Operating Instructions
Operating Instructions
Operating Instructions
Operating Instructions
Printed January 2024
Book No. ESMO-MAN-0103-03 v0
Alfa Laval reserves the right to make changes at any time without
prior notice.
Any comments regarding possible errors and omissions or
suggestions for improvement of this publication would be
gratefully appreciated.
Copies of this publication can be ordered from your local
Alfa Laval company.
Published by: Alfa Laval S.p.A.
Marine & Diesel Equipment
Engineering & Supply Monza
20900 – Monza MB
Italy
The original instructions are in English
1 Control Panel
The operator panel is composed by a set of switches,
pushbuttons and a touchscreen HMI.
4
OPERATING INSTRUCTIONS PUMP SKID
5
PUMP SKID OPERATING INSTRUCTIONS
6
OPERATING INSTRUCTIONS PUMP SKID
NOTE
NOTE
7
PUMP SKID OPERATING INSTRUCTIONS
NOTE
8
OPERATING INSTRUCTIONS PUMP SKID
9
PUMP SKID OPERATING INSTRUCTIONS
10
OPERATING INSTRUCTIONS PUMP SKID
Unacknowledged alarms
If there is at least an unacknowledged alarm the
Alarm symbol is blinking (red and white) and the
related active alarm is marked in RED colour.
Acknowledged alarms
To acknowledge an alarm select it tapping on
alarm line and then tap the Acknowledge button.
12
OPERATING INSTRUCTIONS PUMP SKID
2 Normal Operation
2.1 Before start
The following procedures assumes that the system
pipework and the valves arrangement is set for
operation (valves open and pipework secured).
Moreover, it is assumed that the commissioning
actions described in the Installation System Reference
booklet have been successfully performed.
Make sure that the pumps are filled with oil before start,
otherwise the pumps shaft seal will be damaged. For
pumps startup recommendations, see Installation
System Reference booklet.
NOTE
Make sure that all pipelines have been flushed before
start, otherwise all main components will be damaged.
For first startup procedure, see Installation System
Reference booklet.
2.3 Start
Select the running pump with the selector switch (if installed)
and start the pump by pressing the START button.
2.4 Stop
Stop the running pump by pressing the STOP button.
By stopping the system as described below, no
alarms will be activated.
13
PUMP SKID OPERATING INSTRUCTIONS
NOTE
The pump changeover in case of low pressure
alarm is not automatic. The system is designed
to start automatically the second pump (if installed)
only when the selector switch “pump priority” is
operated while any pump is running.
NOTE
Since the pumps shaft seal has to be lubricated, a small
amount of oil will drop from the pump. About 10 drops
per hours is considered normal.
NOTE
It is always possible to stop the system by mean of
the STOP pushbutton on the local control panel,
regardless the system is in LOCAL or REMOTE mode.
14
OPERATING INSTRUCTIONS PUMP SKID
15