CONCRETE COMPRESSIVE STRENGHT TEST REPORT NF EN

12390-3
Number of Test Report 188
Project CONGO – BIOFUEL 1st AGRI HUB - INDUSTRIAL START-UP
Contractor ZEROCK CONSTRUCTION CONGO
Origin of Concrete Zerock Concrete Batching Plant in Loudima

Temperature 36.8 / 33.7 °C Size of specimen (16 x 32 cm) x 3


Pouring date 10/23/2023 Slump test at 0' 16 cm
Mix Design Code 25 - XC4 - D25 - S3 - 42.5N - SHR - S0/1
Composition Cement Water Sand Gravel 1 Gravel 2 Admixture
Type 42,5N - 0/1 5/12,5 16/25 Admix150
Quantity(Kg/m3) 450 178.78 574 260 1018 4
Part of Structure

Shed BOILER / Sub-column / A1F20-A2F20-A3F20-A4F20-A5F20-B1F20-B2F20-B3F20-B4F20-B5F20

30A100_RFI_229 EXT
Number notification Date of receipt 10/28/2023
30A100_RFI_262 EXT
Curing by Density Strength (Mpa)
Spec. Tag Crushing date Weight (Kg) Load (kN)
days (T/m3) Unit Average
AH889 15.70 2.44 237.29 11.80
AH890 7 10/30/2023 15.64 2.43 363.07 18.06 15.48
AH891 15.64 2.43 333.44 16.58
AH892 15.74 2.45 388.19 19.31
AH893 28 11/20/2023 15.92 2.48 397.67 19.78 19.30
AH894 15.80 2.46 378.53 18.83

Number notification 30A100_RFI_313 EXT Date of receipt 12/18/2023

Density STRENGHT (Mpa)


Spec. Tag Age Crushing date Weight (Kg) Load (kN)
(T/m3) Unit Average
AH895
AH896 56 12/18/2023
AH897

Inspectors for : GEOLAB ENI CONGO ZEROCK