Ø6 4 Ø6
Y Y
F1 F1 F1 F1 F1
DB112683.eps
DB112658.eps
DB112659.eps
F1 F2
F2 F3
E14 E16 X X
E13 E15
2 Ø6 ØT1(1) 4 Ø6
Y Y
(1) The ØT1 holes are required for rear connection only.
F1 F1
DB112684.eps
DB112661.eps
DB112662.eps
F1 F1 F1
F1 F2
F2 F3
E14
E18 X
X
E13 E17
2 Ø6 ØT1(1) 4 Ø6
Y Y
(1) The ØT1 holes are required for rear connection only.
On rails 3P 4P
F7 F8
DB112685.eps
DB112664.eps
DB112665.eps
F9 F9
U
X X
E20
E19
2 Ø6 4 Ø6
Y Y
Type A10 A11 A12 A13 B3 B4 B5 B6 B7 C3 D1 E9 E10 E11 E12 E13 E14
NSX100/160/250 DC 175 210 106.5 103.5 92.5 185 216 220 251 126 75 95 190 87 174 77.5 155
NSX400/630 DC 244 281 140 140 110 220 250 265 295 168 100 150 300 137 274 125 250
Type E15 E16 E17 E18 E19 E20 F1 F2 F3 F7 F8 F9 F10 F11 F12 ØT1 U
NSX100/160/250 DC 79 158 61 122 37.5 75 35 17.5 70 70 105 35 74 148 183 24 y 32
NSX400/630 DC 126 252 101 202 75 150 45 22.5 90 100 145 50 91.5 183 228 33 y 35
C-9
Dimensions 3P 4P
Fixed circuit breaker
DB112693.eps
DB112694.eps
DB112695.eps
DB112696.eps
A17
A15 X X X
A14 A16
Ø5...8
B8 B8
C4
B9 B9
C5/C6
B B
B1 B2
Y Y
Z
C5: without keylock
C6: with keylock
Plug-in circuit breaker
M M
DB112697.eps
DB112698.eps
N N
Ø5...8
27
45
D1 C5
Z
Withdrawable circuit breaker
M M
DB112699.eps
DB112700.eps
N N
X
Ø5...8
27
45
D1 C5 32
Z
C-10
Dimensions 3P 4P
Fixed circuit breaker
B10
DB112701.eps
DB112702.eps
DB112703.eps
DB112704.eps
I
60°
A15 X X X
60°
A14 O
A18
B8 B8
B9 B9
C7
B B
C8/C9 B1 B2
Z Y Y
DB112706.eps
N N
27
45
D1 C8
Z
N N
27
45
D1 C8 32
C-11
Dimensions
MCC type direct rotary handle
DB112712.eps
DB112713.eps
DB112714.eps
A18
A20
Ø5...
8
X X
A19
1...3 max.
P1 B10
B11
Z B12
Y
CNOMO type direct rotary handle
DB112715.eps
DB112716.eps
DB112717.eps
LIN GERI
MER t NS
compac
N
A18 A22
X X
8
Ø5...
push
to
trip
A21
1...3 max.
P2 B10
B13
B14
Z Y
DB111413.eps
DB111414.eps
100 145
Ø5...
8
X X
41 51
50
75
100
145
Y
Y
CNOMO type direct rotary handle
DB112715.eps
DB111415.eps
DB111416.eps
N
LIN GERI
MER t NS
compac
150
119
8
Ø5...
push
to
trip
X X
50.5 50.4
C-12
Dimensions
Fixed and plug-in circuit breakers
M M
DB112709.eps
DB112710.eps
N N
10
X
DB112711.eps
N N
DB111419.eps
C-13
DB114998.eps
DB114999.eps
DB115000.eps
DB416370.eps
X X
A
B 4
Y
DB115002.eps
DB115003.eps
DB115004.eps
X X
A1
B 4
Y
DB115010.eps
DB115011.eps
DB115012.eps
X A3 X
A2
B1 3.5 6.5
Y
DB115022.eps
DB115024.eps
DB115023.eps
X X
A4
B2 35
Y
C-14
DB115031.eps
DB115032.eps
DB115120.eps
X
A5
B3 C
Y
Type A A1 A2 A3 A4 A5 B B1 B2 B3 C
NSX100/160/250 DC 113 138 114 101 73 85 113 157 91 103 40
NSX400/630 DC 163 211 164 151 122.5 138 163 189 122.5 138 60
C-15
DB115445.eps
DB115446.eps
10.5 14
70 113.5
X X
Cables with lugs/bars Bars/cables with lugs
DB416576.eps
43 for short RC
88 for long RC
10 ∅8.6
13
18
70
6 ∅20
X
NSX400/630 DC
Z
DB416577.eps
50 for short RC
115 for long RC
15 ∅13 ∅23.2
14
30
113.5
8
X
C-16
DB416579.eps
DB115450.eps
Z Z
DB416578.eps
63
22
70 70
X X
DB115453.eps
NSX400/630 DC
DB416581.eps
Z Z
DB416580.eps
46.5
14
113.5 113.5
X X
DB416582.eps
70
41
64.5
66.5 (a)
(a) NSX250 DC. Z
Right-angle terminal extensions (upstream only)
NSX100 to 250 DC NSX400/630 DC
Z
DB115458.eps
DB403551.eps
DB403552.eps
Z
37.5 61 8
39.5 (b) 4
20.5 34
70 113.5
X X
(b) NSX250 DC.
Straight terminal extensions (for NSX100 to 250 DC only)
4
DB115461.eps
DB403553.eps
41
30
70
C-17
DB115464.eps
DB115465.eps
30
Z
23.5
58
53
42 8 42
70 113.5
4
X X
DB115467.eps
DB115468.eps
Z 10
13.5
61.5
40 48
31 8
4
70 113.5
X X
DB115470.eps
45
4
46
35
70
C-18
DB115472.eps
DB115473.eps
DB115474.eps
E2 E2 F2 E2 E2 E2 C3
F1
X X X
NSX400/630 DC
Y Y
C4
Type C3 C4 E1 E2 E3 F1 F2
NSX100/160 DC 23.5 - 114 45 159 100 11
NSX250 DC 25.5 - 114 45 159 100 11
NSX400/630 DC - 44 135 52.5 187.5 152.5 15
170 70 240 166 15
DB115477.eps
180.5
DB115476.eps
26
140
45 45 45
130
113.5
X
X
Y
Z
C-19
DB115653.eps
Direct connection to NSX100 to 630 DC
Dimensions NSX100 DC NSX160/250 DC NSX400/630 DC
Ø
400 Bars L (mm) y 25 y 25 y 32
d I (mm) d + 10 d + 10 d + 15
I
d (mm) y 10 y 10 y 15
L
e (mm) y6 y6 3 y e y 10
e
Ø (mm) 6.5 8.5 10.5
Bar.
Lugs L (mm) y 25 y 25 y 32
DB115654.eps
Accessories for NSX100 to 250 DC Connection with accessories to NSX100 to 250 DC (IEC 228)
Straight terminal Double-L terminal Pole pitch
extensions extensions Without spreaders 35 mm
DB112172.eps
DB112176.eps
With spreaders 45 mm
Dimensions With spreaders or terminal extensions
NSX100 DC NSX160/250 DC
Tinned copper Tinned copper Bars L (mm) y 25 y 25
DB115656.eps
l (mm) 20 y I y 25 20 y I y 25
Spreaders: d (mm) y 10 y 10
separate parts One-piece spreader 400 Ø
e (mm) y6 y6
DB112177.eps
DB416402.eps
Pole pitch
Without spreaders 45 mm
With spreaders 52.5 or 70 mm
Tinned copper Dimensions With spreaders With terminal extensions
For U > 600 V, use of the 52.5 mm pitch spreaders Bars L (mm) y 40 y 32
DB115656.eps
Tinned copper
C-20
DB115660.eps
Connection for NSX100 to 250 DC
DB112315.eps
DB112317.eps
DB111327.eps
1-cable 2-cable Distribution connector
connector connector
DB115663.eps
S (mm²) Cu / Al 1.5 to 95 (1) 25 to 50 70 to 95 120 to 185
150 max. flex.
L Torque (Nm) 12 20 26 26
2-cable connector
S
L (mm) 25 or 50
S (mm²) Cu / Al 2 x 50 to 2 x 120
Torque (Nm) 22
6-cable distribution connector (copper or aluminium)
L (mm) 15 or 30
S (mm²) Cu / Al 1.5 to 6 (1) 8 to 35
Torque (Nm) 4 6
(1) For flexible cables from 1.5 to 4 mm², connection with crimped or self-crimping ferrules.
DB111326.eps
C-21
X X X X X X X X X
Y Y Y
Z Y Y Y Y Y
DB402547.eps
X X X
Z
Y Y
X X X X X
Y
Y
Z Y Y
DB402549.eps
DB402550.eps
DB402551.eps
X X
X
Y
Y
Z
C-22
X X X X X X X
Y Y
Z Y Y Y Y
DB402554.eps
DB402555.eps
X X
Y
Z
X
X X X X
Y
Z Y Y
DB402558.eps
DB402560.eps
X X X
Y Y
Z
C-23
DB402562.eps
DB402563.eps
Z
Y
X X
X X
Z
Y
DB402565.eps
DB402566.eps
Y Z
X X
X X
Y Z
4P withdrawable version
Connections mounted with heat sink directed outwards
DB402568.eps
DB402569.eps
DB402567.eps
Y Z
X X
X X
Z
Y
DB402571.eps
DB402572.eps
Y Z
X X
X X
Y Z
C-24
DB402574.eps
DB402575.eps
Y Z
X X
X X
Z
Y
DB402577.eps
DB402578.eps
Y Z
X X
X X
Y Z
4P withdrawable version
Connections mounted with heat sink directed outwards
DB402579.eps
DB402580.eps
DB402581.eps
Y Z
X X
X X
Y Z
DB402583.eps
DB402584.eps
Y Z
X X
X X
Y
Z
C-25
DB413515.eps
12.5 47.5
DB416371.eps
55 60
DB415913.eps
Ø6
190.5
X X 125 X
70 625
Y
Ø22
17.5
Z 70
35 35 35
Y
67
DB416372.eps
75
DB415914.eps
356 Ø6
X X X
200
113.5
100
Ø32 22.5
Y
90
45 45 45
Z Y
Dimensions
DB112061R.eps
DB416373.eps
DB112064R.eps
A4
A3
A
A1
X X
A A2
A3
A4
C1 B
C2
B2
C3
Z Y
Interphase barriers. Long terminal shields (also available for NSX400/630 DC spreaders with 52.5 mm
Long terminal shields. pitch: B2 = 210 mm).
Type A A1 A2 A3 A4 B B2 C1 C2 C3
NSX100/160/250 DC PV 80.5 161 94 145 178.5 52.5 140 81 86 126
NSX400/630 DC PV 127.5 255 142.5 240 237 70 185 95.5 110 168
DB415753.eps
(1)
(2)
254
248.5
163.5 240
X 210 327
200
X
100
254
Z
107.5 169.5 99.5
175.5 Y
182
(1) With terminal shield.
(2) With phase separator.
Rear connection
DB415755.eps
X X
DB415754.eps
100
123
107.5 35
175.5 70
182 169.5 99.5
F
Z
Front-panel cutouts
Door cutout
A
DB415756.eps
150 mini
DB415916.eps
(A)
(1) (2)
Y
264 mini 194 mini
X X 216 (1)
266 (2)
108 (1)
133 (2)
DB415758.eps
4 Ø6.5
X
200
100
169.5 99.5
On rails
DB415759.eps
4 Ø6.5
X
200
100
169.5 99.5
Note: mounting parameters for electrically operated devices are identical to those for manually
operated devices.
X and Y are the symmetry planes for a 4-pole device.
Z is the back plane of the device.
DB415760.eps
4 Ø6.5
X
200
75
60 100
4 R30
169.5 99.5
270
On rails
DB415761.eps
169.5 99.5
2 Ø6.5
100
107
117
3 Ø6.5
35
Y
70 70
Note: mounting parameters for electrically operated devices are identical to those for manually
operated devices.
X and Y are the symmetry planes for a 4-pole device.
Z is the back plane of the device.
DB402242.eps
DB402241.eps
X X
Y
DB402244.eps
X
DB402243.eps
DB402246.eps
DB402247.eps
C-30
DB104832.eps
(fixed device)
NW10 to 40 DC
Version C
Connections
Horizontal rear connection (NW10 - NW20 DC) Detail
DB104808.eps
DB416092.eps
DB416093.eps
Y
X
Db101278.eps
Vertical rear connection (NW10 - NW20 DC) Detail
DB402252_55.eps
DB416094.eps
DB416095.eps
X Y
DB101282.eps
View A detail.
DB416096.eps
DB416097.eps
X Y
Db101314.eps
C-31
DB104833.eps
and connection
(fixed device)
NW10 to 40 DC - DC PV
Version D
Connections
Horizontal rear connection (NW10 - NW20 DC - DC PV) Detail
DB104818.eps
DB416098.eps
DB416099.eps
X
Db101278.eps
Vertical rear connection (NW10 - NW20 DC - DC PV) Detail
DB402264_55.eps
DB416100.eps
DB416101.eps
X
Y
DB101282.eps
View A detail.
Vertical rear connection (NW40 DC - DC PV) Detail
DB402268_55.eps
DB416102.eps
DB416103.eps
Y
Db101314.eps
Note:
Recommended connection screws: M10 class 8.8.
View A detail.
Tightening torque: 50 Nm with contact washer.
C-32
DB104835.eps
(fixed device)
NW10 to 40 DC
Version E
Connections
Horizontal rear connection (NW10 - NW20 DC) Detail
DB416105.eps
DB402272_55.eps
DB416104.eps Y
X
Db101278.eps
Vertical rear connection (NW10 - NW20 DC) Detail
DB402276_55.eps
DB416107.eps
DB416106.eps
X Y
DB101282.eps
View A detail.
DB416108.eps
DB416109.eps
Y
Db101314.eps
Note:
Recommended connection screws: M10 class 8.8.
Tightening torque: 50 Nm with contact washer. View A detail.
C-33
DB416111.eps
Y
X X
X Y
DB416112.eps
DB416113.eps
Db101294.eps
DB416114.eps
C-34
DB104879.eps
(drawout device)
NW10 to 40 DC
Version C
Connections
Horizontal rear connection (NW10 - NW20 DC) Detail
DB402291_55.eps
DB416115.eps
DB416116.eps
Y
Db101278.eps
X
DB416117.eps
DB416118.eps
Y
X
DB101282.eps
View A detail.
DB416119.eps
DB416120.eps
Y
X
Db101314.eps
Note:
Recommended connection screws: M10 class 8.8.
Tightening torque: 50 Nm with contact washer. View A detail.
C-35
DB104880.eps
and connection
(drawout device)
NW10 to 40 DC - DC PV
Version D
Connections
Horizontal rear connection (NW10 - NW20 DC - DC PV) Detail
DB402303_55.eps
DB416121.eps
DB416122.eps
Y
Db101278.eps
Vertical rear connection (NW10 - NW20 DC - DC PV) Detail
DB104859.eps
DB416123.eps
DB416124.eps
X
Y
DB101282.eps
View A detail.
Vertical rear connection (NW40 DC - DC PV) Detail
DB402311_55.eps
DB416125.eps
DB416126.eps
Y
Db101314.eps
Note:
Recommended connection screws: M10 class 8.8.
Tightening torque: 50 Nm with contact washer. View A detail.
C-36
DB104881.eps
(drawout device) 0
NW10 to 40 DC
Version E
Connections
Horizontal rear connection (NW10 - NW20 DC) Detail
DB402315_55.eps
DB416127.eps
DB416128.eps
X Y
Db101278.eps
Vertical rear connection (NW10 - NW20 DC) Detail
DB104871.eps
DB416129.eps
DB416130.eps
X Y
DB101282.eps
View A detail.
Vertical rear connection (NW40 DC) Detail
DB416131.eps
DB402323_55.eps
DB416132.eps
Y
Db101314.eps
Note:
Recommended connection screws: M10 class 8.8. View A detail.
Tightening torque: 50 Nm with contact washer.
C-37
DB416134.eps
Y
X
X
F : Datum.
Escutcheon
Fixed device Drawout device
Y Y
DB416135.eps
DB416136.eps
X X
Db101368.eps
C-38
DB115891.eps
6
3 4 5
S
3 6
MN
UVR
30 V
100/1C
AC/D
C-39
Ecodial
Presentation 2
Functions and characteristics A-1
Installation recommendations B-1
Dimensions and connection C-1
Masterpact NW DC - DC PV
Communication D-12
Withdrawable Masterpact NW DC - DC PV
Wiring of the COM option (with CCM) and external power supply D-15
D-1
C2
A4
A2
B4
B2
C1
a (-)
manu SDE
a (-)
NSX cord
a (220/240 V)
+ -
BSCM
HL
B4
auto 0 I
manu
A1
Communicating motor
mechanism (MTc) (1)
D-2
Indication contacts
DB403696.eps
102
104
134
124
42
32
22
12
82
84
92
94
44
34
24
14
WH
RD
YE
VT
OF4 OF3 OF2 OF1 SDE SD CAF2 CAF1 CAO1
WH
RD
GY
131
41
31
21
121
101
81
91
11
D-3
Remote operation
a (+)
a (+)
DB413077.eps
SDE 81
BPO BPF
82 84
C2
D2
B4
A4
A2
84
RD
A2 WH
BL
C2 OR
A4 OR
BL
D2
B4
B2
MN MX
auto
0 I
or manu
A1
L1
D1
C1
GN
WH
BK
A1
D1/C1
L1
NSX cord
a (220/240 V)
+ -
HL
BSCM
B4
B4 GN
auto
0 I
manu
OR A1
A4
Communicating motor
mechanism (MTc) (1)
D-4
32
22
12
82
84
92
94
44
34
24
14
42 GN
82 GN
92 GN
44 RD
84 RD
94 RD
32 YE
22 YE
12 YE
34 VT
24 VT
14 VT
314
312
352
354
102
104
134
124
WH
GY
GY
RD
VT
VT
YE
VT
OF4 OF3 OF2 OF1 SDE SD CAF2 CAF1 WH CAO1 CE CD
YE
YE
GY
RD
131
121
101
BK 41
GY 31
GY 21
311
351
BK 81
BK 91
GY 11
41
31
21
81
91
11
D-5
The diagram is shown with circuits Motor mechanism (MT) with automatic reset
de-energised, all devices open, connected and a (+)
charged and relays in normal position.
DB114666.eps
SDE 81
BPO BPF
After tripping initiated by the "Push to trip" button or
by the undervoltage (MN) release or the shunt (MX)
release, device reset can be automatic, remote or 82 84
manual.
A4
A2
B4
B2
Following tripping due to an electrical fault (with an
SDE contact), reset must be carried out manually.
Q
auto
0 I
manu
A1
L1
manu SDE
a (-)
SDE 81
BPO BPF Reset
82 84
A4
A2
B4
B2
Q
auto
0 I
manu
A1
L1
manu SDE
a (-)
SDE 81
BPO BPF
82 84
A4
A2
B4
B2
Symbols
Q: circuit breaker
A4 : opening order
A2: closing order
B4, A1: motor mechanism power supply Q
L1: manual position (manu) auto
0 I
manu
B2: SDE interlocking (mandatory for correct
operation)
A1
L1
D-6
NSX cord
DB114669.eps
a (220/240 V)
+ -
HL
BSCM
B4
Q
auto 0 I
manu
A1
a
DB114670R.eps
Symbols
Q: circuit breaker
B4, A1: motor mechanism power supply
BSCM: breaker status and control module
Terminals shown in red O must be connected by the customer.
D-7
Remote operation
MN : undervoltage release
DB128373.eps
or
MX : shunt release
AT BPO BPF
Motor-mechanism module (1)
A4 : electrical opening order
D2
C2
A2
CN1 a - 440/480 V
DB128380.eps
9 11
MN MX Motor-mechanism R
module A4 A2 B4
or
Motor-mechanism
module
D1
A1
C1
A1
CN2 a - 440/480 V
D-8
DB128377R.eps
MN/MX
D1/C1
D2/C2
31 21 11
32 22 12
34 24 14
B4 A4 A2 A1
D-9
DB404307.eps
DB105058.eps
Micrologic DC Micrologic DC
Version E - DC Version D - DC PV
DB416406.eps
DB404308.eps
Micrologic DC
E3 E4 182 82 C3 A3 252 B3
D-10
44 34 24 14 244 234 224 214 144 134 124 114 834 824 814 334 324 314 934 924 914
42 32 22 12 242 232 222 212 142 132 122 112 832 822 812 332 322 312 932 922 912
41 31 21 11 241 231 221 211 141 131 121 111 831 821 811 331 321 311 931 921 911
or or or or or or or or or or
EF24 EF23 EF22 EF21 EF14 EF13 EF12 EF11 CE6 CE5 CE4 CE9 CE8 CE7
248 238 228 218 148 138 128 118 364 354 344 394 384 374
246 236 226 216 146 136 126 116 362 352 342 392 382 372
245 235 225 215 145 135 125 115 361 351 341 391 381 371
OF14 or or
EF14
CD6 Disconnected
OF13 or CD5 position
EF13 CD4 contacts
OF12 or
EF12
OF11 or
EF11
Legend:
Interconnected connections
(only one wire per connection point).
D-11
Ethernet
1 2
24 V c
Modbus 24 V c
6 6
Masterpact NW DC
D-12
Ethernet
+ -
External power supply
24 V c EGX100
Rx- Rx+ Tx- Tx+
+ -
Modbus line
termination
(VW3A8306DRC)
24 V
0V
D0
D1
24 V
0V
D0
D1
24 V
0V
D0
D1
Modbus Communication Interface Module (Compact NSX DC)
+ - + - + -
FDM121 FDM121
Network
A B A' B'
version > V2.0.2 version > V2.0.2
CCM
Breaker
A B A' B'
+ -
E1 E2 E3 E4 E5 E6 E1 E2 E3 E4 E5 E6
24 V
0V
A / Tx - D0
A' / Rx - D0
24 V
0V
B / Tx + D1
B' / Rx+ D1
A / Tx - D0
B / Tx + D1
A' / Rx - D0
B' / Rx+ D1
E5 E6
E3 E4
E1 E2
D-13
Modbus RS 485 4-wire Modbus RS 485 2-wire Modbus RS 485 2-wire + ULP
DB404311.eps
+ - + - + -
EGX100 EGX100 EGX100
Rx- Rx+ Tx- Tx+ Rx- Rx+ Tx- Tx+ Rx- Rx+ Tx- Tx+
+ -
FDM121
version > V2.0.2
Breaker ULP
cord
E1 E2 E3 E4 E5 E6 E1 E2 E3 E4 E5 E6 E1 E2 E3 E4 E5 E6
B / Tx+ D1
A’ / Rx- D0
B’ / Rx+ D1
24 V
0V
A / Tx- D0
B / Tx+ D1
A’ / Rx- D0
B’ / Rx+ D1
24 V
0V
A / Tx- D0
B / Tx+ D1
A’ / Rx- D0
B’ / Rx+ D1
24 V
0V
A / Tx- D0
D-14
A Modbus RS 485 4-wire A Modbus RS 485 2-wire B Modbus RS 485 2-wire + ULP
DB404312.eps
+ - + - + -
EGX100 EGX100 EGX100
Rx- Rx+ Tx- Tx+ Rx- Rx+ Tx- Tx+ Rx- Rx+ Tx- Tx+
The B configuration is
only possible with CCM
marked Schneider Electric
on the front face.
+ - + - + - + -
Network
Network
FDM121
Network
A B A’ B’ A B A’ B’ A B A’ B’
version > V2.0.2
CCM CCM CCM
Breaker
Breaker
Breaker
A B A’ B’ A B A’ B’ A B A’ B’
+ - + - + -
Breaker ULP
cord
E1 E2 E3 E4 E5 E6 E1 E2 E3 E4 E5 E6 E1 E2 E3 E4 E5 E6
24 V
0V
A / Tx- D0
24 V
0V
A / Tx- D0
B / Tx+ D1
A’ / Rx- D0
B’ / Rx+ D1
24 V
0V
A / Tx- D0
B / Tx+ D1
A’ / Rx- D0
B’ / Rx+ D1
B / Tx+ D1
A’ / Rx- D0
B’ / Rx+ D1
D-15
schneider-electric.com
Presentation 2
Functions and characteristics A-1
Installation recommendations B-1
Dimensions and connection C-1
Electrical diagrams D-1
E-1
TM16D TM25D
DB413316.eps
DB413317.eps
TM32D TM40D
DB413318.eps
DB413319.eps
E-2
TM50D TM63D
DB413320.eps
DB413321.eps
TM63D : Im = 11 x In
TM80D TM100D
DB416611.eps
DB416610.e
E-3
Additional Compact NSX100 to 250 DC
characteristics
TMD magnetic trip units, tripping curves
TM125D TM160D
DB416310.eps
DB416311.eps
TM200D TM250D
DB416312.eps
DB416313.eps
E-4
TM16G TM25G
DB416352.eps
DB416353.eps
TM25G DC : Im 4.3 x In
TM40G TM63G
DB416354.eps
DB416355.eps
E-5
TM80G TM100G
DB416583.eps
DB416584.eps
TM80G TM100G
Im = 3.1 x In Im = 4 x In
t < 10 ms t < 10 ms
TM125G TM160G
DB416586.eps
DB416585.eps
TM160G
TM125G
Im = 3.3 x In
Im = 2.7 x In
t < 10 ms t < 10 ms
E-6
TM200G TM250G
DB416587.eps
DB416588.eps
TM200G TM250G
Im = 2.6 x In Im = 2.5 x In
t < 10 ms t < 10 ms
E-7
DB416183.eps
E-8
The limiting capacity of a circuit breaker is its aptitude Ics = 100 % Icu
to let through a current, during a short-circuit, that is The exceptional limiting capacity of the Compact NSX DC range greatly reduces the
less than the prospective short-circuit current. forces created by fault currents in devices.
The result is a major increase in breaking performance.
In particular, the service breaking capacity Ics is equal to 100 % of Icu.
The Ics value, defined by IEC standard 60947-2, is guaranteed by tests comprising
(Isc) the following steps:
DB416363.eps
Prospective b break three times consecutively a fault current equal to 100 % of Icu
Isc peak
b check that the device continues to function normally, that is:
v it conducts the rated current without abnormal temperature rise
v protection functions perform within the limits specified by the standard
Prospective v suitability for isolation is not impaired.
current
Longer service life of electrical installations
Limited Isc Current-limiting circuit breakers greatly reduce the negative effects of short-circuits
peak on installations.
Actual
current Thermal effects
Limited Less temperature rise in conductors, therefore longer service life for cables.
Isc
Mechanical effects
(t) Reduced electrodynamic forces, therefore less risk of electrical contacts or busbars
The exceptional limiting capacity of the Compact NSX DC being deformed or broken.
range is due to the rotating double-break technique (very rapid Electromagnetic effects
natural repulsion of contacts and the appearance of two arc Fewer disturbances for measuring devices located near electrical circuits.
voltages in-series with a very steep wave front).
Current and energy limiting curves
The limiting capacity of a circuit breaker is expressed by two curves which are a
function of the prospective short-circuit current (the current which would flow if no
protection devices were installed):
b the actual peak current (limited current)
b thermal stress (A2s), i.e. the energy dissipated by the short-circuit in a conductor
with a resistance of 1 Ω.
Example
What is the real value of a 150 kA rms prospective short-circuit (i.e. 330 kA peak)
limited by an NSX250L DC upstream ?
The answer is 30 kA peak (curve page E-11).
Example
Is a Cu/PVC cable with a CSA of 10 mm² adequately protected by an NSX160F?
The table above indicates that the permissible stress is 1.32x106 A2s.
All short-circuit currents at the point where an NSX160F (Icu = 35 kA) is installed are
limited with a thermal stress less than 6x105 A2s (curve page E-11).
Cable protection is therefore ensured up to the limit of the breaking capacity of the
circuit breaker.
E-10
DB403733.eps
DB403731.eps
NSX400 DC
NSX630 DC
DC
DC NSX250 DC
DC NSX160 DC
DC NSX100 DC
DC
NSX400 DC
NSX630 DC
DC
DC
NSX250 DC
NSX100 DC
NSX160 DC
E-11
TM80D TM125D
DB416348.eps
DB416349.eps
TM160D TM200D
DB416350.eps
DB416351.eps
E-12
TM250D TM320D/400D
DB415723.eps
DB415724.eps
IEC PV TM250D IEC PV TM320D/400D
Im = 5... 10 x In Im = 5... 10 x In
TM500D
DB415725.eps
IEC PV TM500D
Im = 5... 10 x In
E-13
DB104941.eps
E-14
DB104944.eps
E-15
DB104947.eps
E-16
DB104950.eps
E-17
DB104953.eps
E-18
DB104956.eps
E-19
Ecodial
Order form
Compact NSX100 DC to NSX630 DC F-29
Compact NSX80/500 TM DC PV to NSX100/500 NA DC PV
Circuit breakers and switch-disconnectors F-30
Masterpact NW DC F-32
F-1
F-2
Rating 3P 3d 4P 4d
TM16D LV429037 LV429057
TM25D LV429036 LV429056
TM32D LV429035 LV429055
TM40D LV429034 LV429054
TM50D LV429033 LV429053
TM63D LV429032 LV429052
TM80DC LV438029 LV438049
TM100DC LV438028 LV438048
TM125DC LV438136 LV438146
TM160DC LV438135 LV438145
TM200DC LV438246 LV438256
TM250DC LV438245 LV438255
Type G protection: trip unit TM-G
Rating 3P 3d 4P 4d
TM16G LV429155 LV429165
TM25G LV429154 LV429164
TM40G LV429153 LV429163
TM63G LV429152 LV429162
TM80G LV430080 LV430092
TM100G LV430081 LV430093
TM125G LV430082 LV430094
TM160G LV430083 LV430095
TM200G LV430084 LV430096
TM250G LV430085 LV430097
Compact NSX400/630 DC with trip unit MP
3P 4P
DB404342.eps
F-3
3P LV429517
4P LV429518
Set of 3 LV429242
Set of 4 LV429243
Aluminium connectors 25 to 95 mm2 ; y 250 A Set of 2 LV429255
Set of 3 LV429227
DB112725.eps
Set of 4 LV429228
120 to 185 mm2 ; y 250 A Set of 2 LV429247
Set of 3 LV429259
Set of 4 LV429260
Clips for connectors Set of 10 LV429241
DB112726.eps
DB112227.eps
Aluminium connectors for 2 cables (4) 2 x (50 to 120 mm²) ; y 250 A Set of 3 LV429218 LV432479
(3P)
Set of 4 LV429219 LV432480
(4P)
DB112228.eps
Aluminium connectors (4) for 6 cables 6 x (1.5 to 35 mm²) ; y 250 A Set of 3 LV429248 LV432481
(3P)
Set of 4 LV429249 LV432482
(4P)
6.35 mm voltage tap for steel or aluminium connectors Set of 10 LV429348
DB112724.eps
F-4
Set of 3 LV429263
Set of 4 LV429264
Set of 4 LV429224
Set of 4 LV429222
4P LV431564
4P LV431061
Front alignment base (for one-piece spreader) 3P/4P LV431064
Set of 4 LV429256
For cable 150 mm2 Set of 3 LV429253
Set of 4 LV429257
For cable 185 mm2 Set of 3 LV429254
Set of 4 LV429258
For cable 240 mm2 Set of 3 LV432500
Set of 4 LV432501
For cable 300 mm2 Set of 3 LV432502
Set of 4 LV432503
Crimp lugs for aluminium cable (supplied with 2 or 3 interphase barriers)
For cable 150 mm2 Set of 3 LV429504
DB404351.eps
Set of 4 LV429505
For cable 185 mm2 Set of 3 LV429506
Set of 4 LV429507
For cable 240 mm2 Set of 3 LV432504
Set of 4 LV432505
For cable 300 mm2 Set of 3 LV432506
Set of 4 LV432507
Barriers
Interphase barriers Set of 6 LV429329 LV432570
DB115920.eps
Insulation screen
2 insulating screens for breaker (45 mm pitch) 3P LV429330
DB112242.eps
push
to
4P LV429331
trip
F-5
Electrical auxiliaries
Auxiliary contacts (changeover)
OF or SD or SDE or SDV 29450
DB404352.eps
Voltage releases MX MN
AC 24 V 50/60 Hz LV429384 LV429404
DB404353.eps
F-6
Communication accessories
ULP communication module
Modbus interface Modbus SL communication interface module TRV00210
DB111441.eps
(1)
(2)
24-30 V DC 54440
48-60 V DC 54441
100-125 V AC 54442
110-130 V AC 54443
200-240 V AC 54444
380-415 V AC 54445
(1) SDE adapter mandatory for trip unit TM,TMG.
(2) See Telemecanique catalogue.
F-7
ON
I
With red handle on yellow front LV429339 LV432599
MCC conversion accessory LV429341 LV432606
CNOMO conversion accessory LV429342 LV432602
O
OFF
ON
O
OFF ON
I
With telescopic handle for withdrawable device LV429343 LV432603
OFF
Accessories
Indication auxiliary 1 early-break contact LV429345 LV432605
2 early-break contacts LV429346 LV429346
Locks NSX100-250 DC NSX400-630 DC
Toggle locking device for 1 to 3 padlocks
By removable device 29370 29370
DB115913.eps
push
to
trip
By fixed device for 3P/4P (open position only) LV429370 (1) LV432630 (1)
push
to
trip
ON
I
Keylock (keylock adapter not included) Ronis 1351B.500 41940 41940
Profalux KS5 B24 D4Z 42888 42888
O
OFF
2
Keylock (keylock adapter not included) Ronis 1351B.500 41940
/auto
I
1
Profalux KS5 B24 D4Z 42888
manu O push
ON
OFF
push
LV429344 LV432604
1 set of 2 keylocks Ronis 1351B.500 41950 41950
(1 key only, keylock kit not included) Profalux KS5 B24 D4Z 42878 42878
F-8
IP30
DB112737.eps
IP40
IP43 rubber toggle cover
DB112738.eps
Lead-sealing accessories
DB115615.eps
1 adapter LV429305
F-9
Auxiliary connections
1 9-wire fixed connector (for base)
DB117160.eps
LV429273 LV429273
DB117161.eps
LV429272 LV429272
Base 2P LV429265
3P LV429266 LV432516
DB117181.eps
F-10
NS retrofit escutcheon
DB111432.eps
LV429226 LV429226
DB111429.eps
Torque limiting screws (set of 12) 3P/4P Compact NSX100-630 LV429513 LV432513
DB111436.eps
F-11
F-12
Terminal shield
1 short terminal shield for breaker or plug-in base LV432592
DB416407.eps
4P LV429516
Set of 3 LV429242
Set of 4 LV429243
Aluminium connectors 25 to 95 mm2 ; y 250 A Set of 2 LV429255
Set of 3 LV429227
DB112725.eps
Set of 4 LV429228
120 to 185 mm2 ; y 250 A Set of 2 LV429247
Set of 3 LV429259
Set of 4 LV429260
Clips for connectors Set of 10 LV429241
DB112726.eps
DB112227.eps
Aluminium connectors for 2 cables (1) 2 x (50 to 120 mm²) ; y 250 A Set of 3 LV429218 LV432479
(3P)
Set of 4 LV429219 LV432480
(4P)
DB112228.eps
Aluminium connectors (1) for 6 cables 6 x (1.5 to 35 mm²) ; y 250 A Set of 3 LV429248 LV432481
(3P)
Set of 4 LV429249 LV432482
(4P)
6.35 mm voltage tap for steel or aluminium connectors Set of 10 LV429348
DB112724.eps
F-13
Set of 3 LV429263
Set of 4 LV429264
Set of 4 LV429224
Set of 4 LV429222
4P LV431564
Set of 4 LV429256
For cable 150 mm2 Set of 3 LV429253
Set of 4 LV429257
For cable 185 mm2 Set of 3 LV429254
Set of 4 LV429258
For cable 240 mm2 Set of 3 LV432500
Set of 4 LV432501
2
For cable 300 mm Set of 3 LV432502
Set of 4 LV432503
Crimp lugs for aluminium cable (supplied with 2 or 3 interphase barriers)
For cable 150 mm2 Set of 3 LV429504
DB404351.eps
Set of 4 LV429505
For cable 185 mm2 Set of 3 LV429506
Set of 4 LV429507
For cable 240 mm2 Set of 3 LV432504
Set of 4 LV432505
For cable 300 mm2 Set of 3 LV432506
Set of 4 LV432507
Barriers
Interphase barriers Set of 6 LV429329 LV432570
DB115920.eps
Insulation screen
2 insulating screens for breaker (45 mm pitch) 3P LV429330
DB112242.eps
push
to
4P LV429331
trip
Note: circuit breakers or switch-disconnectors must be in "off" position when fitting the mechanical or electrical accessories.
F-14
Electrical auxiliaries
Auxiliary contacts (changeover)
OF or SD or SDE or SDV 29450
DB404352.eps
Voltage releases MX MN
AC 24 V 50/60 Hz LV429384 LV429404
DB404353.eps
F-15
(2)
24-30 V DC 54440
48-60 V DC 54441
100-125 V AC 54442
110-130 V AC 54443
200-240 V AC 54444
380-415 V AC 54445
(1) NSX80-250 DC PV TM/NA only.
(2) SDE adapter mandatory for trip unit TM,TMG.
F-16
ON
I
With red handle on yellow front LV429339 LV432599
MCC conversion accessory LV429341 LV432606
CNOMO conversion accessory LV429342 LV432602
O
OFF
ON
O
OFF ON
I
With telescopic handle for withdrawable device LV429343 LV432603
OFF
Accessories
Indication auxiliary 1 early-break contact LV429345 LV432605
2 early-break contacts LV429346 LV429346
Locks NSX100-250 NSX400-630
DC PV DC PV
Toggle locking device for 1 to 3 padlocks
By removable device 29370 29370
DB115913.eps
push
to
trip
ON
I
Keylock (keylock adapter not included) Ronis 1351B.500 41940 41940
Profalux KS5 B24 D4Z 42888 42888
O
OFF
2
Keylock (keylock adapter not included) Ronis 1351B.500 41940
/auto
I
1
Profalux KS5 B24 D4Z 42888
manu O push
ON
OFF
push
LV429344 LV432604
1 set of 2 keylocks Ronis 1351B.500 41950 41950
(1 key only, keylock kit not included) Profalux KS5 B24 D4Z 42878 42878
F-17
IP30
DB112737.eps
IP40
IP43 rubber toggle cover
DB112738.eps
Lead-sealing accessories
DB115615.eps
1 adapter LV429305
F-18
Basic Frame
Compact NSX type NA
DB416414.eps
4P
NSX630b NA DC PV LV453421
NSX800 NA DC PV LV453423
NSX1000 NA DC PV LV453425
NSX1250 NA DC PV LV453427
NSX1600 NA DC PV LV453429
I ON
push
OOFF
push
Note: the characteristics of the motor mechanism module for electrical operation are specified
d
discharge
O OFF
separately by selecting a part number from the table at the bottom of this page.
Bottom 33613
Heatsink (mandatory 2 x) Top 2 x LV438966
Rear connection
DB416416.eps
Communication options
For fixed devices Electrically operated
DB416589.eps
Electrical auxiliaries
Indication contacts
6 A - 240 V Low level
DB128428.eps
F-19
Connection
C or D type E type
Fixed or drawout circuit breakers or switches
Rear connection (vertical or horizontal mounting) / Replacement kit (3 or 4 parts)
1000/2000 A Vertical or horizontal 47966 47967
DB404366.eps
Top or bottom
Vertical mounting
Connection accessories
Additional support brackets for mounting on a backplate
For fixed rear-connected circuit breaker (2 parts) 47829
DB404369.eps
F-20
Remote operation
Gear motor
MCH (1 part)
DB404410.eps
AC 50/60 Hz 48 V 47889
100/130 V 47893
200/240 V 47894
250/277 V 47895
380/415 V 47896
440/480 V 47897
DC 24/30 V 47888
48/60 V 47889
100/125 V 47890
DB404322.eps
200/250 V 47891
Terminal block (1 part) For fixed circuit breaker 47074
For drawout circuit breaker 47849
DB416231.eps
AC 50/60 Hz 12 V DC 33658
DC 24/30 V DC, 24 V AC 33659
48/60 V DC, 48 V AC 33660
100/130 V AC/DC 33661
200/250 V AC/DC 33662
277 V AC 33663
380/480 V AC 33664
Communicating coil (1 part)
AC 50/60 Hz 12 V DC 33032
DC 24/30 V DC, 24 V AC 33033
48/60 V DC, 48 V AC 33034
100/130 V AC/DC 33035
200/250 V AC/DC 33036
277 V AC 33037
DB404322.eps
380/480 V AC 33038
Terminal block (1 part) For fixed circuit breaker 47074
For drawout circuit breaker 47849
DB416231.eps
R (non-adjustable) Rr (adjustable)
AC 50/60 Hz 48/60 V AC/DC 33680
DC 100/130 V AC/DC 33684 33681
200/250 V AC/DC 33685 33682
380/480 V AC/DC 33683
Installation manual 47951
F-21
Chassis locking
“Disconnected” position locking / 1 part
By padlocks
DB404325.eps
VCPO Standard
By Profalux keylocks
Profalux 1 lock with 1 key + adaptation kit 64934
2 locks 1 key + adaptation kit 64935
2 locks 2 different keys + adaptation kit 64936
1 keylock Profalux identical key not identified combination 33173
(without adaptation kit): identical key identified 215470 combination 33174
identical key identified 215471 combination 33175
By Ronis keylocks
Ronis 1 lock with 1 key + adaptation kit 64937
2 locks 1 key + adaptation kit 64938
2 locks 2 different keys + adaptation kit 64939
1 keylock Ronis identical key not identified combination 33189
(without adaptation kit): identical key identified EL24135 combination 33190
identical key identified EL24153 combination 33191
identical key identified EL24315 combination 33192
Adaptation kit adaptation kit Profalux / Ronis 48564
(without keylock): adaptation kit Kirk 48565
adaptation kit Castell 48566
Installation manual 47952
Door interlock / 1 part
Right and left-hand side of chassis (VPECD or VPECG) 47914
DB404326.eps
4P 48596
4000b/6300 A 3P 48597
4P 48598
4P 48723
4000b/6300 A 3P 48722
4P 48724
Installation manual 47952
Shutter locking block (for replacement) / 1 part
2 parts for 800/4000 A 48591
DB404333.eps
F-22
Clusters
1 disconnecting contact cluster for chassis (see table below) (part 1) 64906
DB403280.eps
Racking handle
Racking handle 47944
DB403281.eps
DC rear connection
Serial connection kit
For NW10/20 DC 48642
DB416603.eps
F-23
48539
By Profalux keylocks
Profalux 1 lock with 1 key + adaptation kit 64928
2 locks 1 key + adaptation kit 64929
2 locks 2 different keys + adaptation kit 64930
1 keylock Profalux identical key not identified combination 33173
(without adaptation kit): identical key identified 215470 combination 33174
identical key identified 215471 combination 33175
By Ronis keylocks
Ronis 1 lock with 1 key + adaptation kit 64931
2 locks 1 key + adaptation kit 64932
2 locks 2 different keys + adaptation kit 64933
1 keylock Ronis identical key not identified combination 33189
(without adaptation kit): identical key identified EL24135 combination 33190
identical key identified EL24153 combination 33191
identical key identified EL24315 combination 33192
Adaptation kit adaptation kit Profalux / Ronis 64925
(without keylock): adaptation kit Kirk 64927
adaptation kit Castell 64926
Installation manual 47951
Other circuit breaker accessories
Mechanical operation counter / 1 part
Operation counter CDM 48535
DB125617.eps
DB403098.eps
DB403099.eps
Escutcheon Cover
Blanking plate Installation manual 47951
Spring charging handle / 1 part
Spring charging handle 47940
DB404413.eps
F-24
F-25
Indication contacts
ON/OFF indication contacts (OF) / 12 parts
1 additional block of 4 contacts 64922
DB404321.eps
Low-level 47916
Wiring For fixed circuit breaker 47074
For drawout circuit breaker 47849
Combined closed / connected contacts for use with 1 auxiliary contact / 1 part
1 contact (5 A - 240 V) 48477
DB404322.eps
1 pushbutton 48534
F-26
Instructions
Chassis accessories 47952
Circuit breaker accessories 47951
Fixed and drawout circuit breaker 47950
User manual NW DC (French) 64923
NW DC (English) 64924
Modbus communication notice for manual 33088
F-27
(1)
10 Modbus line terminators VW3A8306DRC
DB111443.eps
F-28
F-29
F-30
Communication Locking
COM module Modbus For electrically VBP - ON/OFF pushbutton locking
operated devices (by transparent cover + padlocks)
Front Display Module (FDM121) Mounting accessory (NSX630b/1600 DC PV)
OFF position locking:
Breaker ULP Cord L = 0.35 m
VCPO - by padlocks
L = 1.3 m
VSPO - by keylocks:
L=3m
Keylock kit (w/o keylock) Profalux Ronis
AD - external power-supply module V
1 keylock Profalux Ronis
NSX630b/1600 DC PV connection
2 identical keylocks, 1 key Profalux Ronis
Horizontal rear connections Bottom
Vertical rear connections Bottom Accessories
Front connections Bottom CDM - mechanical operation counter
4 x 240° + bare cable connectors + shields Bottom CDP - escutcheon
Vertical-connection adapters Bottom CP - transparent cover for escutcheon
Cable-lug adapters Bottom OP - blanking plate for escutcheon
Long connection shields (1) Top Bottom
or interphase barriers Bottom
(1) Bottom long connection shield or Bottom interphase
barriers kit is mandatory.
F-31
F-32
LVPED208006EN 12-2013