Fans Static

Pressure Drop
Calculation
NORTH COAST PALACE
El Alamein – Egypt
Revision 0
Table of Contents

· Summary.
· Fans Design Schedule.
· Fans Pressure Drop Calculation.
· Method Statement.
Summary
Fans ESP Calculation Summary

Actual Flow rate Design Schedule -ESP Actual (calculated)-ESP


UNIT -TAG Design Flow rate (CFM) Remarks
(CFM) (PA) (PA)

EXF-01 4150 4150 250 307

EXF-02 2850 2850 250 278

EXF-03 1500 1500 250 228

EXF-04 1400 1400 125 109

EXF-06 1000 1000 250 184

EXF-07 850 850 250 153

EXF-08 750 750 125 94

EXF-09 600 600 125 151

EXF-10 500 500 125 92

EXF-11 450 450 125 160

EXF-12 430 430 62 88

EXF-13 400 400 62 94

EXF-14 330 330 125 133

FAF-01 8150 8150 250 265


Fans Design Schedule
Fans Pressure
Drop Calculation
EXF 01
Calculation Sheet
External Static Pressure calculations

Project: NORTH COAST PALACE


MEP contractor : MAGNA ENGINEERING & CONSTRUCTION
Builing Name: MAIN VILLA
FAN TAG EF-01

GENERAL DATA
DUCT MATERIAL: G. I. Sheet
AIR DENSITY:(Kg/m3) 1.2

SECTION (1-1') (2-2') (3-3') (4-4') (5-5') (6-6') (7-7') (8-8') (9-9') (10-10') TOTAL
CFM 75 150 225 375 525 600 1425 2625 3675 4125

FLOW L/S 35 71 106 177 248 283 673 1239 1734 1947

M3/H 127 255 382 637 892 1019 2421 4460 6244 7008

LENGTH M 1.7 1.5 1.0 3.5 10.0 11.0 7.0 5.5 8.0 9.0

DIAM. mm 152 189 219 244 273 299 381 506 592 592

DIAM. EQUIV. mm 152 189 219 244 273 299 381 506 592 592

WIDTH mm 200 200 200 200 250 250 500 750 750 750

HEIGHT mm 100 150 200 250 250 300 250 300 400 400

AREA M2 0.018 0.028 0.038 0.047 0.059 0.070 0.114 0.201 0.275 0.275

VELOCITY M/S 1.94 2.53 2.83 3.78 4.22 4.03 5.90 6.17 6.31 7.08

PD per Meter Pa 0.44 0.54 0.56 0.83 0.88 0.72 1.08 0.83 0.71 0.88

PD x LENGTH Pa 0.74 0.81 0.56 2.89 8.80 7.96 7.55 4.56 5.70 7.91 47

PA (1-1') (2-2') (3-3') (4-4') (5-5') (6-6') (7-7') (8-8') (9-9') (10-10') TOTAL

Tee Branch 3 1
Transition 1 1
Tee Main 2 1
Transition 1 1
Tee Main 2 1
Tee Branch 3 1
Tee Branch 6 1
Tee Branch 8 1
Transition 2 1
Tee Main 11 1
Elbow 90 9 2
Tee Branch 12 1
Tee Main 9 1
Tee Main 1 1
Tee Main 7 1
Tee Main 3 1
Elbow 90 13 2
Transition 8 1
TOTAL PA 4 3 5 6 8 2 41 10 7 37 123

DUCTS PD Pa 4 3 5 6 8 2 41 10 7 37 123

PRESSURE DROP Pa 5 4 6 9 17 10 49 15 13 45 170

SPECIAL FITTING PRESSURE DROPS

DESIGNATION PD (PA) QTY TOTAL

Canvas 5 1 5 FLOW AT 100% (m3/hr) 7008

Disk Valve 15 1 15 * DUCTS PRESSURE DROP : 170

Volume damper (3) 5 1 5 * FITTING PRESSURE DROP : 109

Volume damper (4) 6 1 6 STATIC PRESSURE AT 100% PA 279

Volume damper (5) 10 1 10 *TOTAL EXTERNAL STATIC PRESSURE + 10% SF PA 307

Fire Damper (8) 18 1 18 STATIC PRESSURE AT 100%(in) 1.12

Fire Damper (10) 25 1 25 *TOTAL EXTERNAL STATIC PRESSURE + 15% SF (in) 1.23

Back Draft Damper 25 1 25

TOTAL 109
Drawing
Duct Fittings
Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER5-2) Tee, Round Tap to Rectangular Main [Ab/As=Ab/Ac=0.5; As/Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 100 Branch


Width (W, mm) 200 BranchVelocity (Vb, m/s) 2.0
Diameter (Db, mm) 150 Vel Pres at Vb (Pvb, Pa) 2
Flow Rate (Qs, L/s) 5 Loss Coefficient (Cb) 1.47
Flow Rate (Qb, L/s) 35 Branch Pressure Loss (Pa) 3
Density (kg/m^3) 1.204 Main
MainVelocity (Vs, m/s) 0.3
Velocity (Vc, m/s) 2.0
Vel Pres at Vs (Pvs, Pa) 0
Vel Pres at Vc (Pvc, Pa) 2
Loss Coefficient (Cs) 19.59
Main Pressure Loss (Pa) 1

01/22/2023 d:\project\ncp\static\ef-01\ef-01-01.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER4-1) Transition, Rectangular, Two Sides Parallel, Symmetrical,


Exhaust/Return Systems (Idelchik 1986, Diagram 5-5)

INPUTS OUTPUTS

Height (Ho, mm) 100 Angle (Theta, deg.) 10


Width (Wo, mm) 200 Velocity (Vo, m/s) 1.8
Height (H1, mm) 150 Velocity (V1, m/s) 1.2
Length (L, mm) 300 Vel Pres at Vo (Pvo, Pa) 2
Flow Rate (Q, L/s) 35 Vel Pres at V1 (Pv1, Pa) 1
Density (kg/m^3) 1.204 Loss Coefficient (Co) 0.10
Loss Coefficient (C1) 0.22
Pressure Loss (Pa) 0

01/22/2023 d:\project\ncp\static\ef-01\ef-01-01.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER5-2) Tee, Round Tap to Rectangular Main [Ab/As=Ab/Ac=0.5; As/Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 150 Branch


Width (W, mm) 200 BranchVelocity (Vb, m/s) 2.0
Diameter (Db, mm) 150 Vel Pres at Vb (Pvb, Pa) 2
Flow Rate (Qs, L/s) 35 Loss Coefficient (Cb) 1.03
Flow Rate (Qb, L/s) 35 Branch Pressure Loss (Pa) 2
Density (kg/m^3) 1.204 Main
MainVelocity (Vs, m/s) 1.2
Velocity (Vc, m/s) 2.3
Vel Pres at Vs (Pvs, Pa) 1
Vel Pres at Vc (Pvc, Pa) 3
Loss Coefficient (Cs) 2.23
Main Pressure Loss (Pa) 2

01/22/2023 d:\project\ncp\static\ef-01\ef-01-01.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER4-1) Transition, Rectangular, Two Sides Parallel, Symmetrical,


Exhaust/Return Systems (Idelchik 1986, Diagram 5-5)

INPUTS OUTPUTS

Height (Ho, mm) 150 Angle (Theta, deg.) 10


Width (Wo, mm) 200 Velocity (Vo, m/s) 2.4
Height (H1, mm) 200 Velocity (V1, m/s) 1.8
Length (L, mm) 300 Vel Pres at Vo (Pvo, Pa) 3
Flow Rate (Q, L/s) 71 Vel Pres at V1 (Pv1, Pa) 2
Density (kg/m^3) 1.204 Loss Coefficient (Co) 0.07
Loss Coefficient (C1) 0.13
Pressure Loss (Pa) 0

01/22/2023 d:\project\ncp\static\ef-01\ef-01-01.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER5-2) Tee, Round Tap to Rectangular Main [Ab/As=Ab/Ac=0.5; As/Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 200 Branch


Width (W, mm) 200 BranchVelocity (Vb, m/s) 2.0
Diameter (Db, mm) 150 Vel Pres at Vb (Pvb, Pa) 2
Flow Rate (Qs, L/s) 71 Loss Coefficient (Cb) 0.55
Flow Rate (Qb, L/s) 35 Branch Pressure Loss (Pa) 1
Density (kg/m^3) 1.204 Main
MainVelocity (Vs, m/s) 1.8
Velocity (Vc, m/s) 2.7
Vel Pres at Vs (Pvs, Pa) 2
Vel Pres at Vc (Pvc, Pa) 4
Loss Coefficient (Cs) 0.93
Main Pressure Loss (Pa) 2

01/22/2023 d:\project\ncp\static\ef-01\ef-01-01.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 250 Branch


Width (W, mm) 200 BranchVelocity (Vb, m/s) 2.7
Height (Hb, mm) 200 Vel Pres at Vb (Pvb, Pa) 4
Width (Wb, mm) 200 Loss Coefficient (Cb) 0.75
Flow Rate (Qs, L/s) 71 Branch Pressure Loss (Pa) 3
Flow Rate (Qb, L/s) 106 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 1.4
Velocity (Vc, m/s) 3.5
Vel Pres at Vs (Pvs, Pa) 1
Vel Pres at Vc (Pvc, Pa) 8
Loss Coefficient (Cs) 3.72
Main Pressure Loss (Pa) 5

01/22/2023 d:\project\ncp\static\ef-01\ef-01.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 250 Branch


Width (W, mm) 250 BranchVelocity (Vb, m/s) 3.5
Height (Hb, mm) 250 Vel Pres at Vb (Pvb, Pa) 8
Width (Wb, mm) 200 Loss Coefficient (Cb) 0.84
Flow Rate (Qs, L/s) 71 Branch Pressure Loss (Pa) 6
Flow Rate (Qb, L/s) 177 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 1.1
Velocity (Vc, m/s) 4.0
Vel Pres at Vs (Pvs, Pa) 1
Vel Pres at Vc (Pvc, Pa) 9
Loss Coefficient (Cs) 7.28
Main Pressure Loss (Pa) 6

01/22/2023 d:\project\ncp\static\ef-01\ef-01.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 300 Branch


Width (W, mm) 250 BranchVelocity (Vb, m/s) 4.0
Height (Hb, mm) 250 Vel Pres at Vb (Pvb, Pa) 9
Width (Wb, mm) 250 Loss Coefficient (Cb) 0.82
Flow Rate (Qs, L/s) 35 Branch Pressure Loss (Pa) 8
Flow Rate (Qb, L/s) 248 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 0.5
Velocity (Vc, m/s) 3.8
Vel Pres at Vs (Pvs, Pa) 0
Vel Pres at Vc (Pvc, Pa) 9
Loss Coefficient (Cs) 19.73
Main Pressure Loss (Pa) 3

01/22/2023 d:\project\ncp\static\ef-01\ef-01.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER4-2) Transition, Pyramidal, Exhaust/Return Systems


(Idelchik 1986, Diagram 5-4)

INPUTS OUTPUTS

Height (Ho, mm) 300 Angle (Theta1, deg.) 24


Width (Wo, mm) 250 Angle (Theta2, deg.) 5
Height (H1, mm) 250 Velocity (Vo, m/s) 3.8
Width (W1, mm) 500 Velocity (V1, m/s) 2.3
Length (L, mm) 600 Vel Pres at Vo (Pvo, Pa) 9
Flow Rate (Q, L/s) 283 Vel Pres at V1 (Pv1, Pa) 3
Density (kg/m^3) 1.204 Loss Coefficient (Co) 0.21
Loss Coefficient (C1) 0.59
Pressure Loss (Pa) 2

01/22/2023 d:\project\ncp\static\ef-01\ef-01.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 250 Branch


Width (W, mm) 500 BranchVelocity (Vb, m/s) 4.5
Height (Hb, mm) 250 Vel Pres at Vb (Pvb, Pa) 12
Width (Wb, mm) 350 Loss Coefficient (Cb) 0.73
Flow Rate (Qs, L/s) 283 Branch Pressure Loss (Pa) 9
Flow Rate (Qb, L/s) 390 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 2.3
Velocity (Vc, m/s) 5.4
Vel Pres at Vs (Pvs, Pa) 3
Vel Pres at Vc (Pvc, Pa) 17
Loss Coefficient (Cs) 3.43
Main Pressure Loss (Pa) 11

01/22/2023 d:\project\ncp\static\ef-01\ef-01.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(CR3-1) Elbow, Smooth Radius without Vanes


(Idelchik 1986, Diagram 6-1)

INPUTS OUTPUTS

Width (W, mm) 500 Velocity (Vo, m/s) 5.4


Height (H, mm) 250 Vel Pres at Vo (Pv, Pa) 17
Radius Ratio (r/W) 0.8 Loss Coefficient (Co) 0.47
Angle (Theta, deg.) 90 Pressure Loss (Pa) 8
Flow Rate (Q, L/s) 673
Density (kg/m^3) 1.204

01/22/2023 d:\project\ncp\static\ef-01\ef-01.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 300 Branch


Width (W, mm) 750 BranchVelocity (Vb, m/s) 5.4
Height (Hb, mm) 250 Vel Pres at Vb (Pvb, Pa) 17
Width (Wb, mm) 500 Loss Coefficient (Cb) 0.70
Flow Rate (Qs, L/s) 566 Branch Pressure Loss (Pa) 12
Flow Rate (Qb, L/s) 673 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 2.5
Velocity (Vc, m/s) 5.5
Vel Pres at Vs (Pvs, Pa) 4
Vel Pres at Vc (Pvc, Pa) 18
Loss Coefficient (Cs) 2.88
Main Pressure Loss (Pa) 11

01/22/2023 d:\project\ncp\static\ef-01\ef-01.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 300 Branch


Width (W, mm) 750 BranchVelocity (Vb, m/s) 4.0
Height (Hb, mm) 250 Vel Pres at Vb (Pvb, Pa) 9
Width (Wb, mm) 500 Loss Coefficient (Cb) 0.48
Flow Rate (Qs, L/s) 744 Branch Pressure Loss (Pa) 5
Flow Rate (Qb, L/s) 496 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 3.3
Velocity (Vc, m/s) 5.5
Vel Pres at Vs (Pvs, Pa) 7
Vel Pres at Vc (Pvc, Pa) 18
Loss Coefficient (Cs) 1.33
Main Pressure Loss (Pa) 9

01/22/2023 d:\project\ncp\static\ef-01\ef-01.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 300 Branch


Width (W, mm) 750 BranchVelocity (Vb, m/s) 2.4
Height (Hb, mm) 150 Vel Pres at Vb (Pvb, Pa) 3
Width (Wb, mm) 200 Loss Coefficient (Cb) -1,167.71
Flow Rate (Qs, L/s) 1168 Branch Pressure Loss (Pa) -3,938
Flow Rate (Qb, L/s) 71 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 5.2
Velocity (Vc, m/s) 5.5
Vel Pres at Vs (Pvs, Pa) 16
Vel Pres at Vc (Pvc, Pa) 18
Loss Coefficient (Cs) 0.06
Main Pressure Loss (Pa) 1

01/22/2023 d:\project\ncp\static\ef-01\ef-01.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 400 Branch


Width (W, mm) 750 BranchVelocity (Vb, m/s) 4.1
Height (Hb, mm) 300 Vel Pres at Vb (Pvb, Pa) 10
Width (Wb, mm) 400 Loss Coefficient (Cb) -1.16
Flow Rate (Qs, L/s) 1238 Branch Pressure Loss (Pa) -12
Flow Rate (Qb, L/s) 496 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 4.1
Velocity (Vc, m/s) 5.8
Vel Pres at Vs (Pvs, Pa) 10
Vel Pres at Vc (Pvc, Pa) 20
Loss Coefficient (Cs) 0.71
Main Pressure Loss (Pa) 7

01/22/2023 d:\project\ncp\static\ef-01\ef-01.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 400 Branch


Width (W, mm) 750 BranchVelocity (Vb, m/s) 3.4
Height (Hb, mm) 250 Vel Pres at Vb (Pvb, Pa) 7
Width (Wb, mm) 250 Loss Coefficient (Cb) -17.99
Flow Rate (Qs, L/s) 1735 Branch Pressure Loss (Pa) -125
Flow Rate (Qb, L/s) 212 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 5.8
Velocity (Vc, m/s) 6.5
Vel Pres at Vs (Pvs, Pa) 20
Vel Pres at Vc (Pvc, Pa) 25
Loss Coefficient (Cs) 0.12
Main Pressure Loss (Pa) 3

01/22/2023 d:\project\ncp\static\ef-01\ef-01.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(CR3-1) Elbow, Smooth Radius without Vanes


(Idelchik 1986, Diagram 6-1)

INPUTS OUTPUTS

Width (W, mm) 750 Velocity (Vo, m/s) 6.5


Height (H, mm) 400 Vel Pres at Vo (Pv, Pa) 25
Radius Ratio (r/W) 0.8 Loss Coefficient (Co) 0.46
Angle (Theta, deg.) 90 Pressure Loss (Pa) 12
Flow Rate (Q, L/s) 1947
Density (kg/m^3) 1.204

01/22/2023 d:\project\ncp\static\ef-01\ef-01.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER4-3) Transition, Rectangular to Round, Exhaust/Return Systems


(Idelchik 1986, Diagram 5-27)

INPUTS OUTPUTS

Height (Ho, mm) 400 Angle (Theta1, deg.) 0


Width (Wo, mm) 750 Angle (Theta2, deg.) 33
Diameter (D1, mm) 400 Velocity (Vo, m/s) 6.5
Length (L, mm) 600 Velocity (V1, m/s) 15.5
Flow Rate (Q, L/s) 1947 Vel Pres at Vo (Pvo, Pa) 25
Density (kg/m^3) 1.204 Vel Pres at V1 (Pv1, Pa) 145
Loss Coefficient (Co) 0.31
Loss Coefficient (C1) 0.05
Pressure Loss (Pa) 8

01/22/2023 d:\project\ncp\static\ef-01\ef-01.adf version: 6.00.04


Duct Accessories
Disk Valve
Return air

Neck position Air flow rate


Size in of disc CFM 10 20 40 60 80 100 150 200
Inches M 0.005 0.0094 0.0189 0.0283 0.0378 0.0472 0.071 0.094
P 0.4 <0.4 1.63 3.8 5.8 9.7
Max NC 20 <20 <20 23 31 37 ……. …….
P 0.4 0.76 2.5 5.6 9.7 14.7
4
MED. NC 20 <20 <20 30 35 45 ……. …….
P 0.61 2.24 7.6 15.2 >20 >20
MIN.
NC 20 <20 35 40 >45 >45 ……. …….
P 0.4 <0.4 0.71 1.42 4.1 4.1 9.7
Max NC 20 <20 <20 <20 25 25 37 …….
P 0.4 <0.4 1.83 4.1 11.2 11.2 20
5
MED. NC 20 <20 <20 21 35 35 >45 …….
P 0.4 2.1 7.1 16.8 >20 >20 20
MIN.
NC 20 <20 23 35 >45 >45 >45 …….
P 0.4 <0.4 0.4 0.81 1.43 2.1 5.2 9.7
Max NC 20 <20 <20 <20 <20 <20 28 37
P 0.4 <0.4 0.81 1.74 3.4 5.3 12.2 20
6
MED. NC 20 <20 <20 <20 <20 25 37 45
P 0.4 0.5 1.47 3.8 7.6 14.7 20 20
MIN.
NC 20 <20 <20 <20 27 35 >45 45
P 0.4 <0.4 <0.4 <0.4 0.76 1.12 2.6 4.38
Max NC 20 <20 <20 <20 <20 <20 27 34
P 0.4 <0.4 0.7 1.4 2.3 3.4 8.4 12.2
8
MED. NC 20 <20 <20 <20 <20 20 35 42
P 0.4 0.5 1.62 3.4 7.1 11.2 20 20
MIN.
NC 20 <20 <20 <20 <20 34 >45 45

Where :
P the pressure drop in mm of water
NC based on room attenuation of 10dB
VOLUME DAMPER 03
VOLUME DAMPER 04
VOLUME DAMPER 05
Fire Damper 8
Fire Damper 10
Back Draft Damper
SUGGESTED SPECIFICATION
Furnish and install, at locations shown on plans or in accordance resistant, long life synthetic type for quiet operation. Linkage shall
with schedules, heavy duty backdraft dampers that meet the follow- be 1 /2 " (13) wide tiebar connected to stainless steel pivot
ing minimum construction standards: Frame shall be .125" (3.2) pins. Dampers shall be designed for maximum 3500 fpm spot
wall thickness 6063T5 extruded aluminum with 12 gage (2.8) gal- velocities and minimum 4 inches w.g. back pressure depending on
vanized steel structural brace at each corner. Blades shall be .070" damper size. Dampers shall be in all respects equivalent to
(1.8) wall thickness 6063T5 extruded aluminum with extruded vinyl Ruskin model CBD6.
blade edge seals mechanically locked into blade edge. Adhesive or
clip on type seals are unacceptable. Bearings shall be
corrosion
INSTALLATION

1. When used in fan discharge applications, damper should 3. Bracing of multiple section assemblies:
be located at least one-half the fan diameter away from the fan. The CBD6 is intended to be self supporting only in the largest
single section size. Multiple section damper assemblies
2. For proper operation, damper must be installed square and free may require bracing to support the weight of the assembly
from racking. and to hold against system pressure. Ruskin recommends
appropriate bracing to support the damper horizontally at
least once for every 8 feet of damper width. Vertical
assemblies and higher system pressures may require more
PERFORMANCE DATA bracing.

DAMPER PERFORMANCE
LEAKAGE* BLADES BLADES
MAXIMUM MAXIMUM SYSTEM
DAMPER WIDTH Percent of CFM/ START TO FULLY
BACK PRESSURE VELOCITY
Max. Flow Sq. Ft. OPEN OPEN

48" (1219) 4.0" w.g. 2500 FPM .6% 15


36" (914) 8.0" w.g. 2500 FPM .6% 15 .01" w.g. .05" w.g.
24" (610) 12.0" w.g. 2500 FPM .7% 17.5
12" (305) 16.0" w.g. 2500 PFM 1% 25

*Leakage information based on pressure differential of 1" w.g. tested per AMCA Std. 500.

DAMPER PRESSURE DROP


(24" x 24")
p p ( [ ] )
0.7
17.78
0.5
12.7
Static Pressure Drop in INCHES and MILLIMETERS of WATER

0.3
7.62

0.2
5.08

0.1
2.54
.07
1.78

.05
1.27

.03
.75

.02
.51

.01
200 300 500 700 1000 2000 3000
60.96 91.44 152.40 213.36 304.80 609.60 914.40

Air velocity in FEET and Meters Per minute through face area
EXF 0
Calculation Sheet
External Static Pressure calculations

Project: NORTH COAST PALACE


MEP contractor : MAGNA ENGINEERING & CONSTRUCTION
Builing Name: MAIN VILLA
FAN TAG EF-02

GENERAL DATA
DUCT MATERIAL: G. I. Sheet
AIR DENSITY:(Kg/m3) 1.2

SECTION (1-1') (2-2') (3-3') (4-4') (5-5') (6-6') (7-7') (8-8') (9-9') TOTAL
CFM 75 150 300 375 525 600 1190 1990 2850

FLOW L/S 35 71 142 177 248 283 562 939 1345

M3/H 127 255 510 637 892 1019 2022 3381 4842

LENGTH M 1.7 1.0 3.0 1.5 3.0 20.0 27.0 4.5 8.0

DIAM. mm 152 189 219 244 273 299 378 378 455

DIAM. EQUIV. mm 152 189 219 244 273 299 378 378 455

WIDTH mm 200 200 200 250 250 300 400 400 500

HEIGHT mm 100 150 200 200 250 250 300 300 350

AREA M2 0.018 0.028 0.038 0.047 0.059 0.070 0.112 0.112 0.163

VELOCITY M/S 1.94 2.53 3.77 3.78 4.22 4.03 5.01 8.38 8.25

PD per Meter Pa 0.44 0.54 0.94 0.83 0.88 0.72 0.81 2.06 1.60

PD x LENGTH Pa 0.74 0.54 2.82 1.24 2.64 14.48 21.85 9.28 12.77 66

PA (1-1') (2-2') (3-3') (4-4') (5-5') (6-6') (7-7') (8-8') (9-9') TOTAL

Tee Branch (1) 1 1


Elbow 90 (1) 1 1
Transition (1) 1 1
Tee Main (2) 2 1
Tee Branch (3) 3 1
Tee Main (3.1) 2 1
Tee Main (3.2) 3 1
Transition (3) 1 1
Tee Main (4) 2 1
Transition (4) 1 1
Tee Main (5.1) 1 1
Tee Main (5.2) 2 1
Tee Main (5.3) 2 1
Tee Branch (6) 11 1
Elbow 90 (6) 5 3
Tee Branch (7) 9 1
Elbow 90 (7.1) 5 1
Tee Main (7) 1 1
Elbow 90 (7.2) 6 1
Transition (7) 2 1
Tee Main (8) 8 1
Transition (8) 2 1
Tee Main (9) 8 1
Elbow 90 (9) 10 1
Elbow 45 (9) 6 2
Rect. To Round (9) 1 1
TOTAL PA 3 2 9 3 5 26 23 10 31 0 112

DUCTS PD Pa 3 2 9 3 5 26 23 10 31 0 112

PRESSURE DROP Pa 4 3 12 4 8 40 45 19 44 0 178

SPECIAL FITTING PRESSURE DROPS

DESIGNATION PD (PA) QTY TOTAL


Canvas 5 1 5 FLOW AT 100% (m3/hr) 4842
Disk Valve 14 1 14 * DUCTS PRESSURE DROP : 178
Volume damper (2) 5 1 5 * FITTING PRESSURE DROP : 74

Volume damper (5) 10 1 10 STATIC PRESSURE AT 100% PA 252


Fire Damper (8) 23 1 23 *TOTAL EXTERNAL STATIC PRESSURE + 10% SF PA 278
Back Draft Damper 18 1 18 STATIC PRESSURE AT 100%(in) 1.01
*TOTAL EXTERNAL STATIC PRESSURE + 10% SF (in) 1.11

TOTAL 74
Drawing
Duct Fittings
Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 100 Branch


Width (W, mm) 200 BranchVelocity (Vb, m/s) 1.6
Height (Hb, mm) 150 Vel Pres at Vb (Pvb, Pa) 2
Width (Wb, mm) 150 Loss Coefficient (Cb) 0.78
Flow Rate (Qs, L/s) 10 Branch Pressure Loss (Pa) 1
Flow Rate (Qb, L/s) 36 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 0.5
Velocity (Vc, m/s) 2.3
Vel Pres at Vs (Pvs, Pa) 0
Vel Pres at Vc (Pvc, Pa) 3
Loss Coefficient (Cs) 10.98
Main Pressure Loss (Pa) 2

01/22/2023 d:\hat project\ncp\calculations\exhaust fan\ef-02\ef-02.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(CR3-1) Elbow, Smooth Radius without Vanes


(Idelchik 1986, Diagram 6-1)

INPUTS OUTPUTS

Width (W, mm) 200 Velocity (Vo, m/s) 1.8


Height (H, mm) 100 Vel Pres at Vo (Pv, Pa) 2
Radius Ratio (r/W) 0.8 Loss Coefficient (Co) 0.47
Angle (Theta, deg.) 90 Pressure Loss (Pa) 1
Flow Rate (Q, L/s) 36
Density (kg/m^3) 1.204

01/22/2023 d:\hat project\ncp\calculations\exhaust fan\ef-02\ef-02.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER4-2) Transition, Pyramidal, Exhaust/Return Systems


(Idelchik 1986, Diagram 5-4)

INPUTS OUTPUTS

Height (Ho, mm) 100 Angle (Theta1, deg.) 0


Width (Wo, mm) 200 Angle (Theta2, deg.) 7
Height (H1, mm) 150 Velocity (Vo, m/s) 1.8
Width (W1, mm) 200 Velocity (V1, m/s) 1.2
Length (L, mm) 400 Vel Pres at Vo (Pvo, Pa) 2
Flow Rate (Q, L/s) 36 Vel Pres at V1 (Pv1, Pa) 1
Density (kg/m^3) 1.204 Loss Coefficient (Co) 0.10
Loss Coefficient (C1) 0.22
Pressure Loss (Pa) 0

01/22/2023 d:\hat project\ncp\calculations\exhaust fan\ef-02\ef-02.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 150 Branch


Width (W, mm) 200 BranchVelocity (Vb, m/s) 1.6
Height (Hb, mm) 150 Vel Pres at Vb (Pvb, Pa) 2
Width (Wb, mm) 150 Loss Coefficient (Cb) 0.66
Flow Rate (Qs, L/s) 36 Branch Pressure Loss (Pa) 1
Flow Rate (Qb, L/s) 36 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 1.2
Velocity (Vc, m/s) 2.4
Vel Pres at Vs (Pvs, Pa) 1
Vel Pres at Vc (Pvc, Pa) 3
Loss Coefficient (Cs) 2.23
Main Pressure Loss (Pa) 2

01/22/2023 d:\hat project\ncp\calculations\exhaust fan\ef-02\ef-02.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 200 Branch


Width (W, mm) 200 BranchVelocity (Vb, m/s) 2.4
Height (Hb, mm) 150 Vel Pres at Vb (Pvb, Pa) 3
Width (Wb, mm) 200 Loss Coefficient (Cb) 0.82
Flow Rate (Qs, L/s) 10 Branch Pressure Loss (Pa) 3
Flow Rate (Qb, L/s) 72 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 0.3
Velocity (Vc, m/s) 2.1
Vel Pres at Vs (Pvs, Pa) 0
Vel Pres at Vc (Pvc, Pa) 3
Loss Coefficient (Cs) 19.90
Main Pressure Loss (Pa) 1

01/22/2023 d:\hat project\ncp\calculations\exhaust fan\ef-02\ef-02.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 200 Branch


Width (W, mm) 200 BranchVelocity (Vb, m/s) 1.2
Height (Hb, mm) 150 Vel Pres at Vb (Pvb, Pa) 1
Width (Wb, mm) 200 Loss Coefficient (Cb) -0.33
Flow Rate (Qs, L/s) 72 Branch Pressure Loss (Pa) 0
Flow Rate (Qb, L/s) 36 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 1.8
Velocity (Vc, m/s) 2.7
Vel Pres at Vs (Pvs, Pa) 2
Vel Pres at Vc (Pvc, Pa) 4
Loss Coefficient (Cs) 0.95
Main Pressure Loss (Pa) 2

01/22/2023 d:\hat project\ncp\calculations\exhaust fan\ef-02\ef-02.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 200 Branch


Width (W, mm) 200 BranchVelocity (Vb, m/s) 1.2
Height (Hb, mm) 150 Vel Pres at Vb (Pvb, Pa) 1
Width (Wb, mm) 200 Loss Coefficient (Cb) -2.25
Flow Rate (Qs, L/s) 108 Branch Pressure Loss (Pa) -2
Flow Rate (Qb, L/s) 36 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 2.7
Velocity (Vc, m/s) 3.6
Vel Pres at Vs (Pvs, Pa) 4
Vel Pres at Vc (Pvc, Pa) 8
Loss Coefficient (Cs) 0.57
Main Pressure Loss (Pa) 3

01/22/2023 d:\hat project\ncp\calculations\exhaust fan\ef-02\ef-02.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER4-2) Transition, Pyramidal, Exhaust/Return Systems


(Idelchik 1986, Diagram 5-4)

INPUTS OUTPUTS

Height (Ho, mm) 200 Angle (Theta1, deg.) 7


Width (Wo, mm) 200 Angle (Theta2, deg.) 0
Height (H1, mm) 200 Velocity (Vo, m/s) 3.6
Width (W1, mm) 250 Velocity (V1, m/s) 2.9
Length (L, mm) 400 Vel Pres at Vo (Pvo, Pa) 8
Flow Rate (Q, L/s) 144 Vel Pres at V1 (Pv1, Pa) 5
Density (kg/m^3) 1.204 Loss Coefficient (Co) 0.06
Loss Coefficient (C1) 0.09
Pressure Loss (Pa) 0

01/22/2023 d:\hat project\ncp\calculations\exhaust fan\ef-02\ef-02.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 200 Branch


Width (W, mm) 250 BranchVelocity (Vb, m/s) 1.8
Height (Hb, mm) 100 Vel Pres at Vb (Pvb, Pa) 2
Width (Wb, mm) 200 Loss Coefficient (Cb) -3.75
Flow Rate (Qs, L/s) 144 Branch Pressure Loss (Pa) -7
Flow Rate (Qb, L/s) 36 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 2.9
Velocity (Vc, m/s) 3.6
Vel Pres at Vs (Pvs, Pa) 5
Vel Pres at Vc (Pvc, Pa) 8
Loss Coefficient (Cs) 0.38
Main Pressure Loss (Pa) 2

01/22/2023 d:\hat project\ncp\calculations\exhaust fan\ef-02\ef-02.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER4-2) Transition, Pyramidal, Exhaust/Return Systems


(Idelchik 1986, Diagram 5-4)

INPUTS OUTPUTS

Height (Ho, mm) 200 Angle (Theta1, deg.) 0


Width (Wo, mm) 250 Angle (Theta2, deg.) 7
Height (H1, mm) 250 Velocity (Vo, m/s) 3.6
Width (W1, mm) 250 Velocity (V1, m/s) 2.9
Length (L, mm) 400 Vel Pres at Vo (Pvo, Pa) 8
Flow Rate (Q, L/s) 180 Vel Pres at V1 (Pv1, Pa) 5
Density (kg/m^3) 1.204 Loss Coefficient (Co) 0.06
Loss Coefficient (C1) 0.09
Pressure Loss (Pa) 0

01/22/2023 d:\hat project\ncp\calculations\exhaust fan\ef-02\ef-02.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 250 Branch


Width (W, mm) 250 BranchVelocity (Vb, m/s) 1.8
Height (Hb, mm) 100 Vel Pres at Vb (Pvb, Pa) 2
Width (Wb, mm) 200 Loss Coefficient (Cb) -8.96
Flow Rate (Qs, L/s) 180 Branch Pressure Loss (Pa) -17
Flow Rate (Qb, L/s) 36 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 2.9
Velocity (Vc, m/s) 3.5
Vel Pres at Vs (Pvs, Pa) 5
Vel Pres at Vc (Pvc, Pa) 7
Loss Coefficient (Cs) 0.29
Main Pressure Loss (Pa) 1

01/22/2023 d:\hat project\ncp\calculations\exhaust fan\ef-02\ef-02.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 250 Branch


Width (W, mm) 250 BranchVelocity (Vb, m/s) 1.6
Height (Hb, mm) 150 Vel Pres at Vb (Pvb, Pa) 2
Width (Wb, mm) 150 Loss Coefficient (Cb) -12.68
Flow Rate (Qs, L/s) 216 Branch Pressure Loss (Pa) -20
Flow Rate (Qb, L/s) 36 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 3.5
Velocity (Vc, m/s) 4.0
Vel Pres at Vs (Pvs, Pa) 7
Vel Pres at Vc (Pvc, Pa) 10
Loss Coefficient (Cs) 0.22
Main Pressure Loss (Pa) 2

01/22/2023 d:\hat project\ncp\calculations\exhaust fan\ef-02\ef-02.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 250 Branch


Width (W, mm) 250 BranchVelocity (Vb, m/s) 1.6
Height (Hb, mm) 150 Vel Pres at Vb (Pvb, Pa) 2
Width (Wb, mm) 150 Loss Coefficient (Cb) -15.47
Flow Rate (Qs, L/s) 252 Branch Pressure Loss (Pa) -24
Flow Rate (Qb, L/s) 36 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 4.0
Velocity (Vc, m/s) 4.6
Vel Pres at Vs (Pvs, Pa) 10
Vel Pres at Vc (Pvc, Pa) 13
Loss Coefficient (Cs) 0.17
Main Pressure Loss (Pa) 2

01/22/2023 d:\hat project\ncp\calculations\exhaust fan\ef-02\ef-02.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 250 Branch


Width (W, mm) 300 BranchVelocity (Vb, m/s) 4.6
Height (Hb, mm) 250 Vel Pres at Vb (Pvb, Pa) 13
Width (Wb, mm) 250 Loss Coefficient (Cb) 0.82
Flow Rate (Qs, L/s) 36 Branch Pressure Loss (Pa) 11
Flow Rate (Qb, L/s) 288 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 0.5
Velocity (Vc, m/s) 4.3
Vel Pres at Vs (Pvs, Pa) 0
Vel Pres at Vc (Pvc, Pa) 11
Loss Coefficient (Cs) 21.01
Main Pressure Loss (Pa) 3

01/22/2023 d:\hat project\ncp\calculations\exhaust fan\ef-02\ef-02.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(CR3-1) Elbow, Smooth Radius without Vanes


(Idelchik 1986, Diagram 6-1)

INPUTS OUTPUTS

Width (W, mm) 300 Velocity (Vo, m/s) 4.3


Height (H, mm) 250 Vel Pres at Vo (Pv, Pa) 11
Radius Ratio (r/W) 0.8 Loss Coefficient (Co) 0.42
Angle (Theta, deg.) 90 Pressure Loss (Pa) 5
Flow Rate (Q, L/s) 324
Density (kg/m^3) 1.204

01/22/2023 d:\hat project\ncp\calculations\exhaust fan\ef-02\ef-02.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 300 Branch


Width (W, mm) 400 BranchVelocity (Vb, m/s) 4.3
Height (Hb, mm) 250 Vel Pres at Vb (Pvb, Pa) 11
Width (Wb, mm) 300 Loss Coefficient (Cb) 0.76
Flow Rate (Qs, L/s) 210 Branch Pressure Loss (Pa) 9
Flow Rate (Qb, L/s) 324 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 1.8
Velocity (Vc, m/s) 4.5
Vel Pres at Vs (Pvs, Pa) 2
Vel Pres at Vc (Pvc, Pa) 12
Loss Coefficient (Cs) 3.93
Main Pressure Loss (Pa) 7

01/22/2023 d:\hat project\ncp\calculations\exhaust fan\ef-02\ef-02.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(CR3-1) Elbow, Smooth Radius without Vanes


(Idelchik 1986, Diagram 6-1)

INPUTS OUTPUTS

Width (W, mm) 400 Velocity (Vo, m/s) 4.5


Height (H, mm) 300 Vel Pres at Vo (Pv, Pa) 12
Radius Ratio (r/W) 0.8 Loss Coefficient (Co) 0.43
Angle (Theta, deg.) 90 Pressure Loss (Pa) 5
Flow Rate (Q, L/s) 534
Density (kg/m^3) 1.204

01/22/2023 d:\hat project\ncp\calculations\exhaust fan\ef-02\ef-02.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 300 Branch


Width (W, mm) 400 BranchVelocity (Vb, m/s) 0.6
Height (Hb, mm) 250 Vel Pres at Vb (Pvb, Pa) 0
Width (Wb, mm) 250 Loss Coefficient (Cb) -986.10
Flow Rate (Qs, L/s) 526 Branch Pressure Loss (Pa) -197
Flow Rate (Qb, L/s) 36 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 4.4
Velocity (Vc, m/s) 4.7
Vel Pres at Vs (Pvs, Pa) 12
Vel Pres at Vc (Pvc, Pa) 13
Loss Coefficient (Cs) 0.06
Main Pressure Loss (Pa) 1

01/22/2023 d:\hat project\ncp\calculations\exhaust fan\ef-02\ef-02.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(CR3-1) Elbow, Smooth Radius without Vanes


(Idelchik 1986, Diagram 6-1)

INPUTS OUTPUTS

Width (W, mm) 400 Velocity (Vo, m/s) 4.7


Height (H, mm) 300 Vel Pres at Vo (Pv, Pa) 13
Radius Ratio (r/W) 0.8 Loss Coefficient (Co) 0.43
Angle (Theta, deg.) 90 Pressure Loss (Pa) 6
Flow Rate (Q, L/s) 562
Density (kg/m^3) 1.204

01/22/2023 d:\hat project\ncp\calculations\exhaust fan\ef-02\ef-02.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER4-2) Transition, Pyramidal, Exhaust/Return Systems


(Idelchik 1986, Diagram 5-4)

INPUTS OUTPUTS

Height (Ho, mm) 300 Angle (Theta1, deg.) 14


Width (Wo, mm) 400 Angle (Theta2, deg.) 7
Height (H1, mm) 350 Velocity (Vo, m/s) 4.7
Width (W1, mm) 500 Velocity (V1, m/s) 3.2
Length (L, mm) 400 Vel Pres at Vo (Pvo, Pa) 13
Flow Rate (Q, L/s) 562 Vel Pres at V1 (Pv1, Pa) 6
Density (kg/m^3) 1.204 Loss Coefficient (Co) 0.13
Loss Coefficient (C1) 0.28
Pressure Loss (Pa) 2

01/22/2023 d:\hat project\ncp\calculations\exhaust fan\ef-02\ef-02.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 350 Branch


Width (W, mm) 500 BranchVelocity (Vb, m/s) 4.3
Height (Hb, mm) 250 Vel Pres at Vb (Pvb, Pa) 11
Width (Wb, mm) 350 Loss Coefficient (Cb) 0.48
Flow Rate (Qs, L/s) 562 Branch Pressure Loss (Pa) 5
Flow Rate (Qb, L/s) 378 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 3.2
Velocity (Vc, m/s) 5.4
Vel Pres at Vs (Pvs, Pa) 6
Vel Pres at Vc (Pvc, Pa) 17
Loss Coefficient (Cs) 1.35
Main Pressure Loss (Pa) 8

01/22/2023 d:\hat project\ncp\calculations\exhaust fan\ef-02\ef-02.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER4-2) Transition, Pyramidal, Exhaust/Return Systems


(Idelchik 1986, Diagram 5-4)

INPUTS OUTPUTS

Height (Ho, mm) 350 Angle (Theta1, deg.) 21


Width (Wo, mm) 500 Angle (Theta2, deg.) 0
Height (H1, mm) 350 Velocity (Vo, m/s) 5.4
Width (W1, mm) 650 Velocity (V1, m/s) 4.1
Length (L, mm) 400 Vel Pres at Vo (Pvo, Pa) 17
Flow Rate (Q, L/s) 940 Vel Pres at V1 (Pv1, Pa) 10
Density (kg/m^3) 1.204 Loss Coefficient (Co) 0.12
Loss Coefficient (C1) 0.20
Pressure Loss (Pa) 2

01/22/2023 d:\hat project\ncp\calculations\exhaust fan\ef-02\ef-02.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 350 Branch


Width (W, mm) 650 BranchVelocity (Vb, m/s) 4.5
Height (Hb, mm) 250 Vel Pres at Vb (Pvb, Pa) 12
Width (Wb, mm) 350 Loss Coefficient (Cb) -0.94
Flow Rate (Qs, L/s) 940 Branch Pressure Loss (Pa) -11
Flow Rate (Qb, L/s) 390 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 4.1
Velocity (Vc, m/s) 5.8
Vel Pres at Vs (Pvs, Pa) 10
Vel Pres at Vc (Pvc, Pa) 21
Loss Coefficient (Cs) 0.73
Main Pressure Loss (Pa) 8

01/22/2023 d:\hat project\ncp\calculations\exhaust fan\ef-02\ef-02.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(CR3-1) Elbow, Smooth Radius without Vanes


(Idelchik 1986, Diagram 6-1)

INPUTS OUTPUTS

Width (W, mm) 650 Velocity (Vo, m/s) 5.9


Height (H, mm) 350 Vel Pres at Vo (Pv, Pa) 21
Radius Ratio (r/W) 0.8 Loss Coefficient (Co) 0.46
Angle (Theta, deg.) 90 Pressure Loss (Pa) 10
Flow Rate (Q, L/s) 1345
Density (kg/m^3) 1.204

01/22/2023 d:\hat project\ncp\calculations\exhaust fan\ef-02\ef-02.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(CR3-1) Elbow, Smooth Radius without Vanes


(Idelchik 1986, Diagram 6-1)

INPUTS OUTPUTS

Width (W, mm) 650 Velocity (Vo, m/s) 5.9


Height (H, mm) 350 Vel Pres at Vo (Pv, Pa) 21
Radius Ratio (r/W) 0.8 Loss Coefficient (Co) 0.28
Angle (Theta, deg.) 45 Pressure Loss (Pa) 6
Flow Rate (Q, L/s) 1345
Density (kg/m^3) 1.204

01/22/2023 d:\hat project\ncp\calculations\exhaust fan\ef-02\ef-02.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER4-3) Transition, Rectangular to Round, Exhaust/Return Systems


(Idelchik 1986, Diagram 5-27)

INPUTS OUTPUTS

Height (Ho, mm) 350 Angle (Theta1, deg.) 28


Width (Wo, mm) 650 Angle (Theta2, deg.) 28
Diameter (D1, mm) 500 Velocity (Vo, m/s) 5.9
Length (L, mm) 300 Velocity (V1, m/s) 6.9
Flow Rate (Q, L/s) 1345 Vel Pres at Vo (Pvo, Pa) 21
Density (kg/m^3) 1.204 Vel Pres at V1 (Pv1, Pa) 28
Loss Coefficient (Co) 0.03
Loss Coefficient (C1) 0.02
Pressure Loss (Pa) 1

01/22/2023 d:\hat project\ncp\calculations\exhaust fan\ef-02\ef-02.adf version: 6.00.04


Duct Accessories
Disk Valve

Return air

Neck position Air flow rate


Size in of disc CFM 10 20 40 60 80 100 150 200
Inches M 0.005 0.0094 0.0189 0.0283 0.0378 0.0472 0.071 0.094
P 0.4 <0.4 1.63 3.8 5.8 9.7
Max NC 20 <20 <20 23 31 37 ……. …….
P 0.4 0.76 2.5 5.6 9.7 14.7
4
MED. NC 20 <20 <20 30 35 45 ……. …….
P 0.61 2.24 7.6 15.2 >20 >20
MIN.
NC 20 <20 35 40 >45 >45 ……. …….
P 0.4 <0.4 0.71 1.42 4.1 4.1 9.7
Max NC 20 <20 <20 <20 25 25 37 …….
P 0.4 <0.4 1.83 4.1 11.2 11.2 20
5
MED. NC 20 <20 <20 21 35 35 >45 …….
P 0.4 2.1 7.1 16.8 >20 >20 20
MIN.
NC 20 <20 23 35 >45 >45 >45 …….
P 0.4 <0.4 0.4 0.81 1.43 2.1 5.2 9.7
Max NC 20 <20 <20 <20 <20 <20 28 37
P 0.4 <0.4 0.81 1.74 3.4 5.3 12.2 20
6
MED. NC 20 <20 <20 <20 <20 25 37 45
P 0.4 0.5 1.47 3.8 7.6 14.7 20 20
MIN.
NC 20 <20 <20 <20 27 35 >45 45
P 0.4 <0.4 <0.4 <0.4 0.76 1.12 2.6 4.38
Max NC 20 <20 <20 <20 <20 <20 27 34
P 0.4 <0.4 0.7 1.4 2.3 3.4 8.4 12.2
8
MED. NC 20 <20 <20 <20 <20 20 35 42
P 0.4 0.5 1.62 3.4 7.1 11.2 20 20
MIN.
NC 20 <20 <20 <20 <20 34 >45 45

Where :
P the pressure drop in mm of water
NC based on room attenuation of 10dB
VOLUME DAMPER 02
VOLUME DAMPER 05
Fire Damper 9
Fire Damper 10
Back Draft Damper
SUGGESTED SPECIFICATION
Furnish and install, at locations shown on plans or in accordance resistant, long life synthetic type for quiet operation. Linkage shall
with schedules, heavy duty backdraft dampers that meet the follow- be 1 /2 " (13) wide tiebar connected to stainless steel pivot
ing minimum construction standards: Frame shall be .125" (3.2) pins. Dampers shall be designed for maximum 3500 fpm spot
wall thickness 6063T5 extruded aluminum with 12 gage (2.8) gal- velocities and minimum 4 inches w.g. back pressure depending on
vanized steel structural brace at each corner. Blades shall be .070" damper size. Dampers shall be in all respects equivalent to
(1.8) wall thickness 6063T5 extruded aluminum with extruded vinyl Ruskin model CBD6.
blade edge seals mechanically locked into blade edge. Adhesive or
clip on type seals are unacceptable. Bearings shall be
corrosion
INSTALLATION

1. When used in fan discharge applications, damper should 3. Bracing of multiple section assemblies:
be located at least one-half the fan diameter away from the fan. The CBD6 is intended to be self supporting only in the largest
single section size. Multiple section damper assemblies
2. For proper operation, damper must be installed square and free may require bracing to support the weight of the assembly
from racking. and to hold against system pressure. Ruskin recommends
appropriate bracing to support the damper horizontally at
least once for every 8 feet of damper width. Vertical
assemblies and higher system pressures may require more
PERFORMANCE DATA bracing.

DAMPER PERFORMANCE
LEAKAGE* BLADES BLADES
MAXIMUM MAXIMUM SYSTEM
DAMPER WIDTH Percent of CFM/ START TO FULLY
BACK PRESSURE VELOCITY
Max. Flow Sq. Ft. OPEN OPEN

48" (1219) 4.0" w.g. 2500 FPM .6% 15


36" (914) 8.0" w.g. 2500 FPM .6% 15 .01" w.g. .05" w.g.
24" (610) 12.0" w.g. 2500 FPM .7% 17.5
12" (305) 16.0" w.g. 2500 PFM 1% 25

*Leakage information based on pressure differential of 1" w.g. tested per AMCA Std. 500.

DAMPER PRESSURE DROP


(24" x 24")
p p ( [ ] )
0.7
17.78
0.5
12.7
Static Pressure Drop in INCHES and MILLIMETERS of WATER

0.3
7.62

0.2
5.08

0.1
2.54
.07
1.78

.05
1.27

.03
.75

.02
.51

.01
200 300 500 700 1000 2000 3000
60.96 91.44 152.40 213.36 304.80 609.60 914.40

Air velocity in FEET and Meters Per minute through face area
EXF 0
Calculation Sheet
External Static Pressure calculations

Project: NORTH COAST PALACE


MEP contractor : MAGNA ENGINEERING & CONSTRUCTION
Builing Name: MAIN VILLA
FAN TAG EF-03

GENERAL DATA
DUCT MATERIAL: G. I. Sheet
AIR DENSITY:(Kg/m3) 1.2

SECTION (1-1') (2-2') (3-3') (4-4') (5-5') (6-6') (7-7') TOTAL


CFM 150 250 325 625 1015 1325 1500
FLOW L/S 71 118 153 295 479 625 708

M3/H 255 425 552 1062 1724 2251 2549

LENGTH M 39.0 2.2 5.6 15.0 5.5 8.0 7.0

DIAM. mm 189 210 244 299 354 383 409

DIAM. EQUIV. mm 189 210 244 299 354 383 409

WIDTH mm 150 250 250 300 350 350 400

HEIGHT mm 200 150 200 250 300 350 350

AREA M2 0.028 0.035 0.047 0.070 0.098 0.115 0.131

VELOCITY M/S 2.53 3.41 3.28 4.20 4.87 5.44 5.39

PD per Meter Pa 0.54 0.82 0.64 0.78 0.83 0.92 0.84

PD x LENGTH Pa 21.14 1.80 3.57 11.69 4.57 7.39 5.88 56

PA (1-1') (2-2') (3-3') (4-4') (5-5') (6-6') (7-7') TOTAL

Plenum Box 1 1
Flexible Duct 9 1
Transition 1 1
Elbow 90 1 4
Elbow 45 1 2
Transition 1 1
Tee main 3 1
Transition 1 1
Tee main 2 1
Transition 1 1
Tee main 1 1
Tee main 4 1
Tee Branch 7 1
Tee main 6 1
Elbow 90 6 1
Transition 1 1
Tee main 5 1
Transition 1 1
Tee main 1 1
Elbow 90 7 1
Transition 1 1

TOTAL PA 18 4 3 12 13 6 9 0 0 0 65

DUCTS PD Pa 18 4 3 12 13 6 9 0 0 0 65

PRESSURE DROP Pa 39 6 7 24 18 13 15 0 0 0 121

SPECIAL FITTING PRESSURE DROPS

`
DESIGNATION PD (PA) QTY TOTAL
Canvas 5 1 5 FLOW AT 100% (m3/hr) 2549

Return slot Diffuser 20 1 20 * DUCTS PRESSURE DROP : 121


Volume damper (1) 10 1 10 * FITTING PRESSURE DROP : 86
Volume damper (4) 8 1 8 STATIC PRESSURE AT 100% PA 207
Fire Damper (5) 13 1 13 *TOTAL EXTERNAL STATIC PRESSURE + 10% SF PA 228
Fire Damper (7) 15 1 15 STATIC PRESSURE AT 100%(in) 0.83
Back Draft Damper 15 1 15 *TOTAL EXTERNAL STATIC PRESSURE + 15% SF (in) 0.91

0
TOTAL 86
Drawing
Duct Fittings
Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER2-1) Bellmouth, Plenum to Round, Exhaust/Return Systems


(Idelchik 1986, Diagram 4-9)

INPUTS OUTPUTS

Diameter (D1, mm) 150 Velocity (Vo, m/s) 0.2


Plenum Height (Ho, mm) 250 Velocity (V1, m/s) 4.0
Plenum Width (Wo, mm) 1200 Vel Pres at Vo (Pvo, Pa) 0
Flow Rate (Q, L/s) 71 Vel Pres at V1 (Pv1, Pa) 10
Density (kg/m^3) 1.204 Bellmouth Radius (r, mm) 50
Loss Coefficient (Co) 8.26
Loss Coefficient (C1) 0.03
Pressure Loss (Pa) 0

01/22/2023 d:\project\ncp\static\ef-03\ef-03-1.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(CD11-2) Straight Duct, Flexible


(Abushakra 2004 and Culp 2011

INPUTS OUTPUTS

Flow Rate (Q, L/s) 71 Velocity (V, m/s) 4.0


Diameter (D, mm) 150 Vel Pres at Vo (Pv, Pa) 10
Installed Length (L, m) 0.4 Compressed (%) 33
Length Fully Extended (m) 0.6 Pressure Drop Correction Factor (PDCF) 10.2
Density (kg/m^3) 1.204 Pressure Loss (Pa) 9

FULLY EXTENDED

LESS THAN FULLY EXTENDED

01/22/2023 d:\project\ncp\static\ef-03\ef-03-1.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(SR4-3) Transition, Round to Rectangular, Supply Air Systems


(Idelchik 1986, Diagram 5-27)

INPUTS OUTPUTS

Diameter (D1, mm) 150 Angle (Theta1, deg.) 10


Height (Ho, mm) 200 Angle (Theta2, deg.) 0
Width (Wo, mm) 150 Velocity (Vo, m/s) 2.4
Length (L, mm) 300 Velocity (V1, m/s) 4.0
Flow Rate (Q, L/s) 71 Vel Pres at Vo (Pvo, Pa) 3
Density (kg/m^3) 1.204 Vel Pres at V1 (Pv1, Pa) 10
Loss Coefficient (Co) 0.42
Loss Coefficient (C1) 0.15
Pressure Loss (Pa) 1

01/22/2023 d:\project\ncp\static\ef-03\ef-03.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(CR3-1) Elbow, Smooth Radius without Vanes


(Idelchik 1986, Diagram 6-1)

INPUTS OUTPUTS

Width (W, mm) 150 Velocity (Vo, m/s) 2.4


Height (H, mm) 200 Vel Pres at Vo (Pv, Pa) 3
Radius Ratio (r/W) 0.8 Loss Coefficient (Co) 0.37
Angle (Theta, deg.) 90 Pressure Loss (Pa) 1
Flow Rate (Q, L/s) 71
Density (kg/m^3) 1.204

01/22/2023 d:\project\ncp\static\ef-03\ef-03.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(CR3-1) Elbow, Smooth Radius without Vanes


(Idelchik 1986, Diagram 6-1)

INPUTS OUTPUTS

Width (W, mm) 150 Velocity (Vo, m/s) 2.4


Height (H, mm) 200 Vel Pres at Vo (Pv, Pa) 3
Radius Ratio (r/W) 0.8 Loss Coefficient (Co) 0.22
Angle (Theta, deg.) 45 Pressure Loss (Pa) 1
Flow Rate (Q, L/s) 71
Density (kg/m^3) 1.204

01/22/2023 d:\project\ncp\static\ef-03\ef-03.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER4-2) Transition, Pyramidal, Exhaust/Return Systems


(Idelchik 1986, Diagram 5-4)

INPUTS OUTPUTS

Height (Ho, mm) 200 Angle (Theta1, deg.) 19


Width (Wo, mm) 150 Angle (Theta2, deg.) 10
Height (H1, mm) 150 Velocity (Vo, m/s) 2.4
Width (W1, mm) 250 Velocity (V1, m/s) 1.9
Length (L, mm) 300 Vel Pres at Vo (Pvo, Pa) 3
Flow Rate (Q, L/s) 71 Vel Pres at V1 (Pv1, Pa) 2
Density (kg/m^3) 1.204 Loss Coefficient (Co) 0.10
Loss Coefficient (C1) 0.15
Pressure Loss (Pa) 0

01/22/2023 d:\project\ncp\static\ef-03\ef-03.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER5-2) Tee, Round Tap to Rectangular Main [Ab/As=Ab/Ac=0.5; As/Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 150 Branch


Width (W, mm) 250 BranchVelocity (Vb, m/s) 2.7
Diameter (Db, mm) 150 Vel Pres at Vb (Pvb, Pa) 4
Flow Rate (Qs, L/s) 71 Loss Coefficient (Cb) 0.65
Flow Rate (Qb, L/s) 47 Branch Pressure Loss (Pa) 3
Density (kg/m^3) 1.204 Main
MainVelocity (Vs, m/s) 1.9
Velocity (Vc, m/s) 3.1
Vel Pres at Vs (Pvs, Pa) 2
Vel Pres at Vc (Pvc, Pa) 6
Loss Coefficient (Cs) 1.32
Main Pressure Loss (Pa) 3

01/22/2023 d:\project\ncp\static\ef-03\ef-03.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER4-1) Transition, Rectangular, Two Sides Parallel, Symmetrical,


Exhaust/Return Systems (Idelchik 1986, Diagram 5-5)

INPUTS OUTPUTS

Height (Ho, mm) 150 Angle (Theta, deg.) 10


Width (Wo, mm) 250 Velocity (Vo, m/s) 3.1
Height (H1, mm) 200 Velocity (V1, m/s) 2.4
Length (L, mm) 300 Vel Pres at Vo (Pvo, Pa) 6
Flow Rate (Q, L/s) 118 Vel Pres at V1 (Pv1, Pa) 3
Density (kg/m^3) 1.204 Loss Coefficient (Co) 0.07
Loss Coefficient (C1) 0.13
Pressure Loss (Pa) 0

01/22/2023 d:\project\ncp\static\ef-03\ef-03.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 200 Branch


Width (W, mm) 250 BranchVelocity (Vb, m/s) 1.8
Height (Hb, mm) 100 Vel Pres at Vb (Pvb, Pa) 2
Width (Wb, mm) 200 Loss Coefficient (Cb) -2.69
Flow Rate (Qs, L/s) 117 Branch Pressure Loss (Pa) -5
Flow Rate (Qb, L/s) 36 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 2.3
Velocity (Vc, m/s) 3.1
Vel Pres at Vs (Pvs, Pa) 3
Vel Pres at Vc (Pvc, Pa) 6
Loss Coefficient (Cs) 0.51
Main Pressure Loss (Pa) 2

01/22/2023 d:\project\ncp\static\ef-03\ef-03.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER4-1) Transition, Rectangular, Two Sides Parallel, Symmetrical,


Exhaust/Return Systems (Idelchik 1986, Diagram 5-5)

INPUTS OUTPUTS

Height (Ho, mm) 200 Angle (Theta, deg.) 19


Width (Wo, mm) 250 Velocity (Vo, m/s) 3.1
Height (H1, mm) 300 Velocity (V1, m/s) 2.1
Length (L, mm) 300 Vel Pres at Vo (Pvo, Pa) 6
Flow Rate (Q, L/s) 154 Vel Pres at V1 (Pv1, Pa) 3
Density (kg/m^3) 1.204 Loss Coefficient (Co) 0.10
Loss Coefficient (C1) 0.22
Pressure Loss (Pa) 1

01/22/2023 d:\project\ncp\static\ef-03\ef-03.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER5-2) Tee, Round Tap to Rectangular Main [Ab/As=Ab/Ac=0.5; As/Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 250 Branch


Width (W, mm) 300 BranchVelocity (Vb, m/s) 2.0
Diameter (Db, mm) 150 Vel Pres at Vb (Pvb, Pa) 2
Flow Rate (Qs, L/s) 154 Loss Coefficient (Cb) -3.60
Flow Rate (Qb, L/s) 36 Branch Pressure Loss (Pa) -9
Density (kg/m^3) 1.204 Main
MainVelocity (Vs, m/s) 2.1
Velocity (Vc, m/s) 2.5
Vel Pres at Vs (Pvs, Pa) 3
Vel Pres at Vc (Pvc, Pa) 4
Loss Coefficient (Cs) 0.35
Main Pressure Loss (Pa) 1

01/22/2023 d:\project\ncp\static\ef-03\ef-03.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 250 Branch


Width (W, mm) 300 BranchVelocity (Vb, m/s) 2.7
Height (Hb, mm) 200 Vel Pres at Vb (Pvb, Pa) 4
Width (Wb, mm) 200 Loss Coefficient (Cb) -0.02
Flow Rate (Qs, L/s) 189 Branch Pressure Loss (Pa) 0
Flow Rate (Qb, L/s) 106 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 2.5
Velocity (Vc, m/s) 3.9
Vel Pres at Vs (Pvs, Pa) 4
Vel Pres at Vc (Pvc, Pa) 9
Loss Coefficient (Cs) 1.10
Main Pressure Loss (Pa) 4

01/22/2023 d:\project\ncp\static\ef-03\ef-03.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 300 Branch


Width (W, mm) 350 BranchVelocity (Vb, m/s) 3.9
Height (Hb, mm) 250 Vel Pres at Vb (Pvb, Pa) 9
Width (Wb, mm) 300 Loss Coefficient (Cb) 0.76
Flow Rate (Qs, L/s) 185 Branch Pressure Loss (Pa) 7
Flow Rate (Qb, L/s) 295 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 1.8
Velocity (Vc, m/s) 4.6
Vel Pres at Vs (Pvs, Pa) 2
Vel Pres at Vc (Pvc, Pa) 13
Loss Coefficient (Cs) 4.15
Main Pressure Loss (Pa) 8

01/22/2023 d:\project\ncp\static\ef-03\ef-03.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 300 Branch


Width (W, mm) 350 BranchVelocity (Vb, m/s) 3.7
Height (Hb, mm) 200 Vel Pres at Vb (Pvb, Pa) 8
Width (Wb, mm) 250 Loss Coefficient (Cb) 0.30
Flow Rate (Qs, L/s) 295 Branch Pressure Loss (Pa) 2
Flow Rate (Qb, L/s) 185 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 2.8
Velocity (Vc, m/s) 4.6
Vel Pres at Vs (Pvs, Pa) 5
Vel Pres at Vc (Pvc, Pa) 13
Loss Coefficient (Cs) 1.25
Main Pressure Loss (Pa) 6

01/22/2023 d:\project\ncp\static\ef-03\ef-03.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(CR3-1) Elbow, Smooth Radius without Vanes


(Idelchik 1986, Diagram 6-1)

INPUTS OUTPUTS

Width (W, mm) 350 Velocity (Vo, m/s) 4.6


Height (H, mm) 300 Vel Pres at Vo (Pv, Pa) 13
Radius Ratio (r/W) 0.8 Loss Coefficient (Co) 0.41
Angle (Theta, deg.) 90 Pressure Loss (Pa) 5
Flow Rate (Q, L/s) 480
Density (kg/m^3) 1.204

01/22/2023 d:\project\ncp\static\ef-03\ef-03.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER4-1) Transition, Rectangular, Two Sides Parallel, Symmetrical,


Exhaust/Return Systems (Idelchik 1986, Diagram 5-5)

INPUTS OUTPUTS

Height (Ho, mm) 300 Angle (Theta, deg.) 10


Width (Wo, mm) 350 Velocity (Vo, m/s) 4.6
Height (H1, mm) 350 Velocity (V1, m/s) 3.9
Length (L, mm) 300 Vel Pres at Vo (Pvo, Pa) 13
Flow Rate (Q, L/s) 480 Vel Pres at V1 (Pv1, Pa) 9
Density (kg/m^3) 1.204 Loss Coefficient (Co) 0.04
Loss Coefficient (C1) 0.06
Pressure Loss (Pa) 1

01/22/2023 d:\project\ncp\static\ef-03\ef-03.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 350 Branch


Width (W, mm) 350 BranchVelocity (Vb, m/s) 3.7
Height (Hb, mm) 200 Vel Pres at Vb (Pvb, Pa) 8
Width (Wb, mm) 200 Loss Coefficient (Cb) -2.71
Flow Rate (Qs, L/s) 480 Branch Pressure Loss (Pa) -22
Flow Rate (Qb, L/s) 147 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 3.9
Velocity (Vc, m/s) 5.1
Vel Pres at Vs (Pvs, Pa) 9
Vel Pres at Vc (Pvc, Pa) 16
Loss Coefficient (Cs) 0.51
Main Pressure Loss (Pa) 5

01/22/2023 d:\project\ncp\static\ef-03\ef-03.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER4-1) Transition, Rectangular, Two Sides Parallel, Symmetrical,


Exhaust/Return Systems (Idelchik 1986, Diagram 5-5)

INPUTS OUTPUTS

Height (Ho, mm) 350 Angle (Theta, deg.) 10


Width (Wo, mm) 350 Velocity (Vo, m/s) 5.1
Height (H1, mm) 400 Velocity (V1, m/s) 4.5
Length (L, mm) 300 Vel Pres at Vo (Pvo, Pa) 16
Flow Rate (Q, L/s) 626 Vel Pres at V1 (Pv1, Pa) 12
Density (kg/m^3) 1.204 Loss Coefficient (Co) 0.04
Loss Coefficient (C1) 0.05
Pressure Loss (Pa) 1

01/22/2023 d:\project\ncp\static\ef-03\ef-03.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 350 Branch


Width (W, mm) 400 BranchVelocity (Vb, m/s) 1.8
Height (Hb, mm) 200 Vel Pres at Vb (Pvb, Pa) 2
Width (Wb, mm) 200 Loss Coefficient (Cb) -19.09
Flow Rate (Qs, L/s) 626 Branch Pressure Loss (Pa) -36
Flow Rate (Qb, L/s) 71 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 4.5
Velocity (Vc, m/s) 5.0
Vel Pres at Vs (Pvs, Pa) 12
Vel Pres at Vc (Pvc, Pa) 15
Loss Coefficient (Cs) 0.11
Main Pressure Loss (Pa) 1

01/22/2023 d:\project\ncp\static\ef-03\ef-03.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(CR3-1) Elbow, Smooth Radius without Vanes


(Idelchik 1986, Diagram 6-1)

INPUTS OUTPUTS

Width (W, mm) 400 Velocity (Vo, m/s) 4.9


Height (H, mm) 350 Vel Pres at Vo (Pv, Pa) 14
Radius Ratio (r/W) 0.8 Loss Coefficient (Co) 0.41
Angle (Theta, deg.) 90 Pressure Loss (Pa) 6
Flow Rate (Q, L/s) 685
Density (kg/m^3) 1.204

01/22/2023 d:\project\ncp\static\ef-03\ef-03.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER4-3) Transition, Rectangular to Round, Exhaust/Return Systems


(Idelchik 1986, Diagram 5-27)

INPUTS OUTPUTS

Height (Ho, mm) 350 Angle (Theta1, deg.) 10


Width (Wo, mm) 400 Angle (Theta2, deg.) 0
Diameter (D1, mm) 400 Velocity (Vo, m/s) 4.9
Length (L, mm) 300 Velocity (V1, m/s) 5.5
Flow Rate (Q, L/s) 685 Vel Pres at Vo (Pvo, Pa) 14
Density (kg/m^3) 1.204 Vel Pres at V1 (Pv1, Pa) 18
Loss Coefficient (Co) 0.03
Loss Coefficient (C1) 0.02
Pressure Loss (Pa) 0

01/22/2023 d:\project\ncp\static\ef-03\ef-03.adf version: 6.00.04


Duct Accessories
Slot Diffuser
Volume Damper 1

%# ( # & & # " #


& ' "
VOLUME DAMPER 04
Fire Damper 05
Fire Damper 07
Back Draft Damper
SUGGESTED SPECIFICATION
Furnish and install, at locations shown on plans or in accordance resistant, long life synthetic type for quiet operation. Linkage shall
with schedules, heavy duty backdraft dampers that meet the follow- be 1 /2 " (13) wide tiebar connected to stainless steel pivot
ing minimum construction standards: Frame shall be .125" (3.2) pins. Dampers shall be designed for maximum 3500 fpm spot
wall thickness 6063T5 extruded aluminum with 12 gage (2.8) gal- velocities and minimum 4 inches w.g. back pressure depending on
vanized steel structural brace at each corner. Blades shall be .070" damper size. Dampers shall be in all respects equivalent to
(1.8) wall thickness 6063T5 extruded aluminum with extruded vinyl Ruskin model CBD6.
blade edge seals mechanically locked into blade edge. Adhesive or
clip on type seals are unacceptable. Bearings shall be
corrosion
INSTALLATION

1. When used in fan discharge applications, damper should 3. Bracing of multiple section assemblies:
be located at least one-half the fan diameter away from the fan. The CBD6 is intended to be self supporting only in the largest
single section size. Multiple section damper assemblies
2. For proper operation, damper must be installed square and free may require bracing to support the weight of the assembly
from racking. and to hold against system pressure. Ruskin recommends
appropriate bracing to support the damper horizontally at
least once for every 8 feet of damper width. Vertical
assemblies and higher system pressures may require more
PERFORMANCE DATA bracing.

DAMPER PERFORMANCE
LEAKAGE* BLADES BLADES
MAXIMUM MAXIMUM SYSTEM
DAMPER WIDTH Percent of CFM/ START TO FULLY
BACK PRESSURE VELOCITY
Max. Flow Sq. Ft. OPEN OPEN

48" (1219) 4.0" w.g. 2500 FPM .6% 15


36" (914) 8.0" w.g. 2500 FPM .6% 15 .01" w.g. .05" w.g.
24" (610) 12.0" w.g. 2500 FPM .7% 17.5
12" (305) 16.0" w.g. 2500 PFM 1% 25

*Leakage information based on pressure differential of 1" w.g. tested per AMCA Std. 500.

DAMPER PRESSURE DROP


(24" x 24")
p p ( [ ] )
0.7
17.78
0.5
12.7
Static Pressure Drop in INCHES and MILLIMETERS of WATER

0.3
7.62

0.2
5.08

0.1
2.54
.07
1.78

.05
1.27

.03
.75

.02
.51

.01
200 300 500 700 1000 2000 3000
60.96 91.44 152.40 213.36 304.80 609.60 914.40

Air velocity in FEET and Meters Per minute through face area
EXF 0
Calculation Sheet
External Static Pressure calculations

Project: NORTH COAST PALACE


MEP contractor : MAGNA ENGINEERING & CONSTRUCTION
Builing Name: MAIN VILLA
FAN TAG EF-04

GENERAL DATA
DUCT MATERIAL: G. I. Sheet
AIR DENSITY:(Kg/m3) 1.2

SECTION (1-1') TOTAL


CFM 1400

FLOW L/S 661

M3/H 2379

LENGTH M 9.0

DIAM. mm 402

DIAM. EQUIV. mm 402

WIDTH mm 750

HEIGHT mm 200

AREA M2 0.127

VELOCITY M/S 5.20

PD per Meter Pa 0.80

PD x LENGTH Pa 7.20 7

PA (1-1') TOTAL

Tee Branch (1) 3 1


Tee Main (1) 6 1
Elbow 90 (1) 6 2
Rect. To Round (1) 1 1
Round To Rect. (1) 3 1
Transition (1) 4 1
TOTAL PA 29 29

DUCTS PD Pa 29 29

PRESSURE DROP Pa 36 36

SPECIAL FITTING PRESSURE DROPS

DESIGNATION PD (PA) QTY TOTAL

Canvas 5 1 5 FLOW AT 100% (m3/hr) 2379

Exhaust Grill 20 1 20 * DUCTS PRESSURE DROP : 36

Exhaust Louver 25 1 25 * FITTING PRESSURE DROP : 63

Back Draft Damper 13 1 13 STATIC PRESSURE AT 100% PA 99

*TOTAL EXTERNAL STATIC PRESSURE + 10% SF PA 109

STATIC PRESSURE AT 100%(in) 0.39

*TOTAL EXTERNAL STATIC PRESSURE + 10% SF (in) 0.43

TOTAL 63
Drawing
Duct Fittings
Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 200 Branch


Width (W, mm) 750 BranchVelocity (Vb, m/s) 2.3
Height (Hb, mm) 100 Vel Pres at Vb (Pvb, Pa) 3
Width (Wb, mm) 1450 Loss Coefficient (Cb) 0.83
Flow Rate (Qs, L/s) 10 Branch Pressure Loss (Pa) 3
Flow Rate (Qb, L/s) 330 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 0.1
Velocity (Vc, m/s) 2.3
Vel Pres at Vs (Pvs, Pa) 0
Vel Pres at Vc (Pvc, Pa) 3
Loss Coefficient (Cs) 34.74
Main Pressure Loss (Pa) 0

01/22/2023 d:\hat project\ncp\calculations\exhaust fan\ef-03\ef-04.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 200 Branch


Width (W, mm) 750 BranchVelocity (Vb, m/s) 2.3
Height (Hb, mm) 100 Vel Pres at Vb (Pvb, Pa) 3
Width (Wb, mm) 1450 Loss Coefficient (Cb) 0.66
Flow Rate (Qs, L/s) 330 Branch Pressure Loss (Pa) 2
Flow Rate (Qb, L/s) 330 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 2.2
Velocity (Vc, m/s) 4.4
Vel Pres at Vs (Pvs, Pa) 3
Vel Pres at Vc (Pvc, Pa) 12
Loss Coefficient (Cs) 2.23
Main Pressure Loss (Pa) 6

01/22/2023 d:\hat project\ncp\calculations\exhaust fan\ef-03\ef-04.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(CR3-1) Elbow, Smooth Radius without Vanes


(Idelchik 1986, Diagram 6-1)

INPUTS OUTPUTS

Width (W, mm) 750 Velocity (Vo, m/s) 4.4


Height (H, mm) 200 Vel Pres at Vo (Pv, Pa) 12
Radius Ratio (r/W) 0.8 Loss Coefficient (Co) 0.51
Angle (Theta, deg.) 90 Pressure Loss (Pa) 6
Flow Rate (Q, L/s) 661
Density (kg/m^3) 1.204

01/22/2023 d:\hat project\ncp\calculations\exhaust fan\ef-03\ef-04.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER4-3) Transition, Rectangular to Round, Exhaust/Return Systems


(Idelchik 1986, Diagram 5-27)

INPUTS OUTPUTS

Height (Ho, mm) 200 Angle (Theta1, deg.) 28


Width (Wo, mm) 750 Angle (Theta2, deg.) 47
Diameter (D1, mm) 400 Velocity (Vo, m/s) 4.4
Length (L, mm) 400 Velocity (V1, m/s) 5.3
Flow Rate (Q, L/s) 661 Vel Pres at Vo (Pvo, Pa) 12
Density (kg/m^3) 1.204 Vel Pres at V1 (Pv1, Pa) 17
Loss Coefficient (Co) 0.05
Loss Coefficient (C1) 0.03
Pressure Loss (Pa) 1

01/22/2023 d:\hat project\ncp\calculations\exhaust fan\ef-03\ef-04.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(SR4-3) Transition, Round to Rectangular, Supply Air Systems


(Idelchik 1986, Diagram 5-27)

INPUTS OUTPUTS

Diameter (D1, mm) 400 Angle (Theta1, deg.) 28


Height (Ho, mm) 200 Angle (Theta2, deg.) 47
Width (Wo, mm) 750 Velocity (Vo, m/s) 4.4
Length (L, mm) 400 Velocity (V1, m/s) 5.3
Flow Rate (Q, L/s) 661 Vel Pres at Vo (Pvo, Pa) 12
Density (kg/m^3) 1.204 Vel Pres at V1 (Pv1, Pa) 17
Loss Coefficient (Co) 0.25
Loss Coefficient (C1) 0.18
Pressure Loss (Pa) 3

01/22/2023 d:\hat project\ncp\calculations\exhaust fan\ef-03\ef-04.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER4-2) Transition, Pyramidal, Exhaust/Return Systems


(Idelchik 1986, Diagram 5-4)

INPUTS OUTPUTS

Height (Ho, mm) 200 Angle (Theta1, deg.) 7


Width (Wo, mm) 750 Angle (Theta2, deg.) 28
Height (H1, mm) 400 Velocity (Vo, m/s) 4.4
Width (W1, mm) 800 Velocity (V1, m/s) 2.1
Length (L, mm) 400 Vel Pres at Vo (Pvo, Pa) 12
Flow Rate (Q, L/s) 661 Vel Pres at V1 (Pv1, Pa) 3
Density (kg/m^3) 1.204 Loss Coefficient (Co) 0.32
Loss Coefficient (C1) 1.44
Pressure Loss (Pa) 4

01/22/2023 d:\hat project\ncp\calculations\exhaust fan\ef-03\ef-04.adf version: 6.00.04


Duct Accessories
Air Grille
Air Louver
Free area for ZAL- S

Free area for ZAL- L


Air Louver

Chart 1
700
Static Pressure Drop (inches w.g.)

600

500

400
x 10-3

300

200

100

0
0 500 1000 1500 2000 2500

Free Area Velocity (ft/min)

Example 1
Given air flow rate of 1500 cfm select a louver size

Dividing flow rate by free area velocity (let say 600 fpm )

Free area = 2.5 ft2 , from the table above , 34”X 22” will be the least louver satisfy the
desired free velocity

Note : other selections are also available

Determine free velocity 1500 /2.51 = 597 fpm

Check for pressure drop across the louver at 597 fpm from chart 1 = 0.06 Wg “

Example 2
Knowing louver size as 24”X28” determine the maximum flow rate

From table 1 free area = 2.28 feet2

For velocity 800 fpm the flow rate = 2.28X 800 = 1824 cfm

Check for pressure drop across the louver at 800 fpm from chart 1 = 0.14 Wg “
Back Draft Damper
SUGGESTED SPECIFICATION
Furnish and install, at locations shown on plans or in accordance resistant, long life synthetic type for quiet operation. Linkage shall
with schedules, heavy duty backdraft dampers that meet the follow- be 1 /2 " (13) wide tiebar connected to stainless steel pivot
ing minimum construction standards: Frame shall be .125" (3.2) pins. Dampers shall be designed for maximum 3500 fpm spot
wall thickness 6063T5 extruded aluminum with 12 gage (2.8) gal- velocities and minimum 4 inches w.g. back pressure depending on
vanized steel structural brace at each corner. Blades shall be .070" damper size. Dampers shall be in all respects equivalent to
(1.8) wall thickness 6063T5 extruded aluminum with extruded vinyl Ruskin model CBD6.
blade edge seals mechanically locked into blade edge. Adhesive or
clip on type seals are unacceptable. Bearings shall be
corrosion
INSTALLATION

1. When used in fan discharge applications, damper should 3. Bracing of multiple section assemblies:
be located at least one-half the fan diameter away from the fan. The CBD6 is intended to be self supporting only in the largest
single section size. Multiple section damper assemblies
2. For proper operation, damper must be installed square and free may require bracing to support the weight of the assembly
from racking. and to hold against system pressure. Ruskin recommends
appropriate bracing to support the damper horizontally at
least once for every 8 feet of damper width. Vertical
assemblies and higher system pressures may require more
PERFORMANCE DATA bracing.

DAMPER PERFORMANCE
LEAKAGE* BLADES BLADES
MAXIMUM MAXIMUM SYSTEM
DAMPER WIDTH Percent of CFM/ START TO FULLY
BACK PRESSURE VELOCITY
Max. Flow Sq. Ft. OPEN OPEN

48" (1219) 4.0" w.g. 2500 FPM .6% 15


36" (914) 8.0" w.g. 2500 FPM .6% 15 .01" w.g. .05" w.g.
24" (610) 12.0" w.g. 2500 FPM .7% 17.5
12" (305) 16.0" w.g. 2500 PFM 1% 25

*Leakage information based on pressure differential of 1" w.g. tested per AMCA Std. 500.

DAMPER PRESSURE DROP


(24" x 24")
p p ( [ ] )
0.7
17.78
0.5
12.7
Static Pressure Drop in INCHES and MILLIMETERS of WATER

0.3
7.62

0.2
5.08

0.1
2.54
.07
1.78

.05
1.27

.03
.75

.02
.51

.01
200 300 500 700 1000 2000 3000
60.96 91.44 152.40 213.36 304.80 609.60 914.40

Air velocity in FEET and Meters Per minute through face area
EXF 0
Calculation Sheet
External Static Pressure calculations

Project: NORTH COAST PALACE


MEP contractor : MAGNA ENGINEERING & CONSTRUCTION
Builing Name: MAIN VILLA
FAN TAG EF-06

GENERAL DATA
DUCT MATERIAL: G. I. Sheet
AIR DENSITY:(Kg/m3) 1.2

SECTION (1-1') (2-2') (3-3') (4-4') (5-5') TOTAL


CFM 250 250 500 750 1000
FLOW L/S 118 118 236 354 472

M3/H 425 425 850 1274 1699

LENGTH M 0.5 1.0 1.0 1.0 2.5

DIAM. mm 164 219 286 321 365

DIAM. EQUIV. mm 164 219 286 321 365

WIDTH mm 150 200 350 450 600

HEIGHT mm 150 200 200 200 200

AREA M2 0.021 0.038 0.064 0.081 0.105

VELOCITY M/S 5.59 3.14 3.66 4.36 4.50

PD per Meter Pa 2.73 0.67 0.64 0.76 0.69

PD x LENGTH Pa 1.36 0.67 0.64 0.76 1.73 5

PA (1-1') (2-2') (3-3') (4-4') (5-5') TOTAL

Plenum Box 1 1
Flexible Duct 14 1
Transition 1 1
Tee Branch 14 1
Transition 1 1
Tee Main 4 1
Transition 1 1
Tee Main 4 1
Transition 1 1
Tee Main 3 1
Transition 2 1
Transition 16 1

TOTAL PA 30 1 5 5 21 0 0 0 0 0 62

DUCTS PD Pa 30 1 5 5 21 0 0 0 0 0 62

PRESSURE DROP Pa 31 2 6 6 23 0 0 0 0 0 67

SPECIAL FITTING PRESSURE DROPS

`
DESIGNATION PD (PA) QTY TOTAL
Canvas 5 2 10 FLOW AT 100% (m3/hr) 1699

Return slot Diffuser 20 1 20 * DUCTS PRESSURE DROP : 67


Volume damper (1) 18 1 18 * FITTING PRESSURE DROP : 100
Back Draft Damper 12 1 12 STATIC PRESSURE AT 100% PA 167
Exhaust Air Louvre 40 1 40 *TOTAL EXTERNAL STATIC PRESSURE + 10% SF PA 184

0 STATIC PRESSURE AT 100%(in) 0.67

0 *TOTAL EXTERNAL STATIC PRESSURE + 15% SF (in) 0.74

0
TOTAL 100
Drawing
EF-06 / 1000 CFM
2 RLSD, 2 SLOTS, 2.1 m 8"x8"
Ex.L 36"x10" 250 cfm
14"x8" 18"x8"
24"x8"
500 cfm 750 cfm
1000 cfm
Duct Fittings
Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER2-1) Bellmouth, Plenum to Round, Exhaust/Return Systems


(Idelchik 1986, Diagram 4-9)

INPUTS OUTPUTS

Diameter (D1, mm) 150 Velocity (Vo, m/s) 0.4


Plenum Height (Ho, mm) 250 Velocity (V1, m/s) 6.6
Plenum Width (Wo, mm) 1200 Vel Pres at Vo (Pvo, Pa) 0
Flow Rate (Q, L/s) 117 Vel Pres at V1 (Pv1, Pa) 26
Density (kg/m^3) 1.204 Bellmouth Radius (r, mm) 50
Loss Coefficient (Co) 8.26
Loss Coefficient (C1) 0.03
Pressure Loss (Pa) 1

01/22/2023 d:\project\ncp\static\ef-06\ef-06.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(CD11-2) Straight Duct, Flexible


(Abushakra 2004 and Culp 2011

INPUTS OUTPUTS

Flow Rate (Q, L/s) 117 Velocity (V, m/s) 6.6


Diameter (D, mm) 150 Vel Pres at Vo (Pv, Pa) 26
Installed Length (L, m) 0.3 Compressed (%) 25
Length Fully Extended (m) 0.4 Pressure Drop Correction Factor (PDCF) 7.9
Density (kg/m^3) 1.204 Pressure Loss (Pa) 14

FULLY EXTENDED

LESS THAN FULLY EXTENDED

01/22/2023 d:\project\ncp\static\ef-06\ef-06.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(SR4-3) Transition, Round to Rectangular, Supply Air Systems


(Idelchik 1986, Diagram 5-27)

INPUTS OUTPUTS

Diameter (D1, mm) 150 Angle (Theta1, deg.) 0


Height (Ho, mm) 150 Angle (Theta2, deg.) 0
Width (Wo, mm) 150 Velocity (Vo, m/s) 5.2
Length (L, mm) 300 Velocity (V1, m/s) 6.7
Flow Rate (Q, L/s) 118 Vel Pres at Vo (Pvo, Pa) 17
Density (kg/m^3) 1.204 Vel Pres at V1 (Pv1, Pa) 27
Loss Coefficient (Co) 0.00
Loss Coefficient (C1) 0.00
Pressure Loss (Pa) 0

01/22/2023 d:\project\ncp\static\ef-06\ef-06.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 200 Branch


Width (W, mm) 200 BranchVelocity (Vb, m/s) 5.2
Height (Hb, mm) 150 Vel Pres at Vb (Pvb, Pa) 17
Width (Wb, mm) 150 Loss Coefficient (Cb) 0.83
Flow Rate (Qs, L/s) 5 Branch Pressure Loss (Pa) 14
Flow Rate (Qb, L/s) 118 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 0.1
Velocity (Vc, m/s) 3.1
Vel Pres at Vs (Pvs, Pa) 0
Vel Pres at Vc (Pvc, Pa) 6
Loss Coefficient (Cs) 32.73
Main Pressure Loss (Pa) 0

01/22/2023 d:\project\ncp\static\ef-06\ef-06.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER4-1) Transition, Rectangular, Two Sides Parallel, Symmetrical,


Exhaust/Return Systems (Idelchik 1986, Diagram 5-5)

INPUTS OUTPUTS

Height (Ho, mm) 200 Angle (Theta, deg.) 28


Width (Wo, mm) 200 Velocity (Vo, m/s) 3.0
Height (H1, mm) 350 Velocity (V1, m/s) 1.7
Length (L, mm) 300 Vel Pres at Vo (Pvo, Pa) 5
Flow Rate (Q, L/s) 118 Vel Pres at V1 (Pv1, Pa) 2
Density (kg/m^3) 1.204 Loss Coefficient (Co) 0.19
Loss Coefficient (C1) 0.58
Pressure Loss (Pa) 1

01/22/2023 d:\project\ncp\static\ef-06\ef-06.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 200 Branch


Width (W, mm) 350 BranchVelocity (Vb, m/s) 5.2
Height (Hb, mm) 150 Vel Pres at Vb (Pvb, Pa) 17
Width (Wb, mm) 150 Loss Coefficient (Cb) 0.66
Flow Rate (Qs, L/s) 118 Branch Pressure Loss (Pa) 11
Flow Rate (Qb, L/s) 118 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 1.7
Velocity (Vc, m/s) 3.4
Vel Pres at Vs (Pvs, Pa) 2
Vel Pres at Vc (Pvc, Pa) 7
Loss Coefficient (Cs) 2.23
Main Pressure Loss (Pa) 4

01/22/2023 d:\project\ncp\static\ef-06\ef-06.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER4-1) Transition, Rectangular, Two Sides Parallel, Symmetrical,


Exhaust/Return Systems (Idelchik 1986, Diagram 5-5)

INPUTS OUTPUTS

Height (Ho, mm) 350 Angle (Theta, deg.) 19


Width (Wo, mm) 200 Velocity (Vo, m/s) 3.4
Height (H1, mm) 450 Velocity (V1, m/s) 2.6
Length (L, mm) 300 Vel Pres at Vo (Pvo, Pa) 7
Flow Rate (Q, L/s) 236 Vel Pres at V1 (Pv1, Pa) 4
Density (kg/m^3) 1.204 Loss Coefficient (Co) 0.06
Loss Coefficient (C1) 0.11
Pressure Loss (Pa) 0

01/22/2023 d:\project\ncp\static\ef-06\ef-06.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 200 Branch


Width (W, mm) 450 BranchVelocity (Vb, m/s) 5.2
Height (Hb, mm) 150 Vel Pres at Vb (Pvb, Pa) 17
Width (Wb, mm) 150 Loss Coefficient (Cb) -0.33
Flow Rate (Qs, L/s) 236 Branch Pressure Loss (Pa) -6
Flow Rate (Qb, L/s) 118 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 2.6
Velocity (Vc, m/s) 3.9
Vel Pres at Vs (Pvs, Pa) 4
Vel Pres at Vc (Pvc, Pa) 9
Loss Coefficient (Cs) 0.95
Main Pressure Loss (Pa) 4

01/22/2023 d:\project\ncp\static\ef-06\ef-06.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER4-1) Transition, Rectangular, Two Sides Parallel, Symmetrical,


Exhaust/Return Systems (Idelchik 1986, Diagram 5-5)

INPUTS OUTPUTS

Height (Ho, mm) 450 Angle (Theta, deg.) 28


Width (Wo, mm) 200 Velocity (Vo, m/s) 3.9
Height (H1, mm) 600 Velocity (V1, m/s) 3.0
Length (L, mm) 300 Vel Pres at Vo (Pvo, Pa) 9
Flow Rate (Q, L/s) 354 Vel Pres at V1 (Pv1, Pa) 5
Density (kg/m^3) 1.204 Loss Coefficient (Co) 0.11
Loss Coefficient (C1) 0.20
Pressure Loss (Pa) 1

01/22/2023 d:\project\ncp\static\ef-06\ef-06.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 200 Branch


Width (W, mm) 600 BranchVelocity (Vb, m/s) 5.2
Height (Hb, mm) 150 Vel Pres at Vb (Pvb, Pa) 17
Width (Wb, mm) 150 Loss Coefficient (Cb) -2.25
Flow Rate (Qs, L/s) 354 Branch Pressure Loss (Pa) -37
Flow Rate (Qb, L/s) 118 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 3.0
Velocity (Vc, m/s) 3.9
Vel Pres at Vs (Pvs, Pa) 5
Vel Pres at Vc (Pvc, Pa) 9
Loss Coefficient (Cs) 0.57
Main Pressure Loss (Pa) 3

01/22/2023 d:\project\ncp\static\ef-06\ef-06.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER4-3) Transition, Rectangular to Round, Exhaust/Return Systems


(Idelchik 1986, Diagram 5-27)

INPUTS OUTPUTS

Height (Ho, mm) 200 Angle (Theta1, deg.) 19


Width (Wo, mm) 600 Angle (Theta2, deg.) 53
Diameter (D1, mm) 300 Velocity (Vo, m/s) 3.9
Length (L, mm) 300 Velocity (V1, m/s) 6.7
Flow Rate (Q, L/s) 472 Vel Pres at Vo (Pvo, Pa) 9
Density (kg/m^3) 1.204 Vel Pres at V1 (Pv1, Pa) 27
Loss Coefficient (Co) 0.18
Loss Coefficient (C1) 0.06
Pressure Loss (Pa) 2

01/22/2023 d:\project\ncp\static\ef-06\ef-06.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(SR4-3) Transition, Round to Rectangular, Supply Air Systems


(Idelchik 1986, Diagram 5-27)

INPUTS OUTPUTS

Diameter (D1, mm) 300 Angle (Theta1, deg.) 5


Height (Ho, mm) 250 Angle (Theta2, deg.) 53
Width (Wo, mm) 900 Velocity (Vo, m/s) 2.1
Length (L, mm) 600 Velocity (V1, m/s) 6.7
Flow Rate (Q, L/s) 472 Vel Pres at Vo (Pvo, Pa) 3
Density (kg/m^3) 1.204 Vel Pres at V1 (Pv1, Pa) 27
Loss Coefficient (Co) 6.23
Loss Coefficient (C1) 0.61
Pressure Loss (Pa) 16

01/22/2023 d:\project\ncp\static\ef-06\ef-06.adf version: 6.00.04


Duct Accessories
Slot Diffuser
Volume Damper

%# ( # & & # " #


& ' "
Back Draft Damper
SUGGESTED SPECIFICATION
Furnish and install, at locations shown on plans or in accordance resistant, long life synthetic type for quiet operation. Linkage shall
with schedules, heavy duty backdraft dampers that meet the follow- be 1 /2 " (13) wide tiebar connected to stainless steel pivot
ing minimum construction standards: Frame shall be .125" (3.2) pins. Dampers shall be designed for maximum 3500 fpm spot
wall thickness 6063T5 extruded aluminum with 12 gage (2.8) gal- velocities and minimum 4 inches w.g. back pressure depending on
vanized steel structural brace at each corner. Blades shall be .070" damper size. Dampers shall be in all respects equivalent to
(1.8) wall thickness 6063T5 extruded aluminum with extruded vinyl Ruskin model CBD6.
blade edge seals mechanically locked into blade edge. Adhesive or
clip on type seals are unacceptable. Bearings shall be
corrosion
INSTALLATION

1. When used in fan discharge applications, damper should 3. Bracing of multiple section assemblies:
be located at least one-half the fan diameter away from the fan. The CBD6 is intended to be self supporting only in the largest
single section size. Multiple section damper assemblies
2. For proper operation, damper must be installed square and free may require bracing to support the weight of the assembly
from racking. and to hold against system pressure. Ruskin recommends
appropriate bracing to support the damper horizontally at
least once for every 8 feet of damper width. Vertical
assemblies and higher system pressures may require more
PERFORMANCE DATA bracing.

DAMPER PERFORMANCE
LEAKAGE* BLADES BLADES
MAXIMUM MAXIMUM SYSTEM
DAMPER WIDTH Percent of CFM/ START TO FULLY
BACK PRESSURE VELOCITY
Max. Flow Sq. Ft. OPEN OPEN

48" (1219) 4.0" w.g. 2500 FPM .6% 15


36" (914) 8.0" w.g. 2500 FPM .6% 15 .01" w.g. .05" w.g.
24" (610) 12.0" w.g. 2500 FPM .7% 17.5
12" (305) 16.0" w.g. 2500 PFM 1% 25

*Leakage information based on pressure differential of 1" w.g. tested per AMCA Std. 500.

DAMPER PRESSURE DROP


(24" x 24")
p p ( [ ] )
0.7
17.78
0.5
12.7
Static Pressure Drop in INCHES and MILLIMETERS of WATER

0.3
7.62

0.2
5.08

0.1
2.54
.07
1.78

.05
1.27

.03
.75

.02
.51

.01
200 300 500 700 1000 2000 3000
60.96 91.44 152.40 213.36 304.80 609.60 914.40

Air velocity in FEET and Meters Per minute through face area
Air Louver

Chart 1
700
Static Pressure Drop (inches w.g.)

600

500

400
x 10-3

300

200

100

0
0 500 1000 1500 2000 2500

Free Area Velocity (ft/min)

Example 1
Given air flow rate of 1500 cfm select a louver size

Dividing flow rate by free area velocity (let say 600 fpm )

Free area = 2.5 ft2 , from the table above , 34”X 22” will be the least louver satisfy the
desired free velocity

Note : other selections are also available

Determine free velocity 1500 /2.51 = 597 fpm

Check for pressure drop across the louver at 597 fpm from chart 1 = 0.06 Wg “

Example 2
Knowing louver size as 24”X28” determine the maximum flow rate

From table 1 free area = 2.28 feet2

For velocity 800 fpm the flow rate = 2.28X 800 = 1824 cfm

Check for pressure drop across the louver at 800 fpm from chart 1 = 0.14 Wg “
Air Louver

Free area for ZAL- S

Free area for ZAL- L


EXF 0
Calculation Sheet
External Static Pressure calculations

Project: NORTH COAST PALACE


MEP contractor : MAGNA ENGINEERING & CONSTRUCTION
Builing Name: MAIN VILLA
FAN TAG EF-07

GENERAL DATA
DUCT MATERIAL: G. I. Sheet
AIR DENSITY:(Kg/m3) 1.2

SECTION (1-1') (2-2') (3-3') (4-4') TOTAL


CFM 95 190 430 850

FLOW L/S 45 90 203 401

M3/H 161 323 731 1444

LENGTH M 1.0 7.0 28.0 17.0

DIAM. mm 164 219 273 328

DIAM. EQUIV. mm 164 219 273 328

WIDTH mm 150 200 250 300

HEIGHT mm 150 200 250 300

AREA M2 0.021 0.038 0.059 0.084

VELOCITY M/S 2.12 2.39 3.46 4.75

PD per Meter Pa 0.47 0.41 0.61 0.87

PD x LENGTH Pa 0.47 2.86 17.13 14.82 35

PA (1-1') (2-2') (3-3') (4-4') TOTAL

Plenum (1) 1 1
Round to Rect. 1 1
Elbow 90 (1) 1 1
Transition (1) 1 1
Tee Main (2) 2 1
Transition (2) 1 1
Tee Main (3) 4 1
Elbow 90 (3) 3 3
Elbow 45 (3) 2 2
Transition (3) 1 1
Tee Main (4.1) 5 1
Tee Main (4.2) 1 1
Elbow 90 (4) 5 2
Rect. To Round (4) 1 1
TOTAL PA 4 3 18 17 0 0 0 0 0 0 42

DUCTS PD Pa 4 3 18 17 0 0 0 0 0 0 42

PRESSURE DROP Pa 4 6 35 32 0 0 0 0 0 0 77

SPECIAL FITTING PRESSURE DROPS

DESIGNATION PD (PA) QTY TOTAL

Canvas 5 1 5 FLOW AT 100% (m3/hr) 1444


Return Slot Linear Diffuser 20 1 20 * DUCTS PRESSURE DROP : 77
Volume damper (1) 5 1 5 * FITTING PRESSURE DROP : 62
Fire Damper (4) 20 1 20 STATIC PRESSURE AT 100% PA 139
Back Draft Damper 10 1 10 *TOTAL EXTERNAL STATIC PRESSURE + 10% SF PA 153
Flexible Connection 2 1 2 STATIC PRESSURE AT 100%(in) 0.56

*TOTAL EXTERNAL STATIC PRESSURE + 10% SF (in) 0.61

TOTAL 62
Drawing
Duct Fittings
Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER2-1) Bellmouth, Plenum to Round, Exhaust/Return Systems


(Idelchik 1986, Diagram 4-9)

INPUTS OUTPUTS

Diameter (D1, mm) 150 Velocity (Vo, m/s) 0.3


Plenum Height (Ho, mm) 200 Velocity (V1, m/s) 2.5
Plenum Width (Wo, mm) 800 Vel Pres at Vo (Pvo, Pa) 0
Flow Rate (Q, L/s) 45 Vel Pres at V1 (Pv1, Pa) 4
Density (kg/m^3) 1.204 Bellmouth Radius (r, mm) 50
Loss Coefficient (Co) 2.25
Loss Coefficient (C1) 0.03
Pressure Loss (Pa) 0

01/22/2023 d:\hat project\ncp\calculations\exhaust fan\ef-07\ef-07.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(CD11-2) Straight Duct, Flexible


(Abushakra 2004 and Culp 2011

INPUTS OUTPUTS

Flow Rate (Q, L/s) 45 Velocity (V, m/s) 2.5


Diameter (D, mm) 150 Vel Pres at Vo (Pv, Pa) 4
Installed Length (L, m) 0.2 Compressed (%) 33
Length Fully Extended (m) 0.3 Pressure Drop Correction Factor (PDCF) 10.2
Density (kg/m^3) 1.204 Pressure Loss (Pa) 2

FULLY EXTENDED

LESS THAN FULLY EXTENDED

01/22/2023 d:\hat project\ncp\calculations\exhaust fan\ef-07\ef-07.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(CR3-1) Elbow, Smooth Radius without Vanes


(Idelchik 1986, Diagram 6-1)

INPUTS OUTPUTS

Width (W, mm) 150 Velocity (Vo, m/s) 1.5


Height (H, mm) 200 Vel Pres at Vo (Pv, Pa) 1
Radius Ratio (r/W) 0.8 Loss Coefficient (Co) 0.37
Angle (Theta, deg.) 90 Pressure Loss (Pa) 1
Flow Rate (Q, L/s) 45
Density (kg/m^3) 1.204

01/22/2023 d:\hat project\ncp\calculations\exhaust fan\ef-07\ef-07.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(SR4-3) Transition, Round to Rectangular, Supply Air Systems


(Idelchik 1986, Diagram 5-27)

INPUTS OUTPUTS

Diameter (D1, mm) 150 Angle (Theta1, deg.) 7


Height (Ho, mm) 200 Angle (Theta2, deg.) 0
Width (Wo, mm) 150 Velocity (Vo, m/s) 1.5
Length (L, mm) 400 Velocity (V1, m/s) 2.5
Flow Rate (Q, L/s) 45 Vel Pres at Vo (Pvo, Pa) 1
Density (kg/m^3) 1.204 Vel Pres at V1 (Pv1, Pa) 4
Loss Coefficient (Co) 0.40
Loss Coefficient (C1) 0.14
Pressure Loss (Pa) 1

01/22/2023 d:\hat project\ncp\calculations\exhaust fan\ef-07\ef-07.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER4-2) Transition, Pyramidal, Exhaust/Return Systems


(Idelchik 1986, Diagram 5-4)

INPUTS OUTPUTS

Height (Ho, mm) 200 Angle (Theta1, deg.) 10


Width (Wo, mm) 150 Angle (Theta2, deg.) 0
Height (H1, mm) 200 Velocity (Vo, m/s) 1.5
Width (W1, mm) 200 Velocity (V1, m/s) 1.1
Length (L, mm) 300 Vel Pres at Vo (Pvo, Pa) 1
Flow Rate (Q, L/s) 45 Vel Pres at V1 (Pv1, Pa) 1
Density (kg/m^3) 1.204 Loss Coefficient (Co) 0.07
Loss Coefficient (C1) 0.13
Pressure Loss (Pa) 0

01/22/2023 d:\hat project\ncp\calculations\exhaust fan\ef-07\ef-07.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 200 Branch


Width (W, mm) 200 BranchVelocity (Vb, m/s) 2.0
Height (Hb, mm) 150 Vel Pres at Vb (Pvb, Pa) 2
Width (Wb, mm) 150 Loss Coefficient (Cb) 0.66
Flow Rate (Qs, L/s) 45 Branch Pressure Loss (Pa) 2
Flow Rate (Qb, L/s) 45 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 1.1
Velocity (Vc, m/s) 2.3
Vel Pres at Vs (Pvs, Pa) 1
Vel Pres at Vc (Pvc, Pa) 3
Loss Coefficient (Cs) 2.23
Main Pressure Loss (Pa) 2

01/22/2023 d:\hat project\ncp\calculations\exhaust fan\ef-07\ef-07.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER4-2) Transition, Pyramidal, Exhaust/Return Systems


(Idelchik 1986, Diagram 5-4)

INPUTS OUTPUTS

Height (Ho, mm) 250 Angle (Theta1, deg.) 7


Width (Wo, mm) 250 Angle (Theta2, deg.) 7
Height (H1, mm) 200 Velocity (Vo, m/s) 1.4
Width (W1, mm) 200 Velocity (V1, m/s) 2.3
Length (L, mm) 400 Vel Pres at Vo (Pvo, Pa) 1
Flow Rate (Q, L/s) 90 Vel Pres at V1 (Pv1, Pa) 3
Density (kg/m^3) 1.204 Loss Coefficient (Co) 0.15
Loss Coefficient (C1) 0.06
Pressure Loss (Pa) 0

01/22/2023 d:\hat project\ncp\calculations\exhaust fan\ef-07\ef-07.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 250 Branch


Width (W, mm) 250 BranchVelocity (Vb, m/s) 3.8
Height (Hb, mm) 150 Vel Pres at Vb (Pvb, Pa) 9
Width (Wb, mm) 200 Loss Coefficient (Cb) 0.71
Flow Rate (Qs, L/s) 90 Branch Pressure Loss (Pa) 6
Flow Rate (Qb, L/s) 113 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 1.4
Velocity (Vc, m/s) 3.2
Vel Pres at Vs (Pvs, Pa) 1
Vel Pres at Vc (Pvc, Pa) 6
Loss Coefficient (Cs) 3.09
Main Pressure Loss (Pa) 4

01/22/2023 d:\hat project\ncp\calculations\exhaust fan\ef-07\ef-07.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(CR3-1) Elbow, Smooth Radius without Vanes


(Idelchik 1986, Diagram 6-1)

INPUTS OUTPUTS

Width (W, mm) 250 Velocity (Vo, m/s) 3.2


Height (H, mm) 250 Vel Pres at Vo (Pv, Pa) 6
Radius Ratio (r/W) 0.8 Loss Coefficient (Co) 0.39
Angle (Theta, deg.) 90 Pressure Loss (Pa) 3
Flow Rate (Q, L/s) 203
Density (kg/m^3) 1.204

01/22/2023 d:\hat project\ncp\calculations\exhaust fan\ef-07\ef-07.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(CR3-1) Elbow, Smooth Radius without Vanes


(Idelchik 1986, Diagram 6-1)

INPUTS OUTPUTS

Width (W, mm) 250 Velocity (Vo, m/s) 3.2


Height (H, mm) 250 Vel Pres at Vo (Pv, Pa) 6
Radius Ratio (r/W) 0.8 Loss Coefficient (Co) 0.24
Angle (Theta, deg.) 45 Pressure Loss (Pa) 2
Flow Rate (Q, L/s) 203
Density (kg/m^3) 1.204

01/22/2023 d:\hat project\ncp\calculations\exhaust fan\ef-07\ef-07.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER4-2) Transition, Pyramidal, Exhaust/Return Systems


(Idelchik 1986, Diagram 5-4)

INPUTS OUTPUTS

Height (Ho, mm) 250 Angle (Theta1, deg.) 7


Width (Wo, mm) 250 Angle (Theta2, deg.) 7
Height (H1, mm) 300 Velocity (Vo, m/s) 3.2
Width (W1, mm) 300 Velocity (V1, m/s) 2.3
Length (L, mm) 400 Vel Pres at Vo (Pvo, Pa) 6
Flow Rate (Q, L/s) 203 Vel Pres at V1 (Pv1, Pa) 3
Density (kg/m^3) 1.204 Loss Coefficient (Co) 0.09
Loss Coefficient (C1) 0.18
Pressure Loss (Pa) 1

01/22/2023 d:\hat project\ncp\calculations\exhaust fan\ef-07\ef-07.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 300 Branch


Width (W, mm) 300 BranchVelocity (Vb, m/s) 3.0
Height (Hb, mm) 200 Vel Pres at Vb (Pvb, Pa) 5
Width (Wb, mm) 250 Loss Coefficient (Cb) 0.53
Flow Rate (Qs, L/s) 203 Branch Pressure Loss (Pa) 3
Flow Rate (Qb, L/s) 151 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 2.3
Velocity (Vc, m/s) 3.9
Vel Pres at Vs (Pvs, Pa) 3
Vel Pres at Vc (Pvc, Pa) 9
Loss Coefficient (Cs) 1.57
Main Pressure Loss (Pa) 5

01/22/2023 d:\hat project\ncp\calculations\exhaust fan\ef-07\ef-07.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 300 Branch


Width (W, mm) 300 BranchVelocity (Vb, m/s) 1.6
Height (Hb, mm) 150 Vel Pres at Vb (Pvb, Pa) 1
Width (Wb, mm) 200 Loss Coefficient (Cb) -16.69
Flow Rate (Qs, L/s) 354 Branch Pressure Loss (Pa) -25
Flow Rate (Qb, L/s) 47 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 3.9
Velocity (Vc, m/s) 4.5
Vel Pres at Vs (Pvs, Pa) 9
Vel Pres at Vc (Pvc, Pa) 12
Loss Coefficient (Cs) 0.15
Main Pressure Loss (Pa) 1

01/22/2023 d:\hat project\ncp\calculations\exhaust fan\ef-07\ef-07.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(CR3-1) Elbow, Smooth Radius without Vanes


(Idelchik 1986, Diagram 6-1)

INPUTS OUTPUTS

Width (W, mm) 300 Velocity (Vo, m/s) 4.5


Height (H, mm) 300 Vel Pres at Vo (Pv, Pa) 12
Radius Ratio (r/W) 0.8 Loss Coefficient (Co) 0.39
Angle (Theta, deg.) 90 Pressure Loss (Pa) 5
Flow Rate (Q, L/s) 401
Density (kg/m^3) 1.204

01/22/2023 d:\hat project\ncp\calculations\exhaust fan\ef-07\ef-07.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER4-3) Transition, Rectangular to Round, Exhaust/Return Systems


(Idelchik 1986, Diagram 5-27)

INPUTS OUTPUTS

Height (Ho, mm) 300 Angle (Theta1, deg.) 0


Width (Wo, mm) 300 Angle (Theta2, deg.) 0
Diameter (D1, mm) 300 Velocity (Vo, m/s) 4.5
Length (L, mm) 500 Velocity (V1, m/s) 5.7
Flow Rate (Q, L/s) 401 Vel Pres at Vo (Pvo, Pa) 12
Density (kg/m^3) 1.204 Vel Pres at V1 (Pv1, Pa) 19
Loss Coefficient (Co) 0.00
Loss Coefficient (C1) 0.00
Pressure Loss (Pa) 0

01/22/2023 d:\hat project\ncp\calculations\exhaust fan\ef-07\ef-07.adf version: 6.00.04


Duct Accessories
Slot Diffuser
Volume Damper

%# ( # & & # " #


& ' "
Fire Damper 9
Fire Damper 10
Back Draft Damper
SUGGESTED SPECIFICATION
Furnish and install, at locations shown on plans or in accordance resistant, long life synthetic type for quiet operation. Linkage shall
with schedules, heavy duty backdraft dampers that meet the follow- be 1 /2 " (13) wide tiebar connected to stainless steel pivot
ing minimum construction standards: Frame shall be .125" (3.2) pins. Dampers shall be designed for maximum 3500 fpm spot
wall thickness 6063T5 extruded aluminum with 12 gage (2.8) gal- velocities and minimum 4 inches w.g. back pressure depending on
vanized steel structural brace at each corner. Blades shall be .070" damper size. Dampers shall be in all respects equivalent to
(1.8) wall thickness 6063T5 extruded aluminum with extruded vinyl Ruskin model CBD6.
blade edge seals mechanically locked into blade edge. Adhesive or
clip on type seals are unacceptable. Bearings shall be
corrosion
INSTALLATION

1. When used in fan discharge applications, damper should 3. Bracing of multiple section assemblies:
be located at least one-half the fan diameter away from the fan. The CBD6 is intended to be self supporting only in the largest
single section size. Multiple section damper assemblies
2. For proper operation, damper must be installed square and free may require bracing to support the weight of the assembly
from racking. and to hold against system pressure. Ruskin recommends
appropriate bracing to support the damper horizontally at
least once for every 8 feet of damper width. Vertical
assemblies and higher system pressures may require more
PERFORMANCE DATA bracing.

DAMPER PERFORMANCE
LEAKAGE* BLADES BLADES
MAXIMUM MAXIMUM SYSTEM
DAMPER WIDTH Percent of CFM/ START TO FULLY
BACK PRESSURE VELOCITY
Max. Flow Sq. Ft. OPEN OPEN

48" (1219) 4.0" w.g. 2500 FPM .6% 15


36" (914) 8.0" w.g. 2500 FPM .6% 15 .01" w.g. .05" w.g.
24" (610) 12.0" w.g. 2500 FPM .7% 17.5
12" (305) 16.0" w.g. 2500 PFM 1% 25

*Leakage information based on pressure differential of 1" w.g. tested per AMCA Std. 500.

DAMPER PRESSURE DROP


(24" x 24")
p p ( [ ] )
0.7
17.78
0.5
12.7
Static Pressure Drop in INCHES and MILLIMETERS of WATER

0.3
7.62

0.2
5.08

0.1
2.54
.07
1.78

.05
1.27

.03
.75

.02
.51

.01
200 300 500 700 1000 2000 3000
60.96 91.44 152.40 213.36 304.80 609.60 914.40

Air velocity in FEET and Meters Per minute through face area
EXF 0
Calculation Sheet
External Static Pressure calculations

Project: NORTH COAST PALACE


MEP contractor : MAGNA ENGINEERING & CONSTRUCTION
Builing Name: MAIN VILLA
FAN TAG EF-08

GENERAL DATA
DUCT MATERIAL: G. I. Sheet
AIR DENSITY:(Kg/m3) 1.2

SECTION (1-1') (2-2') TOTAL


CFM 375 750
FLOW L/S 177 354

M3/H 637 1274

LENGTH M 3.5 8.0

DIAM. mm 245 310

DIAM. EQUIV. mm 245 310

WIDTH mm 350 600

HEIGHT mm 150 150

AREA M2 0.047 0.076

VELOCITY M/S 3.75 4.69

PD per Meter Pa 0.81 0.91

PD x LENGTH Pa 2.83 7.28 10

PA (1-1') (2-2') TOTAL

Tee Branch 1 1
Transition 1 1
Tee Main 2 1
Elbow 5 4
Transition 1 1

TOTAL PA 2 23 0 0 0 0 0 0 0 0 25

DUCTS PD Pa 2 23 0 0 0 0 0 0 0 0 25

PRESSURE DROP Pa 5 30 0 0 0 0 0 0 0 0 35

SPECIAL FITTING PRESSURE DROPS

`
DESIGNATION PD (PA) QTY TOTAL
Canvas 5 1 5 FLOW AT 100% (m3/hr) 1274

Return Linear Grille 20 1 20 * DUCTS PRESSURE DROP : 35


Fire Damper 13 1 13 * FITTING PRESSURE DROP : 50
Back Draft Damper 12 1 12 STATIC PRESSURE AT 100% PA 85

0 *TOTAL EXTERNAL STATIC PRESSURE + 10% SF PA 94

0 STATIC PRESSURE AT 100%(in) 0.34

0 *TOTAL EXTERNAL STATIC PRESSURE + 15% SF (in) 0.37

0
TOTAL 50
Drawing
Duct Fittings
Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 150 Branch


Width (W, mm) 350 BranchVelocity (Vb, m/s) 1.4
Height (Hb, mm) 850 Vel Pres at Vb (Pvb, Pa) 1
Width (Wb, mm) 100 Loss Coefficient (Cb) 0.83
Flow Rate (Qs, L/s) 5 Branch Pressure Loss (Pa) 1
Flow Rate (Qb, L/s) 117 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 0.1
Velocity (Vc, m/s) 2.3
Vel Pres at Vs (Pvs, Pa) 0
Vel Pres at Vc (Pvc, Pa) 3
Loss Coefficient (Cs) 32.67
Main Pressure Loss (Pa) 0

01/22/2023 d:\project\ncp\static\ef-08\ef-08.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER4-1) Transition, Rectangular, Two Sides Parallel, Symmetrical,


Exhaust/Return Systems (Idelchik 1986, Diagram 5-5)

INPUTS OUTPUTS

Height (Ho, mm) 350 Angle (Theta, deg.) 24


Width (Wo, mm) 150 Velocity (Vo, m/s) 2.2
Height (H1, mm) 600 Velocity (V1, m/s) 1.3
Length (L, mm) 600 Vel Pres at Vo (Pvo, Pa) 3
Flow Rate (Q, L/s) 117 Vel Pres at V1 (Pv1, Pa) 1
Density (kg/m^3) 1.204 Loss Coefficient (Co) 0.15
Loss Coefficient (C1) 0.45
Pressure Loss (Pa) 0

01/22/2023 d:\project\ncp\static\ef-08\ef-08.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 150 Branch


Width (W, mm) 600 BranchVelocity (Vb, m/s) 1.4
Height (Hb, mm) 850 Vel Pres at Vb (Pvb, Pa) 1
Width (Wb, mm) 100 Loss Coefficient (Cb) 0.66
Flow Rate (Qs, L/s) 117 Branch Pressure Loss (Pa) 1
Flow Rate (Qb, L/s) 117 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 1.3
Velocity (Vc, m/s) 2.6
Vel Pres at Vs (Pvs, Pa) 1
Vel Pres at Vc (Pvc, Pa) 4
Loss Coefficient (Cs) 2.23
Main Pressure Loss (Pa) 2

01/22/2023 d:\project\ncp\static\ef-08\ef-08.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(CR3-1) Elbow, Smooth Radius without Vanes


(Idelchik 1986, Diagram 6-1)

INPUTS OUTPUTS

Width (W, mm) 600 Velocity (Vo, m/s) 3.9


Height (H, mm) 150 Vel Pres at Vo (Pv, Pa) 9
Radius Ratio (r/W) 0.8 Loss Coefficient (Co) 0.51
Angle (Theta, deg.) 90 Pressure Loss (Pa) 5
Flow Rate (Q, L/s) 354
Density (kg/m^3) 1.204

01/22/2023 d:\project\ncp\static\ef-08\ef-08.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER4-3) Transition, Rectangular to Round, Exhaust/Return Systems


(Idelchik 1986, Diagram 5-27)

INPUTS OUTPUTS

Height (Ho, mm) 150 Angle (Theta1, deg.) 14


Width (Wo, mm) 600 Angle (Theta2, deg.) 28
Diameter (D1, mm) 300 Velocity (Vo, m/s) 3.9
Length (L, mm) 600 Velocity (V1, m/s) 5.0
Flow Rate (Q, L/s) 354 Vel Pres at Vo (Pvo, Pa) 9
Density (kg/m^3) 1.204 Vel Pres at V1 (Pv1, Pa) 15
Loss Coefficient (Co) 0.06
Loss Coefficient (C1) 0.03
Pressure Loss (Pa) 1

01/22/2023 d:\project\ncp\static\ef-08\ef-08.adf version: 6.00.04


Duct Accessories
Air Grille
Fire Damper
Back Draft Damper
SUGGESTED SPECIFICATION
Furnish and install, at locations shown on plans or in accordance resistant, long life synthetic type for quiet operation. Linkage shall
with schedules, heavy duty backdraft dampers that meet the follow- be 1 /2 " (13) wide tiebar connected to stainless steel pivot
ing minimum construction standards: Frame shall be .125" (3.2) pins. Dampers shall be designed for maximum 3500 fpm spot
wall thickness 6063T5 extruded aluminum with 12 gage (2.8) gal- velocities and minimum 4 inches w.g. back pressure depending on
vanized steel structural brace at each corner. Blades shall be .070" damper size. Dampers shall be in all respects equivalent to
(1.8) wall thickness 6063T5 extruded aluminum with extruded vinyl Ruskin model CBD6.
blade edge seals mechanically locked into blade edge. Adhesive or
clip on type seals are unacceptable. Bearings shall be
corrosion
INSTALLATION

1. When used in fan discharge applications, damper should 3. Bracing of multiple section assemblies:
be located at least one-half the fan diameter away from the fan. The CBD6 is intended to be self supporting only in the largest
single section size. Multiple section damper assemblies
2. For proper operation, damper must be installed square and free may require bracing to support the weight of the assembly
from racking. and to hold against system pressure. Ruskin recommends
appropriate bracing to support the damper horizontally at
least once for every 8 feet of damper width. Vertical
assemblies and higher system pressures may require more
PERFORMANCE DATA bracing.

DAMPER PERFORMANCE
LEAKAGE* BLADES BLADES
MAXIMUM MAXIMUM SYSTEM
DAMPER WIDTH Percent of CFM/ START TO FULLY
BACK PRESSURE VELOCITY
Max. Flow Sq. Ft. OPEN OPEN

48" (1219) 4.0" w.g. 2500 FPM .6% 15


36" (914) 8.0" w.g. 2500 FPM .6% 15 .01" w.g. .05" w.g.
24" (610) 12.0" w.g. 2500 FPM .7% 17.5
12" (305) 16.0" w.g. 2500 PFM 1% 25

*Leakage information based on pressure differential of 1" w.g. tested per AMCA Std. 500.

DAMPER PRESSURE DROP


(24" x 24")
p p ( [ ] )
0.7
17.78
0.5
12.7
Static Pressure Drop in INCHES and MILLIMETERS of WATER

0.3
7.62

0.2
5.08

0.1
2.54
.07
1.78

.05
1.27

.03
.75

.02
.51

.01
200 300 500 700 1000 2000 3000
60.96 91.44 152.40 213.36 304.80 609.60 914.40

Air velocity in FEET and Meters Per minute through face area
EXF 0
Calculation Sheet
External Static Pressure calculations

Project: NORTH COAST PALACE


MEP contractor : MAGNA ENGINEERING & CONSTRUCTION
Builing Name: MAIN VILLA
FAN TAG EF-09

GENERAL DATA
DUCT MATERIAL: G. I. Sheet
AIR DENSITY:(Kg/m3) 1.2

SECTION (1-1') (2-2') (3-3') (4-4') TOTAL


CFM 100 200 400 600
FLOW L/S 47 94 189 283

M3/H 170 340 680 1019

LENGTH M 4.0 1.5 1.5 2.0

DIAM. mm 164 219 266 305

DIAM. EQUIV. mm 164 219 266 305

WIDTH mm 150 200 300 400

HEIGHT mm 150 200 200 200

AREA M2 0.021 0.038 0.056 0.073

VELOCITY M/S 2.23 2.51 3.39 3.88

PD per Meter Pa 0.51 0.45 0.61 0.66

PD x LENGTH Pa 2.06 0.67 0.91 1.32 5

PA (1-1') (2-2') (3-3') (4-4') TOTAL

Plenum Box 1 1
Flexible Duct 3 1
Transition 1 1
Tee Branch 2 1
Tee Main 2 1
Transition 1 1
Tee Main 2 2
Transition 1 1
Tee Main 1 2
Transition 1 1
Transition 3 1

TOTAL PA 7 3 5 6 0 0 0 0 0 0 21

DUCTS PD Pa 7 3 5 6 0 0 0 0 0 0 21

PRESSURE DROP Pa 9 4 6 7 0 0 0 0 0 0 26

SPECIAL FITTING PRESSURE DROPS

`
DESIGNATION PD (PA) QTY TOTAL
Canvas 5 2 10 FLOW AT 100% (m3/hr) 1019

Return slot Diffuser 20 1 20 * DUCTS PRESSURE DROP : 26


Volume damper (1) 6 1 6 * FITTING PRESSURE DROP : 111
Back Draft Damper 5 1 5 STATIC PRESSURE AT 100% PA 137
Exhaust Air Louvre 70 1 70 *TOTAL EXTERNAL STATIC PRESSURE + 10% SF PA 151

0 STATIC PRESSURE AT 100%(in) 0.55

0 *TOTAL EXTERNAL STATIC PRESSURE + 15% SF (in) 0.60

0
TOTAL 111
Drawing
Duct Fittings
Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(ER2-1) Bellmouth, Plenum to Round, Exhaust/Return Systems


(Idelchik 1986, Diagram 4-9)

INPUTS OUTPUTS

Diameter (D1, mm) 150 Velocity (Vo, m/s) 0.2


Plenum Height (Ho, mm) 250 Velocity (V1, m/s) 2.7
Plenum Width (Wo, mm) 1200 Vel Pres at Vo (Pvo, Pa) 0
Flow Rate (Q, L/s) 48 Vel Pres at V1 (Pv1, Pa) 4
Density (kg/m^3) 1.204 Bellmouth Radius (r, mm) 50
Loss Coefficient (Co) 8.26
Loss Coefficient (C1) 0.03
Pressure Loss (Pa) 0

01/23/2023 d:\project\ncp\static\ef-09\ef-09.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(CD11-2) Straight Duct, Flexible


(Abushakra 2004 and Culp 2011

INPUTS OUTPUTS

Flow Rate (Q, L/s) 48 Velocity (V, m/s) 2.7


Diameter (D, mm) 150 Vel Pres at Vo (Pv, Pa) 4
Installed Length (L, m) 0.4 Compressed (%) 20
Length Fully Extended (m) 0.5 Pressure Drop Correction Factor (PDCF) 6.5
Density (kg/m^3) 1.204 Pressure Loss (Pa) 3

FULLY EXTENDED

LESS THAN FULLY EXTENDED

01/23/2023 d:\project\ncp\static\ef-09\ef-09.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(SR4-3) Transition, Round to Rectangular, Supply Air Systems


(Idelchik 1986, Diagram 5-27)

INPUTS OUTPUTS

Diameter (D1, mm) 150 Angle (Theta1, deg.) 0


Height (Ho, mm) 150 Angle (Theta2, deg.) 0
Width (Wo, mm) 150 Velocity (Vo, m/s) 2.1
Length (L, mm) 300 Velocity (V1, m/s) 2.7
Flow Rate (Q, L/s) 48 Vel Pres at Vo (Pvo, Pa) 3
Density (kg/m^3) 1.204 Vel Pres at V1 (Pv1, Pa) 4
Loss Coefficient (Co) 0.00
Loss Coefficient (C1) 0.00
Pressure Loss (Pa) 0

01/23/2023 d:\project\ncp\static\ef-09\ef-09.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 200 Branch


Width (W, mm) 200 BranchVelocity (Vb, m/s) 2.1
Height (Hb, mm) 150 Vel Pres at Vb (Pvb, Pa) 3
Width (Wb, mm) 150 Loss Coefficient (Cb) 0.66
Flow Rate (Qs, L/s) 47 Branch Pressure Loss (Pa) 2
Flow Rate (Qb, L/s) 47 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 1.2
Velocity (Vc, m/s) 2.4
Vel Pres at Vs (Pvs, Pa) 1
Vel Pres at Vc (Pvc, Pa) 3
Loss Coefficient (Cs) 2.23
Main Pressure Loss (Pa) 2

01/23/2023 d:\project\ncp\static\ef-09\ef-09.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 200 Branch


Width (W, mm) 200 BranchVelocity (Vb, m/s) 2.1
Height (Hb, mm) 150 Vel Pres at Vb (Pvb, Pa) 3
Width (Wb, mm) 150 Loss Coefficient (Cb) 0.66
Flow Rate (Qs, L/s) 47 Branch Pressure Loss (Pa) 2
Flow Rate (Qb, L/s) 47 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 1.2
Velocity (Vc, m/s) 2.4
Vel Pres at Vs (Pvs, Pa) 1
Vel Pres at Vc (Pvc, Pa) 3
Loss Coefficient (Cs) 2.23
Main Pressure Loss (Pa) 2

01/23/2023 d:\project\ncp\static\ef-09\ef-09.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(ER4-1) Transition, Rectangular, Two Sides Parallel, Symmetrical,


Exhaust/Return Systems (Idelchik 1986, Diagram 5-5)

INPUTS OUTPUTS

Height (Ho, mm) 200 Angle (Theta, deg.) 19


Width (Wo, mm) 200 Velocity (Vo, m/s) 2.4
Height (H1, mm) 300 Velocity (V1, m/s) 1.6
Length (L, mm) 300 Vel Pres at Vo (Pvo, Pa) 3
Flow Rate (Q, L/s) 95 Vel Pres at V1 (Pv1, Pa) 2
Density (kg/m^3) 1.204 Loss Coefficient (Co) 0.10
Loss Coefficient (C1) 0.22
Pressure Loss (Pa) 0

01/23/2023 d:\project\ncp\static\ef-09\ef-09.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 200 Branch


Width (W, mm) 300 BranchVelocity (Vb, m/s) 2.1
Height (Hb, mm) 150 Vel Pres at Vb (Pvb, Pa) 3
Width (Wb, mm) 150 Loss Coefficient (Cb) -2.28
Flow Rate (Qs, L/s) 142 Branch Pressure Loss (Pa) -6
Flow Rate (Qb, L/s) 47 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 2.4
Velocity (Vc, m/s) 3.2
Vel Pres at Vs (Pvs, Pa) 3
Vel Pres at Vc (Pvc, Pa) 6
Loss Coefficient (Cs) 0.56
Main Pressure Loss (Pa) 2

01/23/2023 d:\project\ncp\static\ef-09\ef-09.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(ER4-1) Transition, Rectangular, Two Sides Parallel, Symmetrical,


Exhaust/Return Systems (Idelchik 1986, Diagram 5-5)

INPUTS OUTPUTS

Height (Ho, mm) 300 Angle (Theta, deg.) 19


Width (Wo, mm) 200 Velocity (Vo, m/s) 3.2
Height (H1, mm) 400 Velocity (V1, m/s) 2.4
Length (L, mm) 300 Vel Pres at Vo (Pvo, Pa) 6
Flow Rate (Q, L/s) 189 Vel Pres at V1 (Pv1, Pa) 3
Density (kg/m^3) 1.204 Loss Coefficient (Co) 0.07
Loss Coefficient (C1) 0.13
Pressure Loss (Pa) 0

01/23/2023 d:\project\ncp\static\ef-09\ef-09.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 200 Branch


Width (W, mm) 400 BranchVelocity (Vb, m/s) 2.1
Height (Hb, mm) 150 Vel Pres at Vb (Pvb, Pa) 3
Width (Wb, mm) 150 Loss Coefficient (Cb) -9.05
Flow Rate (Qs, L/s) 236 Branch Pressure Loss (Pa) -24
Flow Rate (Qb, L/s) 47 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 3.0
Velocity (Vc, m/s) 3.5
Vel Pres at Vs (Pvs, Pa) 5
Vel Pres at Vc (Pvc, Pa) 8
Loss Coefficient (Cs) 0.29
Main Pressure Loss (Pa) 1

01/23/2023 d:\project\ncp\static\ef-09\ef-09.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(ER4-3) Transition, Rectangular to Round, Exhaust/Return Systems


(Idelchik 1986, Diagram 5-27)

INPUTS OUTPUTS

Height (Ho, mm) 200 Angle (Theta1, deg.) 19


Width (Wo, mm) 400 Angle (Theta2, deg.) 19
Diameter (D1, mm) 300 Velocity (Vo, m/s) 3.5
Length (L, mm) 300 Velocity (V1, m/s) 4.0
Flow Rate (Q, L/s) 283 Vel Pres at Vo (Pvo, Pa) 8
Density (kg/m^3) 1.204 Vel Pres at V1 (Pv1, Pa) 10
Loss Coefficient (Co) 0.03
Loss Coefficient (C1) 0.03
Pressure Loss (Pa) 0

01/23/2023 d:\project\ncp\static\ef-09\ef-09.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(SR4-3) Transition, Round to Rectangular, Supply Air Systems


(Idelchik 1986, Diagram 5-27)

INPUTS OUTPUTS

Diameter (D1, mm) 300 Angle (Theta1, deg.) 14


Height (Ho, mm) 150 Angle (Theta2, deg.) 53
Width (Wo, mm) 900 Velocity (Vo, m/s) 2.1
Length (L, mm) 600 Velocity (V1, m/s) 4.0
Flow Rate (Q, L/s) 283 Vel Pres at Vo (Pvo, Pa) 3
Density (kg/m^3) 1.204 Vel Pres at V1 (Pv1, Pa) 10
Loss Coefficient (Co) 1.18
Loss Coefficient (C1) 0.32
Pressure Loss (Pa) 3

01/23/2023 d:\project\ncp\static\ef-09\ef-09.adf version: 6.00.04


Duct Accessories
Slot Diffuser
Volume Damper

%# ( # & & # " #


& ' "
Back Draft Damper
SUGGESTED SPECIFICATION
Furnish and install, at locations shown on plans or in accordance resistant, long life synthetic type for quiet operation. Linkage shall
with schedules, heavy duty backdraft dampers that meet the follow- be 1 /2 " (13) wide tiebar connected to stainless steel pivot
ing minimum construction standards: Frame shall be .125" (3.2) pins. Dampers shall be designed for maximum 3500 fpm spot
wall thickness 6063T5 extruded aluminum with 12 gage (2.8) gal- velocities and minimum 4 inches w.g. back pressure depending on
vanized steel structural brace at each corner. Blades shall be .070" damper size. Dampers shall be in all respects equivalent to
(1.8) wall thickness 6063T5 extruded aluminum with extruded vinyl Ruskin model CBD6.
blade edge seals mechanically locked into blade edge. Adhesive or
clip on type seals are unacceptable. Bearings shall be
corrosion
INSTALLATION

1. When used in fan discharge applications, damper should 3. Bracing of multiple section assemblies:
be located at least one-half the fan diameter away from the fan. The CBD6 is intended to be self supporting only in the largest
single section size. Multiple section damper assemblies
2. For proper operation, damper must be installed square and free may require bracing to support the weight of the assembly
from racking. and to hold against system pressure. Ruskin recommends
appropriate bracing to support the damper horizontally at
least once for every 8 feet of damper width. Vertical
assemblies and higher system pressures may require more
PERFORMANCE DATA bracing.

DAMPER PERFORMANCE
LEAKAGE* BLADES BLADES
MAXIMUM MAXIMUM SYSTEM
DAMPER WIDTH Percent of CFM/ START TO FULLY
BACK PRESSURE VELOCITY
Max. Flow Sq. Ft. OPEN OPEN

48" (1219) 4.0" w.g. 2500 FPM .6% 15


36" (914) 8.0" w.g. 2500 FPM .6% 15 .01" w.g. .05" w.g.
24" (610) 12.0" w.g. 2500 FPM .7% 17.5
12" (305) 16.0" w.g. 2500 PFM 1% 25

*Leakage information based on pressure differential of 1" w.g. tested per AMCA Std. 500.

DAMPER PRESSURE DROP


(24" x 24")
p p ( [ ] )
0.7
17.78
0.5
12.7
Static Pressure Drop in INCHES and MILLIMETERS of WATER

0.3
7.62

0.2
5.08

0.1
2.54
.07
1.78

.05
1.27

.03
.75

.02
.51

.01
200 300 500 700 1000 2000 3000
60.96 91.44 152.40 213.36 304.80 609.60 914.40

Air velocity in FEET and Meters Per minute through face area
Air Louver

Chart 1
700
Static Pressure Drop (inches w.g.)

600

500

400
x 10-3

300

200

100

0
0 500 1000 1500 2000 2500

Free Area Velocity (ft/min)

Example 1
Given air flow rate of 1500 cfm select a louver size

Dividing flow rate by free area velocity (let say 600 fpm )

Free area = 2.5 ft2 , from the table above , 34”X 22” will be the least louver satisfy the
desired free velocity

Note : other selections are also available

Determine free velocity 1500 /2.51 = 597 fpm

Check for pressure drop across the louver at 597 fpm from chart 1 = 0.06 Wg “

Example 2
Knowing louver size as 24”X28” determine the maximum flow rate

From table 1 free area = 2.28 feet2

For velocity 800 fpm the flow rate = 2.28X 800 = 1824 cfm

Check for pressure drop across the louver at 800 fpm from chart 1 = 0.14 Wg “
Air Louver

Free area for ZAL- S

Free area for ZAL- L


EXF 10
Calculation Sheet
External Static Pressure calculations

Project: NORTH COAST PALACE


MEP contractor : MAGNA ENGINEERING & CONSTRUCTION
Builing Name: MAIN VILLA
FAN TAG EF-10

GENERAL DATA
DUCT MATERIAL: G. I. Sheet
AIR DENSITY:(Kg/m3) 1.2

SECTION (1-1') TOTAL


CFM 500

FLOW L/S 236

M3/H 850

LENGTH M 17.0

DIAM. mm 274

DIAM. EQUIV. mm 274

WIDTH mm 450

HEIGHT mm 150

AREA M2 0.059

VELOCITY M/S 4.00

PD per Meter Pa 0.80

PD x LENGTH Pa 13.52 14

PA (1-1') TOTAL

Tee Branch (1) 1 1


Elbow 90 (1.1) 4 6
Rect. To Round (1) 1 1
Round To Rect. (1) 7 1
Elbow 90 (1.2) 1 3
TOTAL PA 36 36
DUCTS PD Pa 36 36

PRESSURE DROP Pa 50 50

SPECIAL FITTING PRESSURE DROPS

DESIGNATION PD (PA) QTY TOTAL

Canvas 5 1 5 FLOW AT 100% (m3/hr) 850

Exhaust Round Diffuser 11 1 11 * DUCTS PRESSURE DROP : 50

Fire Damper 10 1 10 * FITTING PRESSURE DROP : 34

Wire Mesh 1 1 1 STATIC PRESSURE AT 100% PA 84


Back Draft Damper 7 1 7 *TOTAL EXTERNAL STATIC PRESSURE + 10% SF PA 92

STATIC PRESSURE AT 100%(in) 0.33

*TOTAL EXTERNAL STATIC PRESSURE + 10% SF (in) 0.37

TOTAL 34
Drawing
Duct Fittings
Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 150 Branch


Width (W, mm) 450 BranchVelocity (Vb, m/s) 1.5
Height (Hb, mm) 400 Vel Pres at Vb (Pvb, Pa) 1
Width (Wb, mm) 400 Loss Coefficient (Cb) 0.83
Flow Rate (Qs, L/s) 10 Branch Pressure Loss (Pa) 1
Flow Rate (Qb, L/s) 236 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 0.1
Velocity (Vc, m/s) 3.6
Vel Pres at Vs (Pvs, Pa) 0
Vel Pres at Vc (Pvc, Pa) 8
Loss Coefficient (Cs) 32.73
Main Pressure Loss (Pa) 0

01/23/2023 d:\hat project\ncp\calculations\exhaust fan\ef-10\ef-10.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(CR3-1) Elbow, Smooth Radius without Vanes


(Idelchik 1986, Diagram 6-1)

INPUTS OUTPUTS

Width (W, mm) 450 Velocity (Vo, m/s) 3.5


Height (H, mm) 150 Vel Pres at Vo (Pv, Pa) 7
Radius Ratio (r/W) 0.8 Loss Coefficient (Co) 0.50
Angle (Theta, deg.) 90 Pressure Loss (Pa) 4
Flow Rate (Q, L/s) 236
Density (kg/m^3) 1.204

01/23/2023 d:\hat project\ncp\calculations\exhaust fan\ef-10\ef-10.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(ER4-3) Transition, Rectangular to Round, Exhaust/Return Systems


(Idelchik 1986, Diagram 5-27)

INPUTS OUTPUTS

Height (Ho, mm) 150 Angle (Theta1, deg.) 11


Width (Wo, mm) 450 Angle (Theta2, deg.) 23
Diameter (D1, mm) 250 Velocity (Vo, m/s) 3.5
Length (L, mm) 500 Velocity (V1, m/s) 4.8
Flow Rate (Q, L/s) 236 Vel Pres at Vo (Pvo, Pa) 7
Density (kg/m^3) 1.204 Vel Pres at V1 (Pv1, Pa) 14
Loss Coefficient (Co) 0.09
Loss Coefficient (C1) 0.05
Pressure Loss (Pa) 1

01/23/2023 d:\hat project\ncp\calculations\exhaust fan\ef-10\ef-10.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(SR4-3) Transition, Round to Rectangular, Supply Air Systems


(Idelchik 1986, Diagram 5-27)

INPUTS OUTPUTS

Diameter (D1, mm) 250 Angle (Theta1, deg.) 11


Height (Ho, mm) 350 Angle (Theta2, deg.) 28
Width (Wo, mm) 500 Velocity (Vo, m/s) 1.3
Length (L, mm) 500 Velocity (V1, m/s) 4.8
Flow Rate (Q, L/s) 236 Vel Pres at Vo (Pvo, Pa) 1
Density (kg/m^3) 1.204 Vel Pres at V1 (Pv1, Pa) 14
Loss Coefficient (Co) 6.59
Loss Coefficient (C1) 0.52
Pressure Loss (Pa) 7

01/23/2023 d:\hat project\ncp\calculations\exhaust fan\ef-10\ef-10.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(CR3-1) Elbow, Smooth Radius without Vanes


(Idelchik 1986, Diagram 6-1)

INPUTS OUTPUTS

Width (W, mm) 500 Velocity (Vo, m/s) 1.3


Height (H, mm) 350 Vel Pres at Vo (Pv, Pa) 1
Radius Ratio (r/W) 0.8 Loss Coefficient (Co) 0.44
Angle (Theta, deg.) 90 Pressure Loss (Pa) 0
Flow Rate (Q, L/s) 236
Density (kg/m^3) 1.204

01/23/2023 d:\hat project\ncp\calculations\exhaust fan\ef-10\ef-10.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(CR6-1) Screen (Only) (Idelchik 1986, Diagrams 8-6 and 3-15)

INPUTS OUTPUTS

Height (Ho, mm) 350 Open Area (%) 70


Width (Wo, mm) 500 Area Ratio (A1/Ao) 1.54
Height (H1. mm) 450 Velocity (Vo, m/s) 1.3
Width (W1, mm) 600 Vel Pres at Vo (Pv, Pa) 1
Free Area Ratio (n) 0.70 Loss Coefficient (Co) 0.25
Flow Rate (Q, L/s) 236 Pressure Loss (Pa) 0
Density (kg/m^3) 1.204

01/23/2023 d:\hat project\ncp\calculations\exhaust fan\ef-10\ef-10.adf version: 6.00.04


Duct Accessories
Return Diffuser

AL-ANDALOSIA FOR AIR OUTLETS

RETURN AIR ROUND CEILING DIFFUSER

PERFORMANCE DATA

Neck Velocity
300 400 500 600 700 800 1000 1200 1400 1600
Neck Neck (FPM)
Size Area Velocity Pressure 0.007 0.01 0.016 0.023 0.031 0.041 0.064 0.091 0.123 0.161
(inches) (FT²) (inches W.G)
Air flowrate(CFM) 60 80 100 120 135 155 195 235 275 315
6" 0.196 Total pressure drop 0.029 0.04 0.076 0.108 0.146 0.18 0.294 0.421 0.569 0.749
NC <20 <20 <20 <20 21 26 32 37 41 46
Air flowrate(CFM) 105 140 175 210 245 280 350 420 490 560
8" 0.349 Total pressure drop 0.020 0.03 0.053 0.077 0.100 0.123 0.207 0.293 0.394 0.519
NC <20 <20 <20 21 26 30 34 39 43 47
Air flowrate(CFM) 165 220 275 325 380 435 545 655 765 870
10" 0.545 Total pressure drop 0101 0.03 0.050 0.071 0.096 0.120 0.196 0.281 0.379 0.477
NC <20 <20 <20 22 27 31 36 41 45 48
Air flowrate(CFM) 225 315 395 470 550 630 785 940 1100 1255
12" 0.785 Total pressure drop 0.018 0.02 0.045 0.064 0.086 0.112 0.176 0.249 0.339 0.443
NC <20 <20 <20 23 29 33 37 42 46 49
Air flowrate(CFM) 320 430 535 640 750 855 1070 1285 1500 1710
14" 1.07 Total pressure drop 0.017 0.02 0.042 0.061 0.083 0.108 0.170 0.242 0.328 0.430
NC <20 <20 <20 25 30 34 38 43 47 50
Air flowrate(CFM) 420 560 700 840 980 1120 1400 1680 1960 2240
16" 1.40 Total pressure drop 0.016 0.02 0.041 0.059 0.079 0.103 0.162 0.231 0.314 0.411
NC <20 <20 21 26 31 35 39 44 48 51
Air flowrate(CFM) 530 710 885 1060 1240 1415 1770 2125 2480 2830
18" 1.77 Total pressure drop 0.015 0.02 0.040 0.057 0.077 0.099 0.156 0.224 0.303 0.397
NC <20 <20 22 27 32 36 40 45 49 52
Air flowrate(CFM) 660 850 1100 1300 1530 1750 2150 2650 3050 3500
20" 2.18 Total pressure drop 0.014 0.02 0.036 0.052 0.071 0.091 0.143 0.205 0.277 0.363
NC <20 <20 21 28 33 37 41 46 50 53
Air flowrate(CFM) 940 1250 1570 1850 2200 2500 3130 3850 4320 4950
24" 3.14 Total pressure drop 0.013 0.02 0.031 0.046 0.064 0.082 0.130 0.185 0.246 0.326
NC <20 <20 23 29 34 38 42 47 51 55

Notes : ─Noise Level→db ─Air Flow→CFM ─Total Pressure → IN W.G


Fire Damper
Back Draft Damper
SUGGESTED SPECIFICATION
Furnish and install, at locations shown on plans or in accordance resistant, long life synthetic type for quiet operation. Linkage shall
with schedules, heavy duty backdraft dampers that meet the follow- be 1 /2 " (13) wide tiebar connected to stainless steel pivot
ing minimum construction standards: Frame shall be .125" (3.2) pins. Dampers shall be designed for maximum 3500 fpm spot
wall thickness 6063T5 extruded aluminum with 12 gage (2.8) gal- velocities and minimum 4 inches w.g. back pressure depending on
vanized steel structural brace at each corner. Blades shall be .070" damper size. Dampers shall be in all respects equivalent to
(1.8) wall thickness 6063T5 extruded aluminum with extruded vinyl Ruskin model CBD6.
blade edge seals mechanically locked into blade edge. Adhesive or
clip on type seals are unacceptable. Bearings shall be
corrosion
INSTALLATION

1. When used in fan discharge applications, damper should 3. Bracing of multiple section assemblies:
be located at least one-half the fan diameter away from the fan. The CBD6 is intended to be self supporting only in the largest
single section size. Multiple section damper assemblies
2. For proper operation, damper must be installed square and free may require bracing to support the weight of the assembly
from racking. and to hold against system pressure. Ruskin recommends
appropriate bracing to support the damper horizontally at
least once for every 8 feet of damper width. Vertical
assemblies and higher system pressures may require more
PERFORMANCE DATA bracing.

DAMPER PERFORMANCE
LEAKAGE* BLADES BLADES
MAXIMUM MAXIMUM SYSTEM
DAMPER WIDTH Percent of CFM/ START TO FULLY
BACK PRESSURE VELOCITY
Max. Flow Sq. Ft. OPEN OPEN

48" (1219) 4.0" w.g. 2500 FPM .6% 15


36" (914) 8.0" w.g. 2500 FPM .6% 15 .01" w.g. .05" w.g.
24" (610) 12.0" w.g. 2500 FPM .7% 17.5
12" (305) 16.0" w.g. 2500 PFM 1% 25

*Leakage information based on pressure differential of 1" w.g. tested per AMCA Std. 500.

DAMPER PRESSURE DROP


(24" x 24")
p p ( [ ] )
0.7
17.78
0.5
12.7
Static Pressure Drop in INCHES and MILLIMETERS of WATER

0.3
7.62

0.2
5.08

0.1
2.54
.07
1.78

.05
1.27

.03
.75

.02
.51

.01
200 300 500 700 1000 2000 3000
60.96 91.44 152.40 213.36 304.80 609.60 914.40

Air velocity in FEET and Meters Per minute through face area
EXF 11
Calculation Sheet
External Static Pressure calculations

Project: NORTH COAST PALACE


MEP contractor : MAGNA ENGINEERING & CONSTRUCTION
Builing Name: MAIN VILLA
FAN TAG EF-11

GENERAL DATA
DUCT MATERIAL: G. I. Sheet
AIR DENSITY:(Kg/m3) 1.2

SECTION (1-1') (2-2') (3-3') TOTAL


CFM 150 300 450

FLOW L/S 71 142 212

M3/H 255 510 765

LENGTH M 1.7 1.0 3.0

DIAM. mm 152 189 219

DIAM. EQUIV. mm 152 189 219

WIDTH mm 200 200 200

HEIGHT mm 100 150 200

AREA M2 0.018 0.028 0.038

VELOCITY M/S 3.88 5.05 5.66

PD per Meter Pa 1.54 1.91 1.97

PD x LENGTH Pa 2.62 1.91 5.90 10

PA (1-1') (2-2') (3-3') TOTAL

Tee Branch (1) 1 1


Elbow 90 (1) 1 1
Transition (1) 1 1
Tee Main (2) 3 1
Transition (2) 1 1
Tee Main (3) 3 1
Elbow 90 (3) 3 2
Rect. To Round (3) 2 1
TOTAL PA 3 4 11 0 0 0 0 0 0 0 18

DUCTS PD Pa 3 4 11 0 0 0 0 0 0 0 18

PRESSURE DROP Pa 6 6 17 0 0 0 0 0 0 0 28

SPECIAL FITTING PRESSURE DROPS

DESIGNATION PD (PA) QTY TOTAL

Canvas 5 1 5 FLOW AT 100% (m3/hr) 765

Volume damper (1) 9 1 9 * DUCTS PRESSURE DROP : 28

Fire damper (1) 28 1 28 * FITTING PRESSURE DROP : 117

Fire damper (3) 40 1 40 STATIC PRESSURE AT 100% PA 145

Flexible Connection 2 1 2 *TOTAL EXTERNAL STATIC PRESSURE + 10% SF PA 160

Linear Slot Diffuser 20 1 20 STATIC PRESSURE AT 100%(in) 0.58

Back Draft Damper 13 1 13 *TOTAL EXTERNAL STATIC PRESSURE + 10% SF (in) 0.64

TOTAL 117
Drawing
Duct Fittings
Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(ER2-1) Bellmouth, Plenum to Round, Exhaust/Return Systems


(Idelchik 1986, Diagram 4-9)

INPUTS OUTPUTS

Diameter (D1, mm) 200 Velocity (Vo, m/s) 1.6


Plenum Height (Ho, mm) 300 Velocity (V1, m/s) 2.3
Plenum Width (Wo, mm) 150 Vel Pres at Vo (Pvo, Pa) 1
Flow Rate (Q, L/s) 71 Vel Pres at V1 (Pv1, Pa) 3
Density (kg/m^3) 1.204 Bellmouth Radius (r, mm) 50
Loss Coefficient (Co) 0.03
Loss Coefficient (C1) 0.01
Pressure Loss (Pa) 0

01/23/2023 d:\hat project\ncp\calculations\exhaust fan\ef-11\ef-11.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(CD11-2) Straight Duct, Flexible


(Abushakra 2004 and Culp 2011

INPUTS OUTPUTS

Flow Rate (Q, L/s) 71 Velocity (V, m/s) 2.3


Diameter (D, mm) 200 Vel Pres at Vo (Pv, Pa) 3
Installed Length (L, m) 0.5 Compressed (%) 29
Length Fully Extended (m) 0.7 Pressure Drop Correction Factor (PDCF) 7.1
Density (kg/m^3) 1.204 Pressure Loss (Pa) 2

FULLY EXTENDED

LESS THAN FULLY EXTENDED

01/23/2023 d:\hat project\ncp\calculations\exhaust fan\ef-11\ef-11.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(CR3-1) Elbow, Smooth Radius without Vanes


(Idelchik 1986, Diagram 6-1)

INPUTS OUTPUTS

Width (W, mm) 200 Velocity (Vo, m/s) 2.4


Height (H, mm) 150 Vel Pres at Vo (Pv, Pa) 3
Radius Ratio (r/W) 0.8 Loss Coefficient (Co) 0.43
Angle (Theta, deg.) 90 Pressure Loss (Pa) 1
Flow Rate (Q, L/s) 71
Density (kg/m^3) 1.204

01/23/2023 d:\hat project\ncp\calculations\exhaust fan\ef-11\ef-11.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(ER4-2) Transition, Pyramidal, Exhaust/Return Systems


(Idelchik 1986, Diagram 5-4)

INPUTS OUTPUTS

Height (Ho, mm) 150 Angle (Theta1, deg.) 7


Width (Wo, mm) 200 Angle (Theta2, deg.) 7
Height (H1, mm) 200 Velocity (Vo, m/s) 2.4
Width (W1, mm) 250 Velocity (V1, m/s) 1.4
Length (L, mm) 400 Vel Pres at Vo (Pvo, Pa) 3
Flow Rate (Q, L/s) 71 Vel Pres at V1 (Pv1, Pa) 1
Density (kg/m^3) 1.204 Loss Coefficient (Co) 0.12
Loss Coefficient (C1) 0.32
Pressure Loss (Pa) 0

01/23/2023 d:\hat project\ncp\calculations\exhaust fan\ef-11\ef-11.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 200 Branch


Width (W, mm) 250 BranchVelocity (Vb, m/s) 2.4
Height (Hb, mm) 150 Vel Pres at Vb (Pvb, Pa) 3
Width (Wb, mm) 200 Loss Coefficient (Cb) 0.66
Flow Rate (Qs, L/s) 71 Branch Pressure Loss (Pa) 2
Flow Rate (Qb, L/s) 71 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 1.4
Velocity (Vc, m/s) 2.8
Vel Pres at Vs (Pvs, Pa) 1
Vel Pres at Vc (Pvc, Pa) 5
Loss Coefficient (Cs) 2.23
Main Pressure Loss (Pa) 3

01/23/2023 d:\hat project\ncp\calculations\exhaust fan\ef-11\ef-11.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(ER4-2) Transition, Pyramidal, Exhaust/Return Systems


(Idelchik 1986, Diagram 5-4)

INPUTS OUTPUTS

Height (Ho, mm) 200 Angle (Theta1, deg.) 0


Width (Wo, mm) 250 Angle (Theta2, deg.) 7
Height (H1, mm) 250 Velocity (Vo, m/s) 2.8
Width (W1, mm) 250 Velocity (V1, m/s) 2.3
Length (L, mm) 400 Vel Pres at Vo (Pvo, Pa) 5
Flow Rate (Q, L/s) 142 Vel Pres at V1 (Pv1, Pa) 3
Density (kg/m^3) 1.204 Loss Coefficient (Co) 0.06
Loss Coefficient (C1) 0.09
Pressure Loss (Pa) 0

01/23/2023 d:\hat project\ncp\calculations\exhaust fan\ef-11\ef-11.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 250 Branch


Width (W, mm) 250 BranchVelocity (Vb, m/s) 2.4
Height (Hb, mm) 150 Vel Pres at Vb (Pvb, Pa) 3
Width (Wb, mm) 200 Loss Coefficient (Cb) -0.33
Flow Rate (Qs, L/s) 142 Branch Pressure Loss (Pa) -1
Flow Rate (Qb, L/s) 71 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 2.3
Velocity (Vc, m/s) 3.4
Vel Pres at Vs (Pvs, Pa) 3
Vel Pres at Vc (Pvc, Pa) 7
Loss Coefficient (Cs) 0.95
Main Pressure Loss (Pa) 3

01/23/2023 d:\hat project\ncp\calculations\exhaust fan\ef-11\ef-11.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(CR3-1) Elbow, Smooth Radius without Vanes


(Idelchik 1986, Diagram 6-1)

INPUTS OUTPUTS

Width (W, mm) 250 Velocity (Vo, m/s) 3.4


Height (H, mm) 250 Vel Pres at Vo (Pv, Pa) 7
Radius Ratio (r/W) 0.8 Loss Coefficient (Co) 0.39
Angle (Theta, deg.) 90 Pressure Loss (Pa) 3
Flow Rate (Q, L/s) 212
Density (kg/m^3) 1.204

01/23/2023 d:\hat project\ncp\calculations\exhaust fan\ef-11\ef-11.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(ER4-3) Transition, Rectangular to Round, Exhaust/Return Systems


(Idelchik 1986, Diagram 5-27)

INPUTS OUTPUTS

Height (Ho, mm) 250 Angle (Theta1, deg.) 7


Width (Wo, mm) 250 Angle (Theta2, deg.) 7
Diameter (D1, mm) 200 Velocity (Vo, m/s) 3.4
Length (L, mm) 400 Velocity (V1, m/s) 6.7
Flow Rate (Q, L/s) 212 Vel Pres at Vo (Pvo, Pa) 7
Density (kg/m^3) 1.204 Vel Pres at V1 (Pv1, Pa) 27
Loss Coefficient (Co) 0.26
Loss Coefficient (C1) 0.07
Pressure Loss (Pa) 2

01/23/2023 d:\hat project\ncp\calculations\exhaust fan\ef-11\ef-11.adf version: 6.00.04


Duct Accessories
Volume Damper

%# ( # & & # " #


& ' "
Fire Damper 1
Fire Damper 3
Slot Diffuser
Back Draft Damper
SUGGESTED SPECIFICATION
Furnish and install, at locations shown on plans or in accordance resistant, long life synthetic type for quiet operation. Linkage shall
with schedules, heavy duty backdraft dampers that meet the follow- be 1 /2 " (13) wide tiebar connected to stainless steel pivot
ing minimum construction standards: Frame shall be .125" (3.2) pins. Dampers shall be designed for maximum 3500 fpm spot
wall thickness 6063T5 extruded aluminum with 12 gage (2.8) gal- velocities and minimum 4 inches w.g. back pressure depending on
vanized steel structural brace at each corner. Blades shall be .070" damper size. Dampers shall be in all respects equivalent to
(1.8) wall thickness 6063T5 extruded aluminum with extruded vinyl Ruskin model CBD6.
blade edge seals mechanically locked into blade edge. Adhesive or
clip on type seals are unacceptable. Bearings shall be
corrosion
INSTALLATION

1. When used in fan discharge applications, damper should 3. Bracing of multiple section assemblies:
be located at least one-half the fan diameter away from the fan. The CBD6 is intended to be self supporting only in the largest
single section size. Multiple section damper assemblies
2. For proper operation, damper must be installed square and free may require bracing to support the weight of the assembly
from racking. and to hold against system pressure. Ruskin recommends
appropriate bracing to support the damper horizontally at
least once for every 8 feet of damper width. Vertical
assemblies and higher system pressures may require more
PERFORMANCE DATA bracing.

DAMPER PERFORMANCE
LEAKAGE* BLADES BLADES
MAXIMUM MAXIMUM SYSTEM
DAMPER WIDTH Percent of CFM/ START TO FULLY
BACK PRESSURE VELOCITY
Max. Flow Sq. Ft. OPEN OPEN

48" (1219) 4.0" w.g. 2500 FPM .6% 15


36" (914) 8.0" w.g. 2500 FPM .6% 15 .01" w.g. .05" w.g.
24" (610) 12.0" w.g. 2500 FPM .7% 17.5
12" (305) 16.0" w.g. 2500 PFM 1% 25

*Leakage information based on pressure differential of 1" w.g. tested per AMCA Std. 500.

DAMPER PRESSURE DROP


(24" x 24")
p p ( [ ] )
0.7
17.78
0.5
12.7
Static Pressure Drop in INCHES and MILLIMETERS of WATER

0.3
7.62

0.2
5.08

0.1
2.54
.07
1.78

.05
1.27

.03
.75

.02
.51

.01
200 300 500 700 1000 2000 3000
60.96 91.44 152.40 213.36 304.80 609.60 914.40

Air velocity in FEET and Meters Per minute through face area
EXF 1
Calculation Sheet
External Static Pressure calculations

Project: NORTH COAST PALACE


MEP contractor : MAGNA ENGINEERING & CONSTRUCTION
Builing Name: MAIN VILLA
FAN TAG EF-12

GENERAL DATA
DUCT MATERIAL: G. I. Sheet
AIR DENSITY:(Kg/m3) 1.2

SECTION (1-1') (2-2') (3-3') (4-4') TOTAL


CFM 75 150 250 430
FLOW L/S 35 71 118 203

M3/H 127 255 425 731

LENGTH M 1.0 2.0 3.0 6.0

DIAM. mm 152 189 210 266

DIAM. EQUIV. mm 152 189 210 266

WIDTH mm 200 200 250 300

HEIGHT mm 100 150 150 200

AREA M2 0.018 0.028 0.035 0.056

VELOCITY M/S 1.94 2.53 3.41 3.64

PD per Meter Pa 0.44 0.54 0.82 0.69

PD x LENGTH Pa 0.44 1.08 2.46 4.15 8

PA (1-1') (2-2') (3-3') (4-4') TOTAL

Tee Branch 4 1
Tee Branch 1 1
Transition 1 1
Tee Main 3 1
Tee Branch 4 1
Tee Main 3 1
Elbow 3 3
Transition 1 1

TOTAL PA 4 2 7 13 0 0 0 0 0 0 26

DUCTS PD Pa 4 2 7 13 0 0 0 0 0 0 26

PRESSURE DROP Pa 4 3 9 17 0 0 0 0 0 0 34

SPECIAL FITTING PRESSURE DROPS

`
DESIGNATION PD (PA) QTY TOTAL
Canvas 5 1 5 FLOW AT 100% (m3/hr) 731

Disk Valve 15 1 15 * DUCTS PRESSURE DROP : 34


Fire Damper 13 1 13 * FITTING PRESSURE DROP : 46
Back Draft Damper 5 1 5 STATIC PRESSURE AT 100% PA 80
Volume Damper (1) 3 1 3 *TOTAL EXTERNAL STATIC PRESSURE + 10% SF PA 88
Volume Damper (3) 5 1 5 STATIC PRESSURE AT 100%(in) 0.32

0 *TOTAL EXTERNAL STATIC PRESSURE + 15% SF (in) 0.35

0
TOTAL 46
Drawing
Duct Fittings
Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(ER5-2) Tee, Round Tap to Rectangular Main [Ab/As=Ab/Ac=0.5; As/Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 100 Branch


Width (W, mm) 200 BranchVelocity (Vb, m/s) 2.0
Diameter (Db, mm) 150 Vel Pres at Vb (Pvb, Pa) 2
Flow Rate (Qs, L/s) 5 Loss Coefficient (Cb) 1.47
Flow Rate (Qb, L/s) 36 Branch Pressure Loss (Pa) 4
Density (kg/m^3) 1.204 Main
MainVelocity (Vs, m/s) 0.3
Velocity (Vc, m/s) 2.1
Vel Pres at Vs (Pvs, Pa) 0
Vel Pres at Vc (Pvc, Pa) 3
Loss Coefficient (Cs) 19.90
Main Pressure Loss (Pa) 1

01/23/2023 d:\project\ncp\static\ef-12\ef-12.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 150 Branch


Width (W, mm) 200 BranchVelocity (Vb, m/s) 1.8
Height (Hb, mm) 100 Vel Pres at Vb (Pvb, Pa) 2
Width (Wb, mm) 200 Loss Coefficient (Cb) 0.66
Flow Rate (Qs, L/s) 36 Branch Pressure Loss (Pa) 1
Flow Rate (Qb, L/s) 36 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 1.2
Velocity (Vc, m/s) 2.4
Vel Pres at Vs (Pvs, Pa) 1
Vel Pres at Vc (Pvc, Pa) 3
Loss Coefficient (Cs) 2.23
Main Pressure Loss (Pa) 2

01/23/2023 d:\project\ncp\static\ef-12\ef-12.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(ER4-1) Transition, Rectangular, Two Sides Parallel, Symmetrical,


Exhaust/Return Systems (Idelchik 1986, Diagram 5-5)

INPUTS OUTPUTS

Height (Ho, mm) 200 Angle (Theta, deg.) 10


Width (Wo, mm) 150 Velocity (Vo, m/s) 2.4
Height (H1, mm) 250 Velocity (V1, m/s) 1.9
Length (L, mm) 300 Vel Pres at Vo (Pvo, Pa) 3
Flow Rate (Q, L/s) 71 Vel Pres at V1 (Pv1, Pa) 2
Density (kg/m^3) 1.204 Loss Coefficient (Co) 0.06
Loss Coefficient (C1) 0.09
Pressure Loss (Pa) 0

01/23/2023 d:\project\ncp\static\ef-12\ef-12.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 150 Branch


Width (W, mm) 250 BranchVelocity (Vb, m/s) 2.1
Height (Hb, mm) 150 Vel Pres at Vb (Pvb, Pa) 3
Width (Wb, mm) 150 Loss Coefficient (Cb) 0.46
Flow Rate (Qs, L/s) 71 Branch Pressure Loss (Pa) 1
Flow Rate (Qb, L/s) 47 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 1.9
Velocity (Vc, m/s) 3.1
Vel Pres at Vs (Pvs, Pa) 2
Vel Pres at Vc (Pvc, Pa) 6
Loss Coefficient (Cs) 1.32
Main Pressure Loss (Pa) 3

01/23/2023 d:\project\ncp\static\ef-12\ef-12.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 200 Branch


Width (W, mm) 300 BranchVelocity (Vb, m/s) 3.1
Height (Hb, mm) 150 Vel Pres at Vb (Pvb, Pa) 6
Width (Wb, mm) 250 Loss Coefficient (Cb) 0.74
Flow Rate (Qs, L/s) 83 Branch Pressure Loss (Pa) 4
Flow Rate (Qb, L/s) 118 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 1.4
Velocity (Vc, m/s) 3.4
Vel Pres at Vs (Pvs, Pa) 1
Vel Pres at Vc (Pvc, Pa) 7
Loss Coefficient (Cs) 3.54
Main Pressure Loss (Pa) 4

01/23/2023 d:\project\ncp\static\ef-12\ef-12.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 200 Branch


Width (W, mm) 300 BranchVelocity (Vb, m/s) 2.2
Height (Hb, mm) 150 Vel Pres at Vb (Pvb, Pa) 3
Width (Wb, mm) 250 Loss Coefficient (Cb) 0.50
Flow Rate (Qs, L/s) 118 Branch Pressure Loss (Pa) 1
Flow Rate (Qb, L/s) 83 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 2.0
Velocity (Vc, m/s) 3.4
Vel Pres at Vs (Pvs, Pa) 2
Vel Pres at Vc (Pvc, Pa) 7
Loss Coefficient (Cs) 1.45
Main Pressure Loss (Pa) 3

01/23/2023 d:\project\ncp\static\ef-12\ef-12.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(CR3-1) Elbow, Smooth Radius without Vanes


(Idelchik 1986, Diagram 6-1)

INPUTS OUTPUTS

Width (W, mm) 300 Velocity (Vo, m/s) 3.4


Height (H, mm) 200 Vel Pres at Vo (Pv, Pa) 7
Radius Ratio (r/W) 0.8 Loss Coefficient (Co) 0.44
Angle (Theta, deg.) 90 Pressure Loss (Pa) 3
Flow Rate (Q, L/s) 203
Density (kg/m^3) 1.204

01/23/2023 d:\project\ncp\static\ef-12\ef-12.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(ER4-3) Transition, Rectangular to Round, Exhaust/Return Systems


(Idelchik 1986, Diagram 5-27)

INPUTS OUTPUTS

Height (Ho, mm) 200 Angle (Theta1, deg.) 10


Width (Wo, mm) 300 Angle (Theta2, deg.) 0
Diameter (D1, mm) 300 Velocity (Vo, m/s) 3.4
Length (L, mm) 600 Velocity (V1, m/s) 2.9
Flow Rate (Q, L/s) 203 Vel Pres at Vo (Pvo, Pa) 7
Density (kg/m^3) 1.204 Vel Pres at V1 (Pv1, Pa) 5
Loss Coefficient (Co) 0.05
Loss Coefficient (C1) 0.06
Pressure Loss (Pa) 0

01/23/2023 d:\project\ncp\static\ef-12\ef-12.adf version: 6.00.04


Duct Accessories
Disk Valve

Return air

Neck position Air flow rate


Size in of disc CFM 10 20 40 60 80 100 150 200
Inches M 0.005 0.0094 0.0189 0.0283 0.0378 0.0472 0.071 0.094
P 0.4 <0.4 1.63 3.8 5.8 9.7
Max NC 20 <20 <20 23 31 37 ……. …….
P 0.4 0.76 2.5 5.6 9.7 14.7
4
MED. NC 20 <20 <20 30 35 45 ……. …….
P 0.61 2.24 7.6 15.2 >20 >20
MIN.
NC 20 <20 35 40 >45 >45 ……. …….
P 0.4 <0.4 0.71 1.42 4.1 4.1 9.7
Max NC 20 <20 <20 <20 25 25 37 …….
P 0.4 <0.4 1.83 4.1 11.2 11.2 20
5
MED. NC 20 <20 <20 21 35 35 >45 …….
P 0.4 2.1 7.1 16.8 >20 >20 20
MIN.
NC 20 <20 23 35 >45 >45 >45 …….
P 0.4 <0.4 0.4 0.81 1.43 2.1 5.2 9.7
Max NC 20 <20 <20 <20 <20 <20 28 37
P 0.4 <0.4 0.81 1.74 3.4 5.3 12.2 20
6
MED. NC 20 <20 <20 <20 <20 25 37 45
P 0.4 0.5 1.47 3.8 7.6 14.7 20 20
MIN.
NC 20 <20 <20 <20 27 35 >45 45
P 0.4 <0.4 <0.4 <0.4 0.76 1.12 2.6 4.38
Max NC 20 <20 <20 <20 <20 <20 27 34
P 0.4 <0.4 0.7 1.4 2.3 3.4 8.4 12.2
8
MED. NC 20 <20 <20 <20 <20 20 35 42
P 0.4 0.5 1.62 3.4 7.1 11.2 20 20
MIN.
NC 20 <20 <20 <20 <20 34 >45 45

Where :
P the pressure drop in mm of water
NC based on room attenuation of 10dB
Fire Damper
Back Draft Damper
SUGGESTED SPECIFICATION
Furnish and install, at locations shown on plans or in accordance resistant, long life synthetic type for quiet operation. Linkage shall
with schedules, heavy duty backdraft dampers that meet the follow- be 1 /2 " (13) wide tiebar connected to stainless steel pivot
ing minimum construction standards: Frame shall be .125" (3.2) pins. Dampers shall be designed for maximum 3500 fpm spot
wall thickness 6063T5 extruded aluminum with 12 gage (2.8) gal- velocities and minimum 4 inches w.g. back pressure depending on
vanized steel structural brace at each corner. Blades shall be .070" damper size. Dampers shall be in all respects equivalent to
(1.8) wall thickness 6063T5 extruded aluminum with extruded vinyl Ruskin model CBD6.
blade edge seals mechanically locked into blade edge. Adhesive or
clip on type seals are unacceptable. Bearings shall be
corrosion
INSTALLATION

1. When used in fan discharge applications, damper should 3. Bracing of multiple section assemblies:
be located at least one-half the fan diameter away from the fan. The CBD6 is intended to be self supporting only in the largest
single section size. Multiple section damper assemblies
2. For proper operation, damper must be installed square and free may require bracing to support the weight of the assembly
from racking. and to hold against system pressure. Ruskin recommends
appropriate bracing to support the damper horizontally at
least once for every 8 feet of damper width. Vertical
assemblies and higher system pressures may require more
PERFORMANCE DATA bracing.

DAMPER PERFORMANCE
LEAKAGE* BLADES BLADES
MAXIMUM MAXIMUM SYSTEM
DAMPER WIDTH Percent of CFM/ START TO FULLY
BACK PRESSURE VELOCITY
Max. Flow Sq. Ft. OPEN OPEN

48" (1219) 4.0" w.g. 2500 FPM .6% 15


36" (914) 8.0" w.g. 2500 FPM .6% 15 .01" w.g. .05" w.g.
24" (610) 12.0" w.g. 2500 FPM .7% 17.5
12" (305) 16.0" w.g. 2500 PFM 1% 25

*Leakage information based on pressure differential of 1" w.g. tested per AMCA Std. 500.

DAMPER PRESSURE DROP


(24" x 24")
p p ( [ ] )
0.7
17.78
0.5
12.7
Static Pressure Drop in INCHES and MILLIMETERS of WATER

0.3
7.62

0.2
5.08

0.1
2.54
.07
1.78

.05
1.27

.03
.75

.02
.51

.01
200 300 500 700 1000 2000 3000
60.96 91.44 152.40 213.36 304.80 609.60 914.40

Air velocity in FEET and Meters Per minute through face area
VOLUME DAMPER 01
VOLUME DAMPER 03
EXF 1
Calculation Sheet
External Static Pressure calculations

Project: NORTH COAST PALACE


MEP contractor : MAGNA ENGINEERING & CONSTRUCTION
Builing Name: MAIN VILLA
FAN TAG EF-13

GENERAL DATA
DUCT MATERIAL: G. I. Sheet
AIR DENSITY:(Kg/m3) 1.2

SECTION (1-1') (2-2') (3-3') (4-4') (5-5') (6-6') TOTAL


CFM 66 66 132 200 325 400
FLOW L/S 31 31 62 94 153 189

M3/H 112 112 224 340 552 680

LENGTH M 1.0 1.0 1.0 4.0 1.5 5.0

DIAM. mm 164 152 189 219 244 273

DIAM. EQUIV. mm 164 152 189 219 244 273

WIDTH mm 150 100 150 200 200 250

HEIGHT mm 150 200 200 200 250 250

AREA M2 0.021 0.018 0.028 0.038 0.047 0.059

VELOCITY M/S 1.48 1.71 2.22 2.51 3.28 3.22

PD per Meter Pa 0.24 0.35 0.43 0.45 0.64 0.54

PD x LENGTH Pa 0.24 0.35 0.43 1.80 0.96 2.68 6

PA (1-1') (2-2') (3-3') (4-4') (5-5') (6-6') TOTAL

Plenum Box 1 1
Flexible Duct 1 1
Transition 1 1
Tee Branch 1 1
Transition 1 1
Tee Main 1 1
Transition 1 1
Tee Main 1 1
Elbow 1 2
Transition 1 1
Tee Main 3 1
Elbow 2 1
Transition 1 1
Tee Main 1 1
Elbow 2 4
Transition 1 1

TOTAL PA 4 1 2 4 6 10 0 0 0 0 27

DUCTS PD Pa 4 1 2 4 6 10 0 0 0 0 27

PRESSURE DROP Pa 4 1 2 6 7 13 0 0 0 0 33

SPECIAL FITTING PRESSURE DROPS

`
DESIGNATION PD (PA) QTY TOTAL
Canvas 5 1 5 FLOW AT 100% (m3/hr) 680

Return slot Diffuser 20 1 20 * DUCTS PRESSURE DROP : 33


Volume damper (1) 3 1 3 * FITTING PRESSURE DROP : 52
Fire Damper (6) 10 2 20 STATIC PRESSURE AT 100% PA 85
Back Draft Damper 4 1 4 *TOTAL EXTERNAL STATIC PRESSURE + 10% SF PA 94

0 STATIC PRESSURE AT 100%(in) 0.34

0 *TOTAL EXTERNAL STATIC PRESSURE + 15% SF (in) 0.38

0
TOTAL 52
Drawing
Duct Fittings
Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(ER2-1) Bellmouth, Plenum to Round, Exhaust/Return Systems


(Idelchik 1986, Diagram 4-9)

INPUTS OUTPUTS

Diameter (D1, mm) 150 Velocity (Vo, m/s) 0.1


Plenum Height (Ho, mm) 250 Velocity (V1, m/s) 1.8
Plenum Width (Wo, mm) 1200 Vel Pres at Vo (Pvo, Pa) 0
Flow Rate (Q, L/s) 32 Vel Pres at V1 (Pv1, Pa) 2
Density (kg/m^3) 1.204 Bellmouth Radius (r, mm) 50
Loss Coefficient (Co) 8.26
Loss Coefficient (C1) 0.03
Pressure Loss (Pa) 0

01/23/2023 d:\project\ncp\static\ef-13\ef-13.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(CD11-2) Straight Duct, Flexible


(Abushakra 2004 and Culp 2011

INPUTS OUTPUTS

Flow Rate (Q, L/s) 32 Velocity (V, m/s) 1.8


Diameter (D, mm) 150 Vel Pres at Vo (Pv, Pa) 2
Installed Length (L, m) 0.4 Compressed (%) 20
Length Fully Extended (m) 0.5 Pressure Drop Correction Factor (PDCF) 6.5
Density (kg/m^3) 1.204 Pressure Loss (Pa) 1

FULLY EXTENDED

LESS THAN FULLY EXTENDED

01/23/2023 d:\project\ncp\static\ef-13\ef-13.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(SR4-3) Transition, Round to Rectangular, Supply Air Systems


(Idelchik 1986, Diagram 5-27)

INPUTS OUTPUTS

Diameter (D1, mm) 150 Angle (Theta1, deg.) 0


Height (Ho, mm) 150 Angle (Theta2, deg.) 0
Width (Wo, mm) 150 Velocity (Vo, m/s) 1.4
Length (L, mm) 300 Velocity (V1, m/s) 1.8
Flow Rate (Q, L/s) 32 Vel Pres at Vo (Pvo, Pa) 1
Density (kg/m^3) 1.204 Vel Pres at V1 (Pv1, Pa) 2
Loss Coefficient (Co) 0.00
Loss Coefficient (C1) 0.00
Pressure Loss (Pa) 0

01/23/2023 d:\project\ncp\static\ef-13\ef-13.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 200 Branch


Width (W, mm) 100 BranchVelocity (Vb, m/s) 1.4
Height (Hb, mm) 150 Vel Pres at Vb (Pvb, Pa) 1
Width (Wb, mm) 150 Loss Coefficient (Cb) 0.81
Flow Rate (Qs, L/s) 5 Branch Pressure Loss (Pa) 1
Flow Rate (Qb, L/s) 32 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 0.3
Velocity (Vc, m/s) 1.9
Vel Pres at Vs (Pvs, Pa) 0
Vel Pres at Vc (Pvc, Pa) 2
Loss Coefficient (Cs) 18.55
Main Pressure Loss (Pa) 1

01/23/2023 d:\project\ncp\static\ef-13\ef-13.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(ER4-1) Transition, Rectangular, Two Sides Parallel, Symmetrical,


Exhaust/Return Systems (Idelchik 1986, Diagram 5-5)

INPUTS OUTPUTS

Height (Ho, mm) 100 Angle (Theta, deg.) 10


Width (Wo, mm) 200 Velocity (Vo, m/s) 1.6
Height (H1, mm) 150 Velocity (V1, m/s) 1.1
Length (L, mm) 300 Vel Pres at Vo (Pvo, Pa) 2
Flow Rate (Q, L/s) 32 Vel Pres at V1 (Pv1, Pa) 1
Density (kg/m^3) 1.204 Loss Coefficient (Co) 0.10
Loss Coefficient (C1) 0.22
Pressure Loss (Pa) 0

01/23/2023 d:\project\ncp\static\ef-13\ef-13.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 200 Branch


Width (W, mm) 150 BranchVelocity (Vb, m/s) 1.4
Height (Hb, mm) 150 Vel Pres at Vb (Pvb, Pa) 1
Width (Wb, mm) 150 Loss Coefficient (Cb) 0.66
Flow Rate (Qs, L/s) 32 Branch Pressure Loss (Pa) 1
Flow Rate (Qb, L/s) 32 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 1.1
Velocity (Vc, m/s) 2.1
Vel Pres at Vs (Pvs, Pa) 1
Vel Pres at Vc (Pvc, Pa) 3
Loss Coefficient (Cs) 2.23
Main Pressure Loss (Pa) 2

01/23/2023 d:\project\ncp\static\ef-13\ef-13.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(ER4-1) Transition, Rectangular, Two Sides Parallel, Symmetrical,


Exhaust/Return Systems (Idelchik 1986, Diagram 5-5)

INPUTS OUTPUTS

Height (Ho, mm) 150 Angle (Theta, deg.) 10


Width (Wo, mm) 200 Velocity (Vo, m/s) 2.1
Height (H1, mm) 200 Velocity (V1, m/s) 1.6
Length (L, mm) 300 Vel Pres at Vo (Pvo, Pa) 3
Flow Rate (Q, L/s) 62 Vel Pres at V1 (Pv1, Pa) 1
Density (kg/m^3) 1.204 Loss Coefficient (Co) 0.07
Loss Coefficient (C1) 0.13
Pressure Loss (Pa) 0

01/23/2023 d:\project\ncp\static\ef-13\ef-13.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 200 Branch


Width (W, mm) 200 BranchVelocity (Vb, m/s) 1.4
Height (Hb, mm) 150 Vel Pres at Vb (Pvb, Pa) 1
Width (Wb, mm) 150 Loss Coefficient (Cb) -0.25
Flow Rate (Qs, L/s) 62 Branch Pressure Loss (Pa) 0
Flow Rate (Qb, L/s) 32 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 1.6
Velocity (Vc, m/s) 2.4
Vel Pres at Vs (Pvs, Pa) 1
Vel Pres at Vc (Pvc, Pa) 3
Loss Coefficient (Cs) 0.99
Main Pressure Loss (Pa) 1

01/23/2023 d:\project\ncp\static\ef-13\ef-13.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(CR3-1) Elbow, Smooth Radius without Vanes


(Idelchik 1986, Diagram 6-1)

INPUTS OUTPUTS

Width (W, mm) 200 Velocity (Vo, m/s) 2.4


Height (H, mm) 200 Vel Pres at Vo (Pv, Pa) 3
Radius Ratio (r/W) 0.8 Loss Coefficient (Co) 0.39
Angle (Theta, deg.) 90 Pressure Loss (Pa) 1
Flow Rate (Q, L/s) 95
Density (kg/m^3) 1.204

01/23/2023 d:\project\ncp\static\ef-13\ef-13.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(ER4-1) Transition, Rectangular, Two Sides Parallel, Symmetrical,


Exhaust/Return Systems (Idelchik 1986, Diagram 5-5)

INPUTS OUTPUTS

Height (Ho, mm) 200 Angle (Theta, deg.) 10


Width (Wo, mm) 200 Velocity (Vo, m/s) 2.4
Height (H1, mm) 250 Velocity (V1, m/s) 1.9
Length (L, mm) 300 Vel Pres at Vo (Pvo, Pa) 3
Flow Rate (Q, L/s) 95 Vel Pres at V1 (Pv1, Pa) 2
Density (kg/m^3) 1.204 Loss Coefficient (Co) 0.06
Loss Coefficient (C1) 0.09
Pressure Loss (Pa) 0

01/23/2023 d:\project\ncp\static\ef-13\ef-13.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 250 Branch


Width (W, mm) 200 BranchVelocity (Vb, m/s) 2.0
Height (Hb, mm) 200 Vel Pres at Vb (Pvb, Pa) 2
Width (Wb, mm) 150 Loss Coefficient (Cb) 0.27
Flow Rate (Qs, L/s) 95 Branch Pressure Loss (Pa) 1
Flow Rate (Qb, L/s) 59 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 1.9
Velocity (Vc, m/s) 3.1
Vel Pres at Vs (Pvs, Pa) 2
Vel Pres at Vc (Pvc, Pa) 6
Loss Coefficient (Cs) 1.23
Main Pressure Loss (Pa) 3

01/23/2023 d:\project\ncp\static\ef-13\ef-13.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(CR3-1) Elbow, Smooth Radius without Vanes


(Idelchik 1986, Diagram 6-1)

INPUTS OUTPUTS

Width (W, mm) 200 Velocity (Vo, m/s) 3.1


Height (H, mm) 250 Vel Pres at Vo (Pv, Pa) 6
Radius Ratio (r/W) 0.8 Loss Coefficient (Co) 0.38
Angle (Theta, deg.) 90 Pressure Loss (Pa) 2
Flow Rate (Q, L/s) 154
Density (kg/m^3) 1.204

01/23/2023 d:\project\ncp\static\ef-13\ef-13.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(ER4-1) Transition, Rectangular, Two Sides Parallel, Symmetrical,


Exhaust/Return Systems (Idelchik 1986, Diagram 5-5)

INPUTS OUTPUTS

Height (Ho, mm) 200 Angle (Theta, deg.) 10


Width (Wo, mm) 250 Velocity (Vo, m/s) 3.1
Height (H1, mm) 250 Velocity (V1, m/s) 2.5
Length (L, mm) 300 Vel Pres at Vo (Pvo, Pa) 6
Flow Rate (Q, L/s) 154 Vel Pres at V1 (Pv1, Pa) 4
Density (kg/m^3) 1.204 Loss Coefficient (Co) 0.06
Loss Coefficient (C1) 0.09
Pressure Loss (Pa) 0

01/23/2023 d:\project\ncp\static\ef-13\ef-13.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 250 Branch


Width (W, mm) 250 BranchVelocity (Vb, m/s) 1.7
Height (Hb, mm) 100 Vel Pres at Vb (Pvb, Pa) 2
Width (Wb, mm) 200 Loss Coefficient (Cb) -6.89
Flow Rate (Qs, L/s) 155 Branch Pressure Loss (Pa) -12
Flow Rate (Qb, L/s) 34 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 2.5
Velocity (Vc, m/s) 3.0
Vel Pres at Vs (Pvs, Pa) 4
Vel Pres at Vc (Pvc, Pa) 6
Loss Coefficient (Cs) 0.32
Main Pressure Loss (Pa) 1

01/23/2023 d:\project\ncp\static\ef-13\ef-13.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(CR3-1) Elbow, Smooth Radius without Vanes


(Idelchik 1986, Diagram 6-1)

INPUTS OUTPUTS

Width (W, mm) 250 Velocity (Vo, m/s) 3.0


Height (H, mm) 250 Vel Pres at Vo (Pv, Pa) 6
Radius Ratio (r/W) 0.8 Loss Coefficient (Co) 0.39
Angle (Theta, deg.) 90 Pressure Loss (Pa) 2
Flow Rate (Q, L/s) 189
Density (kg/m^3) 1.204

01/23/2023 d:\project\ncp\static\ef-13\ef-13.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(ER4-3) Transition, Rectangular to Round, Exhaust/Return Systems


(Idelchik 1986, Diagram 5-27)

INPUTS OUTPUTS

Height (Ho, mm) 250 Angle (Theta1, deg.) 10


Width (Wo, mm) 250 Angle (Theta2, deg.) 10
Diameter (D1, mm) 200 Velocity (Vo, m/s) 3.0
Length (L, mm) 300 Velocity (V1, m/s) 6.0
Flow Rate (Q, L/s) 189 Vel Pres at Vo (Pvo, Pa) 6
Density (kg/m^3) 1.204 Vel Pres at V1 (Pv1, Pa) 22
Loss Coefficient (Co) 0.26
Loss Coefficient (C1) 0.07
Pressure Loss (Pa) 1

01/23/2023 d:\project\ncp\static\ef-13\ef-13.adf version: 6.00.04


Duct Accessories
Slot Diffuser
VOLUME DAMPER

%# ( # & & # " #


& ' "
Fire Damper
Back Draft Damper
SUGGESTED SPECIFICATION
Furnish and install, at locations shown on plans or in accordance resistant, long life synthetic type for quiet operation. Linkage shall
with schedules, heavy duty backdraft dampers that meet the follow- be 1 /2 " (13) wide tiebar connected to stainless steel pivot
ing minimum construction standards: Frame shall be .125" (3.2) pins. Dampers shall be designed for maximum 3500 fpm spot
wall thickness 6063T5 extruded aluminum with 12 gage (2.8) gal- velocities and minimum 4 inches w.g. back pressure depending on
vanized steel structural brace at each corner. Blades shall be .070" damper size. Dampers shall be in all respects equivalent to
(1.8) wall thickness 6063T5 extruded aluminum with extruded vinyl Ruskin model CBD6.
blade edge seals mechanically locked into blade edge. Adhesive or
clip on type seals are unacceptable. Bearings shall be
corrosion
INSTALLATION

1. When used in fan discharge applications, damper should 3. Bracing of multiple section assemblies:
be located at least one-half the fan diameter away from the fan. The CBD6 is intended to be self supporting only in the largest
single section size. Multiple section damper assemblies
2. For proper operation, damper must be installed square and free may require bracing to support the weight of the assembly
from racking. and to hold against system pressure. Ruskin recommends
appropriate bracing to support the damper horizontally at
least once for every 8 feet of damper width. Vertical
assemblies and higher system pressures may require more
PERFORMANCE DATA bracing.

DAMPER PERFORMANCE
LEAKAGE* BLADES BLADES
MAXIMUM MAXIMUM SYSTEM
DAMPER WIDTH Percent of CFM/ START TO FULLY
BACK PRESSURE VELOCITY
Max. Flow Sq. Ft. OPEN OPEN

48" (1219) 4.0" w.g. 2500 FPM .6% 15


36" (914) 8.0" w.g. 2500 FPM .6% 15 .01" w.g. .05" w.g.
24" (610) 12.0" w.g. 2500 FPM .7% 17.5
12" (305) 16.0" w.g. 2500 PFM 1% 25

*Leakage information based on pressure differential of 1" w.g. tested per AMCA Std. 500.

DAMPER PRESSURE DROP


(24" x 24")
p p ( [ ] )
0.7
17.78
0.5
12.7
Static Pressure Drop in INCHES and MILLIMETERS of WATER

0.3
7.62

0.2
5.08

0.1
2.54
.07
1.78

.05
1.27

.03
.75

.02
.51

.01
200 300 500 700 1000 2000 3000
60.96 91.44 152.40 213.36 304.80 609.60 914.40

Air velocity in FEET and Meters Per minute through face area
EXF 1
Calculation Sheet
External Static Pressure calculations

Project: NORTH COAST PALACE


MEP contractor : MAGNA ENGINEERING & CONSTRUCTION
Builing Name: MAIN VILLA
FAN TAG EF-14

GENERAL DATA
DUCT MATERIAL: G. I. Sheet
AIR DENSITY:(Kg/m3) 1.2

SECTION (1-1') (2-2') (3-3') TOTAL


CFM 100 200 330

FLOW L/S 47 94 156

M3/H 170 340 561

LENGTH M 1.0 10.0 7.0

DIAM. mm 164 189 244

DIAM. EQUIV. mm 164 189 244

WIDTH mm 150 150 250

HEIGHT mm 150 200 200

AREA M2 0.021 0.028 0.047

VELOCITY M/S 2.23 3.37 3.33

PD per Meter Pa 0.51 0.92 0.65

PD x LENGTH Pa 0.51 9.15 4.58 14

PA (1-1') (2-2') (3-3') TOTAL

Tee Branch (1) 1 1


Tee Branch(1) 4 1
Transition (1) 1 1
Tee Main (2) 1 1
Elbow 90 (2) 2 1
Transition (2) 1 1
Tee Main (3) 3 1
Elbow 90 (3) 2 2
Rect. To Round (3) 1 1
TOTAL PA 6 4 8 0 0 0 0 0 0 0 18

DUCTS PD Pa 6 4 8 0 0 0 0 0 0 0 18

PRESSURE DROP Pa 7 13 13 0 0 0 0 0 0 0 32

SPECIAL FITTING PRESSURE DROPS

DESIGNATION PD (PA) QTY TOTAL

Canvas 5 1 5 FLOW AT 100% (m3/hr) 561

Linear Slot Diffuser 20 1 20 * DUCTS PRESSURE DROP : 32

Round Volume damper (1) 6 1 6 * FITTING PRESSURE DROP : 89

Fire Damper (2) 25 1 25 STATIC PRESSURE AT 100% PA 121

Fire Damper (3) 28 1 28 *TOTAL EXTERNAL STATIC PRESSURE + 10% SF PA 133

Back Draft Damper 5 1 5 STATIC PRESSURE AT 100%(in) 0.48

*TOTAL EXTERNAL STATIC PRESSURE + 10% SF (in) 0.53

TOTAL 89
Drawing
Duct Fittings
Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(ER2-1) Bellmouth, Plenum to Round, Exhaust/Return Systems


(Idelchik 1986, Diagram 4-9)

INPUTS OUTPUTS

Diameter (D1, mm) 150 Velocity (Vo, m/s) 1.6


Plenum Height (Ho, mm) 200 Velocity (V1, m/s) 2.7
Plenum Width (Wo, mm) 150 Vel Pres at Vo (Pvo, Pa) 1
Flow Rate (Q, L/s) 47 Vel Pres at V1 (Pv1, Pa) 4
Density (kg/m^3) 1.204 Bellmouth Radius (r, mm) 50
Loss Coefficient (Co) 0.04
Loss Coefficient (C1) 0.02
Pressure Loss (Pa) 0

01/23/2023 d:\hat project\ncp\calculations\exhaust fan\ef-14\ef-14.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(CD11-2) Straight Duct, Flexible


(Abushakra 2004 and Culp 2011

INPUTS OUTPUTS

Flow Rate (Q, L/s) 47 Velocity (V, m/s) 2.7


Diameter (D, mm) 150 Vel Pres at Vo (Pv, Pa) 4
Installed Length (L, m) 0.5 Compressed (%) 29
Length Fully Extended (m) 0.7 Pressure Drop Correction Factor (PDCF) 8.9
Density (kg/m^3) 1.204 Pressure Loss (Pa) 4

FULLY EXTENDED

LESS THAN FULLY EXTENDED

01/23/2023 d:\hat project\ncp\calculations\exhaust fan\ef-14\ef-14.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(ER5-2) Tee, Round Tap to Rectangular Main [Ab/As=Ab/Ac=0.5; As/Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 150 Branch


Width (W, mm) 150 BranchVelocity (Vb, m/s) 2.7
Diameter (Db, mm) 150 Vel Pres at Vb (Pvb, Pa) 4
Flow Rate (Qs, L/s) 47 Loss Coefficient (Cb) 1.03
Flow Rate (Qb, L/s) 47 Branch Pressure Loss (Pa) 4
Density (kg/m^3) 1.204 Main
MainVelocity (Vs, m/s) 2.1
Velocity (Vc, m/s) 4.2
Vel Pres at Vs (Pvs, Pa) 3
Vel Pres at Vc (Pvc, Pa) 11
Loss Coefficient (Cs) 2.23
Main Pressure Loss (Pa) 6

01/23/2023 d:\hat project\ncp\calculations\exhaust fan\ef-14\ef-14.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(ER4-2) Transition, Pyramidal, Exhaust/Return Systems


(Idelchik 1986, Diagram 5-4)

INPUTS OUTPUTS

Height (Ho, mm) 150 Angle (Theta1, deg.) 0


Width (Wo, mm) 150 Angle (Theta2, deg.) 7
Height (H1, mm) 200 Velocity (Vo, m/s) 2.1
Width (W1, mm) 150 Velocity (V1, m/s) 1.6
Length (L, mm) 400 Vel Pres at Vo (Pvo, Pa) 3
Flow Rate (Q, L/s) 47 Vel Pres at V1 (Pv1, Pa) 1
Density (kg/m^3) 1.204 Loss Coefficient (Co) 0.07
Loss Coefficient (C1) 0.13
Pressure Loss (Pa) 0

01/23/2023 d:\hat project\ncp\calculations\exhaust fan\ef-14\ef-14.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(ER5-2) Tee, Round Tap to Rectangular Main [Ab/As=Ab/Ac=0.5; As/Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 800 Branch


Width (W, mm) 150 BranchVelocity (Vb, m/s) 2.7
Diameter (Db, mm) 150 Vel Pres at Vb (Pvb, Pa) 4
Flow Rate (Qs, L/s) 94 Loss Coefficient (Cb) 0.55
Flow Rate (Qb, L/s) 47 Branch Pressure Loss (Pa) 2
Density (kg/m^3) 1.204 Main
MainVelocity (Vs, m/s) 0.8
Velocity (Vc, m/s) 1.2
Vel Pres at Vs (Pvs, Pa) 0
Vel Pres at Vc (Pvc, Pa) 1
Loss Coefficient (Cs) 0.95
Main Pressure Loss (Pa) 0

01/23/2023 d:\hat project\ncp\calculations\exhaust fan\ef-14\ef-14.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(CR3-1) Elbow, Smooth Radius without Vanes


(Idelchik 1986, Diagram 6-1)

INPUTS OUTPUTS

Width (W, mm) 150 Velocity (Vo, m/s) 3.1


Height (H, mm) 200 Vel Pres at Vo (Pv, Pa) 6
Radius Ratio (r/W) 0.8 Loss Coefficient (Co) 0.37
Angle (Theta, deg.) 90 Pressure Loss (Pa) 2
Flow Rate (Q, L/s) 93
Density (kg/m^3) 1.204

01/23/2023 d:\hat project\ncp\calculations\exhaust fan\ef-14\ef-14.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(ER4-2) Transition, Pyramidal, Exhaust/Return Systems


(Idelchik 1986, Diagram 5-4)

INPUTS OUTPUTS

Height (Ho, mm) 200 Angle (Theta1, deg.) 14


Width (Wo, mm) 150 Angle (Theta2, deg.) 0
Height (H1, mm) 200 Velocity (Vo, m/s) 3.1
Width (W1, mm) 250 Velocity (V1, m/s) 1.9
Length (L, mm) 400 Vel Pres at Vo (Pvo, Pa) 6
Flow Rate (Q, L/s) 93 Vel Pres at V1 (Pv1, Pa) 2
Density (kg/m^3) 1.204 Loss Coefficient (Co) 0.17
Loss Coefficient (C1) 0.47
Pressure Loss (Pa) 1

01/23/2023 d:\hat project\ncp\calculations\exhaust fan\ef-14\ef-14.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(ER5-3) Tee, 45 Degree Entry Branch [Ab/As=Ab/Ac=0.5; As=Ac], Converging


(SMACNA 1990, Sepsy 1973)

INPUTS OUTPUTS

Height (H, mm) 200 Branch


Width (W, mm) 250 BranchVelocity (Vb, m/s) 2.0
Height (Hb, mm) 150 Vel Pres at Vb (Pvb, Pa) 2
Width (Wb, mm) 200 Loss Coefficient (Cb) 0.43
Flow Rate (Qs, L/s) 93 Branch Pressure Loss (Pa) 1
Flow Rate (Qb, L/s) 61 Main
Density (kg/m^3) 1.204 MainVelocity (Vs, m/s) 1.9
Velocity (Vc, m/s) 3.1
Vel Pres at Vs (Pvs, Pa) 2
Vel Pres at Vc (Pvc, Pa) 6
Loss Coefficient (Cs) 1.31
Main Pressure Loss (Pa) 3

01/23/2023 d:\hat project\ncp\calculations\exhaust fan\ef-14\ef-14.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(CR3-1) Elbow, Smooth Radius without Vanes


(Idelchik 1986, Diagram 6-1)

INPUTS OUTPUTS

Width (W, mm) 250 Velocity (Vo, m/s) 3.1


Height (H, mm) 200 Vel Pres at Vo (Pv, Pa) 6
Radius Ratio (r/W) 0.8 Loss Coefficient (Co) 0.42
Angle (Theta, deg.) 90 Pressure Loss (Pa) 2
Flow Rate (Q, L/s) 156
Density (kg/m^3) 1.204

01/23/2023 d:\hat project\ncp\calculations\exhaust fan\ef-14\ef-14.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023

(ER4-3) Transition, Rectangular to Round, Exhaust/Return Systems


(Idelchik 1986, Diagram 5-27)

INPUTS OUTPUTS

Height (Ho, mm) 200 Angle (Theta1, deg.) 0


Width (Wo, mm) 250 Angle (Theta2, deg.) 7
Diameter (D1, mm) 200 Velocity (Vo, m/s) 3.1
Length (L, mm) 400 Velocity (V1, m/s) 5.0
Flow Rate (Q, L/s) 156 Vel Pres at Vo (Pvo, Pa) 6
Density (kg/m^3) 1.204 Vel Pres at V1 (Pv1, Pa) 15
Loss Coefficient (Co) 0.16
Loss Coefficient (C1) 0.06
Pressure Loss (Pa) 1

01/23/2023 d:\hat project\ncp\calculations\exhaust fan\ef-14\ef-14.adf version: 6.00.04


Duct Accessories
Slot Diffuser
VOLUME DAMPER

%# ( # & & # " #


& ' "
Fire Damper 2
Fire Damper 3
Back Draft Damper
SUGGESTED SPECIFICATION
Furnish and install, at locations shown on plans or in accordance resistant, long life synthetic type for quiet operation. Linkage shall
with schedules, heavy duty backdraft dampers that meet the follow- be 1 /2 " (13) wide tiebar connected to stainless steel pivot
ing minimum construction standards: Frame shall be .125" (3.2) pins. Dampers shall be designed for maximum 3500 fpm spot
wall thickness 6063T5 extruded aluminum with 12 gage (2.8) gal- velocities and minimum 4 inches w.g. back pressure depending on
vanized steel structural brace at each corner. Blades shall be .070" damper size. Dampers shall be in all respects equivalent to
(1.8) wall thickness 6063T5 extruded aluminum with extruded vinyl Ruskin model CBD6.
blade edge seals mechanically locked into blade edge. Adhesive or
clip on type seals are unacceptable. Bearings shall be
corrosion
INSTALLATION

1. When used in fan discharge applications, damper should 3. Bracing of multiple section assemblies:
be located at least one-half the fan diameter away from the fan. The CBD6 is intended to be self supporting only in the largest
single section size. Multiple section damper assemblies
2. For proper operation, damper must be installed square and free may require bracing to support the weight of the assembly
from racking. and to hold against system pressure. Ruskin recommends
appropriate bracing to support the damper horizontally at
least once for every 8 feet of damper width. Vertical
assemblies and higher system pressures may require more
PERFORMANCE DATA bracing.

DAMPER PERFORMANCE
LEAKAGE* BLADES BLADES
MAXIMUM MAXIMUM SYSTEM
DAMPER WIDTH Percent of CFM/ START TO FULLY
BACK PRESSURE VELOCITY
Max. Flow Sq. Ft. OPEN OPEN

48" (1219) 4.0" w.g. 2500 FPM .6% 15


36" (914) 8.0" w.g. 2500 FPM .6% 15 .01" w.g. .05" w.g.
24" (610) 12.0" w.g. 2500 FPM .7% 17.5
12" (305) 16.0" w.g. 2500 PFM 1% 25

*Leakage information based on pressure differential of 1" w.g. tested per AMCA Std. 500.

DAMPER PRESSURE DROP


(24" x 24")
p p ( [ ] )
0.7
17.78
0.5
12.7
Static Pressure Drop in INCHES and MILLIMETERS of WATER

0.3
7.62

0.2
5.08

0.1
2.54
.07
1.78

.05
1.27

.03
.75

.02
.51

.01
200 300 500 700 1000 2000 3000
60.96 91.44 152.40 213.36 304.80 609.60 914.40

Air velocity in FEET and Meters Per minute through face area
FAF 01
Calculation Sheet
External Static Pressure calculations

Project: NORTH COAST PALACE


MEP contractor : MAGNA ENGINEERING & CONSTRUCTION
Builing Name: MAIN VILLA
FAN TAG FAF-01

GENERAL DATA
DUCT MATERIAL: G. I. Sheet
AIR DENSITY:(Kg/m3) 1.2

SECTION (1-1') (2-2') (3-3') (4-4') (5-5') (6-6') (7-7') TOTAL


CFM 1550 2650 3750 4850 5950 7050 8150

FLOW L/S 732 1251 1770 2289 2808 3327 3846

M3/H 2633 4502 6371 8240 10109 11978 13847

LENGTH M 8.0 5.0 4.5 4.5 4.5 4.5 14.0

DIAM. mm 420 506 592 630 703 744 795

DIAM. EQUIV. mm 420 506 592 630 703 744 795

WIDTH mm 500 750 750 750 950 1250 1250

HEIGHT mm 300 300 400 450 450 400 450

AREA M2 0.139 0.201 0.275 0.312 0.388 0.434 0.496

VELOCITY M/S 5.28 6.23 6.44 7.34 7.24 7.66 7.76

PD per Meter Pa 0.78 0.84 0.74 0.87 0.74 0.77 0.72

PD x LENGTH Pa 6.25 4.21 3.32 3.91 3.34 3.45 10.12 35

PA (1-1') (2-2') (3-3') (4-4') (5-5') (6-6') (7-7') TOTAL

ELBOW 90 (1) 6 3
TEE MAIN (2) 1 1
TEE MAIN (3) 1 1
TEE MAIN (4) 1 1
TEE MAIN (5) 1 1
ELBOW 90 (5) 36 2
TEE MAIN (6) 1 1
TEE MAIN (7) 1 1
RECT. TO ROUND (7) 1 1
ROUND TO RECT. (7) 4 1
ELBOW 90 (7) 14 1
TRANSITION (7) 21 1
TOTAL PA 18 1 1 1 73 1 41 136

DUCTS PD Pa 18 1 1 1 73 1 41 136

PRESSURE DROP Pa 24 5 4 5 76 4 51 171

SPECIAL FITTING PRESSURE DROPS

DESIGNATION PD (PA) QTY TOTAL

Canvas 5 2 10 FLOW AT 100% (m3/hr) 13847

Fire Damper 30 1 30 * DUCTS PRESSURE DROP : 171

Air Louver 30 1 30 * FITTING PRESSURE DROP : 70

0 STATIC PRESSURE AT 100% PA 241

0 *TOTAL EXTERNAL STATIC PRESSURE + 10% SF PA 265

0 STATIC PRESSURE AT 100%(in) 0.96

0 *TOTAL EXTERNAL STATIC PRESSURE + 10% SF (in) 1.06

TOTAL 70
Drawing
Duct Fittings
Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(CR3-1) Elbow, Smooth Radius without Vanes


(Idelchik 1986, Diagram 6-1)

INPUTS OUTPUTS

Width (W, mm) 500 Velocity (Vo, m/s) 4.9


Height (H, mm) 300 Vel Pres at Vo (Pv, Pa) 14
Radius Ratio (r/W) 0.8 Loss Coefficient (Co) 0.45
Angle (Theta, deg.) 90 Pressure Loss (Pa) 6
Flow Rate (Q, L/s) 732
Density (kg/m^3) 1.204

01/22/2023 c:\users\ahmed.salahaldin\desktop\fresh fans\faf-01\faf-01.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(SR5-13) Tee, 45 Degree Entry Branch, Diverging (Brooks 1993)

INPUTS OUTPUTS

Height (H, mm) 300 Branch


Width (W, mm) 750 BranchVelocity (Vb, m/s) 2.3
Height (Hs, mm) 300 Vel Pres at Vb (Pvb, Pa) 3
Width (Ws, mm) 500 Loss Coefficient (Cb) 4.65
Height (Hb, mm) 250 Branch Pressure Loss (Pa) 15
Width (Wb, mm) 900 Main
Flow Rate (Qc, L/s) 1251 MainVelocity (Vs, m/s) 4.9
Flow Rate (Qb, L/s) 520 Velocity (Vc, m/s) 5.6
Density (kg/m^3) 1.204 Vel Pres at Vs (Pvs, Pa) 14
Vel Pres at Vc (Pvc, Pa) 19
Loss Coefficient (Cs) 0.09
Main Pressure Loss (Pa) 1

01/22/2023 c:\users\ahmed.salahaldin\desktop\fresh fans\faf-01\faf-01.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(SR5-13) Tee, 45 Degree Entry Branch, Diverging (Brooks 1993)

INPUTS OUTPUTS

Height (H, mm) 450 Branch


Width (W, mm) 750 BranchVelocity (Vb, m/s) 2.3
Height (Hs, mm) 400 Vel Pres at Vb (Pvb, Pa) 3
Width (Ws, mm) 750 Loss Coefficient (Cb) 4.23
Height (Hb, mm) 250 Branch Pressure Loss (Pa) 14
Width (Wb, mm) 900 Main
Flow Rate (Qc, L/s) 1770 MainVelocity (Vs, m/s) 4.2
Flow Rate (Qb, L/s) 520 Velocity (Vc, m/s) 5.2
Density (kg/m^3) 1.204 Vel Pres at Vs (Pvs, Pa) 10
Vel Pres at Vc (Pvc, Pa) 17
Loss Coefficient (Cs) 0.14
Main Pressure Loss (Pa) 1

01/22/2023 c:\users\ahmed.salahaldin\desktop\fresh fans\faf-01\faf-01.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(SR5-13) Tee, 45 Degree Entry Branch, Diverging (Brooks 1993)

INPUTS OUTPUTS

Height (H, mm) 450 Branch


Width (W, mm) 950 BranchVelocity (Vb, m/s) 2.3
Height (Hs, mm) 450 Vel Pres at Vb (Pvb, Pa) 3
Width (Ws, mm) 750 Loss Coefficient (Cb) 4.67
Height (Hb, mm) 250 Branch Pressure Loss (Pa) 15
Width (Wb, mm) 900 Main
Flow Rate (Qc, L/s) 2290 MainVelocity (Vs, m/s) 5.2
Flow Rate (Qb, L/s) 520 Velocity (Vc, m/s) 5.4
Density (kg/m^3) 1.204 Vel Pres at Vs (Pvs, Pa) 17
Vel Pres at Vc (Pvc, Pa) 17
Loss Coefficient (Cs) 0.05
Main Pressure Loss (Pa) 1

01/22/2023 c:\users\ahmed.salahaldin\desktop\fresh fans\faf-01\faf-01.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(SR5-13) Tee, 45 Degree Entry Branch, Diverging (Brooks 1993)

INPUTS OUTPUTS

Height (H, mm) 400 Branch


Width (W, mm) 1250 BranchVelocity (Vb, m/s) 2.3
Height (Hs, mm) 450 Vel Pres at Vb (Pvb, Pa) 3
Width (Ws, mm) 950 Loss Coefficient (Cb) 4.11
Height (Hb, mm) 250 Branch Pressure Loss (Pa) 13
Width (Wb, mm) 900 Main
Flow Rate (Qc, L/s) 2810 MainVelocity (Vs, m/s) 5.4
Flow Rate (Qb, L/s) 520 Velocity (Vc, m/s) 5.6
Density (kg/m^3) 1.204 Vel Pres at Vs (Pvs, Pa) 17
Vel Pres at Vc (Pvc, Pa) 19
Loss Coefficient (Cs) 0.05
Main Pressure Loss (Pa) 1

01/22/2023 c:\users\ahmed.salahaldin\desktop\fresh fans\faf-01\faf-01.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(CR3-2) Elbow, Sharp Throat (r/W=0.5), Radius Heel, 90 Degree


(Idelchik 1986, Diagram 6-1)

INPUTS OUTPUTS

Width (W, mm) 950 Velocity (Vo, m/s) 6.6


Height (H, mm) 450 Vel Pres at Vo (Pv, Pa) 26
Flow Rate (Q, L/s) 2810 Loss Coefficient (Co) 1.40
Density (kg/m^3) 1.204 Pressure Loss (Pa) 36

01/22/2023 c:\users\ahmed.salahaldin\desktop\fresh fans\faf-01\faf-01.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(SR5-13) Tee, 45 Degree Entry Branch, Diverging (Brooks 1993)

INPUTS OUTPUTS

Height (H, mm) 400 Branch


Width (W, mm) 1250 BranchVelocity (Vb, m/s) 2.3
Height (Hs, mm) 450 Vel Pres at Vb (Pvb, Pa) 3
Width (Ws, mm) 950 Loss Coefficient (Cb) 4.29
Height (Hb, mm) 250 Branch Pressure Loss (Pa) 14
Width (Wb, mm) 900 Main
Flow Rate (Qc, L/s) 3327 MainVelocity (Vs, m/s) 6.6
Flow Rate (Qb, L/s) 520 Velocity (Vc, m/s) 6.7
Density (kg/m^3) 1.204 Vel Pres at Vs (Pvs, Pa) 26
Vel Pres at Vc (Pvc, Pa) 27
Loss Coefficient (Cs) 0.05
Main Pressure Loss (Pa) 1

01/22/2023 c:\users\ahmed.salahaldin\desktop\fresh fans\faf-01\faf-01.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(SR5-13) Tee, 45 Degree Entry Branch, Diverging (Brooks 1993)

INPUTS OUTPUTS

Height (H, mm) 450 Branch


Width (W, mm) 1250 BranchVelocity (Vb, m/s) 2.3
Height (Hs, mm) 400 Vel Pres at Vb (Pvb, Pa) 3
Width (Ws, mm) 1250 Loss Coefficient (Cb) 3.40
Height (Hb, mm) 250 Branch Pressure Loss (Pa) 11
Width (Wb, mm) 900 Main
Flow Rate (Qc, L/s) 3846 MainVelocity (Vs, m/s) 6.7
Flow Rate (Qb, L/s) 520 Velocity (Vc, m/s) 6.8
Density (kg/m^3) 1.204 Vel Pres at Vs (Pvs, Pa) 27
Vel Pres at Vc (Pvc, Pa) 28
Loss Coefficient (Cs) 0.05
Main Pressure Loss (Pa) 1

01/22/2023 c:\users\ahmed.salahaldin\desktop\fresh fans\faf-01\faf-01.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(ER4-3) Transition, Rectangular to Round, Exhaust/Return Systems


(Idelchik 1986, Diagram 5-27)

INPUTS OUTPUTS

Height (Ho, mm) 450 Angle (Theta1, deg.) 39


Width (Wo, mm) 1250 Angle (Theta2, deg.) 48
Diameter (D1, mm) 800 Velocity (Vo, m/s) 6.8
Length (L, mm) 500 Velocity (V1, m/s) 7.7
Flow Rate (Q, L/s) 3846 Vel Pres at Vo (Pvo, Pa) 28
Density (kg/m^3) 1.204 Vel Pres at V1 (Pv1, Pa) 35
Loss Coefficient (Co) 0.03
Loss Coefficient (C1) 0.02
Pressure Loss (Pa) 1

01/22/2023 c:\users\ahmed.salahaldin\desktop\fresh fans\faf-01\faf-01.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(SR4-3) Transition, Round to Rectangular, Supply Air Systems


(Idelchik 1986, Diagram 5-27)

INPUTS OUTPUTS

Diameter (D1, mm) 800 Angle (Theta1, deg.) 39


Height (Ho, mm) 450 Angle (Theta2, deg.) 48
Width (Wo, mm) 1250 Velocity (Vo, m/s) 6.8
Length (L, mm) 500 Velocity (V1, m/s) 7.7
Flow Rate (Q, L/s) 3846 Vel Pres at Vo (Pvo, Pa) 28
Density (kg/m^3) 1.204 Vel Pres at V1 (Pv1, Pa) 35
Loss Coefficient (Co) 0.15
Loss Coefficient (C1) 0.12
Pressure Loss (Pa) 4

01/22/2023 c:\users\ahmed.salahaldin\desktop\fresh fans\faf-01\faf-01.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(CR3-1) Elbow, Smooth Radius without Vanes


(Idelchik 1986, Diagram 6-1)

INPUTS OUTPUTS

Width (W, mm) 1250 Velocity (Vo, m/s) 6.8


Height (H, mm) 450 Vel Pres at Vo (Pv, Pa) 28
Radius Ratio (r/W) 0.8 Loss Coefficient (Co) 0.49
Angle (Theta, deg.) 90 Pressure Loss (Pa) 14
Flow Rate (Q, L/s) 3846
Density (kg/m^3) 1.204

01/22/2023 c:\users\ahmed.salahaldin\desktop\fresh fans\faf-01\faf-01.adf version: 6.00.04


Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023

(SR4-2) Transition, Pyramidal, Supply Air Systems


(Idelchik 1986, Diagram 5-4)

INPUTS OUTPUTS

Height (Ho, mm) 1600 Angle (Theta1, deg.) 98


Width (Wo, mm) 1600 Angle (Theta2, deg.) 39
Height (H1, mm) 450 Velocity (Vo, m/s) 1.5
Width (W1, mm) 1250 Velocity (V1, m/s) 6.8
Length (L, mm) 500 Vel Pres at Vo (Pvo, Pa) 1
Flow Rate (Q, L/s) 3846 Vel Pres at V1 (Pv1, Pa) 28
Density (kg/m^3) 1.204 Loss Coefficient (Co) 15.26
Loss Coefficient (C1) 0.74
Pressure Loss (Pa) 21

01/22/2023 c:\users\ahmed.salahaldin\desktop\fresh fans\faf-01\faf-01.adf version: 6.00.04


Duct Accessories
Fire Damper
Air Louver

Chart 1
700
Static Pressure Drop (inches w.g.)

600

500

400
x 10-3

300

200

100

0
0 500 1000 1500 2000 2500

Free Area Velocity (ft/min)

Example 1
Given air flow rate of 1500 cfm select a louver size

Dividing flow rate by free area velocity (let say 600 fpm )

Free area = 2.5 ft2 , from the table above , 34”X 22” will be the least louver satisfy the
desired free velocity

Note : other selections are also available

Determine free velocity 1500 /2.51 = 597 fpm

Check for pressure drop across the louver at 597 fpm from chart 1 = 0.06 Wg “

Example 2
Knowing louver size as 24”X28” determine the maximum flow rate

From table 1 free area = 2.28 feet2

For velocity 800 fpm the flow rate = 2.28X 800 = 1824 cfm

Check for pressure drop across the louver at 800 fpm from chart 1 = 0.14 Wg “
Air Louver

Free area for ZAL- S

Free area for ZAL- L


Method Statement
Method Statement:
-Duct fittings: from ASHRAE Duct Fitting Data Base.
-Volume damper: from Zamzam data sheet.
-Fire damper: from Zamzam data sheet.
-Air outlets: from Zamzam data sheet.
-Air Louver: from Zamzam data sheet.
-Back Draft Damper: from Zamzam data sheet.

You might also like