Fan Static Calc
Fan Static Calc
Fan Static Calc
Pressure Drop
Calculation
NORTH COAST PALACE
El Alamein – Egypt
Revision 0
Table of Contents
· Summary.
· Fans Design Schedule.
· Fans Pressure Drop Calculation.
· Method Statement.
Summary
Fans ESP Calculation Summary
GENERAL DATA
DUCT MATERIAL: G. I. Sheet
AIR DENSITY:(Kg/m3) 1.2
SECTION (1-1') (2-2') (3-3') (4-4') (5-5') (6-6') (7-7') (8-8') (9-9') (10-10') TOTAL
CFM 75 150 225 375 525 600 1425 2625 3675 4125
FLOW L/S 35 71 106 177 248 283 673 1239 1734 1947
M3/H 127 255 382 637 892 1019 2421 4460 6244 7008
LENGTH M 1.7 1.5 1.0 3.5 10.0 11.0 7.0 5.5 8.0 9.0
DIAM. mm 152 189 219 244 273 299 381 506 592 592
DIAM. EQUIV. mm 152 189 219 244 273 299 381 506 592 592
WIDTH mm 200 200 200 200 250 250 500 750 750 750
HEIGHT mm 100 150 200 250 250 300 250 300 400 400
AREA M2 0.018 0.028 0.038 0.047 0.059 0.070 0.114 0.201 0.275 0.275
VELOCITY M/S 1.94 2.53 2.83 3.78 4.22 4.03 5.90 6.17 6.31 7.08
PD per Meter Pa 0.44 0.54 0.56 0.83 0.88 0.72 1.08 0.83 0.71 0.88
PD x LENGTH Pa 0.74 0.81 0.56 2.89 8.80 7.96 7.55 4.56 5.70 7.91 47
PA (1-1') (2-2') (3-3') (4-4') (5-5') (6-6') (7-7') (8-8') (9-9') (10-10') TOTAL
Tee Branch 3 1
Transition 1 1
Tee Main 2 1
Transition 1 1
Tee Main 2 1
Tee Branch 3 1
Tee Branch 6 1
Tee Branch 8 1
Transition 2 1
Tee Main 11 1
Elbow 90 9 2
Tee Branch 12 1
Tee Main 9 1
Tee Main 1 1
Tee Main 7 1
Tee Main 3 1
Elbow 90 13 2
Transition 8 1
TOTAL PA 4 3 5 6 8 2 41 10 7 37 123
DUCTS PD Pa 4 3 5 6 8 2 41 10 7 37 123
Fire Damper (10) 25 1 25 *TOTAL EXTERNAL STATIC PRESSURE + 15% SF (in) 1.23
TOTAL 109
Drawing
Duct Fittings
Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
Where :
P the pressure drop in mm of water
NC based on room attenuation of 10dB
VOLUME DAMPER 03
VOLUME DAMPER 04
VOLUME DAMPER 05
Fire Damper 8
Fire Damper 10
Back Draft Damper
SUGGESTED SPECIFICATION
Furnish and install, at locations shown on plans or in accordance resistant, long life synthetic type for quiet operation. Linkage shall
with schedules, heavy duty backdraft dampers that meet the follow- be 1 /2 " (13) wide tiebar connected to stainless steel pivot
ing minimum construction standards: Frame shall be .125" (3.2) pins. Dampers shall be designed for maximum 3500 fpm spot
wall thickness 6063T5 extruded aluminum with 12 gage (2.8) gal- velocities and minimum 4 inches w.g. back pressure depending on
vanized steel structural brace at each corner. Blades shall be .070" damper size. Dampers shall be in all respects equivalent to
(1.8) wall thickness 6063T5 extruded aluminum with extruded vinyl Ruskin model CBD6.
blade edge seals mechanically locked into blade edge. Adhesive or
clip on type seals are unacceptable. Bearings shall be
corrosion
INSTALLATION
1. When used in fan discharge applications, damper should 3. Bracing of multiple section assemblies:
be located at least one-half the fan diameter away from the fan. The CBD6 is intended to be self supporting only in the largest
single section size. Multiple section damper assemblies
2. For proper operation, damper must be installed square and free may require bracing to support the weight of the assembly
from racking. and to hold against system pressure. Ruskin recommends
appropriate bracing to support the damper horizontally at
least once for every 8 feet of damper width. Vertical
assemblies and higher system pressures may require more
PERFORMANCE DATA bracing.
DAMPER PERFORMANCE
LEAKAGE* BLADES BLADES
MAXIMUM MAXIMUM SYSTEM
DAMPER WIDTH Percent of CFM/ START TO FULLY
BACK PRESSURE VELOCITY
Max. Flow Sq. Ft. OPEN OPEN
*Leakage information based on pressure differential of 1" w.g. tested per AMCA Std. 500.
0.3
7.62
0.2
5.08
0.1
2.54
.07
1.78
.05
1.27
.03
.75
.02
.51
.01
200 300 500 700 1000 2000 3000
60.96 91.44 152.40 213.36 304.80 609.60 914.40
Air velocity in FEET and Meters Per minute through face area
EXF 0
Calculation Sheet
External Static Pressure calculations
GENERAL DATA
DUCT MATERIAL: G. I. Sheet
AIR DENSITY:(Kg/m3) 1.2
SECTION (1-1') (2-2') (3-3') (4-4') (5-5') (6-6') (7-7') (8-8') (9-9') TOTAL
CFM 75 150 300 375 525 600 1190 1990 2850
M3/H 127 255 510 637 892 1019 2022 3381 4842
LENGTH M 1.7 1.0 3.0 1.5 3.0 20.0 27.0 4.5 8.0
DIAM. mm 152 189 219 244 273 299 378 378 455
DIAM. EQUIV. mm 152 189 219 244 273 299 378 378 455
WIDTH mm 200 200 200 250 250 300 400 400 500
HEIGHT mm 100 150 200 200 250 250 300 300 350
AREA M2 0.018 0.028 0.038 0.047 0.059 0.070 0.112 0.112 0.163
VELOCITY M/S 1.94 2.53 3.77 3.78 4.22 4.03 5.01 8.38 8.25
PD per Meter Pa 0.44 0.54 0.94 0.83 0.88 0.72 0.81 2.06 1.60
PD x LENGTH Pa 0.74 0.54 2.82 1.24 2.64 14.48 21.85 9.28 12.77 66
PA (1-1') (2-2') (3-3') (4-4') (5-5') (6-6') (7-7') (8-8') (9-9') TOTAL
DUCTS PD Pa 3 2 9 3 5 26 23 10 31 0 112
TOTAL 74
Drawing
Duct Fittings
Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
Return air
Where :
P the pressure drop in mm of water
NC based on room attenuation of 10dB
VOLUME DAMPER 02
VOLUME DAMPER 05
Fire Damper 9
Fire Damper 10
Back Draft Damper
SUGGESTED SPECIFICATION
Furnish and install, at locations shown on plans or in accordance resistant, long life synthetic type for quiet operation. Linkage shall
with schedules, heavy duty backdraft dampers that meet the follow- be 1 /2 " (13) wide tiebar connected to stainless steel pivot
ing minimum construction standards: Frame shall be .125" (3.2) pins. Dampers shall be designed for maximum 3500 fpm spot
wall thickness 6063T5 extruded aluminum with 12 gage (2.8) gal- velocities and minimum 4 inches w.g. back pressure depending on
vanized steel structural brace at each corner. Blades shall be .070" damper size. Dampers shall be in all respects equivalent to
(1.8) wall thickness 6063T5 extruded aluminum with extruded vinyl Ruskin model CBD6.
blade edge seals mechanically locked into blade edge. Adhesive or
clip on type seals are unacceptable. Bearings shall be
corrosion
INSTALLATION
1. When used in fan discharge applications, damper should 3. Bracing of multiple section assemblies:
be located at least one-half the fan diameter away from the fan. The CBD6 is intended to be self supporting only in the largest
single section size. Multiple section damper assemblies
2. For proper operation, damper must be installed square and free may require bracing to support the weight of the assembly
from racking. and to hold against system pressure. Ruskin recommends
appropriate bracing to support the damper horizontally at
least once for every 8 feet of damper width. Vertical
assemblies and higher system pressures may require more
PERFORMANCE DATA bracing.
DAMPER PERFORMANCE
LEAKAGE* BLADES BLADES
MAXIMUM MAXIMUM SYSTEM
DAMPER WIDTH Percent of CFM/ START TO FULLY
BACK PRESSURE VELOCITY
Max. Flow Sq. Ft. OPEN OPEN
*Leakage information based on pressure differential of 1" w.g. tested per AMCA Std. 500.
0.3
7.62
0.2
5.08
0.1
2.54
.07
1.78
.05
1.27
.03
.75
.02
.51
.01
200 300 500 700 1000 2000 3000
60.96 91.44 152.40 213.36 304.80 609.60 914.40
Air velocity in FEET and Meters Per minute through face area
EXF 0
Calculation Sheet
External Static Pressure calculations
GENERAL DATA
DUCT MATERIAL: G. I. Sheet
AIR DENSITY:(Kg/m3) 1.2
Plenum Box 1 1
Flexible Duct 9 1
Transition 1 1
Elbow 90 1 4
Elbow 45 1 2
Transition 1 1
Tee main 3 1
Transition 1 1
Tee main 2 1
Transition 1 1
Tee main 1 1
Tee main 4 1
Tee Branch 7 1
Tee main 6 1
Elbow 90 6 1
Transition 1 1
Tee main 5 1
Transition 1 1
Tee main 1 1
Elbow 90 7 1
Transition 1 1
TOTAL PA 18 4 3 12 13 6 9 0 0 0 65
DUCTS PD Pa 18 4 3 12 13 6 9 0 0 0 65
`
DESIGNATION PD (PA) QTY TOTAL
Canvas 5 1 5 FLOW AT 100% (m3/hr) 2549
0
TOTAL 86
Drawing
Duct Fittings
Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023
INPUTS OUTPUTS
INPUTS OUTPUTS
FULLY EXTENDED
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
1. When used in fan discharge applications, damper should 3. Bracing of multiple section assemblies:
be located at least one-half the fan diameter away from the fan. The CBD6 is intended to be self supporting only in the largest
single section size. Multiple section damper assemblies
2. For proper operation, damper must be installed square and free may require bracing to support the weight of the assembly
from racking. and to hold against system pressure. Ruskin recommends
appropriate bracing to support the damper horizontally at
least once for every 8 feet of damper width. Vertical
assemblies and higher system pressures may require more
PERFORMANCE DATA bracing.
DAMPER PERFORMANCE
LEAKAGE* BLADES BLADES
MAXIMUM MAXIMUM SYSTEM
DAMPER WIDTH Percent of CFM/ START TO FULLY
BACK PRESSURE VELOCITY
Max. Flow Sq. Ft. OPEN OPEN
*Leakage information based on pressure differential of 1" w.g. tested per AMCA Std. 500.
0.3
7.62
0.2
5.08
0.1
2.54
.07
1.78
.05
1.27
.03
.75
.02
.51
.01
200 300 500 700 1000 2000 3000
60.96 91.44 152.40 213.36 304.80 609.60 914.40
Air velocity in FEET and Meters Per minute through face area
EXF 0
Calculation Sheet
External Static Pressure calculations
GENERAL DATA
DUCT MATERIAL: G. I. Sheet
AIR DENSITY:(Kg/m3) 1.2
M3/H 2379
LENGTH M 9.0
DIAM. mm 402
WIDTH mm 750
HEIGHT mm 200
AREA M2 0.127
PD x LENGTH Pa 7.20 7
PA (1-1') TOTAL
DUCTS PD Pa 29 29
PRESSURE DROP Pa 36 36
TOTAL 63
Drawing
Duct Fittings
Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
Chart 1
700
Static Pressure Drop (inches w.g.)
600
500
400
x 10-3
300
200
100
0
0 500 1000 1500 2000 2500
Example 1
Given air flow rate of 1500 cfm select a louver size
Dividing flow rate by free area velocity (let say 600 fpm )
Free area = 2.5 ft2 , from the table above , 34”X 22” will be the least louver satisfy the
desired free velocity
Check for pressure drop across the louver at 597 fpm from chart 1 = 0.06 Wg “
Example 2
Knowing louver size as 24”X28” determine the maximum flow rate
For velocity 800 fpm the flow rate = 2.28X 800 = 1824 cfm
Check for pressure drop across the louver at 800 fpm from chart 1 = 0.14 Wg “
Back Draft Damper
SUGGESTED SPECIFICATION
Furnish and install, at locations shown on plans or in accordance resistant, long life synthetic type for quiet operation. Linkage shall
with schedules, heavy duty backdraft dampers that meet the follow- be 1 /2 " (13) wide tiebar connected to stainless steel pivot
ing minimum construction standards: Frame shall be .125" (3.2) pins. Dampers shall be designed for maximum 3500 fpm spot
wall thickness 6063T5 extruded aluminum with 12 gage (2.8) gal- velocities and minimum 4 inches w.g. back pressure depending on
vanized steel structural brace at each corner. Blades shall be .070" damper size. Dampers shall be in all respects equivalent to
(1.8) wall thickness 6063T5 extruded aluminum with extruded vinyl Ruskin model CBD6.
blade edge seals mechanically locked into blade edge. Adhesive or
clip on type seals are unacceptable. Bearings shall be
corrosion
INSTALLATION
1. When used in fan discharge applications, damper should 3. Bracing of multiple section assemblies:
be located at least one-half the fan diameter away from the fan. The CBD6 is intended to be self supporting only in the largest
single section size. Multiple section damper assemblies
2. For proper operation, damper must be installed square and free may require bracing to support the weight of the assembly
from racking. and to hold against system pressure. Ruskin recommends
appropriate bracing to support the damper horizontally at
least once for every 8 feet of damper width. Vertical
assemblies and higher system pressures may require more
PERFORMANCE DATA bracing.
DAMPER PERFORMANCE
LEAKAGE* BLADES BLADES
MAXIMUM MAXIMUM SYSTEM
DAMPER WIDTH Percent of CFM/ START TO FULLY
BACK PRESSURE VELOCITY
Max. Flow Sq. Ft. OPEN OPEN
*Leakage information based on pressure differential of 1" w.g. tested per AMCA Std. 500.
0.3
7.62
0.2
5.08
0.1
2.54
.07
1.78
.05
1.27
.03
.75
.02
.51
.01
200 300 500 700 1000 2000 3000
60.96 91.44 152.40 213.36 304.80 609.60 914.40
Air velocity in FEET and Meters Per minute through face area
EXF 0
Calculation Sheet
External Static Pressure calculations
GENERAL DATA
DUCT MATERIAL: G. I. Sheet
AIR DENSITY:(Kg/m3) 1.2
Plenum Box 1 1
Flexible Duct 14 1
Transition 1 1
Tee Branch 14 1
Transition 1 1
Tee Main 4 1
Transition 1 1
Tee Main 4 1
Transition 1 1
Tee Main 3 1
Transition 2 1
Transition 16 1
TOTAL PA 30 1 5 5 21 0 0 0 0 0 62
DUCTS PD Pa 30 1 5 5 21 0 0 0 0 0 62
PRESSURE DROP Pa 31 2 6 6 23 0 0 0 0 0 67
`
DESIGNATION PD (PA) QTY TOTAL
Canvas 5 2 10 FLOW AT 100% (m3/hr) 1699
0
TOTAL 100
Drawing
EF-06 / 1000 CFM
2 RLSD, 2 SLOTS, 2.1 m 8"x8"
Ex.L 36"x10" 250 cfm
14"x8" 18"x8"
24"x8"
500 cfm 750 cfm
1000 cfm
Duct Fittings
Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023
INPUTS OUTPUTS
INPUTS OUTPUTS
FULLY EXTENDED
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
1. When used in fan discharge applications, damper should 3. Bracing of multiple section assemblies:
be located at least one-half the fan diameter away from the fan. The CBD6 is intended to be self supporting only in the largest
single section size. Multiple section damper assemblies
2. For proper operation, damper must be installed square and free may require bracing to support the weight of the assembly
from racking. and to hold against system pressure. Ruskin recommends
appropriate bracing to support the damper horizontally at
least once for every 8 feet of damper width. Vertical
assemblies and higher system pressures may require more
PERFORMANCE DATA bracing.
DAMPER PERFORMANCE
LEAKAGE* BLADES BLADES
MAXIMUM MAXIMUM SYSTEM
DAMPER WIDTH Percent of CFM/ START TO FULLY
BACK PRESSURE VELOCITY
Max. Flow Sq. Ft. OPEN OPEN
*Leakage information based on pressure differential of 1" w.g. tested per AMCA Std. 500.
0.3
7.62
0.2
5.08
0.1
2.54
.07
1.78
.05
1.27
.03
.75
.02
.51
.01
200 300 500 700 1000 2000 3000
60.96 91.44 152.40 213.36 304.80 609.60 914.40
Air velocity in FEET and Meters Per minute through face area
Air Louver
Chart 1
700
Static Pressure Drop (inches w.g.)
600
500
400
x 10-3
300
200
100
0
0 500 1000 1500 2000 2500
Example 1
Given air flow rate of 1500 cfm select a louver size
Dividing flow rate by free area velocity (let say 600 fpm )
Free area = 2.5 ft2 , from the table above , 34”X 22” will be the least louver satisfy the
desired free velocity
Check for pressure drop across the louver at 597 fpm from chart 1 = 0.06 Wg “
Example 2
Knowing louver size as 24”X28” determine the maximum flow rate
For velocity 800 fpm the flow rate = 2.28X 800 = 1824 cfm
Check for pressure drop across the louver at 800 fpm from chart 1 = 0.14 Wg “
Air Louver
GENERAL DATA
DUCT MATERIAL: G. I. Sheet
AIR DENSITY:(Kg/m3) 1.2
Plenum (1) 1 1
Round to Rect. 1 1
Elbow 90 (1) 1 1
Transition (1) 1 1
Tee Main (2) 2 1
Transition (2) 1 1
Tee Main (3) 4 1
Elbow 90 (3) 3 3
Elbow 45 (3) 2 2
Transition (3) 1 1
Tee Main (4.1) 5 1
Tee Main (4.2) 1 1
Elbow 90 (4) 5 2
Rect. To Round (4) 1 1
TOTAL PA 4 3 18 17 0 0 0 0 0 0 42
DUCTS PD Pa 4 3 18 17 0 0 0 0 0 0 42
PRESSURE DROP Pa 4 6 35 32 0 0 0 0 0 0 77
TOTAL 62
Drawing
Duct Fittings
Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023
INPUTS OUTPUTS
INPUTS OUTPUTS
FULLY EXTENDED
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
1. When used in fan discharge applications, damper should 3. Bracing of multiple section assemblies:
be located at least one-half the fan diameter away from the fan. The CBD6 is intended to be self supporting only in the largest
single section size. Multiple section damper assemblies
2. For proper operation, damper must be installed square and free may require bracing to support the weight of the assembly
from racking. and to hold against system pressure. Ruskin recommends
appropriate bracing to support the damper horizontally at
least once for every 8 feet of damper width. Vertical
assemblies and higher system pressures may require more
PERFORMANCE DATA bracing.
DAMPER PERFORMANCE
LEAKAGE* BLADES BLADES
MAXIMUM MAXIMUM SYSTEM
DAMPER WIDTH Percent of CFM/ START TO FULLY
BACK PRESSURE VELOCITY
Max. Flow Sq. Ft. OPEN OPEN
*Leakage information based on pressure differential of 1" w.g. tested per AMCA Std. 500.
0.3
7.62
0.2
5.08
0.1
2.54
.07
1.78
.05
1.27
.03
.75
.02
.51
.01
200 300 500 700 1000 2000 3000
60.96 91.44 152.40 213.36 304.80 609.60 914.40
Air velocity in FEET and Meters Per minute through face area
EXF 0
Calculation Sheet
External Static Pressure calculations
GENERAL DATA
DUCT MATERIAL: G. I. Sheet
AIR DENSITY:(Kg/m3) 1.2
Tee Branch 1 1
Transition 1 1
Tee Main 2 1
Elbow 5 4
Transition 1 1
TOTAL PA 2 23 0 0 0 0 0 0 0 0 25
DUCTS PD Pa 2 23 0 0 0 0 0 0 0 0 25
PRESSURE DROP Pa 5 30 0 0 0 0 0 0 0 0 35
`
DESIGNATION PD (PA) QTY TOTAL
Canvas 5 1 5 FLOW AT 100% (m3/hr) 1274
0
TOTAL 50
Drawing
Duct Fittings
Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
1. When used in fan discharge applications, damper should 3. Bracing of multiple section assemblies:
be located at least one-half the fan diameter away from the fan. The CBD6 is intended to be self supporting only in the largest
single section size. Multiple section damper assemblies
2. For proper operation, damper must be installed square and free may require bracing to support the weight of the assembly
from racking. and to hold against system pressure. Ruskin recommends
appropriate bracing to support the damper horizontally at
least once for every 8 feet of damper width. Vertical
assemblies and higher system pressures may require more
PERFORMANCE DATA bracing.
DAMPER PERFORMANCE
LEAKAGE* BLADES BLADES
MAXIMUM MAXIMUM SYSTEM
DAMPER WIDTH Percent of CFM/ START TO FULLY
BACK PRESSURE VELOCITY
Max. Flow Sq. Ft. OPEN OPEN
*Leakage information based on pressure differential of 1" w.g. tested per AMCA Std. 500.
0.3
7.62
0.2
5.08
0.1
2.54
.07
1.78
.05
1.27
.03
.75
.02
.51
.01
200 300 500 700 1000 2000 3000
60.96 91.44 152.40 213.36 304.80 609.60 914.40
Air velocity in FEET and Meters Per minute through face area
EXF 0
Calculation Sheet
External Static Pressure calculations
GENERAL DATA
DUCT MATERIAL: G. I. Sheet
AIR DENSITY:(Kg/m3) 1.2
Plenum Box 1 1
Flexible Duct 3 1
Transition 1 1
Tee Branch 2 1
Tee Main 2 1
Transition 1 1
Tee Main 2 2
Transition 1 1
Tee Main 1 2
Transition 1 1
Transition 3 1
TOTAL PA 7 3 5 6 0 0 0 0 0 0 21
DUCTS PD Pa 7 3 5 6 0 0 0 0 0 0 21
PRESSURE DROP Pa 9 4 6 7 0 0 0 0 0 0 26
`
DESIGNATION PD (PA) QTY TOTAL
Canvas 5 2 10 FLOW AT 100% (m3/hr) 1019
0
TOTAL 111
Drawing
Duct Fittings
Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023
INPUTS OUTPUTS
INPUTS OUTPUTS
FULLY EXTENDED
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
1. When used in fan discharge applications, damper should 3. Bracing of multiple section assemblies:
be located at least one-half the fan diameter away from the fan. The CBD6 is intended to be self supporting only in the largest
single section size. Multiple section damper assemblies
2. For proper operation, damper must be installed square and free may require bracing to support the weight of the assembly
from racking. and to hold against system pressure. Ruskin recommends
appropriate bracing to support the damper horizontally at
least once for every 8 feet of damper width. Vertical
assemblies and higher system pressures may require more
PERFORMANCE DATA bracing.
DAMPER PERFORMANCE
LEAKAGE* BLADES BLADES
MAXIMUM MAXIMUM SYSTEM
DAMPER WIDTH Percent of CFM/ START TO FULLY
BACK PRESSURE VELOCITY
Max. Flow Sq. Ft. OPEN OPEN
*Leakage information based on pressure differential of 1" w.g. tested per AMCA Std. 500.
0.3
7.62
0.2
5.08
0.1
2.54
.07
1.78
.05
1.27
.03
.75
.02
.51
.01
200 300 500 700 1000 2000 3000
60.96 91.44 152.40 213.36 304.80 609.60 914.40
Air velocity in FEET and Meters Per minute through face area
Air Louver
Chart 1
700
Static Pressure Drop (inches w.g.)
600
500
400
x 10-3
300
200
100
0
0 500 1000 1500 2000 2500
Example 1
Given air flow rate of 1500 cfm select a louver size
Dividing flow rate by free area velocity (let say 600 fpm )
Free area = 2.5 ft2 , from the table above , 34”X 22” will be the least louver satisfy the
desired free velocity
Check for pressure drop across the louver at 597 fpm from chart 1 = 0.06 Wg “
Example 2
Knowing louver size as 24”X28” determine the maximum flow rate
For velocity 800 fpm the flow rate = 2.28X 800 = 1824 cfm
Check for pressure drop across the louver at 800 fpm from chart 1 = 0.14 Wg “
Air Louver
GENERAL DATA
DUCT MATERIAL: G. I. Sheet
AIR DENSITY:(Kg/m3) 1.2
M3/H 850
LENGTH M 17.0
DIAM. mm 274
WIDTH mm 450
HEIGHT mm 150
AREA M2 0.059
PD x LENGTH Pa 13.52 14
PA (1-1') TOTAL
PRESSURE DROP Pa 50 50
TOTAL 34
Drawing
Duct Fittings
Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
PERFORMANCE DATA
Neck Velocity
300 400 500 600 700 800 1000 1200 1400 1600
Neck Neck (FPM)
Size Area Velocity Pressure 0.007 0.01 0.016 0.023 0.031 0.041 0.064 0.091 0.123 0.161
(inches) (FT²) (inches W.G)
Air flowrate(CFM) 60 80 100 120 135 155 195 235 275 315
6" 0.196 Total pressure drop 0.029 0.04 0.076 0.108 0.146 0.18 0.294 0.421 0.569 0.749
NC <20 <20 <20 <20 21 26 32 37 41 46
Air flowrate(CFM) 105 140 175 210 245 280 350 420 490 560
8" 0.349 Total pressure drop 0.020 0.03 0.053 0.077 0.100 0.123 0.207 0.293 0.394 0.519
NC <20 <20 <20 21 26 30 34 39 43 47
Air flowrate(CFM) 165 220 275 325 380 435 545 655 765 870
10" 0.545 Total pressure drop 0101 0.03 0.050 0.071 0.096 0.120 0.196 0.281 0.379 0.477
NC <20 <20 <20 22 27 31 36 41 45 48
Air flowrate(CFM) 225 315 395 470 550 630 785 940 1100 1255
12" 0.785 Total pressure drop 0.018 0.02 0.045 0.064 0.086 0.112 0.176 0.249 0.339 0.443
NC <20 <20 <20 23 29 33 37 42 46 49
Air flowrate(CFM) 320 430 535 640 750 855 1070 1285 1500 1710
14" 1.07 Total pressure drop 0.017 0.02 0.042 0.061 0.083 0.108 0.170 0.242 0.328 0.430
NC <20 <20 <20 25 30 34 38 43 47 50
Air flowrate(CFM) 420 560 700 840 980 1120 1400 1680 1960 2240
16" 1.40 Total pressure drop 0.016 0.02 0.041 0.059 0.079 0.103 0.162 0.231 0.314 0.411
NC <20 <20 21 26 31 35 39 44 48 51
Air flowrate(CFM) 530 710 885 1060 1240 1415 1770 2125 2480 2830
18" 1.77 Total pressure drop 0.015 0.02 0.040 0.057 0.077 0.099 0.156 0.224 0.303 0.397
NC <20 <20 22 27 32 36 40 45 49 52
Air flowrate(CFM) 660 850 1100 1300 1530 1750 2150 2650 3050 3500
20" 2.18 Total pressure drop 0.014 0.02 0.036 0.052 0.071 0.091 0.143 0.205 0.277 0.363
NC <20 <20 21 28 33 37 41 46 50 53
Air flowrate(CFM) 940 1250 1570 1850 2200 2500 3130 3850 4320 4950
24" 3.14 Total pressure drop 0.013 0.02 0.031 0.046 0.064 0.082 0.130 0.185 0.246 0.326
NC <20 <20 23 29 34 38 42 47 51 55
1. When used in fan discharge applications, damper should 3. Bracing of multiple section assemblies:
be located at least one-half the fan diameter away from the fan. The CBD6 is intended to be self supporting only in the largest
single section size. Multiple section damper assemblies
2. For proper operation, damper must be installed square and free may require bracing to support the weight of the assembly
from racking. and to hold against system pressure. Ruskin recommends
appropriate bracing to support the damper horizontally at
least once for every 8 feet of damper width. Vertical
assemblies and higher system pressures may require more
PERFORMANCE DATA bracing.
DAMPER PERFORMANCE
LEAKAGE* BLADES BLADES
MAXIMUM MAXIMUM SYSTEM
DAMPER WIDTH Percent of CFM/ START TO FULLY
BACK PRESSURE VELOCITY
Max. Flow Sq. Ft. OPEN OPEN
*Leakage information based on pressure differential of 1" w.g. tested per AMCA Std. 500.
0.3
7.62
0.2
5.08
0.1
2.54
.07
1.78
.05
1.27
.03
.75
.02
.51
.01
200 300 500 700 1000 2000 3000
60.96 91.44 152.40 213.36 304.80 609.60 914.40
Air velocity in FEET and Meters Per minute through face area
EXF 11
Calculation Sheet
External Static Pressure calculations
GENERAL DATA
DUCT MATERIAL: G. I. Sheet
AIR DENSITY:(Kg/m3) 1.2
DUCTS PD Pa 3 4 11 0 0 0 0 0 0 0 18
PRESSURE DROP Pa 6 6 17 0 0 0 0 0 0 0 28
Back Draft Damper 13 1 13 *TOTAL EXTERNAL STATIC PRESSURE + 10% SF (in) 0.64
TOTAL 117
Drawing
Duct Fittings
Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023
INPUTS OUTPUTS
INPUTS OUTPUTS
FULLY EXTENDED
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
1. When used in fan discharge applications, damper should 3. Bracing of multiple section assemblies:
be located at least one-half the fan diameter away from the fan. The CBD6 is intended to be self supporting only in the largest
single section size. Multiple section damper assemblies
2. For proper operation, damper must be installed square and free may require bracing to support the weight of the assembly
from racking. and to hold against system pressure. Ruskin recommends
appropriate bracing to support the damper horizontally at
least once for every 8 feet of damper width. Vertical
assemblies and higher system pressures may require more
PERFORMANCE DATA bracing.
DAMPER PERFORMANCE
LEAKAGE* BLADES BLADES
MAXIMUM MAXIMUM SYSTEM
DAMPER WIDTH Percent of CFM/ START TO FULLY
BACK PRESSURE VELOCITY
Max. Flow Sq. Ft. OPEN OPEN
*Leakage information based on pressure differential of 1" w.g. tested per AMCA Std. 500.
0.3
7.62
0.2
5.08
0.1
2.54
.07
1.78
.05
1.27
.03
.75
.02
.51
.01
200 300 500 700 1000 2000 3000
60.96 91.44 152.40 213.36 304.80 609.60 914.40
Air velocity in FEET and Meters Per minute through face area
EXF 1
Calculation Sheet
External Static Pressure calculations
GENERAL DATA
DUCT MATERIAL: G. I. Sheet
AIR DENSITY:(Kg/m3) 1.2
Tee Branch 4 1
Tee Branch 1 1
Transition 1 1
Tee Main 3 1
Tee Branch 4 1
Tee Main 3 1
Elbow 3 3
Transition 1 1
TOTAL PA 4 2 7 13 0 0 0 0 0 0 26
DUCTS PD Pa 4 2 7 13 0 0 0 0 0 0 26
PRESSURE DROP Pa 4 3 9 17 0 0 0 0 0 0 34
`
DESIGNATION PD (PA) QTY TOTAL
Canvas 5 1 5 FLOW AT 100% (m3/hr) 731
0
TOTAL 46
Drawing
Duct Fittings
Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
Return air
Where :
P the pressure drop in mm of water
NC based on room attenuation of 10dB
Fire Damper
Back Draft Damper
SUGGESTED SPECIFICATION
Furnish and install, at locations shown on plans or in accordance resistant, long life synthetic type for quiet operation. Linkage shall
with schedules, heavy duty backdraft dampers that meet the follow- be 1 /2 " (13) wide tiebar connected to stainless steel pivot
ing minimum construction standards: Frame shall be .125" (3.2) pins. Dampers shall be designed for maximum 3500 fpm spot
wall thickness 6063T5 extruded aluminum with 12 gage (2.8) gal- velocities and minimum 4 inches w.g. back pressure depending on
vanized steel structural brace at each corner. Blades shall be .070" damper size. Dampers shall be in all respects equivalent to
(1.8) wall thickness 6063T5 extruded aluminum with extruded vinyl Ruskin model CBD6.
blade edge seals mechanically locked into blade edge. Adhesive or
clip on type seals are unacceptable. Bearings shall be
corrosion
INSTALLATION
1. When used in fan discharge applications, damper should 3. Bracing of multiple section assemblies:
be located at least one-half the fan diameter away from the fan. The CBD6 is intended to be self supporting only in the largest
single section size. Multiple section damper assemblies
2. For proper operation, damper must be installed square and free may require bracing to support the weight of the assembly
from racking. and to hold against system pressure. Ruskin recommends
appropriate bracing to support the damper horizontally at
least once for every 8 feet of damper width. Vertical
assemblies and higher system pressures may require more
PERFORMANCE DATA bracing.
DAMPER PERFORMANCE
LEAKAGE* BLADES BLADES
MAXIMUM MAXIMUM SYSTEM
DAMPER WIDTH Percent of CFM/ START TO FULLY
BACK PRESSURE VELOCITY
Max. Flow Sq. Ft. OPEN OPEN
*Leakage information based on pressure differential of 1" w.g. tested per AMCA Std. 500.
0.3
7.62
0.2
5.08
0.1
2.54
.07
1.78
.05
1.27
.03
.75
.02
.51
.01
200 300 500 700 1000 2000 3000
60.96 91.44 152.40 213.36 304.80 609.60 914.40
Air velocity in FEET and Meters Per minute through face area
VOLUME DAMPER 01
VOLUME DAMPER 03
EXF 1
Calculation Sheet
External Static Pressure calculations
GENERAL DATA
DUCT MATERIAL: G. I. Sheet
AIR DENSITY:(Kg/m3) 1.2
Plenum Box 1 1
Flexible Duct 1 1
Transition 1 1
Tee Branch 1 1
Transition 1 1
Tee Main 1 1
Transition 1 1
Tee Main 1 1
Elbow 1 2
Transition 1 1
Tee Main 3 1
Elbow 2 1
Transition 1 1
Tee Main 1 1
Elbow 2 4
Transition 1 1
TOTAL PA 4 1 2 4 6 10 0 0 0 0 27
DUCTS PD Pa 4 1 2 4 6 10 0 0 0 0 27
PRESSURE DROP Pa 4 1 2 6 7 13 0 0 0 0 33
`
DESIGNATION PD (PA) QTY TOTAL
Canvas 5 1 5 FLOW AT 100% (m3/hr) 680
0
TOTAL 52
Drawing
Duct Fittings
Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023
INPUTS OUTPUTS
INPUTS OUTPUTS
FULLY EXTENDED
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
1. When used in fan discharge applications, damper should 3. Bracing of multiple section assemblies:
be located at least one-half the fan diameter away from the fan. The CBD6 is intended to be self supporting only in the largest
single section size. Multiple section damper assemblies
2. For proper operation, damper must be installed square and free may require bracing to support the weight of the assembly
from racking. and to hold against system pressure. Ruskin recommends
appropriate bracing to support the damper horizontally at
least once for every 8 feet of damper width. Vertical
assemblies and higher system pressures may require more
PERFORMANCE DATA bracing.
DAMPER PERFORMANCE
LEAKAGE* BLADES BLADES
MAXIMUM MAXIMUM SYSTEM
DAMPER WIDTH Percent of CFM/ START TO FULLY
BACK PRESSURE VELOCITY
Max. Flow Sq. Ft. OPEN OPEN
*Leakage information based on pressure differential of 1" w.g. tested per AMCA Std. 500.
0.3
7.62
0.2
5.08
0.1
2.54
.07
1.78
.05
1.27
.03
.75
.02
.51
.01
200 300 500 700 1000 2000 3000
60.96 91.44 152.40 213.36 304.80 609.60 914.40
Air velocity in FEET and Meters Per minute through face area
EXF 1
Calculation Sheet
External Static Pressure calculations
GENERAL DATA
DUCT MATERIAL: G. I. Sheet
AIR DENSITY:(Kg/m3) 1.2
DUCTS PD Pa 6 4 8 0 0 0 0 0 0 0 18
PRESSURE DROP Pa 7 13 13 0 0 0 0 0 0 0 32
TOTAL 89
Drawing
Duct Fittings
Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Monday, January 23, 2023
INPUTS OUTPUTS
INPUTS OUTPUTS
FULLY EXTENDED
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
1. When used in fan discharge applications, damper should 3. Bracing of multiple section assemblies:
be located at least one-half the fan diameter away from the fan. The CBD6 is intended to be self supporting only in the largest
single section size. Multiple section damper assemblies
2. For proper operation, damper must be installed square and free may require bracing to support the weight of the assembly
from racking. and to hold against system pressure. Ruskin recommends
appropriate bracing to support the damper horizontally at
least once for every 8 feet of damper width. Vertical
assemblies and higher system pressures may require more
PERFORMANCE DATA bracing.
DAMPER PERFORMANCE
LEAKAGE* BLADES BLADES
MAXIMUM MAXIMUM SYSTEM
DAMPER WIDTH Percent of CFM/ START TO FULLY
BACK PRESSURE VELOCITY
Max. Flow Sq. Ft. OPEN OPEN
*Leakage information based on pressure differential of 1" w.g. tested per AMCA Std. 500.
0.3
7.62
0.2
5.08
0.1
2.54
.07
1.78
.05
1.27
.03
.75
.02
.51
.01
200 300 500 700 1000 2000 3000
60.96 91.44 152.40 213.36 304.80 609.60 914.40
Air velocity in FEET and Meters Per minute through face area
FAF 01
Calculation Sheet
External Static Pressure calculations
GENERAL DATA
DUCT MATERIAL: G. I. Sheet
AIR DENSITY:(Kg/m3) 1.2
ELBOW 90 (1) 6 3
TEE MAIN (2) 1 1
TEE MAIN (3) 1 1
TEE MAIN (4) 1 1
TEE MAIN (5) 1 1
ELBOW 90 (5) 36 2
TEE MAIN (6) 1 1
TEE MAIN (7) 1 1
RECT. TO ROUND (7) 1 1
ROUND TO RECT. (7) 4 1
ELBOW 90 (7) 14 1
TRANSITION (7) 21 1
TOTAL PA 18 1 1 1 73 1 41 136
DUCTS PD Pa 18 1 1 1 73 1 41 136
TOTAL 70
Drawing
Duct Fittings
Tel: ASHRAE DUCT FITTING DATABASE
Fax: Version # 6. 00.04 Sunday, January 22, 2023
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
Chart 1
700
Static Pressure Drop (inches w.g.)
600
500
400
x 10-3
300
200
100
0
0 500 1000 1500 2000 2500
Example 1
Given air flow rate of 1500 cfm select a louver size
Dividing flow rate by free area velocity (let say 600 fpm )
Free area = 2.5 ft2 , from the table above , 34”X 22” will be the least louver satisfy the
desired free velocity
Check for pressure drop across the louver at 597 fpm from chart 1 = 0.06 Wg “
Example 2
Knowing louver size as 24”X28” determine the maximum flow rate
For velocity 800 fpm the flow rate = 2.28X 800 = 1824 cfm
Check for pressure drop across the louver at 800 fpm from chart 1 = 0.14 Wg “
Air Louver