TC806B1076(CDN),

TC806B1084,
TC806DNR(CDN)
Intelligent Plug-In Photoelectric

2151_2251B_CEILING.png
Smoke Detectors with FlashScan
General
Honeywell intelligent plug-in smoke detectors with integral
communication provide features that surpass conventional
detectors. Detector sensitivity can be programmed in the con-
trol panel software. Sensitivity is continuously monitored and TC806B1076(CDN) in B210LP(A) Base
reported to the panel. Point ID capability allows each detec-
tor’s address to be set with rotary, decimal address switches,
providing exact detector location for selective maintenance
when chamber contamination reaches an unacceptable level.
The TC806B1076(CDN) photoelectric detector’s unique opti-
cal sensing chamber is engineered to sense smoke produced
by a wide range of combustion sources. Dual electronic therm- Specifications
istors add 135°F (57°C) fixed-temperature thermal sensing on Sensitivity: 0.5% to 2.35% per foot obscuration
the TC806B1084. The TC806BDNR(CDN) is a remote test
Size: 2.1" (5.3 cm) high; base determines diameter.
capable detector for use with DNR(A)/DNRW duct detector
housings. These detectors are compatible with Honeywell – B210LP(A): 6.1" (15.5 cm) diameter.
XLS series Fire Alarm Control Panels (FACPs) in CLIP or – B501(A): 4.1" (10.4 cm) diameter.
FlashScan® mode. – B200S(A): 6.875" (17.46 cm) diameter.
FlashScan® (U.S. Patent 5,539,389) is a communication pro- – B200SR(A): 6.875" (17.46 cm) diameter.
tocol that greatly increases the speed of communication
– B224RB(A): 6.2" (15.748 cm) diameter.
between analog intelligent devices. Intelligent devices commu-
nicate in a grouped fashion. If one of the devices in the group – B224BI(A): 6.2" (15.748 cm) diameter.
has new information, the panel’s CPU stops the group poll and Shipping Weight: 5.2oz. (147g).
concentrates on single points. The net effect is response Operating Temperature range: TC806B1076(CDN), 0°C to
speed greater than five times that of earlier designs. 49°C (32°F to 120°F). TC806B1084, 0°C to 38°C (32°F to
100°F). Low temperature signal for TC806B1084 at 45°F +/-
Features 10°F (7.22°C +/- 5.54°C). TC806BDNR(CDN)t installed in a
• Sleek, low-profile design. DNR(A)/DNRW, -20°C to 70°C (-4°F to 158°F).
• Addressable-analog communication. UL/ULC Listed Velocity Range: 0-4000 ft/min. (1219.2 m/
min.), suitable for installation in ducts.
• Stable communication technique with noise immunity.
• Low standby current. Relative Humidity: 10%-93% noncondensing.
• Two-wire SLC connection. Thermal Ratings: Fixed-temperature setpoint 135°F (57°C).
• Compatible with FlashScan® and CLIP protocol systems. DETECTOR SPACING AND APPLICATIONS
(XLS140-2, XLS120, XLS3000, XLS1000, and FS90 Plus)
Honeywell recommends spacing detectors in compliance with
• Rotary, decimal addressing (1-99 on CLIP systems, 1-159 NFPA 72. In low airflow applications with smooth ceiling, space
on FlashScan systems). detectors 30 feet (9.144m) for ceiling heights 10 feet (3.148m)
• Optional remote, single-gang LED accessory. and higher. For specific information regarding detector spac-
• Dual LED design provides 360° viewing angle. ing, placement, and special applications refer to NFPA 72.
• Visible bi-color LEDs blink green every time the detector is System Smoke Detector Application Guide, document A05-
addressed, and illuminate steady red on alarm (FlashScan 1003, is available at systemsensor.com
systems only). ELECTRICAL SPECIFICATIONS
• Remote test feature from the panel. Voltage Range: 15-32 volts DC peak.
• Walk test with address display (an address on 121 will blink
Standby Current (max. avg.): 300µA @ 24VDC (one com-
the detector LED: 12-[pause]-1(FlashScan systems only).
munication every five seconds with LED enabled).
• Built-in functional test switch activated by external magnet.
LED Current (max.): 6.5mA @ 24 VDC (“ON”).
• Built-in tamper-resistant feature.
• Sealed against back pressure.
Installation
• Constructed of off-white fire-resistant plastic, designed to
commercial standards, and offers an attractive appearance. TC806B1076(CDN) plug-in detectors use a separate base to
simplify installation, service, and maintenance. A special tool
• 94-5V plastic flammability rating. allows maintenance personnel to plug in and remove detectors
• SEMS screws for wiring of the separate base. without using a ladder.
• Optional relay, isolator, and sounder bases. Mount base (all base types) on an electrical backbox which is
at least 1.5" (3.81 cm) deep. For a chart of compatible junction
boxes, see 85-3043.
NOTE: 1) Because of inherent supervision provided by the SLC B200S(A): Intelligent, programmable sounder base capable of
loop, end-of-line resistors are not required. Wiring “T-taps” or producing sound output in high or low volume with ANSI Tem-
branches are permitted for Style 4 (Class “B”) wiring. 2) When poral 3, ANSI Temporal 4, continuous tone, marching tone,
using relay or sounder bases, consult the TC811A1006(CDN) and custom tone.
installation sheet I56-1385 for device limitations between isolator
modules and isolator bases. B200SR(A): Intelligent sounder base capable of producing
sound output with ANSI Temporal 3 or continuous tone.
Replaces B501BH series bases in retrofit applications.
Agency Listings and Approvals
B224RB(A): Plug-in System Sensor relay base. Screw termi-
These listings and approvals apply to the modules specified in
nals: up to 14 AWG (2.0 mm²). Relay type: Form-C. Rating: 2.0
this document. In some cases, certain modules or applications
A @ 30 VDC resistive; 0.3 A @ 110 VDC inductive; 1.0 A @
may not be listed by certain approval agencies, or listing may
30 VDC inductive.
be in process. Consult factory for latest listing status.
B224BI(A): Plug-in System Sensor isolator detector base.
• UL Listed: S1196.
Maximum 25 devices between isolator bases. Replaces
• ULC Listed: S6959 (TC806B1076CDN, TC806DNRCDN). 14507371-005(CDN).
• MEA Listed: 214-02-E.
ACCESSORIES
• FM Approved.
F110: Retrofit flange to convert B210LP(A) to match the
• CSFM: 7272-1130:0144.
14507371-001(CDN) profile, or to convert older high-profile
bases to low-profile.
Product Line Information
F110BP: Bulk pack of F110; package contains 15.
NOTE: “A” or CDN suffix indicates ULC Listed model.
F210: Replacement flange for B210LP(A) base.
TC806B1076: Low-profile intelligent photoelectric sensor.
Must be mounted to one of the bases listed below. RA100Z(A): Remote LED annunciator. 3 – 32 VDC. Mounts to
a U.S. single-gang electrical box. For use with B501(A) and
TC806B1076CDN: Same as TC806B1076 but with ULC list- B210LP(A) bases only.
ing.
SMB600: Surface mounting kit
TC806B1084: Same as TC806B1076 but includes a built-in
135°F (57°C) fixed-temperature thermal device. M02-04-00: Test magnet.

TC806DNR: Low-profile intelligent photoelectric sensor, M02-09-00: Test magnet with telescoping handle.
remote test capable. For use with DNRA/DNRW. XR2B: Detector removal tool. Allows installation and/or
TC806DNRCDN: Same as TC806DNR but with ULC listing. removal of detector heads from bases in high ceiling applica-
For use with DNRA. tions.
XP-4: Extension pole for XR2B. Comes in three 5-foot (1.524
INTELLIGENT BASES m) sections.
NOTE: “A” or CDN suffix indicates ULC Listed model.
T55-127-010: Detector removal tool without pole.
NOTE: For details on intelligent bases, see 85-3043.
BCK-200B: Black detector covers for use with
B210LP(A): Standard U.S. flanged low-profile mounting base. TC806B1076(CDN) only; box of 10.
B210LPBP: Bulk pack of B210LP; package contains 10. WCK-200B: White detector covers for use with
B501(A): Standard European flangeless mounting base. TC806B1076(CDN) only; box of 10.
B501BP: Bulk pack of B501; package contains 10.

This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific
applications or anticipate all requirements. All specifications are subject to change without notice.
XLS-NET™ is a trademark of Honeywell International Inc.
©2015 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.

Automation and Control Solutions


Honeywell International Inc. Honeywell Limited-Honeywell Limitée
1985 Douglas Drive North 35 Dynamic Drive
Golden Valley, MN 55422 Scarborough, Ontario M1V 4Z9
www.honeywell.com 74-1941-6 Rev. 02-15
February 2015
® U.S. Registered Trademark
© 2015 Honeywell International Inc.
Page 2 of 2

You might also like